s Fire Safety Products

Sinorix Engineered Fire Suppression Systems


Pressure-Operated Switch
Model CPY- POS
ARCHITECT AND ENGINEER SPECIFICATIONS
Only operable via pressure from Sinorix-agent discharge
Used for sending a signal to a fire-alarm control panel
(FACP) when the agent is manually released
Can perform shutdown / interlock functions directly
Connected anywhere in discharge piping
UL Listed & ULC Listed;
FM and CSFM Approved

Product Overview
Used in conjunction with Sinorix Engineered Fire As an option, the Pressure-Operated Switch may be
Suppression systems, the Pressure-Operated connected to the port marked ‘M’ on the Sinorix
Switch (Model CPY-POS) from Siemens is of single- cylinder valve. The maximum length of connecting
pole, double-throw (SPDT) type, and is activated by tubing or pipe shall either be:
the Sinorix pressure agent in the system-discharge 50 feet (1,524 cm.) for the 1" (2.54 cm.) or
piping at the time of agent emission. 1-1/2" (3.81 cm.) valve
Model CPY-POS is used to signal the FACP when 30 feet (914 cm.) for the 2-1/2" (6.4 cm.)
agent discharge occurs. In turn, the panel will or 4” valve (10.2 cm.)
perform its assigned shutdown / interlock Specifications
functions in the event of manual mechanical
A pressure-operated switch shall be provided to
release of the system.
operate upon actual discharge of Sinorix agent
The pressure-operated switch if desired can into the system piping. Siemens Model CPY-POS
also be used to perform shutdown / interlock shall be connected to the FACP, in order to perform
functions directly. Actuating pressure is obtained its assigned shutdown / interlock functions in the
from the outlet of a tee slave located anywhere in event of manual mechanical release of clean agent
the discharge piping. Connection from the tee in the Sinorix system.
slave to the pressure switch can be made, via:
Details for Ordering
¼-inch (0.64 cm.) O.D. copper tubing
Part Shipping Weight
1/8 (0.64 cm.) or ¼-inch (0.64 cm.) Model Description
Number Lbs. Kg.
schedule, 40-pipe and 300-pound-class
Pressure-
(136.078 kg.) malleable iron or ductile- CPY-POS 500-697941BG Operated Switch 2 0.9
iron fittings

[Pressure-Operated Switch] Sinorix® 6626


s Industry, Inc.
Building Technologies Division
Mounting Diagram

(Shown In Inches)

Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.

Fire Safety Fire Safety


8 Fernwood Road 1577 North Service Road
s Industry, Inc. Florham Park, NJ 07932 East Oakville, Ontario June 2014
Building Technologies Division Tel: (973) 593-2600 (SII-FS) L6H 0H6 / Canada Supersedes sheet dated 6/11
FAX: (908) 547-6877 Printed in U.S.A. Tel: [905] 465-8000 (Rev. 5)

URL: www.USA.Siemens.com/ Fire URL: www.Siemens.C A

You might also like