By :- Eng. D M I Sanjeewa
Reg. No. :- 120254638
University :- OUSL
Course :- MSc in Structural Design
Supervisor :- Mr. Indika Fernando
Introduction
- Aim
gaining a comprehensive practice of designing a four storied building according to Eurocodes.
- Exercise
Designing a Four storied building for a hotel
Soil is a alluvial soil which consists of lagoon sand and loose sand
According to the investigation two alternatives have been proposed by geotechnical engineer
1. Ground improvement and raft foundation (bearing capacity tobe taken as 80 kN/m2
BS EN 1991-1-1: 2002: Eurocode-1, part 1-1, Actions on structures, General Actions – Densities, self-weight,
imposed loads for buildings
BS EN 1991-1-1: 2002: Eurocode-1, part 1-4, Actions on structures, General actions – Wind actions.
BS EN 1992-1-1: 2004: Eurocode-2, part 1-1, Design of concrete structures, General rules and rules for buildings
BS EN 1992-1-2: 2004: Eurocode-2, part 1-2, Design of concrete structures, Structural fire design
BS EN 1993-1-1: 2005: Eurocode-3, part 1-1, Design of steel structures, General rules and rules for buildings
BS EN 1994-1-1: 2004: Eurocode-4, part 1-1, Design of composite steel and concrete structures, General rules and
rules for buildings
Loads
Permanent actions – Gk
1. Dead loads and Superimposed loads
2. Creep/ Shrinkage actions – No demand in this assignment
3. Thermal actions – No demand in this assignment
4. Differential settlement – q is similar for all Footings; Small DS is distributed by Tie beams
Variable Actions – Qk
1. Live Loads
2. Wind actions
3. Seismic actions – Not considered
4. Accidental actions – Not Considered in general
Loads
Dead Loads - Gk Live Loads
1. Concrete Density – 24 kN/m3 Reference – “BS 6399 / Table 01
6. Brick walls
225 mm thick – 5 kN/m2
150 mm thick – 3.33 kN/m2
7. Roof
Asbestos – 0.5 kN/m2
Steel purlins – 0.1 kN/m2
Insulation – 0.01 kN/m2
Self Weight of truss – 0.3 kN/m2
Ceiling and Services – 0.5 KN/m2
Wind Loads
Altitude in the locations is around 3 m;
the location is situated in Zone 3.
Corresponding 3 second gust velocity for 50 year return period is 33 ms-1
BS EN 1991-1-4 is used and follow the procedure given.
Vb ~ 22 ms-1
Final values are given here. Open to the Sea breeze
Conclusion
Durability and fire resistance
From Table E.1N – EC2
For Exposure class XS1
Strength class is C25/30
Aggregate Size – 20 mm
One Hour Fire Rated for the all elements
Element Cover
Foundation 50 mm
Column 50 mm
Beam 50 mm
Slab 25 mm
Slab & Beam - Initial Sizing
1. Slab – 1st Floor 3. Columns
Ac / Column
Short lx 4130 4130 4130 2212 Gk Qk Wk N N/Ac Ac
225 sizes
Long ly 5657 9144 4572 4130 C1 259.5 85.9 48.4 551.7 20 27586 123 225x225
Ratio ly/lx 1.4 2.2 1.1 1.9
C2 610.9 154.0 0.0 1055.8 20 52790 235 225x300
End 158.8 158.8 158.8 85.1
d C3 978.9 302.4 0.0 1775.1 20 88753 394 400x450
Interior 137.7 137.7 137.7 73.7
C4 738.6 231.0 0.0 1343.7 20 67183 299 225x350
End 188.8 188.8 188.8 115.1
cover+5=30 C5 434.3 164.3 48.4 905.5 20 45273 201 225x225
Interior 167.7 167.7 167.7 103.7
C6 433.0 113.4 0.0 754.7 20 37734 168 225x225
Slab Thickness 200 200 200 200
2. Beam – 4. Foundation
Ex. Beams along the Grids 4 in 1st floor Gk Qk Wk N 1.08N
q-
Area
Side
Select
Span / Effective depth = 20 kN/m2 length
Effective depth = 5657 / 20 = 283 mm C1 259.5 85.9 48.4 393.8 425.3 100.0 4.253 2.06 2.00
450 x 225 beams are selected C2 610.9 154.0 0.0 765.0 826.2 100.0 8.262 2.87 3.00
Assume T32, 2 bars shall be accommodated. C3 978.9 302.4 0.0 1281.3 1383.8 100.0 13.84 3.72 3.75
Hence, Smin = 32 mm C4 738.6 231.0 0.0 969.6 1047.2 100.0 10.47 3.24 3.25
= 32x2+32+10x2+50x2 = 216 mm < 225 mm ; C5 434.3 164.3 48.4 647.1 698.8 100.0 6.988 2.64 2.50
Hence, 450 x 225 beams are selected C6 433.0 113.4 0.0 546.4 590.1 100.0 5.901 2.43 2.50
GA-Foundation GA-1st Floor
Roof Loads
Roof Gk and Qk applied to the C1 and C6 collumns manually; Those are
calculated by truss tributary area
Story drift is lower than 1/500 as manually checked for all load combinations
Finalized Setup for ULS Checks Results Bar Top Net Bottom Net
Ly = 8,560 mm
Lx = 4,567 mm
STRUCTURAL DESIGN
Slab Design Calculations and Drawings
ly/lx<2; 2way Slab
ULS – 16.11 kN/m
h = 200 mm; Cover – 25 mm; R/f - T10
dshort = 170 mm & dlong = 160 mm
As, req As, prov
(β) Moment k As, prov
mm2 mm2
Checks Results
Transverse R/f in the flange Not needed
Max
Web Max
Compressi
Member Tension
on
1 78.6 208.3
2 6.2 19.6
3 25.3 8.3
4 12.2 40
5 38.5 12.2
h = 100 mm h = 75 mm
b = 100 mm b = 75 mm
t = 10 mm t = 8 mm
e = √235/fy = 0.92442 section is e = √235/fy = 0.92442
section is class 3
15e = 13.87 class 3 15e = 13.87
h/t = 10.0 < 13.87 h/t = 10.0 < 13.87
11.5e = 10.63 11.5e = 10.63
(b+h)/2t = 10 < 10.63 (b+h)/2t = 10 < 10.63
M = 32 kNm – T12@150 mm