McGill AirFlow Corporation offers UNI-GASKET fittings featuring an EPDM rubber gasket that provides a reliable, airtight seal.
Testing has shown that UNI-GASKET fittings meet or exceed SMACNA1 Class 3 for leakage at - 20 in. wg to + 20 in. wg.
Each fitting is constructed of an inner liner7 surrounded by a layer of fiberglass insulation and covered by a solid metal
pressure shell. The insulation is available in 1-, 2-, and 3-inch standard thicknesses and a maximum of 1.5 pounds per cubic
foot (pcf) density6 to meet the thermal and acoustical performance requirements. The galvanized steel construction5 meets
SMACNA’s 10 in. wg positive pressure standards2. UNI-GASKET fittings are compatible and available with all of McGill
AirFlow’s round, double-wall duct types in 1-inch increments for 5- through 12-inch diameters outer shells and in 2-inch
increments in 14- through 24-inch outer shell diameters.
Table 1 - Positive Pressure, Double-wall, Round Duct and Fitting, Outer Shell Galvanized Steel Gauges
1
SMACNA is the Sheet Metal and Air Conditioning Contractors National Association.
2
McGill AirFlow double-wall, round duct and ungasketed fittings are available in diameters of 3 through 90 inches in many
gauges of various materials. See the Double-Wall Round Duct and Fittings Dimensions booklet for the full range of
available sizes.
3
Standard lengths of round UNI-SEAL and UNI-RIB duct are 10, 12, and 20 feet; longer lengths are available on special
order.
4
The rating of +10 in. wg for Spiral Lockseam with Standing Rib Duct is based on McGill AirFlow laboratory testing.
5
Available in galvanized, paintable galvanized, and SilverGuardTM precoated ductwork with antimicrobial.
6
Standard insulation density is 1.0 pcf.
7
Standard inner shell gauges are 28 gauge spiral 3-8 inch diameter and 28 gauge ribbed spiral 9-24 inch diameter.
Approx. 5 to 6 inches
Fitting Construction
Solid Welded Spot Welded, Tack Welded or Mechanically
Fastened
Mechanical Fastener or Spot Weld
Fillet Weld
Tack Weld
Sealant
Sealant
Sealed with United Duct Sealer™ (Water Based) Sealed with United Duct Sealer™ (Water Based)
2
Dimensioning:
All alphanumeric dimensions are in inches; all angles are in degrees.
Designations:
McGill AirFlow uses a designation system that simplifies product nomenclature. Gasketed fitting products can be
accurately identified using a concise alphanumeric designator. Each character in the designation defines a
characteristic of the product.
Example: KR0PT refers to a double-wall (K), round (R), 10 in. wg positive pressure class (0), straight tee tap
(PT).
K = Double-wall
R = Round
0 = +4 to +10 in. wg
S = standard gauge of product type
3
General Notes:
• Dimensions other than diameters are held within a ± 1/4-inch tolerance.
• Given diameters of double-wall, round fittings are sized to slip fit into the same diameter of double-wall, round
duct. Double wall gasketed fittings will have a projecting inner liner slip fit section as shown below.
Gasket
Hem
Bead
X S
• Unless otherwise specified fittings, will be solid inner liner and duct will be perforated inner liner.
• Unless ordered otherwise, the branch taps of laterals, crosses, and lateral crosses are installed at standard
angles to the fittings' bodies and to each other, as shown in the following drawings:
For all:
Laterals - θ standard = 45E
Straight Crosses - θ standard = 90E, Φ standard = 180E
Lateral Crosses - θ standard = 45E, Φ standard = 180E
Y-Branches - θ standard = 90E
Note: Φ is the included angle between taps as viewed in cross section (standard is 180E). When ordering fittings
of nonstandard Φ, please include an end view sketch.
4
Installation:
• Make sure the end of the duct or gasketed fitting is not damaged.
• Insert the extended inner collar of the fitting into the liner of the adjacent duct section.
• Insert the outer gasketed collar of the fitting into the spiral duct up to the fitting bead. Turning the fitting slightly
as it is inserted may make installation easier.
• Secure the fitting to the duct with self-tapping screws uniformly located around the circumference according
to SMACNA recommendations. Use at least one screw for every 15 inches of circumference with a minimum
of three screws for 14-inch or smaller diameters.
1 1 1
2 2 2
3 3 3
• The following figure illustrates gasketed fittings assembled to ductwork with a manifolded tap:
5
DUCT
Diameters:
3-inch minimum inner liner
84-inch maximum outer shell
Diameters:
3-inch minimum inner liner
9-inch minimum outer shell
60-inch maximum outer shell
A
6
ELBOWS
GORED ELBOW
Designation:
KR0E#-θ
Where:
0-35E 2
A θ 36-71E 3
72-90E 5
Dimensions:
R – 1.5 (A+2t)
R
Note:
1. McGill AirFlow UNI-SEAM (standing
seam) construction will be used on the
following available sizes: 9- through 12-
inches in 1-inch increments, 14- through
24-inches in 2-inch increments.
Gasket
Outer Shell Diameter # 22 inches 2. Nonstandard elbows with a different
centerline radius and a different number
of gores are available.
θ
A
7
ELBOWS
Dimensions:
A Number of
(inches) vanes (#)
A 3-9 2
10-14 3
15-19 4
20-24 5
t
1"
1"
1"
Gasket
8
ELBOWS
Dimensions:
2" R = 1.5 (A + 2 t)
Z = 0.086 (A + 2 t)
Maximum C = A
A
Z
C
Gasket
9
TEES
STRAIGHT TEE Designation:
V
KR0T
t
Dimensions:
V = C + 2 +2t
Maximum C = A
1"
C Gasket
4½"
Gasket
C
Dimensions:
V = C + H + 1½ + 2t
J = C + 2 (for C # A - 2)
A
J = C (for C > A - 2)
Maximum C = A
10
TEES
TANGENTIAL TEE Designation:
KR0TT
1" 1" 1"
Dimensions:
C V = C + 2 + 2t
Maximum C = A
V
t Gasket
Dimensions:
V = C + 2 + 2t
Maximum C = A
A - B (1-inch minimum, 12-inch maximum)
A B
1"
Gasket
C
Dimensions:
V = C + 4 + 2t
Maximum C = A - 2
A B A - B (1-inch minimum, 12-inch maximum)
4 ½"
Gasket
C
11
TEES
REDUCING LO-LOSS™ TEE Designation:
KR0TLR
Dimensions:
V A-B J
V = C + H + 1½ +2t
J = C + 2 (for C # A - 2)
J = C (for C > A - 2)
Maximum C = A
A - B (1-inch minimum 12-inch
maximum)
A B
3-9 4½
1" H 9-14 7½
t
16- 24 10½
1"
Gasket C
Dimensions:
A-C V A-D
V = A + 2 + 2t
A - C or A - D
(1-inch minimum or 12-inch maximum)
1
A Number of
(inches) Vanes (#)
C D
2 3-6 1
3
7-9 3
10-24 5
t
1"
Gasket
Vane Spacing
A
1"
12
Y-BRANCHES
Y-BRANCH Designation:
KR0Y
m
(-θ if θ … 90E)
Dimensions:
A
H A + 2t
H= +1
θ
2 tan
2
1"
A + 2t θ
m= tan
θ 2 4
A
1"
1"
Gasket
Dimensions:
H A + 2t
H= +1
θ
2 tan
2
1"
A + 2t θ
m= tan
2 4
θ
A
A - C or A - D
(1-inch minimum or 12-inch maximum)
1" Maximum C or D = A
Gasket 1"
A-C C
13
Y-BRANCHES
Dimensions:
H
t H = 125
. A
L1 = A + t
θ C θ
L 2 = [Hx cos ] + [ x sin ]
O2 2 2 2
θ θ D θ
L 3 = [Hx cos ] + [ x sin ]
A 2 2 2
θ C θ
O1 O1 = [Hx sin ] − [ x cos ]
2 2 2
θ D θ
O 2 = [Hx sin ] − [ x cos ]
2 2 2
Maximum C or D = A
H
Gasket
C
L1
L2
Dimensions:
C
D
L1 = A + t
C
L 2 = L1 +
A L3
2
L2 L1 A
D
L 3 = L1 +
2
Maximum C or D = A
Gasket t
A
14
CROSSES
STRAIGHT 90E CROSS V Designation:
D
KR0TX
1"
(Φ if Φ … 180N)
Dimensions:
V=C+2
Maximum C or D= A
1"
Gasket
t C
4½"
4½"
Gasket
t C
15
CROSSES
Dimensions:
V
D JD
V = C + HC + 2 + 2t
JC = C + 2 (for C # A - 2)
JC = C (for C > A - 2)
JD = D + 2
HD
JD = D (for D > A - 2)
Maximum C = A
C or D Sizes HC or HD
A (inches) (inches)
3-9 4½
9-14 7½
16- 24 10½
HC 1"
1"
t C Gasket JC
Maximum C = A
A - B (1-inch minimum, 12-inch maximum)
A B C or D Sizes HC or HD
(inches) (inches)
3-9 4½
9-14 7½
16- 24 10½
HC 1"
1"
t C
Gasket JC
16
CROSSES
REDUCING STRAIGHT CROSS Designation:
KR0TXR
(Φ if Φ … 180N)
V A-B
Dimensions:
C
1"
V = C + 2 + 2t
Maximum C or D = A
A - B (1-inch minimum, 12-inch maximum)
A B
1"
Gasket
t D
A B
4½"
Gasket
t D
17
REDUCERS
Gasket
A-B Dimensions:
A - B (1-inch minimum 12-inch maximum)
Gasket
A B
18
LATERALS
STRAIGHT LATERAL
Q Designation:
KR0L
t V
(-θ if θ … 45E)
Dimensions:
C + 2t
V= +2
sin θ
A
θ A + 2t C + 2t
2" Q= + +1
2 tan θ 2 sin θ
A + 2t C + 2t
Gasket H= + +2
2 sin θ 2 tan θ
Maximum C = A
H
Designation:
REDUCING LATERAL
KR0LR
(-θ if θ … 45E)
Dimensions:
Q
t
V A-B
C + 2t
V= +2
sin θ
A + 2t C + 2t
Q= + +1
2 tan θ 2 sin θ
A B
2" A + 2t C + 2t
θ H= + +2
2 sin θ 2 tan θ
Maximum C = A
Gasket
A - B (1-inch minimum 12-inch maximum)
19
LATERALS
LATERAL CROSS Designation:
Q D KR0LX
(-θ if θ … 45E, Φ if Φ … 180N)
Dimensions:
t
HD 2"
C + 2t
V= +2
sin θ
θ A + 2t C + 2t
Q= + +1
A 2 tan θ 2 sin θ
θ A + 2t C + 2t
HC = + +2
2 sin θ 2 tan θ
2" A + 2t D + 2t
HD = + +2
HC
2 sin θ 2 tan θ
Maximum C or D = A
C
Gasket
V
Dimensions:
t
2"
HD
A-B C + 2t
V= +2
sin θ
θ A + 2t C + 2t
Q= + +1
A B 2 tan θ 2 sin θ
θ
A + 2t C + 2t
HC = + +2
2 sin θ 2 tan θ
2"
A + 2t D + 2t
HD = + +2
HC 2 sin θ 2 tan θ
Maximum C or D = A
C A - B (1-inch minimum 12-inch maximum)
Gasket
20
TAPS
CONTOURED FLANGED STRAIGHT TEE TAP Designation:
KR0PT
Turnout
1" Dimensions:
Specify diameter of duct, to which
Gasket tap will be attached, as A
C + 2t Turnout C
Maximum C = A
Dimensions:
½" ½" Specify diameter of duct, to which tap will
½" ½" be attached, as A
Maximum C = A - 2
4 ½"
Gasket
1" C + 2t 1" C
Dimensions:
Specify diameter of duct, to which tap will
be attached, as A
2" 2"
4 ½"
Gasket
1" C + 2t 1" C
21
TAPS
CONTOUR FLANGED LO-LOSS™ TEE TAP
Designation:
KR0PTL
Dimensions:
J = C + 2 + 2t (for C # A - 2)
J = C + 2t (for C > A - 2)
Maximum C = A
Available Tap H
Outer Wall (C) Sizes (inches)
(inches)
4, 6, and 8 4½
10, 12, and 14 7½
H
16, 18, 20, 22,and 24 10½
½"
½"
H C + 2t Gasket
½" C
½"
J
Dimensions:
J = C + 2 + 2t (for C # A - 2)
J = C + 2t (for C > A - 2)
Maximum C = A
Available Tap H
Outer Wall (C) Sizes (inches)
(inches)
4, 6, and 8 4½
10, 12, and 14 7½
H 16, 18, 20, 22,and 24 10½
2"
2"
Gasket
2" H C + 2t 2"
C
J
22
TAPS
Dimensions:
θ A C
Gasket
H= + +2
2 sin θ 2 tan θ
½" ½"
2" Maximum C = A
H
½" ½"
C
C + 2t
Dimensions:
Specify diameter of duct, to which tap will be
attached, as A
2"
H
C 2" 2"
C + 2t
23
TAPS OFF FLAT SURFACE
Gasket
t C t
½"
4½”
Gasket
1" 1"
t C t
24
OFFSET and SQUARE-TO-ROUND
OFFSET Designation:
KR0Z
V Dimensions:
V = 2 (A + 2t)
t
θ
Z = Must be specified
Gasket
SQUARE-TO-ROUND Designation:
KR0QR
Dimensions:
V
A = Major axis of rectangular side
1" a = Minor axis of rectangular side
t
Axa B
Gasket
25
COUPLING and END PLUG
COUPLING
Gasket
Designation:
KR0C
A+2t
S+t
26