You are on page 1of 1

Page

DISCONNECT SWITCH 1 of 1

TEST DATA

Test Data No
                                            
Station 40MW Magapit BESS Facility
                             
                                            
Equipment ID Disconnect Switch
                             
                                            
Date of Test 16-Aug-21
                             
                                            
Make COELME
                             
                                            
Serial No C91278/1, C91278/2, C91278/3
                             
                                            
Type CBD-E
                             
                                            
Rated kV 72.5
                             
                                            
Rated Amp 2000
                             
                                            
Year Manufactured 2020
                             
                                            
                             
I. INSULATION RESISTANCE TESTS
RATING
BREAKER TEST MEASURED RESISTANCE
PHASE PARTS MEASURED (MΩ)/kV
POSITION kV (MΩ) @34 degrees (S, P,
C)
A Line Side 5 184900 36980 S
CLOSED B Line Side 5 738000 147600 S
C Line Side 5 339300 67860 S

Remarks:
Overall Remarks:

Tested by : Concurred by :

Engr. Lyndon De Vera Engr. Christian Paul Liquigan


Contractor - Test Engineer Owner's Representative

TEST INSTRUMENTS: Legend

(Eqpt.ID/Make/Model/SN/ Date
S - Satisfactory
of last calibration)
Insulation Resistance Tester
Brand: Chauvin Arnoux / C.A. 6555 P - Poor

Serial Number: 111065QBH C - Critical

Date Calibrated: January 8, 2021

Witnessed By:

Francis Ortiguez Engr. Edward Baraoed / Engr. Jimmy Tenoria


Siemens Energy, Inc. Fluence Energy, Inc.