Professional Documents
Culture Documents
Dedicated to Professor Dr. Bernd Isecke on the occasion of his 60th birthday
M. Ormellese*, F. Bolzoni, L. Lazzari and
P. Pedeferri
Corrosion of carbon steel rebars is the main cause of failure of compared to other preventive methods. This paper analyses results
reinforced concrete structures. To prevent and delay the occurrence of a 10-year investigation on the effectiveness of four commercial
of corrosion, a high quality concrete with a proper cover and a good inhibitors and two pure organic compounds in preventing chloride-
mixture proportion should be designed. Additional prevention induced corrosion. Tested inhibitors seem to be able to increase
methods are used if severe environmental conditions occur, or time-to-corrosion: their effects on chloride penetration rate and on
when structures require very long service life. Corrosion inhibitors
critical chloride threshold are discussed.
seem to be attractive because of their low cost and easy handling,
2 Experimental
Concrete specimens (160 250 70 mm3) were casted performed after 28 days of curing: commercial inhibitors do
with 300 kg/m3 of cement CEM II A/L 42,5R (European not influence the mechanical properties (Table 1).
standard CEN ENV 197/1 [23]), a water/cement ratio (W/C)
equal to 0.5 and calcareous aggregates (10 mm maximum
size) from Zandobbio (BG, Italy) (Table 1). Concrete 2.2 Concrete specimens of series B
samples were cured for 7 days at 20 8C and 95% relative
humidity. Concrete specimens (200 250 50 mm3) were casted
A carbon steel rebar was placed in each concrete with 367 kg/m3 of cement CEM II A/L 42,5R (European
specimen: 10 mm in diameter and 270 mm length. The standard CEN ENV 197/1 [23]), W/C ratio equal to 0.6, and
ends of each rebar were covered by thermoretractil sheath, so 1.770 km/m3 of limestone aggregates (12 mm maximum
that only a length of 170 mm was exposed to the concrete diameter). An acrylic super-plasticizer (0.6% by cement
(Fig. 1). Concrete cover was 20 mm. Two AISI 304 stainless weight) was added to concrete mixture. After 2 days of
steel rebars (10 mm in diameter) and an AISI 304 stainless curing in the mould, the concrete was cured until 28 days in a
steel wire (1 mm diameter) were placed in concrete wet environment (95% RH).
specimens for corrosion rate measurements. Two carbon steel rebars (10 mm in diameter and 290 mm
Commercial corrosion inhibitors (available on market length) were placed in each concrete specimen (Fig. 2). The
in 1997) were added to concrete mixture according to ends of each rebar were coated, so that only a length of
producers recommendations. Three organic products and one 210 mm was exposed to the concrete. Concrete cover was
nitrite-based product were considered. Dosages are reported 20 mm. A thin wire of mixed metal oxide activated titanium
in Table 1. For comparison purposes, specimens without (MMO) was fixed near each rebar to be used as reference
inhibitors were casted. electrode and three AISI 304 stainless steel wires (2 mm in
For each condition, cubic concrete specimens (100 mm in diameter) were embedded in the specimens and used as
side) were casted for compressive strength measurements, counter-electrode for corrosion rate measurements.
www.wiley-vch.de/home/wuk
100 Ormellese, Bolzoni, Lazzari, and Pedeferri Materials and Corrosion 2008, 59, No. 2
The same four commercial corrosion inhibitors (but calculated by means of Stern–Geary equation:
available on market in 2000) were added to the concrete
mixture in the recommended dosages, as reported in Table 1. icorr ðmm=yÞ ¼ 1:17 icorr ðmA=m2 Þ ¼ 1:17 C=Rp (1)
For comparison purposes, specimens without inhibitors were
casted. It is important to underline that the tested corrosion
inhibitors of these two series may have different chemical where Rp is the measured polarization resistance (Vm2) and
composition since they were bought in 1997 and 2000, constant C is assumed equal to 26 mV for actively corroding
respectively. rebars, and 52 mV for passive rebars [26]. Since corrosion
For each condition, three cubic specimens (100 mm in penetration lower than 1–2 mm/y can be considered negligible
side) were casted in order to check compressive strength [27,28], polarization resistance of about 10–20 Vm2 is the
(mean values are reported in Table 1). Also in this case threshold value below which corrosion is significant.
inhibitors do not influence concrete mechanical properties.
2.5 Chloride penetration
2.3 Concrete specimens of series C
Chloride profiles were determined on concrete cores
Concrete samples with the same mixture proportion of (30 mm in diameter) drilled from the reinforced concrete
series B were casted with two pure organic compounds, specimens. Cores were cut into 10 mm slices. Each slice was
sodium benzoate and DMEA: they are claimed to be active crushed and then dissolved into nitric acid. Total chloride
constituents of some organic commercial corrosion inhibi- content was analysed by potentiometric titration with 0.01 N
tors [2], for example they are present in OCIA-1 and silver nitrate.
OCIA-2. The two substances were added in dosages 1% with Titrations were performed on the three series as follows:
respect to cement weight that correspond to 3.6 kg/m3. That two times on series A (at the 4th and 37th ponding cycle);
is a higher dosage with respect to the supposed recommended five times on series B (at the 14th, 30th, 47th, 65th and 86th
one. Powder of sodium benzoate and liquid DMEA were ponding cycles); four times on series C (at the 14th, 29th,
firstly dissolved in water and then added to the mixture as an 47th and 57th ponding cycles).
additive.
3 Results
2.4 Corrosion monitoring
Aim of the paper is the evaluation of the effect of corrosion
Free corrosion potential was measured with respect to a inhibitors on chloride penetration rate and on critical
saturated calomel reference electrode (SCE) placed on the chloride threshold for the initiation of chloride-induced
external surface of the concrete samples [24]. Corrosion corrosion in concrete. A detailed description of corrosion
rate was measured using the linear polarization resistance monitoring results (free corrosion potential and polarization
technique (LPR) [25,26]: a potential scan rate of 10 mV/ resistance) on concrete samples of series A and B is reported
minute from 10 to þ10 mV with respect to the free in previous papers [21,22]. Here, only potential and chloride
corrosion potential was applied. Mean corrosion rate was profiles measurements are presented and discussed.
www.wiley-vch.de/home/wuk
Materials and Corrosion 2008, 59, No. 2 Effect of corrosion inhibitors 101
www.wiley-vch.de/home/wuk
102 Ormellese, Bolzoni, Lazzari, and Pedeferri Materials and Corrosion 2008, 59, No. 2
www.wiley-vch.de/home/wuk
Materials and Corrosion 2008, 59, No. 2 Effect of corrosion inhibitors 103
Fig. 8. Total chloride penetration profiles measured at the 14th, 47th and 86th ponding cycle for reinforced concrete samples of series B
4.2 Influence of inhibitors on chlorides penetration content was measured in concrete without inhibitor, while in
rate the presence of organic inhibitors chloride penetration is
reduced with time. A slight effect was also noticed in the
Tested commercial corrosion inhibitors reduce the presence of NIT. The two pure organic compounds behave
penetration of chlorides into concrete: considering the like organic inhibitors (Fig. 10).
measured profiles in time (Fig. 8), the higher chlorides Chlorides penetration in concrete is due to the presence
of different mechanisms: mainly diffusion
and capillary sorption. Only for compar-
ison purposes, experimental profiles may
be interpolated using an analytical solution
of the second Fick’s law (Equation (2)),
supposing that chlorides content at the
concrete surface is constant with time, and
considering an apparent chloride diffusion
coefficient that does not vary with time and
space (i.e. concrete is homogeneous). By
the interpolation, the apparent chloride
diffusion coefficients were estimated
(Table 2).
First of all, in the case of series B, it is
important to underline that apparent
diffusion coefficient decreases with time
as a result of the continuous cement
hydration that leads to a concrete porosity
Fig. 9. Free corrosion potential of rebars in specimen subjected to chloride penetration reduction, that is independent of the type of
(series C) tested inhibitors. Similar trend was
www.wiley-vch.de/home/wuk
104 Ormellese, Bolzoni, Lazzari, and Pedeferri Materials and Corrosion 2008, 59, No. 2
Fig. 10. Total chloride penetration profiles measured for reinforced concrete samples in the presence of DMEA and sodium benzoate
(series C)
observed for concrete with DMEA and sodium benzoate: values were evaluated also graphically using the measured
apparent diffusion coefficient decreases from 5.6 108 to profiles. Results regarding the three tested series are
2.5 108 cm2/s, and from 7.4 108 to 4.8 108 cm2/s, summarized in Fig. 11.
respectively. First of all, it must be underlined that the extrapolated data
The presence of organic inhibitors reduces the apparent have to be carefully analysed, since the diffusion coefficient
diffusion coefficient from two to four times the values is not constant with time (see Table 2), as requested to use the
obtained for reference concrete (Table 2). Maximum analytical solution of Fick’s law. Besides, values are related
reduction occurs in specimens containing inhibitors OCIA-2 to the described experimental conditions, so they should
and OCIA-3, as already reported in literature [2,10,20]. Also not be considered as absolute values, but used only for
NIT show a slight effect on chloride penetration, since it comparison purposes.
contains some organic compounds. In the absence of inhibitor, estimated critical chloride
Inhibitors have a sort of ‘physical-barrier’ effect: this is content is in the range 0.5–1.2% with respect to cement
probably due to the formation of gel compounds among weight: those values are in accordance with literature, at
organic substances and cement paste that block the pores, least the minimum ones [1]. As reported by Andrade and
reducing chlorides penetration rate. From an electrochemical co-workers [29], the critical chlorides content is influenced
point of view, this effect cannot be considered a real by a lot of parameters: pH of concrete pore solution, type of
inhibiting action, since it can be obtained acting on concrete cement, oxygen availability and temperature. Glass and
mixture proportion, reducing W/C ratio or using pozzolanic Buenfeld [30] underlined the relationship of the critical
or blended cements [1]. Nevertheless, compact and adequate chloride content with the cement paste porosity at the
concrete cover can have a synergic effect in combination interface rebar-concrete: the lower is the porosity, the higher
with inhibitors. For example, Berke and other authors is the critical chloride content. Due to the laboratory-
recommended the use of NIT in combination with low W/C controlled condition during casting of concrete samples, it is
ratio and high concrete cover, not only to prevent leaching of possible to assume that a low level of porosity is achieved at
inhibitor [4]. the interface rebar-concrete: this is the reason of the higher
maximum critical chloride value measured in our tests.
4.3 Effect of inhibitors on critical chloride threshold In the case of commercial organic inhibitors, literature
data do not allow to define a critical chloride content. As
On the basis of the obtained apparent diffusion coef- reported in the state of the art report by Elsener [2], there is
ficients, knowing the time of corrosion initiation (Figs. 4 no agreement among the scientific community in defining the
and 7), the critical chloride content at the rebar level
(x ¼ 20 mm) has been estimated by means of second Fick’s
law analytical solution (Equation (2)). Critical chloride
www.wiley-vch.de/home/wuk
Materials and Corrosion 2008, 59, No. 2 Effect of corrosion inhibitors 105
effectiveness of these inhibitors; conflicting results are – results obtained in the presence of NIT confirm literature
frequently reported. data: the inhibitor is effective if the molar ratio [NO
2 ]/
Considering results illustrated in Fig. 11, organic [Cl] is higher than 0.5–0.6.
inhibitors OCIA-1 and OCIA-3 provide a significant increase
in critical chloride content: both minimum and maximum It is worth noticing that in any case estimated values are
values are doubled with respect to reference condition. scattered: so the inhibitive effect of tested inhibitors is not
Inhibitor OCIA-2 does not offer any significant influence. fully clear, above all in experimental conditions different
The inhibitive effect of inhibitor OCIA-1 is also confirmed from those used in this research. Nevertheless, 10 years of
by results obtained in a parallel series of tests in which testing allow to state that two commercial organic inhibitors
chlorides were directly added in the mixture of the concrete (OCIA-1 and OCIA-3) provide a significant increase in
in concentration 1.2% with respect to cement weight: time-to-corrosion, due to both an increase of the critical
all carbon steel rebars were in passive condition even after chloride threshold and to a reduction of the apparent chloride
5 years [21]. diffusion coefficient.
The two pure organic compounds have only a minimum
effect on the critical chloride interval. As previously
mentioned, these organics substances are two of the active
compounds used in some commercial organic corrosion
inhibitors: OCIA-1 and OCIA-2 contain both of them in 6 References
unknown concentrations. Elsener [2] underlines that only
in the presence of both sodium benzoate and DMEA a clear [1] L. Bertolini, B. Elsener, P. Pedeferri, R. Polder, Corrosion of
inhibitive effect is demonstrated; otherwise, the two pure Steel in Concrete: Prevention, Diagnosis, Repair, Wiley,
compounds have a little or negligible effect. Results obtained Weinheim, 2004.
with series C are in agreement with literature. [2] B. Elsener, Corrosion Inhibitors for Steel in Concrete—State
Calcium NIT must be analysed separately; more literature of the Art Report, EFC Publications, Cambridge, Number
data are available on its inhibiting action [2–7], suggesting 35–2001.
that the corrosion inhibitor is effective if the molar ratio [3] N. S. Berke, Mater. Perform. 1989, 10, 41.
[NO 2 ]/[Cl ] is higher than 0.5–0.6. Tests results seem to be [4] N. S. Berke, T. G. Weil, presented at CANMET, Athen, Greece,
in accordance with literature: considering inhibitor dosage 1992, pp. 899–924.
(7.5 L/m3 for series A and 10 L/m3 for series B) and the [5] I. A. Callander, F. Gianetti, presented at Annual Middle East
obtained critical chloride content (Fig. 11), the estimated Protection & Rehabilitation of Reinforced Concrete Confer-
molar ratio [NO 2 ]/[Cl ] is in the range 0.42–0.51. The ence, Dubai, Saudi Arabia, 1996, pp. 1–12.
reliability of the threshold molar ratio was also confirmed by
[6] N. S. Berke, M. C. Hicks, Cement Concrete Compos. 2004,
tests performed on concrete specimens casted with chloride
26, 191.
0.8 and 1.2% by cement weight [21]: after 5 year tests rebars
are still in passive condition, and the calculated molar ratio is [7] K. J. Ann, H. S. Jung, H. S. Kim, S. S. Kim, H. Y. Moon,
0.55 and 0.37, respectively. Cement Concrete Res. 2006, 36, 530.
[8] C. Andrade, C. Alonso, M. Acha, B. Malric, Cement Concrete
Res. 1996, 26, 405.
5 Conclusions [9] V. T. Ngala, C. L. Page, M. M. Page, Corros. Sci. 2003, 45,
1523.
During the last 10 years, two different laboratory tests on [10] C. K. Nmai, S. A. Farrington, G. S. Bobrowsky, Concrete Int.
commercial corrosion inhibitors have been carried out. Also
1992, 14, 45.
two pure organic compounds were tested. Reinforced
[11] U. Mäder, Concrete 1999, 9, 215.
concrete samples were exposed to accelerated chloride
penetration by means of 3 week long ponding cycles: the first [12] D. Bjegovic, B. Miksic, Mater. Perform. 1999, 9, 52.
week wetting the upper surface of concrete with 3.5% [13] C. K. Nmai, P. E. Faci, presented at the 7th International
sodium chloride solution; then next 2 weeks drying concrete Conference on Concrete in Hot and Aggressive Environment,
in laboratory. Bahrain, 2003, Paper 14.
On the basis of corrosion monitoring results and chloride [14] J. M. Gaidis, Cement Concrete Compos. 2004, 26, 181.
profiles measurements the following can be drawn: [15] F. Wombacher, U. Maeder, B. Marazzani, Cement Concrete
Compos. 2004, 26, 209.
– tested commercial corrosion inhibitors (available in the [16] L. Mechmeche, L. Dhouibi, M. Ben Ouezdou, E. Triki, F.
market in 1997 and 2000) and the two pure organic Zucchi, Cement Concrete Compos. 2007, 29, 365.
substances seem to be able to delay the occurrence of [17] R. J. Kessler, R. G. Powers, M. A. Paredes, A. A. Sagués,
corrosion; inhibitor OCIA-1 is the more effective;
Y. P. Virmani, presented at NACE’07, Nashville (TN), USA,
– the increase of time-to-corrosion is related to both a
2007, paper 293.
reduction of chloride penetration rate (as reduction of
[18] M. Collepardi, R. Fratesi, G. Moriconi, C. Corradetti, L.
apparent chloride diffusion coefficient) and to a certain
increase on the critical chloride threshold; Coppola, presented at International RILEM symposium on
– organic commercial inhibitors reduce apparent chloride admixtures for concrete, Barcellona, Ed. Vazquez, Chapman
diffusion coefficient from two to four times; from an and Hall, London, UK, 1990, pp. 279–288.
electrochemical point of view, this effect is not a real [19] R. Fratesi, G. Moriconi, S. Simoncini, presented at Giornate
inhibitive action, but a sort of ‘physical barrier’ effect; nazionali sulla corrosione e protezione, AIM, Milan, 1994,
– organic commercial inhibitors OCIA-1 and OCIA-3 pp. 39–48 (in Italian).
provide a significant increase of the critical chloride [20] E. Pazini, S. Leao, G. Estefani, presented at NACE Confer-
threshold: both minimum and maximum values are ence: Latin-American Congress, Cancun, Mexico, 1998, pp.
doubled with respect to reference condition; 134–143.
www.wiley-vch.de/home/wuk
106 Ormellese, Bolzoni, Lazzari, and Pedeferri Materials and Corrosion 2008, 59, No. 2
[21] F. Bolzoni, L. Coppola, S. Goidanich, L. Lazzari, M. Ormel- [25] M. Stern, A. L. Geary, J. Electrochem. Soc. 1957, 104,
lese, M. P. Pedeferri, Corros. Eng., Sci. Technol. 2004, 39, 219. 56.
[22] M. Ormellese, M. Berra, F. Bolzoni, T. Pastore, Cement [26] C. Andrade, J. A. Gonzalez, Werkst. Korros. 1978, 29,
Concrete Res. 2006, 36, 536. 519.
[23] CEN ENV 197/1 Standard, Cement - Part 1: composition, [27] J. A. Gonzalez, S. Feliu, P. Rodriguez, E. Ramirez, C.
specifications and conformity criteria for common cements, Alonso, C. Andrade, Mater. Struct. 1996, 29, 40.
2000. [28] C. Alonso, A. Andrade, ACI Mater. J. 1995, 3–4, 130.
[24] ASTM C 876, Standard test method for half-cell potential of [29] C. Alonso, M. Castellote, A. Andrade, Electrochem. Acta
reinforcing steel in concrete, American Society of Testing and 2002, 47, 3469.
Materials, 1991. [30] G. K. Glass, N. R. Buenfeld, Corros. Sci. 2000, 42, 923.
(Received: October 10, 2007) W4155
(Accepted: October 28, 2007)
www.wiley-vch.de/home/wuk