Schenck calibration procedure with DISOMAT Tersus For turret:

Note: If two DISOBOX PLUS scales are disturbed and DISOMAT Tersus controller showing M7501-N
(either 1 or 2) DISOBOX ERROR message. So follow below calibration procedure

Pre-conditions:

1. First ensure RS-485 connections tightness and correct connections as per diagram at DISOBOX
PLUS 1&2 and DISOMAT Tersus
2. All connections are ok , so follow below procedure
3. Information: 1. Master acts as a DISOMAT Tersus controller
2. Slave-1 acts as a DISOBOX PLUS -1 (arm-1)
3. Slave-2 acts as a DISOBOX PLUS -2 (arm-2)
4. In both DISOBOX PLUS boxes we need to put SCALE-1 only in all channel of
loadcell for both slave-1 and slave-2 and configure with different names like
DISOBOX PLUS -1 set as a SLAVE-1 and DISOBOX PLUS -2 set as a SLAVE-2.
5. When both DISOBOX PLUS boxes RS-485 communication established to
DISOMAT Tersus controller, then only the M7501-N(either 1 or 2) DISOBOX
ERROR message will disappear and SCALE-1&2 option appear in “57:SCALE”
parameter.
6. Passwords: parameter setting: 393852
Configuration : 618349
Calibration :505442
Service parameter(5) : 235711

4. Calibration procedure:

Step-1: Switch off the total power supply of DISOMAT Tersus controller and DISOBOXes.

Step-2: At first only turn power on to the DISOBOX PLUS -2 designated as SLAVE-2 and DISOMAT
Tersus controller.

Step-3: DISOMAT boots up, the event message” power fail” will be displayed in the topmost row

Step-4: Press the [quit] button to clear message

Step-5: Go into parameter 41: password Enter configuration password – 618349.

Step-6: Go into parameter 448: Meas input configuration Set Measurement input 1 to “off”

Set Measurement input 2 to “off”

Step-7: Go into parameter 43321: Disonet mode Select interface “S1”

Select net position “Master”

Step-8: Go into parameter 43322: Interfaces Select interface “S1”


Select physics “RS-485 2-WIRE”
Select Baud rate “115kbs”
Hand shake “off”
Data “8bit no” and Stop bit “1”

Step-9: Go into parameter 4471: Configuration Set count of DISOBOX PLUSES TO “2”.

Step-10: Go into parameter 43322: Slave list Select slave 1 “YES”


(Leave the other parameters set to “NO”)

Step-11: Go into parameter 4474: Address setup Serial no ……….. (Not required)

Set Net position “slave-2”.

Note: now the slave-2 agained to DISOBOX PLUS-2 and the M7501-2 DISOBOX ERROR message will
disappear and the M7501-1 DISOBOX ERROR message will appear

Step-12: Turn power on to the DISOBOX PLUS -1 designated as SLAVE-1.

Note: The M7501-1 DISOBOX ERROR message will disappear

Step-13: Go into parameter 43322: Slave list Select slave 2 “YES”


(Leave the other parameters set to “NO”)

Step-14: Go into parameter 41: password Enter configuration password – 515442.

Step-15: Go into parameter 446: SELECT SCALE Select “scale-1” and press “enter” button.

Note: So now we entered into SLAVE-1 (arm-1) and Go into parameter 441: calibration parameters

Unit: “t”
Maxi value: 70.000t
digit: 0.500 like that….

Step-15A: Go into parameter 4472: CHANNEL Select “Channel-1” and press “enter” button.

Enter scale option: “scale-1” and similarly channel-2, 3&4 also enter “scale-1” in scale option

Step-16: Go into parameter 446: SELECT SCALE Select “scale-2” and press “enter” button.

Note: So now we entered into SLAVE-2 (arm-2) and Go into parameter 441: calibration parameters
Unit: “t”
Maxi value: 70.000t
digit: 0.500 like that….

Step-16A: Go into parameter 4472: CHANNEL Select “Channel-1” and press “enter” button.

Enter scale option: “scale-1” and similarly channel-2, 3&4 also enter “scale-1” in scale option

Schenck ZERO calibration procedure with DISOMAT Tersus For turret:

i) Ensure you are in the normal diplay.

ii) Ensue bin is Empty.

iii) Ensure no disturbance around the weighing bin,

iv) Press batten to perform quick tare. This will zero the bin weight values, if bin
weight is 2% lesser than its capacity.

Schenck SPAN calibration procedure with DISOMAT Tersus For turret:

i) Follow above point no – “a to f”. Now display will show you [441.CALIBRATION
PARAMETERS].Then

ii) Press batten to show [445.CALIBRATION], then

iii) Press batten, Display will show you [4451. DEAD WEIGHT], Then
iv) Press battens, Display will show you [DEAD WEIGHT ACTIVE] & [DEAD WEIGHT
COMPLETED] messages.

v) Now go to Parameter [441.CALIBRATION PARAMETERS]. To see the dead weight


stored values.

vi) Press batten to show [4452.LINEARIZATION], then

vii) Press batten to show [4453.RANGE], then EX:70 T

viii) Finally enter “field actual weight of the ladle” the above “EX” place and press
“enter” button.

ix) After the entered value display on controller main page display.