SIMATIC S7-1200 Basic Course

Contents 2
2. Training Area Setup with S7-1200 ......................................................................... 2-2
2.1. Configuration of the S7-1200 Training Device ...................................................................... 2-3
2.2. Simulator Setup..................................................................................................................... 2-4
2.3. Conveyor Model Setup ......................................................................................................... 2-5
2.4. Training Area as Plant with Distribution Conveyor and Touchpanel .................................... 2-6

TIA-MICRO1 - Training Devices


Training Document V16.00.00 2-1
SIMATIC S7-1200 Basic Course

2. Training Area Setup with S7-1200

Components of the Training Area with S7-1200


The training area for this course contains the following components:
• SIMATIC Field PG
• Training case with S7-1200, simulator and touchpanel
• Conveyor model

TIA-MICRO1 - Training Devices


2-2 Training Document V16.00.00
SIMATIC S7-1200 Basic Course

2.1. Configuration of the S7-1200 Training Device

PM CSM CPU 1214 AI4/AO2 DI8/DO8

Modules
The module addresses shown in the picture will be assigned in the chapter "Devices and
networks".

TIA-MICRO1 - Training Devices


Training Document V16.00.00 2-3
SIMATIC S7-1200 Basic Course

2.2. Simulator Setup

4711

DI 0V
I 0.0 S_Operat.ON
I 0.1 S_Operat.OFF -10V +10V
(NC) Poti
I 0.2 S_Right
I 0.3 S_Left
DO

P_Operation Q 4.1

I 0.7 S_Ackn. P_Fault Q 4.3

I 1.1 S_Fault1 P_Fault1 Q 4.6


I 1.2 S_Fault2 P_Fault2 Q 4.6
I 1.3 S_Fault3 P_Fault3 Q 4.7

Simulator Setup:
Together with the touchpanel, the simulator is used to operate the plant. It contains the following
components:
• 14 switches, whereby the switch "S_OperationOFF" (I 0.1) is an NC contact
• 10 LEDs
• Potentiometers for specifying or simulating analog input signals
• Voltmeter for displaying the voltage set on the potentiometer

Addressing
For the addressing shown in the picture, the relevant address settings must be made in the
device configuration.

TIA-MICRO1 - Training Devices


2-4 Training Document V16.00.00
SIMATIC S7-1200 Basic Course

2.3. Conveyor Model Setup

"Horn"
(Q 8.7)
"B_Bay1" "B_Bay2" "B_Bay3" "B_BayLB"
(I 8.5) (I 8.6) (I 8.7) (I 8.0)

"K_Left" (Q 8.6)
"K_Right" (Q 8.5)

"S_Bay1" "S_Bay2" "S_Bay3" "S_BayLB"


(I 8.1) (I 8.2) (I 8.3) (I 8.4)
"P_Bay1" "P_Bay2" "P_Bay3" "P_BayLB"
(Q 8.1) (Q 8.2) (Q 8.3) (Q 8.4)

Setup
The picture shows the sensors and actuators of the conveyor model as well as the I/O addresses
to which they are connected.

TIA-MICRO1 - Training Devices


Training Document V16.00.00 2-5
SIMATIC S7-1200 Basic Course

2.4. Training Area as Plant with Distribution Conveyor and


Touchpanel

DI 0V
I 0.0 S_Operat.ON
I 0.1 S_Operat.OFF -10V +10V
(NC) Poti
I 0.2 S_Right
I 0.3 S_Left
DO
PN
P_Operation Q 4.1

I 0.7 S_Ackn. P_Fault Q 4.3

I 1.1 S_Fault1 P_Fault1 Q 4.6


I 1.2 S_Fault2 P_Fault2 Q 4.6
I 1.3 S_Fault3 P_Fault3 Q 4.7

AI / AO DI/ DO

Industrial
Ethernet

The Training Area as Plant with Distribution Conveyor and Touchpanel


The distribution conveyor is used to transport parts and can be operated in two different operating
modes:
• When "P_Operation" (Q4.0) is switched off...
the conveyor motor can be jogged to the right and left. For now, the simulator switches are to be
used for this, later, the associated buttons on the touchpanel.

• When "P_Operation" (Q4.0) is switched on...


parts are transported on the conveyor model from Bay 1 or 2 until they are through the light
barrier. If a transport sequence takes longer than 6 seconds, the conveyor motor is automatically
switched off and the fault is displayed on the simulator as well as on the touchpanel. Only after
the fault is acknowledged with the simulator switch or on the touchpanel, can a new transport
sequence be started.
All parts that pass the light barrier when "P_Operation" is switched on are counted. When the
ACTUAL number of transported parts reaches the SETPOINT quantity (which can be preset on
the touchpanel) it is indicated on the conveyor model LED of the light barrier bay. Only after the
message is acknowledged with the associated bay pushbutton, can a new transport sequence be
started.
The indicator lights at Bays 1 and 2 show continuous light when a new part can be placed on the
conveyor (conveyor motor is stopped and both proximity sensors are free); 1Hz flashing light at
the Bay at which a part is detected by the associated proximity sensor, however, only as long as
the conveyor has not yet been started (if parts are placed on the conveyor at both proximity
sensors, no indicator lights are to light up); 2Hz flashing light as long as the conveyor motor is
running.
The indicator light at the Light Barrier Bay shows 2Hz flashing light as long as the conveyor motor
is running and continuous light when the SETPOINT quantity has been reached.

TIA-MICRO1 - Training Devices


2-6 Training Document V16.00.00