Professional Documents
Culture Documents
Disconect Switch 2
Disconect Switch 2
DISCONNECT SWITCH 1 of 1
TEST DATA
Test Data No
Station 40MW Magapit BESS Facility
Equipment ID Disconnect Switch
Date of Test 16-Aug-21
Make COELME
Serial No C91278/1, C91278/2, C91278/3
Type CBD-E
Rated kV 72.5
Rated Amp 2000
Year Manufactured 2020
I. INSULATION RESISTANCE TESTS
RATING
BREAKER TEST MEASURED RESISTANCE
PHASE PARTS MEASURED (MΩ)/kV
POSITION kV (MΩ) @34 degrees (S, P,
C)
A Line Side 5 143800 28760 S
CLOSED B Line Side 5 203100 40620 S
C Line Side 5 170000 34000 S
Remarks:
Overall Remarks:
Tested by : Concurred by :
(Eqpt.ID/Make/Model/SN/ Date
S - Satisfactory
of last calibration)
Insulation Resistance Tester
P - Poor
Brand: Chauvin Arnoux / C.A. 6555
C - Critical
Serial Number: 111065QBH
Date Calibrated: January 8, 2021
Witnessed By: