MiCOM C264 Human

Interface
PACiS Technical Training Level 1
PACiS Industrialisation Team

PCL
1) Front Face General
Description

Schneider Electric - COE – C264 HMI – 17/09/2010 2


1.1) MiCOM C264 / C264C (1)
C264C With LCD

Schneider Electric - COE – C264 HMI – 17/09/2010 3


1.1) MiCOM C264 / C264C (2)
C264 With LCD

Schneider Electric - COE – C264 HMI – 17/09/2010 4


1.1) MiCOM C264 / C264C (3)
C264C Without LCD

Schneider Electric - COE – C264 HMI – 17/09/2010 5


1.1) MiCOM C264 / C264C (4)
C264 Without LCD

Schneider Electric - COE – C264 HMI – 17/09/2010 6


1.2) MiCOM C264 Front Face
Large graphic Display control

Large illuminated display

Pre-affected LED

Navigation
keys

Local/Remote
command
Settable LED

Operating keys Open/Close command

Schneider Electric - COE – C264 HMI – 17/09/2010 7


1.3) LED Overview
FRONT FACE
C264C 40TE C264M 80TE
(4U-170mm) (4U-170mm)

4/5 System LED


Local Control Panel
12/13 Configurable LED Liquid Crystal Display
12 Push Buttons

Schneider Electric - COE – C264 HMI – 17/09/2010 8


1.4) System LED
FAULTY OFF No fault
ON DB error, Hardware error
LED 0 FLASHING Slow Not used
FLASHING Fast ISaGRAF Fault (cycle too long,Queue overflow, POU faulty

ALARM OFF No Alarm


ON Alarm acknowledged
LED 1 FLASHING Slow Alarm inactive acknowledged
FLASHING Fast At least one alarm not acknowledged

MODE OFF Reboot


ON Operational mode
FLASHING Slow Maintenance mode
LED 2 FLASHING Fast Test mode

POWER OFF power off


ON power on
FLASHING Slow Not used
LED 3 FLASHING Fast Not used

LOCAL/REMOTEOFF All bays are in remote mode


simple HMI ON All bays are in local mode
only FLASHING Slow At least one bay in local mode
LED 4 FLASHING Fast Not used
Schneider Electric - COE – C264 HMI – 17/09/2010 9
1.5) Configurable LED
LED 5
LED from 5 to LED 16 are controlled via SPS or DPS
LED 6
LED 7 SPS or DPS state

LED 8
SET off / on / flashing slow / flashing fast
LED 9
RESET off / on / flashing slow / flashing fast
LED 10
INVALID off / on / flashing slow / flashing fast
LED 11
LED 12
LED 13
LED 14 Examples
LED 15 OFF Event Not Present, Reset, Remote, Disable
ON Event Present, Set, Local, Enable
LED 16 BLINK SLOW Event Invalid (Fault, unknown, undefined, Invalid,..)
BLINK FAST Events of high gravity

Schneider Electric - COE – C264 HMI – 17/09/2010 10


2) LCD Description

Schneider Electric - COE – C264 HMI – 17/09/2010 11


2.1) LCD Overview
Default View : Bay panel

Bay Name Computer


12 char Time
+
Bay L/R
Animated object
Note : Transformer +
Tap Changer
(min, max, current)

Bay Topology :
•Use extra short name
•Representation with
two drawing sets Optional AI Mini list M = Measurements
up to 4 MV S = States
C = Controls

Configuration : included into PACiS SCE Graphic Editor


Schneider Electric - COE – C264 HMI – 17/09/2010 12
2.2) Buttons

CLEAR HELP

LEFT/RIGHT ENTER
switch panels
PAGE

UP/DOWN
scroll Lists

LOCAL/
REMOTE

SELECTION OPEN/OFF CLOSE/ON

Schneider Electric - COE – C264 HMI – 17/09/2010 13


2.3) LCD Panels Management (1)
 Bay Panels (up to 12)
monitor and control devices, access to measurements and status
 Alarm Panel
acknowledgement and alarm clearing
 Event Panel
FIFO list of 200 events
 Fault Panel
C264 faults

 Disturbance Panel
IED and C264 disturbance files
 Services Panel
general information, board status, IED connection status
 I/O status Panel
DI couplers and DO contacts status on DI, DO and CCU boards
Schneider Electric - COE – C264 HMI – 17/09/2010 14
2.3) LCD Panels Management (2)
Bay panels
1 to 12 BAY_01 Alarms
Measurements panel

Events
panel
Input/Output
panel

Menu Fault panel


Tree
Panel

Services panels :
General Info, Board
Info, IED Info
Disturbance
Schneider Electric - COE – C264 HMI – 17/09/2010
Record panel 15
2.4) LCD Bay Panel
On Bay Panel, Operator can :
 Access other bay panels by pressing on G

 Select devices for command by pressing on


 Control switching devices :
Put in “ON” or “CLOSED” by pressing on I

Put in “OFF” or “OPEN” by pressing on O

Then for execution (SBO case)


 Control Tap Position :
Raise by pressing on
Lower by pressing on G

GoToMax by pressing on G

GoToMin by pressing on G

Then same button again for execution (SBO


case)
Schneider Electric - COE – C264 HMI – 17/09/2010 16
2.5) LCD Events Panel
EVENTS <time>
Event Rank in circular queue
047
01/04/02
S12:15:10.123
FEEDER 63kV /5
SW63-5-2BB1
POSITION DPS
OPEN
Event date time with
048 synchronisation attribute

01/04/02 S12:05:10.123
FEEDER 63kV /5
SW63-5-2BB1
POSITION DPS
CLOSED Bay / Module / Datapoint / Status
↑↓

Schneider Electric - COE – C264 HMI – 17/09/2010 17


2.6) LCD Alarms Panel
ALARMS
Alarm appearance date with
01/04/02S12:15 :10.123
ACTIVE-UNACK 3
synchronisation attribute
0 1 / 0 4 / 02 S 1 2 : 1 5 : 1 0 . 1 2 3
FEEDER63kV/5 Alarm State and Gravity
SW 63-5- 2 BB1
POSITION DPS
OPEN
Alarm last change of state date
with synchronisation attribute

↑↓

Alarm Selection Acknowledge selected Clear selected inactive,


alarm (password) ack. alarm (password)
Schneider Electric - COE – C264 HMI – 17/09/2010 18
2.7) LCD Service Panel (1)
General Services :
 MAC @
 Software version
 Database version
Operating Mode
 ...

Board Status :
 List of boards present in rack / configuration
OK => Board OK
Missing => in DB but not in rack
Too Many => in rack but not in DB
Faulty => Faulty board

Schneider Electric - COE – C264 HMI – 17/09/2010 19


2.7) LCD Service Panel (2)

IED Connection Status :


 SBUS Clients
 Per protocol, connection status of IED, by
IED @

Schneider Electric - COE – C264 HMI – 17/09/2010 20


2.8) LCD Other Panels
Other Panels :
 DISTURBANCE
Is showing disturbance records from IED or CT/VT waveforms
 INPUT/OUPUT
Is showing every I/O board channel status

Schneider Electric - COE – C264 HMI – 17/09/2010 21


3) Menu Tree

Schneider Electric - COE – C264 HMI – 17/09/2010 22


3.1) Menu Tree Panel Access
BAY_0
Bay 1
Events
panels panel
1 to 12

Alarms
Input/Output
panel
Panel

Menu
Tree
Panel
Fault
panel

Services Panel
Disturbance
Record panel
Schneider Electric - COE – C264 HMI – 17/09/2010 23
3.2) Menu Tree Main Menu
MENU TREE

COMMAND

CONFIG

Schneider Electric - COE – C264 HMI – 17/09/2010 24


3.3) Menu “COMMAND”
MENU TREE Reset Operating Hours
Change operating
mode
COMMAND Global Alarm ACK
Main Global Alarm CLR
Date
Counter Time
DB Switch
Language

Change Value

Schneider Electric - COE – C264 HMI – 17/09/2010 25


3.4) Menu “CONFIG”
MENU TREE

COMMAND

CONFIG
Computer
Main

Bay

Comm
port
HMI
Main

Bay
Schneider Electric - COE – C264 HMI – 17/09/2010 26
3.5) Menu “CONFIG COMPUTER” (1)
CONFIG
Computer
Main

Bay

Comm
port

Schneider Electric - COE – C264 HMI – 17/09/2010 27


3.5) Menu “CONFIG/COMPUTER”(2)

Computer IP Address (read only)


Main

Bay

Comm
port

Schneider Electric - COE – C264 HMI – 17/09/2010 28


3.5) Menu “CONFIG/COMPUTER”(3)
IP Address (read only)
Computer
Main
List configured Bay
----------------------
Bay ----------------------
----------------------
Comm
port

Internal SC
AR
DEVICES
BI
MV
Schneider Electric - COE – C264 HMI – 17/09/2010 29
3.5) Menu “CONFIG/COMPUTER”(4)
SC delay
Internal SC
AR
DEVICES AR delays (cycles, reclaim time,..)
BI AR type (1P-3P-3P, 3P-3P,….)
MV

Devices list Time open


Time close

Devices list
Motion 00 filtering
Devices list Motion 11 filtering
persistence Close
persistence open
Hysteresis Toggling option
Deadband
Thresholds 1 to 6
Schneider Electric - COE – C264 HMI – 17/09/2010 30
3.5) Menu “CONFIG/COMPUTER”(5)

Computer
Main

Bay

Comm List configured ports


port

PORT
Speed
parity
stop
…..
Schneider Electric - COE – C264 HMI – 17/09/2010 31
3.6) Menu “HMI” (1)
MENU TREE

COMMAND

CONFIG
Computer

HMI
Main

Bay

Schneider Electric - COE – C264 HMI – 17/09/2010 32


3.6) Menu “HMI” (2)

menu tree timeout


HMI LCD lightness timeout
Main
devices selection timeout
Bay Password
Password validity timeout

Bay list

Suppression – activation
of devices’ names

Schneider Electric - COE – C264 HMI – 17/09/2010 33