STAAD.

Pro Report
To: From:

Copy to: Date:


31/01/2022 Ref:
ca/ 574773593.docx
09:26:00

Job Information

Engineer Checked Approved


Name:
Date: 21-Dec-21

Structure Type SPACE FRAME

Number of Nodes 7700 Highest Node 176


Number of Elements 400 Highest Beam 409
Number of Plates 7290 Highest Plate 7699

Number of Basic Load Cases 6


Number of Combination Load Cases 15

Included in this printout are data for:


All The Whole Structure

Included in this printout are results for load cases:


Type L/C Name
Primary 1 EQX
Primary 2 EQZ
Primary 3 DL
Primary 4 FLL
Primary 5 RLL
Primary 6 FFL
Combination 7 GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 8 1
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 9 2
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 10 3
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 11 4
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 12 5
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 13 6
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 14 7
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 15 8
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 16 9
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 17 10
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 18 11
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 19 12
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 20 13
GENERATED INDIAN CODE GENRAL_STRUCTURES
Combination 21 14
GENERATED INDIAN CODE GENRAL_STRUCTURES
15

Primary Load Cases

06/02/2022
Number Name Type
1 EQX Seismic
2 EQZ Seismic
3 DL Dead
4 FLL Live
5 RLL Roof Live
6 FFL Live

Combination Load Cases

Comb. Combination L/C Name Primary Primary L/C Name


7 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
1 4 FLL
6 FFL
8 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
2 4 FLL
6 FFL
9 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
3 4 FLL
6 FFL
1 EQX
10 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
4 4 FLL
6 FFL
2 EQZ
11 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
5 4 FLL
6 FFL
1 EQX
12 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
6 4 FLL
6 FFL
2 EQZ
13 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
14 7
GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
8 1 EQX
15 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
9 2 EQZ
16 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
10 1 EQX
17 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
11 2 EQZ
18 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
12 1 EQX
19 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
13 2 EQZ
20 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
14 1 EQX
21 GENERATED INDIAN CODE GENRAL_STRUCTURES 3 DL
15 2 EQZ

Beam End Force Summary


The signs of the forces at end B of each beam have been reversed. For example: this means that the Min Fx entry gives the largest
tension value for an beam.
Axial Shear Torsion Be
Fx Fy Fz Mx My
Beam Node L/C
(kN) (kN) (kN) (kNm) (kNm)
Max Fx 1 1 17:GENERATED 5.74E 3 -60.798 226.937 -0.538 -175.897
Min Fx 38 27 INDIAN CODE
1:EQX -1.79E 3 139.808 -8.120 -0.084 4.626
Max Fy 3 2 14:GENERATED 5.29E 3 238.066 17.910 0.939 -9.243
INDIAN CODE

06/02/2022
Min Fy 5 3 16:GENERATED 5.29E 3 -252.464 18.333 -0.932 -9.450
Max Fz 18 16 INDIAN CODE
15:GENERATED 5.66E 3 5.666 256.707 1.216 -197.891
Min Fz 12 9 INDIAN CODE
15:GENERATED 5.67E 3 -5.668 -256.768 -1.195 198.314
Max Mx 399 168 INDIAN CODE
17:GENERATED 17.934 61.436 0.020 4.816 -0.092
Min Mx 396 165 INDIAN CODE
17:GENERATED 17.952 61.437 -0.020 -4.817 0.092
Max My 12 9 INDIAN CODE
15:GENERATED 5.67E 3 -5.668 -256.768 -1.195 198.314
Min My 12 13 INDIAN CODE
15:GENERATED 5.66E 3 -5.668 -256.768 -1.195 -197.936
Max Mz 3 2 INDIAN CODE
14:GENERATED 5.29E 3 238.066 17.910 0.939 -9.243
Min Mz 5 3 INDIAN CODE
16:GENERATED 5.29E 3 -252.464 18.333 -0.932 -9.450
INDIAN CODE

3.100m

Y
X
Z Load 1

Whole Structure (Input data was modified after picture taken)

3D Rendered View (Input data was modified after picture taken)

3.100m

Y
X
Z Load 3

dead load (Input data was modified after picture taken)

06/02/2022
3.100m

Y
X
Z Load 4

floor live load

3.100m

Y
X
Z Load 5

roof live load

3.100m

Y
X
Z Load 6

floor finish load

3.100m

Y
X
Z Load 3 : Mode Shape 1

mode 1

06/02/2022
3.100m

Y
X
Z Load 3 : Mode Shape 2

mode 2

3.100m

Y
X
Z Load 3 : Mode Shape 3

mode 3

* TIME PERIOD FOR Z 1893 LOADING = 0.96860 SEC *


* SA/G PER 1893= 1.404, LOAD FACTOR= 1.000 *
* VB PER 1893= 0.0562 X 36721.82= 2062.43 KN *

MODE FREQUENCY(CYCLES/SEC) PERIOD(SEC) ACCURACY

1 5.340 0.18727 1.616E-15


2 6.092 0.16416 2.758E-13
3 8.278 0.12080 1.391E-08
4 8.440 0.11848 1.011E-11
5 8.769 0.11404 1.001E-08
6 9.175 0.10899 4.687E-11