You are on page 1of 112

Operating Instructions

SF6Gas Insulated Switchgear ELK14

Name of the Installation

1HC0044810 E01 / AA06

Example 3D view
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Content

Content

1 Notes on the Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9


1.1 Supplier and Manufacturer Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.2 Contact Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.3 Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.4 Validity of this document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.5 Purpose of the Operating Instructions SF6Gas Insulated Switchgear
ELK14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.6 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

2 Typographical Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1 Typographical Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.1 References to other Documents . . . . . . . . . . . . . . . . . . . . . . 10
2.1.2 References to Chapter or Sections of the Current
Document . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.3 Document Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.4 Colours in Pictures in this Manual . . . . . . . . . . . . . . . . . . . . 10
2.1.5 Contents of Header and Footer . . . . . . . . . . . . . . . . . . . . . . 11

3 Information and Safety Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12


3.1 Target Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1.1 Definition of qualified personnel: . . . . . . . . . . . . . . . . . . . . 12
3.2 Safety Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2.1 Read Obligation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2.2 How to cope with Problems . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2.3 Application of ELK14 Switchgear . . . . . . . . . . . . . . . . . . . . 12
3.2.4 Using the Operating Instructions . . . . . . . . . . . . . . . . . . . . . 12
3.2.5 Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2.6 Limitation of Subject . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2.7 Working Safety Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.8 Safety Notes for Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.9 Safety Notes for Maintenance and Overhaul . . . . . . . . . . . 13
3.2.10 Operating Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.11 Key Blocking System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3 Safety Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3.1 Symbols and Texts of Particular Importance . . . . . . . . . . . 14
3.4 Notes on Heaters in Drives and Control Cubicle . . . . . . . . . . . . . . . . . . . 15

4 Description of installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.1 Metalenclosed Gas Insulated Switchgear (GIS) . . . . . . . . . . . . . . . . . . . 16
4.1.1 Advantages of the GIS technology . . . . . . . . . . . . . . . . . . . 16
4.1.2 General structure of a GIS . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.2 General structure of the components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3 Short description of the components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3.1 Busbar . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3.2 Circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3.3 Circuit breaker operating mechanism . . . . . . . . . . . . . . . . . 17
4.3.4 Combined disconnector / earthing switch . . . . . . . . . . . . . 17
4.3.5 Cable termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3.6 Earthing switch with short circuit making capacity . . . . . . 18
4.3.7 Barrier insulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3.8 Support insulators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Template: Inhalt 2
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Content

4.3.9 Current and voltage transformers . . . . . . . . . . . . . . . . . . . . 18


4.3.10 Voltage transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3.11 SF6air bushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3.12 Sectionalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3.13 Local control cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

5 Maintenance, inspection and overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . 20


5.1 Definitions and measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.3 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5.4 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.5 Timedependent intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.6 Loaddependent intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.7.1 Safety notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.7.2 Maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.7.3 Intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.7.4 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.7.5 Spare parts for overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.7.6 Spare parts for repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.7.7 Nonswitching components . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.7.8 SF6 gas monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.7.9 Abnormal gas losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.7.10 Isolating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.8 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.8.1 Shutting down and making safe parts of the installation . 29
5.8.2 Execution of overhaul work . . . . . . . . . . . . . . . . . . . . . . . . . . 30

6 Description of components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.1 Circuit breaker type ELKSP14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.1.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.1.2 Circuit Breaker Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.1.3 Operating principle of the interrupter unit . . . . . . . . . . . . . . 34
6.1.4 Operating diagram for circuit breaker with singlepole
operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.1.5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.1.6 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.1.7 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.1.8 Overhaul work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.2 Circuit breaker operating mechanisms type HMB4 . . . . . . . . . . . . . . . . 38
6.3 Disconnector/earthing switch type ELKDE0 . . . . . . . . . . . . . . . . . . . . . . . 39
6.3.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.3.2 Disconnector/earthing switch design . . . . . . . . . . . . . . . . . 40
6.3.3 Operating mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
6.3.3.1 Manual operation (control voltage present) . . . . . . . . . . . . 43
6.3.3.2 Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
6.3.4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
6.3.5 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.3.6 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.3.7 Overhaul work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
6.4 Earthing switch with short circuit making capacity type ELKES0 . . . . 50
6.4.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
6.4.2 Design of earthing switch with short circuit making
capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Template: Inhalt 3
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Content

6.4.3 Operating Mechanism (Fig.19) . . . . . . . . . . . . . . . . . . . . . . 51


6.4.4 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.4.5 Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
6.4.5.1 Crank interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.4.5.2 Switch position lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.4.6 Manual local control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
6.4.6.1 Manual control (control voltage present) . . . . . . . . . . . . . . 54
6.4.6.2 Manual control (control voltage absent) . . . . . . . . . . . . . . . 55
6.4.6.3 Position interlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.4.6.4 Padlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.4.6.5 Cylinder lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.4.7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.4.8 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
6.5 Connecting bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.5.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.5.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
6.5.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
6.5.4 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
6.6 Elbow element ELKVW14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
6.6.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
6.6.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
6.6.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
6.6.4 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
6.7 T and XModule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6.7.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
6.7.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
6.7.3 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
6.8 Splitup with integrated Current Transformer ELKVY14 . . . . . . . . . . . . . 67
6.8.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
6.8.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
6.8.3 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
6.8.4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
6.8.5 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
6.9 End cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
6.9.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
6.9.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
6.9.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
6.9.4 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
6.10 Density monitor ELKWT14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
6.10.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
6.10.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
6.10.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
6.10.4 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
6.11 Pressure relief device ELKXA14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
6.11.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
6.11.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
6.11.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
6.11.4 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
6.11.5 Overhaul work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
6.12 Barrier and support insulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
6.13 Bushing with composite insulator type ELKHB14 . . . . . . . . . . . . . . . . . . 83
6.13.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
6.13.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

Template: Inhalt 4
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Content

6.13.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
6.13.4 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
6.14 Voltage transformer ELKPI04 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
6.14.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
6.14.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
6.14.3 Connection / commissioning . . . . . . . . . . . . . . . . . . . . . . . . 87
6.14.4 Feeder Module with integrated Disconnector/Earthing
Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6.14.5 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
6.14.6 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
6.15 Exit splitup ELKHKY14 and cable connection (IEC) ELKHK14 . . . . . . 92
6.15.1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
6.15.2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
6.15.3 Connection / commissioning . . . . . . . . . . . . . . . . . . . . . . . . 94
6.15.4 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6.15.5 Maintenance work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6.15.6 Overhaul . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

7 Transport, Storage and Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96


7.1 Transport of GIS equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
7.1.1 Packaging of GIS equipment . . . . . . . . . . . . . . . . . . . . . . . . 96
7.1.2 Types of packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
7.1.3 Shipping of GIS equipment . . . . . . . . . . . . . . . . . . . . . . . . . . 98
7.1.4 Inspections to be carried out on equipment . . . . . . . . . . . 99
7.1.5 How to cope with irregularities . . . . . . . . . . . . . . . . . . . . . . . 99
7.1.6 Receiving Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

8 Installation of GIS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102


8.1 Preparation of the installation area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
8.1.1 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
8.1.2 Flange connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
8.1.3 Tightening torque for bolts . . . . . . . . . . . . . . . . . . . . . . . . . . 105
8.2 Filling of gas compartments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
8.3 Earthing of GIS equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

9 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
9.1 Hydraulic operating mechanism of circuitbreaker . . . . . . . . . . . . . . . . . . 107
9.2 Circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
9.3 Disconnector / earthing switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
9.4 Earthing switch with short circuit making capacity . . . . . . . . . . . . . . . . . . 108
9.5 Voltage transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
9.6 Other switchgear modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
9.7 Conversion Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
9.7.1 Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
9.7.2 Tightening Torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
9.7.3 Absolute Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
9.7.4 Force . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
9.7.5 Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
9.7.6 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
9.7.7 Volume . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

10 Customer Comments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112

Template: Inhalt 5
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
List of Figures

List of Figures

Fig.1: Contents of the Header and the Footer on each Page of the
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Fig.2: Overhaul flow chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fig.3: Symbol Circuit Breaker ELKSP14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Fig.4: Circuit breaker ELKSP14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Fig.5: Functional principle of the interrupting chamber during opening
operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Fig.6: Symbols for disconnector and earthing switch ELKDE0 . . . . . . . . . . . . 39
Fig.7: Disconnector/earthing switch ELKDE0 . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Fig.8: Disconnector/earthing switch integrated in the busbar module
(neutral position) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Fig.9: Insulating rods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Fig.10: Operating mechanism of the combined disconnector/earthing
switch ..................................................... 42
Fig.11: Operating mechanism with cover, switching contact in neutral
position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Fig.12: Operating mechanism after removal of its cover, switching contact in
neutral position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Fig.13: Switching positions of handle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Fig.14: Possible combinations of positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Fig.15: Operating elements disconnector (front view) . . . . . . . . . . . . . . . . . . . . . 45
Fig.16: Operating elements earthing switch (front view) . . . . . . . . . . . . . . . . . . . 46
Fig.17: Operating elements disconnector and earthing switch (front view) . . . 47
Fig.18: Symbols for earthing switch with short ciruit making capacity . . . . . . . . 50
Fig.19: Operating mechanism and main contacts of earthing switch with short
circuit making capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Fig.20: Combined crank handle/finalposition interlock . . . . . . . . . . . . . . . . . . . 52
Fig.21: Switch position lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Fig.22: Operating elements of the earthing switch with short circuit making
capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Fig.23: Operating elements after removal of the cover plate . . . . . . . . . . . . . . . . 55
Fig.24: Operating elements of the earthing switch with short circuit making
capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Fig.25: Operating elements of the earthing switch with short circuit making
capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Fig.26: Connecting bus short (a), long with or without transversal
erection (b) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Fig.27: Elbow element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Fig.28: T and Xmodule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Fig.29: Design of splitup with current transformer ELKVY14 . . . . . . . . . . . . . . . 68
Fig.30: Terminal configuration in terminal box . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Fig.31: End cover attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Fig.32: Density monitor ELKWT14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Fig.33: Pressure relief device ELKXA14 (left) and nameplate (right) . . . . . . . . . 78
Fig.34: Pressure relief device ELKXA14 with adsorber . . . . . . . . . . . . . . . . . . . . . 78
Fig.35: Parts to be replaced on maintenance (left) and on damage (right) . . . 81
Fig.36: Barrier insulator (left) and support insulator (right) . . . . . . . . . . . . . . . . . 82
Fig.37: Bushing ELKHB14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Fig.38: Inductive voltage transformer type ELKPI04 . . . . . . . . . . . . . . . . . . . . . . 87
Fig.39: Voltage Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Fig.40: Connection of voltage transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Fig.41: Voltage transformer installed at outgoing disconnector . . . . . . . . . . . . . 89
Fig.42: Voltage transformer installed at exit splitup . . . . . . . . . . . . . . . . . . . . . . . 90

Template: Figur 6
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
List of Figures

Fig.43: Exit splitup ELKHKY14 and cable connection ELKHK14 with


IEC standard dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Fig.44: Exit splitup ELKHKY14 and cable connection ELKHK14 with
IEC standard dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Fig.45: Forces and stresses in transportation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

Template: Figur 7
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
List of Tables

List of Tables

Tab.1: Timedependent intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23


Tab.2: Loaddependent intervals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Tab.3: Sets of spare parts for switchgear and it’s drives . . . . . . . . . . . . . . . . . . . 25
Tab.4: Ordering numbers for repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Tab.5: Weight and gas volume for circuit breaker ELKSP14 . . . . . . . . . . . . . . . 32
Tab.6: Technical data for connecting bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Tab.7: Technical data for connecting piece ELKVW14 . . . . . . . . . . . . . . . . . . . . 62
Tab.8: Technical data for T and Xmodule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Tab.9: Technical data splitup with integrated current transformer
ELKVY14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Tab.10: Technical data for end cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Tab.11: Technical data for density monitor ELKWT14 . . . . . . . . . . . . . . . . . . . . . . 73
Tab.12: Spare parts for density monitor ELKWT14 . . . . . . . . . . . . . . . . . . . . . . . . 76
Tab.13: Technical data for pressure relief device ELKXA14 . . . . . . . . . . . . . . . . . 77
Tab.14: Technical data for bushing ELKHB14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Tab.15: Technical data for inductive voltage transformer type ELKPI 04 . . . . . . 86
Tab.16: Technical data for exit splitup ELKHKY14 and cable connection
ELKHK14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Tab.17: Forces in g (g = Acceleration due to gravity) . . . . . . . . . . . . . . . . . . . . . . 98
Tab.18: Receiving Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Tab.19: Material and cleaning agent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Tab.20: Tightening torques for nongreased bolts . . . . . . . . . . . . . . . . . . . . . . . . . 105
Tab.21: Troubleshooting operating mechanism of circuit breaker . . . . . . . . . . . . 107
Tab.22: Troubleshooting circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Tab.23: Troubleshooting disconnector / earthing switch . . . . . . . . . . . . . . . . . . . . 108
Tab.24: Troubleshooting earthing switch with short circuit making capacity . . . 108
Tab.25: Troubleshooting voltage transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Tab.26: Troubleshooting other switchgear modules . . . . . . . . . . . . . . . . . . . . . . . . 109
Tab.27: Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Tab.28: Tightening Torques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Tab.29: Absolute Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Tab.30: Force ..................................................... 111
Tab.31: Length ..................................................... 111
Tab.32: Weight ..................................................... 111
Tab.33: Volume ..................................................... 111

Template: Tabelle 8
Order No.: 1HC0044810 E01 / AA06
Ñ°»®¿¬·²¹ ײ­¬®«½¬·±²­
ÍÚê ײ­«´¿¬»¼ Í©·¬½¸¹»¿®
ݱ°§®·¹¸¬ ¿²¼ ß¼¼®»­­

ï Ò±¬»­ ±² ¬¸» ܱ½«³»²¬¿¬·±²

ïòï Í«°°´·»® ¿²¼ Ó¿²«º¿½¬«®»® ß¼¼®»­­


ABB High Voltage Switchgear (Xiamen) Co., Ltd
Guanghui Building,6# Chuangxin 3rd Road,Torch Hi-Tech
Development Zone,Xiamen,361006,Fujian, P.R. China

ïòî ݱ²¬¿½¬ ß¼¼®»­­


Telephone(24-hours): +86(0) 13950151634
+86(0592) 5693737
Fax: +86(0592) 5710331
E-mail: Martin-Yong.Wang@cn.abb.com
ײ¬»®²»¬æ http://www.abb.com.cn

ïòí ݱ°§®·¹¸¬
É» ®»­»®ª» ¿´´ ®·¹¸¬­ ¬± ¬¸·­ ¼±½«³»²¬ ¿²¼ ¬± ¬¸» ±¾¶»½¬ ¼»­½®·¾»¼ ¬¸»®»·²ò ̸» ®»½·°·»²¬
±º ¬¸·­ ¼±½«³»²¬ ®»½±¹²·¦»­ ¬¸»­» ®·¹¸¬­ ¿²¼ ©·´´ ²±¬ ©·¬¸±«¬ ±«® °®·±® ©®·¬¬»² ¿°°®±ª¿´
³¿µ» ¬¸·­ ¼±½«³»²¬ ¿ª¿·´¿¾´» »·¬¸»® ·² °¿®¬ ²±® ·² ©¸±´» ¬± ¿²§ ¬¸·®¼ °¿®¬§ ±® «­» ·¬ º±®
¿²§ °«®°±­» ±¬¸»® ¬¸¿² ¬¸¿¬ º±® ©¸·½¸ ·¬ ©¿­ °®»­»²¬»¼ ¬± ¸·³ò
Û ßÞÞ Í©·¬¦»®´¿²¼ Ô¬¼

ïòì Ê¿´·¼·¬§ ±º ¬¸·­ ¼±½«³»²¬


̸·­ ¼±½«³»²¬ ײ­¬®«½¬·±²­ ÍÚê ײ­«´¿¬»¼ Í©·¬½¸¹»¿® ·­ ¬¸»
ø´»¿¼·²¹÷ ³¿­¬»® ¼±½«³»²¬ º±® ¬¸» ­©·¬½¸¹»¿®ò ß´´ ½±²¬·²«¿¬·ª» ¼±½«³»²¬­ ¸¿ª»
¬± ¾» «­»¼ ·² ½±²¶«²½¬·±² ©·¬¸ ¬¸·­ ¼±½«³»²¬ò

ïòë Ы®°±­» ±º ¬¸» Ñ°»®¿¬·²¹ ײ­¬®«½¬·±²­ ÍÚê ײ­«´¿¬»¼ Í©·¬½¸¹»¿®

̸» Ñ°»®¿¬·²¹ ײ­¬®«½¬·±²­ ÍÚ ê ײ­«´¿¬»¼ Í©·¬½¸¹»¿® ¼»­½®·¾»­ ¬¸»


¬·±² ±º ¬¸» ­©·¬½¸¹»¿® ¿²¼ ·¬­ ½±³°±²»²¬­ò

ïòê É¿®®¿²¬§
ײ ±«® »¨°»®·»²½»ô ½±®®»½¬ ±¾­»®ª¿²½» ±º ¬¸» ·²º±®³¿¬·±² ½±²¬¿·²»¼ ·² ¬¸·­
¬·±² ¹«¿®¿²¬»»­ ¬¸» ­¿º» ±°»®¿¬·±² ±º ±«® °®±¼«½¬ò ̸» ¼±½«³»²¬¿¬·±² °®±ª·¼»¼ ¸¿­
¾»»² °®»°¿®»¼ ©·¬¸ ¹®»¿¬ ½¿®»ò д»¿­» ·²º±®³ «­ ±® ±«® ²»¿®»­¬ ®»°®»­»²¬¿¬·ª» ·º ·¬ ·­ ²±
´±²¹»® °±­­·¾´» ¬± ±°»®¿¬» ±«® °®±¼«½¬ ­¿º»´§ ±² ¿½½±«²¬ ±º ·²½±®®»½¬ ±® ±³·¬¬»¼
¬·±²ò
É» ©·´´ ²±¬ ¿½½»°¬ ¿²§ ´·¿¾·´·¬§ ©¸¿¬­±»ª»® º±® ¼¿³¿¹» ¿®·­·²¹ »·¬¸»® ¼·®»½¬´§ ±® ·²¼·®»½¬´§
º®±³ ¬¸» ·²½±®®»½¬ ±°»®¿¬·±² ±º ±«® °®±¼«½¬ò ̸» ·²º±®³¿¬·±² ©·¬¸·² ¬¸·­ ³¿²«¿´ ·­ ­«¾¶»½¬
¬± ¬»½¸²·½¿´ ³±¼·º·½¿¬·±²­ ©·¬¸±«¬ ²±¬·½»ò

Ì»³°´¿¬»æ ÝÎÁïØÝððìëîëèÁßß»² ç
Ñ®¼»® Ò±òæ ïØÝððììèïð Ûðï ñ ßßðê
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Typographical Arrangements

2 Typographical Arrangements

2.1 Typographical Arrangements

2.1.1 References to other Documents


References to other passages of the documentation are made according to the following
way:
Example: all works associated with the revision of the circuit breaker ELKSP14 are de
scribed in document 1HC0030568.

2.1.2 References to Chapter or Sections of the Current Document


The reference will be made in the following way:
Example: see chapter 2; section 2.1.2

2.1.3 Document Format


The present documentation is also available in PDFformat on CDROM together with the
appropriate Adobe[ Acrobat reader.

2.1.4 Colours in Pictures in this Manual


The colours given in pictures, sketches and photographs in this operating instructions
may be different to the actual painting of the GIS.
The printed operating instructions are given in monochrome finish.

Template: TG_1HC0045260_AAen 10
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Typographical Arrangements

2.1.5 Contents of Header and Footer

Title Document
Title Main Chapter

1
2 Template: 1HC0021000 12
Order No.: 1HC0044810 E01 / AA06

1 − Template Number of the Document 4 − Title of Main Chapter


2 − Internal Order Number 5 − Title of Document
3 − Page Number
Fig.1: Contents of the Header and the Footer on each Page of the Documentation

Template: TG_1HC0045260_AAen 11
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Safety Notes

3 Information and Safety Notes

3.1 Target Audience


This operating instruction is to be used by qualified personnel only.

3.1.1 Definition of qualified personnel:


ABB requires that qualified electricians or allied professionals that have read and under
stood this operating instructions work on the electric equipment and the switchgear only.

3.2 Safety Notes


Activities described in this document must only be carried out when corresponding
Warning notes have been both read and understood and the preconditions described are
fulfilled. Otherwise, the manufacturer shall not be liable for damage of any kind as
a result of improper handling.

3.2.1 Read Obligation


The qualified personnel is bound to read the operating instructions and specifically the
safety notes carefully before starting to work on ELK14 switchgear. If there are any ques
tions, please contact ABB Switzerland Ltd. (see contact information in section 1.2)

3.2.2 How to cope with Problems


If there are any problems that cannot be solved using this operating instructions, ABB
Switzerland Ltd. will provide support. In this case, a detailed description of the problem
has to be submitted.
For an exact support, the serial number of the defective part will be needed.

3.2.3 Application of ELK14 Switchgear


The SF6 gasinsulated switchgear is used solely for power transmission and distribution,
as well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
Any other than the specified use is incorrect or has to be released by ABB.
The installation, − assembly, operating,− and maintenance procedures of ABB Switzer
land Ltd. apply.

3.2.4 Using the Operating Instructions


For easeofuse, links in the text to the corresponding information are given. In the col
umn to the left, symbols refer to actions, dangers or instructions. Please follow the in
structions to avoid any residual risks.

3.2.5 Safety
ABB Switzerland Ltd. continuously designs stateoftheart and according to interna
tional standards. Moving parts are always covered during operation. Never remove cov
ers or other parts that are in operation. Make sure to fulfill all requirements and measures
for your safety before starting to work on equipment. Please notice symbols for your
safety.

3.2.6 Limitation of Subject


The secondary protective installations (distance protection, busbar protection, etc.) are
not the subject of these Operating Instructions.

Template: SN_ELK−14_1HC0045262_AAen 12
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Safety Notes

3.2.7 Working Safety Notes


The following general Working Safety Notes must be strictly observed:
S The SF6Gas Insulated Switchgear is safe in operation according to the state of the
art. This installation, however, may produce hazards if operated by untrained per
sons in an improper manner or not as intended.
S Every person involved in the assembly, disassembly, operation, maintenance and
overhaul of this equipment must have read and understood the Operating Instruc
tions. This specifically applies to the Safety Notes.
S All warning plates on the installation must be observed!
S The installation and its components may only be used in the intended manner.
S All countryspecific safety regulations must be complied with.
S Earthing:
All enclosure parts on the installation and the framework must be connected at de
fined points to the earthing system. Earthing connections may be neither loosened
nor removed. The earthing of nonenergized conductors is done using the earthing
switches. The local safety regulations of the plant operator must be observed
thereby.

3.2.8 Safety Notes for Operation


S This installation may only be operated by personnel previously instructed, trained,
skilled and certified by ABB Switzerland Ltd.
S The plant operator must assure that only authorized person’s work on the installa
tion.
S The operator must be familiar with the indicating and operating elements.
S The operator must immediately inform the responsible persons, if the installation
state is such, that it could be detrimental to safety.

3.2.9 Safety Notes for Maintenance and Overhaul


S Working materials and protective clothing must be available and ready before start
ing maintenance and overhaul work.
S The SF6Gas Insulated Switchgear may only be assembled or disassembled, oper
ated, maintained and overhauled by technical personnel who have been previously
instructed and certified by ABB Switzerland Ltd.
S Assembly or disassembly, maintenance and overhaul work may only be carried out
on parts of the installation, which have been shut down (deenergized) and made
safe according to regulations.
S Only original spare parts may be used.
S After each overhaul a functional test must be carried out on the part of the installation
concerned.
S Parts of the installation may only be commissioned when nobody is present in the
hazard area.
S The maintenance and overhaul work and intervals stated in the Operating Instruc
tions must be observed.
S The specific Safety Notes for handling SF6gas must be complied with.
S Key blocking system:
The disconnector and earthing switches can be secured in any position by means
of padlocks against unauthorized handling.

Template: SN_ELK−14_1HC0045262_AAen 13
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Safety Notes

3.2.10 Operating Functions


The operating mechanisms of the disconnectors and earthing switches can be manually
operated in case of emergency by means of a hand crank. The procedure is described
in the component operating instructions (see sections 6.3 et seqq.).

3.2.11 Key Blocking System


For more details of operation and control, see the operating instructions Control and
Protection", given in document Project Specific Data" of the documentation.

The disconnector/earthing switch may be secured during overhaul in the CLOSED


Information or OPEN or NEUTRAL position using the locked" mode and the padlock of the
associated drive (see sections 6.3 et seqq.).

3.3 Safety Notes


The instruction manual contains important information on how to operate the plant
safely, properly and most efficiently. Observing these instructions helps to avoid danger,
to reduce repair costs and downtimes and to increase the reliability and lifetime of the
plant. In the further one we refer to the customary safety regulations and the safety in
structions of the plant operator.
Safety notes are marked in these operating instructions by symbols with signal words.
The signal words in these operating instructions have (according to ANSI Z535.4) the
meanings described in section 3.3.1.

3.3.1 Symbols and Texts of Particular Importance


Texts of particular importance are highlighted in our documentation as follows. We would
like to emphasize specifically that highlighted instructions have to be strictly observed.
Failure to comply with such instructions will lead to immediate invalidation of any associ
ated warranties.
The symbols are divided into three danger stages:
Indicates an imminently hazardous situation which, if not avoided, will result in
Danger death or serious injury.

Indicates a potentially hazardous situation which, if not avoided, could result in


Warning death or serious injury.

Indicates a potentially hazardous situation which, if not avoided, may result in


Caution minor or moderate injury.

Assembly instructions:
Information Information and directions, which will make the work more convenient for you.

Information and directions:


Information Contains information of particular importance. Additionally, we indicate in which
chapter and section the information can be found.

Template: SN_ELK−14_1HC0045262_AAen 14
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Safety Notes

3.4 Notes on Heaters in Drives and Control Cubicle


The operating mechanisms of circuit breakers, disconnector and earthing switches and
the control cubicle are equipped with electric heaters. These heaters serve to prevent
condensation in this equipment.
Condensation can result in corrosion and humidity damage.
The heaters, therefore, must be put into service during the assembly of the installation
and may not be switched off during interruptions of operation.
If during maintenance and overhaul work − as an exception − an interruption of the heat
ers is inevitable, it must be limited to the part of the installation concerned and kept as
short as possible.

Template: SN_ELK−14_1HC0045262_AAen 15
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of Installation

4 Description of installation

4.1 Metalenclosed Gas Insulated Switchgear (GIS)


The metalenclosed SF6gas insulated switchgear ELK14 is designed for the specific
rated data of the installation, which are given in document Project Specific Data". All
switchgears of the GIS type ELK14 comply with the IECstandards and VDEregulations.

4.1.1 Advantages of the GIS technology


Metalenclosed SF6gas insulated substations (GIS) cover approximately only 5 % of the
space needed of comparable conventional airinsulated substations (AIS). For this rea
son, they are of special interest in congested and industrialized areas where they provide
great economics. GIS is characterised by its:
− High operational safety
− High reliability
− Long lifetime
− Maintenancefree design
− Small dimensions
− Low weight
− Modular design
− Short installation times
− Enclosure of all life parts

4.1.2 General structure of a GIS


The interconnection of the individual GIS modules is designed to facilitate future expan
sions and/or changes. Gastight barrier insulators between adjacent gas compartments
limit the impact of an internal fault in one GIS module onto its neighbours to an absolute
minimum.
The enclosure of the GIS is made of noncorrosive aluminium. Due to the light specific
weight of aluminium, costly foundations are no longer required.
The GIS type ELK14 consists of a number of different modules. These individual mod
ules are interconnected by means of bolted flange connections.

Template: Des_GIS_1HC0045263_AAen 16
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of Installation

4.2 General structure of the components


GIS can be arranged in many different busbar layouts and they can be fit to nearly any
given physical layout of the substation and it’s surroundings. The end" of a GIS can be
chosen to fit to transformers, overhead lines, cables or other GIS.
Despite this large geometrical variability, the GIS is built on a small number of generic
components. The variable arrangement of these components leads to the variability of
the overall GIS. The generic components are described in the following section.

4.3 Short description of the components


The following short description of the components is generic and therefore could
Information contain components, which are not supplied.

4.3.1 Busbar
The busbars distribute the current within the switchgear. A busbar system is composed
of the individual busbar segments of each feeder. All busbars feature a threephase en
closure throughout the substation.
The GIS Type ELK14 covers mainly single busbar or double busbar.
The busbar conductors of each feeder are mounted on the gastight barrier insulators
that separate the individual feeders. The busbar modules have a telescopic transversal
installation module for easier extensions. A springloaded lateral disconnecting element
in the busbars is used for compensating any pressurerelated forces and changes in
length induced by temperature gradients in long busbars.
The busbar conductors are interconnected by means of contact plugs in any standard
connecting piece. Length variations due to temperature gradients, e. g. between the en
closure and the individual conductors, are compensated in the plugs and will not cause
any mechanical stress on the insulators.

4.3.2 Circuit breaker


The circuit breaker operates as a single pressure puffer breaker with one interrupting
chamber for each pole. The main and the arcing contacts in the interrupting chamber
are consequently separated from each other. For short circuit interruption the puffer
breaker utilizes the drive energy together with the arc to generate the arc quenching gas
flow. The puffer breaking principle is well established and applied up to highest ratings.

4.3.3 Circuit breaker operating mechanism


All three poles of the circuit breaker are operated individually by a hydraulic spring oper
ating mechanism. This hydraulic spring operating mechanism combines a hydraulic
drive with mechanical energy storage in a set of heavyduty disk springs. The disk
springs are hydraulically charged to store the drive energy. The contacts of the circuit
breaker are switched on respectively off by means of a hydraulic cylinder. The hydraulic
block features a closed loop for the hydraulic oil. Thus, it has no external hydraulic pip
ing.

4.3.4 Combined disconnector / earthing switch


A combined disconnector/earthing switch is incorporated between a busbar module
and a circuit breaker and at the exit side of a bay. The drive mechanism and the mechani
cal linkage for this disconnector/earthing switch is mounted directly on the GIS enclo
sure. The drive works simultaneously on the three moving contacts via a common link
age a gear and an isolating rod. Depending on the direction of rotation, the contacts
move either into the disconnecting or the earthing or the neutral position. A separate
hand crank allows the manual operation of the combined disconnector/earthing switch.
The earthing switch within the disconnector / earthing switch features an insulated earth
connection as option. The fixed earthing contact is insulated from the enclosure. The
earth connection is accomplished outside be means of a removable copper bar. Thus,

Template: Des_GIS_1HC0045263_AAen 17
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of Installation

it is possible to access the main current path without opening the gas compartment. This
greatly simplifies setting and testing of protection relays, cable testing and locating of
cable faults.

4.3.5 Cable termination


The cable termination allows connection of high voltage power cables with a cross sec
tion of up to 2000 mm2. Also a cable termination of plugandsocket type, graded for the
cable cross sections (< 1000 mm2, 1000 − 2000 mm2) can be provided, that greatly
eases the installation of the cable at site.

4.3.6 Earthing switch with short circuit making capacity


The earthing switch with short circuit making capacity is equipped with a snap spring
drive.
The earthing switch with short circuit making capacity can be isolated from the earthed
GIS enclosure. By removing the external earthing bars between the enclosure of the
earthing switch and the individually isolated contacts, it is possible to access the main
current path without opening the gas compartment. This greatly eases setting and test
ing of protection relays, cable testing and locating of cable faults.

4.3.7 Barrier insulators


The GIS is sectionalized into individual gas compartments by means of gastight barrier
insulators. Therefore, the impact of extensions or internal faults on the overall installation
is reduced to a minimum, and control, supervision and maintenance are greatly eased.
All flange connections are sealed by means of ageresistant Orings. The gastight de
sign of the insulator prevents gas leakage between components.

4.3.8 Support insulators


Support insulators are used to mechanically support the conductors. They are mainly
used for long SF6 busduct connections.

4.3.9 Current and voltage transformers


In the usual line of conventional control and protection equipment the GIS is equipped
with inductive current transformers for measurement and protection purposes. The pri
mary side of the current transformers is insulated with SF6. This design provides an ex
ceptional reliability since the insulating medium SF6 is not subject to aging.

4.3.10 Voltage transformer


In the usual line of conventional control and protection equipment the GIS is equipped
with voltage transformers for measurement and protection purposes. The primary side
of the voltage transformers is insulated with SF6. This design provides an exceptional
reliability since the insulating medium SF6 is not subject to aging.

4.3.11 SF6air bushing


The SF6air bushing allows connection of the enclosed switchgear to overhead lines or
to airoil bushings of power transformers.
The bushings are available with composite housings.

4.3.12 Sectionalization
The GIS contains two different types of gas zones. In the circuit breaker SF6 is used both,
as insulating as well as interrupting medium. In all other gas compartments SF6 serves
for insulation purposes only.
All gas compartments are sectionalized by means of gastight barrier insulators. Each in
dividual gas compartment is equipped with studs for connection of a gas density monitor
and non return gas filling devices. Thus, all maintenance works on the gas compart
ments, such as taking gas samples or regenerating gas, can be performed without any

Template: Des_GIS_1HC0045263_AAen 18
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of Installation

loss of gas. The gas density is supervised by means of temperaturecompensated gas


density monitors.

4.3.13 Local control cabinets


Each feeder bay is equipped with a local control cabinet that comprises all auxiliaries for
control, signalling and interlocking. The devices are connected by means of devicespe
cifically coded multiple connector plugs that can not be interchanged with each other.

Template: Des_GIS_1HC0045263_AAen 19
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

5 Maintenance, inspection and overhaul

5.1 Definitions and measures


The definition includes all measures for maintaining and restoring the normal condition
of installation parts and for the determination and assessment of the current condition.
These measures comprise:
S Maintenance (see section 5.2Maintenance")
S Inspection (see section 5.3Inspection")
S Overhaul (see section 5.4Overhaul").

5.2 Maintenance
Maintenance includes all measures for maintaining the normal condition of installation
parts. These measures comprise:
S Preparation of a maintenance plan
(see section 5.5Timedependent Intervals")
S Preparation for its execution
S Execution
S Reporting
The intervals given should be understood as maxima; the actual intervals are determined
by the operator’s maintenance concept.

5.3 Inspection
Inspection includes all measures for the determination and assessment of the current
condition of installation parts. These measures comprise:
S Preparation of a plan for determining the current condition
(see section 5.5Timedependent Intervals")
S Preparation for the execution
S Execution
S Presentation of the results of determination of the current condition and
S Evaluation of the results of the assessment of the current condition
S Deduction of the necessary consequences based on the assessment.

Template: Maint_1HC0045264_AAen 20
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

5.4 Overhaul
Overhaul includes all measures for restoring the normal condition of installation parts.
These measures comprise:
S Order, job documentation and analysis of the contents of the order
S Planning of the job including an evaluation of alternative solutions and operational
requirements
S Decision on the most favourable solution
S Preparation for the execution, comprising calculation, scheduling, coordination,
making available personnel, means and materials, preparation of working plans
S Preliminary measures such as equipment of workplace, protective and safety instal
lations, etc.
S Review of the preparatory work done and preliminary measures, including release
for execution
S Execution
S Functional test and acceptance
S Notification of completion
S Evaluation including documentation, record of costs, pointing out of improvements
and possibly introduction of the latter.

Template: Maint_1HC0045264_AAen 21
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

5.5 Timedependent intervals


Tab.1 gives the recommended timedependent intervals for the GISequipment for
maintenance, inspection and overhaul.

Every Part of installation Activity see


years sections

General:

5 Visible check general Report damage and initiate repair 6

5 Nameplates Check for legibility and clean, or replace if 6


(especially with out necessary
door Installations)

5 Static elements Check for corrosion 6


(especially with out
door installations)

5 Gas density, Check and if necessary replenish SF6 gas Document


gas pressure 1HC0028459
Manual
Handling
5 Gas humidity Carry out dew point measurement Sulphur Hex
afluoride
SF6"

5 Density monitors Check switching points of micro switches 6.10


ELKWT with portable density monitor tester

5 Control cubicle and Check heaters for correct functioning −


operating mechanisms

Switching devices:

Circuit breakers ELKSP14 and operating mechanism ELKHMB4

5 Gas density, gas pres Check and if necessary replenish SF6gas Document
sure 1HC0028459
Manual
Manual
5 Gas humidity Carry out dew point measurement Handling
Sulphur
p Hex
fl id
afluoride
5 Percentage Carry out %SF6measurement SF6"

5 Operating mechanisms Check switching times, oil level, carbon 6.2


ELKHMB4 brushes, possible leaks, electrical connec
tions

Disconnector / Earthing switch ELKDE0

5 Operating mechanism Check switching times. 6.3


Check end positions if necessary.
Check operation functionality.

Earthing switch with short circuit making capacity ELKES0

5 Operating mechanism Check switching times. 6.4


Check end positions if necessary.
Check operation functionality.

Template: Maint_1HC0045264_AAen 22
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

Every Part of installation Activity see


years sections

Installation:

5 Bay structure Retighten all anchor bolts to normal torque −

Nonswitching components:

Pressure relief device ELKXA14

− Protective plate On occasional rounds, check for damage 6.11


(especially with out
door installations)

Voltage transformers ELKPI04

− Terminal box On occasional rounds, check connections 6.14


and fixing screws periodically for loosen
ing and if necessary retighten

Outdoor flanges

5 Flange connection On occasional rounds, check cavity treat Document


ment HASV600715
Corrosion
Protection
and Sealing"

Tab.1: Timedependent intervals

Template: Maint_1HC0045264_AAen 23
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

5.6 Loaddependent intervals


Tab.2 gives the recommended loaddependent intervals for the GISequipment for
maintenance, inspection and overhaul.
After max. .... Part of installation Activity see
CO switching section
operations

Circuit breaker ELKSP14

5000 Arcing unit Inspection/overhaul 6.1


5000 Adsorber Exchange (on overhaul) 6.11
5000 Operating mechanism ELK HMB4 Inspection/overhaul 6.2

Loading de ABB recommends a loaddependend interval for overhaul ac 6.1
pendence of cording to the following diagram.
switching cycles
Number of admissible switching operations
10000

1000
Number of switching operations

100

10
0 10 20 30 40 50 60 70

Switching current (kA)

Disconnector / earthing switch ELKDE0

5000 Main contacts Inspection/overhaul 6.3


5000 Operating mechanism ELKDE0 Inspection/overhaul 6.3
5000 Adsorber Exchange (on overhaul)

Earthing switch with short circuit making capacity ELKES0

1000 Main contacts Inspection/overhaul 6.4


Overhaul after max.
2 shortcircuit closures
2000 Operating mechanism Inspection/overhaul 6.4
Tab.2: Loaddependent intervals

Template: Maint_1HC0045264_AAen 24
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

5.7 Maintenance

5.7.1 Safety notes


You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

5.7.2 Maintenance work


The effort for the maintenance work on installation and components is relatively small.
Occasional checks on routine inspections are, however, recommended. Tab.1 contains
a summary of all necessary maintenance work.
The procedure for maintenance work is described in the respective component operat
ing instructions.
On routine inspections, the personnel must give attention to the following issues:
Caution
S Suspicious noises, odors and other irregularities
S Damage to parts of the installation or buildings
S Changes due to weathering
S Prohibited entry for unauthorized persons
General notes and guidelines of the operator (e.g. reading of diverse meters, etc.).
On detection of irregularities, the responsible person must be informed immediately. The
irregularities found must be eliminated, depending on their importance, immediately or
at the next opportunity. Only on specific events, the manufacturer must be consulted.

5.7.3 Intervals
A list of all necessary maintenance work is shown in Tab.1.
Nonswitching components are largely maintenancefree, however occasional checks
are recommended on the normal rounds.
The procedure for the maintenance work is described in the operating instructions for
the components.

5.7.4 Spare parts


A recommended list of spare parts is given in Tab.3 below. However, a different set of
spare parts or an extract of the recommended list of spare parts may have been agreed
with the manufacturer.

5.7.5 Spare parts for overhaul


The sets of spare parts for switchgear and it’s drives are defined. These sets can be or
dered using the numbers in Tab.3 below.

For Name of spare part set Order number

ELKSP14 ELKSP14 Circuit breaker 1HC0020222M0002

Tab.3: Sets of spare parts for switchgear and it’s drives


The content of the spare parts sets and how to exchange them is described in the mainte
nance manuals of the components. The spare parts sets can be ordered for the date of
revision. Please note, that service life of these sets is limited.

Template: Maint_1HC0045264_AAen 25
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

5.7.6 Spare parts for repair


ABB recommends to have completely assembled components as strategic spare parts
for repair. Thus, Tab.4 gives the ordering numbers of completely assembled compo
nents. These components can be ordered with the first installation or whenever needed.

For Name of spare part Order number

ELKSP14 ELKSP14 Circuit breaker 1HC0020222M0002

Tab.4: Ordering numbers for repair

Template: Maint_1HC0045264_AAen 26
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

5.7.7 Nonswitching components


Nonswitching components are maintenancefree. Occasional checks on routine
rounds are, however, recommended (see Tab.1).

5.7.8 SF6 gas monitoring


Gas filling is carried out according to the operating instructions of the service
Information equipment. Replenishment is also possible during operation of the installation.
Detailed information about the procedures and the safety precautions of replenishment
are to be find in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6".
The gas density is continuously monitored by density monitors which − on reaching pre
set limits − trigger the corresponding alarms. The limits for gas compartments of circuit
breakers and voltage transformers differ from those of the other components.

5.7.9 Abnormal gas losses


In the case of gas leakages causing the alarm Replenish SF6 gas" between two checks,
gas must be replenished immediately. The reason of the excessive gas loss must be in
vestigated and a repair initiated. See also document 1HC0028459 Manual Handling
Sulphur Hexafluoride SF6".
On triggering of the alarm Isolate", the affected gas compartment must be isolated (de
energized) and the gasleak located and eliminated. See also document 1HC0028459
Manual Handling Sulphur Hexafluoride SF6".

5.7.10 Isolating

Gas alarm stage 1


If the gas loss is below 0.5 % p.a., simple replenishment to nominal filling pressure is
sufficient.
Otherwise, gas must be replenished and a manual isolation carried out when the cause
of the gas loss requires a repair action.
Disconnector and breakers in stage 1 may only be switched when necessary for isolat
ing purposes.

Gas alarm stage 2


On reaching gas alarm stage 2, isolation of the installation is urgent and must be carried
out in the shortest possible time, or the rated density must be restored and held by re
plenishing to nominal filling pressure with gas.
Operating breakers and disconnectors
If gas density has dropped below stage 2, the breaker may no longer be operated be
cause the density may be too low to extinguish the arc.
Disconnectors may also not be operated when the density drop reaches stage 2.
A blocking circuit of the REMOTE control assures this automatically.

Breakers, disconnectors and other components of the installation


After the gas density has dropped below stage 2, the part of the installation affected goes
into the dielectric state in which the test voltages can no longer be guaranteed.
However, the switching voltages to be expected are less than the test voltages, so that
a certain safety margin remains for isolation.
This security remains until the density has dropped too far. Since the density loss rate
depends on the size of the leak, no exact statement can be made on the time available
for safe switching.
For this, isolation must be initiated immediately; otherwise there will be a risk of flashover
in the affected gas compartment.
All operating experience to date has shown that this solution works reliably, provided that
the density drop is not instantaneous.

Template: Maint_1HC0045264_AAen 27
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

Blocking
In order to assure that dielectric faults do not occur through switching overvoltages in
stage 2, blocking of the circuit breaker switching elements is provided. These are as a
rule all items of switching equipment of a GIS installation.
The condition for blocking is that in the affected gas compartment both, stage 1 and
stage 2 have been triggered.
To complement this action, the reset devices of the breakers also block switching ON
operations.
With blocking a certain reduction of availability of the installation is consciously ac
cepted. Protection of the installation is not interconnected with this measure.

Instantaneous density drop


If this condition occurs through a faulty arc and triggering of rupture disk, then it is dealt
with by the installation protection system.
Triggering of the pressure relief device for other reasons is extremely unlikely.
Reliable pressure reduction valves are specified for the gas filling equipment.
The rupture disks itself is subject to rigorous sample testing and is well protected against
accidental damage.

Conclusions
The extremely low probability of a fault arising either from isolating too late or from an
instantaneous density drop makes manual isolation the best solution.
Through blocking of the REMOTE and LOCAL control on reaching stage 2, additional
security is obtained with a certain loss of availability. The installation can then only be
operated locally.

Template: Maint_1HC0045264_AAen 28
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

5.8 Overhaul

Safety notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.

Intervals for overhaul work


The intervals are listed in the maintenance table (see Tab.1Timedependent intervals"
and Tab.2Loaddependent intervals"). On reaching the time for overhaul, please con
tact our service department. The address is given in section 1.2Contact adress" of
these operating instructions.
Nonswitching components do not require overhaul.
Please contact our service department on reaching the due date. The address is given
in section 1.2Contact adress" of these operating instructions.

Spare parts
The component spare parts are listed in Tab.3Set of spare parts for switchgear and
it’s drives" and Tab.4 Ordering numbers for repair". However, a different set of spare
parts or an extract of the recommended list of spare parts may have been agreed with
the manufacturer.

Tools, jigs and fixtures


Persons who are skilled and familiar with the parts to be overhauled and who received
all relevant trainings may only carry out the overhaul work.

5.8.1 Shutting down and making safe parts of the installation


Voltages can be induced across switchedoff parts of the installation via rope con
Danger ductors, via parallel overhead lines, via reversely fed voltage transformers, etc.
Such voltages are hazardous to persons and can damage the installation. It is
therefore essential to earthen before starting overhaul work and to maintain earth
ing until operational capability is restored.
The gas pressure inside the GIS tensions the tensioning rods of compensators and lat
eral dismantling units.
In no case should the tensioning rods be released while the inside is pressurized.
Warning Otherwise, the inside pressure will cause the components to burst and severe inju
ries or damage to property may occur.
Before starting overhaul work, read the notes for SF6gas handling in document
1HC0028459 Manual Handling Sulphur Hexafluoride SF6".

Template: Maint_1HC0045264_AAen 29
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

Procedure for shutting down and making the installation safe


1. Isolate part of installation with disconnecting switch and secure switching position
2. Check remote position indicator
3. Check position of disconnector switch via the viewport of the disconnector switch
4. Earthen part of installation with earthing switch and secure switching position of op
erating mechanism with padlock
5. Check position of earthing switch via the viewport of the earthing switch
6. Check remote position indicator
7. Protect against reclosing
8. Evacuate SF6 gas (document 1HC0028459 Manual Handling Sulphur Hexafluo
ride SF6") and open the enclosure.

5.8.2 Execution of overhaul work


Fig.2 gives a guideline for actions to be carried out during overhaul work in a GIS. The
detailed procedure for overhaul work on single components is given in the assembling
and overhaul instructions for each component. These instructions are available as sepa
rate documents from ABB.

Normal Installation Revision In


operation structions of
Components

Overhaul Gas handling

Overhaul yes Shut down Evacuate gas


interval part of in space
reached? stallation Open enclosure
no

Open gas Carry out overhaul


space work according to
Revision Instruc
tions of Compo
Close enclos nents"
ure and fill with
gas

Commission Gas space Clean and treat


part of yes gastight? components
installation according to
document
no HASV600715
Corrosion
Troubleshoot Protection and
Sealing"
Normal
operation

Fig.2: Overhaul flow chart

Template: Maint_1HC0045264_AAen 30
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Maintenance, Inspection and Overhaul

Procedure for putting the installation into operation after overhaul


1. Carry out a functional check of the overhauled part of the installation
2. Close enclosure and fill with SF6 gas (document 1HC0028459 Manual Handling
Sulphur Hexafluoride SF6")
3. Disconnect earthing from part of installation
4. Check position of earthing switch via the viewport of the earthing switch
5. Connect part of installation to grid.

Template: Maint_1HC0045264_AAen 31
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6 Description of components

This chapter lists and describes the components of a GIS.

6.1 Circuit breaker type ELKSP14

6.1.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid.
Any other application is not envisaged and would not conform to the intended purpose.

Symbol

Fig.3: Symbol Circuit Breaker ELKSP14

Nameplate
The installation specific data are given on the nameplate of the circuit breaker ELKSP14.

Technical data of circuit breaker ELKSP14


The installation specific data are given in document Project Specific Data".

Designation Unit Value

Weight of basic equipment kg 380


(without operating mechanism)

Volume of SF6 gas compartment dm3 480

Type designation operating mechanism ELKHMB4

Tab.5: Weight and gas volume for circuit breaker ELKSP14

6.1.2 Circuit Breaker Design


The circuit breaker operates as a single pressure puffer breaker with one interrupting
chamber for each pole. For short circuit interruption the puffer breaker utilizes the drive
energy in combination with the arc energy to generate the arc quenching gas flow. The
puffer breaking principle is well established and applied up to highest ratings.
One interrupting unit is fitted in each of the three singlephase aluminium enclosures.
The breaker is provided with a hydraulic spring operating mechanism type ELKHMB4
for each phase. It is mounted horizontally on a steel bay structure. The circuit breaker
design is based on the wellproven puffer breaker principle and applies latest develop
ments in arc physics and material technology.
The highcurrent connections from the interrupting unit to the flanges are designed as
knife contact (at the drive side) and as plug contact (at the fixed contact side). This allows
the interrupting unit to be pulled out of the tank through the drive side flange without re
moving the connections.

Template: SP_1HC0045266_AAen 32
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.1.3 Operating principle of the interrupter unit


The interrupter unit is operated by a drive HMB4.

CLOSING operation
During the closing operation, the circuit breaker operating mechanism causes the oper
ating rod (4) and, as a consequence, the moving parts of the interrupting chamber, such
as the insulating nozzle, the auxiliary nozzle and the puffer cylinder to move in the direc
tion of the fixed contact. Contact is first established through prearcing between the arc
ing contacts, which subsequently enables the main contacts to close at almost zero cur
rent.

OPENING operation
Opening is affected by withdrawing the moving contact in the opposite direction. During
this operation the main contacts are separated prior to the separation of the arcing con
tacts, resulting in the commutation of the current to the arcing contacts.
The energy of the arc and the drive motion cause a pressure increase in the puffer. During
the separation of the arcing contacts a radial gas blast is released through the auxiliary
and insulating nozzles, cooling down the arc and finally extinguishing it at current zero.
The schematic representation in Fig.5 shows the working principle of a single interrupt
ing chamber following the puffing piston principle. View A shows the initial position of
the interrupting chamber in position ON. Contact ring 4 and the contact fingers 2 form
a conducting unit. During an opening operation (View B), the contact ring 4 separates
from the contact fingers 2. The gas volume in the puffing cylinder 7, which is travelling
backwards, is continually reduced through the stationary puffing piston 8 and the pres
sure of the enclosed gas is thereby increased until the arcing finger contacts 6 also sepa
rate from contact pin 1.
As a result of the separation (View C), an electric arc is burning, which creates a further
pressure increase of the gas in the puffer cylinder 7 due to the effect of local heating from
the shortcircuit current. Due to the increased pressure, the compressed gas flows into
the arc zone through the insulating nozzle 3, or in the other direction through the auxiliary
nozzle 5. The flow and the heat conducting ability of the SF6 gas are cooling the electric
arc and it extinguishes at the current zero transition. Views D show the interrupting cham
ber in the fully open position.

Template: SP_1HC0045266_AAen 34
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

A B

C D

9 8 7 5,6 4 3 2 1 D

8 9 7 4 6 5 3 2 1

AClosed position CArcing


BSeparation of main contacts DOpen position

1 − Contact pin 6 − Finger contacts


2 − Contact finger 7 − Puffer cylinder
3 − Insulating nozzle 8 − Stationary puffing piston
4 − Contact ring 9 − Exhaust
5 − Auxiliary nozzle

Fig.5: Functional principle of the interrupting chamber during opening operation

Template: SP_1HC0045266_AAen 35
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.1.4 Operating diagram for circuit breaker with singlepole operation


For the operating diagram for the ELKSP14 circuit breaker with singlepole operating
mechanism HMB4 refer to the routine test protocol of the circuit breaker.

6.1.5 Operation

Safety notes
You may only carry out activities listed under Operation" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Operating functions
For more detailed information on operation and control, see operating instructions Con
trol and protection".

Manual operation

According to IEC62271100 manual operation shall be used only for maintenance


Danger and for emergency operation on a dead circuit.

Allow sufficient time for the pump to rebuild pressure between operations. Please
Information refer to the operation manual of the operating mechanism Type HMB4.
The manual is available under no. 1HDH118041.

6.1.6 Maintenance

Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Intervals
The intervals for maintenance work are given in chapter 5, Maintenance, inspection and
overhaul".
If the maintenance interval has been reached or irregularities are observed in operational
switching, maintenance work shall be carried out.

Maintenance work
The maintenance work on the circuit breaker is limited to protection of the enclosure
against corrosion and checking the number of switching operations. The circuit breaker
must not be shut down for this purpose.
The control module for the hydraulic pump (cf. operating instructions "Control and
protection") is placed in the local control cabinet.
The control module monitors the pump startup time and counts the number of pump
starts, which occur after each switching operation.
Each pump startup is individually detected and counted for each phase. With the pump
starts, the closing operations of the circuit breaker are also counted for each phase.
S Check number of pump starts
S Check number of switching operations.

Template: SP_1HC0045266_AAen 36
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.1.7 Overhaul

Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.

6.1.8 Overhaul work

Intervals
The intervals for overhaul work are given in chapter 5, Maintenance, inspection and
overhaul".
When the interval has expired, please contact our service department.
For the work to be conducted on overhaul the REVISION INSTRUCTIONS 1HC0030568
has to be referred to.

Template: SP_1HC0045266_AAen 37
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.2 Circuit breaker operating mechanisms type HMB4


Please refer to the operation manual of the operating mechanism type HMB4.
The manual is available under no. 1HDH118041.

Template: SP_1HC0045266_AAen 38
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.3 Disconnector/earthing switch type ELKDE0

6.3.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid.
Any other application is not envisaged and would not conform to the intended purpose.

Symbol

Disconnector Earthing switch

Fig.6: Symbols for disconnector and earthing switch ELKDE0

Nameplate
The installation specific data are given on the nameplate of the disconnector/earthing
switch ELKDE0.

Technical Data of Disconnector/Earthing Switch ELKDE0


The installation specific data are given in document Project Specific Data".

If the operating mechanism is equipped with an anticondensation heater, it is


Information vented.

Template: DE0_1HC0045267_AAen 39
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.3.2 Disconnector/earthing switch design

View x

Fig.7: Disconnector/earthing switch ELKDE0


The disconnector and the earthing switch are combined in one switching device (Fig.7).
The moving contacts (4), Fig.8 can be moved into the three following positions for the
disconnector respectively the earthing switch:
− Disconnector closed
− Disconnector open / Earthing Switch open (neutral position, Fig.8)
− Earthing switch closed

1 2 2

1 − Barrier insulators 4 − Moving contacts


2 − Conductors 5 − Counter contacts for disconnector
3 − Counter contacts for earthing switch

Fig.8: Disconnector/earthing switch integrated in the busbar module (neutral position)


The conductors (2) are fixed at the barrier insulator (1) (alternatively at a support insula
tor) in such a way that the operating rod for the moving contacts (4) is aligned.
The fixed contacts for the earthing switch (3) respectively the disconnector (5) are lo
cated opposite to the corresponding position of the moving contact (Fig.8).
The operating mechanism (Fig.10) is mounted outside the gas compartment and oper
ates the moving contacts ((4), Fig.8) via the insulating rods, see Fig.9.

Template: DE0_1HC0045267_AAen 40
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

Insulating rods

Fig.9: Insulating rods


In combination with the various available conductor and enclosure arrangements this
layout can be used to realize the following function modules:
− Busbar with integrated disconnector/earthing switch, as shown in Fig.8
− Connection piece with integrated disconnector/earthing switch

Template: DE0_1HC0045267_AAen 41
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.3.3 Operating mechanism

8 5 9 7 10

4 6
EarthingSwitch

2
Disconnector

1 − Interlocking Switch 4 − Auxiliary Contacts 8 − Drive Rod


2 − Rod for Emergency 5 − Cam Disk 9 − Carrier
Manual Operation 6 − Plug Connections 10 − Operating
3 − Position Indicator 7 − Gear Spindle Mechanism Motor

Fig.10: Operating mechanism of the combined disconnector/earthing switch


The operating mechanism is normally motoroperated. Manual operation is possible in
emergencies. The rotating movement of the operating mechanism is transmitted
through a threaded spindle (7) and a cam disk (5) via the drive rod (8) onto the moving
contacts (Fig.10).
The combined disconnector/earthing switch has two drive motors(10), one for the dis
connector and one for the earthing switch. For manual emergency operation a hand
crank can be attached to the rod (2) that operates the threaded spindle (7).
The cam disk (5) is located between the threaded spindle (7) and the drive rod (8) of the
contact blades and is actuated by a carrier (9). The cam disk (5) locks the device in the
following end positions:
− Disconnector closed
− Disconnector open / Earthing Switch open (neutral position)
− Earthing Switch closed

Template: DE0_1HC0045267_AAen 42
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

The cam disk (5) has the following functions (Fig.10):


− Torquefree startup of the operating mechanism
− End position locking
− End positioning
The motor current is interrupted by a limit switch.
When the device is manually operated, the interlocking switch (1) automatically discon
nects the motor circuit.
The auxiliary contacts (4) and the position indicator (3) are linked to the operating
rod(8).
All electrical connections are separated for the disconnector and the earthing switch and
are connected with coded plug connections (6).

6.3.3.1 Manual operation (control voltage present)


With present control voltage the system is supervised.
Danger Without control voltage the interlocking conditions are not controlled. Therefore,
a secure operation isn’t anymore made sure. Because this case of operation can
be dangerous to life or physical condition (i.E. switching shortcircuit), is the op
eration without control voltage allowed only for specially trained personal and can
be carried out only with special tools.

For manual operation all interlocking conditions (6.3.3.2Locking") have to be ful


Information filled. The device has to be unlocked.
In emergencies the disconnector and the earthing switch can be operated locally directly
on the device by means of a handcrank. As soon as the handcrank is inserted, the motor
circuit is automatically interrupted.
For manual operation of the disconnector/earthing switch the front cover has to be re
moved from the operating mechanism (Fig.12). The front cover is secured with 4 screws
M6 (4Nm).

1 2

1 − Position indicator disconnector


2 − Position indicator earthing switch

Fig.11: Operating mechanism with cover, switching contact in neutral position

Template: DE0_1HC0045267_AAen 43
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

1 2

1 − Position indicator disconnector


2 − Position indicator earthing switch

Fig.12: Operating mechanism after removal of its cover, switching contact in neutral position

Switching positions of handle

3 2 1 1 2 3

1 − Local manual control (hand crank): Local control with hand crank possible
2 − Interlock (electrically switchable) = Default setting: Local and remote control possible,
control with hand crank not possible
3 − Mechanically and electrically blocked

Fig.13: Switching positions of handle

Possible combinations of positions

Disconnector ON Earthing switch ON

Disconnector OFF Earthing switch OFF

Fig.14: Possible combinations of positions

Template: DE0_1HC0045267_AAen 44
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

Manual operation of the disconnector

3 1 2 4,5

1 − Locking bolt 4 − Cover


2 − Handle 5 − Blocking solenoid
3 − Opening (not shown, behind 4)

Fig.15: Operating elements disconnector (front view)

Precondition: neutral position


1. The earthing switch must be open
(otherwise bring the earthing switch into the OFF position first)
2. Optional: Remove padlock (if fitted), pulls back
slide is in middle position
3. Move handle (2) in direction switching position local manual control" until mechan
ical resistance
4. In case of existing control voltage:
As soon as mechanical resistance is reached, wait for releasing by the operating
personal for remote control operation for the further moving of the handle

In case of breakdown of control voltage the operation is allowed only for specially
Danger trained personal and can be carried out only with special tools:
As soon as resistance is reached:
a)Remove cover (4) with tool
b)Unlock blocking solenoid (5) by pressing and hold
c)Move handle (2) to position local manual control"
5. After release for the further moving move handle (2) until mechanical end stop for
releasing the hand crank opening (3) completely
6. Insert hand crank in opening (3)
7. Switch disconnector with hand crank in position ON or OFF
8. Turn hand crank until freewheel
9. Remove hand crank
10. Tighten handle (2) and bring into neutral position
11. Pull locking bolt (1) and optional: Fit padlock
12. In case of breakdown of control voltage: Screw the cover (4) back again
13. Put the cover back in place again

Template: DE0_1HC0045267_AAen 45
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

Operation Earthing Switch

4,5 2 1 3

6 6

1 − Locking bolt 5 − Blocking solenoid (not shown, be


2 − Handle hind4)
3 − Opening 6 − Lock
4 − Locking screw

Fig.16: Operating elements earthing switch (front view)

Precondition: neutral position


1. The disconnector must be open
(otherwise bring the disconnector into the OFF position first)
2. Optional: Remove padlock, pulls back
3. Move handle (2) in direction switching position local manual control" until mechan
ical resistance
4. In case of existing control voltage:
As soon as mechanical resistance is reached, wait for releasing by the operating
personal for remote control operation for the further moving of the handle

In case of breakdown of control voltage the operation is allowed only for specially
Danger trained personal and can be carried out only with special tools:
As soon as resistance is reached:
a)Remove cover (4) with tool
b)Unlock blocking solenoid (5) by pressing and hold
c)Move handle (2) on position local manual control"
5. After release for the further operation move handle (2) until mechanical end stop for
releasing the hand crank opening (3) completely
6. Insert hand crank in opening (3)
7. Switch earthing switch with hand crank ON or OFF

Template: DE0_1HC0045267_AAen 46
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

8. Turn hand crank until freewheel


9. Remove hand crank
10. Tighten handle (2) and bring into neutral position
11. Pull locking bolt (1) and optional: Fit padlock
12. In case of breakdown of control voltage: Screw the cover (4) back again
13. Put the cover back in place again

6.3.3.2 Locking
It is possible to lock the disconnector/earthing switch electrically and mechanically both,
in the open and in the closed position.
In order to lock the disconnector/earthing switch, the cover must be removed from the
operating mechanism (Fig.12).

After locking the device it can no longer be operated manually with the handcrank.
Information
Disconnector Earthing switch

1 2 2 1

1 − Locking bolt
2 − Handle

Fig.17: Operating elements disconnector and earthing switch (front view)

Precondition: neutral position


1. Remove padlock ⇒ locking bolt pulls back itself
2. Move handle (2) by pushing in position locked"
3. Pull locking bolt (1) and fit padlock

Template: DE0_1HC0045267_AAen 47
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.3.4 Operation

Notes
You may only carry out activities listed under Operation" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Operating functions
For more detailed information on operation and control, see the manual for the local con
trol cubicle referred to in document Project Specific Data".

Manual operation
Manual operation of the disconnector/earthing switch ELKDE0 is accomplished via the
drive. The procedure is described in the operating instructions for the operating mecha
nism.

Template: DE0_1HC0045267_AAen 48
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.3.5 Maintenance
Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".
If the maintenance interval has been reached or irregularities are observed in operational
switching, maintenance work shall be carried out.

Maintenance work
The maintenance work on the disconnector is limited to protection of the enclosure
against corrosion, whereby it does not need to be shut down. Maintenance can be car
ried out without opening of the gas compartment.

6.3.6 Overhaul
Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.

6.3.7 Overhaul work


Intervals
The intervals for overhaul work are given in chapter 5,Maintenance, inspection and
overhaul".
When the interval has expired, please contact our service department.
For the work to be conducted on overhaul the overhaul manual" has to be referred to.
See document Project Specific Data" for details.

Spare parts and tools


Overhaul work requires skilled and trained personelle and ABB spare parts. Please con
tact our service department for assistance

Template: DE0_1HC0045267_AAen 49
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.4 Earthing switch with short circuit making capacity type ELKES0

6.4.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.

Symbol

Fig.18: Symbols for earthing switch with short ciruit making capacity

Nameplate
The installation specific data are given on the nameplate of the earthing switch with short
circuit making capacity.

Technical data
The installation specific data are given in document Project Specific Data".

Template: ES0_1HC0045269_AAen 50
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.4.2 Design of earthing switch with short circuit making capacity


The earthing switch consists of the switching device and a fixed contact, which is
mounted to the unit to be earthed (13).
The earthing switch may be disconnected from the main earthing system for the pur
poses of testing the protective relay and measuring the voltage drop of the main current
path. Therefore, an insulating connection is provided between the contact tubes (14)
and the operating mechanism arranged in the center of the unit (Fig.19).
For proper switch operation, the conductors (12a and 12b) must be correctly mounted
to ensure that the contact tubes (14) are connected to earth through the contact lamina
tion. Adequate control of circuit conditions that may occur when parallel overhead lines
are unearthed is achieved through an appropriate contact system.

15 14 13 12a 11 10 12b

1 2 3 4 5 6 7 12a 8 9

1 − Closing spring 9 − Plug arrangement


2 − Motor 10 − Mechanical connection
3 − Intermediate shaft 11 − Actuator lever
4 − Limit switch 12 − (a/b) Earthing bridges
5 − Drive lever 13 − Fixed contact of the unit to be earthed
6 − Limit switch 14 − Contact tube
7 − Connecting rod 15 − Actuator lever
8 − Gear assembly

Fig.19: Operating mechanism and main contacts of earthing switch with short circuit making
capacity

6.4.3 Operating Mechanism (Fig.19)


The earthing switch is equipped with a snapaction spring mechanism which is actuated
by an electric motor. An intermediate shaft (3) in the gear assembly (8) allows for emer
gency manual operation.
Drive lever (5) is rotated by motor (2) through the interposed reduction gear assem
bly(8). As a result, connecting rod (7) rotates the actuator lever (15), thereby compress
ing the closing springs (1). As soon as the springs have passed their deadcenter posi

Template: ES0_1HC0045269_AAen 51
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

tion, a torque is produced which acts upon the actuator lever (15) and, consequently,
effects the actual closing operation.
This independent action of the contact system and the spring mechanism is made pos
sible by the slot provided in connecting rod (7). The end positions are determined by
internal stops.
The operating mechanism is decoupled from the gear assembly by means of a free
wheeling mechanism which is effective in both directions.
The alarm switches and the switchposition indicator are actuated through a mechanical
connection (10) to the actuator lever (11). The motor current is cut off by the limit switch
(6). In the case of emergency manual operation the motor circuit is interrupted by the
limit switch (4). All electrical connections are brought out to a coded plug arrangement
(9).

6.4.4 Operation

Notes
You may only carry out activities listed under Operation" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

6.4.5 Interlock

7
2
6
3

4 5

1 − Limit switch 5 − Locking


2 − Interlocking magnet 6 − Crank opening
3 − Limit switch 7 − Slide bar
4 − Limit switch

Fig.20: Combined crank handle/finalposition interlock


As a standard feature, the operating mechanism is provided with a combined crank han
dle/finalposition interlock.

Template: ES0_1HC0045269_AAen 52
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.4.5.1 Crank interlock

Crank interlock (Fig.20)


The slide bar (7) has two positions and blocks the crank opening (6). In a
deenergized state, the slide bar is locked in place by the interlocking magnet (2).
When the slide bar (7) is moved to the left in the presence of the control voltage, the limit
switch (1) closes a test circuit. If the interlocking conditions are not satisfied and, there
fore, switch operation is not permissible, the interlocking magnet (2) remains deener
gized and prevents the slide bar (7) from being moved any further to the left.
If the interlocking conditions are satisfied, that is, switch operation is permissible, the in
terlocking magnet (2) is energized and the slide bar (7) clears the crank opening (6).
The crank handle can now be inserted into the crank opening. At the same time, the mo
tor circuit is interrupted by the limit switches (3).

6.4.5.2 Switch position lock

5
2

4 locked
3
4 unlocked

1 − Cylinder lock 4 − Operating lever


2 − Motor 5 − Square end
3 − Support

Fig.21: Switch position lock


The top end of the motor shaft (2) is fitted with a square end (5) which is pinned to the
shaft (Fig.21). A support (3) is mounted to the corresponding flange end of the motor
(2). The operating lever (4) is bolted to the side of the support and pivoted in point (6).
When the cylinder lock (1) is pushed in, the operating lever (4) is moved from the un
locked position to the locked position, thereby mechanically blocking the square end
(5) and, consequently, the motor. At the same time, the motor circuit is interrupted by the
limit switches (4) (Fig.20).
This interlocking is also availiable for padlock.

Template: ES0_1HC0045269_AAen 53
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.4.6 Manual local control


For manual local control, the interlocking preconditions must be fulfilled. The
Information switching position must be unlocked.
The earthing switch with short circuit making capacity can be actuated in emergency
mode directly at the system by means of a hand crank. When this is carried out, the elec
trical control is automatically interrupted.

6.4.6.1 Manual control (control voltage present)


Before manually controlling the earthing switch with short circuit making capacity, the
operating mechanism safety cover must be removed (Fig.22).

Fig.22: Operating elements of the earthing switch with short circuit making capacity

Switching with hand crank (Fig.22):


1. Push the button (2) to the left to the stopper"
2. Insert hand crank in the entry hole (1)
3. CLOSEOPEN earthing switch with hand crank
4. Remove hand crank
5. Refit safety cover

With a singlepin layout, the operating elements of the earthing switch with short
Information circuit making capacity are available for each pin.

Template: ES0_1HC0045269_AAen 54
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.4.6.2 Manual control (control voltage absent)


Following controlvoltage failure, electrical lines or connections must not be dis
Information connected or removed.
Before manually controlling the earthing switch with short circuit making capacity, the
operating mechanism safety cover must be removed (Fig.23).

2
3 4

1 − Cover plate 4 − Entry hole


2 − Screws 5 − Button
3 − Magnet

Fig.23: Operating elements after removal of the cover plate

Switching with hand crank (Fig.23):


1. Unscrew bolts (2) and remove cover plate (1)
2. Press in magnet (3) and, when doing this, push the button (5) to the left over the
pressedin magnet to the stopper
3. Insert hand crank in the entry hole (4)
4. CLOSEOPEN earthing switch with hand crank
5. Remove hand crank
6. Screw cover plate (1) back on
7. Refit safety cover

Template: ES0_1HC0045269_AAen 55
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.4.6.3 Position interlocking


The purpose of the position interlocking system is to mechanically and electrically lock
switchgear in opened and closed position.
Before manually controlling the earthing switch with short circuit making capacity, the
operating mechanism safety cover must be removed.

6.4.6.4 Padlock

1 2

1 − Pin
2 − Padlock

Fig.24: Operating elements of the earthing switch with short circuit making capacity

Position interlocking (Fig.24)


Please observe the following steps when locking:
1. Press in pin (1)
2. Attach padlock (2)
3. Refit safety cover

After the switching position has been locked, the switching device can no longer
Information be actuated with the hand crank.

Template: ES0_1HC0045269_AAen 56
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.4.6.5 Cylinder lock

cylinder lock

Fig.25: Operating elements of the earthing switch with short circuit making capacity

Position interlocking (Fig.25)


Please observe the following steps when locking:
1. Open lock and press in cylinder
2. Close lock while it is still pressed in
3. Pull out key
4. Refit safety cover

After the switching position has been locked, the switching device can no longer
Information be actuated with the hand crank.

6.4.7 Maintenance

Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Intervals
The intervals for maintenance work are given in chapter 5, Maintenance, inspection and
overhaul".
If the maintenance interval has been reached or irregularities are observed in operational
switching, maintenance work shall be carried out.

Maintenance work
The maintenance work is limited to inspection of the drive system and protection of the
enclosure against corrosion by cleaning if necessary. In addition, the connections and
fixing screws must be periodically checked for loosening and if necessary tightened.
The drive has running time control; in order to test the drive function a switching opera
tion is sufficient.

Template: ES0_1HC0045269_AAen 57
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

Spare parts and tools


Maintenance work usually does not include any manipulation of the drive system. There
fore, no spare parts and tools are required

6.4.8 Overhaul

Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.

Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".
When the interval has expired, please contact our service department.

Spare parts and tools


Overhaul work usually includes replacing of parts of the drive system or a replacement
of the complete drive system together with the primary apparatus.
Overhaul work requires skilled and trained personelle and ABB spare parts.

Template: ES0_1HC0045269_AAen 58
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.5 Connecting bus

6.5.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.

Symbol
The connecting bus does not have a specific symbol.

Nameplate
The connecting bus does not have a specific nameplate.

Technical data

Designation Unit Minimum Maximum

a mm 330 1000
Installation length
b mm 490 2000

a kg 110 + 158/m
Mass
b kg 110 + 132/m

a dm3/m 269
Volume of SF6 gas compartment
b dm3/m 248

Tab.6: Technical data for connecting bus

Template: CBus_1HC0045277_AAen 59
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

4 6 1 5 8 7 6 1 5

3 7 2 3 4 2

1 − Enclosure 5 − Insulator
2 − Contact support 6 − Pressure relief device
3 − Contact support 7 − Attachment possibility
4 − Conductor 8 − Transversal erection module

Fig.26: Connecting bus short (a), long with or without transversal erection (b)

6.5.2 Description
The connecting bus is a rigid, linear current connector and serves to connect installation
components. Depending on the configuration of the installation, it is installed with fixed
or variable length, horizontally or vertically. For distances longer than the maximum
length, several connecting buses have to be bolted together.
Enclosure (1) of the connecting bus is screwed onto adjacent installation components
with its standard flanges that can be equipped with insulators (5) barrier or support type.
The conductor (4) is supported by the contact support (2).
Length, configuration and number of connecting buses are specified according to the
configuration of the installation. Specific variants of the connecting bus having a rotating
flange or attachment possibilities for e.g. pressure relief device are available
The connecting bus usually forms a common gas compartment with other installation
components.
The insulating medium is SF6 gas.

6.5.3 Maintenance

Notes

You may only carry out activities listed under Maintenance" when you have
read and understood the notes; in particular the safety notes at the beginning of
the operating instructions and you fulfil the conditions stated therein. Other
wise, the manufacturer will decline all responsibility for damage caused by im
proper handling.

Maintenance work
The maintenance work on the connecting bus is limited to protection of the enclosure
against corrosion. See details in chapter 5,Maintenance, inspection and overhaul".

Template: CBus_1HC0045277_AAen 60
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.5.4 Overhaul

Notes

You may only carry out activities listed under Overhaul" when you have read
and understood the notes; in particular the safety notes at the beginning of the
operating instructions and you fulfil the conditions stated therein. Otherwise,
the manufacturer will decline all responsibility for damage or injury caused by
improper handling.

Overhaul work
The connecting bus does not need overhauling.

Template: CBus_1HC0045277_AAen 61
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.6 Elbow element ELKVW14

6.6.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.

Symbol
The elbow element does not have a specific symbol.

Nameplate
The elbow element does not have a specific nameplate.

Technical data

Designation Unit Value

Installation length mm 600 x 450

Mass kg 260

Volume of SF6 gas compartment dm3 276

Angle ° 90

Tab.7: Technical data for connecting piece ELKVW14

Template: VW_1HC0045278_AAen 62
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

2 1

1 − Flange 1
2 − Flange 2

Fig.27: Elbow element

6.6.2 Description
The elbow element is a rigid current connection with a 90° angle. It provides two stan
dard flanges to accomplish specific connection purposes.
The elbow element is built on an enclosure with two standard flanges in a 90° angle. The
distance between the flanges and the centre of the connecting piece is within the stan
dard length of the modules or can be prolonged for special requirements. It can be
equipped with different configurations of active parts to connect components in a 90°
angle.
The base insulator on flange 1 supports the currentcarrying parts arranged inside the
housing. Attachments on flange 2 can be chosen according to the required function in
the substation layout.
In general, the elbow element forms a common gas compartment with other installation
components.
The insulating medium is SF6 gas.

6.6.3 Maintenance

Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Maintenance work
The maintenance work on the elbow element is limited to protection of the enclosure
against corrosion. See details in chapter 5,Maintenance, inspection and overhaul".

Template: VW_1HC0045278_AAen 63
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.6.4 Overhaul

Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Overhaul work
The elbow element does not need overhauling.

Template: VW_1HC0045278_AAen 64
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.7 T and XModule

6.7.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.

Symbol
The T and Xmodule does not have a specific symbol.

Nameplate
The T and Xmodule does not have a specific nameplate.

Technical data

Value
Designation Unit
Tmodule Xmodule

Mass kg 330 350

Volume of SF6 gas


dm3 290 330
compartment

Tab.8: Technical data for T and Xmodule

Template: T_X_1HC0045279_AAen 65
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

Fig.28: T and Xmodule

6.7.2 Maintenance

Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Maintenance work
The maintenance work on the T and Xmodule is limited to protection of the enclosure
against corrosion. See details in chapter 5,Maintenance, inspection and overhaul".

6.7.3 Overhaul

Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Overhaul work
The T and Xmodule does not need overhauling.

Template: T_X_1HC0045279_AAen 66
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.8 Splitup with integrated Current Transformer ELKVY14

6.8.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.

Symbol
The splitup with integrated current transformer ELKVY14 does not have a specific sym
bol.

Nameplate
The installation specific data are given on the nameplate of spliup with integrated cur
rent transformer ELKVY14.

Technical data
The installation specific data are given in document Project Specific Data".

Designation Unit Value

Installation length mm 560

Mass (basic equipment) kg 160

Volume of SF6 gas compartment dm3 22

Tab.9: Technical data splitup with integrated current transformer ELKVY14

Template: VY_1HC0045280_AAen 67
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.8.2 Description
The enclosure 1 and the current transformer support 2 are forming the pressurized GIS
enclosure. The ringcores 3 are integrated inside the gas compartment. During assem
bly, the ringcores are mechanicaly fixed on the current transformer support. The ring
cores are protected by metallic shielding 4 for dielectric reasons and against very fast
transients phenomenons.
The secondary windings are collected in a common terminal box 5. The outer sheet
metal casing protects the windings.
The splitup module is one of the interfaces from the singlephase 6 to the 3phase 7
technology.
The splitup with current transformers ELKVY14 are connected to various types of
protection and measuring equipment and the specific requirements are accordingly
multiple. In principle the splitup with current transformers ELKVY14 can be assigned
to two applications: Measuring and Protection. For both applications, international stan
dards for its accuracy class are defined.

7 5 1 7 4

2 6 3 6 2

1 − Enclosure 5 − Terminal box


2 − Transformer support 6 − Partition (1phase technology)
3 − Ringcores 7 − Partition (3phase technology)
4 − Metallic shielding

Fig.29: Design of splitup with current transformer ELKVY14


The splitup with current transformers ELKVY14 forms a common gas compartment with
other installation components that have:
S gas connection for gas filling
S density monitor ELKWT14 for monitoring the gas density
S pressure relief device.

Template: VY_1HC0045280_AAen 68
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.8.3 Operation
You may only carry out activities listed under Operation" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Connection / commissioning
Before energizing the primary connector, the following provisions have to be
Warning taken:

S The secondary windings shall be connected for operation to the specified load
S Nonattached cores (e.g. reserve cores) shall be shortcircuited
The secondary wires from the ring cores are connected to the terminals 1 (Fig.30) in the
terminal box 2 (Fig.30). Fig.30 shows the terminal configuration in the terminal box. The
secondary wires are short circuited by the switching bridge 2. The load may be attached
to the second side of the terminals 1.
The earth connection screws 5 on the terminals 1 have to be loosened when a load has
been connected.

3 5

1 2

1 − Universal terminal 4 − Flex (for earthing)


2 − Insulating bridge switching bridge 5 − Earth connection screw
3 − Insulating bridge

Fig.30: Terminal configuration in terminal box

Template: VY_1HC0045280_AAen 69
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

Operation
Secondary windings must either be loaded as specified or shortcircuited! A sec
Warning ondary circuit may never be open!
Operation with open secondary circuit (e.g. open secondary terminals) causes
overvoltages hazardous to personal and thermally damaging of the transformer
cores.
Procedure for changing loads or transformer ratio during operation:
S Short circuit and earth the affected core by fastening the corresponding earth con
nection screws 5 (Fig.30)
S Change the connecting cable to the universal terminals 1 (Fig.30)
S Loose the earth connection screws 5 (Fig.30)

Operating functions
For more detailed information on operation and control, see operating instructions Con
trol and protection".

6.8.4 Maintenance

Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Maintenance work
The maintenance work on the splitup with current transformers ELKVY14 is limited to
protection of the enclosure against corrosion and periodic cleaning. See details in chap
ter 5,Maintenance, inspection and overhaul".
In addition, the connections and fixing screws must be periodically checked for loosen
ing and if necessary tightened.

6.8.5 Overhaul

Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, all regulations have to
be followed. With improper treatment, reliable operation of the installation is not assured.

Overhaul work
The splitup with current transformers ELKVY14 does not need overhauling.

Template: VY_1HC0045280_AAen 70
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.9 End cover

6.9.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.

Symbol
The end cover does not have a specific symbol.

Nameplate
The end cover does not have a specific nameplate.

Technical data

Designation Unit Cover with Cover without


attachment attachment option

Mass (basic equipment) kg 36 32

Volume of SF6 gas compartment dm3 24 22

Tab.10: Technical data for end cover

Template: EndCover_1HC0045281_AAen 71
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

3
1 2 1

1 − Standard flange 3 − Attachment possibility


2 − Small flange 4 − Attachment possibility

Fig.31: End cover attachment

6.9.2 Description
The end cover serves as a cover to shut gas compartments tightly. It is employed in differ
ent sizes and shapes as:
S Cover without attachment option
S Cover with attachment option
The end cover with attachment option can be equipped with the following components:
S Density monitor ELKWT14
S Pressure relief device
S Housing attachments, such as gas connection, blind cover, indicator glass

6.9.3 Maintenance

Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Maintenance work
The maintenance work on the end cover is limited to protection of the enclosure against
corrosion. See details in chapter 5,Maintenance, inspection and overhaul".

6.9.4 Overhaul

Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Overhaul work
The end cover does not need overhauling.

Template: EndCover_1HC0045281_AAen 72
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.10 Density monitor ELKWT14

6.10.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.

Symbol
The density monitor ELKWT14 do not have a specific symbol.

Nameplate
The installation specific data are given on the nameplate of the density monitor ELK
WT14.

Technical data
The installation specific data are given in document Project Specific Data".

Designation Unit Value

Pressure range kPa 0  1000

Ambient temperature °C 50 to +80

Mass kg 1.1

Measurement principle Reference gas measurement

Meter movement Stainless steel 1.4541, AISI 321

Housing aluminium, clear anodized

Pressure connection ABB Standard 2800

Tab.11: Technical data for density monitor ELKWT14

Template: WT_1HC0038827_AAen 73
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

1 2 3 4

6 5
1 − Indicator 4 − Transparent enclosure
2 − Sealing 5 − Cable connection
3 − Enclosure 6 − Terminals

Fig.32: Density monitor ELKWT14

6.10.2 Description
The density monitor ELKWT14 monitors the gas density of the SF6 installation part and
compares it with that of the gas in a closed reference gas compartment. If the density
drops below the set value in each case (warning, alarm, blocking), the mutually indepen
dent micro switch contacts close.
The density monitor ELKWT14 is available in the following versions:
S without outdoor hood for indoor version
S with outdoor hood for outdoor version
Depending on the version, density monitors ELKWT14 with are equipped 2 or 3 con
tacts.
Pressure comparison is provided by a metal bellow, which separates the SF6 gas
compartment of the installation from the reference gas compartment. The movement of
the bellows actuates microswitches via operating rod. The microswitches trigger the
relevant indications through different switching points.
Microswitches are connected to the plug contacts via a PCB. Plug contacts are coded
and cannot be interchanged inadvertently.
The movement of operating rod is indicated via a meter movement on a display visible
from the outside. As long as the pointer remains in the GREEN range of the scale, the
gas density is adequate. The transition GREENRED is set to the lowest switching point
(alarm).
The density monitor ELKWT14 has the following characteristics:
S high shock resistance
S no false alarms at low temperatures
S up to three mutually independent, galvanically separated circuits

Template: WT_1HC0038827_AAen 74
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.10.3 Maintenance

Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".

Maintenance work
Maintenance of the density monitor ELKWT14 is limited to testing the switching points
of the microswitches by means of the portable tester.

Testing switching points:


Readjustment of the switching points may only be carried out by the supplier (Tra
Warning fag AG).

Removal
S Switch off control voltage
S Remove outdoor hood (if present).
S Release socket head screws and swing open cast hood.
S Pull off plug contacts. The plug contacts are provided with a coding pin and hence
cannot be interchanged inadvertently (cast hood with control cable remains on the
installation).
S Release coupling ring. Grip density monitor ELKWT14 firmly and pull off carefully,
since the residual pressure between pressure connection and gas connection is re
lieved.
S Protect gas connection from damage and environmental influences by screwing on
sealing cap.
S Check switching points of microswitches with portable tester for density monitor
ELKWT14.

Installation
S Insert new sealing rings.
S Remove sealing nut.
S Introduce pressure connection carefully into gas connection.
S Fix density monitor ELKWT14 with coupling ring in original position.
S Insert plug contacts according to coding.
S Fix cast hood with socket head screws to the baseplate.
S Assemble outdoor hood (if present).
S Switch on control voltage.

Template: WT_1HC0038827_AAen 75
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

Spare parts for pressure connection


Maintenance work does include an exchange of the sealing system. For this, the follow
ing spare parts are required.

Piece Designation Order number

2 Sealing ring 15.3x2.4 mm GPFA732058P0001

1 Sealing nut 1HDG111106

1 Portable tester for density monitor incl. SK509R003


description Dilo, DBabenhausen

Tab.12: Spare parts for density monitor ELKWT14

6.10.4 Overhaul

Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Overhaul work
The density monitor ELKWT14 does not need overhauling.

Template: WT_1HC0038827_AAen 76
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.11 Pressure relief device ELKXA14

6.11.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.

Symbol
The pressure relief device ELKXA14 does not have specific symbol.

Nameplate
The installation specific data are given on the nameplate of the pressure relief device
ELKXA14.

Technical data
The installation specific data are given in document Project Specific Data".

Designation Unit Value

Inverse rupture disk

Type S90 (BS & B)

Rated size mm ø 102

Bursting pressure for the circuit breaker at 20 °C kPa 1150

Bursting pressure for the installation at 20 °C kPa 1000

Triggering precision % ± 10

Mass

Adsorber

Filter material Molecular sieve 5A

Type 5A 8/2

Tab.13: Technical data for pressure relief device ELKXA14

Template: XA_1HC0038828_AAen 77
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

Fig.33: Pressure relief device ELKXA14 (left) and nameplate (right)

6.11.2 Description
The pressure relief device ELKXA14 has the task of initiating pressure relief if the gas
pressure in the gas compartments rises above the permitted pressure value. An increase
of gas pressure may be caused by an internal arc fault but never during normal operation
of the switchgear.
On reaching the bursting pressure, the pressure relief device ELKXA14 is destroyed at
its predetermined triggering point and the SF6 gas is relieved.

1 − Exhaust 6 − Rupture disc


2 − Cover plate 7 − Intermediate flange
3 − Greasing nipple 8 − Intermediate ring
4 − Connection flange ø 212 mm 9 − Protective cover
5 − Adsorber

Fig.34: Pressure relief device ELKXA14 with adsorber


Any separate gas compartment in an SF6−gas insulated switchgear installation is
equipped with a pressure relief device ELKXA14 on a connection flange 4 (Fig. 5). The
pressure relief device ELKXA14 is a safety element for the enclosures of SF6 switchgear.
On the rare occasion of an internal arc, the gas pressure in a compartment may increase
to a level equal to the bursting pressure of the pressure relief device ELKXA14. This will
trigger the pressure relief device followed by gas deflating through the exhaust 1.
The protective cover 9 and cover plate 2 secures the pressure relief device 6 against acci
dental mechanical damage from outside and from weather in the case of outdoor instal
lations.
The pressure relief device ELKXA14 attachment usually contains an adsorber 5. The ad
sorber gathers moisture in the gas compartment and thus maintains the quality of the

Template: XA_1HC0038828_AAen 78
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

SF6 gas. In some gas compartments e.g. in the circuit breaker ELKSP14 the adsorber
material may be placed in different containers.

Adsorber
An adsorber 5 is installed in any gas compartment to withdraw moisture from the SF6
gas. Moisture in the SF6 gas may origin from diffusion into the gas compartment or mois
ture of built−in components. The adsorber material is enclosed in a filter cage.

6.11.3 Maintenance

Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".

Maintenance work
The maintenance work on the pressure relief device is limited to protection of the hous
ing against corrosion, and checking the protective plate. Maintenance can be carried out
without opening of the gas compartment.

6.11.4 Overhaul

Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.

Intervals
The intervals for overhaul work are summarized in the operating instructions for the
installation in the form of a table. On expiry of the interval, please contact our service de
partment.
S During overhaul work in the gas compartment, the adsorber must be replaced
S In case of damage, the complete pressure relief device is replaced

Template: XA_1HC0038828_AAen 79
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.11.5 Overhaul work

Replacement of pressure relief device and adsorber

Before starting overhaul work, the part of the installation affected must be shut
Danger down and made safe according to the operating instructions for the installation.

The gas pressure in adjacent gas compartments must be lowered. See operating in
structions for the installation, document 1HC0028459 Manual Handling Sulphur Hexa
fluoride SF6".
Regeneration of the adsorber material is theoretically possible, but not intended.
Information

Repair and disposal


Gas compartment and reusable parts must be cleaned according to instructions for
treatment, in document (HASV600715) Corrosion Protection and Sealing".
All replaced parts must be cleaned according to instructions for treatment. The cleaned
parts must be disposed according to local regulations.

Disposal of decomposition products


The decomposition products are electrically nonconductive but in contact with
Warning moisture (open parts of installation) can form toxic and corrosive substances (hy
drogen fluoride HF).
Decomposed SF6 gas has a pungent odour already in low concentrations. It irritates
eyes, mucous membranes, the respiratory tract and other unprotected skin surfaces.
The working area must be well ventilated.
On disposal of decomposition products, the local safety regulations must be followed.
Decomposition products must be neutralized before disposal or incineration. For this
purpose the following working materials are required:
S Protective equipment, soap and water
S Calcium chloride hexahydrate (CaCl2 − 6 H2O)
S Balance with 100 g graduation
S Utensils in polypropylene or polyethylene
S Flask (size determined by:
1 part decomposition products + 1.5 parts water + 250 g calcium chloride hexahy
drate per kg water
S Bucket with volume scale
S Flask with screw cap and wide neck and
S Matching funnel

Procedure
1. Take safety precautions.
2. Empty decomposition products into bucket and note volume.
3. Pour contents of bucket into flask using funnel.
4. Fill bucket with 1.5 times the amount of water and determine weight.
5. Weigh out 250 g calcium chloride hexahydrate per kg water.
6. Pour water stepwise into flask and then allow cooling (on addition of water, the solu
tion heats up and foams).
7. Add calcium chloride hexahydrate to the flask to neutralize and allow standing for
24 hours. Then close the flask tightly with the cap.

Template: XA_1HC0038828_AAen 80
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

8. As a personal protective measure: wash face, neck, arms and hands with soap and
copious amounts of water.

Fig.35: Parts to be replaced on maintenance (left) and on damage (right)

Assembly
Adsorbers are dispatched and stored in special packing. Before assembly, check
Caution the enclosed humidity indicator for color changes (see instructions for storage).
After assembly of the adsorber, the gas compartment must be evacuated within two
hours.
The unlimited operation of the installation requires the observance of the specified oper
ating materials. The operating materials and any additional measures are marked with
capital letters in brackets and explained in the instructions for treatment. As a general
rule, use only new seals.

Corrective maintenance
The components treated in these operating instructions require no special measures of
corrective maintenance.
Checks based upon intervals are, however, indispensable for those parts of the installa
tion, which are not monitored, e.g earthing connections or flange connections. See the
operating instructions for the installation.

Template: XA_1HC0038828_AAen 81
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.12 Barrier and support insulator

Barrier Insulators
The GIS type ELK14 is sectionalized into individual gas compartments by means of gas
tight barrier insulators. Therefore, the impact of extensions or internal faults on the overall
installation is reduced to a minimum and control, supervision and maintenance are
greatly eased. All flange connections are sealed by means of ageresistant Orings. Due
to the gastight design of the insulator no gas leakage between components can occur.

Support Insulators
Support insulators are used to mechanically support the conductors. They are mainly
used for long SF6 busduct connections. Fig.36 shows both types of insulators.

1 2 6 1 2 3 4 5 6

1 2 3 4 6 1 3 2 4 5 6

2
2 2
2

1 − Insulator 4 − Bolts
2 − Inner armature 5 − Through holes
3 − Outer armature 6 − Groove for gaskets

Fig.36: Barrier insulator (left) and support insulator (right)

Intermediate rings
Intermediate rings are used to connect two standard flanges if no insulator is present.
It provides the same dimensions and sealing systems as the insulators but does not sup
port the conductor or other active parts inside.

Template: Insul_1HC0045283_AAen 82
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.13 Bushing with composite insulator type ELKHB14

6.13.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
The bushing can be attached to the following component:
S Air splitup

Symbol
The bushing with composite insulator type ELKHB14 does not have a specific symbol.

Nameplate
The installation specific data are given on the nameplate of the bushing ELKHB14.

Technical data
The installation specific data are given in document Project Specific Data".

Designation Unit Value

Max. bending load kN 5

Weight without SF6 kg 100

SF6 volume dm3 131

Tab.14: Technical data for bushing ELKHB14

Template: HB_1HC0045284_AAen 83
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6
2
3

1 − Bushing 6 − Shield electrode


2 − Conductor tube 7 − Shield electrode
3 − Contact support 8 − Glassfibre reinforced tube
4 − Upper flange 9 − Silicone shield
5 − Current connection *) Adjacent component

Fig.37: Bushing ELKHB14

6.13.2 Description
Bushings ELKHB14 serve as links for the current transfer between the gasinsulated
switchgear and the airinsulated components of the openair transmission line. They
have the task of transferring the current with low losses and simultaneously of ensuring
the dielectric strength both in the gas compartment and in the air under the most extreme
environmental conditions.

Template: HB_1HC0045284_AAen 84
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

The bushing (1) consists of a conductor tube (2) that transmits the current from contact
support (3) via the rigidly connected upper flange (4) to the current connection (5) (stan
dard is a pin). Here, connections to the open air can then be connected directly or via
an adapter.
The two shield electrodes (6) and (7) are used to control the electrical field. The glass
fibre reinforced tube (8) is used for mechanical and dielectric stability. The silicone shield
(9) mounted on it guarantees the electrical air insulation such as clearance and creep
age and also provides optimal protection against environmental influences such as ex
treme contamination and salt fog.
The bushing ELKHB14 with composite insulating Fig.37 is a gasinsulated bushing in
accordance with IEC 60137.
On account of the simplicity of its design, the bushing ELKHB14 is maintenancefree.
The bushing ELKHB14 includes a control electrode (7) for field grading in the transition
between the bottom flange and outside air. Therefore no measuring adapter is assigned.
The current connector (5) is round and is made of aluminium.
As a protection against corrosion, all flange joints and other sealing positions to the gas
compartment are coated with grease through lubricating nipples.

6.13.3 Maintenance

Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".

Maintenance work
The maintenance work of the bushing ELKHB14 is limited to protection of the enclosure
against corrosion. Maintenance can be carried out without opening of the gas compart
ment.

6.13.4 Overhaul

Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be followed.
With improper treatment, reliable operation of the installation is not assured.

Overhaul work
The bushing with composite insulator ELKHB14 does not need overhauling.

Template: HB_1HC0045284_AAen 85
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.14 Voltage transformer ELKPI04

6.14.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.

Symbol
Voltage transformer ELKPI04 does not have a specific symbol.

Nameplate
The installation specific data are given on the nameplate of the voltage transformer
ELKPI04.

Technical data
The installation specific data are given in document Project Specific Data".

Designation kV 245 / 253

Weight without SF6 kg ca. 1050

Weight of SF6 filling kg 32.5

SF6 volume ltr ca. 760

Tab.15: Technical data for inductive voltage transformer type ELKPI 04

Template: PI_1HC0045285_AAen 86
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

8
View “A” 1 A
9
5
3 2 4

6 7

1 − Terminal box with terminals for 10mm2 5 − Earthing connection 2xM12, 20 mm


cross section (Phoenix UK 16) depth
2 − Bursting disc 6 − Barrier insulator
3 − Cable gland standard 8xPG21 und 7 − Lifting lugs ∅ 50 mm
1xPG11 8 − Nameplate
4 − Gas connection ABBSystem, 1 x angle 9 − Additional nameplate if required
type

Fig.38: Inductive voltage transformer type ELKPI04

6.14.2 Description
Inductive voltage transformers are low power transformers in which the secondary volt
age is proportional to and in phase with the primary voltage for all practical purposes.
The voltage transformer of the GIS transforms the network voltage to be measured into
a secondary voltage that can be fed to measuring and protective devices. At the same
time, the primary and the secondary windings are galvanically separated from each
other.
The inductive voltage transformer type ELKPI04 (Fig.38) complies with the relevant
IEC and IEEEstandards. Usually it has two secondary windings and one auxiliary wind
ing for earth fault detection. The ratings are projectspecific.
The inductive voltage transformer is a sealed gas compartment (6) with two gas connec
tions (4), an SF6 gas moisture filter and a bursting disc assembly (3). The terminal box
(1) attached to the side wall of the enclosure accommodates wiring, terminals and fuses.
The inductive voltage transformer is delivered filled with SF6 at a pressure of
Caution 150 kPa. Do not evacuate!

6.14.3 Connection / commissioning


During installation the barrier insulator (2) of the voltage transformer must not be dis
mounted, as the voltage transformer is already being shipped with a SF6 prefilling
(Fig.39). For the installation of the voltage transformer, a lifting device with a minimum
lifting capacity of 1500 kg is required.
The inductive voltage transformer (Fig.39) is shipped filled with SF6 at a pressure
Caution of 150 kPa. Do not evacuate!

Template: PI_1HC0045285_AAen 87
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

Gas compartments
During connection or commissioning work, gas compartments must be opened and en
tered. For this, the regulations in document 1HC0028459 Manual Handling Sulphur
Hexafluoride SF6" have to be executed. Before reassembling the affected components,
the regulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6"
have to be followed. With improper treatment, reliable operation of the installation is not
assured.

1
1 − Connection flange
2 − Barrier insulator
3 − Gas fitting

Fig.39: Voltage Transformer

6.14.4 Feeder Module with integrated Disconnector/Earthing Switch


Fig.40 shows the connection of the voltage transformer to a feeder module with inte
grated disconnector/earthing switch. The voltage transformer is connected in this case
to the GIS side.
Installation of the Voltage Transformer to the GIS side
1. Connect the plugin contact (2) to the barrier insulator (1) (Fig.40)
2. Place an oring (4) in the groove of the barrier insulator (1) on the voltage trans
former
3. Lower the voltage transformer straight and carefully into the connection flange (5)
using a lifting device with a minimum lifting capacity of 1500 kg
4. Make sure that the plugin contact (2) smoothly slides into the contact pieces(3)
without jamming; check correct fitting of the oring (4)
5. Bolt the voltage transformer flange and the connection flange (5) together with the
specified torque
6. Carry out necessary gas handling

Template: PI_1HC0045285_AAen 88
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

3 2
1

1 − Barrier insulator 4 − 0-Ring


2 − Plug-in contact cpl. 5 − Connection flange
3 − Contact piece

Fig.40: Connection of voltage transformer

Fig.41: Voltage transformer installed at outgoing disconnector

Template: PI_1HC0045285_AAen 89
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

Fig.42: Voltage transformer installed at exit splitup

6.14.5 Maintenance

Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

Intervals
The intervals for maintenance work are given in chapter 5,Maintenance, inspection and
overhaul".

Maintenance work
The maintenance work of the voltage transformer ELKPI04 is limited to protection of the
enclosure against corrosion. Maintenance can be carried out without opening of the gas
compartment.

Template: PI_1HC0045285_AAen 90
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.14.6 Overhaul

Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in docu
ment 1HC0028459 Manual Handling Sulphur Hexafluoride SF6"have to be followed.
With improper treatment, reliable operation of the installation is not assured.

Overhaul work
The voltage transformer ELKPI 04 does not need overhauling.

Template: PI_1HC0045285_AAen 91
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.15 Exit splitup ELKHKY14 and cable connection (IEC) ELKHK14

6.15.1 General information

Application
The components described are used solely for power transmission and distribution, as
well as for the coupling of parts of the grid. Any other application is not envisaged and
would not conform to the intended purpose.
The exit splitup ELKHKY14 can be attached to various components.

Symbol
The exit splitup ELKHKY14 and cable connection ELKHK14 do not have a specific sym
bol.

Nameplate
The exit splitup ELKHKY14 and cable connection ELKHK14 do not have a specific
nameplate.

Technical data
The installation specific data are given in document Project Specific Data".

Designation Unit Dry type Fluid-filled type

Installation length mm 1400 1740

Mass (basic equipment)


kg 665 716
without insulator

Volume of SF6 gas compartment dm3 824 905

Tab.16: Technical data for exit splitup ELKHKY14 and cable connection ELKHK14

Template: HK_1HC0045286_AAen 92
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

1 5

5
5

1 − ELKHKY14 dividing piece 4 − Cable (cable supplier)


2 − Cable end box connection 5 − Insulator
3 − ELKHK14 cable connection (IEC)

Fig.43: Exit splitup ELKHKY14 and cable connection ELKHK14 with


IEC standard dimensions

6.15.2 Description
The exit splitup ELKHKY14 and the cable connection ELKHK14 provides an interface
between a gasinsulated switchgear and a highvoltage cable. It is built of an ELKHKY14
dividing piece with active parts, an enclosure specifically designed to hold the cable con
nection enclosure and a base plate. The base plate is removed onsite when inserting
the cable.
The scope of supply includes all items of the cable sealing end and all necessary mount
ing parts but not the cable itself (No.4 in Fig.43).
Before commencing mounting all delivered parts should be checked for completeness
and signs of damage. Any damaged parts must be replaced.
The maximal mechanical force transversal during mounting work and during op
Caution eration, must not exceed 2000 Nm.

The handling of insulator surfaces, Orings, sealing nuts and sealing surfaces is
Information described in detail in chapter 8Installation of GIS".
Due to the variety of cable suppliers, there are different types of cable connection ELK
HK14 available. Each type needs specific work to be conducted during installation.

Template: HK_1HC0045286_AAen 93
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

IEC long: 960 mm


IEC short: 620 mm

Fig.44: Exit splitup ELKHKY14 and cable connection ELKHK14 with


IEC standard dimensions
The exact dimensions for the cable supplier are given in the interface drawings
1HC0035277 (IEC short, dry type") and 1HC0035265 (IEC long, fluidfilled type").

6.15.3 Connection / commissioning


For shipment the exit interface ELKHKY14 is filled with N2 at a pressure of 150kPa!
Caution Vent the gas to atmosphere via the valve before removing the transport cap!
The exit splitup ELKHKY14 and cable connection ELKHK14 have to be pressurized to
the rated pressure before energization.

6.15.4 Maintenance

Notes
You may only carry out activities listed under Maintenance" when you have read
Warning and understood the notes; in particular the safety notes at the beginning of the op
erating instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage caused by improper han
dling.

6.15.5 Maintenance work

Intervals
The intervals for maintenance work are given in chapter 5Maintenance, inspection and
overhaul".

Maintenance work
The maintenance work on the exit splitup ELKHKY14 and cable connection ELKHK14
is limited to protection of the housing against corrosion. Maintenance can be carried out
without opening of the gas compartment.

Template: HK_1HC0045286_AAen 94
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Description of the Components

6.15.6 Overhaul

Notes
You may only carry out activities listed under Overhaul" when you have read and
Warning understood the notes; in particular the safety notes at the beginning of the operat
ing instructions and you fulfil the conditions stated therein. Otherwise, the
manufacturer will decline all responsibility for damage or injury caused by im
proper handling.

Gas compartments
During overhaul work, gas compartments must be opened and entered. For this, the reg
ulations in document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have
to be executed. Before reassembling the affected components, the regulations in chap
ter document 1HC0028459 Manual Handling Sulphur Hexafluoride SF6" have to be fol
lowed. With improper treatment, reliable operation of the installation is not assured.

Overhaul work
The exit splitup ELKHKY14 and cable connection ELKHK14 do not need overhauling.

Template: HK_1HC0045286_AAen 95
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Transport, Storage and Treatment

7 Transport, Storage and Treatment

This chapter provides information on transport, storage and treatment of GIS equip
ment.

7.1 Transport of GIS equipment

7.1.1 Packaging of GIS equipment

Packaging requirements
The following factors must be taken into account when packaging equipment for ship
ping:
S stresses occurring during multiple transhipments
S climatic conditions
S shipping routes
S duration of shipment (preservation, environmental factors)
S storage after shipment
S bottoms of containers must be designed to carry the full load of the package equip
ment
S packaging must be able to withstand stresses caused by weight and by forces oc
curring during transportation
S packaging must be geared to the intended type of transportation and designed to
preclude any damage to the equipment
S packaging / equipment may be provided with shock indicators

7.1.2 Types of packaging

Wooden support/skid and protective sheeting


S Only for shipment by truck, by rail or by airway
S Not suitable for storage
S To receive on crane use only the craneeyelets of the switchgear!

Wooden box
S For shipment by truck, rail or ship
S Suitable for storage

Container
S For shipment by truck, rail or ship
S Suitable for storage

Requirements for container


S Container must have nailable wooden floors

Types of container
S Not specified.

General container requirements


S Containers holding dangerous goods must be CSCcertified
S Containers bearing the ACEP mark are approved for unrestricted use

Template: Tr_1HC0024456_AAen 96
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Transport, Storage and Treatment

S Containers must be checked for proper technical condition prior to shipment (Con
tainers provided with the ACEP mark have been inspected by the manufacturer)

Container data
Container data concerning weight and dimensions should, as far as possible, be geared
to the related data for the intended means of transportation.

Environmental factors
Equipment may be shipped at temperatures in the range of −30 °C to +60 °C. The pack
aging must ensure that all items of equipment are positively protected against any direct
contact with water. The packing shall provide adequate protection against dirt, insects
and animals.

Preservation
The shipment within Europe, specifications concerning equipment preservation shall be
included in the order. If no preservative measures are specified, the freight will be pack
aged in the usual manner.
The preservation required depends on the method of transportation, the storage classifi
cation and the storage period.
Storage requirements and classifications are described in detail in document
HASV600715 Corrosion Protection and Sealing".
In the case of ocean transport, preservation of the equipment is mandatory, since ELK14
components could be damaged by the associated exposure to humidity.
Protection against condensation of humidity is provided for a transportation period of
up to 12 months. If this period is exceeded, adequate measures must be taken to prevent
the formation of condensation water.
The packaging may be monitored by means of moisture indicators.
If the expiry date of equipment preservation falls within the period before or during ship
ment, or within the expected storage period, persons responsible for shipment / storage
shall be informed in due time so that appropriate measures can be taken.

Sealing of equipment
For transportation the equipment is filled with N2 to a absolute pressure of 150 kPa.
The gas pressure shall not drop below 110 kPa during shipment and storage.
All open flanges must be sealed with a shipping cover.
Shipping covers are chosen according to 1HC0021062.

Packing and unpacking of equipment


Packing and unpacking of equipment shall always take a place in a dry
(airconditioned) environment.
When unpacking switchgear components, check shock indicators on packaging /
equipment, if provided.

Securing of equipment
Freestanding parts shall be provided with appropriate support structures.
All loads shall be prevented from slipping by lashing and blocking. Means of securing
equipment in place: Chains, lashes, ropes, square timber and wooden wedges.
Make sure that loads are evenly distributed.
The sidewalls of shipping containers shall not be subjected to any loads. Only container
bottoms are designed to withstand loading and possess sufficient stability.
The circuit breaker shall be shipped only in its upright (operating) position.

Template: Tr_1HC0024456_AAen 97
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Transport, Storage and Treatment

Shipping marks
Markings provided on the packaging shall include fixing and hitching points for trans
portation and hoisting, total weight, installation point of equipment components, and the
packed unit’s centre of gravity.
The place of delivery shall be marked on the packaging in accordance with the data pro
vided in the order.
When dangerous goods are shipped, applicable regulations (of the countries of origin
and destination as well as transit countries) shall comply with.

7.1.3 Shipping of GIS equipment

Loading and lifting facilities


To prevent equipment and parts from being damaged during loading and lifting opera
tions, the facilities shall be suitable for this purpose in terms of intended applications and
loadcarrying capacities.
When moving or lifting packed equipment, make sure that no other than the fixing and
hitching points marked on the packaging are used.
Switchbays and components that are not packed may be lifted at suitable hitching
points, provided that every precaution has been taken to prevent these parts from being
damaged in the process.
The shipping units’ centre of gravity markings shall be taken into account to prevent the
units from tipping over.

Means of transportation
The means of transportation is selected so as to ensure that the shipping units will be
subjected to the smallestpossible amount of vibration. Any damage to the equipment
must be prevented by all means.

Forces and stresses in transportation


The admissible forces on GIS equipment are specified in Fig.45 and Tab.17.
During loading and lifting operations higher values may occur.
Information
FL
FQ

FV

direction

Fig.45: Forces and stresses in transportation

FL FV FQ

Railway 4.0 g 0.5 g 0.4 g

Road 1.0 g 2.0 g 0.6 g

Ship 0.4 g 2.0 g 0.8 g

Aircraft 4.0 g 0.5 g 0.4 g

Tab.17: Forces in g (g = Acceleration due to gravity)

Template: Tr_1HC0024456_AAen 98
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Transport, Storage and Treatment

7.1.4 Inspections to be carried out on equipment

Before shipment
Prior to closing the shipping containers, make sure that the equipment to be shipped is
properly secured and without damage.
Check shipping containers for proper technical condition. This is particularly important
in the case of freight containers.

After shipment
Check shipping container for any damage before opening.
After opening a container, immediately check the equipment for external damage and
completeness.

7.1.5 How to cope with irregularities

During shipment
Any damage occurring on the packaging in transit shall, as far as possible, be repaired
immediately. If this cannot be done, appropriate measures shall be taken at once to pre
clude any further damage to the cargo.
All irregularities occurring during shipment as well as any remedial action taken shall be
documented and reported see form Receiving inspections" below.

After shipment
In the event of any damage detected on the packaging or equipment, the insurance
company should be called in and the damage should be assessed and recorded by an
authorized agent.
Photographs should be taken of any damaged packaging to serve as evidence at a later
time.
Any packaging that is damaged or soaked shall under no circumstances be used for pro
longed storage of equipment.
Any corrective action taken with regard to packaging or equipment preservation shall
be recorded in detail. All materials used for these measure must have been tested and
approved.

Standards and regulations


The most important standards and regulations are:
− DIN 50 010 climatic definitions
− DIN 50 019 climates with regard to technology
− DIN 55 402 markings
− DIN 55 405 packaging
− DIN ISO 668 freight container
These standards also make reference to other pertinent standards, which must be ob
served as well.
Additional regulations, guidelines and instruction sheets have been issued by the follow
ing organizations:
S German Lloyd (GLRegulations and codes of practice)
German Lloyd (GLVorschriften und Richtlinien)
S Association for Rationalization in Packaging/Packaging Consulting and Research
Office (RGV / BFSV Instruction sheets)
Rationalisierungsgesellschaft Verpackung/Beratungs und Forschungsstelle Ver
packung (RGV / BFSVBetriebsblätter)
S Association of german Engineers (VDIRegulations and Guidelines)
Verein deutscher Ingenieure (VDIVorschriften und Richtlinien)

Template: Tr_1HC0024456_AAen 99
Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Transport, Storage and Treatment

These regulations, guidelines, instruction sheets and the relevant standards must be
equally observed.
Standards and regulations of the country of destination shall be considered, if applica
ble.
Applicable regulations and guidelines issued by ABB shall also be observed.

Template: Tr_1HC0024456_AAen 100


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Transport, Storage and Treatment

7.1.6 Receiving Inspection


All gas compartments of the individual GIS transport units are filled in our factory
Information with N2 to a pressure of approximately 150 kPa. The only exception is the inductive
voltage transformer that will be delivered ex works filled with SF6 to a pressure of
approximately 150 kPa. In order to detect transport damages as early as possible,
check the pressure upon arrival of the equipment at site. Gas compartments that
are not pressurized have to be checked for gas tightness prior to assembly of the
transport units.

Protocol for Receiving Inspection Page_____of_____

Number of Storage Date Checked by Remarks, Measures, Checks


Transport Class
Unit

Tab.18: Receiving Inspection

Template: RecInsp_1HC0024457AAen 101


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Installation of GIS

8 Installation of GIS

These instructions refer to the installation of a GIS and to all works that require opening
a gas compartment.
All the relevant instructions for safety and accident prevention as given in chapter
Warning 3 Information and Safety Notes" must be observed during the installation works.

It must be possible to clean the shoes before entering the immediate working area. The
working clothes must be made of nonfluffing material.

8.1 Preparation of the installation area

Securing the installation area


The installation area must be secured against entry of unauthorized personnel.

Power supply
The following power supply outlets must be made available in the installation area:
S 1phase AC outlets (16 A) and
S 3phase AC outlets (16 A)

Walls and ceilings


S Walls and ceilings have to be in a condition, that neither dirt nor plaster might fall
or rub off
S If necessary, apply a surfacebinding coat of paint
S Formation of condensation water on the ceiling has to be prevented under any cir
cumstance

Floor conditions
S The floor in the installation area must have a firm surface
S It must be possible to keep the floor dustfree with a vacuum cleaner

Outdoor installation
S In case of an outdoor installation of the GIS or of GIS components, open gas
compartments must be protected from the entry of dust or humidity (e. g. by means
of installation covers, tarpaulins etc.)

Room for repair works


A room must be provided for necessary repair works that is:
S weather protected
S lockable
S separated from the installation area

8.1.1 Cleaning
SF6 can loose its arc quenching and insulating properties when contaminated. For
Caution this reason, all surfaces and components that will be in contact with SF6 have been
thoroughly cleaned in our factory and have been installed under conditions of ut
most cleanliness. When working on open devices or gas compartments, avoid the
entry of or contact with dirt, sweat and humidity at any time.
Water, acid contamination and oxygen (especially when simultaneously present) can
cause corrosion that might have a negative impact on the mechanical function of the GIS
components.

Template: Inst_of_GIS_1HC0024550_AAen 102


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Installation of GIS

Water, especially when combined with acid contamination, can reduce the dielectric
strength of the GIS due to condensation at low operating temperatures and high pres
sure. For this reason, the degree of contamination has to be limited to a level that corro
sion and/or condensation are of no significance.

Installation area
Prior to opening a gas compartment, thoroughly clean and vacuum clean the installation
area, especially in the immediate vicinity of the flanges to be connected. Avoid dust dis
turbance in the installation area.

Carry out a visual inspection of the interior of an open gas compartment.


Information

Rub the insulators and all Teflon parts with a cloth moistened with a suitable clean
Caution ing agent. Cleaned insulators may only be touched wearing disposable latex
gloves. Do not use water for cleaning under any circumstance!

Cleaning the GIS components


Immediately before assembly, clean all loose metal parts and subassemblies that have
to be installed and all contacting and sealing surfaces.

Material Cleaning agent

S Flange sealing surfaces and orings


S Contacting surfaces of the conductors
S Connectors S Rivolta M.T.X. 60 (preferably)
S Links S Ethanol 99
S Screens S Isopropanol, purity min. 99%
S Insulators
S Teflon parts

S painted surfaces of the GIS S pure water or soap suds (0.5%)

S Silicon shielding of the bushing S Wacker SiliconOilemulsion E 1044

Tab.19: Material and cleaning agent


Use a nonfluffing cloth for cleaning, moistened with the cleaning agent. Rub all parts
with this cloth. Take note of the following:
S Try to avoid touching the components internal to the gas compartments
S Use disposable gloves for cleaning
S Use a spray bottle to prevent contamination of the cleaning agent
S Cleaning cloth must not contain any substances that could dissolve in the cleaning
agent
S Moisten the cloth so that the cleaning agent does not drip or spill
S Remove residues of the cleaning agent with a clean cloth

Cleaning the painted GIS


Painted surfaces are only allowed to be cleaned by means of pure water or soap suds
(0.5%).

Cleaning the bushing with composite insulator


Use a nonfluffing cloth for cleaning, moistened with the cleaning agent Wacker Silicon
Oil emulsion E 1044. Rub all silicon shieldings with this cloth. Take note of the following:
S Cleaning cloth must not contain any substances that could dissolve in the cleaning
agent

Template: Inst_of_GIS_1HC0024550_AAen 103


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Installation of GIS

S Moisten the cloth so that the cleaning agent does not drip or spill
S Remove residues of the cleaning agent with a clean cloth

8.1.2 Flange connections


Once the transport covers have been removed, the installation of the flanges must be
completed without interruptions.
If interruptions cannot be avoided, open flanges must be covered with a clean plastic
foil. This instruction must also be observed if an insulator is mounted on the flange.

Sealing surfaces
S Check sealing surfaces for scratches or similar damages
S Even out any scratches with fine sand paper
S Remove the dust with a vacuum cleaner
S Clean the sealing surfaces

Orings
Orings have to be cleaned before they are installed, see document HASV600715 Cor
rosion Protection and Sealing".
Do not install any Orings that show damages or deformation from previous use.
Before closing a flange connection, clean the immediate vicinity and all accessible parts
of the components to be connected with a vacuum cleaner. Do not touch the active parts
and the insulators with the vacuum cleaner’s nozzle.

Template: Inst_of_GIS_1HC0024550_AAen 104


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Installation of GIS

8.1.3 Tightening torque for bolts


The following tightening torques are valid for nongreased bolts in threads and holes.
Any deviations from these values are indicated in the assembly drawings.

Tightening torque in Nm
Thread
Steel/8.8 *) Steel/A270 **) Aluminium ***)

M4 2,9 − 1,5

M5 6 5,2 3

M6 10 7,8 5,5

M8 25 19,5 14

M10 49 38,3 26

M12 86 67,2 45

M16 210 147,6 100

*) Extract from NB305080, tolerance "3%


**) Extract from GPDT049615, tolerance "3%
***) Extract from GPFA820006, tolerance +20% −0%, independent from the material
of the bolts

Tab.20: Tightening torques for nongreased bolts

8.2 Filling of gas compartments


All works associated with the handling of SF6 are described in detail in document
Information 1HC0028459 Manual Handling Sulphur Hexafluoride SF6".

Transport units
All gas compartments are delivered ex works filled with N2 at a pressure of approximately
150 kPa. The exception from this rule is the inductive voltage transformer which will be
delivered ex works filled with SF6 at a pressure of approximately 150kPa.
The enclosures of inductive voltage transformers may not be opened or evacuated
Caution without the prior consent of the manufacturer!

After the installation of the GIS, the gas compartments are initially filled up to a pressure
of 150 kPa only in order to check for gas tightness. The GIS must not be filled with SF6
up to its rated filling pressure before all installation works have been completed.

Template: Inst_of_GIS_1HC0024550_AAen 105


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Installation of GIS

8.3 Earthing of GIS equipment


Earthing" is defined as the entirety of means and procedures associated with the earth
ing of equipment. Earthing means to connect a conductor via an earthing system to
earth.
Earth" refers to both, the earth as a location and the earth as a substance such as hu
mus, clay, sand, gravel and rock. The earth is a conductor whose potential outside the
influence of earthing systems is considered to be zero. The Reference Earth" (neutral
earth) is defined as a part of the earth, especially of its surface, outside the influence of
an earthing system in which between two random points no voltages deriving from the
earth current can be measured.
Earthing system" is defined as the entirety of electrically connected earthes, metal parts
acting similarly (e g. pole bases, armatures, metal cable sheathing) and earthing leads.
Earth electrode" is a conductor that is embedded in the ground and electrically con
nected to it, or a conductor embedded in concrete that is in contact with the earth over
a large area (e. g. foundation earth).
Earthing lead" is defined as an electrical lead laid either outside the earth or insulated
in the earth that connects a GIS part to be earthed with the earth. If a disconnecting link,
a disconnector or a Petersen coil is installed between a center point or an outer conduc
tor and the earth, only the connection between earth and the earthing terminal of such
a device is considered as an earthing lead.

The installation of the GIS earthing and the earthing leads shall be strictly in ac
cordance with the projectspecific earthing layout diagrams and the earthing
plans in the projectspecific part of this documentation!

Template: Inst_of_GIS_1HC0024550_AAen 106


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Troubleshooting

9 Troubleshooting

In this chapter, some advices for quick onsite troubleshooting are provided. Practical
experience has shown that strict adherence to the recommendation of this instructions
will ensure the best proceed to restore the function of the switchgear.
These instructions are based on the present technical design. ABB reserves the right to
make any technical changes.
If an existing problem is not identified by the reasons given below or cannot be solved
by applying the remedial measures, please contact our service department.

9.1 Hydraulic operating mechanism of circuitbreaker

Trouble Reasons Remedical Measures

Operating mechanism is not charged MCB* tripped Switch the MCB* on


automatically Supply voltage lacking Secure the supply voltage
Motor defective Replace the motor
Coal brushes worn out Replace the coal brushes

Motor is running but the disc spring as Pressure release screw in the position Close the pressure release screw
sembly is not tensioned open"
Changeover valve in intermediate Press the rubber cap of the OPEN
position (only HMB1 and HMB1S) solenoid
Pump defective Replace the pump
Oil level too low Refill the oil
Filter clogged Exchange the filter

Operating mechanism does Tripping voltage lacking Secure the tripping voltage
not trigger Coil defective Replace the coil
Auxiliary switch does not transmit the Adjust the auxiliary switch
command
Auxiliary switch defective Replace the auxiliary switch

Corrosion in the operating mechanism Heating MCB* tripped Switch the MCB* on
housing Heating voltage lacking Secure the heating voltage
Heating plate defective Replace the heating plate
Mechanism housing not tight Check the seals of the operating
mechanism housing and if necessary
replace them

Operating mechanism too often Pressure release screw not in the Close the pressure release screw
repumps position closed"
(On an average more than Internal leak Operate the operating mechanism
20 times per day / 600 times several times
per month)
If the trouble continues: Perform the leak
test and if necessary inform ABB.

*) MCB = mini circuit breaker

Tab.21: Troubleshooting operating mechanism of circuit breaker

Template: TrSh_1HC0045287_AAen 107


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Troubleshooting

9.2 Circuit breaker

Fault Cause Remedy

Low SF6density Alarm of pilot relay Check leakage rate:


Low SF6pressure" <1%/year is normal
S filling up gas.
>1%/year:
S Check flange seals and change
the faulty seal
S When sealing system is ok,
check electric circuit

Circuit breaker is Alarm of pilot relay Check SF6pressure


locked Circuit breaker locked" Check charging condition of oper
ating mechanism
Check electric circuit

Tab.22: Troubleshooting circuit breaker

9.3 Disconnector / earthing switch

Fault Cause Remedy

Low SF6density Alarm of pilot relay Check leakage rate:


Low SF6pressure" <0.5 % / year is normal
S filling up gas.
>0.5 % / year:
S Check flange seals and change
the faulty seal
S When sealing system is ok,
check electric circuit

Operating mecha MCB* tripped Switch on MCB*


nism not running Supply voltage locking Secure supply voltage
Motor defect Change motor, check limit switch
Conductor defect Change conductor

No ON/OFF MCB* tripped Switch the MCB* on


Signal Control voltage lacking Secure the control voltage

Tab.23: Troubleshooting disconnector / earthing switch

9.4 Earthing switch with short circuit making capacity

Fault Cause Remedy

Operating mecha MCB* tripped Switch on MCB*


nism not running Supply voltage locking Secure supply voltage
Motor defect Change motor, check limit switch
Conductor defect Change conductor

No ON/OFF MCB* tripped Switch the MCB* on


Signal Control voltage lacking Secure the control voltage

*) MCB = mini circuit breaker

Tab.24: Troubleshooting earthing switch with short circuit making capacity

Template: TrSh_1HC0045287_AAen 108


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Troubleshooting

9.5 Voltage transformer

Fault Cause Remedy

Low SF6pressure Alarm of pilot relay Check leakage rate:


Low SF6pressure" <0.5 % / year is normal
S filling up gas.
>0.5 % / year:
S Check flange seals and change
the faulty seal
S When sealing system is ok,
check electric circuit

Tab.25: Troubleshooting voltage transformer

9.6 Other switchgear modules

Fault Cause Remedy

Low SF6pressure Alarm of pilot relay Check leakage rate:


Low SF6pressure" <0.5 % / year is normal
S filling up gas.
>0.5 % / year:
S Check flange seals and change
the faulty seal
S When sealing system is ok,
check electric circuit

*) MCB = mini circuit breaker

Tab.26: Troubleshooting other switchgear modules

Template: TrSh_1HC0045287_AAen 109


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Conversion Tables

9.7 Conversion Tables

9.7.1 Temperature

°C (Degree Celsius) °F (Degree Fahrenheit)* K (Kelvin) **

0° 32 ° 273.16

15 ° 59 ° 288.16

20 ° 68 ° 293.16

25 ° 77 ° 298.16

30 ° 86 ° 303.16

*n °C = ( 1.8 x n + 32) °F
**n K = n − 273.16 °C

Tab.27: Temperature

9.7.2 Tightening Torques

Nm (Newtonmeter) lbf x ft kpm (Kilopondmeter)

1 0.7376 0.102

1.356 1 0.1383

9.807 7.233 1

Tab.28: Tightening Torques

9.7.3 Absolute Pressures

kPa MPa bar psi (Pound per Torr


(KiloPascal) (MegaPascal) Square Inch)*

0.133322 0.0001333 0.001333 0.01934 1

6.8948 0.0068948 0.068948 1 51.715

100 0.1 1 14.504 750.06

420 0.42 4.2 60.917 3150.25

440 0.44 4.4 63.817 3300.26

500 0.5 5 72.520 3750.3

600 0.6 6 87.024 4500.36

620 0.62 6.2 89.925 4650.37

700 0.7 7 101.528 5250.42

* psig = ( n + 14,7) psi (psi may also be expressed as lbf/in2)

Tab.29: Absolute Pressures

Template: ConvTab_1HC0024461_AAen 110


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Conversion Tables

9.7.4 Force

N (Newton) lbf (Pound)

1 0.22481

4.4482 1

Tab.30: Force

9.7.5 Length

mm (Millimeter) in (Inches)

1 0.03937

25.4 1

Tab.31: Length

9.7.6 Weight

kg (Kilogramm) t (Tons metric) lbm (Pound) US t (2000 lbm)

1 0.001 2.20462 0.0011

1000 1 2204.62 1.1

0.4536 0.00045 1 0.0005

507.185 0.907 2142.56 1

Tab.32: Weight

9.7.7 Volume

gal (liquid) gal (dry) m3 ft3


l (Liter)
Gallons Gallons Cubicmeter Cubicfeet

1 0.26417 0.22702 0.001 0.03531

3.78541 1 0.85937 0.0037 0.13368

4.40489 1.16365 1 0.0044 0.15556

1000 264.17 227.02 1 35.31467

28.31685 7.48052 6.42851 0.02832 1

Tab.33: Volume

Template: ConvTab_1HC0024461_AAen 111


Order No.: 1HC0044810 E01 / AA06
Operating Instructions
SF6Gas Insulated Switchgear ELK14
Customer Comments

10 Customer Comments

Dear Customer,
We are permanently looking to further improve the quality of our documentation. For this
reason, we are very much interested in your feedback. Please take the time to fill in the
form below if you notice any incomplete or omitted information, or in case you encounter
typographical errors. Please feel free to make any suggestions how we could further im
prove this documentation to your benefit.
Please find our contact address in the product manual in chapter 1.2
Information

Thank you very much for your help.

Your comments:
Document

Page_____

V
Typographical Error
V
Incomplete Information
V
Omitted Information
V
Amendment
V

Your comments:
Document

Page_____

V
Typographical Error
V
Incomplete Information
V
Omitted Information
V
Amendment
V

Customer ...........................................................................
Installation ...........................................................................
Person in Charge ...........................................................................
Street/P.O. Box ...........................................................................
Town, Postal Code ...........................................................................
Country ...........................................................................

Template: CustCom_1HC0024451_AAen 112


Order No.: 1HC0044810 E01 / AA06

You might also like