You are on page 1of 11

Guide to Overvoltage Categories &

Measurement Categories
A GAMBICA Technical Guide
1 Overvoltage Category

Overvoltage categories are defined control the mains supply within the
by a Roman numeral according building, and similar equipment.
to the potential for transient All such equipment is permanently
overvoltage to occur. Overvoltage connected to the mains and is
categories are created to determine permanently installed in the building.
the required insulation strength of However, equipment that utilizes the
the components and equipment mains supply only for powering itself
used within the low-voltage mains and associated equipment is not
supply system. considered to be part of the building
installation, even if it is permanently
Equipment forming part of the connected or permanently installed
building installation will include in the building.
insulation material, equipment
intended to protect, measure or

Overvoltage categories are Overvoltage Category I Overvoltage Category IV


defined in IEC 60364 as follows: is used for equipment intended to is for equipment installed at or
be connected to a mains supply in near the origin of the electrical
which means have been taken to supply to a building, between
substantially and reliably reduce the building entrance and
transient overvoltages to a level the main distribution board.
where they cannot cause a hazard. Such equipment may include
electricity tariff meters and
Overvoltage Category II primary overcurrent protection
is for equipment intended to be devices. Manufacturers may
supplied from the building wiring. also design equipment for
It applies both to plug-connected Overvoltage Category IV when an
equipment and to permanently even higher degree of reliability
connected equipment. and availability is desired.

Overvoltage Category III


is for equipment intended to
form part of a building wiring
installation. Such equipment
includes socket outlets,
distribution boards, and some
mains installation control
equipment. Manufacturers
may also design equipment for
overvoltage category III when
a higher degree of reliability
and availability is desired.

1
2 Measurement Category

Measurement category is a means overvoltage categories, short-


of classifying the terminals of test circuit current levels, the location
and measurement equipment in the building installation where
according to the type of mains the test or measurement is to be
circuit to which they are intended made, and some forms of energy
to be connected. Measurement limitation or transient protection
categories take into account included in the building installation.

Measurement categories are Measurement category II Examples include measurements


defined in IEC 61010-2-x and are is applicable to test and measuring on distribution boards (including
summarized here: circuits connected directly to secondary meters), photovoltaic
utilization points (socket outlets panels, circuit-breakers, cables,
and similar points but excluding bus-bars, junction boxes, lighting,
installed lighting) of the low-voltage switches, wiring to socket-outlets,
mains installation. Examples include equipment for industrial use and
measurements on mains circuits some other equipment (such as
of household appliances, portable stationary motors) with permanent
tools and similar equipment, and on connection to the fixed installation.
the consumer side only of socket-
outlets in the fixed installation. Measurement category IV
Short circuit currents are typically is applicable to test and measuring
below 10kA, depending on the circuits connected between the
characteristics of the installation. source of the building’s low-
voltage supply and the first
Measurement category III accessible isolator switch able
is applicable to test and measuring to disconnect all line and neutral
circuits connected between connections. The high potential
Measurement category II and short-circuit currents, typically
Measurement category IV of the greater than 50kA, depending
building’s low-voltage mains on the characteristics of the
installation. To avoid risks caused installation, existing in these circuits
by the hazards arising from higher can create an extremely dangerous,
short-circuit currents, typically high energy arc flash through any
up to 50kA, depending on the accidental short-circuit caused
characteristics of the installation, whilst making measurements.
additional insulation and other Precautions must be taken to avoid
provisions are required. For any chance of a short-circuit.
equipment that is part of a fixed Examples include measurements
installation, the fuse or circuit on the unisolated conductors
breaker of the installation must at the isolator switch, the tariff
provide adequate protection meter, service fuse and low voltage
against short-circuit currents. devices installed in the sub-station.

2
3 Measuring Circuits
Without a Measurement
Category Rating

Many types of test and measuring transient overvoltages in these


circuits, although not intended to circuits is necessary to determine
be directly connected to the mains, the insulation requirements and
may have very high amounts of short-circuit current requirements.
available energy from high short- Examples include thermocouple
circuit currents or high open-circuit measuring circuits, high-frequency
voltages. There are no standard measuring circuits, automotive
transient levels defined for these testers, and testers used to prove
circuits. An analysis of the working the mains installation before it is
voltages, loop impedances, connected to the mains supply.
temporary overvoltages, and

3
4 Test Instrument Selection

It is important that an instrument marked with the value of the rated


with an appropriate measurement voltage to earth and the applicable
category is used when making measurement category, often
measurements on mains circuits. abbreviated to “CAT.” Measurement
Figure 1 (page 9) shows the terminals can be safely connected
measurement categories specified to a measurement category lower
for various parts of an installation. than the marking on the terminals.
The measurement terminals must
The safety standard for test and never be connected to a circuit
measurement equipment, BS that exceeds the rated voltage or
EN61010, requires that terminals are measurement category.

CAT IV 300 V

> 550 V
L1 L2 L3

MFT L PE N

This typical multifunction tester The triangle refers the operator


terminal panel is rated for CAT IV to the user instructions where more
300 V measurement connection. detailed information on the ratings
Measurement connection to CAT may be given, along with other
IV, CAT III or CAT II circuits may be hazards, such as unmated terminals
made provided voltage does not becoming live from high voltage
exceed 300 V with respect to earth. within the instrument.
Measurement connection not
exceeding 550 V between phases
may be made provided no voltage
exceeds 300 V with respect to earth.

4
MAX
10 A
500 V

DMM VΩ COM A

This typical multimeter terminal The triangle refers the


panel is rated for measurement operator to the instruction
connection up to 500 V with manual for more information.
respect to earth.
Instruments and test leads
There is no CAT rating, so this with no CAT rating must have
instrument must not be connected a warning in the instructions
to the mains even though the not to connect to the mains
rated voltage is greater than the supply - but some manufacturers
nominal domestic supply voltage. overlook this requirement.

MAX
CAT III 250 V
fused
10 A

DMM VΩ COM A

This multimeter is rated for mains This instrument must not be


measurement connection up to connected to voltage higher
CAT III 250 V with respect to earth than 250 V across phases.
and 250 V between terminals.
Measurement connection
Measurement connection to to CAT IV circuits must NOT
CAT III or CAT II circuits may be made at any voltage.
be made provided voltage does
not exceed 250 V with respect
to earth and does not exceed
250 V between terminals.

5
MAX
MAX
CAT
CAT III III 450 V 1010
A A
250 V 450 V fused
250 V fused

DMM VΩ COM A

DMM VΩ COM A

This multimeter is rated for mains to earth and does not exceed
measurement connection up to 450 V between terminals.
CAT III 250 V with respect to earth This instrument must not be
and 450 V between terminals. connected to voltage higher
than 450 V between phases.
Measurement connection to
CAT III or CAT II circuits may be Measurement connection
made provided voltage does to CAT IV circuits must NOT
not exceed 250 V with respect be made at any voltage.

MAX
10 A
CAT III fused

250 V

DMM VΩ COM A

This multimeter is rated for mains Measurement connection


measurement connection up to to CAT IV circuits must NOT
CAT III 250 V with respect to earth. be made at any voltage.

Measurement connection to CAT Note that one cannot ‘trade-off’


III or CAT II circuits may be made CAT rating and voltage: connecting
provided voltage does not exceed to a CAT circuit higher than the
250 V with respect to earth. instrument rating but with half the
It cannot be taken for granted that instrument’s voltage rating, or vice-
this instrument may be connected to versa: connecting to a voltage higher
voltage higher than 250 V between than the instrument is rated but at
phases. Often there is insufficient a lower measurement category.
space for all ratings to be marked.
Dual-rated instruments permit this
The triangle refers the ‘trade-off’ but, unless it is specified
operator to the instruction on the instrument or the user
manual for more information instructions, it is unsafe to do so.

6
MAX
CAT IV 300 V
CAT III 600 V fused
10 A

DMM VΩ COM A

This multimeter is dual rated for place all rating information.


mains measurement connection The triangle refers the operator
up to CAT IV 300 V with respect to the user instructions.
to earth, and to CAT III 600 V
with respect to earth. Measurement connection to
CAT IV circuits may be made
Measurement connection to CAT provided voltage does not exceed
III or CAT II circuits may be made 300 V with respect to earth.
provided voltage does not exceed
600 V with respect to earth. It must not be taken for granted
It must not be taken for granted that this instrument is safe to
that this instrument is safe to connect to a CAT IV voltage higher
connect to a CAT III voltage than 300 V between phases. The
higher than 600 V between triangle refers the operator to
phases. There is often insufficient the user instructions where more
space on an instrument to detailed safety information is given.

7
CAT II 1,000V
CAT III 1,000V CAT III 1,000V
CAT IV 600V CAT IV 600V

2PV CAT II
1,000 V
CAT III 1,000V
CAT IV 600V

This two-pole voltage detector is and the exposed tip is safe to use
rated for measurement connection only in protected, lower energy CAT
to CAT II 1,000 V, or CAT III 1,000 V II circuits as marked. It is important
and CAT IV 600 V. to note that if the exposed tip
is a 4 mm unshrouded ‘banana’
This is achieved with detachable plug, it must not be used to attach
insulators on the probes. When crocodile clips or other probes.
the insulators are in place only
a small length of each tip is The probes are designed so that the
exposed and the risk of one of higher marked rating is removed
them accidentally short-circuiting with the insulator and reveals the
between conductors is much lower rated marking. This feature is
reduced. The insulated tip is safe seen on multiple rated test probes
to use in higher energy CAT III as well. There is often insufficient
and CAT IV circuits as marked. space at the measurement
terminals so the key ratings are
When the insulators are removed marked on the instrument body and
the tips are longer than permitted the triangle refers to operator to
for safe high energy connections. the user instructions.
The risk of short-circuit is higher

8
4 Location of Measurement
Categories
CAT Ratings Match your test equipment safety
BS EN61010-1 Installation Categories rating to the installation category.
(CAT ratings) define the risks from
hazardous transient impulses and CAT II socket outlets and
potentially lethal short circuit similar points of the
currents on the mains supply system mains installation.
based on where you are working. CAT III the distribution part of the
building’s mains installation.
Voltage Ratings CAT IV the supply side source of the
Test equipment used for measuring building’s mains installation.
mains circuits will have a CAT rating
to show where it can be used. Each Testers, leads and accessories
category also has a voltage rating to all need safety ratings equivalent
show the maximum safe phase to to, or higher than the installation
earth system voltage, normally 50V, category and voltage rating
100V, 150V, 300V, 600V or 1000V. for the location to be safe.

Figure 1 Location of
Measurement Categories
*The main isolator switch may be installed by
the service provider. If not, the demarcation
point between CAT IV and CAT III is the first
isolating switch in the distribution board.

PV PV
array array

Lighting Electrical
appliances

888
*Main isolator Generation
switch meter

L1 (L2, L3)
Low-voltage
supply source 888 Circuit
breakers
N

Distribution
Plug-in lamps
Over or board
Service
under fuse
ground
Socket wiring Socket outlets

CAT IV CAT III CAT II

Footnote: In some installations the main isolator switch may be the device provided
by the DNO. Where this is not the case it will be on the distribution board.

9
The GAMBICA Association Ltd
Rotherwick House,
3 Thomas More Street,
London E1W 1YZ
T + 44 (0) 20 7642 8080
E info@gambica.org.uk
W gambica.org.uk Version 1.1

You might also like