You are on page 1of 35

MiCOM C264 Human

Interface
PACiS Technical Training
CS&P – Support Team

PCL
• Content

 Front Face Description


 LED Description
 LCD Description
 Menu Tree

Schneider Electric - CS&P – C264 HMI – E01 2


• Content

 Front Face Description


 LED Description
 LCD Description
 Menu Tree

Schneider Electric - CS&P – C264 HMI – E01 3


• MiCOM C264C
C264C With LCD

Schneider Electric - CS&P – C264 HMI – E01 4


• MiCOM C264
C264 With LCD

Schneider Electric - CS&P – C264 HMI – E01 5


• MiCOM C264C
C264C Without LCD

Schneider Electric - CS&P – C264 HMI – E01 6


• MiCOM C264
C264 Without LCD

Schneider Electric - CS&P – C264 HMI – E01 7


• MiCOM C264 Front Face
Large graphic Display control

Large illuminated display

Pre-affected LED

Navigation
keys

Local/Remote
command
Settable LED

Operating keys Open/Close command

Schneider Electric - CS&P – C264 HMI – E01 8


• LED Overview
FRONT FACE
C264C 40TE C264M 80TE
(4U-170mm) (4U-170mm)

4/5 System LED


Local Control Panel
12/13 Configurable LED Liquid Crystal Display
12 Push Buttons

Schneider Electric - CS&P – C264 HMI – E01 9


• Content

 Front Face Description


 LED Description
 LCD Description
 Menu Tree

Schneider Electric - CS&P – C264 HMI – E01 10


• System LEDs
FAULTY OFF No fault
ON DB error, Hardware error
LED 0 FLASHING Slow Not used
FLASHING Fast ISaGRAF Fault (cycle too long,Queue overflow, POU faulty

ALARM OFF No Alarm


ON Alarm acknowledged
LED 1 FLASHING Slow Alarm inactive acknowledged
FLASHING Fast At least one alarm not acknowledged

MODE OFF Reboot


ON Operational mode
FLASHING Slow Maintenance mode
LED 2 FLASHING Fast Test mode

POWER OFF power off


ON power on
FLASHING Slow Not used
LED 3 FLASHING Fast Not used

LOCAL/REMOTEOFF All bays are in remote mode


simple HMI ON All bays are in local mode
only FLASHING Slow At least one bay in local mode
LED 4 FLASHING Fast Not used
Schneider Electric - CS&P – C264 HMI – E01 11
• Configurable LEDs
LED 5
LED from 5 to LED 16 are controlled via SPS or DPS
LED 6
LED 7 SPS or DPS state

LED 8
SET off / on / flashing slow / flashing fast
LED 9
RESET off / on / flashing slow / flashing fast
LED 10
INVALID off / on / flashing slow / flashing fast
LED 11
LED 12
LED 13
LED 14 Examples
LED 15 OFF Event Not Present, Reset, Remote, Disable
ON Event Present, Set, Local, Enable
LED 16 BLINK SLOW Event Invalid (Fault, unknown, undefined, Invalid,..)
BLINK FAST Events of high gravity

Schneider Electric - CS&P – C264 HMI – E01 12


• Content

 Front Face Description


 LED Description
 LCD Description
 Menu Tree

Schneider Electric - CS&P – C264 HMI – E01 13


• LCD Overview
Default View : Bay panel

Bay Name Computer


12 char Time
+
Bay L/R
Animated object
Note : Transformer +
Tap Changer
(min, max, current)

Bay Topology :
•Use extra short name
•Representation with
two drawing sets Optional AI Mini list M = Measurements
up to 4 MV S = States
C = Controls

Configuration : included into PACiS SCE Graphic Editor


Schneider Electric - CS&P – C264 HMI – E01 14
• Front Face Buttons
SERVICE
CLEAR/ PAGE
CANCEL

LEFT/RIGHT ENTER
switch panels
PAGE

UP/DOWN
scroll Lists

LOCAL/
REMOTE

SELECTION OPEN/OFF CLOSE/ON

Schneider Electric - CS&P – C264 HMI – E01 15


• LCD Panels Arrangement
 Bay Panels (up to 12)
monitor and control devices, access to measurements and status
 Alarm Panel
acknowledgement and alarm clearing
 Event Panel
FIFO list of 200 events
 Fault Panel
C264 faults
 Disturbance Panel
IED and C264 disturbance files
 Services Panel
general information
 I/O status Panel
DI couplers and DO contacts status on DI, DO and CCU boards

Schneider Electric - CS&P – C264 HMI – E01 16


• LCD Panels Arrangement
Bay panels
1 to 12 BAY_01 Alarms
Measurements panel

Events
panel

Input/Output
panel

Menu Fault panel


Tree
Panel
Services panels :
General Info

Disturbance
Schneider Electric - CS&P – C264 HMI – E01 Record panel 17
• LCD Bay Panels
On Bay Panel, Operator can :
 Access other bay panels by pressing on G
or G

 Select devices for command by pressing on


 Control switching devices :
 Put in “ON” or “CLOSED” by pressing on I
 Put in “OFF” or “OPEN” by pressing on O

 Then for execution (SBO case)


 Control Tap Position :
 Raise by pressing on
 Lower by pressing on G

 GoToMax by pressing on G

 GoToMin by pressing on G

 Then same button again for execution (SBO case)

Schneider Electric - CS&P – C264 HMI – E01 18


• LCD Events Panel

EVENTS <time>
Event Rank in circular queue
047----------------------------------
01/04/02 *12:15:10.123
FEEDER 63kV
SW63-5-2BB1
POSITION DPS
OPEN

Event date time with


048----------------------------------
01/04/02 *12:05:10.123 synchronisation attribute (*)
FEEDER 63kV
SW63-5-2BB1
POSITION DPS
CLOSED

↑↓
Bay / Module / Datapoint / Status

Schneider Electric - CS&P – C264 HMI – E01 19


• LCD Alarms Panel
ALARMS
Alarm appearance date with
0 1 / 0 4 / 0 2 *1 2 : 1 5 : 1 0 . 1 2 3
ACTIVE-UNACK 3
synchronisation attribute (*)
FEEDER63kV/5
SW 63-5- 2 BB1 Alarm State and Gravity
POSITION DPS
OPEN

0 1 / 0 4 / 0 2 *1 2 : 1 5 : 1 2 . 8 2 4
ACTIVE-UNACK 3
FEEDER63kV/5
SW 63-5- 2 BB2
POSITION DPS
OPEN

↑↓

Bay / Module / Datapoint / Status

Alarm Selection Acknowledge selected Clear selected inactive,


alarm (password) ack. alarm (password)
Schneider Electric - CS&P – C264 HMI – E01 20
• LCD Service Panel
General Services :
 MAC @
 Software version
 Database version
 Operating Mode
 ...

Schneider Electric - CS&P – C264 HMI – E01 21


• LCD Other Panels
Other Panels :
 DISTURBANCE
Is showing disturbance records from IED or CT/VT waveforms

 INPUT/OUPUT
Is showing every I/O board channel status

Schneider Electric - CS&P – C264 HMI – E01 22


• LCD Fault Panels
Fault type display
Is showing DISCONN if an IED is not connected
Is showing HARDWARE if an hardware problem (boards, …) occurs

Fault List
 By selecting the Fault Type, it will display the list of faults

Schneider Electric - CS&P – C264 HMI – E01 23


• Content

 Front Face Description


 LED Description
 LCD Description
 Menu Tree

Schneider Electric - CS&P – C264 HMI – E01 24


• Menu Tree Panel Access
BAY_0
Bay 1
Events
panels panel
1 to 12

Alarms
Input/Output
panel
Panel

Menu
Tree Fault
Panel panel

Services Panel
Disturbance
Record panel
Schneider Electric - CS&P – C264 HMI – E01 25
• Menu Tree Main Menu
MENU TREE

COMMAND

CONFIG

Schneider Electric - CS&P – C264 HMI – E01 26


• Menu « Command »
MENU TREE Reset Operating Hours
Change operating
mode
COMMAND Global Alarm ACK
Main Global Alarm CLR
Date
Counter Time
DB Switch
Language

Change Value

Schneider Electric - CS&P – C264 HMI – E01 27


• Menu « Config »
MENU TREE

COMMAND

CONFIG
Computer
Main

Bay

Comm
port
HMI
Main

Bay
Schneider Electric - CS&P – C264 HMI – E01 28
• Menu « Config / Computer »
CONFIG
Computer
Main

Bay

Comm
port

Schneider Electric - CS&P – C264 HMI – E01 29


• Menu « Config / Computer »

Computer IP Address (read only)


Main

Bay

Comm
port

Schneider Electric - CS&P – C264 HMI – E01 30


• Menu « Config / Computer »
IP Address (read only)
Computer
Main
List configured Bay
----------------------
Bay ----------------------
----------------------
Comm
port

Internal SC
AR
DEVICES
BI
MV
Schneider Electric - CS&P – C264 HMI – E01 31
• Menu « Config / Computer »
SC delay
Internal SC
AR
DEVICES AR delays (cycles, reclaim time,..)
BI AR type (1P-3P-3P, 3P-3P,….)
MV

Devices list Time open


Time close

Devices list
Motion 00 filtering
Devices list Motion 11 filtering
persistence Close
persistence open
Hysteresis Toggling option
Deadband
Thresholds 1 to 6
Schneider Electric - CS&P – C264 HMI – E01 32
• Menu « Config / Computer »

Computer
Main

Bay

Comm List configured ports


port

PORT
Speed
parity
stop
…..
Schneider Electric - CS&P – C264 HMI – E01 33
• Menu « HMI »
MENU TREE

COMMAND

CONFIG
Computer

HMI
Main

Bay

Schneider Electric - CS&P – C264 HMI – E01 34


• Menu « HMI »
menu tree timeout
HMI LCD lightness timeout
Main
devices selection timeout
Bay Password
Password validity timeout

Bay list

Suppression – activation
of devices’ names

Schneider Electric - CS&P – C264 HMI – E01 35