: PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 12 PAGE 00 OF 20
REVISIONS 00 APPROVED BY
L SUBBALAKSHMI
Sheet 1 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 10 PAGE 01 OF 20
1. Project Details
(WGC) Project
3 Customer HPCL Rajasthan Refinery Ltd. (HRRL)
4 Customer’s Consultant Engineers India Limited (EIL)
5 LSTK Contractor Tata Projects Ltd., Mumbai
6 LSTK Contractor’s Consultant Aker Solutions, Mumbai
2. Environment Specifications
REVISIONS 00 APPROVED BY
L SUBBALAKSHMI
Sheet 2 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 02 OF 20
Frequency Variation
5 Fault Level 40kA/3 sec
6 Transformer Type Dry type integrated Transformer (In Vendor scope),
Indoor
7 Rating Transformer must be designed to carry 110% of
calculated VFD rating. Transformer sizing
calculation shall be provided along with offer.
COPYRIGHT AND CONFIDENTIAL
4. Motor Data :
Sheet 3 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 03 OF 20
5. Scope:
Synchronous Bypass feature This shall include but not be limited to inverter
for bumpless transfer from sizing, transformer sizing, transformer impedance
VFD to DOL and vice versa; selection, vector group, input and output harmonic
Output choke for filter design and sizing, output dv/dt filter sizing,
synchronization, if required, motor cable selection etc.
Output PT for
synchronization VFD shall be provided with Synchronous bypass
COPYRIGHT AND CONFIDENTIAL
d) Power Cable glands (Flame The machine shall normally run on VFD. However
proof) and hardware for VFD at the discretion of the operator, it shall be
and Transformer, Cable switched on to bypass after synchronization with
glands (Flameproof) and lugs the VFD feeder. The transfer should be bumpless
for LCS. from VFD to DOL and vice versa.
e) Any special cable other than In case of drive mal-operation, the motor could be
power and control cables taken on bypass control manually, while the drive
from VFD to other could be attended independently.
equipment.
All other control and protections not included in
f) Any special tools and tackles. owner’s scope but required for vendors supplied
system for Synchronous Bypass shall be in
g) Mandatory Spares and vendor’s scope
Commissioning Spares.
Sheet 4 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 04 OF 20
6. VFD Specifications
Sl. Parameter Specification
1 Drive Wet Gas Compressor
2 Input Voltage From Integrated dry type Transformer
3 Power/Torque vs Speed Torque Speed2; Power Speed3
4 Single Line Diagram See Attachment 3-661-00-00979 REV.03
5 Output Voltage of VFD 0 to 6.6kV (V/f = Constant)
The information on this document is the property of BHARAT HEAVY ELECTRICALS LIMITED.
Sheet 5 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 05 OF 20
Sheet 6 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 06 OF 20
Sheet 7 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 07 OF 20
4 years.
It must not be used directly or indirectly in anyway detrimental to the interest of the company.
Sheet 8 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 08 OF 20
Sheet 9 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 09 OF 20
i) Output Frequency
ii) Output Current
iii) Motor Speed
iv) Output Voltage
v) DC Bus Voltage
vi) Output Power (It shall be possible to display
power output of the drive in kW)
COPYRIGHT AND CONFIDENTIAL
Sheet 10 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 10 OF 20
Sheet 11 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 11 OF 20
o) Inverter fault
p) System earth fault protection
q) The system shall be designed to deliver the motor input
current and torque for the complete speed torque
characteristics of the driven equipment.
r) If the motor load exceeds the limit, the drive shall
automatically reduce the frequency and voltage to the
COPYRIGHT AND CONFIDENTIAL
Sheet 12 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 12 OF 20
Sheet 13 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 13 OF 20
Protection:
It must not be used directly or indirectly in anyway detrimental to the interest of the company.
Connection:
HV Incomer: Termination arrangement to be provided for
3RX3CX300 sq. mm, Al, XLPE cable. Cable glands to be
provided by the vendor. The exact number and size will be
intimated during drawing approval stage. Cables in customer
scope.
Sheet 14 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 14 OF 20
Sheet 15 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 15 OF 20
33. SPARES
Sl. No. Parameter Specification
A Mandatory Spares Supplier should quote item wise price for the following
and Commissioning spares. Unpriced List of Spares quoted for shall be
Spares provided in the Technical Offer. Vendor to quote for
both Mandatory and Commissioning Spares.
The information on this document is the property of BHARAT HEAVY ELECTRICALS LIMITED.
Sl . Commissioning
Items Mandatory Spares
It must not be used directly or indirectly in anyway detrimental to the interest of the company.
no. Spares
Complete Power Cell 10% of the total quantity of Power
containing Rectifier & Inverter cells or 1no. (min of each rating,
with Gate Driver Modules, etc. whichever is more)
for one to one replacement at OR
site 10% of the total quantity of
converter & Inverter module
1 -
COPYRIGHT AND CONFIDENTIAL
OR (containing Rectifier
Diode/IGBT/IGCT/SGCT & Gate
Separate Converter & Inverter Driver modules) or 1no. (min of
Module containing Rectifier each rating, whichever is more
Diode/IGBT / IGCT /SGCT, Note- "OR" option is based on VFD
etc. with Gate Driver Modules construction of the Vendor
Transistors /IGBT/IGCT/ Other
1 no. of each rating
2 Power Semiconductor devices -
& type
along with gate driver
3 Control Cards 1 no. of each type 1 no. of each type
Power supply card and Power 1 no. of each rating
4 supply module
1 no. of each rating & type
& type
20% of each rating or 1 no. (min) of 1 no. of each rating
5 Power fuses
each rating, whichever is more & type
1 no. of each rating
6 Control fuses / MCB 10 nos. of each rating & type
& type
10% of each type or 1 no. (min) of
7 Contactors
each rating, whichever is more
-
12 RTD for Dry type Transformer 1 no. of each rating & type -
Sheet 16 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 16 OF 20
final tests.
b) Training: Vendor shall be responsible to train the
Owner's personnel at manufacturer's works and at Site.
The training shall include detail operation,
configuration, modification, calibration, troubleshooting,
preventive/ breakdown maintenance etc. as a minimum.
The outline and duration of this training shall be as
follows:
i)At manufacturer’s works : Two Owner’s Engineers
for a period of at least Seven man days.
ii)At site: Ten Owner’s Engineers for a period of at
least Seven man days
c) Commissioning: Commissioning of VFD System at
HRRL, Rajasthan site shall be in the scope of Vendor.
Final Acceptance shall be based on successful completion
of the same.
d) Any replacement of failed/damaged items during
commissioning shall be exclusively at Vendor’s cost.
e) Vendor is advised to stock necessary spares and ensure
easy availability to facilitate trouble free commissioning.
36 Software for Computer This software should be an easy to use commissioning tool for
Interface drives and shall be provided along with the system. The
interface details of VFD shall be incorporated as required for
data communication with DCS system with serial interfaces
with RS485 data links. Necessary hardware shall be included
in the scope and the interface protocol (Modbus only) shall be
provided.
Sheet 17 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 17 OF 20
Sheet 18 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 18 OF 20
Sheet 19 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 19 OF 20
8. Documentation
Sheet 20 of 93
P.S NO. : PS/445/2680
PURCHASE SPECIFICATION
REV. NO: 00
GROUP: CE-T&PD/COE
A4 – 11 PAGE 20 OF 20
Sheet 21 of 93
Sheet 22 of 93
High Voltage Squirrel Cage Document No.
Induction Motor B224-114-16-50-DS-1038
Datasheet Rev. No. A
Page Page 1 of 3
Project PMC Services for Execution of Rajasthan Refinery Project (RRP) Client HRRL - REGD. OFFICE
Unit Delayed Coker Unit Location Job No. B224 Unit No. 114
PURCHASER'S DATA
A. Site Conditions
1. Maximum Ambient Temperature °C 48.2
2. Minimum Ambient Temperature °C 3.4
3. Design Ambient Temperature °C 45
4. Relative Humidity % 100
5. Altitude mm Less than 1000
6. Environment Humid & Highly Corrosive
B. Technical particulars
1. Motor Tag no.: 114-KM-1001
2. Driven Equipment name: Wet Gas Compressor
3. Voltage: kV 6.6 +/- 10 %
4. Phase: Three
5. Frequency: Hz 50 +/- 3 %
6. Fault level: kA 40
7. Fault Duration: sec. 0.25
8. System Earthing: Resistance Earthing
9. Duty: Continuous
10. Method of starting: V.S.D & DOL
11. Cable size: mm² 3 Runs of 3Cx300 Sq.mm.
12. Cable type: Al. cond. XLPE insulated
13. Temperature rise: °C 80 °C (By RTD Method)
14. Cooling: CACA / IC611
15. Insulation class: F
16. Temperature rise Limited to insulation class B
17. Hazardous area classification: Zone 2, T3
18. Dust classification NA
19. Gas group: IIA/ IIB
20. Dust Group NA
21. Type of explosion protection: Ex’P’
22. Prestart purging for Ex(n) motor Applicable (Ex’P’ Motor)
23. Type of ingress protection: IP 55
24. Reacceleration:: Yes
25. Diff. protection CTs: Yes , 3 Nos. in NTB (By Purchaser) R1
26. CT specs.: CORE WOUND TYPE CT
CT Ratio: 630/1A,
Secondary Winding Resistance Rct (max) at 75 ˚C≤ 5 Ω,
Knee Point Voltage : Vk ≥ 252 V,
Excitation Current : Imag ≤ 30mA at Vk/2
Insulation Class: E or Better
Material : Cast Resin
BIL: 7.2kV/ 20kV / 60kVp, Freq.: 50 Hz
Standard: IS-16227-1 & 2 , STC: 40kA / 3 Sec
(CTs are Not in BHEL scope) R2
27. Color shade: 632 as per IS 5
28. Thermisters: Not Required
29. RTD: Required
30. BTD: Required
31. RTD/BTD monitoring device: Compressor vendor BHEL, Hyderabad Scope R1
32. Applicable specification: EIL spec. 6-51-0031 Rev 6
DRIVEN EQUIPMENT MANUFACTURER's DATA
1. Suggested motor rating: kW 5150 kW
A 13-MAR-2019 ISSUED WITH TENDER BANSAL VARUN SAHU MANJIT KUMAR SAHU MANJIT KUMAR
Sheet 23 of 93
High Voltage Squirrel Cage Document No.
Induction Motor B224-114-16-50-DS-1038
Datasheet Rev. No. A
Page Page 2 of 3
Project PMC Services for Execution of Rajasthan Refinery Project (RRP) Client HRRL - REGD. OFFICE
Unit Delayed Coker Unit Location Job No. B224 Unit No. 114
1. Rating: kW 5150
2. Manufacturer: BHEL Bhopal
3. Frame designation: 1SB1908-4
4. No. of poles: 4
5. Full load speed: RPM 1496
6. Mounting: Horizontal
7. Full load torque (FLT): mkg 3351
8. Starting torque: % of FLT 75
9. Break down or pull out torque % of FLT 175
10. Full load current (FLC): A 516
11. Starting current at 100% % of FLC 500 % FLC (Incl. of Tolerane)
12. Rotation viewed from coupling end: CW (Looking from Motor DE)
13. Starting time at 80%/100% voltage: sec. 42 (@ 85%) / 19 (@ 100%) (Min. Voltage–85%RV)
14. Locked rotor withstand time (cold/hot) at,
80% voltage sec. 44 / 32 (Cold & Hot withstand time @85% Voltage) R2
100% voltage: sec. 30 /24
15. Time (Te) for Increased Safety Motor at 100% Voltage NA
16. Efficiency at 75%/100% Load: % 96.6 / 97.0
17. Power factor at 75%/100% Loa 0.90 / 0.90
18. Heating/Cooling Time Const. (min.) min 30/90
19. Space heater - voltage & power: 1000 Watts , 1Ph 240V AC R2
20. Moment of inertia, GD2: kgm² 2070
21. DE/NDE bearing type & no.: Sleeve bearings, DIN Standard 1 No DE (Size-22-Ø200) & 1
No. NDE (22-Ø200)
22. Type of lubrication: FOLS (6.0 LPM / Per Brg., ISO VG 46)
23. Type of main terminal box: PSTB Type
24. Type of neutral terminal b Fabricated Terminal Box
25. No. of Terminals 6 Nos.
26. Weight of motor: kg 25000 kg
A 13-MAR-2019 ISSUED WITH TENDER BANSAL VARUN SAHU MANJIT KUMAR SAHU MANJIT KUMAR
Project PMC Services for Execution of Rajasthan Refinery Project (RRP) Client HRRL - REGD. OFFICE
Unit Delayed Coker Unit Location Job No. B224 Unit No. 114
Eil Notes
1 Recommended list of maintenance spares for two years operation shall include the following as minimum: (a) Bearing DE/NDE one set, (b) Terminal box
coverwith screws, (c) Fan, (d) Terminal block
2 Thermistors, RTDs and BTDs are applicable for motors as per EIL Specification 6-51-0031.
3 Cable glands to be supplied with motors shall meet all requirements as pe IS/IEC-60079.
4 HV motors starting current shall be limited to <= 500% of FLC (Subject to IS tolerance) .
5 Starting time calculations shall be based on operating conditions specified on Material Requisition eg. open valve ccondition/closed valve condition, at no
load/full load, as applicable.
4 HV motors starting current shall be limited to ≤500% of FLC (Incl. of IS tolerance). R1
5 Starting time calculations shall be based on operating conditions during 121%DC1_MINMW start-up condition. R1
6 Minimum no. of consecutive COLD & HOT starts for motor shall be 2 and 1 respectively. R1
A 13-MAR-2019 ISSUED WITH TENDER BANSAL VARUN SAHU MANJIT KUMAR SAHU MANJIT KUMAR
Sheet 25 of 93
STARTING TORQUE CURVE FOR CENTRIFUGAL
COM PRESSOR Sheet 1 of 2
65 DC1_M AXM W
Nominal Torque %
60 DC2_M INM W
55
DC2_NORM W
50
DC2_M AXM W
45
40 S/ U_N2
35 S/ U_FUELGAS_RICH
30 S/ U_FUELGAS_LEAN
25
S/ U_NATGAS_RDG
20
S/ U_NATGAS_CH_LEAN
15
10 S/ U_NATGAS_CH_RICH
5 VAP_LPG
0 DC1_NORM W_TD
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
DC2_NORM W_TD
Rotational Speed %
The motor is provided with VFD in order to realize different operating conditions as specified by the
customer. These are indicated by the curves as shown above.
Motor Rating 5150 kW
Nominal Power 4477 kW
Motor Speed at Full Load 1485 rpm
Nominal Torque 2933 kgm
Static Torque 439.95 kgm
GD2 (Referred to Motor Speed) 6900 kgm2
Direction of Rotation seen from Coupling end (for Motor) CW
Shaft end cylindrical diameter 220 mm #
No. of Keys on Shaft end 1
Speed Range % 60-105%
Connection for Hub on Shaft Cylindrical fit of H6 / m5
Compressor Power is referred to low speed shaft of step up Gear Box
ARRANGEMENT OF MACHINES
2MCL807
(#) Considered for coupling sizing. Motor group to check adequacy and confirm.
Please refer enquiry specification for all other technical details to finalize the motor design (Refer sheet2 for DOL)
Date Dept. code
STEAM TURBINES AND COM PRESSORS
11.06.2020 420
Format No. Prepared Checked Approved Draw ing No. Rev
CA0-1-034-00 KVS NEM A YVRL 4CM 41600934 00
Sheet 26 of 93
STARTING TORQUE CURVE FOR CENTRIFUGAL
COM PRESSOR Sheet 2 of 2
CASE DESCRIPTION
SL NO DESCRIPTION COMPR. POWER (KW) COMPR. SPEED (RPM)
1 121% FLOW DC1 NOR MW 3986 7844
2 121% FLOW DC1 +NOR MW 3596 7377
3 121% FLOW DC1 -NOR MW 4477 8405
4 DESIGN CASE1 NOR MW 3294 7544
5 DESIGN CASE1 +NOR MW 3001 7133
6 DESIGN CASE1 -NOR MW 3654 8028
7 DESIGN CASE2 NOR MW 3275 7557
8 DESIGN CASE2 +NOR MW 2981 7145
9 DESIGN CASE2 -NOR MW 3631 8041
10 START UP NITROGEN 1546 6695
11 START UP FG RICH GAS 1883 7500
12 START UP FG LEAN GAS 1451 8400
13 START UP NG RDG CAIRN 2104 8100
14 START UP NG CHHARA LEAN LNG 1612 8100
15 START UP NG CHHARA RICH LNG 1967 8100
16 START UP VAPOURIZED LPG 1927 5251
17 DESIGN CASE1 TURNDOWN 3095 7482
18 DESIGN CASE2 TURNDOWN 3106 7507
Sheet 27 of 93
Copyright ElL - All rights Format No. 8-00-0001-F1 Rev. 0
pamasai sly6P IIV — 313 31150do0
Sheet 28 reserved
of 93 0 'Aed 6d-1000-00-9 '0N iewiod
Approved
Aq panoiddv
by
Aq ON
No
Aq
Chairman Convenor
by by
ueuule43 Jouanuo3
Purpose Date
asocUnd a;ea
'AO>:
Checked Prepared Rev.
Bureau Committee Pa)1381-13 paJedaid 1
nearng eamwwoo
Standards Standards
spiepuels spiepuelS
SKG VPS AAN SSM ISSUED AS STANDARD SPECIFICATION 25.03.03 0
ONS SdA NW INSS NOLLVO1d103dS Cl2:IVCINV1S sv awssi £0.£0.9Z 0
SPECIFICATION
NO JMS SG AM NOIIVOIJI03dS 24.04.09
aN SINf DS 1NV REVISED AND ISSUED AS STANDARD 60•40"4Z I.
ClizIVCINVIS sv a3nssi CINV CI3SIA3d
SPECIFICATION
NOI1VOld103dS 16.10.14 2
>1H VS/NIN REVISED AND ISSUED AS STANDARD .171:01;91.
CkIVONVIS sv cnnssi CINV CI3SIA3H
DRIVE SYSTEM
waisAs 3A12111
HV VARIABLE FREQUENCY
ADMaflòalli altIVDIVA AH
FOR
210,1
SPECIFICATION
NOLLVDIJIDads
~ Fqr~e:~1 ct
he:u4
~ r~f2li
4ik
L14-Itg
Page 1 of 16 DRIVE SYSTEM
91.10 l afied LAGISAS 3A121CI (A Go'll 01 India Undertaking)
HV VARIABLE FREQUENCY (6.1.1.P.F1 .P.1 I. V.9 V/ (1:.1:12C 11.1
A3N3flO32ld 319V12IVA AH
6-51-0050 Rev. 2 INDIA LIMITED
•Aed 0900- 1S-9 FOR G311W11 VIGNI
ENGINEERS
STANDARD SPECIFICATION No. dOd
SPECIFICATION S2133NION]
.oN NOLLV3ld103dS adVCINVIS NOLIVOld103dS
NOIIV3ld103dS NOI1V31d103dS 421VCINVIS '01.%1
.kir?MIDP S2133N19N1 SPECIFICATION
210d STANDARD SPECIFICATION No.
4311VVI1 VIGINI FOR Z .A021 0900-1,9-9
A3N13110321d 318V121VA AH 6-51-0050 Rev. 2
HVVAR~BLEFREQUENCY
..7triss,?1,1,..., aiui (6.Nel.Ouri .1.1 lo 1,09 vl
111131SAS 3A121C1 91 Jo Z 95ed
DRIVE SYSTEM Page 2 of 16
:suogmitaiqqy
Abbreviations:
3V lua.unp 2u!I2wolIV
AC Alternating Current
SIU splupuels uu!pui jo nuaing
BIS Bureau of Indian Standards
SH prepuels qsgpg
BS British Standard 41011TrIV 43II1M3 I-41103
V3D
CEA Central Electricity Authority
durei waosaionid puthuop
CFL Compact Fluorescent Lamp
21,11AII3 (Rgnip XpatuJoj) qateasai land puu utuiyA13o ainlgsui teijuap
CIMFR Central Institute of Mining and Fuel Research (formerly CMRI)
V32ID paluauuy pioD P3II021 PI03
CRCA Cold Rolled Cold Annealed
M3 Jalum
CW DG Cooling Water
Direct Current
lua.unp pa.ga
DC SDG waisiCs io.uuop paincuiTsm
DCS Distributed Control System
'10G oun uo paim
DOL Direct On Line
Sag Luois4 10.ijuo3 Feogpoia
ECS Electrical Control System
ogauRewoijoam
EMAH Electromagnetic or1i0/1 II2!H
HV High Voltage
Dai uo!ss!uauop 1u3!uqoa1o.upan Feuo!wuniui
IEC International Electrotechnical Commission
aam sioloua souloipola puu lupploao jo aTnTgsul
IEEE Institute of Electrical and Electronics Engineers
ZOgI
IEGT
sJols!surii aiug paouuqua uogoarui
Injection Enhanced Gate Transistors
199I JoIsIsurii imodm alug pamnsui
IGBT Insulated Gate Bipolar Transistor
IDDI Jo1s1suu.11 pamnuauop aiu9 paluinsui
IGCT Insulated Gate Commutated Transistor
O/I TndlnO/Tndul
110dI
Input/Output
IP Ingress Protection
uogoaloid ssaffiui
SI piepueis ue!pui
IS Indian Standard
apogj &gi.i!tua TiOn
LED Light Emitting Diode
Val andure!IIIN
rnA Milliampere
HDIN Ja)fuaig Tmoti3 aJniu!ugni
MCB Miniature Circuit Breaker
MTBF Mean Time Between Failure
ainuud uaamjag augj, uuaini
MTTR Mean Time to Repair
.qudax oT awu uuaw
uogupossy s,Jainprjnuulni luo!ipan teuoguN
NEMA National Electrical Manufacturer's Association
PLC Programmable Logic Controller
Jailanuop o!&yi aiqututuuffiald
Od Japio asugamd
PO Purchase Order igod
3Ad
PVC Poly Vinyl Chloride
I39S Jois!sue.u, pamnunuop alug uom!s
SGCT Silicon Gate Commutated Transistor
GHI uo!polsm o!uoturcH luTo.L
THD Total Harmonic Distortion
Break Over Voltage Jano xuaJH
V BO
ouA
gQA Javitioaloipao iagosInau purcpaA
VDE Verband Deutscher Electrotechniker
CLIA anpa X3uanbaid aiquprA
VFD Variable Frequency Drive
simaimop
CONTENTS
o" i 3do3s t7
1.0 SCOPE ................................................................................................................................. 4
0•Z SCRIVGNIVIS GNV SWOD 17
2.0 CODES AND STANDARDS .............................................................................................. 4
o" £ sNOLLICINOD L1IS s
3.0 SITE CONDITIONS ............................................................................................................ 5
0"17, simmniaxinÒax -rvxamao s
4.0 GENERAL REQUIREMENTS ........................................................................................... 5
0' S sit\law3xinö INTDINH= s
5.0 TECHNICAL REQUIREMENTS ....................................................................................... 5
0'9 aDNIVIdaDDV GI\IV omusai `NOLL33dS1\11 S1
6.0 INSPECTION, TESTING AND ACCEPTANCE ............................................................. 15
o•L NOLLVDIdumap 91
7.0 CERTIFICATION ............................................................................................................. 16
0.8 HaLVdS3G OINV ONDIDVd 91
8.0 PACKING AND DESPATCH ........................................................................................... 16
O'I 1dO3S
1.0 SCOPE
ayI Joj sluotuagnboi lupulq3oi wnutijugn otp. ougop oI st uo!luDgpods su.l jo odoos oqi
1.1 The scope of this specification is to define the minimum technical requirements for the
onpa i<ouonboij 01(121.tgA 3V `o2unoA 42!H Jo iClddns puu Rugsoi `oinpujnuetu `112!sop
design, manufacture, testing and supply of High Voltage, AC Variable Frequency Drive
/JoioN uogonpui oReD latunbs tplm oioldwoo aq gugs tuaiss cHA oqj, luol.ss
system. The VFD system shall be complete with Squirrel Cage Induction Motor/
jt) Jatwojsueg Indu! .13110ALIO3 `Joponuop `looqs ulup ui powoods su JoioN snouonpuiCs
Synchronous Motor as specified in data sheet, Converter, Converter input transformer (if
liuqs Jouuojsueij Indlno aApp `P°3.& 423IPoads ssanin) tauttojsueij indtno antip `(pa.ijnbai
required), drive output transformer (unless specifically agreed, drive output transformer shall
(paitnbai j!) siagg ontouuuti `sat.rutgxnu patupossu gltArt .1040E3.1 )11.11I 3Q `(popytoid aq Iou
not be provided), DC link reactor with associated auxiliaries, harmonic filters (if required)
lauud io.nuoo Jolotu feool patunotu piag puu
and field mounted local motor control panel.
Z.I `tualsiCs aialdwoo atp. jo 2utuogounj puu 2utiaautRua Joj apellsuodsal aq gegs JopuaA
1.2 The Vendor shall be responsible for engineering and functioning of the complete system,
apniou! geqs siy j. .staags mup puu uogeoupads snp jo tuatuaitnbai puu tuatut aqt 2ugaaut
meeting the intent and requirement of this specification and data sheets. This shall include
`uogoalas aottepadtu! Jaugojsuu.g `'u!zts Jautiojstreit `x.ijz!s Japanut ol palttug aq jou inq
but not be limited to inverter sizing, transformer sizing, transformer impedance selection,
`2u!z!s Jagg Tp/Ap Indlno `Stqz!s puu uRtsap Jaqij otuoutreq indino puu indu! `dnot2 .101.A
vector group, input and output harmonic filter design and sizing, output dv/dt filter sizing,
.uogoolos/Ru!z!s Jolow puu uogoolos oiquo
motor cable selection and motor sizing/selection.
£.1 DV A 0001 anoqu oReijon indu! Japonuoo 5'tgiveq stuoisXs oApp ol soudde uoguogtoods suu,
1.3 This specification applies to drive systems having converter input voltage above 1000 V AC
A000I I 2u!pniout puu ol dn puu
and up to and including II OOOV AC.
0.Z al\IV S31103
2.0 CODES AND STANDARDS
I.Z ssalun spiepums 2utAnollo3 atg jo suompa Isam atg gitm "Cidutoo gegs Tuawd!nba
2.1 The equipment shall comply with the latest editions of the following standards unless
:as!nniaglo pagpads
specified otherwise:
SZESI sJotoN uogonpui asuqd-aaita
IS:325 Three-phase Induction Motors
OOLESI saotnaa Jolonpuootwas jo sogspaputegp puu s&qtex Fuguass
IS:3700 Essential Ratings and Characteristics of Semiconductor Devices
SIL£SI saotnap 2'utionpuoo-nuas Joj sloquKs tauai
IS:3715 Letter symbols for semi-conducting devices
I I1717:SI soolnop Rugonpuoo-guas jo uoijeuR!sap jo apop
IS:4411 Code of designation of semi-conducting devices
IOOSSI paluffiatui puu S33IA0p Jolonpuoo!was jo s2utAnuJp jo 110pUndald .10.1 opi[n9
IS:5001 Guide for preparation of drawings of semiconductor devices and Integrated
sitno.qp
Circuits
69.17S:SI sao!nau uogounf topnpuoonuas jo asn agt toj aogorid jo apop
IS:5469 Code of practice for the use of semiconductor Junction Devices
68L8:SI uogonput asugd aanu .10,1 sogspaloungo 03UULL1.10j.10d jO sanluA .101.0W
IS:8789 Values of Performance characteristics for Three Phase induction motor
519ZISI aSup lan!nbs asuqd aatta - stol.oN uogonpui tuatogn iQlaua
IS: 12615 Energy Efficient Induction Motors - Three Phase Squirrel Cage
6ZLZI:SI .103 uoguogpads uotutuop Jua4xnuo3 puu Jgo4owns
IS:12729 Common specification for High-Voltage Switchgear and Controlgear
standards spiupums
106.171:S1 stgiotp palut2alui 2 sao!nap ataJosta -saotnap Jolonpuoo-ttuas
IS:14901 Semi-conductor devices- Discrete devices & Integrated Circuits
088SISI -S.101.10M103 iggi1110.1j paj uatinn sJoiotu uogonpui a5'-up asuqd aanll,
IS:15880 Three Phase Cage Induction motors when fed from IGBT Converters-
amno U0pMliddV
Application Guide
palmnunuoo auq puu stuawaitnbat iuJaua' stopanuop topnpuoonuas£- 1-9t7109:Dai
IEC:60 146-1-3 Semiconductor Convertors general requirements and line commutated
S.1010U0.175,.10111.10JSUUJI-S101.10AU00
convertors-Transformer & reactors
00819:pal swalsi(s attpp Jamod luottpala paads alquistifpy
IEC:61800 Adjustable speed electrical power drive systems
reOl.11.000 1.1I10.111.10D S3ILIOULLCH JOJ STUOCUOJIribal puu saogouid papuatutuooa
IEEE:519 Recommended Practices and requirements for Harmonics Control in Electrical
ST1101SXS JOMOd
Power Systems
Z.Z aiquondde aq gutis ut5'tio jo X.nunoo atp Jo sptupuets atp `tuawdtnba patiodtut Jo asuo uI
2.2 In case of imported equipment, the standards of the country of origin shall be applicable if
- spirpums impui aiquogddu atp. umg wa2uttls .10 Tualunniba a.tu spnpums asatg
these standards are equivalent or stringent than the applicable Indian standards.
£.Z X.tolrums Jalgo pue suotluln2a2l dg3 Jo suo!s!Acud aqt ot uuojuoo osue ijugs Inauldtnba aqi
2.3 The equipment shall also conform to the provisions of CEA Regulations and other statutory
regulations currently in force in the country. . /(4unoo atp. tij aoioj ui Xnuauno suogmn2ai
17.Z /SH nai Xq panss! spsupuuts `tuawdwba Xuu soj aiquiluxu 10U OIC spiupuuis umpui asuo
2.4 In case Indian standards are not available for any equipment, standards issued by IECI BSI
-aiquoudde aq puqs XouaRe luatunpba ao ViniaN /a3AI ijaA
VDEI IEEEI NEMA or equivalent agency shall be applicable.
S'Z atp `swawnaop alquollddu snotiun ur pagpads swatuagnbai uaampq ptpuoo Xne jo OSU3 UI
2.5 In case of any conflict between requirements specified in various applicable documents, the
puu tuug aq prqs pse2as stql ut uo!spap S,JOUMO `10A0MOH prqs auo tuaut.ps isow
most stringent one shall prevail. However, owner's decision in this regard shall be final and
-21nputq
binding.
0*£ SKOLLIONO3 3IIS
3.0 SITE CONDITIONS
I.£ ut pagpads su suompuoo atts pagpads Japun asesado oi pautsap aq peqs waisXs antip aqi
3.1 The drive system shall be designed to operate under specified site conditions as specified in
Dopt, jo anuriadwat watqwe uS!sap u `watalp pauoguaw Xpuogpads tou 3I .spaqs uiup alp
the data sheets. If not specifically mentioned therein, a design ambient temperature of 40°C
. paiap!suoo aq prqs pnal uas nuaw anoqu sanaw 000 I tqpaaaxa tou aptumu uu puu
and an altitude not exceeding 1000 metres above mean sea level shall be considered.
Z.£ pazt.mssaid ao pauompuoo-stu `snopsezuq-uou u ut sJoopu! MII21-su! 0€1 llugs 0^!-IP DV 011I
3.2 The AC drive shall be installed indoors in a non-hazardous, air-conditioned or pressurized
su aq peqs (Jooput isoopino) uogupmsut Jaustojsuesi 1.aaqs uiup ui pagpads su `W00.1
room, as specified in data sheet. Transformer installation (outdoorl indoor) shall be as
pagpads su UOIC snopiuzuq .10 OSUS ut ssoopwo 130IMsui aq puqs soloN iaaqsutup ui pmuo!put
indicated in datasheet. Motor shall be installed outdoors in safe or hazardous area as specified
.Taaqsmup ui
in datasheet.
£.£ aql sapun 2ugm amdawuu sad su Xinp snonuiiuoo Joj pautsap aq puqs utawdwba atp. IIV
3.3 All the equipment shall be designed for continuous duty as per nameplate rating under the
.suompuoa wa!qure pagpads
specified ambient conditions.
simawamnöall IvllaKa9
4.0 GENERAL REQUIREMENTS
mau pursq aq prqs wawd!nba paiajjo aqiOMS 1.11I/4A )1ausT piag uanoid puu X&mouqoal 1-1C 30
4.1 The offered equipment shall be brand new with state of art technology and proven field track
.pasajjo aq prqs wawdpba adX4oloJd oN1 .psooas
record. No prototype equipment shall be offered.
aqt .10,1 SODIAJOS poddns aotteuannew puu sprd ands jo 4pqrpuive ainsua peqs sopuaA
4.2 Vendor shall ensure availability of spare parts and maintenance support services for the
Addns jo mup aqt wag sie3/ 0 I 1S10I iu .101 watudwba paJajjo
offered equipment for at least 10 years from the date of supply.
aiojaq Zlg puu tuawdpba jo sasn pua atp. oi ivaX OUO Tsual iu jo aogou u anis ireqs sopua A
4.3 Vendor shall give a notice of at least one year to the end user of equipment and ElL before
puu saseds Joj sap.to jo tuatuaamd Joj sasn pua alp aiquua ot saiuds/pnposd aqi ino 2utsuqd
phasing out the product/spares to enable the end user for placement of order for spares and
servIces. 'SOOIAJOS
f't7 uogaaias ut Jallddns Tuawdwba uantip ati tittm uogrutpso-oa Jadoid asnsua prqs JopuaA
4.4 Vendor shall ensure proper co-ordination with the driven equipment supplier in selection I
.utaiss antip Xauanbag alqutien paJajjo jo Sutz!s
sizing of offered variable frequency drive system.
O'S iNaixamaÒall
5.0 TECHNICAL REQUIREMENT
I'S
5.1 Performance Requirement
watuaiwball ammumopad
I' Otti Xsax ap!Awd peqs puu tonpoid psepums su pau!sap luatagja X5Jaua aq peqs tualss ola
5.1.1 The system shall be energy efficient, designed as standard product and shall provide very high
-aspu JUOM uogweilx moi puu uogioistp owousteq moi `.101OUJ JOMOd 0!q 'Ximqullat
reliability, high power factor, low harmonic distortion and low vibration I wear I noise. It
pagnbal aq putis sloot imoads ou puu asuadxa puu awg mntwww ut puisut oi Xsua aq prqs
shall be easy to install in minimum time and expense and no special tools shall be required
for routine maintenance. .aoueuatumu autinos Joj
Z' I ataidwoo atit Joj anlmoi puu tua.uno indui Jotom atp saxgap oi patffitsap aq puqs watsXs
5.1.2 The system shall be designed to deliver the motor input current and torque for the complete
puu %0 jo uogmsex Xiddns indut qttm `wawd!nba uantsp atp jo sagspapuseqa anbsot paads
speed torque characteristics of the driven equipment, with input supply variation of ±1 0% and
atp pur sogspapuseqa puoi aqt soj aiqultns aq peqs waisXs aqi .yo u jo uogm.tun Xauanbap
frequency variation of ±3%. The system shall be suitable for the load characteristics and the
puu tutuaaqi aqt titpuutsqltm jo alquduo aq prqs iI .wawd!nba uaxpp atp. jo Xinp iuuogmado
operational duty of the driven equipment. It shall be capable of withstanding the thermal and
.wia.no-tsoqs tuag 2uttinsai `anlmol luattreqoaw itmstrup alp puu sassaps o!utuuXp
dynamic stresses and the transient mechanical torque, resulting from short-circuit.
utsuJado 1.ijmopo3 atp jo 0.10111 .10 OUO ui 012.10d0 oi pautsap aq peqs tuatsXs antsp auti
5.1.3 The drive system shall be designed to operate in one or more of the following operating
:paqs uiup aqi ui pagpads .10 wawdpba uant.tp atp jo sagsismouseqo iins oi su sapow
modes as to suit characteristics of the driven equipment or specified in the data sheet:
pasunbs paads a t paads jo uogaunj u su 14uuqa anlikn aiqmseA
a. Variable torque changing as a function of speed i.e. Speed squared
b.
.q paads ogpads u JOAO anbiol iuuisuoj
Constant torque over a specific speed range
paads uaqm sasuapap anbiot atp ataqm O&r0.1 paads ogpads u JOAO JOMOd iuuisuoj
c.
*0 Constant power over a specific speed range where the torque decreases when speed
mcreases SOSUOJOUI
d.
.p Any other as specified in data sheet
paqs uiup ut pagpads su Jawo Xuy
twm jul124) pasuq JossanoJdomw twm paddwba aq uqs -MloJtuon an!Jp aqi
5.1.4 The drive controller shall be equipped with microprocessor based digital regulator with
uu Joj aptnoid nutis n!$21[ JoTeinaJ wituon Jamod aqZ suo!inunj aiquwureffloid
programmable functions. The power control regulator logic shall provide for an
sluawisnfpu plag jo awuden aq Hugs puu aninn wull luaJinn uoguialanap/uotTuJatannu
acceleration/deceleration current limit curve and shall be capable of field adjustments
iCiaTeJudas aq iiugs uwwJalanap puu uog.uniannu JuautT .umop waisi(s aqi Wwwws Tnotwm
without shutting the system down. Linear acceleration and deceleration shall be separately
.spuonas oz woJj aiquwwuffloid
programmable from 0.1 to 20 seconds.
I "S aq Hutis uopugun paads aq1 puu uoguJado wuJpenb affitijs Joj awwws aq ireqs walsiCs ata
5.1.5 The System shall be suitable for single quadrant operation and the speed variation shall be
jo Xouinoou ias paads twm laags uiup ut pagtoads as!mialgo ssawn % oot-ot 021.mi giiM
with range 10-100 % unless otherwise specified in data sheet with speed set accuracy of
.paads patui jo 0/0 - 0± jo uogrwRai ams i(puais puu paads tunwpcew pairJ jo
±l % of rated maximum speed and steady state regulation of ±0.5% of rated speed.
9' I su aq llugs indino wa.unn puu a2unon agi jO (GELL) uopioistp nwoutzug lutol atu,
5.1.6 The total harmonic distortion (THO) of the voltage and current at inverter output shall be as
2s, situull winp aqi -Joww aqi jo tffi!sap aq1 tij paJap!suon aq llugs atuus puu 00819 D31 .rad
per IEC 61800 and same shall be considered in the design of the motor. The dvldt limits &
"z-oos .tad su aq osue llugs )feadA
Vpeak shall also be as per IEC-61800-2.
S L" Jautiojstre4 indut wew agt jo i(tuw!Jd iu walsXs amip aqi jo ap!s ic:Idns aqi iu snwoutteH
5.1. 7 Harmonics at the supply side of the drive system at primary of the main input transformer
su uotpols!p aRellon puu luallno jo sianai alqumollu wnwtxrw agl twillm palopisai aq Hugs
shall be restricted within the maximum allowable levels of current and voltage distortion as
tffl!sap tuJojJad Hugs Jopuan atli jo uompa isam ag1 ui suogepuautwonai .tad
per recommendations in the latest edition of IEEE-519. The vendor shall perform design
puu walsi(s Jamod atp oi papauuon GjA 1.1!Jap!suon tualsis Jang nwoutteti Joj uoguinniun
calculation for harmonic filter system considering VFO connected to the power system and
PoIlulsiji aq llugs tinwm SOIJOSS330E ffe twm uolu s.tallg nwounug jO /Ciddns ag12utpnloui
including the supply of harmonic filters along with all accessories which shall be installed at
aq llugs satpws nwowirq asata - patipads as!mJawo ssawn walsiCs Jamod s,Jaumo
owner's power system unless otherwise specified. These harmonic studies shall be
walss `anuw!nuden aiqun `ianai iinuj wntwww puu wnwpzuw twm palonpuon
conducted with maximum and minimum system fault level, cable capacitance, system
peol wnwpzuw oi pailwil aq Hutis saumus aqZ '31.0 001I01.3.00.1 wawdwba
equipment reactance etc. The studies shall highlight but not be limited to maximum load
jo titgni.tivts jo anuanbas `siang nutownq jo paau `satnuanbaJj wuuosai palnadxa `wallno
current, expected resonant frequencies, need of harmonic filters, sequence of switching of
S,JOIDA0 11104 sJaijg x.1!paa3 .10,1 Japaaj isluawd!nba jo 2upri `W.103 anuM 0"0110A
filters, voltage wave form, rating of equipmentsl feeder for feeding filters from owner's
.31.0 Jua2gmms
switchgear etc.
8' I 'S P312.1J° %0ST aq llugs Jallatwon aqi jo 4ouden puoliano
5.1.8 Unless otherwise specified, the overload capacity of the controller shall be 150% of rated
`palpoads as!mJawo ssawn
wanno palri Jo %oti puu `suogrolldde anb.toi iuuisuoo Joj awww auo Joj Joww jo luanno
current of motor for one minute for constant torque applications, and 110% of rated current
spaanxa puoi joiow -artion palui iu suogroildde anb.toi awrgun Joj awww auo Joj
for one minute for variable torque applications at rated voltage. If the motor load exceeds the
pien2 o1 .1.040W puu iouanbaJj atp annpai Xffenprwolau Hugs antip oq1 `wwi
limit, the drive shall automatically reduce the frequency and voltage to the motcrr to guard
I
an!Jp aqi `alnum ump. a.row .103 Twiti walinn aq1 paanxa spuuwap puoi 3l .puoliano IsutuRe
against overload. If load demands exceed the current limit for more than 1 minute, the drive
- aApp auurep puu .1010W agT3o 2uguag .10A0 wanaJd ot umowngs llugs
shall shutdown to prevent over heating of the motor and damage to the drive.
6' I 'S Puol IIu Japun anbiol Tuat. ntjjns 2wdoianap jo alqudun aq llugs walsiCs ato `uoguJado 2winci
5.1. 9 During operation, the system shall be capable of developing sufficient torque under all load
09 oidn wwi awg u twwm Twod Tas paads ui uoguJaite %0Z u 01 puodsaJ 01 suompuon
conditions to respond to a 20% alteration in speed set point within a time limit upto 60
.spuonas
seconds.
0II' JOJ awrisnfpu Âguapuadapw aq llugs uoguiatir wpd Sas paads agT jo uotpe Jolufflaw! atu
5.1.10 The integrator action of the speed set point alteration shall be independently adjustable for
ligod ias uaamtaq Iun.taTui auw wntwww aqi .uop.uJalue piUMUM0p u puu piemdn uu woq
both an upward and a downward alteration. The minimum time interval between set point
- spuonas oi su paJap!suon aq llugs tualsis loijuon palnqt4s!p aqt iq swatulsnfge
adjustments by the distributed control system shall be considered as 10 seconds.
Jo paads iuuwirJado wnwpzuw aqi jo0/0 01 spaanxa paads aqi OSUO ut 411 1124s anup aqj
5.1.11 The drive shall trip in case the speed exceeds 105%of the maximum operational speed or
.spuonas oi uutp. atow JOJ paads iuuopriado wnwmw jo
reduces to 95% of the minimum operational speed for more than 10 seconds. sannpaJ
iutuJou jue twm proi pairi Japun `antrelsw
5.1.12 Maximum noise level from the drive at I-meter distance, under rated load with all normal
aApp agT woJj tanal astou wnwpzuN
"VEIP S8 M°33‘3 iou ffeqs IttleJado suuj 2ulloon
cooling fans operating shall not exceed 85 dBA.
winJp uado uu ut parriado aq uuo 1.! Tutg os pa&teme aq llugs an!Jp /(ouanbaJj awwigA
5.1.13 Variable frequency drive shall be arranged so that it can be operated in an open circuit
ffiwoogsappoil puu stuaunsnfpu dn puis Joj Joww aqT woJj papauuonsw `apow
mode, disconnected from the motor for start up adjustments and troubleshooting!
maintenance. - anuguawrew
17I ' I "S 'wtuJado luioT agt Joj luguaiod punoffl1u paumwew aq Hugs iuJwau Joww
5.1.14 V oltage at motor neutral shall be maintained at ground potential for the total operating
condition.
- uompuon
Z
5.2 Control Requirement
luatuaiwbaH
I 'Z' 41!quden isooq 4wion paiwbaJ tp!m X1ddns j/A wwsuon uo amado llugs tuaiss
5.2.1 The system shall operate on constant VIf supply with required voltage boost capability in
low frequency mode of operation. . uoguJado Jo apow iCnuanbaJj moi
Z.Z. S dn isels Joww a&ei u jo asun ut -2.a) a2ution tutuwou Jo %oz ot dn scijp artion aw9.3Jogs
5.2.2 Short time voltage dips up to 20% of nominal voltage (e.g. in case of a large motor start up
2uwognunj dors oi wals/Cs pruluon aqi asnun iou llugs (sajA su snq awus agi oi papauuon
connected to the same bus as VFO) shall not cause the control system to stop functioning
and shall not trip the drive system. - tualsis an!ip aqi dui Tou llugs puu
£Z qa!qm ainTuaj q2no.n1 app ssopamod iCieniaulow U qnm padcnnba aq osir ims inals/Cs aqi
5.2.3 The system shall also be equipped with a momentary powerloss ride through feature which
Z uelp ssai Joj suondnnann Jamod .10 %OZ JaA0 d113, aunon jo OSUO ut tual.sis aqu.relsai inm
will restart the system in case of voltage dip over 20% or power interruptions for less than 2
i(nllauj aql anuq ffeqs aApp aqi tuunuou s4i O1 aunon ag13o ÂnA000.1 qnm `spuoaas
seconds, with recovery of the voltage to its nominal value .. The drive shall have the facility
aiqudea aq Huqs Japanuoa atp. `1Ju4sa.1 uodn -Jomado aql /(q pannbai ji `an-uraj sng )loolq
to block this feature, if required by the operator. Upon restart, the converter shall be capable
()I uninm anbao4 uoprialaaau jjnj dolanap puu .1010111 1.1gE40.1 U 01110 tijz!uon.puXs jo
of synchronizing onto a rotating motor and develop full acceleration torque within 10
. spuoaas
seconds.
paqauue Jad su s1JU4s jo Jaquinu Joj aiqunns aq IIUgs walsis aqZ 45!H ioj uoguagpads
5.2.4 The system shall be suitable for number of starts as per attached ElL specification for High
aunoA
Voltage Motors.
- uogoanp pienuoj agl ui Jolou( aqj puls s/Cumm o4 pallanuoa a q tiuqs JaHanuoa Jamod
5.2.5 The power controller shall be controlled to always start the motor in the forward direction.
luanaid O4 paInnoid aq iteqs a!Roi WO.Ij .101011.1 OS.10A0.1 agl Ui papuis
Logic shall be provided to prevent the motor from being started in the reverse direction.
0°1-1°10.10-1 A 0I -0 ao Vul OZ-tF O12tnpuods0I103 patio.nuoa paads aq ituqs 1040111 aApp aqi
5.2.6 The drive motor shall be speed controlled corresponding to 4-20 mA or 0-10 V reference
00110.10.10.1 paads srlasn jo ssot alaiduloa uodn `pagpads astmiatpo ssaiun .1uu2!s indu!
input signal. Unless otherwise specified, upon complete loss of the user's speed reference
paads lsUl ag13o %001-08 1U su paads nreisuoa 4U un.) Xlluogutuome iteqs an!ip aq). 'imffl!s
signal, the drive shall automatically run at constant speed as at 80-100% of the last speed
.feu!s jo ssol aqi O4 zoud aigenung aoualajaJ
reference available prior to the loss of signal.
L. Z. .apoui onku .10 luntrew Jagna Ui an!ip aqi jo paads ag4 iClun o4 alcnssod aq liuqs ll
5.2.7 It shall be possible to vary the speed of the drive in either manual or auto mode.
- pagpads as!Auatgo ssalun raurd adA moij aq iirqs uop.aalas junuemoinv
AutolManual selection shall be from VFD panel unless otherwise specified.
paads aqi 4as o1 aiqu aq Huqs JoluJado aqi `apow „tenurtu„ ui qanms Joiaatas ag4 qnm
a)
(U
With the selector switch in "manual" mode, the operator shall be able to set the speed
asuanap/asuanui paads tuoJj .10 (laurd aApp ag13o luoij uo paiunow) pUd iCa)1 Ono.n1
through key pad (mounted on front ofthe drive panel) or from speed increase/decrease
U su pap!noid aq iluqs Jalatuogualod paTendo JoToN -(plag alll tuag) suonnq qsnd
push buttons (from the field). Motor operated potentiometer shall be provided as a
- aa!nap nnod 4as paads
speed set point device.
(q Uwag pationnoa aq Huqs Joiotu aq) jo paads `apow „olne„ ui qanms Jolaaias aqi qnm
b) With the selector switch in "auto" mode, speed of the motor shall be controlled from a
i(JussaaaN .Lualsi(s (lo.nuop ssaawd) sDamd S,1011M0 1.110.13 ‘I'21121s dui OZ-17
4-20 mA signal, from owner's PLCIDCS (Process Control) system. Necessary
cuA ag4 ui pap!noid aq oste Huqs spaiym qnm 2u!aujia1u! Joj pannbaJ luatud!nba
equipment required for interfacing with PLC/DCS shall also be provided in the VFD
. pued
panel.
(3 qnm .(pia!d u!) uoguls to.nuoa jUOOj ui painnoJd aq lueqs qanms Joloaias aloulaw(epoi
c) Local/Remote selector switch shall be provided in local control station (in Field). With
ag~ las puu isuis O1 aiqu aq iteqs Joiriado `apow „Feaol„ ui qanms Knoatas agl
the selector switch in "Local" mode, the operator shall be able to start and set the
„alowax„ ui tionms Joiaaias atp. qnm .(piaL4 ui) uonfis januoa luaol Ono.ng4 paads
speed through local control station (in Field). With the selector switch in "Remote"
s,Jaumo tuoij .10 j011Ud CLIA tuoJj Jagna pallo.nuoo aq fluqs Jolow atg jo paads `apow
mode, speed of the motor shall be controlled either from VFD panel or from Owner's
.13,10.1 OSIU `uc:gris loanioa luaol Joj) .anoqu (q puu (U ut patnuldxa su sponld
PLC/DCS as explained in a) and b) above. (For local control station, also refer Cl.
"(mcgul L'S'
5.5.7 below).
8'Z'S Huqs 11100.1 j0.14U00 1"C pairaol sjcuyid alowai qnm 03P3.101U! ag4 .103 uo!spko.id pannbai ata
5.2.8 The required provision for the interface with remote PLC/DCS located at control room shall
su siannpsuu.i1 pue slounioa aaij tu!lualod qnm) uonaauuoa panmp.mq Onang Jagna aq
be either through hardwired connection (with potential free contacts and transducers as
ui pautjap su )1uu uogra!untutuoa pias qRno.np .10 (uoguagpads snp Ui aJaqmasia paqpasap
described elsewhere in this specification) or through serial communication link as defined in
. paufsulup atp.
the datasheet.
6.Z. S su qans uoprtuoinu lanai Jaddn qnm 03k1.104111 .10j UOISIA0.1d ONC11 liuqs u.lalss anpo
5.2.9 Drive system shall have provision for interface with upper level automation such as
ulup ag4 ui pagpads asUO 1.11 tua4s1 S 10.141.103 Ig0I140910 .10 tualsiCs 2u!Jo4iuoul uogulsqns
Substation monitoring system or electrical control system in case specified in the data
. uopragpads qoffiaaqs
sheet/job specification.
Oi • Z S aq Huqs Jauuojsurij 4nd ino Ru!iveq tuaisiCs aApp ag4 Joj )1auq paaj io.nuoo dooi pasola aqi
5.2.1 0 The closed loop control feed back for the drive system having out put transformer shall be
- Jauuojsuu.n aquo ap!s i(npuoaas ag1 tuoij paddel
tapped from the secondary side of the output transformer.
5.3 Panel Construction
uopni1suo3 laued
I•£ /ijouggi/sapom) saa!nap Jamod fi'uganpuoa nuas aiqunns apn Jou! Huqs latred aqi
5.3.1 The panel shall include suitable semi conducting power devices (Diodes/IGBT/IGCT/
`(pannbal j!) siang (pannbai j!) siolauai `saa!nap angoaloid qnm sainpow (L3Ds/ipai
IEGT/SGCT) modules with protective devices, reactors (if required) , filters (if required),
aqi jo uogamnsuoa ag J, O40 uogepunutre puu uoguaipu! `sapossaaau io.nuoa `nnana joinioa
control circuit, control accessories, indication and annunciation etc. The construction of the
aq) patu ireqs puu SUOISSIU10 39OURC1110.143310 1SIIIU2U U0i40010.1d OAIpajja ap!noid ireqs tatted
panel shall provide effective protection against electromagnetic emissions and shall meet the
design requirement of relevant standards. .splupums nignajai jo luatuannbai ti!sap
Z. £. 5 qsnd d!.i4 pur ti!sola ia)feaJq alotuai puU suonea!pu! ,dniujjoiNo, Ja)lualq turansdn
5.3.2 Upstream breaker 'ON/OFF/TRIP' indications and remote breaker closing and trip push
buttons shall be provided on the front door. .ioop Tuoij agp uo pappwid aq lueqs suonnq
£ • £* dn ato ssaiun pauado aq LUBD pwquo Jamod luto os pap!mud aq ouqs )foopalui i(pjus
5.3.3 Safety Interlock shall be provided so that power cabinet can't be opened unless the up
st impudeo )iull pci puu pasop s! qoqms 2ffuno.18-/(pjus `papauuoosw s! Ja)luaJ44 ureaus
stream breaker is disconnected, safety-grounding switch is closed and DC link capacitor is
puu uado st tpqms 2uup_tua ato aouo pasop aq iquo ItU3 Ja)i-ea.iq aomos Jamod - pa&utpsw
discharged. Power source breaker can only be closed once the earthing switch is open and
. 4llouj Teajap voi qqm pasop s! .loop pued
panel door is closed with lock defeat facility.
ploo Rwsn paluouquj aq ileqs puu spued pais paqs ut pasnoq iqq-eqns aq ituqs anup aqi
5.3.4 The drive shall be suitably housed in sheet steel panels and shall be fabricated using cold
- v3x3 tutu 9. I wnuquuu jo aq iirqs lauud ato Joj pasn pais paqs aqZ .pais paqs Polloi
rolled sheet steel. The sheet steel used for the panel shall be of minimum 1.6 mm CRCA.
liegs laued aqi .pagpads as!Auatoo iou Ji `uoguirelsw Joopw Joj aiquqns aq ireqs laued aqi
The panel shall be suitable for indoor installation, if not otherwise specified. The panel shall
umuquwi puu wntwxuK • su uogoaloid amsopua jo aafflap qqm 2wptrels aaJj aq
be free standing with degree of enclosure protection as IP-31. Maximum and minimum
.XpAgoadsai tum ooc puu LUW 0061 aq ireqs 1.0!aq Swmado
operating height shall be 1900 mm and 300 mm respectively.
S'E•S aq iluqs siuuutual acUl. dureo -wouoq ie pammud aq tlegs aluid puei2 paupp-un paijog
5.3.5 Bolted un-drilled gland plate shall be provided at bottom. Clamp type terminals shall be
used for connection of all wires up to 10 mm 2 and terminal for higher sizes shall be bolted
paijoq aq Hutis saz!s Jatfflui Joj tutuutial puu zumu 0I oi dn saqm IJe jo uogoattuoo Joj pasn
u u009 aq Huqs uogruutual alquo JoMOd JOj aouds tuntwum .sRni alquo Joj aiquqns acliCt
type suitable for cable lugs. Minimum space for power cable termination shall be 600mm
- amel pueg alquo ato jo tuouoq wag ..reap
clear from bottom of the cable gland plate.
9. £'S 3 JOJ iCiatundas papoo Joloo `panaais `tunugumte/Jaddoo ogiCioijoap jo aq Huqs sjuq sng
5.3.6 Bus bars shall be of electrolytic copper/aluminium, sleeved, color coded separately for AC
• iCiases apidutoo antsua oi papnonis / panaais aq Huqs suud anq aql IIV •tualsi(s puu
and DC system. All the live parts shall be sleeved / shrouded to ensure complete safety to
°I.14 IIV .sioop pued ato 2uutado iq uogoadsw augno.1 ino /thuo oi 2wpuawi puuosJad
personnel intending to carry out routine inspection by opening the panel doors. All the
.aruidauteu aiquqns qqm pap!noid aq ouqs sioop ati uo puu pued ati amsw wawdwba
equipment inside the panel and on the doors shall be provided with suitable nameplate.
£. puu luauodwoo `"1131!ms 0111 IIV SOpOSS390•0 tio!qm 0.1U oua5Jauta puu puuou Joj l'UgUOSSO
5.3.7 All the switches, component and accessories which are essential for normal and emergency
31g IIV .4-etuaixa alqeJado aq Huqs puu .loop aqi uo paqmout aq iqquiajaid iteqs uouwado
operation shall preferably be mounted on the door and shall be operable externally. All the
azts jo ag papauuoo )p-eq `ad/Ct pieoqqoqms aq iteqs `pap!Awd alaqm `sluautrulsw at-tolutre
analogue instruments, where provided, shall be switchboard type, back connected & of size
- 2uguJ 2uggiado alq!ssutuad wnwpcew gut uotpw paJ anuq iteqs apos - tutu96x96
96x96mm. Scale shall have red mark indicating maximum permissible operating rating.
8' £'S .asnj puu tpqms totm 7d3 m i/dtuut 2uguwwnII! 1111^A pap!noid aq Iiegs lauud ipea
5.3.8 Each panel shall be provided with illuminating lamp/11 W CFL with switch and fuse.
.pap!nald aq outis asnj puu tpqms qqm 1a)pos Jamod A0t7Z `VSI/S aiveq ffeqs jaurd tiou
5/15A, 240V power socket with switch and fuse shall be provided. Each panel shall have
-1-elsouuato 2uups aiquuen puu asnj tpqms qqm Jaluaq aouds
space heater with switch fuse and variable setting thermostat.
6' £' puu jo 4oudeo puristolm qnoqo uoqs oidn .tuw.bs 9x0c .ugu jo snq quua Jaddo3
5.3.9 Copper earth bus of min. 30x6 sq.mm. upto short circuit withstand capacity of 31.5kA and
atp ui pap!mmd aq Huqs 3/)1 . anoqu Xqouduo puulsqqm quoip poqs e .103 "LULLUbS 9x0
50x6 sq.mm. for a short circuit withstand capacity above 31.5kA shall be provided in the
olltulaw-uou atp IIV •PO quua tuuld SclOWY\O o1 U09.00UUW JOj uo!spkoid qqm puud
panel with provision for connection to owner's plant earth grid. All the non-metallic
puu .req snq quua aterudas Juq snq tona wuut ato oi papauuoo aq ouvis suud/sTuauodwoo
components/parts shall be connected to the main earth bus bar. Separate earth bus bar and
- pap!noid aq ireqs paqnbai ji[ tuatsiCs ioijuoo outo.tpaia Joj pnis
stud for electronic control system if required shall be provided.
0 I 'C'S ouatosau poo2 an!2 oi `dn-auu twojum u uuoj o1 su os qffl!aq amus jo aq ouqs spued IIV
5.3.10 All panels shall be of same height so as to form a uniform line-up, to give good aesthetic
.aottexuadde
appearance.
I I • £•S aq Ilegs aqm qou3 lauueqo imaut pusuld ut pasopua aq quqs u!.qm joiluoo ato IIV
5.3.11 All the control wiring shall be enclosed in plastic/ metal channel. Each wire shall be
ioijuoo puu JOMOd .sainuaj 3AdJ0 SLIW.10)1.1•0111 O.UM uppijs-jjos spua tooq iu pagguapr
identified at both ends by self-sticking wire marker tapes or PVC ferrules. Power and control
moi `wep.tup..1 Oly `pawinsw 3Ad `pammdde sig qqm auop aq quqs pued ati ap!sw fi'wqm
wiring inside the panel shall be done with BIS approved, PVC insulated, fire retardant, low
2
loiwoo ato pap!Awd pasn aq iCllutwou liuqs a.ijm az!s zututS I aqm ioionpuoo Jaddoo `a)louts
smoke, copper conductor wire 1.5mm size wire shall normally be used provided the control
Joj v 91 anoqu utiuJ asnj ionuoo Joj az!s zunu 2 puu ssat .10 sduuy 0I s! 2wiw asnj
fuse rating is 10 Amps or less and 2.5 mm size for control fuse rating above 16 A for
IIV
puu pain.uaj aq quqs SO.UM 2 .squoip outoijoap Joj zunqs.0 puu sqnoqo luoupala
electrical circuits and 0.5mm for electronic circuits. All wires shall be ferruled and
.pap!Awd aq ouqs siuwunai. ands %oz tunuijugn `paiaquinu ./(pado.id aq Ilegs stewunal
terminals shall be properly numbered, minimum 20% spare terminals shall be provided.
I • £* Ctuo puud jo luoij uuoij amssaoou aq treqs sluauodutoo puu sainpout outoipaia IIV
5.3.12 All electronic modules and components shall be accessible from front of panel only.
outoipata Jamod puu sluautd!nba outo.uoala io.ouoo tualss ato tooq Joj sallqwassu .reinpoN
Modular assemblies for both the system control electronic equipments and power electronic
. pasn aq quqs swatudwba
equipments shall be used.
aq; tuoij powledas iCireo!s4d puu 4uoupap aq ffeqs 2ullquo puu watupudutoo a2ution moi
5.3.13 Low voltage compartment and cabling shall be electrically and physically separated from the
ivatuuudwoo tffilq
high voltage compartment.
ui paiunow iqquiajaid aq Jtegs itnoiio 20.relpsw as) gut&utio-aid puu Joqoudeo )iull DU •
5.3.14 DC link capacitor and pre-charging & discharging circuit shall be preferably mounted in the
. pued ato jo 100.1
rear ofthe panel.
jo 5'uojll JOJ pap!mmd aq iteqs wawa2ur.uu aweio de.os /sdutup 8u9j11 /suoqa/a alquqns
5.3.15 Suitable eyebolts/ lifting clamps/ strap & cradle arrangement shall be provided for lifting of
ato 1.tutado "Cur anual iou ouqs paA0I110.1 uaqm `sqoq aq1 .uogoas 2wdd!qs/puud aqi
the panel/shipping section. The bolts, when removed shall not leave any opening in the
. tatted
panel.
9 I ' £•S .stuauodutoo anq 1.11.10A00 .10,1 pasn aq itutis rutialutu up:up-tsw Tuandsue.0 ad/(.1 olliCloy
5.3.16 Acrylic type transparent insulating material shall be used for covering live components.
LI« swawainsuatu puu WupoTwow Iotwoo toj pagnbat lauud lotwoo Jowtado `pucliCa)i anua
5.3.17 Drive keypad, operator control panel required for control, monitoring and measurements
toj aiwssaoou aq guqs ii - Joop wo.g agi uo puud agi awswo pagelstg puu pagddns aq gugs
shall be supplied and installed outside the panel on the front door. It shall be accessible for
.ad/Ci awunotuat-uou aq grqs puu toop wcuj tiptado wowtm uouutado
operation without opening the front door and shall be non-removable type.
81. £'S ai&its aq guqs spuetp alquo puu a1a sffig `spuut alquo qi!M alaidwoo aq gugs watudinba
5.3 .18 All equipment shall be complete with cable glands, lugs etc. and cable glands shall be single
spuw2 aigu3 -Xiangoadsat wawdwba ioopino puu Jooput Joj adX uotssaidwoo aignop .10
or double compression type for indoor and outdoor equipment respectively. Cable glands
iaags wup ui pagtoads 3t uogeogddg 00.I0 snoptuzug ag1 toj alqwws aq osw geqs
shall also be suitable for the hazardous area application if specified in data sheet.
b'S 2tmoop
5.4 Cooling
I '17'S s‘tatwoujnuetu .tad su ad■ 4 pal000 tawm .10 pal000 Xffetniuu aq gutis lauud anup ata
5.4.1 The drive panel shall be naturally cooled or water cooled type as per manufacturer's
paoioj `awup!onuun 3I .uualsXs p01000 Jr U tutriwu angti panajaid st it `.10A0M011 .spnpueis
standards. However, it is preferred to have natural air cooled system. If unavoidable, forced
pauotsuaugp-IPm oPnlow geqs tualsi(s Rugoop - paptnald aq gugs tualsi(s 2tw000-adki.
type-cooling system shall be provided. Cooling system shall include well-dimensioned
tw000 lauud `.1USSaDOU ji puu trej .rewpow `qiud mouttu 2ull000 awnbapu `Iatted
panel, adequate cooling airflow path, modular cooling fan and if necessary, panel cooling
latted aqt wqt atnsua geqs JopuaA .patawsuoo aq gugs tualss 2ull000-Jawm Jo truj
fan or water-cooling system shall be considered. Vendor shall ensure that the panel
pagtoads snonuguoo toj pau2!sap uaag anug stpud mou puu suotsuatutp
dimensions and flow paths have been designed for continuous running at the specified
geqs (i+N) suej 1.1g-eiguaik wupunpat `sanup pal000 trej Joj .2uguatpano wow!m wawutu
ambient without overheating. For fan cooled drives, redundant ventilating fans (N+ 1) shall
aulus `pued aqi at pawnow aq o1 alq!ssod iou si uej titi000 wepunpat OSUO uI - paptikoid aq
be provided. In case redundant cooling fan is not possible to be mounted in the panel, same
- asool patiddns aq gegs
shall be supplied loose.
`ia2uutioxa waq oi palww tou inq Rutptijout wals/(s t.tg000 aigua `sanup pai000-tatum tod
5.4.2 For water-cooled drives, entire cooling system including but not limited to heat exchanger,
aq gegs wats/Cs agi -adoos s‘topuan ui aq guqs sdwnd puu sialaut atnssatd puu mou
flow and pressure meters and pumps shall be in vendor's scope. The system shaH be
pagnbaJ Jawi■A dn aluuu Xjuo 2upwbat `tual.sis 2ull000 iatum Itnotto pasolo twm paptnoid
provided with closed circuit water cooling system, requiring only make up water required
. /Couupunpat %00I angq gugs `paptnoid OS•03 ut `schund Jawm tgl000 atu, -dn toj
for topping up. The cooling water pumps, in case provided, shaH have 100% redundancy.
Jawm 'itg000 papaias puu pags wup ag1 ui pautjap su aq geqs sogspaiountioAgenb tawm
Water quality/characteristics shall be as defined in the data sheet and selected cooling water
guqs sainsuaut /Ciajus awnbapv -atuus aqi ioj awwws aq geqs wuatutuistuauodutoo watsis
system components/material shall be suitable for the same. Adequate safety measures shaH
ut stinsat gowm alaw si aRe)wat ou wgi gons sanup pal000 .131:0AA ui pamothoolg aq
be incorporated in water cooled drives such that no leakage is there which results in
puu waisiCs t..w000 .131:0M uaamlaq uou4afflas tadoid -sao!nap otuagoala jo t.ituogounjwut
malfunctioning of electronic devices. Proper segregation between water cooling system and
aq gegs lauud iautquo tw000 panajaid s! ii - paptnoid aq guqs wawdwba tawo
other equipment shall be provided. It is preferred that cooling cabinet panel shall be
siatted utew utatj patundas
separated from the main panels.
2ullooD `suuj uogullwaA aqi .103 spued cljA aql uttwm pap!noid aq guqs siauris iCtussaoaN.
5.4.3 Necessary starters shall be provided within the VFD panels for the Ventilation fans, Cooling
aq guqs paptmud tual.s/s tolout X.wwxnu Jawo Xue `sdwnd uoguwo.go tawm
Water circulation pumps, any other auxiliary motor etc. The system provided shall be
1I1111.13d ]_1'0].S su gons moopaw! /(tajus iegi os umownqs pue 2ug_rws anup twm paoujtalut
interfaced with drive starting and shutdown so that safety interlocks such as start permit
2tw000 jo asuo ut anup o1 tuals/s 2tw000 1.110.1j 1[RIffilS 41i puu anup o1 wa4si(s 1.111000 WOJJ
from cooling system to drive and trip signal from cooling system to drive in case of cooling
aouanbas gutano aqi ut pawtothoout a.te `-ola atnifej walsiCs
system failure etc., are incorporated in the overall sequence logic.
lauud anup `iatted wow ioj pagnbat j! iqddns Jamod i(regtxnu `tawaq ands .1010111 .10j ajlAl
5.4.4 MCB for motor space heater, auxiliary power supply if required for local panel, drive panel
. uoguoot amssaoou i(sua ut pawnom pue paptgow aq guqs - 31.0 taluaq aouds
space heater etc. shall be included and mounted in easy accessible location.
5.5 uogemjpads juauodtuop iwatud!nba
Equipment/ Component Specification
5.5.1 Motor
jo uwstnat isawl aqi wtm aouupt000u ui paisai puu pai.onnsuoo `pau2!sap aq guqs Jowtu aq,)(
The motor shall be designed, constructed and tested in accordance with the latest revision of
uomppu ui `JoloK snouotqouÂs uoponpui auijoA tffitH Joj paqs wupi uoguotjtoads s,-jrj
ElL's Specification /data sheet for High Voltage Induction / Synchronous Motor, in addition
to the following requirements: :stuawattnbat 2wmogo3
jo Rugstsuoo iqddns tamod awis-ptios e twm uogetado Joj alqwws aq guqs Jotout agi
a. The motor shall be suitable for operation with a solid-state power supply consisting of
lotwoo paads toj tauanw XouanbaJj algutsnfpu uu
an adjustable frequency inverter for speed control.
iqddns tamod aq1 "Cg paonpotd suuojanum wanno atp Joj awwws aq geqs tolout agi
b. The motor shall be suitable for the current waveforms produced by the power supply
'anup aqi iq pairiaua sowouueq atp fi'wpwout
including the harmonics generated by the drive.
aqi .rano paads iCuu tu iqsnonutwoo amado oi pautsap aq guqs tolow aqi
c. The motor shall be designed to operate continuously at any speed over the range
'3 O&IU.1
iaatis wup ut pagpads astmiawo ssaym paads pawt jo (0/0001-0 I)
(10-100%) of rated speed unless otherwise specified in data sheet.
d.
-p dotp aution awis Xpuals aqi wn000u owt a)fw pwoqs uoueuen aullon pamuuad aqi
The permitted voltage variation should take into account the steady state voltage drop
- tolow agi jo weatisdn swauodwoo walsiCs tawo tle puu anup Dy agi SSOJOU
across the AC drive and all other system components upstream of the motor.
.a paw3ads Joj palet aq itegs apotu ssucl-4 JOU ol panajstreij aq ol pa.nnbaJ s.IOloy J
e. Motors required to be transferred to DOL by-pass mode shall be rated for specified
qoa UI Jolotu Jo lua.uno Wup.ms - Xouanbaij puu a5'unon atni tuals/Cs u! suopupun
variations in system line voltage and frequency. Starting current of motor in DOL
ssatun `suopuolpoads .1040111 ai pagpads anfen Ol patuull aq puqs apout ssucl4
bypass mode shall be limited to value specified in motor specifications, unless
-slaagsulup ui pawoads aspniatpo
otherwise specified in datasheets.
tuatj Rumnsai suogusind anbiol puelsq4m Ol papn.nsuo3 aq pugs Jolow aqi
f.
.j The motor shall be constructed to withstand torque pulsations resulting from
- /Cieldns Jamod ams-p!los atp iCq pairiatia sonlotunti
harmonics generated by the solid-state power supply.
uni4m `upojanum pallcIde atl icla3ou ol pauW!sap aq pugs uoguinsu! .1010111 aqi
g. The motor insulation shall be designed to accept the applied voltage waveform, within
atp uaanntaq uoputup.io-oo X.IESS3001.1 puu 17-00819-331 Jacl su svnu!I Tp/Ap puu WdA alp
the V peak and dv/dt limits as per IEC-61800-4 and necessary co-ordination between the
Jo uoguJodioou! Jainpujnneuu 1010W ?g Jatrpoujnuuut adA
VPD manufacturer & motor manufacturer W.r.t. incorporation of VPD output
ino pa!lluo aq tivqs Jolotu Jouffi!sap atp. ui Jaiaturird
parameter in the design of motor shall be carried out.
.4 Jolout alp jo uog3alas Jacloid Joj alcllsuodsai Xialos aq putis Jainpujnuutu aApp aqi
h. The drive manufacturer shall be solely responsible for proper selection of the motor
.aik!Jp atp jo sops!Jalou.req3 lndlno atp pur uogrouclde puoi uanIR atp Joj
for the given load application and the output characteristics ofthe drive.
.1 44nA papinoJd aq ireqs sJoloN . (scum) siopoiou ammadwai aottels!sax
1. Motors shall be provided with Resistance Temperature Detectors (RTDs).
j!) Jauluojsuu4 puijno /.13111.10JSUelf Jalianuop (Jasugaind Xq paaie
5.5.2 Converter Transformer/ Output transformer (if specifically agreed by Purchaser)
uirp atp ui paimoads su papg Iro .10 acIkt aq preqs .11.11.10JSUE.11.10P0A1100
a. The converter transformer shall be dry type or oil filled type as specified in the data
tualss an!ip agl UI pawnow aq ItEgs li `.13W.10JSIMil acliCt Âap atp jo OSE3 UI laaqs
sheet. In case of the dry type transformer, it shall be mounted in the drive system
Jad su aq IIEgs Jauuojsue4 paiajjo laagsmrp atl ui as!Auatpo pagpads ssatun joUUd
panel unless specified otherwise in the datasheet. Offered transformer shall be as per
iaaqs uwp/suogrogpads pasoloua
enclosed ElL Specifications/data sheet.
.a /(tepuooas auo ump. 3.10W tp!An S.131111.10JSUEll lndut tapanuoo Jo saotrupaduij
b. The impedances of converter input transformers with more than one secondary
Tuanno/proi junba ainsua ol papaias aq puqs stuals■Cs asind 9ufrz/8 Liz JOj s&npupn
windings for 12/18/24/36 pulse systems shall be selected to ensure equal load/current
Japun s2u!pu!m Jolow atp. puu S.101nA1103 atp. `s2tuputm /(repuooas atp uaam4aq 2ut.reqs
sharing between the secondary windings, the converters and the motor windings under
.2up_re4saJ puu 5.upsels 2u431431q suompuo3 ieuoguiaclo itu
all operational conditions including starting and restarting.
.3 palui p.repuuis upaatti Jo asoclind atp JOJ iquo paJapisuoo Jauuojsuu.n lnd ino anpa
c. Drive out put transformer considered only for the purpose of meeting standard rated
p3OffiU as!Auatpo ssatun pap!noid aq Tou pugs A00011 `A0099 `00££ .a.! a Elton .1(401.11
motor voltage i.e. 3300, 6600V, 11000V shall not be provided unless otherwise agreed
.Jampoujnuutu atp puu Jasugaind uaampq
between purchaser and the manufacturer.
£'S'S Jalianuop JaAtod
5.5.3 Power Converter
su 110gE.13d0 .10j .101.13A1.103 Jamod ap!s atiji E Jo 4s!suo3 putis .101.10AU00 .10A10d 3IMS
a. The static power converter shall consist of a line side power converter for operation as
.Jalianu! p3panuo3 Xiinj E su uopmado .10,1 .101.10AU03 JOMOd ap!s puoi E puu tagpoai
a rectifier and a load side power converter for operation as a fully controlled inverter.
ad Cl ssol MoI puu tuaptija tsout `uttiottms isej aq puqs .131.10A1103 .13MOd
Power converter shall be fast switching, most efficient and low loss type.
.ct .M1.10A1103 atp Joj pap!noid aq putis uogoaloicl afiv4on .10A0 puu 4113.ijo poqs airnbapy
b. Adequate short circuit and over voltage protection shall be provided for the converter
'11101S/CS JOJJOnui puu
and inverter system.
puu s)ponklau Jaqqnus `sa3!Aap anpoalpicl apni3ut itugs sa3!Aap 101.10A1.103 JOMOd IIV
c.
'3
All power converter devices shall include protective devices, snubber networks and
.pa.nnbai su s)ponklau 1.p/Ap
dv/dt networks as required.
*P uutg ssai aq Tou putis sluauoduio3 Jopnpuoo-nuas s,Japanuoo alp jo 2upui wallno aqi
d. The current rating of the converter's semi-conductor components shall not be less than
CIAA JO prot pnj lE swawaia atp Ononp u!Akou lualln3 lutnwou alp Jo 0Apzi
120% of the nominal current flowing through the elements at full load of the VPD
.a2trei paaels aigua atp Ono.n.p.
through the entire speed range.
09A tunuunnui tp!isn adX uo3ms Jo aq puqs sapow Jamod atl satup S Z su
e.
.a All power diodes shall be of silicon type with minimum V 80 rating as 2.5 times the
rated operating voltage. fi'uguiaclo pam
pnj sli lE paiamod aq ttuo imout wtp os pau!sap aq peqs 4n3.no .101.10A1103 JOMOd agl
f. The power converter circuit shall be designed so that motor can be powered at its full
ol anp asp ammadutai palui
tt!paao,ca inotplm igsnonuguo3 2upri amclaureu
nameplate rating continuously without exceeding its rated temperature rise due to
.uogunclo Japanu! atp. /Cq pairiau swann3 oniouaug
harmonic currents generated by the inverter operation.
Irtp. 43ns pamwassu aq putis s)itns Ivaq pairpossu pur sa3!Aap UOIS.13A1103 aqi
g. The conversion devices and associated heat sinks shall be assembled such that
poads iCuu jo asn atp. 2up!nbaJ Tnoq4m. paoridai aq tre3 sa3!Aap renp!A!pu!
individual devices can be replaced without requiring the use of any special
precau ti ons/too Is. .sloovsuopnuoaid
- ij puu paio4uotu aq prqs `paptftald jt `sluauodtuo3 onto.4.3aia atp Jo tualsXs tnioon ata
h. The cooling system of the electronic components, if provided, shall be monitored and
tamod atl ol avutep tuguanbasuo3 /Cuu wanaid ol pap!Awd aq puqs sultere XIESSO3OU
necessary alarms shall be provided to prevent any consequential damage to the power
control devices. -sao!nap io.nuo3
Copyright ElLSheet 37reserved
of 93
IDONGSGJ S11.16p 11V —113 Iy6wCdo0
o •Aad td-1000-00-2 '0N tewioj
Format No. 8-00-0001-F1 Rev. 0 - All rights
Page 20139 of 22455
-1 puu lauud anuu uaamlaq aoums!p aqi lunoaar olui a)lui osiu iiugs tuals/Cs paJajjo
1. Offered system shall also take into account the distance between Orive panel and
alqullns tualsiCs a)fetu Oi sapossaoau puu repaimu IIE opriput puqs uuolsiCs pur .103.0W
motor and system shall include all material and accessories to make system suitable
.tooqs ulup otp ui powoods ospvuotpo ssolun uttp£ jo oottulstp E toi
for a distance of 350m unless otherwise specified in the data sheet.
Da Jo).3uall
5.5.4 DC Link Reactor
aq; aidnoaap Xpua!agjns pau2!sap aq itutis )iull ja atp. Joj sJolouai Sungomus
a. Smoothing reactors for the OC link shall be designed to sufficiently decouple the
sup ui sluauna unuj puu .101.10A1109 jo uoiniod .10].13A1.1! puu Ja!j!pai
rectifier and inverter portion of the converter and to limit fault currents in this circuit.
`pagpads aspszuagio ssaiun palooa-.iju aq liugs .10].3U0.1 UUJ .10 paluaoi acKi. palooa
b. Unless otherwise specified, the reactor shall be air-cooled or fan cooled type located
lauud atp. unfilm
within the panel.
saclugs anum luanna imosnu!s-uou atp. tplm uoguiado Joj aiqui!ns aq Hugs .10].3•CO'H
c.
"3
Reactor shall be suitable for operation with the non-sinusoidal current wave shapes
2tnpaaaxa inotwAt tualsis jo suou!puoa iuuo!mado IIE Japun swauodwoo 3Q puu
and OC components under all operational conditions of the system without exceeding
- sittull anpuiodutol sl!
its temperature limits.
Jaipi inclino
5.5.5 Output Filter
aulotung 1mm `spaads lue lup!osnu!s Xilualaqui aq pinogs uuojanum wauna GjA
VFO output current waveform should be inherently sinusoidal at all speeds, with harmonic
incijno - pannbai j! `pap!noid aq itugs Jaillj incijno .uogualpaads sup ui paupads sE siniull
limits as specified in this specification. Output filter shall be provided, if required. Output
paiols tunp!sai lIg lutp. ainsua slIna.go a2..rugas!p tpIAn pap!noid aq ireqs sicmardua Jalig
filter capacitors shall be provided with discharge circuits to ensure that all residual stored
IIV JV jo ssot e JOIJE spuoaas 00£ unplAn Da A OS uutg ssai paanpai si a&utia
charge is reduced to less than 50 V OC within 300 seconds after a loss of AC voltage. All
uquaq-jios puu ootj-oouguotutew aq iteqs Jol.toude3
capacitor shall be maintenance-free and self-healing type.
wapuadapu! `ssans jp/Ap a2rlion ui2u1 moij .10].OW paloid Cpua.iagui itugs walsiCs cidA oqi
The VFO system shall inherently protect motor from high voltage dv/dt stress, independent
puu tualsXs sajA aq; jo ued ir.12alui uu aq itutis Jaijij Oual alqua jo
of cable length to motor. Output filter shall be an integral part of the VFO system and
.amsopuo adA aq; utquiNA popnput
included within the VFO enclosure.
9.S. S
5.5.6 Bypass Feature
ssuclUg
Ilegs Ja)feaiqporeiosi apis inchno puu /Culai uogoaloid Joloui twm 'uolu anuraj ssuclig
a. Bypass feature along with motor protection relay and output side isolator/breaker shall
ity -iaagsulup aq; paipaads as!Auatpo ssaiun Jasugaind Xq pap!noid aq X.IUSS0301.1
be provided by purchaser unless otherwise specified in the datasheet. All necessary
ssucI4 tplm 2uolu waisXs c[dA jo uogundo alqullai puu ajus Joj pannbai su moopailij
interlocks as required for safe and reliable operation ofVFO system along with bypass
ui papp.oid aq iteqs tasuqotnd Xq poptnotd to)tuotqiiotelost opts puu Japaaj
feeder and output side isolator/breaker provided by Purchaser shall be provided in
VFO system.
•11131S/S CHA
gans aq llegs awaqas 2unimms puu watuuechuoa alundas ui aq ifeqs Jaums ssuctiCg
b.
-q Bypass starter shall be in separate compartment and switching scheme shall be such
lo.nuoa ssuchCq uo ua)tel aq pinoo .10].0111 atp. `uoguiadolum anup jo OSUO ut Tutp
that in case of drive mal-operation, the motor could be taken on bypass control
aq Hugs ropaiu! aiqmns -i(guapuadaptij papuauu aq pinoa anup 111 atigM `4gnugm
manually, while the drive could be attended independently. Suitable interlock shall be
Asnoaueinuu!s awJaclo ireqs apow GJA puu apow ssucI4 iutp. gans pappkoid
provided such that bypass mode and VFO mode shall not operate simultaneously.
L. S
5.5.7 Local Motor Control Station
uoguN guiuop Joinix tuaori
ilugs Jolow aql JU31.1 plag ui pairelsu! aq
a.
-e The local motor control station, to be installed in the field near the motor shall
`uon:els io.nuoa Jolow juaoi aqZ
sapossaaau puu swauodulop -suop.uaimaads pagaupu aiE j:elp
conform to the attached ElL specifications. Components and accessories that are uuojuoo
palunow piag Feaoi aql uo palunow aq i(utu uon.uls io.n.uoa Jolow tuool aqi ai pa.ijnba.i
required in the local motor control station may be mounted on the local field mounted
- Tuauud!nba uanup aql Joj pars!nua purd
panel envisaged for the driven equipment.
puu slndlno Jaanpsuu.n Vw0Z-17 103 aiqui!ns aq ilugs uoguls io.nuoa tepoi atp. ui sialaK
b. Meters in the local control station shall be suitable for 4-20mA transducer outputs and
`41!au3 ssudiCq giinn sanup Joj `Jagund luauna Jolow lurnau
shall be calibrated for the actual motor current. Further, for drives with bypass facility,
Joj paluiqllua aq Hugs
sE sluanna Wunsels puu puoi linj apoul ssEdXq 2u!pual jo alqudua aq ireqs S.10p11.1 atn
the meters shall be capable of reading bypass mode full load and starting currents as
luanna anup apow (-1,4A aqi sE liann
well as the VFO mode drive current.
9'S
5.6 Protection, Control, Metering, Indication and Annunciation
uo!lupunuuy puu uopu3!pui '2upainAl 'ffliptop ‘uolpaioid
I .9.S puE uuulu `uouaaloid loijuoa tuals/Cs iCrussaoau IIg oPInoid ilugs Jopuan Lualss aqZ
5.6.1 The system vendor shaH provide all the necessary system control, protection, alarm and
- Tuauidinba X.rewxnu sli puu waisiCs anup aniva
metering equipment for the entire drive system and its auxiliary equipment.
Joj luawd!nba Supalaw
Z.9.5 atp. jo tualsiCs X.10!uxnu `tualsis 2ull000 jo
5.6.2 apnIou! Ilugs to.nuoa anuanbas aguwoiny
Automatic sequence control shall include start-up of cooling system, auxiliary system of the
i(3110a101110 puu pauueld `anup jo dn-uru puu iiEis agetuoinu '2umaaga ropang `Joloui
motor, interlock checking, automatic start and run-up of drive, planned and emergency
- Luals/Cs pasuq-Jossaaoidomw Onong passaaoid aq iiugs aulus aqi - unnopIngs
shutdown. The same shall be processed through microprocessor-based system.
v.
-A Inverter Fault.
- ijnuA Japanui
•IA
Vl. Over frequency/Over speed of motor
poads Janop(ouanbaJj Jano 1010111,10
5.9'S
5.6.5 Control
q2nonp 10 pued lo.nuo3 Joiriodo oqi Jo pud u su pomnoid aq ims sloijuoo 2upsnotio3 oqi
The following controls shall be provided as a part of the Operator Control Panel or through
•sogol!ms owndas
separate switches.
•i dols/puls
1. Start/Stop
- 11 (nM01/0S) 10.111100 poods
II. Speed control (RaiselLower)
(pOIJI0OdS OS.10A0X/K0M.10d
'111
111. ForwardlReverse (if specified)
opow renuemolny •AI
IV. AutolManual /Test mode
"A v. Local/Remote
NOW0/[000'j
- IA dols iouoWiowa
vi. Emergency stop
(pogpods oioqm) Jopuls ssucl4 JOJ doisiprls 'IIA
VII. Start/Stop for bypass starter (where specified)
'IIIA Jo)woig 01.01.1.1021-41
viii. Trip-Remote Breaker
siolotu snouo.nputs JOJ wowiCs lo.nuoo uogulpxa
IX. Excitation control system for synchronous motors
-x sniqj Jo u!1.131!ms wpuonbos
x. Sequential switching of filters
9.9'S
5.6.6 Indications
suom3!pui
puu uogundo wullou .10j pannbal su suopuo!pu! oppkoid iiugs JopuoA JO 0SUO .10,1
Vendor shall provide indications as required for normal operation and for ease of
suoguoijou! 5'tnmolio3 pol.null oq iou Huqs gon4An `ootreuonquui
maintenance, which shall not be limited to the following indications.
tquuru JoToN
-1 I. Motor running
•it poddols Jolow
II. Motor stopped
•III mo1s4 ain ijruod
111. VFD System Fault
•AI IV.
o1,Cpua.r wolsiCs
System ready to start
1.101.S
suww 3d -A
v. AC mains ON
vi.
'IA poods JOAO .1010N
Motor over speed
vii.
- IIA indino Joggoox
Rectifier output 'ON'
poods oioz .1010K 'IIIA
viii. Motor zero speed
- xiIX. Remote breaker trip
d!.n. Jo)woiq olotuox
snouoiqouiCs JOJ 4Twoq tuolsXs uoguTpxa
x.
•x Excitation system healthy for synchronous motors
polunow Joop -o-! `Iouud lo.nuoo ioiUJodo otp. jo l_red e su pop!noid oq iCum suo!wo!pur onoqy
Above indications may be provided as a part of the operator control panel, i.e. door mounted
tp!An Jawnp oq quqs uoguo!pu! JOJ pomnald sag-1 •sual po.nmpnq Ono.up JO pudiCo)1
keypad or through hardwired LEDs. LEDs provided for indication shall be cluster type with
tij popouuoo oq ims sual •144 .rad scijqo saA-1 som z tunuqunu puu ssounfflpq ownbopu
adequate brightness and minimum 2 Nos LEDs chips per light. LEDs shall be connected in
•unuc urq4 ssoi iou Joputew u!ikuti dmo QgZ qouo pue tollund
parallel and each LED chip having diameter not less than 3mm.
ilownclos po.nAn oq iiugs AI .10j suopuo!pu! olowoi
Potential free contacts for items i to iv shall be wired separately for remote indications in
SLL104I .103 S1.301,1100 00.11 I0111.1010d
DCS system. •LuolsÂs sjci
L.9.5
5.6.7 Metering
2upoi.aw
`ioued lanuop Jowiodo olll Jo i_red u su oq iwqs sio4outund 2u!mollo3 aqp Jo Xuids!p wO!,3
Digital display of the following parameters shall be as a part of the Operator Control Panel,
selectable by the operator. -lowndo aqi iCq oicrepoios
•I
1.
oRmion inchno
Output voltage
opow ssucliC9 iapow adA-luo.uno
11. Output current-VFD model Bypass mode
111 Output frequency
ouonbaJj
Al
IV Drive thermal state
ams wuuoqi antJU
v.
•A Motor speed
poods JoloN
O'L KOLLV3I3Inla3
7.0 CERTIFICATION
onuti peqs wouldwbo woi.s/Cs on!Jp i(Duonbag oicteguA polupossu puu sKnow oqi
The motors and associated Variable frequency drive system equipment shall have test
KinfIRDI ivdaasvu mdina3) osnoq 4sa4 wopuoclopw pozw2o3oi /(ci ponssi soluolppoo
certificates issued by recognized independent test house (CIMFRI BASEEFA/ LCIEIULlFM
oq peqs puu spiupums cre!pui o4 LU.10,11103 peqs S.1010111 snouoW113 -(wojunwbo -10
or equivalent). All indigenous motors shall conform to Indian Standards and shall be
onuq osfe peqs (papodwl puu snoupw) sao4ouz lld -sopuoRe Wugsoi ue!pui Xci poupio3
certified by Indian testing agencies. All motors (indigenous and imported) shall also have
snouo5ww IlV .uoge3o1 snop.ruzuq poppods aq4 JOJ oiquolldde su siunoicIde i(knweis ppun
valid statutory approvals as applicable for the specified hazardous location. All indigenous
X.kwnws poiwboi su 2upgew puu asuoop sig ppen onuq peqs S.1010W .100.1d0Wqj
flameproof motors shall have valid BIS license and marking as required by statutory
somioquIe
authorities.
tplm uonwodo Joj oiqunns s! Joww otp Tew oluoppw kwop puqs omdowuu Know ow. osiy
Also the motor nameplate shall clearly indicate that the motor is suitable for operation with
.Joqwnu ppouu puu o)tucu cidA cplAn 2uoiu on!ip X3uonbag oicp.run
variable frequency drive along with VFD make and model number.
0.8 HaLVdSMI aNIV DKINDV41
8.0 PACKING AND DESPATCH
jo osuo pue uo!powid Joj suogoos 2wdcijqs iwonos o4 ui pop!Alp oq puqs wawdwbo IIV
All the equipment shall be divided in to several shipping sections for protection and ease of
jo opow popops Joi po)ped Xpodo.id oq peqs wowcijnbo oqi .uonepodsuen 2ullpuuq
handling during transportation. The equipment shall be properly packed for selected mode of
spoqs ouoii(qpiqod uc poddwm oq peqs wowcijnbo aqi ..copun 10 pw/Wqs .o.i uogupodsuun
transportation i.e. ship/rail or trailer. The equipment shall be wrapped in polyethylene sheets
sosuoisowlp .qskuj ag4 cn. oSuwep luana.td o4 S3SUO/SOW.I0 uopoom ut poould Inoq oJopq
before being placed in wooden crates/cases to prevent damage to the finish. Crates/cases
`,dn oms sku, `,op2w,4, su gons suonwou repods .2ullpueq Joj swouoq pms on-eq peqs
shall have skid bottoms for handling. Special notations such as 'Fragile', 'This side up',
oRe)pud uo pax.teut Xgeolo oq puqs "op ,.sou Od, `,s.teinonJud s,Jounko, `,10pm,
'Weight', 'Owner's particulars', 'PO nos.' etc., shall be clearly marked on the package
.Xunn.ps Joi Josulpind Jod su spupp ioij4o cp!An
together with other details as per purchaser for scrutiny.
2uppud oqi .uonepwsw oiopq spopod icu sioopwo poicns oq iCutu wowcijnbo aqZ
The equipment may be stored outdoors for long periods before installation. The packing
wo!ciure Iffinusuwi Knuoq qnm SUOIC ut '0U-101S Joopwo icn oictenns iqopidwoo oq peqs
shall be completely suitable for outdoor storage, in areas with heavy rains/high ambient
-onnuiodwol
temperature.
7FF ich*4-1
f~F T
SPECIFICATION
FOR
DRY TYPE DISTRIBUTION
TRANSFORMERS
Abbreviations:
CONTENTS
1.0 SCOPE 4
5.0 CONSTRUCTION 4
7.0 COOLING 6
9.0 ACCESSORIES 6
Sheet 46 of 93
Format No. 8-00-0001-F1 Rev. 0 Copyright EIL — All rights reserved
1.0 SCOPE
The intent of this specification is to define the requirements for design, manufacture, testing,
packing and supply of cast resin / resin impregnated dry type distribution transformers.
2.1 The equipment shall comply with the requirements of the latest revision of the following
standards issued by BIS (Bureau of Indian Standards) unless otherwise specified.
2.2 In case of imported equipment, standards of the country of origin shall be applicable, if these
standards are equivalent to or stringent than the applicable Indian standards.
2.3 The equipment shall also conform to the provisions of the CEA Regulations with latest
amendments and other statutory regulations currently in force in the country.
2.4 In case Indian standards are not available for any equipment, standards issued by IEC/ BS/
VDE/ IEEE/ NEMA or equivalent agency shall be applicable.
2.5 In case of any conflict between requirements specified in various applicable documents for the
project, the most stringent one shall prevail. However Owner's / EIL's decision in this regard
will be final and binding.
3.1 The offered equipment shall be brand new with state of art technology and proven field track
record. No prototype equipment shall be offered.
3.2 Vendor shall ensure availability of spare parts and maintenance support services for the
offered equipment for at least 10 years from the date of supply.
3.3 Vendor shall give a notice of at least one year to the end user of equipment and EIL before
phasing out the product/spares to enable the end user for placement of order for spares and
services.
Transformer shall be suitable for installation and satisfactory operation in tropical, humid and
corrosive atmospheres found in refineries, Petrochemical and Fertiliser Plants or as specified
in the Material Requisition / Tender . The transformer shall be designed to operate under site
conditions as specified in data sheet. If not specifically mentioned therein, design ambient
temperature of 40°C and altitude not exceeding 1000m above MSL shall be considered.
5.0 CONSTRUCTION
5.1 The transformers shall have core type construction. The core shall be assembled out of
low-loss, nonageing, high permeability cold rolled grain oriented steel laminations.
Sheet 47 of 93
Format No. 8-00-0001-F1 Rev. 0 Copyright EIL —All rights reserved
5.2 The windings shall be of high-grade electrolytic copper. The insulation system for cast resin
transformers shall comprise of windings cast under vacuum, free of voids in a homogenous
uniform laminate of epoxy resin/ polyester resin. The totally assembled core and coil
assembly, for resin impregnated transformers, shall be vacuum pressure impregnated to
effectively make it impermeable to moisture, dirt, salt, air and other industrial contaminants.
5.3 The entire core assembly shall be covered with a resin-based lacquer for corrosion protection.
5.4 Lifting lugs shall be provided for core and winding assemblies.
5.5 The HV and MV windings shall have class 'F' or better insulation. The temperature rise of
windings under continuous full load shall not exceed the maximum allowable temperature for
the appropriate class of insulation as per IS 11171, above the design temperature specified in
the data sheet.
5.6 The insulation material used shall be non-hygroscopic, non- inflammable and self-
extinguishing if ignited by direct flame or arc. No toxic or harmful gases shall form during
heating and for burning. The insulation materials shall be sufficiently resistant to ageing.
5.7 The transformers shall be capable of withstanding the thermal and mechanical effects of a
dead short circuit on any or all winding terminals with full voltage maintained on other
windings as per IS. The transformers shall sustain a symmetrical short circuit on secondary
terminals for 2 seconds without damage or impairment.
5.8 Each limb shall have two solid state winding temperature monitoring elements to initiate an
alarm and trip for winding over temperature.
5.9 The transformers for Indoor & outdoor location shall have minimum degree of protection as
IP 23 & IP 43 respectively. However the marshalling box, cable termination box, bus-duct
termination chamber etc. shall have a degree of protection not less than IP-55.
5.11 The transformers shall be spray-painted or powder coated with epoxy paint. Colour shade of
final paint shall be as specified in the data sheet.
6.1 Windings shall be brought out on suitable nickel-plated copper terminals for cable
termination. HV side termination shall be from the bottom. Suitable disconnection chambers
shall be provided to permit the transformer to be removed without disconnecting the cable
termination. The MV side termination shall be by bus-duct or cable as defined in datasheet /
job specification.
6.2 The high voltage and medium voltage cable termination arrangement shall be complete with
cable box and bolted type undrilled cable gland plates. Non-magnetic gland plate shall be
provided for single core cables.
6.3 Primary cable box shall be able to withstand specified primary system fault level for 0.2 secs.
6.4 Terminal chamber for busduct termination shall have a gasketed cover plate, bolted to it.
Separate inspection covers shall be provided to facilitate connection and inspection.
6.5 All protection, alarm and indication devices and neutral CTs shall be wired by means of PVC
insulated cables upto the marshalling box. There shall be two gland plates, one for internal
wiring to the marshalling box from various devices which shall be glanded and pre-wired,
while the second gland plate shall be removable and undrilled for glanding outgoing cables.
6.6 One neutral terminal inside the cable box/ MV bus-duct connection chamber and a separate
neutral terminal outside shall be provided for earthing of transformer winding neutral on the
secondary side. The neutral terminal shall be complete with connector block assembly for
easy termination of GI earth strip/cable.
6.8 Two earthing terminals shall be provided on the transformer frame for transformer body
earthing. Suitable lifting arrangement shall be provided in the transformer frame. The
transformer shall be supported on flat rollers.
7.0 COOLING
Primary off-circuit rotary type tap changer shall be provided and shall have a range as
specified in the data sheet. Tap changing arrangement through links is not acceptable. Under
conditions of external short circuit, the tap changing device shall be capable of carrying the
same current as the windings.
9.0 ACCESSORIES
9.1 Accessories as specified on data sheet shall be included in the scope of supply. All protective,
alarm and indicating devices shall have minimum I no. potential free contact each for alarm
and trip. All transformers must be provided with at least the following:
9.2 Temperature monitoring system shall be supplied with temperature sensors fitted in each limb.
Temperature monitoring system shall initiate alarm and trip for winding over temperature.
Alarm and trip temperatures shall be site settable. The monitoring system shall also have an
indicating device.
The average audible sound level for the transformers at a distance of 30 cm shall be as below:
EIL / owner's representatives shall be given free access to enter the plant and inspect the
equipment at any time during fabrication. However, 4 weeks advance notice shall be given by
vendor to witness the final tests.
For testing requirements, refer Inspection & Test Plan doc. no. 6-81-1044. All testing shalt be
carried out at manufacturer's works under his care and expense.
All the equipment shall be divided into several sections for protection and ease of handling
during transportation. The equipment shall be properly packed for the selected mode of
transportation i.e. by ship/ rail or trailer. The equipment shall be wrapped in polythene sheets
before being placed in the crates/ cases to prevent damage to the finish. Crates / cases shall
have skid bottom for handling. Special notations such as 'Fragile', 'This side up', 'Centre of
gravity', 'Weight', 'Owner's particulars', 'P.O. numbers' etc., shall be clearly marked on the
package together with other tag numbers etc.
The equipment may be stored outdoors for long periods before erection. The packing shalt be
suitable for outdoor storage in areas with heavy rains/ high ambient temperature.
afT9-trtw fier-Tir
WRT
SPECIFICATION
FOR
FLAMEPROOF CONTROL STATIONS
Sheet 51 of 93
Format No. 8-00-0001-F1 Rev. 0 Copyright EIL — All rights reserved
Abbreviations:
AC Alternating Current
BIS Bureau of Indian Standards
BS British Standards
CEA Central Electricity Authority
CIMFR Central Institute of Mines and Fuel Research (formerly CMRI)
CT Current Transformer
DGMS Directorate General of Mines Safety
ERTL Electronics Regional Test Laboratory
FM Factory Mutual Research Corporation
GI Galvanised lion
IEC International Electro-technical Commission
IEEE Institute of Electrical and Electronics Engineers
IP Ingress Protection
IS Indian Standards
LCIE Laboratoire Central des Industries Electriques
LED Light Emitting Diodes
NEMA National Electrical Manufacturers Association
PESO Petroleum and Explosives Safety Organisation
PVC Poly Vinyl Chloride
SWG Standard Wire Gauge
VDE Verband Der Electrotechnik, Elecktronik and Information Stechnik
UL Underwriters Laboratory
CONTENTS
1.0 SCOPE 4
5.0 CERTIFICATION 5
1.0 SCOPE
This specification covers the requirements of design, manufacture, testing, packing and supply
of flameproof control stations and accessories suitable for installation in locations handling
flammable liquids and gases / vapours.
2.1 The equipment shall comply with the requirements of latest revision of the following
standards issued by BIS:
2.2 In case of imported equipment, standards followed in the country of origin shall be applicable,
if these standards are equivalent or more stringent than the applicable Indian Standards.
2.3 The equipment shall also confirm to the provisions of CEA Regulations with latest
amendments and other statutory regulations currently in force in the country.
2.4 In case Indian standards are not available for any equipment, standards issued by IEC/ BS/
VDE/ IEEE/ NEMA or equivalent agency shall be applicable.
2.5 In case of any conflict between requirements specified in various applicable documents for the
project, the most stringent requirement shall govern. However, Owner's/EIL's decision in this
regard will be final and binding.
3.1 The offered equipment shall be brand new with state of art technology and having proven field
track record. No prototype equipment shall be offered.
3.2 Vendor shall ensure availability of spare parts and maintenance support services for the
offered equipment for at least 10 years from the date of supply.
The equipment shall be suitable for installation and satisfactory operation in classified
hazardous locations in tropical, humid and corrosive atmosphere as prevalent in refineries,
petrochemical and fertilizer plants. Unless otherwise specified, a design ambient temperature
of 40° C and an altitude not exceeding 1000 m above mean sea level shall be considered.
5.0 CERTIFICATION
The equipment shall have test certificates issued by recognised independent test house
(CIMFR/ ERTL/ Baseefa/ LCIE/ UL/ FM or equivalent). All equipment (indigenous &
imported) shall also have valid statutory approvals as applicable for the specified location. All
indigenous flameproof equipment shall have valid BIS license and marking as required by
statutory authorities.
6.1 Construction
6.1.1 The enclosures of the control stations shall be made of cast light metal alloy.
6.1.2 The control stations shall be suitable for use in outdoor open locations and shall have IP-55
degree of protection. They shall preferably be provided with integral canopy. However, where
the enclosure has been certified without integral canopy, a separate canopy can be accepted.
The separate canopy shall be made of at least 14 SWG (2mm) galvanised sheet steel. The
canopy shall be suitable for providing protection against rain from top and two sides.
6.1.3 The control stations shall be provided with gaskets made of non-inflammable and self-
extinguishing material.
6.1.4 All metal surfaces shall undergo manufacturer's standard cleaning/ painting cycle. After
preparation of under surface, the equipment shall be painted with two coats of epoxy based
final paint with colour shade as below:
Flame proof (Gas group IIA/ IIB) : Dark admiralty grey shade 632 of IS-5/
RAL 7031
Flame proof (Gas group IIC) : Light yellow shade 355 of IS-5/ RAL-1012
All unpainted steel parts shall be suitably treated to prevent rust formation. If these parts are
moving elements then these shall be greased.
6.1.5 A warning inscription "DO NOT OPEN WHEN ENERGIZED" shall be provided on each
enclosure. The warning inscription shall be embossed on the enclosure or a separate warning
plate with above inscription shall be fixed to the enclosure with screws. The warning plate
shall be of nickel plated brass or stainless steel.
6.1.6 All accessories like nuts, bolts, washers etc. and operating shaft of pushbuttons, switches etc.
shall be made of stainless steel SS-304.
6.1.7 The control stations shall be provided with two earthing studs with lugs on the external
surface of the enclosures suitable for termination of 8 SWG GI wire.
6.1.8 The control station shall be provided with bottom cable entries. Required number of
flameproof double compression nickel plated brass cable glands and flameproof nickel plated
brass sealing plugs shall be provided.
6.1.9 The control stations shall have external fixing lugs for mounting on wall or column. The holes
provided on these lugs shall be of oblong type.
6.1.10 A nameplate indicating Tag Number shall be provided on each control station. Separate
nameplate shall also be provided to indicate the details of testing agency (CIMFR or
equivalent), test certificate reference, statutory approval agency (PESO / DGMS) and
reference, BIS license number, applicable gas group etc. The nameplates shall be engraved
type and permanently fixed on the equipment. In case the standard details given above are
embossed on the enclosures, the same need not be repeated on the name plate.
6.1.11 All flameproof control station shall be suitable for 240V AC as well as 110V/220V DC
control supply.
All the equipment shall be divided into several sections for protection and ease of handling
during transportation. The equipment shall be properly packed for the selected mode of
transportation, i.e. by ship/ rail or trailer, and shall be wrapped in polythene sheets before
being placed in crates/ cases to prevent damage to finish. The crates/ cases shall have skid
bottom for handling. Special notations such as 'Fragile', 'This side up', 'Center of gravity',
`Weight', 'Owner's particulars', 'PO no.' etc., shall be clearly marked on the packages
together with other details as per purchase order.
The equipment may be stored outdoors for long periods before installation. The packing
should be suitable for outdoor storage in areas with heavy rains and high ambient temperature
unless otherwise agreed. A set of instruction manuals for installation, testing and
commissioning, a set of operation & maintenance manuals and a set of final drawing shall be
enclosed in a waterproof cover along with the shipment.
Sheet 58 of 93
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
1. Make :
2. Model No. :
3. Rating :
4. Applicable code/standards :
5. Speed range :
6. Speed reference :
7. Input power supply ratings
a) Voltage : ± %
b) Frequency : ± %
8. Overload capability
a) 125% : minutes
b) 150% : secs.
c) Inrush current 250% In for : secs.
9. Overall efficiency at
a) 100% load :
b) 75% load :
c) 50% load :
d) 25% load :
10. Overall power factor at
a) 100% load :
b) 75% load :
c) 50% load :
d) 25% load :
11. AC Output
a) Output voltage range :
b) Voltage accuracy :
c) Frequency range :
d) Frequency accuracy :
12. Output short circuit capability and duration :
13. Deration of motor at
a) Maximum speed :
b) Minimum speed :
14. Rectifier/Inverter
a) Make :
b) Type/Model No. :
c) Diodes/GTOs configuration :
d) Total No. of Diodes/GTOs :
e) Cooling system
- Type :
- Redundancy in cooling Units :
Sheet 59 of 93
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
Sheet 60 of 93
Format No. EIL 1641-1924 Rev. 1 Copyright EIL – All rights reserved
Unit Delayed Coker Unit Location Job No. B224 Unit No. 114
PURCHASER'S DATA
A. Site Conditions
1. Maximum Ambient Temperature °C 48.2
2. Minimum Ambient Temperature °C 3.4
3. Design Ambient Temperature °C 45
4. Relative Humidity % 100
5. Altitude Above MSL m Less than 1000
6. Environment Humid & Highly Corrosive
B. Technical particulars
1. Tag no.
2. Duty Continuous
3. Service Lighting
4. No. of windings Two
5. Type of cooling AN
6. Rated MVA
7. Rated voltage
HV winding kV 0.415
LV winding kV 0.415
8. System earthing
HV side Solidly Earthed
LV side Solidly Earthed
9. Rated frequency Hz 50 +/- 3 %
10. No. of phases Three
11. Fault level on HV side kA
12. Connection
HV side Delta
LV side Star
protected As per IS
LV winding
total As per IS
protected As per IS
A 13-MAR-2019 ISSUED WITH TENDER BANSAL VARUN SAHU MANJIT KUMAR SAHU MANJIT KUMAR
Unit Delayed Coker Unit Location Job No. B224 Unit No. 114
Type Offcircuit
Range % ± 10
No. of steps As per specification
LV w.r.t HV ° 90
Vk A
Im at Vk/2 mA
RCT ohm
28. Installation Indoor
29. Painting & colour RAL-7032
30. AC Auxiliary voltage V 240 +/- 10 % SPN
31. DC Auxiliary voltage V
32. Bidirectional roller type
33. ¢ distance of flat rollers mm 1000 mm
resistance type
thermometer with contacts
A 13-MAR-2019 ISSUED WITH TENDER BANSAL VARUN SAHU MANJIT KUMAR SAHU MANJIT KUMAR
Unit Delayed Coker Unit Location Job No. B224 Unit No. 114
MANUFACTURER'S DATA
1. Make
2. Rated power at ambient temperature of
25 °C
30 °C
35 °C
40 °C
45 °C
50 °C
3. Insulation type
B. Performance
1. No load loss at
100% voltage kW
110% voltage kW
2. Full load copper loss at 75 °C kW
3. No load current at
100% voltage A
100% voltage A
4. Efficiency at full load at 75 °C
at 0.8 p.f %
at 1.0 p.f %
5. Eff. at half load at 75 °C
at 0.8 p.f %
at 1.0 p.f %
6. Load at which max eff. occurs MVA
7. Regulation at 75 0 C
at 0.8 p.f %
at 1.0 p.f %
8. Maximum efficiency %
C. Mechanical data
1. Core & winding weight kgs.
2. Total weight kgs.
3. Wheel gauge
4. Overall dimensions
Length mm
Breadth mm
Height mm
A 13-MAR-2019 ISSUED WITH TENDER BANSAL VARUN SAHU MANJIT KUMAR SAHU MANJIT KUMAR
Unit Delayed Coker Unit Location Job No. B224 Unit No. 114
Eil Notes
A 13-MAR-2019 ISSUED WITH TENDER BANSAL VARUN SAHU MANJIT KUMAR SAHU MANJIT KUMAR
a>
O
a>
a>
cu
• c
o
z
cn
o_
=o cno_
rt
ra w
cn
0.
• o
Q.
c->
uo4eweweldw! JC4 penssi
co
0
c_
panss% pue pes!neu
C3
Z LOZ'90'6Z
STANDARD SPECIFICATION NO.
•
•
r)
cz ? ,-••■ .--■ ■-■ ■--1 ~
e'D Z '71 'rl '-r1 trl C1 pl n pi p ,_,:
<
»0<D . 0 cri rrl c) n '-' >.-,c-1 ?.-.) H R, . ›c,,› ?1, J 1 ,0 :-
cr fl5 0%
,H (-) (-) (-)
)--1 (--■
:9 H :T] 4 — tri C4 CA fT)
ro O •-■- r-' rrl .....
9
cA 5* 7z g rri f4
-o. . ()
- .,-1 -,-
(-) > 5
Z' o .
».. m
»
0..
,•■■ • CD "'.L
CD 1--,
('I=D--.)•
{
PD 1D) CD cn cn
c.D I.
cn sn ril
S=D
— (5
'- • ..c 2
p0 = o ',---,' ..E
o.$ •
CL, >
1=0 co
• :,)
• 't CD m
S=■ m o
-n
s'll 73 0
r=•r m Z
5
::. C
cr M 0z
4 -ctr Z
C)
-< m
CD '-' •
CD CJ
't:f po 73
r=,) '< '..C/ ''' 1. ":1 '-': '-‘7) Z Z Z 4 4
crq r' 0./y 0.0 r-, s-i ..H,:i H
r) ,0
(-)1-CJ 4 ,c) (.4 ril C) tri '-ci o ,3
4 ■4
-c■
• `.)-• '"1:i 0 v) o
(-)c— 4 H v) (-) ,H H m
• c tri -, o > ,'-'i
— p,.0 H !3 Cn Z
';-; '. cn
o" . m
O CD CD c,
;:,7 • cn :,,, •-1 ,-, ,-r- = ,-r ty,' t.,'„
''''t ,-t-
cn• C> ) ,.., .-t . —•
--
cl.. ., ,..., „_, `-.0_..,....,..,
,---. •-•c.-cu o n ES o '''zi t) ,g)
ri) -- o .-1 e', ''''' .., co
‘"' '. --
rn -s CrQ•-s „, ....,
< •-• p) , --: <0
. (%) @" 16) ,r9 1--, -- p9 cQn E . S=D ~.
cn .. • ...... ,-...
■-...CD
■
-c) ,..0 l-., :=1. .(7--) .-, • k ., '..• t'D ,-.1
CD .-t CD s..
,
7T' cp ,.., sw ,-+- ,.• •,
: -A
,
CD .-t o $5 Lit) 1H (..) ,, n „. til '''t CD C) eD (-) v,
s:). ,-) (-) CD ' i A> ..1 .., t'D ..C)
:. CD ....) >< CL. f.i O, , ,-,. CA _
'"Cl C:) co (1)
:),,,,
t-' c4.
zr (!) Cr) '—' =1. C. ;'' >"E_i, 2̀) R
o —o f=k) tn .--,• c Crg
,-, - o g' ()
(.1) .2=1 cr = CD
CD .-1. .-- '' • ::-•-' cn co o" CD c-) ,,, cp
P0 H z'• .ct
`-'-<- ~1 0 Cfc7 2. C... ~ •-•'• c) -- o --
t-r1 c.)
,...„ rD C./) CD s=,)
--t <--t. ''-'•
0 CD CD = ')r- CD Cn
o- -o o o . ., ,...
`-' r'::) CD rD C c4 A>
•• cm rw
5 CD 0 .--P-
(7; 2. o (1) ft,,
› ..: i AD CD
(-) 7ci ,_„
(1) ,-1 Cl.,
'Cj> SDD')
CD .--, • C> '''
' <.1) '" C>
5 0,-, ..,, 0 =E
-
o o 0. crc, CD,
.-t•
.-1
'6"' cn
-t••77.
pamaseJ siy 6P IIV— 113400c100
cn
0
Sheet 66 of 93
STANDARD SPECIFICATIONNO.
11 Z"Aall0S01-18-9
0
I—■
INSPECTIONANDTEST REQUIREMENTS
SCOPE OF INSPECTION
7 C/)
CD t."1
QUANTUM
r)
0
STAGE/ACTIVITY CHARACTERISTICS SUB
OF CHECK
ril
.0
I■1
I■1
SUPPLIER
SUPPLIER
0
1■•+
Procedures
i
I
i
11‘à
MaterialInspection
C:,
Material Identification
Incoming Material like Operational checks
fabricated panels,Power
,
semiconductors,
CD rt, ,-,-
(-) ---- •-
■
c) (I)
-t
••
l•-)
,H
r-, r)
IGBT/SCRs,relays,meters,
-■
,--,
x
CD
CZ
X
,-,-
,--r-
v)
CT/PT,transducers
cr
94
u)
CD
transformerunit,rectifier
unit, filteretc.
P
(....)
Inprocess Inspection
Visual ,Dimensional, Bill of Materials
1,)
»,--•
VFD Assembly
,--.
C)
CD
x
Supplier'srecords
•F,
0
FinalInspection
Sheet
Copyright EIL— Allrights 67
reserved of 93
Z C/
i•-) -■• 0
';21
0
n ::,
CD
,--,
s ,D .
n n
(TypeTests)
n
CD ,-,-
, • Zrg
n 0
Final Inspection
cf)
,-e-
zp
cn
•• • ••
Z > r, z(-)c-.)nnr-r-r-, 5 4 ,L. n ("") cl) CO (-
1) n<
o o- n - • o- a- o- O- 0DO erq* v) ,..,cp '-o `-' ° o- ;" a_ ': a- - -
ascirQrDroronsD, o,... -- n 9.4.
- " 3.
° ,9 - - - o n o - -- "fr> -, 91
o 2 „ -- t=2". ö
> ,..,_ R.- r-0 :::::-
0, ,.- 0- ;-_-,_ o
(D
r- r,,,f,. -0,n-1 -6-
< 0 ,, cD cD s< .-t AD p-s-, ('-7. C) po = n
(:, ci) ,-s• r-'- p,, Q-
Efficiency
-
CD -t - • o 6-,E. ,-,-t AD so. ■-i
c) .., ^szs (-) ro
n o -1 -1 -:• ,-,-, s-* co n --•
Z -8 , E — 2, '• c., 4) .7. 2 rED ci) '-
cp Q- '-c &D s=.— D (1) 0
-!
rD -s• o rD -, .-••
v)- '-ri
-. o ----- -s -•• CD
Temperaturerise
Pp Q. C/) „.-,-.
., ,- 1 C> < c) :c
" C1) ,-1., C CD n v) O C> o 5.
- o -b
Modeasappli cable.
rD 4 c c ( .15 .., < n
- , r, O *. -, ro ar - s::,, n
n (I) c-) ..d .1, r) o -•• o so
cD n -,- (i) e• ■• ro Z- CM ,
(1) FP '-3 . =.. (,) CD ~-:
'--+, 2
-, -•••• AD CD ,--rD -b
.o "z1 r;') '-' o
v)
-s- ..s., v) n o o ' -s v) • cn
-s
ro -s- C -.
rD CrQ
o. °
-t e-s- -,- CD ,-1- w -o
o -sa -t ~1., C> r- m
,--.
CHARACTERISTICS
O .-s CD 15 ro vp m (-)
ro sn o ..C]
: o -n
frequencyatconstanttorque/ Voltage/Power
,- .--r ,- o
co -•
o m z
CfQ z
Voltage division
o
m
• u)
•
'-'
CD
CD
fromeach c::› m
type/rating
cn
Onesample
QUANTUM
OFCHECK
-<
cn
•••
CA
CD '0 M
n "o
c -- n
0
. .
Supplier'srecords
SUB
SUPPLIER
cD
O
x z
Copyright EIL—All rightsreserved
Z'AallOSOI-I8-9
SUPPLIER
Sheet 68 of 93
,--,
SCOPEOFINSPECTION
STANDARD SPECIFICATION NO.
t-,
x x
■-t
,--,
›,-
m z
m0 z
m
cn
STANDARD SPECIFICATION NO.
r-
11
-n
Z*Aa21050I-I8-9
•
7:1
z
cn
03
-<
-<
c-)
c
m
•
SCOPE OF INSPECTION
QUANTUM
W
0
STAGE/ ACTIVITY CHARACTERISTICS SUB
0
,
?)-'
Submissionofcertificates
CA
,.-
independenttest housesuch as ERTL,
o
o
P,)
n
.4.
i....)
o
forrated currenttest,power loss
(-)
cn
determination,temperaturerise, EM
Immunityand EMEmission
U1
Painting
Visual Packing list /
Protection against damage during
tn
c)
c:'
Z
c>
Paintingand Packing
—
Supplier' s
transportation. Records
Z " CZj
o
m Z
</)
STANDARD SPECIFICATION NO.
-0
m
cn
m0
A -n
Z'Aall
•
-n
m
rn
.22
co
•
•
SCOPE OF INSPECTION
QUANTUM
cA
'1
o
g
r)
ril
(-5
cn
(n
STAGE/ ACTIVITY
.-
SUB
0
Z
OF CHECK
5
ril
SUPPLIER
,:51,
,---
SUPPLIER
GD
cr■
Documentationand IC
Reviewof Internal Test Reportsand MTCs. Supplier's Test
IC issuance Records /
x
;.--•
cD
cr■
DocumentationandIC
Inspection
Certificate(IC)
Final data folder
Compilationof Inspectionreports,drawings,etc
o
c)
ch
iN.)
x
Final Documentsubmission /Completeness
asper VDR / PR
certificate
iF iE
A11the loadtests/Functional Checksareto becarried outeitherwith thejob motororwith ShopMotor
••
...
>
i-i"
Cl,
f:1-
.---s•
■-r-
■-+
■cn-t-
..--r
-1
cr ro
-)
o
ö
0
c)
CIA
;=■.,
O
O
cp
10
cn
cn
cn
.-s
..c)
CD
CD
CDco
CD
co
co
co
AD
CD
`'
C)
‹-4-.
—.
—.
--.....
,-h
CD-
c:1.,
CL
cr
"d
st
<._.,
-.Q-
,-,-
O
c)
a)
cn
cn
cn
cn
CD
)=,)
co
cp
CD
<
co
AD
AD
AD
AD
~t
>1:,
7:1
7:1
uo!muaruaidwn roj panssi
C)
o
CrJ
ci)
STANDARD SPECIFICATIONNO.
=1 uu > cl)
(-) (") (-) p: c)
r-4
s0 co
<-)
rrl
sumjmnaacmv
S
DZZ
uldnD .D. s
CD CD CD .1 E cr, -.. * ''.
(i) ,,› C-.) (") e) crc '-C■ 2 '-ii o -i -,., --,- ;:p 0 (/) rn
o n) , • ,1'.
ft g.
,cn 0 '.-: c° " r) -I ) . (,) (-) o c,
_ „.."
v) -- vD
InspectionStandards Committee
c"o -':< 0 ''-'' 1-1-1 ■-•-■ ■:,0 0 0 -42- ›
cp 8 -, $=,, 3 4 ,.,. (-)
-• e)
,, <• --- ::::.
c , n ■-•■•, <2, :ziEsj eD
1 (-D
(71-:,' $''
.2-, ':E7 (-) <•,, o , ,-. c) w, , F5-
o- . ,i- -• o ,t o cp •••,
,..,• '-• ,- rri 0 Q
til
,-1 ....., C ‹.,, l'° <
-« ,- -•Cl.. c) ,./)
,-- Cr2 . H 4) (.,,
L), c'"[7 cr,9 ("D '-'6')« p,)
,..,
0 CDr)() o '-4" (:) ■-3 o 0 , • 0
(-1) r4- ■-t c) ei) 0. co 0 .-+. CD ,-■ ■-1-,
cn cfc? cr, ■-r, C/)
c") o ■-t A) rw •'
0 P4. '4 () CD ril
4 (1)
eD ,-. c) Cr■:■ ,t >C
— 1,1- H
0- (D 5. ,,,, 'l O.
00
r) 0 1:0 r) rw <).
-* co
0 cn CM cp CL,
(") CfC7 0
,
o :,,,ED A) co
E cr' ,-11 rri
n CD C)ri 94 '''
0 A) CD 0 C)
■-1~),
0 ) ,-1
C '. .(7') .
CD 5 A)
E
cr
>< o cl cDczzz
rl 44
o 4 4
r. =6 r. -c) H0
() (-) '-rc
rri 0 s-3
■
-3 ■
-3
2
r) cc, c„ CD
< -•1 >-.3 7z:J
,-• ''' CD AD
'"t: '""ci '-'0 't::
0 0 2, '-zi
CD
C).• r:t ■74 . 4) 4
CD s• o -1 (,) o ■-ci r) crc? ,Rs- ---, z AD CL, '<7D-
,— cn crt:r ,__, z go ("D_ p0
" r) E• a cr) ''' r2 §
,..
.-,:i ,.., ,...., n. 'i.5",.- —•-ot , ,-.< 4 .,..,
r:::4-
-9 '-3 c) '-< ,, (-) •:4' 0) ,c) t'll
,,
,,)
.10p.10 3S1I10.1rid
.— cp c) ,c7
:,.,. h7,, . ~. -o
O 5 ..,=:, cr ,„
0 (1,:■ c") `4
E•
. -,.-
{=1., E,.,' .(3' • e) .".' •
t'D ,-1 ,-+
r- .
ril e)
,-,.. OC/D CD 0 Cra (I) ep 0 94 ep
-C1 E . 3" cla
a, . .D'' > ... ■-b
cn
Freall uopns anwsod
0 $:') .-"'Z'à
CFC? '-'th
c) ...., (1)
CD .--■ • n
co A)
,-- CD
o k'
:=.'t A) 0
r)
,‹ .8" 0 C)
c) .c.. "
),) o
,r CfC7
•-■ • A)
0
N
pamasai sp.161-1 11V— 1134L16pAcloo
O
.nall9001-18-9
Sheet 72 of 93
STANDARD SPECIFICATION NO.
3d03S
ThisInspectionandTestPlancoverstheminimumtestingrequirementsofFlameproof ControlStations.
SIA131A1f130(1aDNIM13,1321[
O
tvl
SCOPE OF INSPECTION
Zw
or
QUANTUM
r)
STAGE/ ACTIVITY
ril
H
cn
"1'
r)
o
g
OF CHECK SUB
SUPPLIER EIL/TPIA
SUPPLIER
o o
Procedures
,—,
..
..
its.à
Material Inspection
castings,glass,meters,
!--)
o
o
o
of Manufacturer's Certificatesetc.
asapplicable Testrecords / Lab
Fastenersetc
Test Records
o
w
Inprocess Inspection
Flameproof enclosure
RoutinePressuretest 100% by Supplier'sTest
L.,
withoutcomponents
7
Supplier Records
SCOPE OF INSPECTION
z CA
0 t""
QUANTUM
0
STAGE/ ACTIVITY CHARACTERISTICS SUB
OF CHECK SUPPLIER EIL/TPIA
SUPPLIER
,:::,
Final Inspection
cz,
Visual/Dimensional/BOMChecks
.,• ,...,—,
7. °3-,1, -cs ©
,
<., -cs c:,
'—i
,4,C4
»
.•-, •--,-. 0
V) CD cD
CD
,__, C) e•-,
cn
Plan Gap/Path/Clearances
cr —.c,
Flameproof Control Station
;-","• •-.■
Zn '1:$
.t=.
__,
Electrical/Functional Checks
.3 ,
—, ___
I ci ....<
(Acceptancetests)
0
n
a
CD
CD
trl
Highvoltagetest
-
IRtestbeforeand after High voltage
..- .
(-)
CD ■
CD ,"-P-
rW r,
<D
ci) C)
-s
(I)
r) (4
i.)
-1=.
Cii
C4
CCoE/ PESOasapplicable.
5
cn
SDD
&Documents
-...
■
V)
CD
CfCi
Valid BISLicenseasapplicable
Degreeof protectioncertificateasapplicable
••••• • • •• •• •
....
G>
C1
f.ii
=
DD
Z
CM
PaintingandPacking Visual
Suitableprotectiontoprevententryof foreign Packinglist /
,—,
(..ii
o
c:'
..--,
material. Supplier' s
Properpackingtopreventany damage during Records
transportationand storage.
•
CA
,:::D
Documentationand IC
01 Z c4
_ o r.,
r,> —1
co
• 7)•
o
CD
Cfg
O rD ■"r
Documentationand IC
cr'
P.) • 9,
STAGE/ ACTIVITY
t-F
CD
ct)
il
!ZD CfC?
• co
••
• ••ci •
CD
CD
IC Issuance
CD
s=,)
cn
CD
CD
~17
>
•-G
C/)
■
-F
•
0
CHARACTERISTICS
C■1••
cn CD
cn
Reviewof Internal Test Reports&MTC
0
co
CL,
oco
0
O
—
c>
cr' >10
0
cn .
4; ,=='
"CS
CD cn
QUANTUM
OF CHECK
cn cA
cn
'-cs c) r)
-• n) 0
.--, ■ 0 .-s " 0
"
0 Q,'
rD --- (.7,
(,)
,-,
o
CD
• (i)
cn
cn
SUB
0
SUPPLIER
<1)
pamasai sli4 61-1 11V— 113414 60doo
CD
Aau 9001-18-9
SUPPLIER
Sheet 75 of 93
<1)-'
cn
SCOPE OF INSPECTION
cn
STANDARD SPECIFICATION NO.
EIL/TPIA
Cover Page 1
Contents 1
Abbreviations 1
1 Objective 2
2 Packing Procedure 2
3 Marking Procedure 5
5 Phytosanitary Certificate 6
ABBREVIATIONS
cm Centimeter
M3 Meter Cube
MT Metric Ton
M Meters
Sheet 76 of 93
1. OBJECTIVE
The Objective of this procedure is to provide guidelines for Packing & Marking of Project Materials
to ensure safe Handling, Transportation & Storage of Materials.
2. PACKING PROCEDURE
2.1 General
The following instructions are intended as minimum requirements, and adherence to these
instructions in no way absolve or relieve the Supplier of any his responsibilities or obligations agreed
in the P.O.
2.2 Purpose
Packing shall be sufficient to withstand without limitation, rough handling during loading / unloading,
inland & ocean transportation, outdoor storage, exposure to extreme temperatures & rain etc.
Packing shall be to ensure protection against both mechanical damage (shocks, rupture, breakage,
loss) and corrosion (rain, salty atmosphere, etc.).
Packing includes pre-packing treatment and protection activities such as application of anti-
corrosion, coating, pealing, desiccants, solvents, etc.
Due to climatic extremes encountered during transit & storage (i.e. extreme heat, high humidity and
fine drifting sand) and the transport operation (i.e. road, sea or air), it is essential that protection and
packing be of the highest standard.
• Supplier shall be responsible for compliance with these instructions and select the packing type
according to the nature of the CARGO and transport facilities used.
• Supplier shall be responsible for the accuracy of the weights and dimensions declared and
marking on packages. The packing list shall be in strict conformity with the packing contents.
• In case of damages due to improper packing, all resultant replacements required shall be
promptly made by the Supplier. The liability of free replacements of damaged items (due to
defective or insufficient packing and/or protection, or for short supplied items) shall be entirely to
Supplier and such supplies shall be made good at no cost to BUYER.
• BUYER reserves the right to reject the packing when the packing is not conforming to these
instructions, and/or when the packing does not ensure perfect protection of the CARGO.
Sheet 77 of 93
2.5 Packing List
2.5.1 Pro-forma Packing List: before delivery of the cargo, Supplier shall send a Pro-forma
Packing List to TPL. The Pro-forma Packing List shall clearly mention the following:
a) Total number of Packages,
b) Net and Gross Weight and dimensions of each package
c) Delivery Point and Date,
d) Information of Hazardous Cargo, if any,
e) Details of items packed in each package
f) Declaration of “Rust Prevention Agents & Removal Solutions” packed in each package
g) Any other details as informed by TPL time to time.
Supplier shall also submit the Containerized PL once the cargo will be stuffed into the
containers.
2.5.2 A master list of all packages (mentioning package-wise weights & dimensions) shall be
prepared and kept in package no. one of the shipment. If the material is shipped unpacked,
master packing list and individual packing list shall be placed in waterproof envelope and
securely attached to the material with Galvanized, Stainless steel or Aluminium Wires.
2.5.3 Packing List must show, apart from other particulars, purchase order number and item tag,
relevant material code for each item as per Purchase Order, actual contents in each case,
net and gross weights, dimensions (LXBXH in cms), packing style and the total number of
packages.
2.6.1 The material must be free from rust, dents, cracks and surface defects at the time of
packing/ loading.
2.6.2 Adequate protection shall be provided to prevent seepage of water due to rains, rough sea
weather etc.
2.6.3 Spares / Tools & Tackles shall be packed in separate package & must be clearly marked as
spares. It shall not be shipped unmarked alongwith the main equipment.
2.6.4 CS / AS / SS Pipes, Valves shall be protected with plastic end caps at both ends. All
equipment nozzles & openings will be suitably protected with wooden or plastic cover.
2.6.5 All electrical and instrumentation items shall be individually wrapped in polyethylene or
polypropylene plastic sheets in additions to normal outside packing for protection against
moisture. Openings in electric motors, generators and other electrical equipment shall be
sealed with waterproof tape. Under no circumstances, fragile or delicate material should be
packed with steel items. All fragile / delicate items shall be packed in separate boxes.
2.6.6 For all pressure, temperature and flow instruments, which are not mounted on the
equipment and shipped in loose, the measuring range must be mentioned in the packing list.
and the range on the packing list should not exceed the scale range of respective indicator
or meter. In case if the item is detailed in the packing list or in the purchase order as a
separate item, but is mounted on a skid or panel, the exact location of mounting needs to be
indicated for easier custom clearance and verification.
Sheet 78 of 93
2.6.7 Supplier shall tag each item giving description of the item for easy identification by Customs
Authorities as well as Site Store In-charge.
2.6.8 Cases and / or Crates should be constructed using top quality plywood and shall be solid
and robust. Under no circumstances shall fiberboard, cardboard or similar cartons be used
as outside packing. Hay, straw or similar vegetable fibers subject to disease or fungus shall
not be used in packing.
2.7.1 Hazardous materials shall be packed separately and shall be labeled, marked, and certified
in compliance with applicable government and international regulations.
2.7.2 Material Safety Data Sheet (MSDS) shall be sent to BUYER. MSDS shall also be attached to
Packing List.
2.7.3 For explosives or other Hazardous items, which require prior approval by Statutory
Authorities, Supplier shall submit all necessary documents for Buyer to obtain necessary
approvals.
2.7.4 The Supplier shall produce hazardous cargo certificates, in accordance with the appropriate
Government and International Transportation regulations for all shipments.
2.7.5 If there are any Radioactive material in the shipment, Supplier shall submit within 60 days
from PO date, radioactive element name, its radioactive strength, brand name, chemical
composition and physical properties, original materials, description of protective device and
method in transportation, leakage rate in transportation, operation and maintenance manual,
special packing and marking requirement (as per the guidelines set in IMCO regulations).
Modes of packing
In accordance with the Type of Cargo, the following modes of packing shall be considered :
• Wooden cases
• Wooden crates
• Skid construction
• Non-returnable steel drums (export variety)
• Non-returnable cable drums
• Bundles
• 20 ft – 40 ft non-returnable containers / shipper’s own containers
Sheet 79 of 93
3. MARKING PROCEDURE AS PER INDIAN IMPORT POLICIES /
DOMESTIC POLICIES
3.1 General
3.1.1 All markings shall be painted clearly and thickly with black oil-based ink on the front and rear
panels of each package.
3.1.2 The Shipping Mark should be printed in the largest possible block letters. If packing is Bare,
Bundle, Skid, Pallet, Crate (Wooden or Steel), Dura-Board, the shipping mark should be
printed on plywood or tin plate & firmly attached on at least two easily visible places.
3.1.3 Packages/equipment of five tons or more must be marked with slinging points and also
clearly show on all sides the center of gravity.
3.1.5 Fragile items shall be clearly marked, Fragile Handle with Care and or This Side Up etc.
All boxes and crates shall also be marked with the appropriate international standard symbols
for handling. All boxes and crates are to be marked clearly on all four sides:
"Handle with care" / "right side up" / "keep dry" / "hazardous" / "restricted" “sling / fragile, "flash
point", etc.
Sheet 80 of 93
4. STORAGE & HANDLING OF CARGO
Supplier shall submit precaution for storage and handling of cargo, which requires special attention
in handling. Supplier shall stencil appropriate instructions for the handling, transport and storage of
the equipment and material on the outside of the package.
SUPPLIER should submit the proposed transportation drawing/ sketch clearly mentioning all
dimensions (Length x width x Height) and weight to TPL, after getting detailed drawing approval.
This will be an approval category document and the comments from TPL shall be incorporated by
SUPPLIER with no cost and time implication to TPL.
******************************
Sheet 81 of 93
PROJECT : RAJASTHAN REFINERY PROJECT (RRP) ;
FORM SP-11(iii)
PRICES FOR POST WARRANTEE COMPREHENSIVE ANNUAL MAINTENANCE CONTRACT SERVICES FOR VFD
INDIAN CURRENCY
FOREIGN CURRENCY COMPONENT
COMPONENT
(IN CURRENCY AS INDICATED IN
(IN INR)
FORM-SP-0)
1. Comprehensive post warrantee Annual charges for maintenance of
VFD after 2 years extended warrantee of all types comprising of
deployment of minimum one Supervisor including supply of spare parts
and deployment of extra personnel required for repair or replacement
of the above systems for the following periods:
a) First year after expiry of extended warranty period
b) Second year after expiry of extended warranty period
c) Third year after expiry of extended warranty period
d) Fourth year after expiry of extended warranty period
e) Fifth year after expiry of extended warranty period
TOTAL PRICES (a + b + c + d + e)
Note: 1. EPCC-04 Contractor to provide 2 years extended warrantee of all VFD after completion of Defect liability period. Comprehensive post
warrantee Annual Maintenance Contract (CPWAMC) period shall start after completion of 2 years extended warrantee period,
JOB SPECIFICATION
(ELECTRICAL)
UNIT : 114
Sheet 83 of 93
Proper sealing / baffles or frame shall be installed to separate busduct sections inside and
outside building in order to prevent interchange of air between the sections.
The minimum head clearance for personnel movement for cross cable trays in cable cellar
shall be 1800mm for escape routes. The cable cellar clear height shall be decided accordingly.
The air-conditioning ducts in substation shall be so mounted that they do not fall above the
switchboard and do not obstruct illumination.
Fire fighting system like emulsifying system for transformers, water sprinkler system for cable
cellar, portable type CO2 extinguishers, sand buckets, Fire paint etc shall be provided for
substation, transformer bay etc. as per statutory regulations and as defined elsewhere.
Switchboards shall not be located on the building expansion joints. If unavoidable, dummy
panel shall be provided on expansion joint.
Mono rail with chain pulley block shall be provided above 66kV GIS isolator breaker panels for
installation and maintenance.
Any other civil work required for completion of work is included in contractor’s scope of work.
4.6.17 RCC LINED TRENCHES/CABLE TRAYS
(i) Overhead electrical cable Trays shall be provided for cable cellar in substations, plant/
unit area and upto SRR.
(ii) Cables for different voltage grades shall be laid in independent cable trays. Separate
cable trays shall be provided for control cables.
(iii) Wherever trenches/trays within battery limit have interface with the trays and trenches
outside battery limit, the details shall be finalized during detailed engineering.
(iv) It shall be contractor’s responsibility to co-ordinate the cable trench/ tray routing from
other contractor and other agencies involved. Trenches and trays shall be provided up
to the battery limits as per the final approved layouts.
(v) Cable trenches in unit shall be sand filled.
(vi) Refer plot plan for exact location of substation, SRR and unit for further details and
estimation of cabling.
(vii) All HV & MV power cables in racks/trays shall be laid in single layer only.
(viii) Single core cables shall be laid in Trefoil configuration.
(ix) 20% spare space shall be provided in cable trays/trenches.
(x) Cable trays covers shall be provided for top most cable trays and vertical trays. Further
wherever trays crosses hydrocarbon lines, bottom covers shall be provided.
(xi) Cable tags shall be made from Stainless steel and numbers shall be engraved. SS
wires to be used for binding Cable Tags.
4.6.18 ECS SYSTEM
Refer ECS system job specifications. Doc No. B224-114-16-50-SP-7205 attached.
4.6.19 HV VFD
a. Motors and VFD shall be suitable for the driven equipment for the required conditions as
specified elsewhere.
b. VFD shall be V/F controlled type.
c. All HV switchboard feeders, input transformer (if applicable) and VFD shall be part of the
single line up/ board.
Sheet 84 of 93
d. Motors shall be started through VFD system consisting of suitably rated input transformer (if
applicable), power electronic circuits to reduce the voltage / frequency at the time of starting
so that starting current is restricted to a value not more than 1to 1.5 times rated full load
current. The VFD system shall be complete in all respects including all connections between
the breakers& other components, VFD panels and input transformer (if applicable). VFD shall
have facility for make before break (during switching over to Bypass). VFD system sizing
calculation including sizing of input transformer (if applicable) shall be furnished for owner’s
review.
e. VFD panel shall include line PT(as required) on outgoing side of VFD and any other hardware
required for synchronization of output breaker and bypass (DOL) breaker (in order to generate
synchronizing signal for bypass etc,) and all other control and protections required shall be in
vendors scope (as required).
f. Input transformer (if applicable) for VFD shall be panel mounted dry type suitable for indoor
installation and comply with EIL standard specification 6-51-0044, clause 5.5.2 of Specification
for HV variable frequency drive system (Doc. No. 6-51-0050) & Dry type transformer
datasheet.
g. VFD though shall be installed in Air-Conditioned/ Non-air-conditioned area but it shall be
suitable for continuous operation in non-air-conditioned area.
h. Suitable hardware (including all CTs, PTs, cables etc.) & software as required for satisfactory
operation of VFD system, online transfer of VFD mode to bypass (DOL) mode/ bumpless
operation of the motor shall be provided.
Sheet 85 of 93
Pre-defined visits shall start immediately from the next month after commissioning. HRRL will
have the right to reschedule the visits. Each Visit shall be of Min 2 days including to & fro
charges, lodging and boarding and shall conclude only after the deliverables are achieved as
per the approved check list. Checking of computer/printer hardware and software is also be
covered in these visits, no other extra cost will be reimbursed for the same.
Sheet 86 of 93
(xi) Contractor shall include painting and marking of all buses, individual incomers, all
outgoing feeders etc. with detail such as Tag no., feeder rating, sending end source
reference etc. for all switchboards.
(xii) Paint shade for indoor electrical equipment shall be RAL 7032 and for outdoor
electrical equipment shall be RAL 7031.
(xiii) HV busducts shall be air insulated type only. MV busducts shall be Sandwich type.
(xiv) For termination of aluminium cables to copper bus or copper cables to aluminium bus,
bimetal lugs shall be used.
(xv) Sealing of cut-outs for switchboards on switchgear hall floor shall be properly done
after placement of chequered plates.
(xvi) Proper stencilling showing reading & date with letters of radium stickers to be done on
each and every Earth Electrode.
(xvii) Use of power junction boxes for cable terminations to be avoided to the extent
possible. Use of power junction box shall be under exception cases subject to Owner’s
approval.
(ii) Contractor shall ensure that the electrical equipment procured have type test
certificates. Type test certificates for HV and MV switchboards shall not be more than
five years old. In those cases where type test certificates are more than five years old,
contractor/manufacturer shall carry out the type tests at CPRI or any authorized testing
lab prior to dispatch of equipment with no commercial implication.
(iii) During fabrication, all the equipment shall be subject to inspection by owner/PMC or by
an agency authorized by the owner to assess the progress of work as well as to
ascertain that only quality raw material is used.
(iv) Routine and acceptance tests as listed in relevant Indian standard and equipment
specifications shall be conducted. Type test if listed in ITPs and in the relevant data
sheet shall be conducted. Type test, if specified, shall be conducted only on one of
equipment of each type and rating. These tests shall be carried out by the
Contractor/vendor/sub-vendor and shall be witnessed by owner/PMC or an agency
authorized by owner/PMC.
(v) Contractor shall ensure that the hazardous area equipments provided shall have the
necessary test certificates and valid CCOE approval certificates.
Sheet 87 of 93
Sheet 88 of 93
cn
0
900Z.Z 1.90
penssheu pue pas!neu Z 10Z•90'6Z
panss!-au pue pes!neu
cn
n
oca
O
Z Z1701-18-9
STANDARD SPECIFICATION NO.
et o .,; ct :,1 EF1' '--1 'c=. :=1 ri 1 'r1 ril C5 C7 C7 () (-) (-) r) tO co >.
<
1:st'D 'M ;
r; (-) :' 'H "1 trl 4 rl c) >. w
.i.-,
cr ro ,4n Hnnn 7:IHH H „.1 r- — w
-. .-1n r. rli
oo
o-: rri
.1
r) >
suo9mAaaqqv
444 4,-, 5- o o
• • • rri
. w 1L,
op CD r '' n »,R.
AD "
c (")
■
- 3 H
n - ('7-)t
n., rn (1)-r crc,cn
cn 1,)'-- ,+- (-) ,
-,
mos — - cn
''' -• - 00,-r FF',-'2.8 MEI, (...--]17Q
4grrig
, =.v)»0•ZL. ><-...,•
(
D 'o7'n ~n
r- crq,F1)'.- cn -,,
0
() i'S qg ''"DD .--t < '-•t
0 ='D c rri
C
p.) -
Cr cr
`r1 '''
~t
CD o..,
O 5 o nj •••■•
,n
Er •
-s.
a" 7C n
CD ‘• co
CD cn -' lw
cn"
cn 0 »-• CTI
-s an
n •(7Dr-
44 - CL 45'
C5 n
n '• .Z
CD
:,› 5
-cs ,,
cr'
-t n
0.
CD
n
-,.
7Jr17J'-c:i'-0 "1:Jzzz44 44
><-<csHHzle',
n—
:;)
.c. c .. 3 o,<D i ,,z) -o ,, ZZZ44 44
onn (..D.--....n$00(.2, .
f. 0 CD
CD DD
.4. r'''' 94
u,--- ., .z+ .1. i). s=1 po 'z' 't, g ,--s ...•
0 otnn n Oti
w ol.. cl. cl. n cn cl,
CD .- • 0 : '-'' nO
~t (
i.i ?2<''"<""PCLCI7
t•-.--t •
—cn-•
■
-ty....).-1. '.(). ,9- 2-pr-N4(.1 - •-•
ril.10H ''. ‹.
)
,-----
(1)
c,,., ,s2q*-1 (Detri nn (I) !W
Or) n!-1 (") .-1 (-)
,v)F-PHOaCDNDMS
Japio osup.md
A-
D
• •
O
pamasei sp.16!.1 IIV -113 ILI 6Odoo
Sheet 90 of 93
STANDARD SPECIFICATION NO.
adops o.i
0
w)
n
,-o
EOF INSPECTION
QUANTUM
Z CP
0
STAGE/ ACTIVITY CHARACTERISTICS SUB
.-.
0
ri
ril
SUPPLIER
.-,it
OF CHECK
SUPPLIER
■■:,
Procedures
•■
l
I
0
tvl
Material Inspection
...,,.
cn , y4.
-4,._. FO
cn CD
box,cables, fastenersand Calibrationchecks(asapplicable)
x
C)
C)
n
<, ''
I-•-•
o ,-,
,—,
l \ ..)
CD cp
•• •
.
bolts,copper flexible,
CL.
H
,,
,..,
insulators, dials,Scanners
and gaugesetc.
Z:=
(.›)
Inprocess Inspection
1■.,
C,
C '''
C)
Cl.,
x
X
trJ
Transformer Assembly
■
o
to
,—I
C fl
EOF INSPECTION
cA
o,r.)-,:i
QUANTUM
0 t"'
~
H
r)
ci)
cn
M
xr5
H
SUB
cn
STAGE/ ACTIVITY
ril
..-.
.-.so
r,
OF CHECK SUPPLIER
SUPPLIER
O
Final Inspection
Physical and dimensional check.
Measurementof windingresistance
Measurementof voltageratioand check of
voltagevectorrelationship
Measurementof impedancevoltage,short-
circuit impedanceand load loss.
"
. -.
5"
4
CD5 .
-1 ■-3
,5r
CD
CD 'S
0
s.....-, cn
CD
cn SW
cor) eDr)=
-
z
o
o
>.
—
o
—
i
■
e-r-
-,
cn
Separate—sourcevoltagewithstand test(HV
test)
Measurementof Insulation Resistance before
and after HVtest.
Induced overvoltagewithstand test
Onesample
Temperaturerise Inspectiontest
z
z
fromeach
i.)
Transformer(Special Test)
a
Noise Level Test records
type/rating
••• • •• • • •• •••• ••
Shortcircuittest
Impulse Withstand Test. Onesample
Inspectiontest
›zi
fromeach
i...)
1
records
DegreeofProtectionof Enclosure. type/rating
O
Painting
Visual, Packing list.
Properpackingtoavoid anydamage during Supplier' s
z
o
o
—
--
PaintingandPacking
.
transportation. records
Documentationand IC
c, o. z ci)
iN, — P
CIQ
O.
CD
5
-• o
••
•
STAGE/ ACTIVITY
00
st, .ct
Final Documentsubmission
CD CD
eD
t=0 CfC1 C2)
(-) n
O CD
--,-. CD
.-5 7G- S=1
,-r. '-C-) .
(''''D ■-■- ru
cn CD
cn
cn
‹-r-
■-t '"Z=I
• CD
...- .n
• -c
IC issuance
cr r--c • cp
•(i) co
cn
CD
n CD >
-c P-f.
cn
1-cl o
0
, o <I>
‘-<
cl. 'Fcr
per VDR / PR
cn cl.. G.
,-t- .--"t--
Reviewof Internal Test Reports.
o
CHARACTERISTICS
cl.
Po
■
-t AD
CL,
cn CD s=0
.-I fM
CD ■-r-
0 O
CD .-I
,-- .
co cn
0.
Compilationof Inspectionreports,drawings,etcas
CD ■c) 5
co
,-1 .--
-■-.
fMfM
co o
....
fM
c-, 0
0
(5
c) (:z,
cp'
O ''ti ro
Cr CD ro c:'
..,c:i: ...
QUANTUM
OF CHECK
C)
-. ro
o -.
po .n. ■
—•
,-,-4-• CD
0 Cl., C>
•
cn
~.
n
, 0 o
folder
0
Records /
,r-
Final data
Inspection
.-t ■-1
AD
g
/Completeness
Supplier' s Test
O c)
< -f
certificate
Certificate(IC)
n CD
a., o
ci. c)
o
o fM
• co .
,,.4-
SUB
•co cn C9 w
cn n
cn
AD (:■L. o
co
SUPPLIER
,-- ,-o
AD
o
0-
c'D
O x
-ci O
Ict
SUPPLIER
cr
Z'AallZP01-18-9
E OF INSPECTION
g,
patuom sp.161.1 IIV— 1131-16!-1h100
z
fM
fM ,'..5
STANDARD SPECIFICATION NO.