Pressure Switch Calibration Procedure PresSwH100R
Pressure Switch Calibration Procedure PresSwH100R
PRESSURE SWITCH
Make UE
Model H100
Type
Set Point 1.0 Bar
Note: The up arrow “” indicates that the switch contact will change at 1.0 Bar increasing pressure.
PRE-REQUISITES
Digital Multi-meter with Continuity Test (with audible sound)
Connecting Leads
Pressure Source (Deadweight Oil Tester/DRUCK DPI 601/COMBITEST or
Any other)
PRECAUTIONS
CONNECTION
Connect the C (Common) and NO (Normally Open) with Multimeter’s Continuity Test Port
as above diagram
Connect Pressure source (Deadweight) with switch’s pressure input port with proper
fittings.
REPEATABILITY CHECK
The calibration of the switch should be tested minimum 3 times to ensure repeatability.