Battery Backup Sizing Calculations
And Suggestions
Guide On  Backup Battery    We are all aware of active Load shedding in South Africa, this is equally followed
by the in flood of generally low quality off the shelf “solutions to load shedding” , In
a single box, would be a 2 kW DC AC Power inverter, with a build in battery charger
Guide On  Solar Battery   and a single deep cycle battery promised to give you up to 6 hours of backup
during load shedding

It come as no surprise that these systems often work, but within 2­3 months the
Theory On Batteries     deep cycle included battery fail, or the client /user would complain that he is not
getting the backup time he use to get (deep cycle battery failure).

The problem with most of these units are common, we get calls daily of people who
Calculator Solar Battery just want to buy a new battery and it often come as a surprise that we prefer not
to sell them a new battery why?

The reason is simple, the new deep cycle battery will also be destroyed within 2­
Calculator Back­Up Battery
3 months and then the client would expect another new battery “under warrantee”

Deep Cycle batteries are an essential very critical components of any Power
Backup system, the under design, over use and under charge of the deep cycle
battery cause battery failures, a problem which will keep on repeating itself over in
  Contact Detail :
over in the same scenario.
 Email :
Deep Cycle Batteries are designed according to certain specifications, they have
info@planmypower.co.za
limitations and should be used in accordance to these specifications.
 Tel No:
We will herewith present to you considerations to choose the correct deep cycle
 Voip:     087 802 8479 battery and also the rating of the minimum requirement of batteries for your
 Land :  +27 (11) 6785101 specific application, in order to get the most effective prolonged lifetime out of the
deep cycle batteries for any system.
 Cell:     +27 79 491 3431 (Geoff)
We discuss battery types under a different page and so the rating and quality of
battery chargers, the focus here is merely on the design of the deep cycle battery
Technical Email : pack, in each scenario, I would make suggestion of what should be the minimum
size of the internal battery charger rating ­ assuming it is a good quality battery
 gawie@planmypower.co.za
charger, which take care of battery temperature, Proper Boost/absorb and float
phases, which is not part of this discussion­ From experience I can advice that
cheap low cost systems, also have a low cost build in charger, which do not take
care of the battery in anyway, however this discussion is excluded from this page.
We Specialize in : I will discuss the calculations based on a few Examples followed by general
guideline­  as follows:
Design
1. 600 W backup for 4 hours (TV, DSTV, few lights)
Supply & 2. 1200 W Backup with 4 hours(TV, DSTV, Computers, Lights)
3. 600 W hours with occasional load peaks of 2 kW, backup 5 hours
Installation (Same as per point 1, but including occasional use of Hairdryer,
microwave oven or Kettle
Of all systems 4. 2 kW Backup for 6 hours (typical office, lots of PC’s , Server, printer and
Kettle)
5. 5 kW backup for 8 hours (Big office, or a big house hold, TV, lights,
PC, server, Microwave, Hairdryer etc

As Load shedding do not happen every day, as a result batteries are not discharged every day, therefor it
is generally acceptable that deep cycle  batteries used for power backup applications can be discharged

down to around 60% , as to on solar backup systems, where cycling will be daily, we do not want to go
down to around 60% , as to on solar backup systems, where cycling will be daily, we do not want to go
above 30% DOD (Depth of Discharge)

Example 1 (600W Backup for 4 hours)
This is a typical application , in which people only want to keep essentials running during load shedding. I am not
being product specific, as TV ratings all differ and so on. Typical appliances usage are, The size of Backup inverter­
charger required is no more than a 1kW unit ­ a 600W Unit should do , but its a bit on the edge
TV
DSTV/Explorer
10 CFL Lights
Computer

Estimated power 600W,  if you need to keep same running for 4 hours, battery storage requirements would be
 600w X 4 Hours = 2400 Watt.hours

The total battery power you would thus need is

2400W/60% (DOD) = 4000 Watt.hour of deep cycle batteries

If you have a 12V Power inverter­charger , you thus require
  4000Watt.hour/12V = 333A.h of deep cycle batteries

I would thus suggest 4x 102 A.h batteries for your application
   If it is a 24V system, the battery power requirements remain the same, as it would be

            4000Watt.hour/24 = 166A.h , remember this is in 24V configuration, thus 2 banks of 102 AH deep
cycle batteries, it is still 4x 102 AH batteries.

As deep cycle batteries are not cycled every day, you do not need to go to the top class AGM, lead Crystal or
equivalent batteries, the Calcium calcium, Silver Calcium type VRLA batteries are sufficient for this
 At a DOD of 60%, the deep cycle battery lifetime is expected to be around 350 cycles , considering about 70 Load
shedding's per year, a life time (Subject to proper battery recharging ability of the power inverter­charger unit),
We could expect a life time of the deep cycle battery of around 350/70 = 5 Years

Example 2 (1200 Watt Backup for 4 hours)
This is a bigger  application , in which people only want to keep essentials running during load shedding, but with a
few more computers, maybe 2 or 3 TV’s etc. I am not being product specific, as TV ratings all differ and so on. The
size of Backup inverter­charger required is no more than a 1.5kW unit. Typical appliances usage are
3 x TV
DSTV/Explorer
30 CFL Lights
3 x Computers
1 x Fridge

Estimated power 1200W,  if you need to keep same running for 4 hours, battery storage requirements would
be

 1200w X 4 Hours = 4800 Watt.hours

The total battery power you would thus need is

4800W/60% (DOD) = 8000 Watt.hour of deep cycle batteries

If you have a 12V Power inverter­charger , you thus require
  8000Watt.hour/12V = 666A.h of deep cycle batteries

I would thus suggest 7x 102 A.h deep cycle batteries for your application
   If it is a 24V system, the battery power requirements remain the same, as it would be

            4000Watt.hour/24 = 333A.h , remember this is in 24V configuration, thus 4 banks of 102 AH
batteries, it is  8 x 102 AH batteries.

As batteries are not cycled every day, you do not need to go to the top class AGM, lead Crystal or equivalent deep
cycle batteries, the Calcium calcium, Silver Calcium type VRLA batteries are sufficient for this.At a DOD of
60%, the battery lifetime is expected to be around 350 cycles , considering about 70 Load shedding's per year, a life
time (Subject to proper battery recharging ability of the power inverter­charger unit),
We could expect a life time of the deep cycle battery of around 350/70 = 5 Years

Example 3 (600 W hours with occasional load peaks of 2 kW, backup 5 hours (Same as
per point 1, but including occasional use of Hairdryer, microwave oven or Kettle)
This is a typical application , in which people only want to keep essentials running during load shedding, but also
need to occasionally run a Kettle, a hairdryer or a Microwave ­ all three of these items are very heavy on power.
 I am not being product specific, as TV ratings all differ and so on. Typical appliances usage are, The size of Backup
inverter­charger required minimum a 2kW units, that is for a small kettle, a Small Microwave and really small
hairdryer…a 3kW backup power inverter is preferable in such a situation
The typical normal usage are :

DSTV/Explorer
10 CFL Lights
Computer
Add to this other appliances, say for average of 30 Minutes, during the 4 hour period

If we assume a average power draw of around 1700W for power appliance for 30 minute,s the power is thus
          1700W x 30 minutes/60 minutes = 850Watt.hour

Your total energy requirement now becomes

     600 Watt x 4 hours  +  850 Watt.hours  = 3250 Watt.hours

The total battery power you would thus need is

3250 W.h/60% (DOD) = 5420 Watt.hour of deep cycle batteries

   If it is a 24V system, the battery power requirements remain the same, as it would be

            5420Watt.hour/24 = 226 A.h , remember this is in 24V configuration, thus 3 banks of 102 AH deep
cycle batteries, it is  6 x 102 AH batteries.

As deep cycle batteries are not cycled every day, you do not need to go to the top class AGM, lead Crystal or
equivalent batteries, the Calcium calcium, Silver Calcium type VRLA batteries are sufficient for this
 At a DOD of 60%, the deep cycle battery lifetime is expected to be around 350 cycles , considering about 70 Load
shedding's per year, a life time (Subject to proper battery recharging ability of the power inverter­charger unit),
We could expect a life time of the deep cycle battery of around 350/70 = 5 Years

Example 4 (2 kW Backup for 6 hours (typical office, lots of PC’s , Server, printer and
Kettle)
This is a typical office application , in which office need to keep PC’s Servers and lights operational, but also need to
occasionally run a Kettle,  ­ all three of these items are very heavy on power. A Minimum of a 3kW 24V Power
backup inverter­charger is required here.

The typical normal usage are :

8 x PC
1 x Server
Occasional kettle

If we assume a average power draw of around 2000W for power appliance
          2000W x 6 Hours = 12000 Watt.hours

The total deep cycle  battery power you would thus need is

12000 W.h/60% (DOD) = 20000 Watt.hour of deep cycle batteries

   If it is a 24V system, the battery power requirements are

20000 Watt.hour/24 = 833 A.h , remember this is in 24V configuration,
Because of the size, it now make more sense to use a bigger battery  range, perhaps 180A.h, it is possible with
100A.h to build up such a bank, but using less of bigger is often more practical
thus 5  banks of 180 AH deep cycle batteries, it is  10 x 180 AH batteries.

As deep cycle batteries are not cycled every day, you do not need to go to the top class AGM, lead Crystal or
equivalent batteries, the Calcium calcium, Silver Calcium type VRLA batteries are sufficient for this. For this
application, I would however suggest the Monobat  180A.h VRLA Gell battery .
 At a DOD of 60%, the deep cycle battery lifetime is expected to be around 500 cycles , considering about 70 Load
shedding's per year, a life time (Subject to proper battery recharging ability of the power inverter­charger unit),
We could expect a life time of the deep cycle battery of around 350/70 = 7 Years

Example 5 (5 kW Backup for 8 hours (typical BIG office, clinic , lots of PC’s , Server,
printer and Kettle)
This is a typical office application , in which office need to keep PC’s Servers and lights operational, but also need to
occasionally run a Kettle,  ­ all three of these items are very heavy on power. A Minimum of a 5kW 48V Power
backup inverter­charger is required here.

The typical normal usage are :

8 x PC
8 x PC
1 x Server
Occasional kettle
Operating equipment and lights
Emergency lights
Switch board

If we assume a average power draw of around 5000W for power appliance
          5000W x 8 Hours = 40000 Watt.hours

The total deep cycle  battery power you would thus need is

40000 W.h/60% (DOD) = 66600 Watt.hour of deep cycle batteries

   If it is a 24V system, the battery power requirements are

66600 Watt.hour/48 = 1400 A.h , remember this is in 48V configuration,
Because of the size, it now make more sense to use a bigger battery  range, perhaps 180A.h, it is possible with
100A.h to build up such a bank, but using less of bigger is often more practical
thus 8  banks of 180 AH deep cycle batteries, it is  32 x 180 AH batteries.

As deep cycle batteries are not cycled every day, you do not need to go to the top class AGM, lead Crystal or
equivalent batteries, the Calcium calcium, Silver Calcium type VRLA batteries are sufficient for this. For this
application, I would however suggest the Monobat  180A.h VRLA Gell battery .
 At a DOD of 60%, the deep cycle battery lifetime is expected to be around 500 cycles , considering about 70 Load
shedding's per year, a life time (Subject to proper battery recharging ability of the power inverter­charger unit),
We could expect a life time of the deep cycle battery of around 350/70 = 7 Years

Conclusion
The designed /suggested battery banks are probably bigger and more costly than you expected. I can assure you
that most suppliers will inform you against the quantity and cut on cost, but the reality is according the battery
specifications, expected assumptions and field experience, these examples are not over the board. The only
uncertainty is the amount of load shedding's and the durations of same­ combined with uncertainty of the future.

Again, I need to highlight the importance of a proper battery charger facility of your inverter­charger system, for
instance if your 12V system, only charger your battery to 13.8V, your batteries WILL not last, your inverter­
Chargers, have to properly look after your batteries, with a proper cycle of Charging/Discharging equalization etc
Without those charger abilities, your batteries doesn't matter what the investment, WILL NOT survive for 5 years
plus

Please fee free to contact us, for proper advice on your choice of battery or system design.  Send us an email to
 info@planmypower.co.za   

Copyright : Dr Gawie van der Merwe; PlanMyPower (PTY) Ltd