3219-00 New College Durham STEM

G30
Metal profiled sheet decking
Revision C1

Section Revision History


No. Purpose
P1 Tender 4th Sep 2018
C1 Construction Issue 27th Nov 2018

Clauses amended in Revision C1


No. Clause
1 REASON FOR ISSUE Revised

Rev C1
G30
3219-00 New College Durham STEM

G30 Metal profiled sheet decking

1 REASON FOR ISSUE CONSTRUCTION


(Revised - G30 revision C1 - 27th Nov 2018)

TO BE READ WITH STRUCTURAL ENGINEER'S SPECIFICATION AND


PRELIMINARIES/ GENERAL CONDITIONS AND SPECIFICATION PREAMBLES
(SECTION A)

PROPRIETARY SPECIFIED ROOF/ FLOOR DECKING

PERFORMANCE SPECIFIED ROOF/ FLOOR DECKING

155 CONTRACTOR'S DESIGN OF ROOF DECKING TO ALL ROOFS


• Design responsibility: Determine profile, depth and thickness of metal decking, types,
sizes, number and spacing of fixings, stiffening around openings and cleader angles to
gables.
• Structural and fire requirements:
- Generally: As section B50.
- Modifications: None.
- Design: Complete the design in accordance with the designated code of practice to
satisfy specified performance criteria.
• Functional requirements: As specified in this section.
• Additional requirements: None.
• Design and production information: As Preliminaries section A33.
• Timing of submissions: As Preliminaries section A33.

175 STRUCTURAL DESIGN PROVIDED


• Description: Refer to Structural Engineers Specification.
• Requirements:
- Generally: As section B50.
- Additional requirements: None.

180 DESIGN REQUIREMENTS FOR DECKING


• Material: Steel, Grade S350 GD + Z275 to BS EN 10326.
• Depth of profile: Contractor's choice.
• Soffit finish: PVF2 - White.
• Maximum allowable deflection: Refer to Structural Engineers Specification.
• Sound transmittance: Not required.
• Accessories: None.

FIXING DECKING

220 PAINTING STRUCTURE


• Sequence: Before the decking is attached paint surfaces of supporting structure that will be
subsequently inaccessible.

230 PREVENTION OF ELECTROLYTIC ACTION


• Isolating tape: Type recommended by decking manufacturer.
- Location: To contact surfaces of supports and sheets of dissimilar metals.

Rev C1
G30
Page 1 of 2
3219-00 New College Durham STEM

240 FIRE RESISTING PROFILE FILLERS


• Supplier: Decking manufacturer.
• Type/ shape: To match decking profile void.
• Location: To perimeter of openings.
• Fixing: Fit securely, as recommended by manufacturer, to form fire compartment.

260 FIXING DECKING GENERALLY


• Cut sheets: Clean edges with true lines and no burrs.
- Treatment of edges: As recommended by manufacturer.
• Penetrations: Cut openings to the minimum size necessary.
- Edge reinforcement: As recommended by manufacturer .
Fixings: Drill all holes.
• Cleanliness: Remove debris from within decking construction.
• Installation: Seams and ribs of deck must be parallel, with no damage to deck coating.

285 ATTACHMENT OF DECKING AND ACCESSORIES


• Scope of Contactor's design: Types, sizes, number and spacing of fixings for deck and
accessories.
• Requirement: To resist specified wind load.
- Additional requirements: None.

Rev C1
G30
Page 2 of 2