Trouble Shooting Guide For AC Power

Consumption
www.huawei.com

HUAWEI TECHNOLOGIES CO., LTD.


1. AC Meter Current Sensor Installation Sequence Wrong
 Description
Site the AC Meter R,S,T current sensor is match with the Voltage cable R,S,T
 Possible reason
1. Wrong installation on site, current sensor Ia,Ib,Ic not match with voltage R,S,T
 Solution

1. Follow the user manual guide make sure current sensor Ia,Ib,Ic must N Ic
match with voltage R,S,T T
S Ib
R Ia
 Verification

1. Check the picture of the site installation


2. Check the voltage and current in Neteco remotely
3. Check every phase active power, if value is NA ,the sequence is wrong
4. Every phase active power is positive or zero, the sequence is right.

ECC reboot operation


HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 2
2. AC Meter Current Sensor Installation Direction is Wrong
 Description
Site the AC Meter R,S,T current sensor direction is not the same with site AC current direction
 Possible reason
1. Wrong direction installation on site
 Solution
Number “4” is MUS01A board

 Verification
1.Check the site installation picture
2.Check the picture of the site installation
3.Check the voltage and current in Neteco
remotely
4.Check every phase active power, if value is
NA ,the sequence is wrong
5.Every phase active power is positive or
zero, the sequence is right.

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 3
3. Not connect the R/S/T any phase voltage cable
 Description
Yada2060 Ammeter not connect the R/S/T any phase voltage cable
 Possible reason
1. Wrong direction installation on site
 Solution

1. Follow the user manual guide make sure all


voltge cables connect rightly.

 Verification

1. Use a multimeter to measure the voltage between


the R S T and N . Each phase voltage is greater than
150V and less than 300V.
2. View voltage values ​on real-time data :The phase
voltage of each phase of R S T is greater than 150V
and less than 300V, indicating that the connection is
right.

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 4
4. R/S/T voltage cable connectiong is wrong
 Description
Yada2060 Ammeter R/S/T voltage cable connectiong is wrong
 Possible reason
1. Wrong direction installation on site
 Solution

1. Follow the user manual guide make


sure all voltge cables connect rightly.

 Verification

1. Use a multimeter to measure the voltage between


the R S T and N . Each phase voltage is greater than
150V and less than 300V.
2. View voltage values ​on real-time data :The phase
voltage of each phase of R S T is greater than 150V
and less than 300V, indicating that the connection is
right.

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 5
5. N cable not connected
 Description
N cable not connected
 Possible reason
1. Wrong direction installation on site
 Solution

1. Follow the user manual guide make sure all


voltge cables connect rightly.

 Verification

1. Use a multimeter to measure the voltage between


the R S T and N . Each phase voltage is greater than
150V and less than 300V.
2. View voltage values ​on real-time data :The phase
voltage of each phase of R S T is greater than 150V
and less than 300V, indicating that the connection is
right.

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 6
6. Yada2060 Ammeter configuration is wrong
 Description
Yada2060 Ammeter is configured by default as 3Phase_4Line ,But some sites are set to 1Phase_2Line.
 Possible reason
1. Mistaken setting
 Solution
1. The current network wiring needs to be changed
to 3Phase_4Line. There may be a 1 2 4 5
situation, then follow the instructions given .
2. Select the AC standard as shown: 3Phase_4Line
 Verification

1. Use a multimeter to measure the voltage between the R S T and N .


Each phase voltage is greater than 150V and less than 300V.
2. View voltage values ​on real-time data :The phase voltage of each phase
of R S T is greater than 150V and less than 300V, indicating that the
connection is right.

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 7
7. A/C AC Phase type(3 phase 4 line) setting is wrong
 Description
A/C default configuration is 1Phase_2Line , But some sites are set to 2Phase_2Line, 3Phase_4Line.
 Possible reason
1. Mistaken setting
 Solution

1. A/C wiring needs to be


1Phase_2Line. If it is
wrong, it needs to be
corrected.

2. Select the AC standard as


shown: 1Phase_2Line

 Verification

View configuration parameter settings

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 8
8. DC Power AC Phase type(3 phase 4 line) setting is wrong
 Description
DC Power default configuration is 3Phase_4Line , But some sites are set to 1Phase_2Line、2Phase_2Line、
3Phase_3Line
 Possible reason
1.Mistaken setting
 Solution

1. The DC power supply wiring


needs to be 3Phase_4Line.
If it is wrong, it needs to be
corrected.
2. Select the AC standard as
shown: 3Phase_4Line

 Verification

View configuration parameter settings

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 9
9. AC Mains AC Phase type(3 phase 4 line) setting is wrong
 Description
AC Mains default configuration is 3Phase_4Line, But some sites are set to 1Phase_2Line、 2Phase_2Line、
3Phase_3Line
 Possible reason
1.Mistaken setting
 Solution

1. The AC Mains supply


wiring needs to be
3Phase_4Line. If it is
wrong, it needs to be
corrected.
2. Select the AC standard
as shown: 3Phase_4Line

 Verification

View configuration parameter settings

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 10
10.Power AC Meter channel is the same with PLN
 Description
DELTA、 DC Power、Emerson Power、Huawei MS Power AC meter channel occupies the AC Mains meter's
inherent address 1 channel 1
 Possible reason
1.Mistaken setting
 Solution
1. Correct wiring (please refer to the Indonesian installation manual);
2. NO DG site, DELTA can select a meter channel that is not used by other devices;
3. DG site, the site needs at least 3 meters ,DELTA must select the meter channel detection with
meter address greater than or equal to 3,and the channel is not occupied by other devices.

NO DG site meter channel selection DG site meter selection

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 11
 Verification

1. View the correct selection of the meter channel in the configuration data;
2. View data in real-time data display normally.

Configuration parameter Real-time data

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 12
11. power supply not select the AC Meter
 Description
DC Power、Eltek、 DELTA、 DC Power、Emerson Power、Huawei Power, no meter selected to detect relevant data
 Possible reason
1. Wrong direction installation on site
 Solution
1. Correct wiring (please refer to the Indonesian installation manual);
2. NO DG site, Power can select a meter channel that is not used by other devices;
3. DG site, the site needs at least 3 meters ,Power must select the meter channel detection with meter
address greater than or equal to 3,and the channel is not occupied by other devices.

NO DG site meter channel selection DG site meter selection


HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 13
 Verification
1. View the correct selection of the meter channel in the configuration data;
2. View data in real-time data display normally.

Configuration parameter Real-time data

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 14
13. Site missing test meter
 Description
1.Some sites only one meter (the site has AC Mais and DG);
2. In multiple power supply sites, the number of meters is insufficient, resulting in multiple power supplies sharing
one meter channel.
 Possible reason
1. Wrong direction installation on site
 Solution
1. At least 3 meters are required for the DG site,must use the meter 1
channel 1 to detection the mains and meter 2 channel 1 detection DG .
2. Meters with addresses greater than or equal to 3 detect devices such as
air conditioners and power supplies
3. If the site does not have a meter, you need to bring new meters to
install it. After the installation is complete, select the scene file according
to the actual device.
For example: 1 Mains, 1 DG, 1 air conditioner, 1 DC Power, 1 fuel tank,
need to select scene file:
SCENE_ID_INDOSAT_02C_1M_1G_1A_1R_1T_Vxx

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 15
 Verification

In real-time monitoring, the mains, air conditioner, The meter address is selected normally.
power supply, DG, fuel tank, meters are created
normally.

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 16
14. No meter is selected.
 Description
Some sites have no meter created
 Possible reason
1. The meter is not installed, the port configuration is incorrect, or the meter address is set incorrectly.
 Solution

1. Carry new meters to site;


2. Confirm or correctly install the meter to the site;
3. Correct port configuration (need to choose NIM-
COM4)

 Verification

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 17
15.Repeated meter address
 Description
Some sites different meter addresses set to the same address
 Possible reason
1.Meter address setting error
 Solution

1. Go to the site to check the address


of each meter, record each meter
address;
2. if there meters address are the
same, you need to change to a
different address.

 Verification

If there are 4 meters, they can


be seen in the real-time monitoring.

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 18
HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 19
16.Site has no Mains and DG create
 Description
Some sites have neither mains supply nor DG
 Possible reason
No connection to the mains or installation of the DG, or the scene file selection error
 Solution
1. Confirm whether there is mains or DG, and import the
correct scene configuration file according to the
corresponding equipment;
2. NO DG site, such as: 1 mains, 0 DG, 1 air conditioner, 1
DC Power , 0 fuel tank, select the scene file:
SCENE_ID_INDOSAT_02C_1M_0G_1A_1R_0T_Vxx,
3. DG site, such as: 1 mains, 1 DG, 1 air conditioner, 1 DC
Power , 1 fuel tank, select the scene file:
SCENE_ID_INDOSAT_02C_1M_1G_1A_1R_1T_Vxx,
4. If it is created normally but there is no data in the mains,
please check the wiring of meter 1 ,and the mains must be
channel 1 of meter 1.

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 20
 Verification

1. DG site: In real-time monitoring, the mains, air conditioner, DC Power,DG, fuel tank, meters are created normally.
2. the meter address is selected normally.

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 21
17. DG site meter selection error
 Description
DG site, power supply and other equipment to detect the address of the meter selected 1 or 2
 Possible reason
1.Setting error
 Solution

1. If the wiring is wrong, need to correct the


wiring.
2. DG site, the site needs at least 3
meters ,Power must select the meter
channel detection with meter address
greater than or equal to 3,and the channel
is not occupied by other devices.

 Verification

Check the meter address of air conditioner、Power etc.

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 22
19. DC Unavailable Voltage Threshold(V) Set too high
 Description
DC Power、DELTA 、Eltek PSC 、Emerson、Huawei MS Power DC Unavailable Voltage Threshold(V) Set to
56V, default is 46V
 Possible reason
1. The error is set to 56V, the default is 46V.
 Solution

Set to 46.0V

 Verification

View configuration
parameter settings

HUAWEI TECHNOLOGIES CO., LTD. Huawei proprietary. No spread without permission. Page 23
Thank you
www.huawei.com

Copyright© 2013-2015 Huawei Technologies Co., Ltd. All Rights Reserved.


The information in this document may contain predictive statements including, without limitation, statements regarding the
future financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could
cause actual results and developments to differ materially from those expressed or implied in the predictive statements.
Therefore, such information is provided for reference purpose only and constitutes neither an offer nor an acceptance. Huawei
may change the information at any time without notice.