Professional Documents
Culture Documents
Example 3D view
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Content
Content
2 Typographical Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1 Typographical Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.1 References to other Documents . . . . . . . . . . . . . . . . . . . . . . 10
2.1.2 References to Chapter or Sections of the Current
Document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.3 Document Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.4 Colours in Pictures in this Manual . . . . . . . . . . . . . . . . . . . . 10
2.1.5 Contents of Header and Footer . . . . . . . . . . . . . . . . . . . . . . 11
4 Description of installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1 Metalenclosed Gas Insulated Switchgear (GIS) . . . . . . . . . . . . . . . . . . . 16
4.1.1 Advantages of the GIS technology . . . . . . . . . . . . . . . . . . . 16
4.1.2 General structure of a GIS . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.2 General structure of the components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3 Short description of the components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3.1 Busbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3.2 Circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3.3 Circuit breaker operating mechanism . . . . . . . . . . . . . . . . . 17
4.3.4 Combined disconnector / earthing switch . . . . . . . . . . . . . 17
4.3.5 Cable termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3.6 Earthing switch with short circuit making capacity . . . . . . 18
4.3.7 Barrier insulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3.8 Support insulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Template: Inhalt 2
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Content
6 Description of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.1 Circuit breaker type ELKSP14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.1.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.1.2 Circuit Breaker Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.1.3 Operating principle of the interrupter unit . . . . . . . . . . . . . . 34
6.1.4 Operating diagram for circuit breaker with singlepole
operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.1.5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.1.6 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.1.7 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.1.8 Overhaul work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.2 Circuit breaker operating mechanisms type HMB4 . . . . . . . . . . . . . . . . 38
6.3 Disconnector/earthing switch type ELKDE0 . . . . . . . . . . . . . . . . . . . . . . . 39
6.3.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.3.2 Disconnector/earthing switch design . . . . . . . . . . . . . . . . . 40
6.3.3 Operating mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.3.3.1 Manual operation (control voltage present) . . . . . . . . . . . . 43
6.3.3.2 Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.3.4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.3.5 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.3.6 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.3.7 Overhaul work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.4 Earthing switch with short circuit making capacity type ELKES0 . . . . 50
6.4.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
6.4.2 Design of earthing switch with short circuit making
capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Template: Inhalt 3
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Content
Template: Inhalt 4
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Content
6.13.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
6.13.4 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
6.14 Voltage transformer ELKPI04 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
6.14.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
6.14.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
6.14.3 Connection / commissioning . . . . . . . . . . . . . . . . . . . . . . . . 87
6.14.4 Feeder Module with integrated Disconnector/Earthing
Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.14.5 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
6.14.6 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
6.15 Exit splitup ELKHKY14 and cable connection (IEC) ELKHK14 . . . . . . 92
6.15.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
6.15.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6.15.3 Connection / commissioning . . . . . . . . . . . . . . . . . . . . . . . . 94
6.15.4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6.15.5 Maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6.15.6 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
9 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
9.1 Hydraulic operating mechanism of circuitbreaker . . . . . . . . . . . . . . . . . . 107
9.2 Circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
9.3 Disconnector / earthing switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
9.4 Earthing switch with short circuit making capacity . . . . . . . . . . . . . . . . . . 108
9.5 Voltage transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
9.6 Other switchgear modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
9.7 Conversion Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
9.7.1 Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
9.7.2 Tightening Torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
9.7.3 Absolute Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
9.7.4 Force . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
9.7.5 Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
9.7.6 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
9.7.7 Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Template: Inhalt 5
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
List of Figures
List of Figures
Fig.1: Contents of the Header and the Footer on each Page of the
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Fig.2: Overhaul flow chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fig.3: Symbol Circuit Breaker ELKSP14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Fig.4: Circuit breaker ELKSP14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Fig.5: Functional principle of the interrupting chamber during opening
operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Fig.6: Symbols for disconnector and earthing switch ELKDE0 . . . . . . . . . . . . 39
Fig.7: Disconnector/earthing switch ELKDE0 . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Fig.8: Disconnector/earthing switch integrated in the busbar module
(neutral position) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Fig.9: Insulating rods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Fig.10: Operating mechanism of the combined disconnector/earthing
switch ..................................................... 42
Fig.11: Operating mechanism with cover, switching contact in neutral
position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Fig.12: Operating mechanism after removal of its cover, switching contact in
neutral position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Fig.13: Switching positions of handle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Fig.14: Possible combinations of positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Fig.15: Operating elements disconnector (front view) . . . . . . . . . . . . . . . . . . . . . 45
Fig.16: Operating elements earthing switch (front view) . . . . . . . . . . . . . . . . . . . 46
Fig.17: Operating elements disconnector and earthing switch (front view) . . . 47
Fig.18: Symbols for earthing switch with short ciruit making capacity . . . . . . . . 50
Fig.19: Operating mechanism and main contacts of earthing switch with short
circuit making capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Fig.20: Combined crank handle/finalposition interlock . . . . . . . . . . . . . . . . . . . 52
Fig.21: Switch position lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Fig.22: Operating elements of the earthing switch with short circuit making
capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Fig.23: Operating elements after removal of the cover plate . . . . . . . . . . . . . . . . 55
Fig.24: Operating elements of the earthing switch with short circuit making
capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Fig.25: Operating elements of the earthing switch with short circuit making
capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Fig.26: Connecting bus short (a), long with or without transversal
erection (b) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Fig.27: Elbow element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Fig.28: T and Xmodule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Fig.29: Design of splitup with current transformer ELKVY14 . . . . . . . . . . . . . . . 68
Fig.30: Terminal configuration in terminal box . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Fig.31: End cover attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Fig.32: Density monitor ELKWT14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Fig.33: Pressure relief device ELKXA14 (left) and nameplate (right) . . . . . . . . . 78
Fig.34: Pressure relief device ELKXA14 with adsorber . . . . . . . . . . . . . . . . . . . . . 78
Fig.35: Parts to be replaced on maintenance (left) and on damage (right) . . . 81
Fig.36: Barrier insulator (left) and support insulator (right) . . . . . . . . . . . . . . . . . 82
Fig.37: Bushing ELKHB14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Fig.38: Inductive voltage transformer type ELKPI04 . . . . . . . . . . . . . . . . . . . . . . 87
Fig.39: Voltage Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Fig.40: Connection of voltage transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Fig.41: Voltage transformer installed at outgoing disconnector . . . . . . . . . . . . . 89
Fig.42: Voltage transformer installed at exit splitup . . . . . . . . . . . . . . . . . . . . . . . 90
Template: Figur 6
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
List of Figures
Template: Figur 7
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
List of Tables
List of Tables
Template: Tabelle 8
Order No.: 1HC0044810 E01 / AA06
Ñ°»®¿¬·²¹ ײ¬®«½¬·±²
ÍÚê ײ«´¿¬»¼ Í©·¬½¸¹»¿®
ݱ°§®·¹¸¬ ¿²¼ ß¼¼®»
ïòí ݱ°§®·¹¸¬
É» ®»»®ª» ¿´´ ®·¹¸¬ ¬± ¬¸· ¼±½«³»²¬ ¿²¼ ¬± ¬¸» ±¾¶»½¬ ¼»½®·¾»¼ ¬¸»®»·²ò ̸» ®»½·°·»²¬
±º ¬¸· ¼±½«³»²¬ ®»½±¹²·¦» ¬¸»» ®·¹¸¬ ¿²¼ ©·´´ ²±¬ ©·¬¸±«¬ ±«® °®·±® ©®·¬¬»² ¿°°®±ª¿´
³¿µ» ¬¸· ¼±½«³»²¬ ¿ª¿·´¿¾´» »·¬¸»® ·² °¿®¬ ²±® ·² ©¸±´» ¬± ¿²§ ¬¸·®¼ °¿®¬§ ±® «» ·¬ º±®
¿²§ °«®°±» ±¬¸»® ¬¸¿² ¬¸¿¬ º±® ©¸·½¸ ·¬ ©¿ °®»»²¬»¼ ¬± ¸·³ò
Û ßÞÞ Í©·¬¦»®´¿²¼ Ô¬¼
ïòê É¿®®¿²¬§
ײ ±«® »¨°»®·»²½»ô ½±®®»½¬ ±¾»®ª¿²½» ±º ¬¸» ·²º±®³¿¬·±² ½±²¬¿·²»¼ ·² ¬¸·
¬·±² ¹«¿®¿²¬»» ¬¸» ¿º» ±°»®¿¬·±² ±º ±«® °®±¼«½¬ò ̸» ¼±½«³»²¬¿¬·±² °®±ª·¼»¼ ¸¿
¾»»² °®»°¿®»¼ ©·¬¸ ¹®»¿¬ ½¿®»ò д»¿» ·²º±®³ « ±® ±«® ²»¿®»¬ ®»°®»»²¬¿¬·ª» ·º ·¬ · ²±
´±²¹»® °±·¾´» ¬± ±°»®¿¬» ±«® °®±¼«½¬ ¿º»´§ ±² ¿½½±«²¬ ±º ·²½±®®»½¬ ±® ±³·¬¬»¼
¬·±²ò
É» ©·´´ ²±¬ ¿½½»°¬ ¿²§ ´·¿¾·´·¬§ ©¸¿¬±»ª»® º±® ¼¿³¿¹» ¿®··²¹ »·¬¸»® ¼·®»½¬´§ ±® ·²¼·®»½¬´§
º®±³ ¬¸» ·²½±®®»½¬ ±°»®¿¬·±² ±º ±«® °®±¼«½¬ò ̸» ·²º±®³¿¬·±² ©·¬¸·² ¬¸· ³¿²«¿´ · «¾¶»½¬
¬± ¬»½¸²·½¿´ ³±¼·º·½¿¬·±² ©·¬¸±«¬ ²±¬·½»ò
Ì»³°´¿¬»æ ÝÎÁïØÝððìëîëèÁßß»² ç
Ñ®¼»® Ò±òæ ïØÝððììèïð Ûðï ñ ßßðê
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Typographical Arrangements
2 Typographical Arrangements
Template: TG_1HC0045260_AAen 10
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Typographical Arrangements
Title Document
Title Main Chapter
1
2 Template: 1HC0021000 12
Order No.: 1HC0044810 E01 / AA06
Template: TG_1HC0045260_AAen 11
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Safety Notes
3.2.5 Safety
ABB Switzerland Ltd. continuously designs stateoftheart and according to interna
tional standards. Moving parts are always covered during operation. Never remove cov
ers or other parts that are in operation. Make sure to fulfill all requirements and measures
for your safety before starting to work on equipment. Please notice symbols for your
safety.
Template: SN_ELK−14_1HC0045262_AAen 12
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Safety Notes
Template: SN_ELK−14_1HC0045262_AAen 13
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Safety Notes
Assembly instructions:
Information Information and directions, which will make the work more convenient for you.
Template: SN_ELK−14_1HC0045262_AAen 14
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Safety Notes
Template: SN_ELK−14_1HC0045262_AAen 15
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of Installation
4 Description of installation
Template: Des_GIS_1HC0045263_AAen 16
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of Installation
4.3.1 Busbar
The busbars distribute the current within the switchgear. A busbar system is composed
of the individual busbar segments of each feeder. All busbars feature a threephase en
closure throughout the substation.
The GIS Type ELK14 covers mainly single busbar or double busbar.
The busbar conductors of each feeder are mounted on the gastight barrier insulators
that separate the individual feeders. The busbar modules have a telescopic transversal
installation module for easier extensions. A springloaded lateral disconnecting element
in the busbars is used for compensating any pressurerelated forces and changes in
length induced by temperature gradients in long busbars.
The busbar conductors are interconnected by means of contact plugs in any standard
connecting piece. Length variations due to temperature gradients, e. g. between the en
closure and the individual conductors, are compensated in the plugs and will not cause
any mechanical stress on the insulators.
Template: Des_GIS_1HC0045263_AAen 17
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of Installation
it is possible to access the main current path without opening the gas compartment. This
greatly simplifies setting and testing of protection relays, cable testing and locating of
cable faults.
4.3.12 Sectionalization
The GIS contains two different types of gas zones. In the circuit breaker SF6 is used both,
as insulating as well as interrupting medium. In all other gas compartments SF6 serves
for insulation purposes only.
All gas compartments are sectionalized by means of gastight barrier insulators. Each in
dividual gas compartment is equipped with studs for connection of a gas density monitor
and non return gas filling devices. Thus, all maintenance works on the gas compart
ments, such as taking gas samples or regenerating gas, can be performed without any
Template: Des_GIS_1HC0045263_AAen 18
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of Installation
Template: Des_GIS_1HC0045263_AAen 19
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
5.2 Maintenance
Maintenance includes all measures for maintaining the normal condition of installation
parts. These measures comprise:
S Preparation of a maintenance plan
(see section 5.5Timedependent Intervals")
S Preparation for its execution
S Execution
S Reporting
The intervals given should be understood as maxima; the actual intervals are determined
by the operator’s maintenance concept.
5.3 Inspection
Inspection includes all measures for the determination and assessment of the current
condition of installation parts. These measures comprise:
S Preparation of a plan for determining the current condition
(see section 5.5Timedependent Intervals")
S Preparation for the execution
S Execution
S Presentation of the results of determination of the current condition and
S Evaluation of the results of the assessment of the current condition
S Deduction of the necessary consequences based on the assessment.
Template: Maint_1HC0045264_AAen 20
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
5.4 Overhaul
Overhaul includes all measures for restoring the normal condition of installation parts.
These measures comprise:
S Order, job documentation and analysis of the contents of the order
S Planning of the job including an evaluation of alternative solutions and operational
requirements
S Decision on the most favourable solution
S Preparation for the execution, comprising calculation, scheduling, coordination,
making available personnel, means and materials, preparation of working plans
S Preliminary measures such as equipment of workplace, protective and safety instal
lations, etc.
S Review of the preparatory work done and preliminary measures, including release
for execution
S Execution
S Functional test and acceptance
S Notification of completion
S Evaluation including documentation, record of costs, pointing out of improvements
and possibly introduction of the latter.
Template: Maint_1HC0045264_AAen 21
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
General:
Switching devices:
5 Gas density, gas pres Check and if necessary replenish SF6gas Document
sure 1HC0028459
Manual
Manual
5 Gas humidity Carry out dew point measurement Handling
Sulphur
p Hex
fl id
afluoride
5 Percentage Carry out %SF6measurement SF6"
Template: Maint_1HC0045264_AAen 22
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
Installation:
Nonswitching components:
Outdoor flanges
Template: Maint_1HC0045264_AAen 23
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
Loading de ABB recommends a loaddependend interval for overhaul ac 6.1
pendence of cording to the following diagram.
switching cycles
Number of admissible switching operations
10000
1000
Number of switching operations
100
10
0 10 20 30 40 50 60 70
Template: Maint_1HC0045264_AAen 24
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
5.7 Maintenance
5.7.3 Intervals
A list of all necessary maintenance work is shown in Tab.1.
Nonswitching components are largely maintenancefree, however occasional checks
are recommended on the normal rounds.
The procedure for the maintenance work is described in the operating instructions for
the components.
Template: Maint_1HC0045264_AAen 25
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
Template: Maint_1HC0045264_AAen 26
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
5.7.10 Isolating
Template: Maint_1HC0045264_AAen 27
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
Blocking
In order to assure that dielectric faults do not occur through switching overvoltages in
stage 2, blocking of the circuit breaker switching elements is provided. These are as a
rule all items of switching equipment of a GIS installation.
The condition for blocking is that in the affected gas compartment both, stage 1 and
stage 2 have been triggered.
To complement this action, the reset devices of the breakers also block switching ON
operations.
With blocking a certain reduction of availability of the installation is consciously ac
cepted. Protection of the installation is not interconnected with this measure.
Conclusions
The extremely low probability of a fault arising either from isolating too late or from an
instantaneous density drop makes manual isolation the best solution.
Through blocking of the REMOTE and LOCAL control on reaching stage 2, additional
security is obtained with a certain loss of availability. The installation can then only be
operated locally.
Template: Maint_1HC0045264_AAen 28
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
5.8 Overhaul
Safety notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.
Spare parts
The component spare parts are listed in Tab.3Set of spare parts for switchgear and
it’s drives" and Tab.4 Ordering numbers for repair". However, a different set of spare
parts or an extract of the recommended list of spare parts may have been agreed with
the manufacturer.
Template: Maint_1HC0045264_AAen 29
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
Template: Maint_1HC0045264_AAen 30
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul
Template: Maint_1HC0045264_AAen 31
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6 Description of components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid.
Any other application is not envisaged and would not conform to the intended purpose.
Symbol
Nameplate
The installation specific data are given on the nameplate of the circuit breaker ELKSP14.
Template: SP_1HC0045266_AAen 32
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
CLOSING operation
During the closing operation, the circuit breaker operating mechanism causes the oper
ating rod (4) and, as a consequence, the moving parts of the interrupting chamber, such
as the insulating nozzle, the auxiliary nozzle and the puffer cylinder to move in the direc
tion of the fixed contact. Contact is first established through prearcing between the arc
ing contacts, which subsequently enables the main contacts to close at almost zero cur
rent.
OPENING operation
Opening is affected by withdrawing the moving contact in the opposite direction. During
this operation the main contacts are separated prior to the separation of the arcing con
tacts, resulting in the commutation of the current to the arcing contacts.
The energy of the arc and the drive motion cause a pressure increase in the puffer. During
the separation of the arcing contacts a radial gas blast is released through the auxiliary
and insulating nozzles, cooling down the arc and finally extinguishing it at current zero.
The schematic representation in Fig.5 shows the working principle of a single interrupt
ing chamber following the puffing piston principle. View A shows the initial position of
the interrupting chamber in position ON. Contact ring 4 and the contact fingers 2 form
a conducting unit. During an opening operation (View B), the contact ring 4 separates
from the contact fingers 2. The gas volume in the puffing cylinder 7, which is travelling
backwards, is continually reduced through the stationary puffing piston 8 and the pres
sure of the enclosed gas is thereby increased until the arcing finger contacts 6 also sepa
rate from contact pin 1.
As a result of the separation (View C), an electric arc is burning, which creates a further
pressure increase of the gas in the puffer cylinder 7 due to the effect of local heating from
the shortcircuit current. Due to the increased pressure, the compressed gas flows into
the arc zone through the insulating nozzle 3, or in the other direction through the auxiliary
nozzle 5. The flow and the heat conducting ability of the SF6 gas are cooling the electric
arc and it extinguishes at the current zero transition. Views D show the interrupting cham
ber in the fully open position.
Template: SP_1HC0045266_AAen 34
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
A B
C D
9 8 7 5,6 4 3 2 1 D
8 9 7 4 6 5 3 2 1
Template: SP_1HC0045266_AAen 35
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.1.5 Operation
Safety notes
You may only carry out activities listed under Operation" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Operating functions
For more detailed information on operation and control, see operating instructions Con
trol and protection".
Manual operation
Allow sufficient time for the pump to rebuild pressure between operations. Please
Information refer to the operation manual of the operating mechanism Type HMB4.
The manual is available under no. 1HDH118041.
6.1.6 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Intervals
The intervals for maintenance work are given in chapter 5, Maintenance, inspection and
overhaul".
If the maintenance interval has been reached or irregularities are observed in operational
switching, maintenance work shall be carried out.
Maintenance work
The maintenance work on the circuit breaker is limited to protection of the enclosure
against corrosion and checking the number of switching operations. The circuit breaker
must not be shut down for this purpose.
The control module for the hydraulic pump (cf. operating instructions "Control and
protection") is placed in the local control cabinet.
The control module monitors the pump startup time and counts the number of pump
starts, which occur after each switching operation.
Each pump startup is individually detected and counted for each phase. With the pump
starts, the closing operations of the circuit breaker are also counted for each phase.
S Check number of pump starts
S Check number of switching operations.
Template: SP_1HC0045266_AAen 36
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.1.7 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.
Intervals
The intervals for overhaul work are given in chapter 5, Maintenance, inspection and
overhaul".
When the interval has expired, please contact our service department.
For the work to be conducted on overhaul the REVISION INSTRUCTIONS 1HC0030568
has to be referred to.
Template: SP_1HC0045266_AAen 37
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Template: SP_1HC0045266_AAen 38
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid.
Any other application is not envisaged and would not conform to the intended purpose.
Symbol
Nameplate
The installation specific data are given on the nameplate of the disconnector/earthing
switch ELKDE0.
Template: DE0_1HC0045267_AAen 39
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
View x
1 2 2
Template: DE0_1HC0045267_AAen 40
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Insulating rods
Template: DE0_1HC0045267_AAen 41
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
8 5 9 7 10
4 6
EarthingSwitch
2
Disconnector
Template: DE0_1HC0045267_AAen 42
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
1 2
Template: DE0_1HC0045267_AAen 43
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
1 2
Fig.12: Operating mechanism after removal of its cover, switching contact in neutral position
3 2 1 1 2 3
1 − Local manual control (hand crank): Local control with hand crank possible
2 − Interlock (electrically switchable) = Default setting: Local and remote control possible,
control with hand crank not possible
3 − Mechanically and electrically blocked
Template: DE0_1HC0045267_AAen 44
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
3 1 2 4,5
In case of breakdown of control voltage the operation is allowed only for specially
Danger trained personal and can be carried out only with special tools:
As soon as resistance is reached:
a)Remove cover (4) with tool
b)Unlock blocking solenoid (5) by pressing and hold
c)Move handle (2) to position local manual control"
5. After release for the further moving move handle (2) until mechanical end stop for
releasing the hand crank opening (3) completely
6. Insert hand crank in opening (3)
7. Switch disconnector with hand crank in position ON or OFF
8. Turn hand crank until freewheel
9. Remove hand crank
10. Tighten handle (2) and bring into neutral position
11. Pull locking bolt (1) and optional: Fit padlock
12. In case of breakdown of control voltage: Screw the cover (4) back again
13. Put the cover back in place again
Template: DE0_1HC0045267_AAen 45
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
4,5 2 1 3
6 6
In case of breakdown of control voltage the operation is allowed only for specially
Danger trained personal and can be carried out only with special tools:
As soon as resistance is reached:
a)Remove cover (4) with tool
b)Unlock blocking solenoid (5) by pressing and hold
c)Move handle (2) on position local manual control"
5. After release for the further operation move handle (2) until mechanical end stop for
releasing the hand crank opening (3) completely
6. Insert hand crank in opening (3)
7. Switch earthing switch with hand crank ON or OFF
Template: DE0_1HC0045267_AAen 46
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.3.3.2 Locking
It is possible to lock the disconnector/earthing switch electrically and mechanically both,
in the open and in the closed position.
In order to lock the disconnector/earthing switch, the cover must be removed from the
operating mechanism (Fig.12).
After locking the device it can no longer be operated manually with the handcrank.
Information
Disconnector Earthing switch
1 2 2 1
1 − Locking bolt
2 − Handle
Template: DE0_1HC0045267_AAen 47
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.3.4 Operation
Notes
You may only carry out activities listed under Operation" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Operating functions
For more detailed information on operation and control, see the manual for the local con
trol cubicle referred to in document Project Specific Data".
Manual operation
Manual operation of the disconnector/earthing switch ELKDE0 is accomplished via the
drive. The procedure is described in the operating instructions for the operating mecha
nism.
Template: DE0_1HC0045267_AAen 48
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.3.5 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".
If the maintenance interval has been reached or irregularities are observed in operational
switching, maintenance work shall be carried out.
Maintenance work
The maintenance work on the disconnector is limited to protection of the enclosure
against corrosion, whereby it does not need to be shut down. Maintenance can be car
ried out without opening of the gas compartment.
6.3.6 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.
Template: DE0_1HC0045267_AAen 49
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.4 Earthing switch with short circuit making capacity type ELKES0
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
Symbol
Fig.18: Symbols for earthing switch with short ciruit making capacity
Nameplate
The installation specific data are given on the nameplate of the earthing switch with short
circuit making capacity.
Technical data
The installation specific data are given in document Project Specific Data".
Template: ES0_1HC0045269_AAen 50
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
15 14 13 12a 11 10 12b
1 2 3 4 5 6 7 12a 8 9
Fig.19: Operating mechanism and main contacts of earthing switch with short circuit making
capacity
Template: ES0_1HC0045269_AAen 51
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
tion, a torque is produced which acts upon the actuator lever (15) and, consequently,
effects the actual closing operation.
This independent action of the contact system and the spring mechanism is made pos
sible by the slot provided in connecting rod (7). The end positions are determined by
internal stops.
The operating mechanism is decoupled from the gear assembly by means of a free
wheeling mechanism which is effective in both directions.
The alarm switches and the switchposition indicator are actuated through a mechanical
connection (10) to the actuator lever (11). The motor current is cut off by the limit switch
(6). In the case of emergency manual operation the motor circuit is interrupted by the
limit switch (4). All electrical connections are brought out to a coded plug arrangement
(9).
6.4.4 Operation
Notes
You may only carry out activities listed under Operation" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
6.4.5 Interlock
7
2
6
3
4 5
Template: ES0_1HC0045269_AAen 52
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
5
2
4 locked
3
4 unlocked
Template: ES0_1HC0045269_AAen 53
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Fig.22: Operating elements of the earthing switch with short circuit making capacity
With a singlepin layout, the operating elements of the earthing switch with short
Information circuit making capacity are available for each pin.
Template: ES0_1HC0045269_AAen 54
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
2
3 4
Template: ES0_1HC0045269_AAen 55
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.4.6.4 Padlock
1 2
1 − Pin
2 − Padlock
Fig.24: Operating elements of the earthing switch with short circuit making capacity
After the switching position has been locked, the switching device can no longer
Information be actuated with the hand crank.
Template: ES0_1HC0045269_AAen 56
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
cylinder lock
Fig.25: Operating elements of the earthing switch with short circuit making capacity
After the switching position has been locked, the switching device can no longer
Information be actuated with the hand crank.
6.4.7 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Intervals
The intervals for maintenance work are given in chapter 5, Maintenance, inspection and
overhaul".
If the maintenance interval has been reached or irregularities are observed in operational
switching, maintenance work shall be carried out.
Maintenance work
The maintenance work is limited to inspection of the drive system and protection of the
enclosure against corrosion by cleaning if necessary. In addition, the connections and
fixing screws must be periodically checked for loosening and if necessary tightened.
The drive has running time control; in order to test the drive function a switching opera
tion is sufficient.
Template: ES0_1HC0045269_AAen 57
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.4.8 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.
Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".
When the interval has expired, please contact our service department.
Template: ES0_1HC0045269_AAen 58
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
Symbol
The connecting bus does not have a specific symbol.
Nameplate
The connecting bus does not have a specific nameplate.
Technical data
a mm 330 1000
Installation length
b mm 490 2000
a kg 110 + 158/m
Mass
b kg 110 + 132/m
a dm3/m 269
Volume of SF6 gas compartment
b dm3/m 248
Template: CBus_1HC0045277_AAen 59
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
4 6 1 5 8 7 6 1 5
3 7 2 3 4 2
1 − Enclosure 5 − Insulator
2 − Contact support 6 − Pressure relief device
3 − Contact support 7 − Attachment possibility
4 − Conductor 8 − Transversal erection module
Fig.26: Connecting bus short (a), long with or without transversal erection (b)
6.5.2 Description
The connecting bus is a rigid, linear current connector and serves to connect installation
components. Depending on the configuration of the installation, it is installed with fixed
or variable length, horizontally or vertically. For distances longer than the maximum
length, several connecting buses have to be bolted together.
Enclosure (1) of the connecting bus is screwed onto adjacent installation components
with its standard flanges that can be equipped with insulators (5) barrier or support type.
The conductor (4) is supported by the contact support (2).
Length, configuration and number of connecting buses are specified according to the
configuration of the installation. Specific variants of the connecting bus having a rotating
flange or attachment possibilities for e.g. pressure relief device are available
The connecting bus usually forms a common gas compartment with other installation
components.
The insulating medium is SF6 gas.
6.5.3 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have
read and understood the notes; in particular the safety notes at the beginning of
the operating instructions and you fulfil the conditions stated therein. Other
wise, the manufacturer will decline all responsibility for damage caused by im
proper handling.
Maintenance work
The maintenance work on the connecting bus is limited to protection of the enclosure
against corrosion. See details in chapter 5,Maintenance, inspection and overhaul".
Template: CBus_1HC0045277_AAen 60
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.5.4 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read
and understood the notes; in particular the safety notes at the beginning of the
operating instructions and you fulfil the conditions stated therein. Otherwise,
the manufacturer will decline all responsibility for damage or injury caused by
improper handling.
Overhaul work
The connecting bus does not need overhauling.
Template: CBus_1HC0045277_AAen 61
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
Symbol
The elbow element does not have a specific symbol.
Nameplate
The elbow element does not have a specific nameplate.
Technical data
Mass kg 260
Angle ° 90
Template: VW_1HC0045278_AAen 62
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
2 1
1 − Flange 1
2 − Flange 2
6.6.2 Description
The elbow element is a rigid current connection with a 90° angle. It provides two stan
dard flanges to accomplish specific connection purposes.
The elbow element is built on an enclosure with two standard flanges in a 90° angle. The
distance between the flanges and the centre of the connecting piece is within the stan
dard length of the modules or can be prolonged for special requirements. It can be
equipped with different configurations of active parts to connect components in a 90°
angle.
The base insulator on flange 1 supports the currentcarrying parts arranged inside the
housing. Attachments on flange 2 can be chosen according to the required function in
the substation layout.
In general, the elbow element forms a common gas compartment with other installation
components.
The insulating medium is SF6 gas.
6.6.3 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Maintenance work
The maintenance work on the elbow element is limited to protection of the enclosure
against corrosion. See details in chapter 5,Maintenance, inspection and overhaul".
Template: VW_1HC0045278_AAen 63
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.6.4 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Overhaul work
The elbow element does not need overhauling.
Template: VW_1HC0045278_AAen 64
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
Symbol
The T and Xmodule does not have a specific symbol.
Nameplate
The T and Xmodule does not have a specific nameplate.
Technical data
Value
Designation Unit
Tmodule Xmodule
Template: T_X_1HC0045279_AAen 65
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.7.2 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Maintenance work
The maintenance work on the T and Xmodule is limited to protection of the enclosure
against corrosion. See details in chapter 5,Maintenance, inspection and overhaul".
6.7.3 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Overhaul work
The T and Xmodule does not need overhauling.
Template: T_X_1HC0045279_AAen 66
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
Symbol
The splitup with integrated current transformer ELKVY14 does not have a specific sym
bol.
Nameplate
The installation specific data are given on the nameplate of spliup with integrated cur
rent transformer ELKVY14.
Technical data
The installation specific data are given in document Project Specific Data".
Template: VY_1HC0045280_AAen 67
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.8.2 Description
The enclosure 1 and the current transformer support 2 are forming the pressurized GIS
enclosure. The ringcores 3 are integrated inside the gas compartment. During assem
bly, the ringcores are mechanicaly fixed on the current transformer support. The ring
cores are protected by metallic shielding 4 for dielectric reasons and against very fast
transients phenomenons.
The secondary windings are collected in a common terminal box 5. The outer sheet
metal casing protects the windings.
The splitup module is one of the interfaces from the singlephase 6 to the 3phase 7
technology.
The splitup with current transformers ELKVY14 are connected to various types of
protection and measuring equipment and the specific requirements are accordingly
multiple. In principle the splitup with current transformers ELKVY14 can be assigned
to two applications: Measuring and Protection. For both applications, international stan
dards for its accuracy class are defined.
7 5 1 7 4
2 6 3 6 2
Template: VY_1HC0045280_AAen 68
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.8.3 Operation
You may only carry out activities listed under Operation" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Connection / commissioning
Before energizing the primary connector, the following provisions have to be
Warning taken:
S The secondary windings shall be connected for operation to the specified load
S Nonattached cores (e.g. reserve cores) shall be shortcircuited
The secondary wires from the ring cores are connected to the terminals 1 (Fig.30) in the
terminal box 2 (Fig.30). Fig.30 shows the terminal configuration in the terminal box. The
secondary wires are short circuited by the switching bridge 2. The load may be attached
to the second side of the terminals 1.
The earth connection screws 5 on the terminals 1 have to be loosened when a load has
been connected.
3 5
1 2
Template: VY_1HC0045280_AAen 69
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Operation
Secondary windings must either be loaded as specified or shortcircuited! A sec
Warning ondary circuit may never be open!
Operation with open secondary circuit (e.g. open secondary terminals) causes
overvoltages hazardous to personal and thermally damaging of the transformer
cores.
Procedure for changing loads or transformer ratio during operation:
S Short circuit and earth the affected core by fastening the corresponding earth con
nection screws 5 (Fig.30)
S Change the connecting cable to the universal terminals 1 (Fig.30)
S Loose the earth connection screws 5 (Fig.30)
Operating functions
For more detailed information on operation and control, see operating instructions Con
trol and protection".
6.8.4 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Maintenance work
The maintenance work on the splitup with current transformers ELKVY14 is limited to
protection of the enclosure against corrosion and periodic cleaning. See details in chap
ter 5,Maintenance, inspection and overhaul".
In addition, the connections and fixing screws must be periodically checked for loosen
ing and if necessary tightened.
6.8.5 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, all regulations have to
be followed. With improper treatment, reliable operation of the installation is not assured.
Overhaul work
The splitup with current transformers ELKVY14 does not need overhauling.
Template: VY_1HC0045280_AAen 70
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
Symbol
The end cover does not have a specific symbol.
Nameplate
The end cover does not have a specific nameplate.
Technical data
Template: EndCover_1HC0045281_AAen 71
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
3
1 2 1
6.9.2 Description
The end cover serves as a cover to shut gas compartments tightly. It is employed in differ
ent sizes and shapes as:
S Cover without attachment option
S Cover with attachment option
The end cover with attachment option can be equipped with the following components:
S Density monitor ELKWT14
S Pressure relief device
S Housing attachments, such as gas connection, blind cover, indicator glass
6.9.3 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Maintenance work
The maintenance work on the end cover is limited to protection of the enclosure against
corrosion. See details in chapter 5,Maintenance, inspection and overhaul".
6.9.4 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Overhaul work
The end cover does not need overhauling.
Template: EndCover_1HC0045281_AAen 72
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
Symbol
The density monitor ELKWT14 do not have a specific symbol.
Nameplate
The installation specific data are given on the nameplate of the density monitor ELK
WT14.
Technical data
The installation specific data are given in document Project Specific Data".
Mass kg 1.1
Template: WT_1HC0038827_AAen 73
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
1 2 3 4
6 5
1 − Indicator 4 − Transparent enclosure
2 − Sealing 5 − Cable connection
3 − Enclosure 6 − Terminals
6.10.2 Description
The density monitor ELKWT14 monitors the gas density of the SF6 installation part and
compares it with that of the gas in a closed reference gas compartment. If the density
drops below the set value in each case (warning, alarm, blocking), the mutually indepen
dent micro switch contacts close.
The density monitor ELKWT14 is available in the following versions:
S without outdoor hood for indoor version
S with outdoor hood for outdoor version
Depending on the version, density monitors ELKWT14 with are equipped 2 or 3 con
tacts.
Pressure comparison is provided by a metal bellow, which separates the SF6 gas
compartment of the installation from the reference gas compartment. The movement of
the bellows actuates microswitches via operating rod. The microswitches trigger the
relevant indications through different switching points.
Microswitches are connected to the plug contacts via a PCB. Plug contacts are coded
and cannot be interchanged inadvertently.
The movement of operating rod is indicated via a meter movement on a display visible
from the outside. As long as the pointer remains in the GREEN range of the scale, the
gas density is adequate. The transition GREENRED is set to the lowest switching point
(alarm).
The density monitor ELKWT14 has the following characteristics:
S high shock resistance
S no false alarms at low temperatures
S up to three mutually independent, galvanically separated circuits
Template: WT_1HC0038827_AAen 74
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.10.3 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".
Maintenance work
Maintenance of the density monitor ELKWT14 is limited to testing the switching points
of the microswitches by means of the portable tester.
Removal
S Switch off control voltage
S Remove outdoor hood (if present).
S Release socket head screws and swing open cast hood.
S Pull off plug contacts. The plug contacts are provided with a coding pin and hence
cannot be interchanged inadvertently (cast hood with control cable remains on the
installation).
S Release coupling ring. Grip density monitor ELKWT14 firmly and pull off carefully,
since the residual pressure between pressure connection and gas connection is re
lieved.
S Protect gas connection from damage and environmental influences by screwing on
sealing cap.
S Check switching points of microswitches with portable tester for density monitor
ELKWT14.
Installation
S Insert new sealing rings.
S Remove sealing nut.
S Introduce pressure connection carefully into gas connection.
S Fix density monitor ELKWT14 with coupling ring in original position.
S Insert plug contacts according to coding.
S Fix cast hood with socket head screws to the baseplate.
S Assemble outdoor hood (if present).
S Switch on control voltage.
Template: WT_1HC0038827_AAen 75
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.10.4 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Overhaul work
The density monitor ELKWT14 does not need overhauling.
Template: WT_1HC0038827_AAen 76
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
Symbol
The pressure relief device ELKXA14 does not have specific symbol.
Nameplate
The installation specific data are given on the nameplate of the pressure relief device
ELKXA14.
Technical data
The installation specific data are given in document Project Specific Data".
Triggering precision % ± 10
Mass
Adsorber
Type 5A 8/2
Template: XA_1HC0038828_AAen 77
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.11.2 Description
The pressure relief device ELKXA14 has the task of initiating pressure relief if the gas
pressure in the gas compartments rises above the permitted pressure value. An increase
of gas pressure may be caused by an internal arc fault but never during normal operation
of the switchgear.
On reaching the bursting pressure, the pressure relief device ELKXA14 is destroyed at
its predetermined triggering point and the SF6 gas is relieved.
Template: XA_1HC0038828_AAen 78
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
SF6 gas. In some gas compartments e.g. in the circuit breaker ELKSP14 the adsorber
material may be placed in different containers.
Adsorber
An adsorber 5 is installed in any gas compartment to withdraw moisture from the SF6
gas. Moisture in the SF6 gas may origin from diffusion into the gas compartment or mois
ture of built−in components. The adsorber material is enclosed in a filter cage.
6.11.3 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".
Maintenance work
The maintenance work on the pressure relief device is limited to protection of the hous
ing against corrosion, and checking the protective plate. Maintenance can be carried out
without opening of the gas compartment.
6.11.4 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.
Intervals
The intervals for overhaul work are summarized in the operating instructions for the
installation in the form of a table. On expiry of the interval, please contact our service de
partment.
S During overhaul work in the gas compartment, the adsorber must be replaced
S In case of damage, the complete pressure relief device is replaced
Template: XA_1HC0038828_AAen 79
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Before starting overhaul work, the part of the installation affected must be shut
Danger down and made safe according to the operating instructions for the installation.
The gas pressure in adjacent gas compartments must be lowered. See operating in
structions for the installation, document 1HC0028459 Manual Handling Sulphur Hexa
fluoride SF6".
Regeneration of the adsorber material is theoretically possible, but not intended.
Information
Procedure
1. Take safety precautions.
2. Empty decomposition products into bucket and note volume.
3. Pour contents of bucket into flask using funnel.
4. Fill bucket with 1.5 times the amount of water and determine weight.
5. Weigh out 250 g calcium chloride hexahydrate per kg water.
6. Pour water stepwise into flask and then allow cooling (on addition of water, the solu
tion heats up and foams).
7. Add calcium chloride hexahydrate to the flask to neutralize and allow standing for
24 hours. Then close the flask tightly with the cap.
Template: XA_1HC0038828_AAen 80
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
8. As a personal protective measure: wash face, neck, arms and hands with soap and
copious amounts of water.
Assembly
Adsorbers are dispatched and stored in special packing. Before assembly, check
Caution the enclosed humidity indicator for color changes (see instructions for storage).
After assembly of the adsorber, the gas compartment must be evacuated within two
hours.
The unlimited operation of the installation requires the observance of the specified oper
ating materials. The operating materials and any additional measures are marked with
capital letters in brackets and explained in the instructions for treatment. As a general
rule, use only new seals.
Corrective maintenance
The components treated in these operating instructions require no special measures of
corrective maintenance.
Checks based upon intervals are, however, indispensable for those parts of the installa
tion, which are not monitored, e.g earthing connections or flange connections. See the
operating instructions for the installation.
Template: XA_1HC0038828_AAen 81
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Barrier Insulators
The GIS type ELK14 is sectionalized into individual gas compartments by means of gas
tight barrier insulators. Therefore, the impact of extensions or internal faults on the overall
installation is reduced to a minimum and control, supervision and maintenance are
greatly eased. All flange connections are sealed by means of ageresistant Orings. Due
to the gastight design of the insulator no gas leakage between components can occur.
Support Insulators
Support insulators are used to mechanically support the conductors. They are mainly
used for long SF6 busduct connections. Fig.36 shows both types of insulators.
1 2 6 1 2 3 4 5 6
1 2 3 4 6 1 3 2 4 5 6
2
2 2
2
1 − Insulator 4 − Bolts
2 − Inner armature 5 − Through holes
3 − Outer armature 6 − Groove for gaskets
Intermediate rings
Intermediate rings are used to connect two standard flanges if no insulator is present.
It provides the same dimensions and sealing systems as the insulators but does not sup
port the conductor or other active parts inside.
Template: Insul_1HC0045283_AAen 82
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
The bushing can be attached to the following component:
S Air splitup
Symbol
The bushing with composite insulator type ELKHB14 does not have a specific symbol.
Nameplate
The installation specific data are given on the nameplate of the bushing ELKHB14.
Technical data
The installation specific data are given in document Project Specific Data".
Template: HB_1HC0045284_AAen 83
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6
2
3
6.13.2 Description
Bushings ELKHB14 serve as links for the current transfer between the gasinsulated
switchgear and the airinsulated components of the openair transmission line. They
have the task of transferring the current with low losses and simultaneously of ensuring
the dielectric strength both in the gas compartment and in the air under the most extreme
environmental conditions.
Template: HB_1HC0045284_AAen 84
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
The bushing (1) consists of a conductor tube (2) that transmits the current from contact
support (3) via the rigidly connected upper flange (4) to the current connection (5) (stan
dard is a pin). Here, connections to the open air can then be connected directly or via
an adapter.
The two shield electrodes (6) and (7) are used to control the electrical field. The glass
fibre reinforced tube (8) is used for mechanical and dielectric stability. The silicone shield
(9) mounted on it guarantees the electrical air insulation such as clearance and creep
age and also provides optimal protection against environmental influences such as ex
treme contamination and salt fog.
The bushing ELKHB14 with composite insulating Fig.37 is a gasinsulated bushing in
accordance with IEC 60137.
On account of the simplicity of its design, the bushing ELKHB14 is maintenancefree.
The bushing ELKHB14 includes a control electrode (7) for field grading in the transition
between the bottom flange and outside air. Therefore no measuring adapter is assigned.
The current connector (5) is round and is made of aluminium.
As a protection against corrosion, all flange joints and other sealing positions to the gas
compartment are coated with grease through lubricating nipples.
6.13.3 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".
Maintenance work
The maintenance work of the bushing ELKHB14 is limited to protection of the enclosure
against corrosion. Maintenance can be carried out without opening of the gas compart
ment.
6.13.4 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.
Overhaul work
The bushing with composite insulator ELKHB14 does not need overhauling.
Template: HB_1HC0045284_AAen 85
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
Symbol
Voltage transformer ELKPI04 does not have a specific symbol.
Nameplate
The installation specific data are given on the nameplate of the voltage transformer
ELKPI04.
Technical data
The installation specific data are given in document Project Specific Data".
Template: PI_1HC0045285_AAen 86
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
8
View “A” 1 A
9
5
3 2 4
6 7
6.14.2 Description
Inductive voltage transformers are low power transformers in which the secondary volt
age is proportional to and in phase with the primary voltage for all practical purposes.
The voltage transformer of the GIS transforms the network voltage to be measured into
a secondary voltage that can be fed to measuring and protective devices. At the same
time, the primary and the secondary windings are galvanically separated from each
other.
The inductive voltage transformer type ELKPI04 (Fig.38) complies with the relevant
IEC and IEEEstandards. Usually it has two secondary windings and one auxiliary wind
ing for earth fault detection. The ratings are projectspecific.
The inductive voltage transformer is a sealed gas compartment (6) with two gas connec
tions (4), an SF6 gas moisture filter and a bursting disc assembly (3). The terminal box
(1) attached to the side wall of the enclosure accommodates wiring, terminals and fuses.
The inductive voltage transformer is delivered filled with SF6 at a pressure of
Caution 150 kPa. Do not evacuate!
Template: PI_1HC0045285_AAen 87
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Gas compartments
During connection or commissioning work, gas compartments must be opened and en
tered. For this, the regulations in document 1HC0028459 Manual Handling Sulphur
Hexafluoride SF6" have to be executed. Before reassembling the affected components,
the regulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6"
have to be followed. With improper treatment, reliable operation of the installation is not
assured.
1
1 − Connection flange
2 − Barrier insulator
3 − Gas fitting
Template: PI_1HC0045285_AAen 88
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
3 2
1
Template: PI_1HC0045285_AAen 89
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.14.5 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".
Maintenance work
The maintenance work of the voltage transformer ELKPI04 is limited to protection of the
enclosure against corrosion. Maintenance can be carried out without opening of the gas
compartment.
Template: PI_1HC0045285_AAen 90
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.14.6 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6"have to be followed.
With improper treatment, reliable operation of the installation is not assured.
Overhaul work
The voltage transformer ELKPI 04 does not need overhauling.
Template: PI_1HC0045285_AAen 91
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
The exit splitup ELKHKY14 can be attached to various components.
Symbol
The exit splitup ELKHKY14 and cable connection ELKHK14 do not have a specific sym
bol.
Nameplate
The exit splitup ELKHKY14 and cable connection ELKHK14 do not have a specific
nameplate.
Technical data
The installation specific data are given in document Project Specific Data".
Tab.16: Technical data for exit splitup ELKHKY14 and cable connection ELKHK14
Template: HK_1HC0045286_AAen 92
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
1 5
5
5
6.15.2 Description
The exit splitup ELKHKY14 and the cable connection ELKHK14 provides an interface
between a gasinsulated switchgear and a highvoltage cable. It is built of an ELKHKY14
dividing piece with active parts, an enclosure specifically designed to hold the cable con
nection enclosure and a base plate. The base plate is removed onsite when inserting
the cable.
The scope of supply includes all items of the cable sealing end and all necessary mount
ing parts but not the cable itself (No.4 in Fig.43).
Before commencing mounting all delivered parts should be checked for completeness
and signs of damage. Any damaged parts must be replaced.
The maximal mechanical force transversal during mounting work and during op
Caution eration, must not exceed 2000 Nm.
The handling of insulator surfaces, Orings, sealing nuts and sealing surfaces is
Information described in detail in chapter 8Installation of GIS".
Due to the variety of cable suppliers, there are different types of cable connection ELK
HK14 available. Each type needs specific work to be conducted during installation.
Template: HK_1HC0045286_AAen 93
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.15.4 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.
Intervals
The intervals for maintenance work are given in chapter 5Maintenance, inspection and
overhaul".
Maintenance work
The maintenance work on the exit splitup ELKHKY14 and cable connection ELKHK14
is limited to protection of the housing against corrosion. Maintenance can be carried out
without opening of the gas compartment.
Template: HK_1HC0045286_AAen 94
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components
6.15.6 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.
Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in chap
ter document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be fol
lowed. With improper treatment, reliable operation of the installation is not assured.
Overhaul work
The exit splitup ELKHKY14 and cable connection ELKHK14 do not need overhauling.
Template: HK_1HC0045286_AAen 95
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Transport, Storage and Treatment
This chapter provides information on transport, storage and treatment of GIS equip
ment.
Packaging requirements
The following factors must be taken into account when packaging equipment for ship
ping:
S stresses occurring during multiple transhipments
S climatic conditions
S shipping routes
S duration of shipment (preservation, environmental factors)
S storage after shipment
S bottoms of containers must be designed to carry the full load of the package equip
ment
S packaging must be able to withstand stresses caused by weight and by forces oc
curring during transportation
S packaging must be geared to the intended type of transportation and designed to
preclude any damage to the equipment
S packaging / equipment may be provided with shock indicators
Wooden box
S For shipment by truck, rail or ship
S Suitable for storage
Container
S For shipment by truck, rail or ship
S Suitable for storage
Types of container
S Not specified.
Template: Tr_1HC0024456_AAen 96
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Transport, Storage and Treatment
S Containers must be checked for proper technical condition prior to shipment (Con
tainers provided with the ACEP mark have been inspected by the manufacturer)
Container data
Container data concerning weight and dimensions should, as far as possible, be geared
to the related data for the intended means of transportation.
Environmental factors
Equipment may be shipped at temperatures in the range of −30 °C to +60 °C. The pack
aging must ensure that all items of equipment are positively protected against any direct
contact with water. The packing shall provide adequate protection against dirt, insects
and animals.
Preservation
The shipment within Europe, specifications concerning equipment preservation shall be
included in the order. If no preservative measures are specified, the freight will be pack
aged in the usual manner.
The preservation required depends on the method of transportation, the storage classifi
cation and the storage period.
Storage requirements and classifications are described in detail in document
HASV600715 Corrosion Protection and Sealing".
In the case of ocean transport, preservation of the equipment is mandatory, since ELK14
components could be damaged by the associated exposure to humidity.
Protection against condensation of humidity is provided for a transportation period of
up to 12 months. If this period is exceeded, adequate measures must be taken to prevent
the formation of condensation water.
The packaging may be monitored by means of moisture indicators.
If the expiry date of equipment preservation falls within the period before or during ship
ment, or within the expected storage period, persons responsible for shipment / storage
shall be informed in due time so that appropriate measures can be taken.
Sealing of equipment
For transportation the equipment is filled with N2 to a absolute pressure of 150 kPa.
The gas pressure shall not drop below 110 kPa during shipment and storage.
All open flanges must be sealed with a shipping cover.
Shipping covers are chosen according to 1HC0021062.
Securing of equipment
Freestanding parts shall be provided with appropriate support structures.
All loads shall be prevented from slipping by lashing and blocking. Means of securing
equipment in place: Chains, lashes, ropes, square timber and wooden wedges.
Make sure that loads are evenly distributed.
The sidewalls of shipping containers shall not be subjected to any loads. Only container
bottoms are designed to withstand loading and possess sufficient stability.
The circuit breaker shall be shipped only in its upright (operating) position.
Template: Tr_1HC0024456_AAen 97
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Transport, Storage and Treatment
Shipping marks
Markings provided on the packaging shall include fixing and hitching points for trans
portation and hoisting, total weight, installation point of equipment components, and the
packed unit’s centre of gravity.
The place of delivery shall be marked on the packaging in accordance with the data pro
vided in the order.
When dangerous goods are shipped, applicable regulations (of the countries of origin
and destination as well as transit countries) shall comply with.
Means of transportation
The means of transportation is selected so as to ensure that the shipping units will be
subjected to the smallestpossible amount of vibration. Any damage to the equipment
must be prevented by all means.
FV
direction
FL FV FQ
Template: Tr_1HC0024456_AAen 98
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Transport, Storage and Treatment
Before shipment
Prior to closing the shipping containers, make sure that the equipment to be shipped is
properly secured and without damage.
Check shipping containers for proper technical condition. This is particularly important
in the case of freight containers.
After shipment
Check shipping container for any damage before opening.
After opening a container, immediately check the equipment for external damage and
completeness.
During shipment
Any damage occurring on the packaging in transit shall, as far as possible, be repaired
immediately. If this cannot be done, appropriate measures shall be taken at once to pre
clude any further damage to the cargo.
All irregularities occurring during shipment as well as any remedial action taken shall be
documented and reported see form Receiving inspections" below.
After shipment
In the event of any damage detected on the packaging or equipment, the insurance
company should be called in and the damage should be assessed and recorded by an
authorized agent.
Photographs should be taken of any damaged packaging to serve as evidence at a later
time.
Any packaging that is damaged or soaked shall under no circumstances be used for pro
longed storage of equipment.
Any corrective action taken with regard to packaging or equipment preservation shall
be recorded in detail. All materials used for these measure must have been tested and
approved.
Template: Tr_1HC0024456_AAen 99
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Transport, Storage and Treatment
These regulations, guidelines, instruction sheets and the relevant standards must be
equally observed.
Standards and regulations of the country of destination shall be considered, if applica
ble.
Applicable regulations and guidelines issued by ABB shall also be observed.
8 Installation of GIS
These instructions refer to the installation of a GIS and to all works that require opening
a gas compartment.
All the relevant instructions for safety and accident prevention as given in chapter
Warning 3 Information and Safety Notes" must be observed during the installation works.
It must be possible to clean the shoes before entering the immediate working area. The
working clothes must be made of nonfluffing material.
Power supply
The following power supply outlets must be made available in the installation area:
S 1phase AC outlets (16 A) and
S 3phase AC outlets (16 A)
Floor conditions
S The floor in the installation area must have a firm surface
S It must be possible to keep the floor dustfree with a vacuum cleaner
Outdoor installation
S In case of an outdoor installation of the GIS or of GIS components, open gas
compartments must be protected from the entry of dust or humidity (e. g. by means
of installation covers, tarpaulins etc.)
8.1.1 Cleaning
SF6 can loose its arc quenching and insulating properties when contaminated. For
Caution this reason, all surfaces and components that will be in contact with SF6 have been
thoroughly cleaned in our factory and have been installed under conditions of ut
most cleanliness. When working on open devices or gas compartments, avoid the
entry of or contact with dirt, sweat and humidity at any time.
Water, acid contamination and oxygen (especially when simultaneously present) can
cause corrosion that might have a negative impact on the mechanical function of the GIS
components.
Water, especially when combined with acid contamination, can reduce the dielectric
strength of the GIS due to condensation at low operating temperatures and high pres
sure. For this reason, the degree of contamination has to be limited to a level that corro
sion and/or condensation are of no significance.
Installation area
Prior to opening a gas compartment, thoroughly clean and vacuum clean the installation
area, especially in the immediate vicinity of the flanges to be connected. Avoid dust dis
turbance in the installation area.
Rub the insulators and all Teflon parts with a cloth moistened with a suitable clean
Caution ing agent. Cleaned insulators may only be touched wearing disposable latex
gloves. Do not use water for cleaning under any circumstance!
S Moisten the cloth so that the cleaning agent does not drip or spill
S Remove residues of the cleaning agent with a clean cloth
Sealing surfaces
S Check sealing surfaces for scratches or similar damages
S Even out any scratches with fine sand paper
S Remove the dust with a vacuum cleaner
S Clean the sealing surfaces
Orings
Orings have to be cleaned before they are installed, see document HASV600715 Cor
rosion Protection and Sealing".
Do not install any Orings that show damages or deformation from previous use.
Before closing a flange connection, clean the immediate vicinity and all accessible parts
of the components to be connected with a vacuum cleaner. Do not touch the active parts
and the insulators with the vacuum cleaner’s nozzle.
Tightening torque in Nm
Thread
Steel/8.8 *) Steel/A270 **) Aluminium ***)
M4 2,9 − 1,5
M5 6 5,2 3
M6 10 7,8 5,5
M8 25 19,5 14
M10 49 38,3 26
M12 86 67,2 45
Transport units
All gas compartments are delivered ex works filled with N2 at a pressure of approximately
150 kPa. The exception from this rule is the inductive voltage transformer which will be
delivered ex works filled with SF6 at a pressure of approximately 150kPa.
The enclosures of inductive voltage transformers may not be opened or evacuated
Caution without the prior consent of the manufacturer!
After the installation of the GIS, the gas compartments are initially filled up to a pressure
of 150 kPa only in order to check for gas tightness. The GIS must not be filled with SF6
up to its rated filling pressure before all installation works have been completed.
The installation of the GIS earthing and the earthing leads shall be strictly in ac
cordance with the projectspecific earthing layout diagrams and the earthing
plans in the projectspecific part of this documentation!
9 Troubleshooting
In this chapter, some advices for quick onsite troubleshooting are provided. Practical
experience has shown that strict adherence to the recommendation of this instructions
will ensure the best proceed to restore the function of the switchgear.
These instructions are based on the present technical design. ABB reserves the right to
make any technical changes.
If an existing problem is not identified by the reasons given below or cannot be solved
by applying the remedial measures, please contact our service department.
Motor is running but the disc spring as Pressure release screw in the position Close the pressure release screw
sembly is not tensioned open"
Changeover valve in intermediate Press the rubber cap of the OPEN
position (only HMB1 and HMB1S) solenoid
Pump defective Replace the pump
Oil level too low Refill the oil
Filter clogged Exchange the filter
Operating mechanism does Tripping voltage lacking Secure the tripping voltage
not trigger Coil defective Replace the coil
Auxiliary switch does not transmit the Adjust the auxiliary switch
command
Auxiliary switch defective Replace the auxiliary switch
Corrosion in the operating mechanism Heating MCB* tripped Switch the MCB* on
housing Heating voltage lacking Secure the heating voltage
Heating plate defective Replace the heating plate
Mechanism housing not tight Check the seals of the operating
mechanism housing and if necessary
replace them
Operating mechanism too often Pressure release screw not in the Close the pressure release screw
repumps position closed"
(On an average more than Internal leak Operate the operating mechanism
20 times per day / 600 times several times
per month)
If the trouble continues: Perform the leak
test and if necessary inform ABB.
9.7.1 Temperature
0° 32 ° 273.16
15 ° 59 ° 288.16
20 ° 68 ° 293.16
25 ° 77 ° 298.16
30 ° 86 ° 303.16
*n °C = ( 1.8 x n + 32) °F
**n K = n − 273.16 °C
Tab.27: Temperature
1 0.7376 0.102
1.356 1 0.1383
9.807 7.233 1
9.7.4 Force
1 0.22481
4.4482 1
Tab.30: Force
9.7.5 Length
mm (Millimeter) in (Inches)
1 0.03937
25.4 1
Tab.31: Length
9.7.6 Weight
Tab.32: Weight
9.7.7 Volume
Tab.33: Volume
10 Customer Comments
Dear Customer,
We are permanently looking to further improve the quality of our documentation. For this
reason, we are very much interested in your feedback. Please take the time to fill in the
form below if you notice any incomplete or omitted information, or in case you encounter
typographical errors. Please feel free to make any suggestions how we could further im
prove this documentation to your benefit.
Please find our contact address in the product manual in chapter 1.2
Information
Your comments:
Document
Page_____
V
Typographical Error
V
Incomplete Information
V
Omitted Information
V
Amendment
V
Your comments:
Document
Page_____
V
Typographical Error
V
Incomplete Information
V
Omitted Information
V
Amendment
V
Customer ...........................................................................
Installation ...........................................................................
Person in Charge ...........................................................................
Street/P.O. Box ...........................................................................
Town, Postal Code ...........................................................................
Country ...........................................................................