SR NO COMMENTS IN RO COMPLIANCE FOR COMMENTS IN R1
The Rated capacity of Air Scour blower
has been revised to 206 Nm3/hr which is 10 % more than the normal process requirement mentioned in the tender. With this revised rated capacity of blower the air scouring rate for filters will be 50 Nm3/m2/hr, while the velocity of air in the blower discharge pipeline will be 11.4 m/sec, both of which is within the permissible/acceptable design limits. We have ordered our blowers considering a rated flowrate of 206 Nm3/hr & this has happened because for all HMEL-Bhatinda projects the process specifications requires rated capacity of blowers to be 10 % more than the normal process requirements . We therefore request you to kindly review & approve the same . We have already submitted the blower vendor documents to EIL rotating group for their approval. Rated Capacity of blower has been changed We now require EIL Environment dept. 1 from 187 Nm3/hr to 206 Nm3/hr confirmation for the revised capacity.