You are on page 1of 1

Installation and Startup Guide | Envision for BACtalk

Ta bl e 3 Device capability descriptions (Continued)

Device capability Description How to use When checked, it does this


Supports Alerton VAV VLCs such as VAV-xx or VAVi- Device Managers Send/Save NOTE: All Alerton VLCs auto
flow sensor setup xx each have an on-board flow writes/reads the VAV flow configure this setting as checked
sensor (velocity sensor), this sensor’s parameters to/from by default. However, the
(Alerton proprietary)
sensor has setup parameters pointdata.mdb to/from the practical application for this is
used for balancing and device. Writing/reading these VAV controllers. It is acceptable
reporting. values to/from a VLC does not to leave the default set for all
cause any system issues. VLCs.

Supports BACnet Enables the Envision server to To save and restore a BACnet Back up devices that have the
backup and restore back up BACnet compliant compliant devices configuration BACnet backup device capability
devices that have the BACnet data. A password is required selected in their device profile.
(BACnet- Backup and
Restore) backup device capability when backing up devices. You Device Manager: Select
selected in their device profile. can also select a character set (if
Advanced->Back up Devices...
necessary) and define a timeout
Or -> Restore Devices...
period after which the back up
process is stopped.
Password: Type the password
defined for the selected
device(s). The default password
for all Alerton controllers is
ALERcomm (case-sensitive).
Character set: This is the char-
acter set recognized by the
selected devices. ANSI X3.4 is
selected by default. You can
select ISO 8859-1 if appropriate.
Timeout: This is the amount of
time, in seconds, in which
Envision for BACtalk attempts to
back up a selected device before
stopping. If all of the devices use
the same timeout value, the
value is displayed here by
default. A valid timeout value is
between 10 and 65535 seconds.

Acts as a smoke Password protects the controller Select this capability and then Forces the user to enter a
controller so users can only download set the password. Remember password to send DDC, device
DDC to it if they enter the the password so you can configuration or Point Data to the
password. Protects some download DDC to this smoke device. Prevents unauthorized
systems from being modified in controller. users from modifying controllers
ways that prevent them from that have been configured as
functioning appropriately during part of a smoke system.
a smoke event.

Preferences
Use the Preferences tab in the Add/Edit Device Profile dialog box to identify the
DDC application that will control this device. You also use the Preferences tab to
identify the host controller for the device. This is where the trendlogs, schedules,
and alarms for the device are stored and run.

Do Not select the Auto Download option to automatically send a ROC file from
the operator workstation hard disk to controllers if it is different than the file on
the device. This automatic download occurs once a day at midnight. Instead,
ROC file downloads should be done under the direct supervision of a trained
technician only.

54 © Honeywell. All Rights Reserved. LTBT-TM-ADMIN26 Rev. A