Date: 01.03.2023
Pre-Qualification Criteria
Item : VFDs for Captive Power Plant (350kW, 690V Motor)
Project : 1 x 120 MW PH#7 Unit of Captive Power Plant
Customer : IEL Jamshedpur
1. The vendor shall be an Original Equipment Manufacturer (OEM) of VFD Equipment. Only the
OEM can submit offers.
2. The vendor should have designed, engineered, manufactured, type tested or got type tested,
supplied and commissioned at least one (1) number of VFD system (of the type & model
offered) for feeding squirrel cage induction motor of 350 kW, 690 V or higher rating, which is in
successful operation for a period of at least one (1) year as on 01.03.2023. Necessary supporting
document shall be provided.
The Reference List of VFD supplies made giving the ratings, application, Details of the
customers, Year of supply and Commissioning status to be provided along with the offer.
3. The vendor or their authorized service representatives shall have trained engineers for
commissioning & service for the offered equipment and shall be in a position to provide prompt
after sales service and spares support for our installations. This service network shall necessarily
be available in India.
4. The vendor shall be in a position to undertake AMC or provide service support for the equipment
supplied, after the expiry of the warranty / guarantee period either directly or through a service
representative.
5. Technical clearance of vendor offer will be based on Customer acceptance of Vendor
Credentials.
Note:
a. Vendor must furnish all necessary supporting documents, as required, along with the bid to
satisfy Pre-Qualification criteria as specified above.
b. The Pre-Qualification criteria are mandatory requirements and the technical bids will be
evaluated only when the Pre-Qualification criteria are met.
Project location
1. Project Details
The information on this document is the property of BHARAT HEAVY ELECTRICALS LIMITED.
It must not be used directly or indirectly in anyway detrimental to the interest of the company.
2. Environment Specifications
.
REVISION 01 Date:18.01.2023 APPROVED BY
L SUBBALAKSHMI
Frequency Variation
5 Fault Level 40kA for 3 sec
6 Transformer Type Dry Type Transformer is being procured by
BHEL.
7 Distance between ~ 50 metres
Transformer and VFD panel
COPYRIGHT AND CONFIDENTIAL
C
P.S NO. : PS/445/2624
PURCHASE SPECIFICATION
REV. NO : 01
GROUP: T&PD/COE
A4 – 11 PAGE 03 OF 22
4. Motor Data
Tested Panel
6. VFD Specifications
2.9 2.9
Sl. No. Parameter Specification
1 Drive VFD for Forced Draft (FD) Fan - 4 nos
2 Input Voltage From Transformer in Section 3 above
3 Power/Torque vs Speed Torque α Speed2; Power α Speed3
4 Single Line Diagram See Attachment 3-661-00-00970 (Sheet no.2 ) for
The information on this document is the property of BHARAT HEAVY ELECTRICALS LIMITED.
FD Fan
It must not be used directly or indirectly in anyway detrimental to the interest of the company.
Filter, if required.
If Output filter is required, then the Cables
between VFD and filter shall be in VFD Vendor
scope.
Cable Glands, Lugs for the cable termination at
both ends of the filter shall also be supplied by
the vendor.
Output Voltage
DC Bus Voltage
Torque
Output Power (It shall be possible to display
power output of the drive in kW and
accumulated power over the time in kWHr)
Digital Input Status
COPYRIGHT AND CONFIDENTIAL
1) AC MAINS ON
2) AUXILIARY CONTROL SUPPLY ON
3) VFD READY
4) VFD RUN & BYPASS RUN
5) VFD FAULT/TRIP & BYPASS TRIP
6) EMERGENCY STOP ACTIVATED
7) EXTERNAL FAULT
8) VFD ACB ON
9) VFD ACB OFF
10) VFD ACB TRIP
11) BYPASS ACB ON
12) BYPASS ACB OFF
13) BYPASS ACB TRIP
P.S NO. : PS/445/2624
PURCHASE SPECIFICATION
REV. NO : 01
GROUP : T&PD/COE
A4 – 11 PAGE 12 OF 22
24 Protection
Following protections shall be built in within
the inverter and any other protection as
COPYRIGHT AND CONFIDENTIAL
required:
a) Motor Overload / Over Torque
b) Instantaneous Over current (This device
shall monitor the peak output current
continuously and shall provide instantaneous
shutdown without component failure
whenever its trip point is surpassed. The trip
point must be greater than or equal to 105%
of the VFD's rated full load output current)
c) Ground Fault Protection
d) Over Voltage/Under Voltage - VFD shall
be able to withstand >20% dip in supply
voltage for 2 secs without damage to
semiconductors or fuses.
e) Output Short Circuit
f) Output Phase Loss/Fuse Failure
g) Phase Sequence Protection
h) Input Phase Loss/Single Phasing Preventer
i) Over Speed
j) Heat sink over temperature/VFD Panel
Temperature High Stall prevention (During
acceleration, deceleration and constant speed
operation)
k) Loss of Cooling Fans
l) External faults
m) DC Link Overvoltage
P.S NO. : PS/445/2624
PURCHASE SPECIFICATION
REV. NO : 01
GROUP : T&PD/COE
A4 – 11 PAGE 13 OF 22
encoder or tachometer.
The drive shall have programmable V/F patterns
along with user definable custom V/F patterns.
26 Harmonic Limitations – Shall be as per latest IEEE 519 (Refer Clause 6.8.7
Source in page 31 of 48 of Customer specification).
Voltage Harmonics: Vendor to inform the values
with calculations during detailed engineering stage.
COPYRIGHT AND CONFIDENTIAL
27 Harmonics at VFD Output Shall be as per latest IEC 61800-4 (Refer Clause
/ Motor Input 6.8.6 in page 31 of 48 of Customer Specification).
Vendor to specify the maximum amount of voltage
and current harmonics at the VFD Output / Motor
Input terminals.
the motor:
It must not be used directly or indirectly in anyway detrimental to the interest of the company.
1. Start
2. Stop
3. Emergency Stop
4. Speed Increase
5. Speed Decrease
n) Switch:
1. Local/Remote Selection (with key)
o) Indications:
1. VFD mode
2. Bypass mode
3. VFD Fault
4. VFD Ready
5. VFD Running
6. DOL Start Permissive
p) 20% Spare terminals shall be provided
C
P.S NO. : PS/445/2624
PURCHASE SPECIFICATION
REV. NO : 01
GROUP : T&PD/COE
A4 – 11 PAGE 18 OF 22
v
Sl. No. Parameter Specification
34 Laptop & Software for Laptop shall be installed with Latest
Computer Interface Compatible Licensed Operating System. The
(as per Clause 6.7 in page software must be loaded in the laptop &
30 of 48 of Customer VFD supplied along with interconnecting cables
specification) and accessories required for interface with the
The information on this document is the property of BHARAT HEAVY ELECTRICALS LIMITED.
drive.
It must not be used directly or indirectly in anyway detrimental to the interest of the company.
3. Laptop 1 No.
It must not be used directly or indirectly in anyway detrimental to the interest of the company.
8. Documentation
Sl. No. Parameter Specification
1 Attached Documents a) Customer specification for VFD System
GSP-01-00-00-08-000-00l-R3
b) Single Line Diagram: 3-661-00-00970
c) Datasheet for VFD
d) Sub-vendor list of Customer
e) Pre-Qualification Criteria (PQC)
2 Technical Information a) Dimensional Drawing of Panels along with
required along with Offer minimum clearance to be maintained for effective
cooling, and Weight
b) Technical Catalogue of VFD System being offered
c) Reference list for similar rating VFDs giving the
following: Model number, Application, Rating, Year
of supply and commissioning.
C
4 Technical (unpriced) and Refer sheet no. 20 of 22. Unpriced and Priced
COPYRIGHT AND CONFIDENTIAL
Commercial (priced) Bids – bids for Sl. Nos. 7(1), 7(2), 7(3) and 7(4).
For Bid Evaluation
5 Information required for a) Dimensional Drawing of Panels along with
Customer / Consultant minimum clearance to be maintained for
Approval (after placement of effective cooling, and Weight
Purchase Order) b) Schematic Diagram
c) Bill of Materials for equipment to be
supplied
d) Feeder Requirements for UPS supply
e) Losses at Rated Load (including Fans)
f) Heat Loss for Air Conditioning System
sizing
g) Technical Catalogue of VFD System being
offered
h) Test Protocol and Quality Plan.
i) Type test certificates of similar or higher
rating equipment
j) Filled up Data sheet for VFD system
C
A4 – 11
GROUP : T&PD/COE
PURCHASE SPECIFICATION
C
PAGE
(INDICATIVE)
REV. NO : 01
22
OF
P.S NO. : PS/445/2624
22
VFD DATASHEET IEL-FD
PURCHASE SPECIFICATION
REV. NO: 01
GROUP: T&PD/COE
A4 – 11 PAGE 01 OF 04
A Environment Specification
1 Maximum Ambient Temperature 45°C
2 Minimum Ambient Temperature 5°C
3 Equipment Design Temperature (IS-9676) 40°C
The information on this document is the property of BHARAT HEAVY ELECTRICALS LIMITED.
E VFD Data
1 Manufacturer
2 Model No.
3 Manufacturing Location address
4 Rating
5 Protection class IP42
6 Applicable codes /standards
7 Speed reference 4-20 mA from DCS
8 Speed range
COPYRIGHT AND CONFIDENTIAL
9 Switching Frequency
10 VFD Control Location VFD, LCS & DCS
11 No. of Pulse 6
Input Transformer Rating (Transformer in BHEL
12 750KVA, 6.6kV/725 V
scope)
13 Drive Output Voltage 690V
14 Overload capability
i)110% 60 secs.
ii)150% 30 secs.
iii)Inrush current 250% In for
15 Harmonics at VFD Input
16 Harmonics at VFD Output
17 VFD efficiency at:
i) 100% Load
ii) 75% Load
iii) 50% Load
iv) 25% Load
C
v) Paint shade
vi) Heat output of Panel (kW)
vii) Busbar Material Electrolytic grade tinned copper.
20 Acceleration time
21 Deceleration time
The information on this document is the property of BHARAT HEAVY ELECTRICALS LIMITED.
23 AC Output :
i) Output Voltage range
ii) Voltage Accuracy
iii) Frequency range
iv) Frequency accuracy
COPYRIGHT AND CONFIDENTIAL
i) Make
ii) Type
iii) Model No
iv) Cont Current Rating
v) Short Circuit Rating
vi) Rated Voltage
vii) Applicable Standard
VFD DATASHEET IEL-FD
PURCHASE SPECIFICATION
REV. NO: 01
GROUP: T&PD/COE
A4 – 11 PAGE 04 OF 04
i) Make
ii) Type
iii) Model No
iv) Cont Current Rating
v) Short Circuit Rating
vi) Rated Voltage
vii) Applicable Standard
viii) Panel details
- Overall Length
- Height
- Depth
- Degree of protection
I Auxilary Power requirement
(UPS Supply etc)
i) KW
ii) Voltage
C
VFD VENDOR'S SCOPE
General Specification for AC Motors, Drives & Control Cabinets
6.3 Where group AC drives system is considered, each group shall control a
technological group of motors through voltage source inverters. For each
group, common DC Bus (copper) fed individual vector controlled
regenerative type (4-quadrant operation) PWM IGBT or IGCT based
inverters shall be considered for individual motors of the group. Non-
regenerative type line side common converter (6-pulse or as specified)
with diode rectifier or half-controlled bridge with IGBTIIGCT may be
considered with suitable dynamiC braking, for the applications requiring
regulated braking, through chopper circuit by monitoring the DC bus
voltage in case the energy recovery is not appreciable considering the
operational philosophy as specified in the Technical Specification.
However, regenerative type common converter (6-pulse) using IGBT
IIGCT may be adopted in case the energy recovery by regenerative
braking is appreciable. In such case proper care shall be taken for
regenerative mode of operation to avoid device failure while delivering
power to the bus. The converter shall be capable of maintaining rated
DC voltage at all values of load current including short time service
current rating at 90% rated AC voltage considering incoming voltage
fluctuation of up to +1-10%. Isolation 1 converter transformer of suitable
rating shall be considered for feeding each common converter supplying
the inverter groups through DC link.
?
General Specification for AC Motors, Drives & Control Cabinets
6.6 The power semiconductor devices shall be selected such that more than
one cell may be connected in parallel but only one cell shall be provided
in series. Adequate safety factor for withstanding reverse voltage shall
be considered for power circuit semiconductor devices. For group dive
with DC link, each inverter section shall be provided with disconnecting
device with semiconductor fuses at the line side. If not otherwise
specified in technical specification, motorised isolating device or
contactor depending on the load of motors shall be considered in the
motor circuit for isolation. Also the devices shall be selected considering
the ambient temperature outside the panel as well as the specified
overloads 1 trip setting. Number 1 type of devices shall be kept as
minimum as possible.
6.7 Microprocessor based digital regulation and control shall be provided for
precise speed and torque control. The adjustment of system variables
and the modification of the control blocks shall be achieved through user
friendly software. Basic parameter programming, drive diagnostics and
troubleshooting shall be possible from built-in panel door mounted
console. Separate indications of salient parameters on panel shall be
provided.
6.8.1 The system shall be energy efficient, designed as standard product and
shall provide very high reliability, high power factor, low harmonic
distortion and low vibrationl wearl noise.
6.8.2 The system shall be designed to deliver the motor input current and
torque for the complete speed torque characteristics of the driven load
with input supply variation of +1-10% and frequency V,&L'
q,f +1-5%. It
GSP-Ol-00-00-08-000-001-R3 '" 30 of 48
Confidential. ©2016 TATA Steel Limited, All rights reserve'"
General Specification for AC Motors, Drives & Control Cabinets
6.8.3 The drive system shall be designed to operate in one or more of the
following operating modes as to suit characteristics of the driven
equipment:
(iii) Constant power over a specific speed range where the torque
decreases when speed increases.
6.8.4 Drive controller shall meet the following based on the applications:
(ii) Full, closed' loop flux vector control shall be available for constant
torque applications.
(v) Suitable for use on both constant torque & variable torque loads.
6.8.5 The drive controller shall be equipped with microprocessor based digital
regulator with programmable functions. The power control regulator logic
shall provide for an acceleration/deceleration current limit curve and shall
be capable of field be separately programmable from 0.1 to 20 seconds.
6.B.6 The Total Harmonic Distortion (THO) of the voltage and current at
inverter output shall be as per IEC 61800-4 and it shall be considered in
the design of the drive system.
6.B.7 Harmonics at the supply side of the drive system at primary of the main
input transformer shall be restricted within the maximum allowable levels
of current and voltage distortion as per recommendations in the latest
edition of IEEE-519.
6.B.8 Overload capability of the inverter units shall match with that of the
motors. However, minimum overload capacity of the drive applies to the
rated speed range and unless otherwise specified in Technical
Specification, shall be over a duty cycle with minimum capabilities
defined as: 110% of the rated ,current for 1 minute, 30 seconds at 150%
.n.!!!£4!! .•
General Specification for AC Motors, Drives & Control Cabinets
6.8.9 Efficiency shall be More than 97% or better at full speed and full load
state regulation of (+1-) 0.25% guaranteed against 100 to 200% load
disturbance and + 5% & -5% input supply frequency variation.
The drive should be designed to operate on an AC supply, which may
contain line notching, and up to 10% harmonic distortion.
Operating ambient temperature range without de-rating.: 0° C to 40° C
6.8.10 The drive shall trip in case the speed exceeds 105% of the maximum
operational speed or reduces to 95% of the minimum operational speed
for more than 10 second.
6.8.11 Maximum noise level from the drive at 1 meter distance, under rated
load with all normal cooling fans operating shall not exceed 85dBA.
(a) Harmful VFD induced harmonics which can create motor heating
are eliminated.
6.8.15 It shall be possible to vary the speed of the drive in either manual or auto
mode.
6.8.16 Auto/manual selection shall be from VFD panel as given below unless
otherwise specified:
(i) With the selector switch in "manual" mode, the operator shall be
able to set the speed through keypad, mounted on front of the drive
panel or from speed increase/decrease push buttons or
potentiometer from the field (or as specified in technical
specification).
(!i) With selector switch in "auto" mode, speed of the motor shall be
controlled from PLC/DCS system.
6.8.17 The required provision for the interface, hard wired and / or
communication network, with remote plant PLCIDCS shall be considered
as per technical specification.
6.8.18 Faults, not limited to the following, shall be detected, annunciated and
protective measures shall be initiated accordingly if not asked otherwise
in the Technical Specification:
(i) Power supply & Converter Transformer (if used) faults: Line
side faults - SIC, OIC, ON, UN; Transformer winding temperature
(High - warning & trip)
(ii) Drive faults: Fuse blown, cooling fan stop, device over temperature,
DC bus faults, instant OIC, overload, stall detection, shoot through,
earth fault in motor circuit
(ii) Others: Control power failure, sync. Power failure, CPU failure,
speed detection abnormal, speed/voltage relationship abnormal,
control cubicle over-temperature.
Separate indication on the panel shall be provided for the line side
current, voltage and output DC voltage for converter and output load
current for the inverters apart from other standard displays if not
otherwise specified in the Technical Specification
GSP-Ol-OO-OO-Q8-000-001-R3 P
Confidential. ©2016 TATA Steel Limited, All rights reserved
General Specification for AC Motors, Drives & Control Cabinets
6.8.20 AC drive system shall conform to IEEE, IEC 61800-2 and equivalent
international standards.
6.9.1 The panel shall include suitable semi conducting power devices
(DiodesIlGBT) modules with protective devices, reactors (if required),
filters (if required), control circuit, control accessories, indication and
annunciation etc. The construction of the panel shall provide effective
protection against electromagnetic emissions and shall meet design
requirement of integrated standards.
6.9.2 The drive shall be housed in sheet steel panels fabricated with minimum
2mm thick CRCA sheet steel, if not specified otherwise. The panel shall
be suitable for indoor installation, if not otherwise specified. The panel
shall be free standing with degree of enclosure protection as IP-42 &
above. However, if VVVF drives with microprocessor based regulation
and control equipment are located in air-conditioned rooms with 35°C,
these shall be designed for 40°C ambient or as specified in technical
specification. Separate drive programming and diagnostic terminal where
provided shall generally be located in air-conditioned control room
having 25°C ambient.
6.9.4 Bolted un-drilled gland plate (minimum 3mm thick) shall be provided at
bottom. Clamp type terminals shall be used for connection of all wires up
to 10mm2 and terminal for higher sizes shall be bolted type suitable for
cable lugs. Minimum space for power cable termination shall be 600mm
clear from bottom of the cable gland plate.
6.9.5 Bus bars shall be of electrolytic copper, colour coded separately for AC
and DC system. All the live parts shall be sleeved I shrouded to ensure
complete safety to personnel intending to carry out routine inspection by
opening the panel doors. All the equipment inside the panel and on the
doors shall be provided with suitable nameplate.
6.9.6 All the switches, component and accessories which are essential for
normal and emergency operation shall be mounted on the door and shall
be operable externally. All the analog instruments, where provided, shall
be switchboard type, back connected; 72x72mm.Scale shall have red
mark indicating maximum permissible operating rating. Digital indicating
meters shall preferably be used.
6.9.7 Each panel shall be provided with illuminating lamp/11W CFL with switch
and fuse. 5/15A, 240V power socket with switch and fuse shall be
provided. Each panel shall have space heater with ¥I{~tch fuse and
variable setting thermostat. ,l.."'......c ~h
GSP-OI-00-00-08-000-001-R3 34 of 48
Confidential. ©2016 TATA Steel Limited, All rights rese
General Specification for AC Motors, Drives & Control Cabinets
6.9.8 Copper earth bus of min. 50x6 mm size shall be provided in the panel
with provision for connection to secondary earth grid. All the non-metallic
components/parts shall be connected to the main earth bus bar.
Separate earth bus bar and stud for electronic control system, if
required, shall be provided.
6.9.9 All the metal parts shall be treated so as to ensure efficient anti-corrosive
protection. Hard wares shaH be zinc passivated or electro galvanised.
Panel enclosure and structure supports shall be thoroughly cleaned and
degreased to remove mill scale and rust etc. External surface shall be
painted Siemens grey (RAL - 7032) with two coats of synthetic enamel
paint.
6.9.10 All panels shall be of same height so as to form a uniform line-up, to give
good aesthetic appearance.
6.9.11 Power and control wiring shall be segregated and 20% spare control
terminals shall be provided. All the control wiring shall be enclosed in
plastic/metal channel. Each wire shall be identified at both ends by self-
sticking wire marker tapes of PVC ferrules. All wires shall be ferruled and
terminals shall be properly numbered.
6.9.12 All electronic modules and components shall be accessible from front of
panel only. Modular assemblies for both the system control electronic
equipment and power electronic equipment shall be used. All low voltage
compartment and cabling shall be electrically and physically separated
from the high voltage compartment. DC link capacitor and pre charging
and discharging circuit shall be preferably mounted in the rear of the
panel. Suitable removable type hooks shall be provided for lifting the
panel. Perspex type transparent insulating material shall be used for
covering live compartments.
6.9.13 Drive keypad, operator control panel required for control, monitoring and
measurements shall be supplied and installed outside the panel on the
front door. It shall be accessible for operation without opening the front
door and shall be non-removable type.
6.9.14 All the equipment shall be complete with cable glands, lugs etc. and
cable glands shall be single or double compression type for indoor and
outdoor eqUipment respectively.
6.10 COOLING
6.10.1 The drive panel shall be naturally cooled type as per manufacturer's
standards. If unavoidable, forced type cooling system shall be provided.
Cooling system shall include well-dimensioned panel, adequate cooling
airflow path, and module cooling fan and if necessary, panel-cooling fan
shall be considered. Cubicle cooling fans' speed shall preferably be
limited to 1500 rpm. All louvers provided in the cubicle will have fine wire
mesh. Noise level shall be limited to international norm. Necessary
starters shall be provided within the VFD panels for the ventilation fans
and shall be interlocked with drive and
GSP-Ol-00-00-08-000-001-R3
Confidential. ©2016 TATA Steel Limited, All rights reserved
General ,n<'rifiir"tinn for AC Motors, Drives & Cor'ltrol Cabinets
control philosophy. MCB for motor space heater, auxiliary power supply
if required for local panel, drive panel space etc. shall be included and
mounted in easy accessible location.
6.11.2.1 The static power shall consist of a line side power converter for operation
as a rectifier and a load side power converter for operation as a fully
controlled inverter. Power converter shall be fast switching, most efficient
and low loss type. For inverters and controlled converters, IGBT / IGCT
shall be considered. All power converter devices shall include protective
devices, Snubber networks and dv/dt networks as required. The current
rating of the converter's semi-conductor components shall not be less
than 120% of the nominal current flowing through the elements at full
load of the VFD through the whole speed range. All power diodes shall
be of silicon type with minimum Vbo rating as 2.5 times the rated
operating voltage.
6.11.2.2 Adequate short circuit and over voltage protection shall be provided for
the converter and inverter system. The power converter circuit shall be
designed so that motor can be powered at its full nameplate rating
continuously without exceeding its rated temperature rise due to
harmonic currents generated by the inverter operation. The conversiOn
devices and associated heat sinks shall be assembled such that
individual devices can be replaced without requiring the use of any
special precautions/tools. The cooling system of the electronic
components, if provided, shall be monitored and necessary alarms shall
be provided to prevent any consequential damage to the power control
devices.
6.11.2.2 Offered system shall also take in account the distance between drive
panel and motor and the drive system shall include all material and
accessories to be suitable for a distance of 350m.
GSP-01-00-00-08-000-001-R3 60f48
General Specification for AC Motors, Drives & Control Cabinets
6.11.3 DC Link Reactor: Smoothing reactors for the DC link shall be designed
to sufficiently decouple the rectifier and inverter portion of the converter
and to limit fault currents in this circuit. Unless otherwise specified, the
reactor shall be dry type, air cored, air-cooled or fan cooled type located
within the panel.
6.11.5 Operator Control Panel: Each drive shall be equipped with a froAt
mounted operator control panel consisting of a backlit alphanumeric
display and a keypad with keys for parameterization and adjusting
parameter which shall be· limited to Start/Stop, Local/Remote,
Auto/Manual, Increase/Decrease, menu navigation and protection and
measurement parameter selection, etc.
7.1.1 All push buttons and illuminated push buttons shall be of sturdy desig n of
22.5 mm diameter and suitable for all types of control circuits. The
components shall conform to IS: 13947 for their mechanical and
electrical design features. Modular contact blocks and actuators shall be
adopted so as to have any desired arrangement of contacts. The contact
design shall be such as to provide enhanced contact reliability required in
circuits with electronic interfaces involving low voltage and small value
currents.
7.1.2 Shrouded arrangement shall be provided for 'Start ' application, "Un
shrouded 'arrangement for Stop' application, 'Mushroom' arrangement for
- Emergency Stop' application and key type arrangement for "Lock-out'
application. Each push button shall be provided with minimum 2 NO & 2
NC contact.
GSP-OI-OO-OO-08-000-001-R3 Pa
ConfidentiaL ©2016 TATA Steel Limited, All rights reserved
General Specification for AC Motors, Drives & Control Cabinets
7.1.3 Control and selector switches shall be of sturdy design with modular
construction comprising a number of switching elements operated by a
single shaft and shall have suitable position indicator s to show that the
switch is in the selected position.
7.3.1 Non-contact type limit switches shall only be provided as far as possible.
Contact type limit switches, where provided, shall be of robust
construction capable of withstanding repetitive operation and housed in
cast metal-clad dust and oil tight enclosure, conforming to IP65. The limit
switches shall have high mechanical endurance exceeding Class 10 and
suitable for heavy-duty operation. Contacts shall be adequately rated to
handle inductive currents in the circuits and shall be of design suitable
for electronic interfaces as mentioned above. The limit switches shall be
provided with actuators in the form of plungers, roller tappets, push-
rollers, roller levers, as required. These actuators shall be operated by
means of actuating bars, cams, stops etc.
7.6.2 Linear position transducer with detector unit shall be provided for
accurate detection of linear position or displacement. It shall basically
comprise a scale rod mounted on movable object and a head mounted
on a stationary member of the machine. The unit shall be housed in mild
steel or non- magnetic metal case for protection against dust, water as
well as stray magnetic field. It shall also have provision for air- purging.
The transducer shall be provided with necessary cable connectors and
cables of adequate length as required to connect it with the evaluation
electronics unit.
7.7 RESISTORS:
7.7.1 The resistors provided for motor starting and control shall be suitably
rated for the starting conditions. The current carrying capacity of the
resistors shall be so selected that the temperature rise shall not exceed
375 degree C.
.. t!!?!SS E?!?!!!
General Specification for AC Motors, Drives & Control Cabinets
7.8 Legend Plates for Push Buttons, Lamps: Anodised aluminium legend
plates shall be provided for all push-buttons, control switches, pilot lamps
etc. with following standard marking. Other markings shall be provided
as required.
8.1 Requisite type and number of operators control desks and local
operator stations/posts shall be provided for proper control and operation
of the plant. The operation shall generally be carried out from HIVII with
local control box for maintenance to be located near the respective
equipment.
8.2 Control desks where specified shall be free standing, floor mounted or
pedestal mounted based on the type of operator control required. Control
desks shall comprise sturdy frame work with hinged sloping top, bolted
sides, front and rear covers fabricated from 2.5 mm thick CRCA sheet
steel with proper painting and finish. The front side shall generally
provide access to the terminal blocks and shall be provided with hinged
doors. The bottom of the desk shall have removable cover plate to
facilitate drilling of holes for cable entry as required during installation.
Neoprene rubber gasketing shall be provided to all doors and hinged top
plate. Enclosure protection shall be IP-31 (min) in control rooms and IP-
54 for indoor shop floor installation and IP-55 with canopy for outdoor
installation.
8.3 Layout of the desk sections as well as the devices on the desks shall be
ergonomically designed to provide maximum operator's comfort as well
as un-hindered view of the controlled equipment, where called for. Apart
from the normal components of control desks like push buttons, selector
switches, indicating lamps etc., other equipment such as PC based
operator's terminals, printers, intercom equipment, CCTV control etc.
shall also be located on desk in control room, as applicable. The physical
dimensions and the desk design shall be so engineered as to ensure
effective utilisation and efficient layout of the operator devices.
8.4 The desk shall be factory assembled and fully wired. The internal control
circuit wiring shall be with 1100 V grade single-core, multi-strand PVC
cable with copper conductors having minimum size of mm and
conformin to IS:694. All out oing connections shall J§ ~c ut to
GSP-Oi-00-OO-OB-000-00I-R3
Confidential. 102016 TATA Steel Limited, All rights reserv
Annexure-1 of COEM office oreder no.COEM/27/T 87/2019, 24th May 2019
3 THRUSTER BRAKE (GENERAL APPLICATION) SVENDBORG / STROM KRAFT / KAKKU / SIBRE / SIME-France
4 D.C.E.M BRAKE (GENERAL APPLICATION) BCH / STROM KRAFT / ELEKTROMAG / KAKKU / ELECTROMECH / EPC / IS
RAYCHEM - RPG / SIEMENS / ABB (HIVELM acqired by RAYCHEM RPG and ELPRO by
18 132KV DISCONNECTING SWITCH
SIEMENS)
19 LIGHTENING ARRESTERS for 132kV system. ELPRO / CGL / ALSTOM/ SIEMENS ( Aurangabad)
20 132KV CT - Dead Tank ABB (Imported) / BHEL / ALSTOM (Imported) / ALSTOM (India with European design)
22 132KV CVT (PT SHOULD NOT BE USED) ABB / BHEL / Alstom ( India) / Siemens ( Aurangabd)
Page 1 of 12
S No. Item Vendors Comments
24 HV and EHV INSULATOR. ELPRO / ALSTHOM / BHEL / JSI (Jai Shree Industries)
ABB India (33 KV & 132 kV), ALSTOM Europe, Siemens (Aurangabad for 132 KV), Siemens
28 132kV/33kV GAS INSULATED SWITCHGEAR
(Goa for 33 KV), Alstom India for 132 KV ( 33 KV not being manufactured in India)
SIEMENS (Model-3TL8 or any other newer model after this like NX-AIR etc is not
6.6/11 kV VACCUM CONTACTOR WITH SHUNT TRIP
34 acceptable)
MECHANISM
/ ABB- only Unigear with Permanent Magnet drive / L&T
35 6.6/11 KV CT/PT KAPPA / ABB / BHEL / PRAGATI / PROYOG / NARAYANA POWERTECH, Vadodara.
LIGHTING TRANSFORMER/AUX. TRANS. -UP TO 500 KVA TRANSO INDIA / INDUSREE / VOLTAMP / RAYCHEM RPG / KALPA / ADROIT / ANU
37
(DRY TYPE) ELECTRICALS
Page 2 of 12
S No. Item Vendors Comments
OIL TYPE POWER TRANSFORMER > 31.5 MVA OR voltage > ABB / BHEL / ALSTOM (Naini &Vadodara) / SIEMENS Mumbai
41
33 KV TBEA / Transformers & Rectifiers (India) Ltd.
RESIN CAST POWER TRANSFORMER –up to 2.5 MVA and KEC (Kirloskar Electric Co.) / BHEL / VOLTAMP / Raychem RPG,Pune / ABB / Esennar,
42
voltage up to 11 kV Hyderabad.
52 Air circuit Breaker, 690 Volts of any current rating. SIEMENS / SCHNEIDER ELECTRIC / ABB
Page 3 of 12
S No. Item Vendors Comments
LT PANELS AND ACCESSORIES FOR MINES (DGMS MINE LINE / ELECTROTECHNICA / PRABHU SWITCHGEAR PVT.LTD / ABC ELECTRICAL
58
APPROVED) PVT.LTD
LINE DIFFERENTIAL PROTECTION RELAYS (for 132kV /33kV SCHNIEDER-Micom P521, ALSTOM-Micom P541 / P542 / P543
63
/6.6 kV/3.3kV Voltage level) ABB-RED 670/ SIEMENS-7SD80
Page 4 of 12
S No. Item Vendors Comments
101 CRANE DUTY POWER CONTACTOR SIEMENS / BCH / C&S(TM) / L&T / EATON
TERMINAL BLOCK
110 WAGO / PHOENIX / SCHNEIDER-TELEMECHANIQUE/ CONNECTWELL / ELMEX
(POWER, CONTROL, & INSTRUMENT)
Page 7 of 12
S No. Item Vendors Comments
119 HT AC MOTOR (200KW-1000KW) BHEL / CGL / ABB / KEC / WEG ( India & Brazil) / SIEMENS / TMEIC
120 HT AC MOTORS (above 1000 KW - 3000KW) BHEL / CGL / ABB / WEG ( India & Brazil) / SIEMENS-upto 2.5 MW / TMEIC
SYNCHRONOUS & SQUIRREL CAGE MOTORS ABOVE BHEL / SIEMENS GERMANY / ABB FINLAND / HITACHI JAPAN / WEG ( India & Brazil) /
121
3000KW. ABB India
124 LT AC MOTOR (FLAME PROOF) KEC / SIEMENS / CGL / MARATHAN / BHARAT BIJLEE
125 INVERTER DUTY AC MOTOR UP TO 690 VOLT ABB / SIEMENS / MARATHAN / KEC / BHARAT BIJLEE
135 LED LAMP (Panel mounted indication lamp only) BINAY / SCHREIDER-TELEMECHANIQUE / GE INDIA / BCH
Page 8 of 12
S No. Item Vendors Comments
136 LIGHTING FIXTURES (GENERAL PURPOSE) PHILIPS / BAJAJ / CROMPTON / GE / HAVELLS / SURYA
137 LIGHTING FIXTURES (INCREASED SAFETY & FLAME PROOF) PHILIPS / BAJAJ / CROMPTON / GE / HAVELLS
138 CRANE POWER CONDUCTOR ACESSORIES IMSS / INT ENGG / AGMECH / VARIETY / EMERALD
139 CRANE POWER INSULATOR ASSEMBLY IMMS / UIC / INT ENGG / AG MECH / VARIETY / EMERALD
140 DOUBLE GIRDER EOT CRANE (CRITICAL APPLICATION) TGS / WMI / MUKAND / HITACHI
141 DOUBLE GIRDER EOT CRANE (GENERAL PURPOSE) TGS / WMI / MUKAND / HITACHI / FAFECO-MUMBAI / JESSOPH-Kolkata
142 SINGLE GIRDER ELECTRICALLY OPERATED & JIB CRANES ARMSEL / MME / VOLTAS / PLICARE
146 VIBRATING MONITORING SYSTEM SCHENCK AVERY / FORBES MARSHALL / BENTLEY NEVADA
147 PULL CHORD & BELT SWAY SWITCH AG SYSTEM / JSI / JAI BALAJI / PB / IS / PROTOCONTROL
148 SOLID STATE ANNUNCIATOR APLAB / L&T / PROCON / MINILEC / CONTROL & DYNAMIC
152 MICRO PLC MITSUBISHI / WAGO / MOELLER / LOGO / ROCKWELL / GE FANUC / SCHNEIDER
ABB (PROCESS PORTAL) / SIEMENS (WIN CC) / ALLEN BRADELY (RS VIEW) / I FIX /
155 HMI SOFTWARE
SCHNEIDER (WONDERWARE / CITECT) / HONEYWELL (EXPERION)
Page 9 of 12
S No. Item Vendors Comments
157 OPERATOR PANELS ABB / SIEMENS / ALLEN BRADELY / MODICON / HITACHI / GE FANUC / MITSUBISHI
Page 10 of 12
S No. Item Vendors Comments
170 FLEXIBLE CABLE UNIVERSAL CABLES / POLYCAB WIRES /APAR INDUSTRIES / SKYTONE / KEI,BHIWADI
174 CABLE GLAND FOR HAZARDOUS AREA BALIGA / DOWELLS / ELECTROMEG / HEX
175 CABLE GLANDS ELECTROMEG / DOWELLS / Metal Craft Industries Rajkot / HEX
177 PILCA CABLE STRAIGHT THROUGH JOINT KIT UP TO 6.6 KV RAYCHEM-HEAT SHRINK HVS SERIES
XLPE STRAIGHT THROUGH JOINT KIT > 1.1 KV AND UPTO 6.6
182 3M-COLD SHRINK (IMPORTED) I RA YCHEM ' HEAT SHRINK EPKJ / MXSW SERIES
KV
XLPE STRAIGHT THROUGH JOINT KIT > 6.6 KV AND UPTO 33
183 RAYCHEM-HEAT SHRINK EPKJ /MXSW SERIES / 3M COLD SHRINK (IMPORTED)
KV
Page 11 of 12
S No. Item Vendors Comments
189 TRANSMISSION LINE HARDWARE AND YARD ACCESSORIES Supreme Industries / Transmission Line Products
192 O/H Transmission Line Conductor Diamond Cable / Sterlite Cable / Gupta Power Ltd.
Page 12 of 12
Annexure-2 of COEM office oreder no.COEM/27/T 87/2019, 24th May 2019
Note : If vendor category is not mentioned in the Purchase Requisition, RFQ shall be sent to both Category A & B Vendors.
1.6 MOLTEN STEEL TEMP. SYSTEMS Electro–Nite / Ardee Business Rungta Pyro Instruments
1.7 MOLTEN STEEL OXYGEN SYSTEMS Electro–Nite / Ardee Business Rungta Pyro Instruments
2 INSTRUMENTATION CABLES
2.2 LANCE CABLES MINERAL INSULATED Ardee / Tempsens/ Pyroelectric Instruments Goa Rungta Pyro Instruments
2.3 INST. CONTROL / SIGNAL CABLES Cords Cable/ Udey Pyrocables/ Special Cables Thermocables
Page 1 of 6
S.No Item Categotry 'A' Vendors Category 'B' Vendors
3 GAUGES
GE Gauges/ Oyster Enterpreneurs/
3.1 PRESSURE GAUGES Wika/ Waaree/ Forbes Marshall/ Hydac / Rexroth Pyroelectric Instruments Goa/ GIC / Sree
Guru
3.2 TEST PRESSURE GAUGES Burdenberg/ Odin/ Wika/ Scandura Waree
3.3 TEMPERATURE GAUGES Wika/ Waaree/ Forbes Marshall/ Pyroelectric Instruments Goa GE Gauges/ Oyster Enterpreneurs/ GIC
4.4 FLOW SWITCHES Switzer/ Indfoss/ Levcon/ Endress &Hauser / IFM Waree/ D K Enterprises
5.1 GENERAL SWITCHES Switzer/ Levcon/ Nivo Controls/ Magnetrol D K Enterprises/ V Automat/ Kobold
PT & DPT
6.3 Endress & Hauser(European Origin)/ Yokogawa SIEMENS
(Foundation FieldBus &Profibus)
Page 2 of 6
S.No Item Categotry 'A' Vendors Category 'B' Vendors
7 VIBRATION SENSOR & MONITOR Bentley Nevada/ Schenk Avery/ Sherman/ Chemtrol Shinkawa( Forbes Marshall)
8.1 MAGNETIC FLOW METERS Yokogawa/ Endress &Hauser/ ABB/ Emerson Rosemount Krohne/ Burket (Germany)
8.2 VORTEX FLOW METERS Yokogawa/ Endress &Hauser/ ABB/ Emerson Rosemount Krohne
8.4 ULTRASONIC FLOW METERS Emerson Rosemount/ Yokogawa/ Endress & Hauser Krohne
8.6 ORIFICE PLATES/ NOZZLES/ VENTURIES Engineering Specialities/ Mechanical Engineers/ Emerson/ GIC Oyster Enterpreneurs/ Marc/ Unicontrols
9 PANEL INSTRUMENTS
9.1 SINGLE LOOP PID/ ON-OFF CONTROLLERS Invensys (Foxboro)/ Honeywell/ Eurotherm/ ABB/ Moore(Forbes Marshall)/ Yokogawa Masibus
9.7 POWER SUPPLY (24 VDC) Phoenix/ Masibus/ Siemens MTL Instrumentation Ltd.
12 FLAME DETECTOR Honeywell / Durag/ Fire eye/ Krom Schroder Industrial Research Associates/ COEN
13 ANALYSERS
Page 3 of 6
S.No Item Categotry 'A' Vendors Category 'B' Vendors
13.5 CALIBRATION GAS FOR GAS ANALYSERS Inox Air Products/ Bhorukha Gases Limited/ BOC/ Praxair -
GENERAL SERVICE CONTROL VALVES WITH Neles-Jamesbury / Instrumentation Limited/ Fisher Xomox/ Arca Controls/ Flowserve/ Samson/ Fouress Engineering/ Deltech/
14.1
DIAPHRAM ACTUATORS Valtek/ Adam/ Metso (Neles&Jamesbury)/ Dresser Masonelien Koso/ Dembla Valves/ Copes Vulcan
14.2 OXYGEN SERVICE Severn Glucon/ Arca (Germany)/ Metso(Neles Jamesbury)/ Valtek(Flowserve) Bailey/ Masoneilan
CONTROL VALVE WITH QUARTER TURN
14.3 Virgo/ Fisher Xomox/ Deletch/ L&T Kenetrol/ Keystone
ACTUATOR
14.7 POWER CYLINDERS Instrumentation Ltd./ Schrader/ Norgen/ Rotex OM Controls / KAT Instrumentation
14.8 ELECTRICAL ACTUATORS Limitorque (I) Ltd./ Auma India Limited/ Beacon Rotork Marsh
14.9 I/P CONVERTERS Emerson Rosemount/ Yokogawa/ ABB/ Watson Smith/ Moore MTL Instrumentation Ltd.
14.10 SOLENOID VALVES Asco/ Schradder/ Norgen/ Rotex/ Burket (Germany) Festo/ Avcon Controls
14.13 BUTTERFLY VALVES Instrumentation Limited / Metso/ Fisher Xomox/ Virgo(Stafford)/ Intervalve/ Masoneilan L&T/ BDK/ Deltech/ Dembla/ Keystone
Page 4 of 6
S.No Item Categotry 'A' Vendors Category 'B' Vendors
14.15 GLOBE / PISTON VALVES Audco/ Fisher Xomox/ Klinger Forbes Marshall/ KSB
17 CONTROL PANELS Pyrotech/ Power Control/ Techno Commerce/ Power Electronics/ Rittal -
18 MOISTURE MEASUREMENT
18.1 COKE MOISTURE GAUGE Chemtrol (TN Technologies)/ Concord Intl (Berthold) -
18.2 NEUTRON MOISTURE GAUGE Concord/ Emerson/ ECIL/ Endress&Hauser(European Origin) / Shaw -
23 DENSITY MEASUREMENT
Page 5 of 6
S.No Item Categotry 'A' Vendors Category 'B' Vendors
Page 6 of 6