You are on page 1of 10

Introduction of the

SAM
MINI DIALOG
Genset Application

SE-P
Product Engineering (Support)

22.03.2006 Service Update 2006 / Genset Application 2


Genset Application (Minidialogue)
MAIN MENUE
A SE 410
ERROR PAGE (A) active Alarm
(*)
SE System Error (**) B DL 10
(B) 0h > 1h
DL Default BUS Lost
RL Redundant BUS Lost
C RL 10
AL Alarm (C) 1h > 4h
EC ECU Error Code
NMT Network Management D AL 10
SD Sensor Defect (D) 4h > 12h
FB1 AL Project Related Al
E EC 303
(E) 12h > infinity
RED Red Alarm
YEL Yellow Alarm
MG Message
(**) System Error Numbers are (*) an (A) active Alarm is immediately
explained on the next sheet shown in
the (B) category as well

22.03.2006 ADEC Genset Application 3


Genset Application (System Failure numbers)
SE Failure Identifier SE No. SE Failuretext
SYS_ERR_TEMP_SD 0 Sensor Temperature Defect
SYS_ERR_TEMP 1 Temperature failure
SYS_ERR_SUPPLY_SD 2 Sensor Voltage Defect
SYS_ERR_SUPPLY 3 Voltage failure
SYS_ERR_CAN_A_BUS_OFF 4 CAN Bus-1 Error/Bus Defect
SYS_ERR_CAN_A_OVERRUN 5 CAN Bus-1 Overrun
SYS_ERR_CAN_B_BUS_OFF 6 CAN Bus-2 Error/Bus Defect
SYS_ERR_CAN_B_OVERRUN 7 CAN Bus-2 Overrun
TEMP_COMP_ERR 8 Temperature Compensation
Error
SYS_ERR_IO_SLOT_2 9 I/O-Module Slot2 Defect
SYS_ERR_IO_SLOT_3 10 I/O-Module Slot3 Defect
SYS_ERR_IO_SLOT_4 11 I/O-Module Slot4 Defect
SYS_ERR_SER_CONN_LOST 12 Serial Connection Lost
SYS_ERR_CAN_C_BUS_OFF 13 CAN Bus-3 Error/Bus Defect
SYS_ERR_CAN_C_OVERRUN 14 CAN Bus-3 Overrun
SYS_ERR_SA_CONN_LOST 15 S/A Bus Faulty
SYS_ERR_PAN_1_LOST 16 PAN 1 Defect
SYS_ERR_PAN_2_LOST 17 PAN 2 Defect
SYS_ERR_PAN_3_LOST 18 PAN 3 Defect
SYS_ERR_PAN_4_LOST 19 PAN 4 Defect
SYS_ERR_PAN_5_LOST 20 PAN 5 Defect
SYS_ERR_PAN_6_LOST 21 PAN 6 Defect
SYS_ERR_IO_SLOT_1 22 I/O-Module Slot1 Defect
SYS_ERR_IO_SLOT_5 23 I/O-Module Slot5 Defect
SYS_ERR_IO_SLOT_6 24 I/O-Module Slot6 Defect
SYS_ERR_IO_SLOT_7 25 I/O-Module Slot7 Defect
SYS_ERR_IO_SLOT_8 26 I/O-Module Slot8 Defect
SYS_ERR_DWNLD_SERVER 27 Download Server Collision
SYS_ERR_NOT_PROJ_NODE 28 not projected node

22.03.2006 ADEC Genset Application 4


Genset Application (Minidialogue)
MAIN MENUE
A SE 705
ERROR PAGE No TEXT

ESC+ENTER (Swap to OEM – Level)

ALARM PAGE A SE 705


ALARMTEXT

7 05

Explaining of the failure Sytem Failure Node Number


number above (705) (like MCS-5 System
Falure of DIS)

22.03.2006 ADEC Genset Application 5


Genset Application (Minidialogue)
MAIN MENUE

CAN 1 FB1
VIEW CONFIG ND: 5 BD: 125
PAGE
CAN 2 FB1
ND: 5 BD: 125

CAN 3 COORD
ND: 3 BD: 125

BDM SERVER CONF:


YES

Serial Usage:
TERMINAL

INFO PAGE Project + Software Versions


(like SmartLine)

22.03.2006 ADEC Genset Application 6


Genset Application (Minidialogue)
MAIN MENUE

VOLT: 24,70V
POWER PAGE TEMP: 31 DEGR

ECU Operating Hours


ACT. VALUE
PAGE
Engine Speed

P-Lube Oil (ECU)

T-Coolant (ECU)

T-Lube Oil (ECU)

FAN Speed in %

22.03.2006 ADEC Genset Application 7


Genset Application (Minidialogue)
MAIN MENUE

Function
MONITOR PAGE not available

I/O VALUE PAGE SLOT1/1 BOB2


NOT PROJ.

SLOT 1/2 BOB2


A.BIN 0

Attention:
- Next Channel Slot 1 with „Cursor down“
- Next Slot with „Cursor up“ (Slot2, Slot 3, Onboard Channel)“

22.03.2006 ADEC Genset Application 8


Genset Application (Minidialogue)
MAIN MENUE

BDM SERVICE
DWL/BDM COMPLETED
PAGE ND 2 PU CNT 1 ND 2 SYS CNT 1
CS OK BL 0 ENTER NO DATA BL 0

Attention:
- Next Node Number with „Cursor down“ / „Cursor up“

PASSWORD ENTER PASSWORD


h0000
PAGE

22.03.2006 ADEC Genset Application 9


Genset Application (Minidialogue)
CONFIGURAT.
MENUE

SELECT ENGINE TYPE:


PARAMETER 10V2000 M93
PAGE
SELECT DISPLAY:
ECU Overview

INTERFACE CONF:
No

Dwl. Node 2
Force DWL Page ESC
OK

Attention:
- Next Node Number with „Cursor down“ / „Cursor up“

Reset parameters
Reset parameters Exit Yes

Upgrade Firmware
Firmware Upgrade No Yes

22.03.2006 ADEC Genset Application 10