You are on page 1of 4

Application Paper AP020006EN Effective September 2020

Benefits of contactors vs. breakers for


medium-voltage motor control applications
Reduced footprint, clearances,
and front accessibility
Presently used MV MCCs, measure about
36 inches wide by 30 inches deep and only
require a front clearance of 36 inches. They are
front accessible and commonly available in a
single-high 800 A or a two-high 400 A starter
configuration, which can be installed against a
wall, back to back, or in a corner.
MV switchgear on the other hand, requires rear
access, is 96 inches deep, and has clearance
requirements of 70 inches at the front, 32 inches
on the side, and 36 inches at the rear. This
Introduction increased footprint and additional access
requirements can become costly, particularly
With both power circuit breakers and contactors
when the equipment is installed in locations
able to start and stop a motor, how do you decide
such as prefabricated electrical houses where
which option makes the most sense?
the cost per square foot is very significant.
The availability of fully rated 800 A contactors has
For example, a typical MV MCC lineup with
been a great advantage for medium-voltage (MV)
ten 400 A starters will measure 180 inches in
motor control. With contactors available at this
width and would require about 83 square feet
higher amperage, there is a reason to assess the
of floor space, including front clearances. Using
typical approach for motor control and understand
circuit breakers in MV switchgear for the same
what are the advantages a contactor provides over
application would more than triple the overall
a circuit breaker.
required footprint and clearances to 253 square
Full-voltage starters are the most commonly used feet. This increase in footprint, clearances, and
method of MV motor control. Also known as overall cost is not necessary especially for
across-the-line starters, this equipment applies motors below 6000 horsepower (hp), which can
line voltage to the motor in a single action via be controlled by a fully rated 800 A contactor-
contactors rated to connect and disconnect motor based starter.
in-rush currents. An assembly of motor controllers
under a common bus is often called a motor Lower chopping current means there’s less
control center (MCC). chance for adverse impact on your motor
On the other hand, an MV circuit breaker is a When a vacuum interrupter opens, the level of
power distribution protection equipment designed current produced by the arcing between the
to interrupt high levels of short-circuit current. interrupter’s contacts almost instantly falls to
These devices are commonly found installed in zero instead of following a nominal current zero
assemblies called switchgear. decrease of the fundamental 60 Hz waveform.
This application paper will discuss common This sudden interruption in current is defined as
application considerations when choosing a motor current chop and depending on its magnitude
starting method including: size of equipment, and frequency, it can cause serious insulation
endurance, impact on other equipment, and safety. degradation over the lifetime of a motor.
Here is the upshot—the contactor-based motor By design, vacuum interrupters in contactors have
starter solution comes out substantially ahead in a lower interrupting rating and are constructed to
each of these parameters. The following pages operate more frequently than the ones used in
will describe the benefits of using contactors for breakers. Vacuum interrupters in contactors are
motor starting applications. manufactured using different metallurgy, which
allows them to exhibit a lower chop current (about
1 A) than the chop current produced by a breaker
interrupter (about 5 A). See Figure 1.
Application Paper AP020006EN Benefits of contactors vs. breakers for
Effective September 2020 medium-voltage motor control applications

Depending on the characteristic impedance of the electrical system, systems and will not compel design engineers to use surge
the transient voltage created by the chopping current could be arresters. Vacuum interrupters in circuit breakers, on the other hand,
detrimental to equipment insulation. Figure 2 presents the transient have a 5 A current chop, increasing the voltage transient to levels
voltage created by a 1 A and 5 A chopping current in a simulated above four times the system voltage. These higher levels of transient
circuit with a characteristic impedance of 3000 ohms. As shown, the voltages often require the use of surge arresters as a mitigator to
1 per unit overvoltage condition created by the 1 A current chop of protect insulation systems.
a vacuum contactor is well within the rating of most MV insulation

Figure 1. 1 A and 5 A chopping current waveforms

Figure 2. 1 A and 5 A voltage transient waveform (Z0 = 3000 ohms)

2 EATON www.eaton.com
Benefits of contactors vs. breakers for  Application Paper AP020006EN
medium-voltage motor control applications Effective September 2020

Higher mechanical and electrical endurance Enhanced safety: faster clearing times
Motor starters using contactors have extended mechanical and and lower let-through currents
electrical life when compared to breakers used in the same Breaker-based motor controller short-circuit protection is usually
application. The impact here is substantial. For motor starting provided by the instantaneous overcurrent setting of the motor
applications, contactors can require little, if any, maintenance for protection relay. Although this type of protection operates with no
decades. In contrast, breaker-based solutions for motor starting intentional time delay, it is important to note that inherit delays exist
could require repeated maintenance beginning within a year of due to relay and breaker operations or total clearing time.
operation.
To obtain the relay operating time, the protection engineer must
As seen in Table 1, vacuum breakers have a mechanical endurance account for the relay’s output contact and instantaneous protection
of 10,000 operations with a manufacturer recommended operating time. Relays typically have an 8 msec contact operation
maintenance period of 500 operations. Vacuum contactors are time with a 30 msec maximum pickup time. This means the relay’s
commonly rated for 25,000 electrical operations before maintenance total operating time is about 38 msec or about 2¼ cycles. Once the
is recommended and a total electrical life up to 300,000 operations. relay picks up and closes its output contact to trip the breaker, it
will take an additional 50 to 83 msec (3 to 5 cycles) in order to fully
Table 1.  Vacuum breaker and contactor rated operations
open its contacts and clear the fault. Adding both the relay’s and the
and maintenance
breaker’s operating times, the total clearing time is 88–121 msec
Recommended (5–7 cycles).
Rated electrical maintenance
Device operations operations
Class E2 motor controllers use a main contactor to make and break
Vacuum breaker 10,000 500 load and overload currents, in addition to MV current-limiting fuses
400 A vacuum contactor 300,000 25,000 for interrupting fault currents that exceed the breaking capacity of
800 A vacuum contactor 200,000 25,000 the main contactor.
Most 400 A MV contactors have interrupting ratings between
6000 A and 8500 A; and 800 A MV contactors have interrupting
ratings of 7200 A to 12,500 A. In order to obtain higher interrupting
Breakers are constructed to stop high levels of current in the event ratings, current-limiting fuses are supplied as backup protection to
of a fault. They are excellent interrupters, and as such, they are interrupt and limit short-circuit currents higher than the contactor’s
better suited for power distribution applications instead of motor rating. The motor starter design must ensure the contactor does not
starting applications where the number of operations significantly open above its interrupting rating, and instead allow the fuse to
increases. For example, an application where only four motor starting clear this fault.
operations are required per day would lead to maintenance periods of
four months if a breaker-based controller is applied. Using the same Table 2 tabulates the minimum and total clearing times as well as
scenario, we find that the contactor will not require any recommended the let-through current of common fuses used in 400 A and 800 A
maintenance for more than ten years. Breakers can be used in this MV motor starters. As seen in this table, the higher the levels of
context, but it’s important to understand manufacturers’ maintenance prospective short-circuit current at the fuse location, the faster the
recommendations in order to implement maintenance schedules that fuse takes to clear and limit the let-through fault current feeding
accommodate for this usage. the fault. This current-limiting feature clears a fault within ½ cycle or
at least 10 times faster than a breaker’s instantaneous protection,
greatly reducing the amount of arc-flash energy produced during a
fault, making it safer for its users.

Table 2.  400 A and 800 A MV starter fuse characteristics [1]


400 A—24R 800 A—44R 800 A—57X
Prospective Total Total Total
short-circuit Minimum clearing Peak let Minimum clearing Peak let Minimum clearing Peak let
current rms (A) melt (cycle) (cycle) through (A) melt (cycle) (cycle) through (A) melt (cycle) (cycle) through (A)
12,000 2 2.6 33,000 15 18 N/A 18 60 N/A
15,000 1 1.2 35,000 6 9 N/A 4.8 16 N/A
20,000 Let-through <0.5 37,000 2 4 N/A 1.4 4.7 N/A
region
25,000 Let-through <0.5 40,000 1 2 N/A 0.6 2.4 N/A
region
30,000 Let-through <0.5 43,000 Let-through 1 N/A Let-through 1.5 76,000
region region region
35,000 Let-through <0.5 45,000 Let-through 0.9 82,000 Let-through 1.1 80,000
region region region
40,000 Let-through <0.5 47,000 Let-through <0.5 87,000 Let-through 0.8 83,000
region region region
45,000 Let-through <0.5 50,000 Let-through <0.5 90,000 Let-through <0.5 86,500
region region region
50,000 Let-through <0.5 51,000 Let-through <0.5 93,000 Let-through <0.5 90,000
region region region

EATON www.eaton.com 3
Application Paper AP020006EN Benefits of contactors vs. breakers for
Effective September 2020 medium-voltage motor control applications

Conclusion
With the ability to pair a fully rated 800 A starter with an 800 A
induction motor, there’s an opportunity for an optimum solution to
starting and stopping MV motors. Applying a fully rated 800 A starter
instead of a 1200 A circuit breaker not only right-sizes the equipment
for the application but also translates to other benefits: reduced
footprint, lower chopping currents, higher endurance, and faster
clearing times. The contactor-based solution provides significant
advantages along each of these parameters:

1. One-third less footprint and clearance requirements.


2. Lower chopping current means reduced likelihood of adverse
impact on downstream equipment.
3. 20 times higher mechanical and electrical endurance and
50 times operations between maintenance intervals.
4. Faster clearing time, which further enhances safety.

All that said, the traditional approach can work, and equipment
can last until it becomes too expensive and too difficult to find
replacement parts. When that happens, there’s an opportunity
to assess the best approach available today.

References
[1] Eaton Corp., R-Rated Medium-Voltage fuses for
Motor Circuit Protection, 2018.

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

© 2020 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. AP020006EN / Z24197 All other trademarks are property
September 2020 of their respective owners.

You might also like