1. Follow the user manual guide make sure current sensor Ia,Ib,Ic must N Ic
match with voltage R,S,T T
S Ib
R Ia
Verification
Verification
1.Check the site installation picture
2.Check the picture of the site installation
3.Check the voltage and current in Neteco
remotely
4.Check every phase active power, if value is
NA ,the sequence is wrong
5.Every phase active power is positive or
zero, the sequence is right.
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 3
3. Not connect the R/S/T any phase voltage cable
Description
Yada2060 Ammeter not connect the R/S/T any phase voltage cable
Possible reason
1. Wrong direction installation on site
Solution
Verification
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 4
4. R/S/T voltage cable connectiong is wrong
Description
Yada2060 Ammeter R/S/T voltage cable connectiong is wrong
Possible reason
1. Wrong direction installation on site
Solution
Verification
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 5
5. N cable not connected
Description
N cable not connected
Possible reason
1. Wrong direction installation on site
Solution
Verification
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 6
6. Yada2060 Ammeter configuration is wrong
Description
Yada2060 Ammeter is configured by default as 3Phase_4Line ,But some sites are set to 1Phase_2Line.
Possible reason
1. Mistaken setting
Solution
1. The current network wiring needs to be changed
to 3Phase_4Line. There may be a 1 2 4 5
situation, then follow the instructions given .
2. Select the AC standard as shown: 3Phase_4Line
Verification
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 7
7. A/C AC Phase type(3 phase 4 line) setting is wrong
Description
A/C default configuration is 1Phase_2Line , But some sites are set to 2Phase_2Line, 3Phase_4Line.
Possible reason
1. Mistaken setting
Solution
Verification
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 8
8. DC Power AC Phase type(3 phase 4 line) setting is wrong
Description
DC Power default configuration is 3Phase_4Line , But some sites are set to 1Phase_2Line、2Phase_2Line、
3Phase_3Line
Possible reason
1.Mistaken setting
Solution
Verification
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 9
9. AC Mains AC Phase type(3 phase 4 line) setting is wrong
Description
AC Mains default configuration is 3Phase_4Line, But some sites are set to 1Phase_2Line、 2Phase_2Line、
3Phase_3Line
Possible reason
1.Mistaken setting
Solution
Verification
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 10
10.Power AC Meter channel is the same with PLN
Description
DELTA、 DC Power、Emerson Power、Huawei MS Power AC meter channel occupies the AC Mains meter's
inherent address 1 channel 1
Possible reason
1.Mistaken setting
Solution
1. Correct wiring (please refer to the Indonesian installation manual);
2. NO DG site, DELTA can select a meter channel that is not used by other devices;
3. DG site, the site needs at least 3 meters ,DELTA must select the meter channel detection with
meter address greater than or equal to 3,and the channel is not occupied by other devices.
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 11
Verification
1. View the correct selection of the meter channel in the configuration data;
2. View data in real-time data display normally.
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 12
11. power supply not select the AC Meter
Description
DC Power、Eltek、 DELTA、 DC Power、Emerson Power、Huawei Power, no meter selected to detect relevant data
Possible reason
1. Wrong direction installation on site
Solution
1. Correct wiring (please refer to the Indonesian installation manual);
2. NO DG site, Power can select a meter channel that is not used by other devices;
3. DG site, the site needs at least 3 meters ,Power must select the meter channel detection with meter
address greater than or equal to 3,and the channel is not occupied by other devices.
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 14
13. Site missing test meter
Description
1.Some sites only one meter (the site has AC Mais and DG);
2. In multiple power supply sites, the number of meters is insufficient, resulting in multiple power supplies sharing
one meter channel.
Possible reason
1. Wrong direction installation on site
Solution
1. At least 3 meters are required for the DG site,must use the meter 1
channel 1 to detection the mains and meter 2 channel 1 detection DG .
2. Meters with addresses greater than or equal to 3 detect devices such as
air conditioners and power supplies
3. If the site does not have a meter, you need to bring new meters to
install it. After the installation is complete, select the scene file according
to the actual device.
For example: 1 Mains, 1 DG, 1 air conditioner, 1 DC Power, 1 fuel tank,
need to select scene file:
SCENE_ID_INDOSAT_02C_1M_1G_1A_1R_1T_Vxx
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 15
Verification
In real-time monitoring, the mains, air conditioner, The meter address is selected normally.
power supply, DG, fuel tank, meters are created
normally.
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 16
14. No meter is selected.
Description
Some sites have no meter created
Possible reason
1. The meter is not installed, the port configuration is incorrect, or the meter address is set incorrectly.
Solution
Verification
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 17
15.Repeated meter address
Description
Some sites different meter addresses set to the same address
Possible reason
1.Meter address setting error
Solution
Verification
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 18
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 19
16.Site has no Mains and DG create
Description
Some sites have neither mains supply nor DG
Possible reason
No connection to the mains or installation of the DG, or the scene file selection error
Solution
1. Confirm whether there is mains or DG, and import the
correct scene configuration file according to the
corresponding equipment;
2. NO DG site, such as: 1 mains, 0 DG, 1 air conditioner, 1
DC Power , 0 fuel tank, select the scene file:
SCENE_ID_INDOSAT_02C_1M_0G_1A_1R_0T_Vxx,
3. DG site, such as: 1 mains, 1 DG, 1 air conditioner, 1 DC
Power , 1 fuel tank, select the scene file:
SCENE_ID_INDOSAT_02C_1M_1G_1A_1R_1T_Vxx,
4. If it is created normally but there is no data in the mains,
please check the wiring of meter 1 ,and the mains must be
channel 1 of meter 1.
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 20
Verification
1. DG site: In real-time monitoring, the mains, air conditioner, DC Power,DG, fuel tank, meters are created normally.
2. the meter address is selected normally.
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 21
17. DG site meter selection error
Description
DG site, power supply and other equipment to detect the address of the meter selected 1 or 2
Possible reason
1.Setting error
Solution
Verification
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 22
19. DC Unavailable Voltage Threshold(V) Set too high
Description
DC Power、DELTA 、Eltek PSC 、Emerson、Huawei MS Power DC Unavailable Voltage Threshold(V) Set to
56V, default is 46V
Possible reason
1. The error is set to 56V, the default is 46V.
Solution
Set to 46.0V
Verification
View configuration
parameter settings
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 23