Professional Documents
Culture Documents
Unlike most other hazards which can be seen, felt • Contact between a live conductor and
or heard there is no advance warning of danger earth
from electricity; and electricity can kill. • Contact between phase and neutral
conductors (as the body is likely to be of
Electricity and electrical installations on
less resistance than any load)
construction sites must always be treated with the
utmost care and be under the control and According to the Health and Safety Executive, the
supervision of experienced competent persons. majority of electrical accidents happen because
Hazards arise through faulty installations, lack of people are working on or close to equipment which
maintenance and abuse of equipment. is either:
In the Construction Industry, in one year, there • assumed to be dead, but is in fact live
were 194 reported accidents resulting in injury, • known to be live, but workers have not
and over 200 dangerous occurrences involving received adequate training, lack adequate
electricity. Accidents involving live overhead lines equipment or have not taken adequate
are a particular concern as, in the same period, precautions
one in three proved fatal.
The Health and Safety at Work Act 1974 BS 2754 Construction of electrical equipment for
protection against electric shock
The Electrical (Overhead Lines) Regulations 1970
BS 4293 Specification for residual current
The Electricity Supply Regulations 1988 operated circuit breakers 1993
The Electricity at Work Regulations 1989 BS 4363 Specification for distribution assemblies
The Low Voltage Electrical Equipment (Safety) for electricity supplies for construction and building
Regulations 1989 sites 1991
The Construction (Design and Management) BS 5345 Code of practice for selection and
Regulations 1994 installation and maintenance of electrical
apparatus for use in potentially explosive
The Provision and Use of Work Equipment atmospheres
Regulations 1998
BS 7071 Specification for portable residual current
The Management of Health and Safety at Work devices 1992
Regulations 1999
BS 7288 Specifications for socket outlets
incorporating residual current devices (SRCDs)
References
BS 7375 Code of practice for the distribution of
HSE Guidance Notes, etc. electricity on construction and building sites
GS 6 Avoidance of Danger from Overhead BS 7430 Code of practice for earthing 1998
Electrical Lines 1991 BS 7671 Requirements for electrical installations,
PM 29 Electrical Hazards from Steam/Water IEE wiring regulations 16th edition
Pressure Cleaners 1988 BS EN 60309 Plugs, socket-outlets and couplers
HSG 47 Avoiding Danger from Underground for industrial purposes
Services 1989
Other references
HSG 85 Electricity at Work: safe working
Institute of Electrical Engineers
practices 1993
A Commentary and Guide to the IEE Regulations
HSG 107 Maintaining portable and transportable (16th edition)
electrical equipment 1994
Chartered Institute of Building Services
HSG 118 Electrical safety in arc welding 1994 Engineers
HSG 141 Electrical safety on construction sites Code of Practice for Interior Lighting and Lighting
1995 Guide for Building and Civil Engineering Sites
HSR 25 Memorandum of guidance on the
Construction Industry Training Board
Electricity at Work Regulations 1989
Memorandum of Guidance on the Electricity at EE 111 IEE Regulations Study Notes
Work Regulations 1989 VID 018 Video training programme Danger of
The Electricity at Work Regulations 1989 Death
Approved Code of Practice, Use of Electricity at
Quarries
20/2
CONTENTS FIRST PAGE
The Provision and Use of Work Equipment (For further information see Construction Site
Regulations 1998 require that an employer only Safety, Module 2, General Safety Legislation)
supplies work equipment that is correct and
Both sets of regulations additionally require the
suitable for the job and ensures that the
employer to provide employees with adequate
equipment is maintained and kept in good working
information, instruction and training to be able to
order.
carry out any work task to the best of their ability
Where the use of the equipment involves a and in complete safety.
specific risk to the health and safety of employees, It cannot be emphasised too strongly that the
the use of the equipment must be restricted to installation, maintenance and repair of
specified workers. electrical services must only be done by a
competent, qualified electrician.
All work, and that includes work on electrical
systems, or work with electrical equipment, must Many electrical risks can be eliminated, or reduced
have been subject to a risk assessment under the by careful attention to design and planning
Management of Health and Safety at Work aspects before the start of work. Remaining risks
Regulations 1999. can be controlled by good management practices
during work.
The Management of Health and Safety at
Work Regulations 1999 place a requirement on Planning and management are key requirements
every employer to make a suitable and sufficient of the Construction (Design and Management)
assessment of every work activity to detect and Regulations 1994.
define any hazard that either employees might
These regulations place health and safety
encounter during their work, or any other persons
responsibilities on the client, designers and
who might be affected by the employer’s
contractors, and provide a framework for the
operations.
management of risks, including electrical risks.
Once those hazards have been identified, it is the
A planning supervisor must be appointed by the
employer’s duty to put control measures in place,
client and provided with relevant health and safety
to remove or reduce those hazards as far as is
information which could include a location plan (if
reasonably practicable.
available) of the electrical supply system.
Where a hazard is identified that requires it, the
Hazards must be identified and inherent risks that
employer must offer health surveillance to
may arise must be eliminated or reduced.
employees. This must be appropriate, taking into
account the risks to health and safety that have The main principles of risk control should be
been identified. utilised, of which the following are a selection:
The employer must provide employees with • if possible avoid the risk
comprehensible and relevant information on any • combat risks at source
risks that exist in the workplace and of any
control measures that are in place to reduce • give priority to those measures which will
those risks. protect all the workforce
20/3
CONTENTS FIRST PAGE
The planning supervisor must also prepare a (ii) ‘Electrical equipment’ includes everything
health and safety plan at the pre-tender stage of from overhead to underground cables with
the contract. This plan should contain information thousands of volts, right down to 6 volt circuits
on the project health and safety risks, and the and even battery-powered hand lamps. The
means to eliminate or reduce them. spark from the switch on a hand lamp could
be a source of danger in an explosive
A principal contractor must be appointed to
manage and co-ordinate the work and also to atmosphere.
develop the health and safety plan. This should (iii) ‘Danger’ is the risk of injury to any person
contain all the relevant information on how health
and safety risks will be managed. (iv) ‘Injury’ means death or any injury caused
by electricity. This covers electric shock,
The principal contractor also co-ordinates the electric burns, fires, arcing or explosions
activities of other contractors and may make site caused by electricity.
rules.
Contractors must co-operate with the planning • the strength and capability of electrical
supervisor and comply with any rules or directions equipment must not be exceeded in such a
given. way as may give rise to any danger
Reference
Electricity at Work Regulations The Electricity at Work Regulations 1989,
Regulation 5
The Electricity at Work Regulations apply to all
situations involving electricity, at any place of All electrical equipment which may be exposed to:
work, and place legal obligations on both • mechanical damage
employers and employees.
• the effects of weather, temperature, etc.
The main points of the regulations are, briefly: • wet, dirty or corrosive conditions
• all systems shall be of such a construction • flammable or explosive dusts or gases
so as to prevent, so far as is reasonably
practicable, any danger. must be constructed, or protected to prevent, so
far as reasonably practicable, any danger arising.
• all work activity, on or near a system,
including operation, use or maintenance, Reference
shall be carried out, so far as it is The Electricity at Work Regulations 1989,
reasonably practicable, so as not to give Regulation 6
rise to any danger. • all conductors which may give rise to
• any equipment provided to protect people danger must be insulated, protected, so
while they are at work on, or near, any placed and have other precautions taken
electrical equipment shall be suitable for so as to prevent danger
use and properly maintained. Reference
Reference The Electricity at Work Regulations 1989,
The Electricity at Work Regulations 1989, Regulation 7
Regulation 4 • earthing, or other protective measures
must be taken to prevent cables, other than
Notes
circuit cables, from becoming live
(i) ‘System’ includes every part of the system
or installation, all conductors and electrical Reference
equipment, whether the system is electrically The Electricity at Work Regulations 1989,
Regulation 8
alive or dead.
20/4
CONTENTS FIRST PAGE
• placing switches in the neutral side of a • adequate access, lighting and working
circuit is prohibited, unless specific safety space must be provided, as necessary, to
precautions are taken prevent any injury from occurring
Reference Reference
The Electricity at Work Regulations 1989, The Electricity at Work Regulations 1989,
Regulation 9 Regulation 15
• all joints and connections must be • no person is to be engaged in work, where
electrically sound and mechanically technical knowledge or experience is
suitable for use necessary to prevent danger, unless they
have the knowledge and experience or are
Reference
under the appropriate supervision
The Electricity at Work Regulations 1989,
Regulation 10 Reference
The Electricity at Work Regulations 1989,
• the use of fuses, or circuit breakers, to
Regulation 16
protect electrical systems is required
Note
Reference
The Electricity at Work Regulations 1989, ‘Technical knowledge and experience’ means
Regulation 11 that the person must be competent to do their
job. To be considered competent a person
• a suitable means must exist for:
needs:
cutting off the electricity supply to any item adequate knowledge of electricity
of electrical equipment good experience of electrical work
an understanding of the system being worked
isolating any such item on
20/5
CONTENTS FIRST PAGE
20/6
CONTENTS FIRST PAGE
Any ground level barriers should consist of either: There should be a general rule prohibiting the
(a) a stout post and rail fence, or storage of materials in the area between the
overhead lines and the ground-level barriers.
(b) a tension wire fence, earthed at both ends, Precautions are necessary even though work in
having flags on the wire. The fence being the vicinity of the line may be of short duration.
earthed in consultation with the electricity
company, or • Before doing any work on site consult the
local electricity company. They will
(c) large steel drums (for example 200-litre oil normally arrange a site meeting (which is
drums) filled with rubble or concrete, and usually a free service) and advise on
placed at frequent intervals, or heights, distances and other precautions. A
(d) an earth bank, not less than 1 m high and Code of Practice of Do’s and Don’ts is
marked by posts to stop vehicles, or available from most companies
(e) substantial timber baulks, to act as wheel • It must be assumed that all overhead lines
stops and cables are live unless advised
Fences, posts, oil drums, etc. should be made as otherwise by the electricity company
distinctive as possible by being painted with red • All work should be carried out under the
and white stripes. As an alternative, red and white direct supervision of a responsible
plastic warning flags or hazard bunting should be supervisor, appointed by the employer, who
used on wire fences. is familiar with the hazards likely to be
encountered
20/7
CONTENTS FIRST PAGE
• Ensure that safety precautions are It is essential that all those involved, particularly
observed machine operators, are aware of the hazards.
• All plant, cranes and excavators may be Before any excavation work commences:
modified with suitable physical restraints to
limit their operations where applicable • ensure that employees have proper and
safe work procedures and are working
• Additional care may be needed as work under adequate supervision
proceeds because of reduced clearances
• Electronic proximity warning devices may • check with the electricity board that it is
be fitted on crane jibs, etc. safe to commence work
20/8
CONTENTS FIRST PAGE
BS 4363 Units
20/9
CONTENTS FIRST PAGE
20/10
CONTENTS FIRST PAGE
20/11
CONTENTS FIRST PAGE
the continuity of final circuit conductors Particular care is needed in respect of any
alterations and extensions to existing installations,
the continuity of protective conductors especially in the identification of circuits.
the earth electrode resistance Reference
the insulation resistance HSG 85 and HSG 141
polarity
Residual current devices
the earth fault loop impedance
RCDs or ELCBs (earth leakage circuit
the correct operation of residual current breakers)
devices and fault voltage operated
When installed, these devices sense a current
protective devices
flow to earth, or an imbalance in the current in the
Weekly inspections should be made of the whole circuit. They disconnect the supply before a
system, including all portable electric tools. person can receive a potentially lethal shock. They
Records should also be kept of all these also protect plant and equipment, and prevent the
installation from catching fire. RCDs must be
inspections.
installed by competent electricians and should be
regularly tested.
Power requirements
RCDs do not reduce current flow, nor the voltage,
The calculation for power requirements should be only the time that the current flows (about 30
left to an experienced person or to the electricity milliseconds), and thereby the severity of the
company. shock.
Advice on suitable RCDs for construction sites
To enable the total site requirements to be should be sought from manufacturers.
established, a site demand table listing items of
plant, equipment and general site requirements It should be noted that the use of a RCD does not
should be completed (see Appendix D). A guide to give 100% guarantee of safety.
voltages required for typical plant is also listed in The device does not have a fail-safe feature and
Appendix D. will not give an indication if it is faulty. Additionally,
because it only protects against earth faults, it will
When computing the demand, it is permissible to not function if current is passing from a live to
allow a diversity factor (assuming not all neutral phase. It is possible for a worker to get an
appliances will be in use at the same time), and a electric shock even though a RCD is fitted to the
figure of not more than 50% is generally circuit and is operating correctly.
acceptable. Care should be taken to ensure that
items such as lighting and heating remain at their
full rated value, because heaters used in huts
20/12
CONTENTS FIRST PAGE
• 63.5 volts to earth in the case of a three Long leads trailing over the ground or floor and
phase neutral point earthed supply creating a tripping hazard must be avoided. Care
must be taken in the use of cable drums or reels,
The maximum recommended voltage to earth for a as internal cable terminations may become loose.
reduced low voltage system is stated as 65 volts. They can overheat and cause a fire. Drums and
Both of these systems will offer a phase to phase reels should be inspected regularly for signs of
voltage of 110 volts for supplying power tools on damage or wear.
site.
All insulated or double-insulated tools
A reduced low voltage system will eliminate the manufactured in accordance with BS 2754 and
risk of death from a phase to earth shock in the with the recognised symbol attached, give extra
majority of situations. Other safer systems, i.e. protection against the danger of electric shock.
compressed air, battery power etc., should be
considered when working in confined spaces or Fuses
damp conditions.
Fuses usually blow for a reason. The reason
Outputs of 240 volts or 110 volts should be investigated and rectified before a fuse
is replaced.
110 volt systems that are neither centre tapped or
neutral point earthed can be equally as lethal as a Nails, screws, wire or silver paper must never be
240 volt system in phase to earth faults. In certain used to replace fuses. It is illegal as well as very
situations, even reduced low voltages are not safe. dangerous.
The maximum voltage for portable and hand-held
electric tools should be 110 V centre tapped to Lighting
earth. Flexible cables should be kept as short as Lighting is needed for safety, productivity and
possible, frequently checked for damage and security.
properly repaired as necessary.
The Construction (Health, Safety and Welfare)
Regulations require that every working place,
approach, dangerous opening and lifting appliance
be adequately and suitably lighted.
20/13
CONTENTS FIRST PAGE
There are many different types of lighting, each • adaptable, remembering that 50 to 100%
with its own most suitable application. Advice more light is required for persons over 40
should be sought in order to obtain the best light years of age
for a particular place, considering such factors as
colour rendition, humidity and flammable or • increased if necessary, because more light
explosive atmosphere, etc. will be required in hazardous situations and
when goggles are worn
Reference
PM 38 Selection and use of electrical hand • so positioned that it can be screened or
lamps shielded from reflective surfaces, on traffic
routes, etc.
Levels of illumination • treated as a heat source, with the
Illumination is measured in units of lumens or lux, possibility of burns or fire hazards
which is the amount of light falling on one square
metre. Site lighting
Light meters are used to check levels of Area lighting with floor lights or beam floodlights:
illumination. Illumination should be measured at • all areas should receive light from at least
the workplace, not at the light fitting.
two directions
There are certain factors which can affect the
• fittings mounted on poles, towers and high
efficiency of lighting, such as:
masts must be securely stayed
• the amount of daylight available
• fittings spaced at usually not more than two
• the cleanliness and maintenance of light or three times the mounting height
fittings and reflectors
• the reflections from walls and ceilings
• the distance of the light source from the
workplace
• shadows thrown from furniture and fittings
20/14
CONTENTS FIRST PAGE
maintaining adequate levels of lighting for both Types include dispersive, cargo, cluster,
working and safety. fluorescent trough, wall glass unit, bulkhead unit
tungsten or fluorescent.
Local lighting
• Fittings should be similar to the industrial
This is usually of the tungsten filament type. indoor type but waterproof
• It is used to supplement the general area • They should be mounted centrally,
lighting scheme overhead where possible
• Small sources of light tend to produce • They should be spaced usually one-and-a-
shadows; they should be used with a half times mounted height, but the
diffuser or be hung in rows manufacturer's recommendations should
• Lights should be positioned in the same be followed
direction as the permanent source in order
• They should be mounted as high as
to show up any blemishes in the work
possible to give an even spread of light
• Pendant fittings should be supported so as
• Mains voltage (230 V) should only be used
not to tension the supply cable. They
where the installation is well protected and
should be of the festoon type only with
of a permanent nature. Reduced voltages
moulded on lampholders and protective
should be used for regular site work
guards
Dispersive lighting
Used over working areas, walkways, ladder
access, stairs, etc.
20/15
CONTENTS FIRST PAGE
20/16
CONTENTS FIRST PAGE
20/17
CONTENTS FIRST PAGE
• Are all plugs being used suitable for the • Have the tools or machines been checked
site conditions prevailing? to ensure that there are no cracks, or
missing pieces ?
• Have any plugs been forced into the wrong
sockets (by the removal of keys, etc.)? • Is the chuck in good condition and is the
correct key attached?
• When plugs have been fitted, have the
correct connections been made, with the • Have checks been carried out to ensure
wire being correctly colour coded? that any bit retaining mechanism is in good
working order?
• Are cable grips being used and is the earth
cable fitted with some slack, so that it is the • Have checks been made to ensure that the
last to be pulled out? nameplate is secure with details of:
20/18
CONTENTS FIRST PAGE
• Are cables of an adequate rating for the Precautions near live overhead power
tool that is being used? lines
• Are checks carried out to ensure that no • Has an essential ongoing system of liaison
unofficial cables, etc. are being used? between employer or contractor and the
• Have instructions been issued to ensure electricity company been established?
that no makeshift repairs or maintenance • Where overhead power lines have been
are carried out? diverted or (if possible) made dead, or
• Are all defects reported immediately to a where live lines remain, have all practicable
competent person? steps been taken to provide adequate
barriers, goal posts, etc. to comply with the
• Is the machine kept clean and free from relevant regulations?
damp?
• Have adequate arrangements been made
• Are all connections correctly made,
for the passage of tall plant, etc. at specific
including waterproofing?
times where overhead power lines have
• Are all operatives aware that they should been made dead?
never carry any tool or machine by its
cable? Work beneath overhead power lines
• Have instructions been issued to ensure • On sites where work will take place below
that no machine is started or stopped overhead power lines, have additional
under load? precautions, as necessary, been taken, as
well as the provision of barriers with
Working near overhead power passageways?
lines • Is all work carried out under the direct
supervision of a responsible person,
• Is everyone working on site aware that no familiar with the hazards, after consultation
work should take place: with local electricity company?
20/19
CONTENTS FIRST PAGE
20/20
CONTENTS FIRST PAGE
Applies to both indoor and outdoor activities and relates to the value on the ground, floor or horizontal working
plane.They may require adjustment according to district brightness.
Site entrances 30
Fine craft work Joinery, all work with power tools and circular saws, plastering, 300
painting, electrical, plumbing, shop fitting, brickwork
Site offices On desks and reference tables, general lighting of drawing 500
office
20/21
CONTENTS FIRST PAGE
* The efficacy is the measure of effectiveness of converting electrical energy into usable light
20/22
CONTENTS FIRST PAGE
For calculation purposes - check only the formula: ixV = W should be used
where i = current in amps
V = voltage
W = wattage
415 3 Supply undertaking Fixed and transportable equipment above 5 hp, e.g.
crane, hoist, compressor, concrete mixer, and large
scale personnel amenities
240 1 Supply undertaking Site offices, personnel amenities and fixed
floodlighting
110 3 415 V transformer Secondary winding phase Transportable equipment up to 5 hp, e.g. vibrators,
to earth 64 V pumps, site lighting other than fixed floodlighting, and
hand tools
110 1 230 V transformer Secondary winding outers All portable and transportable tools up to 2.5 hp and
to earth 55 V site lighting
50 1 Transformer Secondary winding outers Dangerous situations, tunnelling work, inside boilers,
to earth 25 V confined spaces
25 1 Transformer Secondary winding outers Dangerous situations, tunnelling work, inside boilers,
to earth 12.5 V confined spaces
20/23
CONTENTS FIRST PAGE
No.
I hereby declare that it is safe to work on the following H.V. apparatus which is dead, isolated from all live
conductors and is connected to earth.
SWITCHING AND ISOLATING. The apparatus is disconnected from all live conductors by the following operations.
OTHER PRECAUTIONS
I hereby declare that I accept responsibility for carrying out work on the apparatus detailed on this permit and that no
attempt will be made by me, nor by any man under my control, to carry out work on any other apparatus
Note: After signature for work to proceed, this receipt must be signed by, and the Permit to Work retained by, the
person in charge of the work until work is suspended or completed and the clearance section has been signed.
This is to certify that the work authorised above has been completed or stopped* and that all men under my charge
have been withdrawn and warned that it is no longer safe to work on the apparatus specified on this Permit to Work
and that gear, tools and additional earthing connections are all cleared. Automatic fire extinguishing control has been
restored.
20/24
CONTENTS FIRST PAGE
is the person responsible on this site for seeing that the Rules for the safe operation of H.V.
systems and the Permit to Work system are complied with in every respect.
The authorised person(s) for H.V. switching, isolation, testing and earthing is (are):
................................................................................................................................................................
................................................................................................................................................................
................................................................................................................................................................
................................................................................................................................................................
20/25