Opti-Climate YAM Series
YAM Features
Coupling with high-quality closed cell foam Airflow Range: 1,200~200,000m3/h The flush-joint from the panel to frame
synthetic rubber, the unique knife-shaped at the has a smooth surface and arcs at corners
foam panel edge gives perfect ring seal. to prevent dirt retention and water
standing.
The air leakage at joint is eliminated by the anti-
flaming and high/low temperature resistant gasket Drain pan is dual V-shaped structure with
and professional mechanical assemble. longitudinal slope, and allows quick and
easy drainage of condensate water.
The air leakage at the double-layer sealed access
door is eliminated by reliable vehicle-using sponge The high quality direct-driven fan (plug
sealing strip and high-strength lockers. fan) is optional, to avoid pollution caused
by wheel belt.
4 5
Opti-Climate YAM Series
1241
390
Example: Length of 28M - long delivery section = 28 × 95 + 96 = 2756 (mm)
for professional's direct use.
475
100
2566
1521
1340
90
9M 6M 6M 5M
1201
2566
6 7
Opti-Climate YAM Series
Quick Selection
Model Model
Airflow: m3/h Airflow: m3/h
0 5000 10000 15000 20000 25000 30000 35000 40000 20000 30000 40000 50000 60000 70000 80000 90000 100000 110000 120000 130000 140000 150000 160000 170000 180000 190000 200000 210000
0507 2222
0707 1728
0511 2620
0709 2224
0909 1730
1307 2820
0713 2028
1109 3019
0911 2424
0715 2228
1111 2624
0915 2824
1311 2429
0917 2628
1511 3224
1115 2828
1313 2433
1711 3027
1117 2633
1315 2436
1120 2834
1515 3232
1318 3036
2013 3236
1320 3046
1518 2654
1717 3246
1520 2854
2215 2658
1324 3446
1719 2858
2415 3254
3058
1524
3454
1722
3258
2020
3458
1527
3066
2022
3266
2419
3466
2618
3272
1726
3472
Airflow under recommended
推荐风量(2.0~2.5m/s) Airflow under high face
高速风量(2.5~3.0m/s) Airflow under recommended Airflow under high face
face velocity (2.0-2.5m/s) velocity (2.5-3.0m/s) 推荐风量(2.0~2.5m/s)
face velocity (2.0-2.5m/s) 高速风量(2.5~3.0m/s)
velocity (2.5-3.0m/s)
Note: Preferred standard models are listed. Note: Preferred standard models are listed.
8 9
Opti-Climate YAM Series
Segment Specifications
Segment Specifications
Segment Specifications
Return Fan- Fan brand, Motor brand, Fan discharge, Motor location,
Open Return Filter G3/G4 Plate filter, Without filter media (only offer plate RF-P L=11M~39M
OF No occupy a separate segment Plug Fan Segment Access door, Moisture-proof light, Viewport
Segment filter frame), Spare filter
L
G3/G4 Plate filter, Without filter media (Plate filter frame Top and side damper, Access door, Moisture-proof light,
L=2M 46mm Plate Empty Segment ES L=2M~21M
Plate Filter Segment PF only), Spare filter, Pressure difference gauge, Pressure Viewport
L=3M 96mm Plate
difference transmitter
L
L
CC
1-6&8&10R Cooling coil+1-4R Heating coil, 1-6&8&10R
EL
Cooling Coil Segment CC L=5M~11M Cooling coil, Dual cooling coil, Steel/Copper header,
Piping direction, Eliminator
L
Electric Heater
EH L=3M Heater Power
Segment
10 11
Opti-Climate YAM Series
Air Inlet / Mixing Box / Air Outlet / Economizer Segment Filter Segment
Air Inlet Segment - It's connected to the duct to supply air into AHU of air conditioning system. Plate filter: Polyester synthetic fiber filter media (thickness of 46mm or
Air Outlet Segment - It's connected to the air supply duct to supply air to the air conditioning 96mm available; filtering efficiency: G3/G4).
system. Bag filter: Polyester synthetic fiber and glass fiber is optional (bag
Mixing Box Segment - It can adjust the ratio of return air and fresh air to satisfy the need of air length of 380mm or 530mm; filtering efficiency: F6/F7/F8).
conditioning environment. High efficiency filter: The V-shape pleated filter and box filter are
Economizer Segment - It can adjust the ratio of return air to fresh air and exhaust air to satisfy available, using ultra fine glass fiber filter paper. (Filter efficiency
the need of air conditioning environment. available are F9/H11/ H13).
Options
Actuator
- Pressure difference gauge: Provide the visual reading of differential
Use On-off or analog signal actuator pressure through the filter, avoiding the filter efficiency reduction due
- On-Off type actuator: Open or cut off air flow through AHU. to dust over-accumulation.
- Pressure difference transmitter: Translate the differential pressure
through the filter into signals to the control system to monitor
pressure variation.
Options
Bottom damper.
12 13
Opti-Climate YAM Series
Unit Size 1527 1711 1717 1719 1722 1726 1728 1730 2013 2020 2022 2028 2215 2222 2224 2228 2415 2419 2424 2429 2433 2436 2618 2620 2624 2628 2633
12"x12" - 1 1 - 1 - 1 1 - - - - 1 1 1 1 1 - 1 1 - 1 - - - - -
12"x20" - - - 1 2 1 2 - - - - - 2 2 - 2 2 1 - 1 - 1 - - - - -
12"x20" - - - - 2 - 2 1 1 - 1 - 1 - - - - - - - - - - - - - -
12"x24" - - 3 3 2 5 6 8 2 4 4 7 8 10 - - - - - - - - - - - - -
20"x12" 1 - - 2 2 - 2 - - - - - - - 1 - 1 - 1 - - - - - - - -
H×W
(Height x 20"x20" 2 1 - - 4 - 4 2 - - - - - - - 1 1 - 2 1 - - - - - - -
Width)
20"x24" 6 8 6 6 4 10 12 16 - - - - - - 3 4 4 7 6 8 10 11 - - - - -
24"x12" 3 - - 2 2 - 2 - - - 4 - - - 4 - 4 - 4 - - - - 5 - - -
24"x20" 6 3 - - 4 - 4 2 4 - 4 - 4 - - 4 4 - 8 4 - - - 10 5 - -
24"x24" 18 24 6 6 4 10 12 16 8 16 16 28 32 40 12 16 16 28 24 32 40 44 35 30 40 50 55
Note: Sizes of the plate filters and high-efficiency filters in the table are stated non-directionally, meaning that 12"x20" is identical to 20"x12", and so is 12"x24" to 24"x12", 20"x24" to 24"x20".
The delivery sizes are stated in 12"x20"/12"x24"/20"x24". Sizes of bag filters are stated directionally, of which the front one stands for the height.
High-medium Sub-HEPA
China Premium efficiency≥5μm Medium efficiency≥1μm HEPA efficiency≥0.5μm
efficiency≥1μm efficiency≥0.5μm
GB/T14295 80%>Efficiency≥20% 70%>Efficiency≥20% Efficiency≥99.9%
99%>Efficiency≥70% 99.9%>Efficiency≥25%
U.S.
C1 C2-C4 L5 L6 L7 L8 M9 M10 M11 M12 M13 M17 H12~H16 VH17 VH18 VH19 VH20
ASHRAE
Europe
G1 G2 G3 G4 F5 F6 F7 F8 F9 H10 H11 H12 H13 H14 V15V17
New
65% 80% 80%~90% >90% 40% 60% 90% 90% 85% 95% 99% 99.90% 99.95% 99.995% 99.9995%
specification
Europe
Old EU1 EU2 EU3 EU4 EU5 EU6 EU7 EU8 EU9 EU10 EU11 EU12 EU13 EU14
specification
14 15
Opti-Climate YAM Series
Fan Segment
Schematics of installation and maintenance
Double-inlet forward-curve/backward-curve centrifugal fan or plug fan
Foundation Schematic Schematic of Service Space
from well known brand is adopted, safer and more reliable.
Both impeller and frame are made from high-strength alloy steel plate with
drainage ditch
robust design. Impeller has been statically and dynamically balanced. foundation 150 150 floor
The optional VSD converter can regulate the running speed of fan,
W=Unit width+200
H
reducing energy consumption of system.
High-quality damper spring is used for damping, which effectively Floor drain
L
surface of which
must be flat. H≥P/10+50(mm)
The founda- Floor drain and drain pipe shall
A Coil at the positive pressure side
tion bolt hole. be located at the same side.
P=Absolute value of negative
pressure(Pa) in the Segment
L=Unit length+200
On outlet of fan there's flexible connection of canvas up to H≥P/10+100(mm) Wall
requirements for fire prevention, which prevents transfer of vibration. L stands for the distance from the service side to wall,
must be longer than width of casing
A
be acceptable during the field installation. Before tightening bolts, ensure all contact
European-style taper sleeve belt pulley is used, reliable in running and surface retain the same level.
B
easy for disassembly. 3. The foundation height must be enough to install the water trap as required and no
Each bearing is product from known brand, with high assembly lower than 150mm. Coil at the negative pressure side Coil at the positive pressure side
P=Absolute value of positive P=Absolute value of negative
accuracy. This guarantees long-time continuous running of unit. 4. The tube near equipment must be fixed to eliminate any torque-caused damages pressure(Pa) in the Segment pressure(Pa) in the Segment
A=P/10(mm) A≥50(mm)
against equipment when tubing (inlet, outlet, steam).
B≥50(mm) B≥P/10+60(mm)
5. It is recommended to use flexible connectors for inlet and outlet pipes and self-closing
valves (provided by customers) for steam and hot water inlets to ensure that the internal temperature is not higher than 60°C.
For plug fan application, depending on flexible air-out modes, it is 6. When using the crane or forklift to load/unload or position equipment, please ensure the stress points shall be
unnecessary to consider driving direction of fan. This avoids use of lifting holes or forklift holes and no shoveling or lifting on the base or any other casing part shall be allowable.
unnecessary air duct and makes installation easier. 7. The electric heater must interlock with the fan when an electric heater segment exists.
Plug fan with open structure, easier for cleaning and maintenance 8. The installation of AHU water trap must follow the right figure.
High efficiency, low noise 9. All electrical components and shell of the AHU must be grounded.
Direct-driven plug fan is directly driven with motor. This avoids
secondary pollution from debris of belt produced during belt driving.
Such fan is widely used in clean-room industries e.g. electronics, Notes for Maintenance
pharmacy etc.
1. The AHU shall be under the maintenance by specially-appointed staff.
2. All electrical components and safety devices shall be regularly inspected.
3. Periodically inspect and adjust the belt tension to optimize the AHU state.
High-quality motor with high energy efficiency from famous brand is
4. Periodically inspect the filter DP and cleanliness and clean or replace those with over DP.
used, high in efficiency and reliable in running. It is IP55 protection class
5. Periodically lubricate components that need lubricating.
and Class F insulation.
6. Vent air in the coil before starting the unit.
Constant-speed motors and VSD motors are available.
7. During shutdown in winter, cut off all water and steam supplies and drain off the coil or take other anti-freezing measures to
Power supply: 380V/3P/50Hz, 380-415V/3/50Hz, 460V/3P/60Hz,
prevent coil cracking.
380 V/3P/60Hz, /230V/3P/60Hz
8. Periodically clean the AHU internal and coil. The coil is cleaned by compressed air or high-pressure steam.
16 17