Opti-Climate YAM Series

Tailor Made Design Opti-Climate YAM Series

Energy
Saving

Intelligent
Control

Indoor Air
Clean
Indoor Air
Quiet Precise Control Quality
Operation of Temperature &
Humidity

2 3
Opti-Climate YAM Series

YAM Features

Superior Performance Better Heat Insulation

The patented design of YAM series meets the


EN1886 class(D1,L1,T2,TB2)*. The unit casing Double skin construction is provided by
consists of foam injected,cold bridge free, Al frame "sandwich" type with high density strip.
profiles and high density polymerized polyurethane foam
The foam panel and profile skins are injected
injected panel with edges, which are joined together with strong
with PU foam of 45kg/m3, providing a thermal
AL-plastic composite tri-axial angle lug.
conductivity coefficient lower than 0.02W/m·k.
*YMM version yet to be certified by Eurovent Certification Body.

High Intensity Cold Bridge Free Design

Al profile employs nylon insulation


strips design and the skin is filled
The casing boasts a strong frame
with PU foam.
that is a complete metal complex of
AL-plastic composite tri-axial angle The damper and drain pan are fixed
lug and foam injected AL profile. with strips to isolate the cold bridge.

The drain pan uses 20mm thickness


synthetic rubber insulation for heat
resistance and anti-condensation.

Low Air Leakage Special design for clean-room industry application

Coupling with high-quality closed cell foam Airflow Range: 1,200~200,000m3/h The flush-joint from the panel to frame
synthetic rubber, the unique knife-shaped at the has a smooth surface and arcs at corners
foam panel edge gives perfect ring seal. to prevent dirt retention and water
standing.
The air leakage at joint is eliminated by the anti-
flaming and high/low temperature resistant gasket Drain pan is dual V-shaped structure with
and professional mechanical assemble. longitudinal slope, and allows quick and
easy drainage of condensate water.
The air leakage at the double-layer sealed access
door is eliminated by reliable vehicle-using sponge The high quality direct-driven fan (plug
sealing strip and high-strength lockers. fan) is optional, to avoid pollution caused
by wheel belt.

4 5
Opti-Climate YAM Series

Nomenclature Selection Software Overview

Model Description AECworks YAM Selection Software Features


Custom Made
YAM 50 - 1518 - S - R The user-friendly selection software UI makes easy selection.
The perfect project management system quickly responds to
customer's increasing design requirements.
The flexible parametric design improves the design efficiency
Opti-Climate YAM Series AHU Unit Hand: Left Hand (L) or Right
Hand (R) and effectively shortens supply period.
Insulation Thickness: 50mm
Unit Configuration: S-Single-tier,
Dimension: Height Module × Width D-Double-tier
Module, 15M×18M Powerful Function
Diverse configurations include simple and practical single-
tier unit, slim unit and double-tier unit with smaller occupied
area, to meet various customer requirements.
Over 400 models including 81 preferred standard models are
available to satisfy for both ordinary application and special
Note applications with high requirement for dimension.
Providing 19 segments for your option.
Distinguishing the unit hand Calculating the Overall Dimension
Single-tier units 1. Module Design: 1M=95mm
2. Unit Height
Professional software for coil selection
a) Height of single-tier unit
Providing diverse rows of coils, circuit designs and fin options,
= (Height module × 95 + 96) + Height of base (mm)
the software is suitable for different operating conditions and
Example: Height of 15M high single-tier unit with 100mm base
environments, and can optimize configuration and improve
= (15 × 95 + 96) + 100 = 1621 (mm)
efficiency of heat exchange.
b) Height of double-tier unit
=2× (Height module × 95 + 96) + Height of base (mm)
Example: Height of 15M high double-tier unit with 100mm base
The left hand is shown in the figure. =2× (15 × 95 + 96) + 100 = 3142 (mm)
3. Unit Width = Width module × 95 + 96(mm)
Example: Width of 18M-wide unit = 18×95 + 96 = 1806 (mm)
Double-tier units Comprehensive Output Reports
4. Length of the unit = Sum of lengths of all delivery sections.
Comprehensive performance report is provided.
Length of delivery section = length module ×95 + 96 (mm) C
Scaled assembly drawing with automatic output is provided

1241
390
Example: Length of 28M - long delivery section = 28 × 95 + 96 = 2756 (mm)
for professional's direct use.

475
100
2566

1521
1340
90
9M 6M 6M 5M
1201
2566

The left hand is shown in the figure.

6 7
Opti-Climate YAM Series

Quick Selection

Model Model
Airflow: m3/h Airflow: m3/h
0 5000 10000 15000 20000 25000 30000 35000 40000 20000 30000 40000 50000 60000 70000 80000 90000 100000 110000 120000 130000 140000 150000 160000 170000 180000 190000 200000 210000

0507 2222
0707 1728
0511 2620
0709 2224
0909 1730
1307 2820
0713 2028
1109 3019
0911 2424
0715 2228
1111 2624
0915 2824
1311 2429
0917 2628
1511 3224
1115 2828
1313 2433
1711 3027
1117 2633
1315 2436
1120 2834
1515 3232
1318 3036
2013 3236
1320 3046
1518 2654
1717 3246
1520 2854
2215 2658
1324 3446
1719 2858
2415 3254
3058
1524
3454
1722
3258
2020
3458
1527
3066
2022
3266
2419
3466
2618
3272
1726
3472
Airflow under recommended
推荐风量(2.0~2.5m/s) Airflow under high face
高速风量(2.5~3.0m/s) Airflow under recommended Airflow under high face
face velocity (2.0-2.5m/s) velocity (2.5-3.0m/s) 推荐风量(2.0~2.5m/s)
face velocity (2.0-2.5m/s) 高速风量(2.5~3.0m/s)
velocity (2.5-3.0m/s)

Note: Preferred standard models are listed. Note: Preferred standard models are listed.

8 9
Opti-Climate YAM Series

Segment Specifications
Segment Specifications
Segment Specifications

Sketch Length (Module) Sketch Length (Module)


Segment Name Notation Optional Segment Name Notation Optional
( Airflow direction) (for reference only) ( Airflow direction) (for reference only)

Damper arrangement, Flange, Manual damper, Motorized


Supply Fan – Fan brand, Motor brand, Fan discharge, Motor location,
damper without actuator, Motorized damper with On- SF-D L=8M~37M
Air Inlet Segment AI L=5M~36M DIDW Fan Segment Access door, Moisture-proof light, Viewport
Off or analog signal actuator, Access door, Moisture-
proof light, Viewport
L
L

Damper arrangement, Fresh air ratio, Flange, Manual


Return Fan – Fan brand, Motor brand, Fan discharge, Motor location,
damper, Motorized damper without actuator, Motorized RF-D L=8M~37M
Mixing Box Segment MB L=5M~36M DIDW Fan Segment Access door, Moisture-proof light, Viewport
damper with On-Off or analog signal actuator, Access
door, Moisture-proof light, Viewport
L
L

Damper arrangement, Exhaust air ratio, Flange, Manual


Supply Fan- Fan brand, Motor brand, Fan discharge, Motor location,
damper, Motorized damper without actuator, Motorized SF-P L=11M~39M
Economizer Segment EE L=12M~36M Plug Fan Segment Access door, Moisture-proof light, Viewport
damper with On-Off or analog signal actuator, Access
door, Moisture-proof light, Viewport
L
L

Return Fan- Fan brand, Motor brand, Fan discharge, Motor location,
Open Return Filter G3/G4 Plate filter, Without filter media (only offer plate RF-P L=11M~39M
OF No occupy a separate segment Plug Fan Segment Access door, Moisture-proof light, Viewport
Segment filter frame), Spare filter
L

G3/G4 Plate filter, Without filter media (Plate filter frame Top and side damper, Access door, Moisture-proof light,
L=2M 46mm Plate Empty Segment ES L=2M~21M
Plate Filter Segment PF only), Spare filter, Pressure difference gauge, Pressure Viewport
L=3M 96mm Plate
difference transmitter
L
L

G3/G4 Plate filter, G3/G4/F6/F7/F8 Bag filter, 380/530mm


L=6M 380mm Bag,
Bag filter, Single-bag filter, Plate and bag Combination
Plate+380mm Bag, Diffuser Segment DF L=5M~10M Access door, Moisture-proof light, Viewport
Bag Filter Segment BF filter (with Single-bag or Plate and bag combination
L=8M 530mm Bag,
filter frame), Spare filter, Pressure difference gauge,
Plate+530mm Bag.
L
Pressure difference transmitter L

Damper arrangement, Flange, Manual damper, Motorized


F9/H11/H13 High-efficiency filter, Without filter media damper without actuator, Motorized damper with On-
High-efficiency Filter Air Outlet Segment AO L=5M~36M
HF L=5M (Filter frame only), Spare filter, Pressure difference Off or analog signal actuator, Access door, Moisture-
Segment
gauge, Pressure difference transmitter proof light, Viewport
L
L

Damper arrangement, Exhaust air ratio, Flange, Manual


Vertical Economizer damper, Motorized damper without actuator, Motorized
HC L=3M 1R、2R VE L=5M~34M
Heating Coil Segment HC 1~4R Heating coil, Steel/Copper header, Piping direction Segment damper with On-Off or analog signal actuator, Access
L=4M 3R、4R
door, Moisture-proof light, Viewport
L
L

CC
1-6&8&10R Cooling coil+1-4R Heating coil, 1-6&8&10R
EL
Cooling Coil Segment CC L=5M~11M Cooling coil, Dual cooling coil, Steel/Copper header,
Piping direction, Eliminator
L

Turn Segment TN L=5M~15M Access door, Moisture-proof light, Viewport

Electric Heater
EH L=3M Heater Power
Segment

10 11
Opti-Climate YAM Series

Segment Specifications & Application

Air Inlet / Mixing Box / Air Outlet / Economizer Segment Filter Segment
Air Inlet Segment - It's connected to the duct to supply air into AHU of air conditioning system. Plate filter: Polyester synthetic fiber filter media (thickness of 46mm or
Air Outlet Segment - It's connected to the air supply duct to supply air to the air conditioning 96mm available; filtering efficiency: G3/G4).
system. Bag filter: Polyester synthetic fiber and glass fiber is optional (bag
Mixing Box Segment - It can adjust the ratio of return air and fresh air to satisfy the need of air length of 380mm or 530mm; filtering efficiency: F6/F7/F8).
conditioning environment. High efficiency filter: The V-shape pleated filter and box filter are
Economizer Segment - It can adjust the ratio of return air to fresh air and exhaust air to satisfy available, using ultra fine glass fiber filter paper. (Filter efficiency
the need of air conditioning environment. available are F9/H11/ H13).

Damper and Others


Damper
Damper material options: Galvanized steel, Aluminum alloy and stainless steel.
Providing flange, manual damper, motorized damper without actuator or with actuator.
Damper Location Installation Framework
- Air inlet, Air outlet, Mixing box segment: Front/Top/Side/Bottom - The filter framework is made of galvanized steel or stainless steel.
- Economizer segment: Top/Side - The primary filter and secondary pre-filter and medium filter
Optional damper dimension module (Mdl_X, Mdl_Y) is matched with AHU module. segments are fixed with clamps and bolts and the high-efficiency
Example: 7Mx9M damper can be positioned at the front of YAM0709 or above models., filter segment is pulled tightly with bolts to minimize the leakage rate
Mdl_X/Y is same as height module H or less than height module H-4 at height. even under high air pressure drop.
Mdl_X/Y logic at width is as follow (n is number such as 0,1,2)
Unit Width Module W 7M 9M ≥11M
Service Instructions
Mdl_X/Y 7 9,5 W,W-4-2n
- Remove the open return filter from side.
Note:
- Replace the plate and bag filters from the Front side (upstream side)
1. If a damper located at the side of AHU, the width (Mdl_Y) will determine the length of AHU segment (Damper required to
be installed in the casing which length module not less than width module of damper). To minimize the length size and and Rear side (downstream side).
cost of AHU, it is recommended to maximize the width of damper, rather than the length.
- Replace the high-efficiency filter from the Front side (upstream side).
2. Because of high volume of return air, it is recommended to position the return air damper at the front of unit. If no
damper is needed, you can only choose flange opening.
3. Please contact our local office for detailed damper dimension.

Options
Actuator
- Pressure difference gauge: Provide the visual reading of differential
Use On-off or analog signal actuator pressure through the filter, avoiding the filter efficiency reduction due
- On-Off type actuator: Open or cut off air flow through AHU. to dust over-accumulation.
- Pressure difference transmitter: Translate the differential pressure
through the filter into signals to the control system to monitor
pressure variation.

Options
Bottom damper.

12 13
Opti-Climate YAM Series

Segment Specifications & Application

Quantity of Filters Cooling Coil Segment/Heating Coil Segment


Cooling and heating coil are made of mechanically expanded copper tubes with
Unit Size 0507 0511 0707 0709 0713 0715 0909 0911 0915 0917 1109 1111 1115 1117 1120 1307 1311 1313 1315 1318 1320 1324 1511 1515 1518 1520 1524
aluminium fins, providing reliable performance and satisfying AHRI 410.
12"x12" - 1 - - - - 1 1 1 1 1 1 1 1 - - - - - - - - 1 1 - - 1 All coils are pre-tested for leakage according to the national standard before delivery.
12"x20" - - - - - - 1 - 2 - 1 - 2 - - - - - - - - - - 2 2 - - The coil has a framework made of galvanized steel or stainless steel for protection.
H×W
(Height x 12"x24" 1 1 - - - - - 1 - 2 - 1 - 2 3 - - - - - - - 1 - 1 3 3 The drain pan is made of galvanized steel or stainless steel.
Width)
20"x12" - - - - - - 1 1 1 1 - - - - - - 1 - 1 - - 1 2 2 - - 2
Drain pan is dual V-shaped structure with longitudinal slope, and allows quick and
easy drainage of condensed water.
20"x20" - - - - - - 1 - 2 - - - - - - - - 1 2 2 - - - 4 4 - -
An eliminator can be installed if required by customer to prevent condensed water
20"x24" - - - - - - - 1 - 2 - - - - - 1 1 1 - 1 3 3 2 - 2 6 6
from being blown out of coil. (As specified by the manufacturer, eliminator can be
24"x12" - - - 1 - 1 - - - - 1 1 1 1 - - 1 - 1 - - 1 - - - - - installed for coil face velocity in the range 2.5~3m/s).
24"x20" - - - 1 1 2 - - - - 1 - 2 - - - - 1 2 2 - - - - - - - Aluminum fin and hydrophilic aluminum fin is available.
24"x24" - - 1 - 1 - - - - - - 1 - 2 3 1 1 1 - 1 3 3 - - - - -

Unit Size 1527 1711 1717 1719 1722 1726 1728 1730 2013 2020 2022 2028 2215 2222 2224 2228 2415 2419 2424 2429 2433 2436 2618 2620 2624 2628 2633

12"x12" - 1 1 - 1 - 1 1 - - - - 1 1 1 1 1 - 1 1 - 1 - - - - -

12"x20" - - - 1 2 1 2 - - - - - 2 2 - 2 2 1 - 1 - 1 - - - - -

12"x24" 4 1 2 2 1 3 2 4 - - - - - 1 3 2 - 2 3 3 5 4 - - - - - Electric Heater Segment


H×W
20"x12" - - - - - - - - - - - - 2 2 2 2 - - - - - - - - 1 1 - The electric heater employs stainless steel tube with helical fins and temperature
(Height x 20"x20" - - - - - - - - - - - - 4 4 - 4 - - - - - - 2 - - 2 - protection switch, etc.
Width)
20"x24" 8 - - - - - - - - - - - - 2 6 4 - - - - - - 1 3 3 2 5 The electric heater element is fixed on the frame. Electric control box is supplied and
24"x12" - 2 2 - 2 - 2 2 - - 3 3 1 1 1 1 3 - 3 3 - 3 - - 3 3 - installed by the user. And its control must be interlocked with the fan.
24"x20" - - - 2 4 2 4 - 3 - 6 6 2 2 - 2 6 3 - 3 - 3 6 - - 6 - Features
24"x24" - 2 4 4 2 6 4 8 3 9 3 6 - 1 3 2 - 6 9 9 15 12 3 9 9 6 15 - 1-4 steps control, to satisfy various needs of heating power;
Unit Size 2654 2658 2820 2824 2828 2834 2854 2858 3019 3027 3036 3046 3058 3066 3224 3232 3236 3246 3254 3258 3266 3272 3446 3454 3458 3466 3472
- Overheating protection: Built-in temperature protection switch shall automatically
shut off when the temperature is too high.
12"x12" - - - 1 1 - 1 - - - 1 - - - - - - - - - - - - - - - -

12"x20" - - - - 2 - 2 1 1 - 1 - 1 - - - - - - - - - - - - - -

12"x24" - - 3 3 2 5 6 8 2 4 4 7 8 10 - - - - - - - - - - - - -

20"x12" 1 - - 2 2 - 2 - - - - - - - 1 - 1 - 1 - - - - - - - -
H×W
(Height x 20"x20" 2 1 - - 4 - 4 2 - - - - - - - 1 1 - 2 1 - - - - - - -
Width)
20"x24" 6 8 6 6 4 10 12 16 - - - - - - 3 4 4 7 6 8 10 11 - - - - -

24"x12" 3 - - 2 2 - 2 - - - 4 - - - 4 - 4 - 4 - - - - 5 - - -

24"x20" 6 3 - - 4 - 4 2 4 - 4 - 4 - - 4 4 - 8 4 - - - 10 5 - -

24"x24" 18 24 6 6 4 10 12 16 8 16 16 28 32 40 12 16 16 28 24 32 40 44 35 30 40 50 55

Note: Sizes of the plate filters and high-efficiency filters in the table are stated non-directionally, meaning that 12"x20" is identical to 20"x12", and so is 12"x24" to 24"x12", 20"x24" to 24"x20".
The delivery sizes are stated in 12"x20"/12"x24"/20"x24". Sizes of bag filters are stated directionally, of which the front one stands for the height.

Comparison of Efficiency and Specifications in China, USA and EU

High-medium Sub-HEPA
China Premium efficiency≥5μm Medium efficiency≥1μm HEPA efficiency≥0.5μm
efficiency≥1μm efficiency≥0.5μm
GB/T14295 80%>Efficiency≥20% 70%>Efficiency≥20% Efficiency≥99.9%
99%>Efficiency≥70% 99.9%>Efficiency≥25%

U.S.
C1 C2-C4 L5 L6 L7 L8 M9 M10 M11 M12 M13 M17 H12~H16 VH17 VH18 VH19 VH20
ASHRAE

Europe
G1 G2 G3 G4 F5 F6 F7 F8 F9 H10 H11 H12 H13 H14 V15V17
New
65% 80% 80%~90% >90% 40% 60% 90% 90% 85% 95% 99% 99.90% 99.95% 99.995% 99.9995%
specification

Europe
Old EU1 EU2 EU3 EU4 EU5 EU6 EU7 EU8 EU9 EU10 EU11 EU12 EU13 EU14
specification

14 15
Opti-Climate YAM Series

Segment Specifications & Application Notes for installation and maintenance

Fan Segment
Schematics of installation and maintenance
Double-inlet forward-curve/backward-curve centrifugal fan or plug fan
Foundation Schematic Schematic of Service Space
from well known brand is adopted, safer and more reliable.
Both impeller and frame are made from high-strength alloy steel plate with
drainage ditch
robust design. Impeller has been statically and dynamically balanced. foundation 150 150 floor
The optional VSD converter can regulate the running speed of fan,

W=Unit width+200

H
reducing energy consumption of system.
High-quality damper spring is used for damping, which effectively Floor drain

lowers vibration and noise produced by fan. A-A Enlargement


A
Base of motor is equipped with sliding rail adjustment device to The shadow Coil at the negative pressure side
stands for
P=Absolute value of positive
facilitate adjusting motor belt by user. foundation, the
pressure(Pa) in the Segment

L
surface of which
must be flat. H≥P/10+50(mm)
The founda- Floor drain and drain pipe shall
A Coil at the positive pressure side
tion bolt hole. be located at the same side.
P=Absolute value of negative
pressure(Pa) in the Segment
L=Unit length+200
On outlet of fan there's flexible connection of canvas up to H≥P/10+100(mm) Wall

requirements for fire prevention, which prevents transfer of vibration. L stands for the distance from the service side to wall,
must be longer than width of casing

Notes for Installation


1. The AHU must have a horizontal foundation and proper vibration-isolating measure
during the installation. After installation, fix the AHU with foundation bolts.
Belt is product from well known brand, with high driving power and 2. Important: all delivery sections must stay at the same level and no inclination shall
good wear resistance.

A
be acceptable during the field installation. Before tightening bolts, ensure all contact
European-style taper sleeve belt pulley is used, reliable in running and surface retain the same level.

B
easy for disassembly. 3. The foundation height must be enough to install the water trap as required and no
Each bearing is product from known brand, with high assembly lower than 150mm. Coil at the negative pressure side Coil at the positive pressure side
P=Absolute value of positive P=Absolute value of negative
accuracy. This guarantees long-time continuous running of unit. 4. The tube near equipment must be fixed to eliminate any torque-caused damages pressure(Pa) in the Segment pressure(Pa) in the Segment
A=P/10(mm) A≥50(mm)
against equipment when tubing (inlet, outlet, steam).
B≥50(mm) B≥P/10+60(mm)
5. It is recommended to use flexible connectors for inlet and outlet pipes and self-closing
valves (provided by customers) for steam and hot water inlets to ensure that the internal temperature is not higher than 60°C.
For plug fan application, depending on flexible air-out modes, it is 6. When using the crane or forklift to load/unload or position equipment, please ensure the stress points shall be
unnecessary to consider driving direction of fan. This avoids use of lifting holes or forklift holes and no shoveling or lifting on the base or any other casing part shall be allowable.
unnecessary air duct and makes installation easier. 7. The electric heater must interlock with the fan when an electric heater segment exists.
Plug fan with open structure, easier for cleaning and maintenance 8. The installation of AHU water trap must follow the right figure.
High efficiency, low noise 9. All electrical components and shell of the AHU must be grounded.
Direct-driven plug fan is directly driven with motor. This avoids
secondary pollution from debris of belt produced during belt driving.
Such fan is widely used in clean-room industries e.g. electronics, Notes for Maintenance
pharmacy etc.
1. The AHU shall be under the maintenance by specially-appointed staff.
2. All electrical components and safety devices shall be regularly inspected.
3. Periodically inspect and adjust the belt tension to optimize the AHU state.
High-quality motor with high energy efficiency from famous brand is
4. Periodically inspect the filter DP and cleanliness and clean or replace those with over DP.
used, high in efficiency and reliable in running. It is IP55 protection class
5. Periodically lubricate components that need lubricating.
and Class F insulation.
6. Vent air in the coil before starting the unit.
Constant-speed motors and VSD motors are available.
7. During shutdown in winter, cut off all water and steam supplies and drain off the coil or take other anti-freezing measures to
Power supply: 380V/3P/50Hz, 380-415V/3/50Hz, 460V/3P/60Hz,
prevent coil cracking.
380 V/3P/60Hz, /230V/3P/60Hz
8. Periodically clean the AHU internal and coil. The coil is cleaned by compressed air or high-pressure steam.

16 17
Office Locations

Australia (Sydney) Indonesia (Jakarta) Malaysia (Kuala Lumpur)


Tel: +61 (2) 9805 8300 Tel: +62 (21) 5366 8500 Tel: +60 (3) 7628 4300
Fax: +61 (2) 9241 7128 Fax: +61 (21) 5366 8300 Fax: +60 (3) 7874 1180

China (Shanghai) Japan (Tokyo) New Zealand (Auckland)


Tel: +86 (21) 6276 6509 Tel: +81 (3) 5738 6100 Tel: +64 (9) 444 6434
Fax: +86 (21) 6277 3543 Fax: +81 (3) 5738 6298 Fax: +64 (9) 444 2092

Hong Kong Korea (Seoul) Singapore


Tel: +852 2590 0012 Tel: +822 554 5935 Tel: +65 6748 0202
Fax: +852 2516 5648 Fax: +822 554 5739 Fax: +65 6743 4420

India (Mumbai) Macau Thailand (Bangkok)


Tel: +91 (22) 6683 7000 Tel: +853 2875 1820 Tel: +66 (2) 717 1260-80
Fax: +91 (22) 6683 7002 Fax: +853 2875 1825 Fax: +66 (2) 717 1325-8

Manufacturing/assembly: Guangzhou, China; Selangor, Malaysia