Method of Wiring Uses Permitted Uses Not Bending Radius Securing and Supporting Construction.

Permitted

(1) In both exposed (1)Where subject to The radius of the - secured within 300 mm of every outlet box, Armor of flexible
ARTICLE 3.20 and concealed work physical damage curve of the inner junction box, cabinet, or fitting and at metal tape and shall have an
edge of any bend intervals not exceeding 1 400 mm where internal bonding strip of copper
ARMORED (2) In cable trays (2) In damp or wet shall not be less installed on or across framing members. or aluminum in intimate contact
CABLE: TYPE AC locations than five times the with the armor for its entire
(3) In dry locations diameter of the Type AC cable shall be length.
(3) In air voids of cable. supported at intervals not exceeding 1 400
Armored Cable, (4) Embedded in masonry block or tile mm.
Type AC. A plaster finish on brick walls where such
fabricated assembly or other masonry, walls are exposed or - shall be permitted to be unsupported where
of insulated except in damp or wet subject to excessive the cable complies with any of the
conductors in a locations moisture or following:
flexible metallic dampness
enclosure. (5) To be run or fished (1) Is fished between access points through
in the air voids of (4) Where exposed concealed spaces in finished buildings or
masonry block or tile to corrosive fumes or structures and supporting is impracticable
walls where such vapors
walls are not exposed (2) Is not more than 600 mm in length at
or subject to excessive (5) Embedded in terminals where flexibility is necessary
moisture or dampness plaster finish on
brick or other (3) Is not more than 1 800 mm in length
masonry in damp from the last point of cable support to the
or wet locations point of connection to a luminaire(s)
[lighting fixture(s)] or other electrical
equipment and the cable and point of
connection are within an accessible ceiling.
Method of Uses Permitted Uses Not Installation Clearance Securing and Construction.
Wiring Permitted Supporting

ARTICLE 3.66 Auxiliary gutters shall be Auxiliary gutters Number of Clearance of Bare (a) Sheet Metal Splices and Taps. Splices and taps
permitted to supplement shall not be used Conductors. Live Parts. Bare Auxiliary shall comply with the following
AUXILIARY wiring spaces at meter under the (a) Sheet Metal conductors shall be Gutters. Sheet
GUTTERS centers, distribution center, following Auxiliary Gutters. securely and rigidly metal auxiliary (a) Within Gutters. Splices or taps
Metallic switchboards, and may conditions: The sum of the cross- supported so that gutters shall be shall be permitted within gutters
Auxiliary enclose conductors or sectional areas of all the minimum supported where they are accessible by means of
Gutters. busbars. (1) To enclose contained conductors clearance between throughout their removable covers or doors. The
Sheet metal switches, at any cross section bare current- entire length at conductors, including splices and
enclosures with (a) Sheet Metal Auxiliary overcurrent of a sheet metal carrying metal parts intervals not taps, shall not fill the gutter to more
hinged or Gutters. devices, auxiliary gutter shall of different potential exceeding than
removable covers (1) Indoor and Outdoor appliances, or not exceed 20 percent mounted on the 1 500 mm. 75 percent of its area.
for housing and Use. Sheet metal auxiliary other similar of the interior cross same surface will
protecting electric gutters shall be permitted equipment. sectional area of the not be less than 50 (b) Nonmetallic (b) Bare Conductors. Taps from
wires, cable, and for indoor and outdoor use. sheet metal auxiliary mm, nor less than Auxiliary bare conductors shall leave the gutter
busbars in which (2) Wet Locations. Gutters (2) To extend a gutter. 25 mm for Gutters. opposite their terminal connections,
conductors are laid installed in wet locations greater distance parts that are held Nonmetallic and conductors shall not be brought in
in place after the shall be suitable for such than 9 000 mm (b) Nonmetallic free in the air. A auxiliary gutters contact with uninsulated current-
wireway has been location beyond the Auxiliary Gutters. clearance not less shall be supported carrying parts of different potential.
installed as a equipment that it The sum of cross- than 25 mm shall at intervals not to
complete system. (b) Nonmetallic Auxiliary supplements. sectional areas of all be secured between exceed 900 mm (c) Suitably Identified. All taps shall
Gutters. Nonmetallic contained conductors bare current- and at each end be suitably identified at the gutter as
Nonmetallic auxiliary gutters shall be at any cross section carrying metal parts or joint, unless to the circuit or equipment that they
Auxiliary listed for the maximum of the nonmetallic and any metal listed for other supply.
Gutters. Flame ambient temperature of the auxiliary gutter shall surface. Adequate support intervals.
retardant, installation and marked for not exceed 20 percent provisions shall be In no case shall the (a) Electrical and Mechanical
nonmetallic the installed conductor of the interior cross- made for the distance between Continuity. Gutters shall be
enclosures with insulation temperature sectional area of the expansion and supports exceed constructed and installed so that
removable covers rating. nonmetallic auxiliary contraction of 3 000 mm. adequate electrical and mechanical
for housing and (1) Outdoors. Nonmetallic gutter. busbars. continuity of the complete system is
protecting electric auxiliary gutters shall be secured.
wires, cable, and permitted to be installed
busbars in which outdoors where listed and (b) Substantial Construction.
conductors are laid marked as suitable for the Gutters shall be of substantial
in place after the purpose. construction and shall provide a
wireway has been (2) Indoors. Nonmetallic complete enclosure for the contained
installed as a auxiliary gutters shall be conductors. All surfaces, both interior
complete system permitted to be installed and exterior, shall be suitably
indoors. protected from corrosion. Corner
joints shall be made tight, and where
the assembly is held together by
rivets, bolts, or screws, such fasteners
shall be spaced not more than
300 mm apart.

(c) Smooth Rounded Edges. Suitable


bushings, shields, or fittings having
smooth, rounded edges shall be
provided where conductors
pass between gutters, through
partitions, around bends, between
gutters and cabinets or junction
boxes, and at other locations where
necessary to prevent abrasion of the
insulation of the conductors.

(d) Covers. Covers shall be securely


fastened to the gutter.
Method of Uses Permitted Uses Not Permitted Marking and Construction.
Wiring Supporting

ARTICLE 3.68 (a) Exposed. Busways shall be permitted to be located (a) Physical Damage. Support -Busways shall Feeder or Branch Circuits. Where a
in the open where visible. Busways shall not be be securely supported at busway is used as a feeder, devices or plug-
BUSWAYS installed where subject to intervals not exceeding in connections for tapping off feeder or
(b) Concealed. Busways shall be permitted to be severe physical damage or 1 500 mm unless branch circuits from the busway shall
A grounded installed behind access panels, provided the busways corrosive vapors. otherwise designed and contain the overcurrent devices required for
metal enclosure are totally enclosed, of nonventilating-type marked. the protection of the feeder or branch
containing construction, and installed so that the joints (b) Hoistways. Busways circuits. The plug-in device shall consist of
factory-mounted, between sections and at fittings are accessible for shall not be installed in Marking. Busways an externally operable circuit breaker or an
bare or insulated maintenance purposes. Means of access shall be hoistways. shall be marked with the externally
conductors, provided, and either of the following conditions shall be voltage and current operable fusible switch.
which are usually met: (c) Hazardous Locations. rating for which they are
copper or (1) The space behind the access panels shall not be Busways shall not be designed, and with the Branches from Busways.
aluminum bars, used for airhandling purposes. installed in any hazardous manufacturer's name or Branches from busways shall be permitted
rods, or tubes. (2) Where the space behind the access panels is used (classified) location. trademark in such a to use any
for environmental air, other than ducts and plenums, manner as to be visible of the following wiring methods:
there shall be no provisions for plug-in connections, (d) Wet Locations. after installation. (1) Type AC armored cable
and the conductors shall be insulated. Busways shall not be (2) Type MC metal-clad cable
installed outdoors or in wet Dead Ends. A dead end (3) Type MI mineral-insulated, metal-
(c) Through Walls and Floors. Busways shall be or damp locations . of a busway shall be sheathed cable
permitted to be installed through walls or floors in closed. (4) Type IMC intermediate metal conduit
accordance below: (e) Working Platform. (5) Type RMC rigid metal conduit
(1) Walls. Unbroken lengths of busway shall be Lighting busway and Grounding. Busway (6) Type FMC flexible metal conduit
permitted to be extended through dry walls. trolley busway shall not be shall be grounded (7) Type LFMC liquidtight flexible metal
(2) Floors. Floor penetrations shall comply below: installed less than 2 400 conduit
a. Shall be permitted to be extended vertically mm above the floor or (8) Type RNC rigid nonmetallic conduit
through dry floors if totally enclosed (unventilated) working platform unless (9) Type LFNC liquidtight flexible
where passing through and for a minimum distance of provided with a cover nonmetal conduit
1 800 mm above the floor to provide adequate identified for the purpose. (10) Type EMT electrical metallic tubing
protection from physical damage. (11) Type ENT electrical nonmetallic
b. In other than industrial establishments, where a tubing
vertical riser penetrates two or more dry floors, a (12) Busways
minimum 100 mm high curb shall be installed around (13) Strut-type channel raceway
all floor openings for riser busways to prevent liquids (14) Surface metal raceways
from entering the opening. The curb shall be installed (15) Surface nonmetallic raceways
within 300 mm of the floor opening. Electrical
equipment shall be located so that it will not be
damaged by liquids that are retained by the curb.
Method of Wiring Uses Permitted Size and Securing and Supporting Construction.
Marking

ARTICLE 3.70 Approved cablebus shall Size and Number of The insulated conductors shall Types of Conductors. The current-carrying conductors in
be permitted at any Conductors. The size be supported on blocks or other cablebus shall have an insulation rating of 75°C or higher and be an
CABLEBUS voltage or current for and number of mounting means designed for approved type suitable for the application.
which spaced conductors shall be the purpose.
An assembly of conductors are rated and that for which the Transversely Routed. Cablebus shall be permitted to extend
insulated conductors shall be installed only cablebus is designed, The individual conductors in a transversely through partitions or walls, other than fire walls,
with fittings and for exposed work. and in no case smallercablebus shall be supported at provided the section within the wall is continuous, protected against
conductor than 50 mm2 intervals not greater than physical damage, and unventilated.
terminations in a Cablebus installed 900 mm for horizontal runs
completely enclosed, outdoors or in corrosive, Marking. Each section and 450 mm for vertical runs. Through Dry Floors and Platforms. Except where firestops are
ventilated protective wet, or damp locations of cablebus shall be required, cablebus shall be permitted to extend vertically through
metal housing. shall be identified for marked with the Vertical and horizontal spacing dry floors and platforms, provided the cablebus is totally enclosed
such use. manufacturer’s name between supported conductors at the point where it passes through the floor or platform and for a
Cablebus is ordinarily or trade designation shall not be less than one distance of 1 800 mm above the floor or platform.
assembled at the Cablebus shall not be and the maximum conductor diameter at the
point of installation installed in hoistways or diameter, number, points of support. Through Floors and Platforms in Wet Locations. Except
from the components hazardous (classified) voltage rating, and where firestops are required, cablebus shall be permitted to extend
furnished or specified locations. ampacity of the Fittings. A cablebus system vertically through floors and platforms in wet locations where:
by the manufacturer conductors to be shall include approved fittings
in accordance with Cablebus shall be installed. for the following: (1) there are curbs or other suitable means to prevent water flow
instructions for the permitted to be used for through the floor or platform opening, and
specific job. This branch circuits, feeders, Markings shall be (1) Changes in horizontal or
assembly is designed and services. located so as to be vertical direction of the run (2) where the cablebus is totally enclosed at the point where it
to carry fault current visible after passes through the floor or platform and for a distance of 1 800 mm
and to withstand the Cablebus framework, installation. (2) Dead ends above the floor or platform.
magnetic forces of where bonded, shall be
such current. permitted to be used as (3) Terminations in or on Grounding. A cablebus installation shall be grounded and bonded.
the equipment connected apparatus or
grounding conductor for equipment or the enclosures
branch circuits and for such equipment
feeders.
(4) Additional physical
protection where required,
such as guards where subject to
severe physical damage
Method of Wiring Uses Not Permitted Size and Construction.
Marking

ARTICLE 3.72 Conductors shall not Size of Conductors. No conductor Header. The header shall be installed in a straight line at right angles to the cells.
be installed in precast larger than 50 mm2 shall be installed, The header shall be mechanically secured to the top of the precast cellular concrete
CELLULAR cellular concrete floor except by special permission. floor. The end joints shall be closed by a metal closure fitting and sealed against the
CONCRETE raceways as follows: entrance of concrete. The header shall be electrically continuous throughout its
FLOOR Maximum Number of Conductors. entire length and shall be electrically bonded to the enclosure of the distribution
RACEWAYS (1) Where subject to The combined cross sectional area of all center.
corrosive vapor conductors or cables shall not exceed
40 percent of the cross-sectional area of Connection to Cabinets and Other Enclosures. Connections from headers to
Cell. A single, (2) In any hazardous the cell or header. cabinets and other enclosures shall be made by means of listed metal raceways and
enclosed tubular (classified) locations listed fittings.
space in a floor made Ampacity of Conductors. The ampacity
of precast cellular (3) In commercial adjustment factors, provided in Junction Boxes. Junction boxes shall be leveled to the floor grade and sealed
concrete slabs, the garages, other than for 3.10.1.15(b)(2), shall apply to against the free entrance of water or concrete. Junction boxes shall be of metal and
direction of the cell supplying ceiling conductors installed in cellular concrete shall be mechanically and electrically continuous with the header.
being parallel to the outlets or extensions to floor raceways.
direction of the floor the area below the Markers. A suitable number of markers shall be installed for the future location of
member. floor but not above cells.

Header. Transverse Inserts. Inserts shall be leveled and sealed against the entrance of concrete. Inserts
metal raceways for shall be of metal and shall be fitted with grounded-type receptacles. A grounding
electric conductors, conductor shall connect the insert receptacles to a positive ground connection
providing access to provided on the header. Where cutting through the cell wall for setting inserts or
predetermined cells other purposes (such as providing access openings between header and cells), chips
of a precast cellular and other dirt shall not be allowed to remain in the raceway, and the tool used shall
concrete floor, be designed so as to prevent the tool from entering the cell and damaging the
thereby permitting conductors.
the installation of
electric conductors Splices and Taps. Splices and taps shall be made only in header access units or
from a distribution junction boxes. For the purposes of this section, so-called loop wiring (continuous
center to the floor unbroken conductor connecting the individual outlets) shall not be considered to be
cells. a splice or tap.

Discontinued Outlets. When an outlet is abandoned, discontinued, or removed, the


sections of circuit conductors supplying the outlet shall be removed from the
raceway. No splices or reinsulated conductors, such as would be the case of
abandoned outlets on loop wiring, shall be allowed in raceways.
Method of Wiring Uses Not Permitted Size and Construction/ Installation
Marking

ARTICLE 3.74 (1) Where subject to Size of Conductors. No conductor Discontinued Outlets. When an outlet is abandoned, discontinued, or removed, the
corrosive vapor larger than 50 mm2 shall be installed, sections of circuit conductors supplying the outlet shall be removed from the
CELLULAR METAL except by special permission. raceway. No splices or reinsulated conductors, such as would be the case with
FLOOR RACEWAYS (2) In any hazardous abandoned outlets on loop wiring, shall be allowed in raceways.
(classified) location. Maximum Number of Conductors
Cellular Metal Floor in Raceway. The combined cross- Markers. A suitable number of markers shall be installed for locating cells in the
Raceway. The hollow (3) In commercial sectional area of all conductors or future.
spaces of cellular metal garages, other than for cables shall not exceed 40 percent of
floors, together with supplying ceiling outlets the interior cross-sectional area of Junction Boxes. Junction boxes shall be leveled to the floor grade and sealed
suitable fittings, that or extensions to the area the cell or header. against the free entrance of water or concrete. Junction boxes used with these
may be approved as below the floor but not raceways shall be of metal and shall be electrically continuous with the raceway.
enclosures for electric above Splices and Taps. Splices and taps
conductors. shall be made only in header access Inserts. Inserts shall be leveled to the floor grade and sealed against the entrance of
units or junction boxes. concrete. Inserts shall be of metal and shall be electrically continuous with the
Cell. A single enclosed raceway. In cutting through the cell wall and setting inserts, chips and other dirt
tubular space in a For the purposes of this section, loop shall not be allowed to remain in the raceway, and tools shall be used that are
cellular metal floor wiring (continuous unbroken designed to prevent the tool from entering the cell and damaging the conductors.
member, the axis of the conductor connecting the individual
cell being parallel to the outlets) shall not be considered to be Connection to Cabinets and Extensions from Cells. Connections between
axis of the metal floor a splice or tap. raceways and distribution centers and wall outlets shall be made by means of
member. liquidtight flexible metal conduit, flexible metal conduit where not installed in
Ampacity of Conductors. The concrete, rigid metal conduit, intermediate metal conduit, electrical metallic tubing,
Header. A transverse ampacity adjustment factors or approved fittings. Where there are provisions for the termination of an
raceway (talabok) for in 3.10.1.15(b)(2) shall apply to equipment grounding conductor, nonmetallic conduit, electrical nonmetallic tubing,
electric conductors, conductors installed in cellular metal or liquidtight flexible nonmetallic conduit shall be permitted. Where installed in
providing access to floor raceways. concrete, liquidtight flexible nonmetallic conduit shall be listed and marked for
predetermined cells of a direct burial.
cellular metal floor,
thereby permitting the Cellular metal floor raceways shall be constructed so that adequate electrical and
installation of electric mechanical continuity of the complete system will be secured. They shall provide a
conductors from a complete enclosure for the conductors. The interior surfaces shall be free from burrs
distribution center to the and sharp edges, and surfaces over which conductors are drawn shall be smooth.
cells. Suitable bushings or fittings having smooth rounded edges shall be provided where
conductors pass.
Method of Uses Permitted Uses Not Clearances Securing and Supporting
Wiring Permitted

Concealed knob- (1) Commercial Through or Parallel to Framing Members. Where Supporting. Conductors shall be rigidly
ARTICLE 3.94 and-tube wiring garages passing through wood cross members in plastered supported onnoncombustible, nonabsorbent
shall be permitted partitions, conductors shall be protected by insulating materials and shall not contact any
CONCEALED to be installed in 2) Theaters and noncombustible, nonabsorbent, insulating tubes extending other objects. Supports shall be installed as
KNOB-AND- the hollow spaces similar locations not less than 75 mm beyond the wood member. follows:
TUBE WIRING of walls and (1) Within 150 mm of each side of each tap or
ceilings or (3) Motion picture (a) General. A clearance of not less than 75 mm shall be splice, and
A wiring method in unfinished attics studios maintained between conductors and a clearance of not less (2) At intervals not exceeding 1 400 mm.
using knobs, and roof spaces than 25 mm between the conductor and the surface over
tubes, and follows: (4) Hazardous which it passes. Securing. Where solid knobs are used,
flexible (1) For extensions (classified) conductors shall be securely tied thereto by tie
nonmetallic of existing locations (b) Limited Conductor Space. Where space is too wires having insulation equivalent to that
tubing for the installations limited to provide these minimum clearances, such as at of the conductor.
protection and (5) Hollow spaces meters, panelboards, outlets, and switch points, the
support of (2) Elsewhere by of walls, ceilings, individual conductors shall be enclosed in flexible
single insulated special permission and attics where nonmetallic tubing, which shall be continuous in length
conductors such spaces between the last support and the enclosure or terminal
are insulated by point.
loose, rolled, or
foamed-in-place Accessible by Stairway or Permanent Ladder.
insulating material Conductors shall be installed along the side of or through
that envelops the bored holes in floor joists, studs, or rafters. Where run
conductors through bored holes, conductors in the joists and in studs
or rafters to a height of not less than 2 100 mm above the
floor or floor joists shall be protected by substantial
running boards extending not less than 25 mm on each
side of the conductors. Running boards shall be securely
fastened in place. Running boards and guard strips shall
not be required where conductors are installed along the
sides of joists, studs, or rafters.

Not Accessible by Stairway or Permanent Ladder.


Conductors shall be installed along the sides of or through
bored holes in floor joists, studs, or rafters.
Method of Uses Permitted Uses Not Permitted Bends Size and Securing and Supporting Construction.
Wiring Marking

a) Exposed and (1) Where, during How Made. Bends (a) Minimum. (a) Securely Fastened. EMT Reaming and Threading.
Concealed. The use installation or afterward, shall be made so EMT smaller shall be securely fastened in (a) Reaming. All cut ends of
ARTICLE 3.58 of EMT shall be it will be subject to that the tubing is than metric 15 place at least every 3 000 mm. EMT shall be reamed or
permitted for both severe physical damage not damaged and mm shall not be In addition, each EMT run otherwise finished to remove
exposed and the internal used. between termination points shall rough edges.
ELECTRICAL concealed work. (2) Where protected diameter of the be securely fastened within 900 (b) Threading. EMT shall
METALLIC from corrosion solely by tubing is not (b) Maximum. mm of each outlet box, junction not be threaded.
TUBING: TYPE (b) Corrosion enamel Effectively The maximum box, device box, cabinet,
EMT Protection. Ferrous reduced. size of EMT conduit body, or other tubing Grounding. EMT shall be
An unthreaded or nonferrous EMT, (3) In cinder concrete or shall be 100 termination. permitted as an equipment
thin wall raceway elbows, couplings, cinder fill where subject Number in One mm. Grounding conductor.
of circular cross and fittings shall be to permanent moisture Run. There shall (b) Supports. Horizontal runs of
section designed permitted to be unless protected on all not be more than Marking. EMT EMT supported by openings
for the physical installed in concrete, sides by a layer of the equivalent of shall be clearly through framing members at
protection and in direct contact with noncinder concrete at four quarter bends and durably intervals not greater than 3 000
routing of the earth, or in areas least 50 mm thick or (360 degrees total) marked at least mm and securely fastened
conductors and subject to severe unless the tubing is at between pull every 3 000 mm within 900 mm of termination
cables and for use corrosive influences least 450 mm under the points, for points shall be permitted.
as an equipment where protected by fill example, conduit
grounding corrosion protection bodies and boxes.
conductor when and judged suitable (4) In any hazardous
installed utilizing for the condition. (classified) location
appropriate
fittings. (c) Wet Locations. (5) For the support of
All supports, bolts, luminaires (fixtures) or
EMT is generally straps, screws, and so other equipment except
made of steel forth shall be of conduit bodies no larger
(ferrous) with corrosion-resistant than the largest trade
protective materials. size of the tubing
coatings or Where practicable,
aluminum dissimilar metals in
(nonferrous). contact anywhere in
the system shall be
avoided to eliminate the
possibility of action
Method of Wiring Uses Permitted Uses Not Permitted Securing and Supporting Construction.

(1) In any building not (1) In hazardous Bends ENT shall be installed as a Grounding. Where equipment
ARTICLE 3.62 exceeding three floors (classified) locations complete system grounding is required, a
above grade as follows: Number in One Run. separate equipment grounding
ELECTRICAL a. For exposed work, (2) For the support of There shall not be more Securely Fastened. ENT shall conductor shall be installed in
NONMETALLIC b. Concealed within luminaires (fixtures) and than the equivalent of four be securely fastened at intervals the raceway.
TUBING: TYPE walls, floors, and other equipment quarter bends (360 degrees not exceeding 900 mm. In
ENT ceilings total) between pull points, addition, ENT shall be securely ENT shall be made of material
A nonmetallic (3) Where subject to for example, conduit fastened in place within 900 mm that does not exceed the
pliable corrugated (2) In any building ambient temperatures in bodies and boxes. of each outlet box, device box, ignitibility, flammability,
raceway of circular exceeding three floors excess of 50°C unless junction box, cabinet, or fitting smoke generation, and toxicity
cross section with above grade, ENT shall listed otherwise where it terminates. characteristics of rigid
integral or be concealed within polyvinyl chloride.
associated walls, floors, and (4) For conductors or Supports. Horizontal runs of
couplings, ceilings where the cables operating at a Size and Marking ENT supported by openings in ENT, as a pre-wired
connectors, and walls, floors, and temperature higher than framing members at intervals manufactured assembly, shall
fittings for the ceilings provide a the ENT listed Minimum. ENT smaller not exceeding 900 mm and be provided in continuous
installation of thermal barrier of temperature rating than 15 mm shall not be securely fastened within lengths capable of being
electric conductors. material that has at least used. 900 mm of termination points shipped in a coil, reel, or
a 15- minute finish 5) For direct earth burial shall be permitted. carton without damage.
ENT is composed of rating Maximum. ENT larger
a material that is (6) Where the voltage is than 50 mm shall not be Bushings. Where a tubing enters
resistant to moisture (3) In locations subject over 600 volts used. a box, fitting, or other enclosure,
and chemical to severe corrosive a bushing or adapter shall be
atmospheres and is influences (7) In exposed locations Marking. ENT shall be provided to protect the wire
flame retardant. clearly and durably marked from abrasion unless the box,
A pliable raceway is (4) In concealed, dry, (8) In theaters and similar at least every 3 000 mm fitting, or enclosure design
a raceway that can and damp locations locations. provides equivalent protection
be bent by hand with
a reasonable force (5)Above suspended (9) Where exposed to the
but without other ceilings where the direct rays of the sun.
assistance. suspended ceilings
provide a thermal (10) Where subject to
barrier of material that physical damage
has at least a 15-minute
finish rating
6) Encased in poured
concrete, or embedded
in a concrete slab
on grade where ENT is
placed on sand or
approved screenings,
provided fittings
identified for this
purpose are used for
connections.

(7) For wet locations


indoors as permitted in
this section or in a
concrete slab on or
below grade, with
fittings listed for the
purpose.

(8) Raceway size 15


mm through 25 mm as
listed manufactured
pre-wired assembly.
Method of Uses Permitted Uses Not Permitted Securing and Supporting Construction. Marking.
Wiring

ARTICLE 3.22 - (1) As branch circuits to (1) Where subject to The flat cable assemblies shall - Splices shall be made in - shall have the temperature
supply suitable tap corrosive vapors unless be supported by means of their listed junction boxes. rating durably marked on
FLAT CABLE devices for lighting, suitable for the special design features, within the surface at intervals not
ASSEMBLIES: small appliances, or small application the surface metal raceways. -Flat cable assemblies shall exceeding 600 mm.
TYPE FC power loads. The rating The surface metal raceways consist of two, three, four, or
of the branch circuit shall (2) In hoistways or on shall be supported as required five conductors The grounded conductor
An assembly of not exceed 30 amperes. elevators or escalators for the specific raceway to be shall be identified
parallel conductors installed. - Flat cable assemblies shall throughout its length by
formed integrally (2) Where installed for (3) In any hazardous have conductors of means of a distinctive and
with an insulating exposed work. (classified) location 5.5 mm2 (2.6 mm dia.) special durable white or gray
material web stranded copper wires. marking.
specifically (3) In locations where (4) Outdoors or in wet
designed for field they will not be subjected or damp locations -Each flat cable assembly dead
installation in to physical damage. unless identified for the end shall be terminated in an
surface metal Where a flat cable use end-cap device identified for
raceway assembly is installed less the use.
than 2 400 mm above the
floor or fixed working
platform, it shall be
protected by a cover
identified for the use.

(4) In surface metal


raceways identified for
the use. The channel
portion of the surface
metal raceway systems
shall be installed as
complete systems before
the flat cable assemblies
are pulled into the
raceways.
Method of Wiring Uses Permitted Uses Not Permitted Marking. Construction.

ARTICLE 3.24 - Branch Circuits. Use of (1) Outdoors or in wet Type FCC cable shall be clearly and Type FCC cable shall be listed for use with
FCC systems shall be locations durably marked on both sides at the FCC system and shall consist of three,
FLAT permitted both for general- intervals of not more than 600 mm four, or five flat copper conductors, one of
CONDUCTOR purpose and appliance (2) Where subject to with the information required by which shall be an equipment grounding
CABLE: TYPE FCC branch circuits and for corrosive vapors 3.10.1.11(a) and with the following conductor.
individual branch circuits. additional information:
A complete wiring (3) In any hazardous
system for branch - Branch-Circuit Ratings. (classified) location (1) Material of conductors
circuits that is (1) Voltage. Voltage (2) Maximum temperature rating
designed for between ungrounded (4) In residential, school, and (3) Ampacity
installation under conductors shall not hospital buildings
carpet squares. exceed 300 volts. Voltage
between ungrounded
The FCC system conductors and the
includes Type FCC grounded conductor shall
cable and associated not exceed 150 volts.
shielding, connectors,
terminators, adapters, System Height. Any portion
boxes, and receptacles. of an FCC system with a
height above floor level
Three or more flat exceeding 2.30 mm shall be
copper conductors tapered or feathered at the
placed edge-to-edge edges to floor level.
and separated and
enclosed within an Floor-mounted Type FCC
insulating assembly. cable, cable connectors, and
insulating ends shall be
covered with carpet squares
not larger than 900 mm 2
Method of Uses Uses Not Permitted Bends and Size and Securing and Supporting
Wiring Permitted Markings Marking

ARTICLE 3.48 FMC shall be (1) In wet locations There shall not be Minimum. FMC less than Securely Fastened. FMC shall be securely
permitted to be unless the conductors are more than the 15 mm shall not be used. fastened in place by an approved means within
FLEXIBLE used in exposed approved for the equivalent of four 300 mm of each box, cabinet, conduit body, or
METAL and concealed specific conditions and quarter bends (360 (a) Minimum. FMC larger other conduit termination and shall be
CONDUIT: locations. the installation is such degrees total) than raceway size 100 mm supported and secured at intervals not to exceed
TYPE FMC that liquid is not likely to between pull points, shall not be used. 1 400 mm.
enter raceways or for example,
A raceway of enclosures to which the conduit bodies and Supports. Horizontal runs of FMC supported
circular cross conduit is connected boxes. by openings through framing members at
section made of intervals not greater than 1 400 mm and
helically wound, (2) In hoistways securely fastened within 300 mm of
formed, interlocked termination points shall be permitted
metal strip. (3) In storage battery
rooms

(4) In any hazardous


(classified) location

(5) Where exposed to


materials having a
deteriorating effect on
the installed conductors,
such as oil or gasoline

(6) Underground or
embedded in poured
concrete or aggregate

(7) Where subject to


physical damage
Method of Uses Permitted Uses Not Permitted Bends Size and Construction.
Wiring Marking

ARTICLE 3.60 (1) In dry locations (1) In hoistways Table 3.60.2.15(a) (a) Minimum. FMT Number of Conductors.
Minimum Radius for Flexing Use smaller than raceway size
FLEXIBLE (2) Where (2) In storage battery 15 mm shall not be used. (a) Raceway size 15 mm and
Raceway Size Minimum Radius
METALLIC concealed rooms 20 mm. The number of
(mm) (mm) (b) Maximum. The
TUBING: TYPE conductors in raceway size 15
10 250 maximum size of FMT
FMT (3) In accessible (3) In hazardous mm and 20 mm shall not exceed
15 310 shall be raceway size
locations (classified) locations that permitted by the percentage
20 440 20 mm
A raceway that is unless otherwise fill specified in Table 9.1.1.1
circular in cross (4) For system permitted under other
section, flexible, voltages of 1 000 articles in this Code (b) Metric Designator 12
metallic, and volts maximum (Trade Size ). The number of
liquidtight without a (4) Under ground for Table 3.60.2.15 (b)
conductors in raceway size 10
nonmetallic jacket. direct earth burial, or Minimum Radius for Fixed Bend
mm shall not exceed that
embedded in poured Raceway Size Minimum Radius permitted in Table 3.48.2.13
concrete or aggregate (mm) (mm)
10 90 Grounding. FMT shall be
(5) Where subject to 15 100 permitted as an equipment
physical damage 20 125 grounding conductor where
installed in accordance with
(6) In lengths over 2.50.6.9(7).
1 800 mm

Table 9.1.1.1 Percent of Cross


Section of Conduit and Tubing for
Conductors
Number of All Conductor
Conductors Types

1 53
2 31
Over 2 40
Method of Wiring Uses Permitted Uses Not Permitted Bends Size and Securing and Construction.
Marking Supporting

ARTICLE 3.53 (1) In discrete (1) Where exposed How Made. Bends (a) Minimum. HDPE Number of Conductors. The
lengths or in shall be so made that conduit smaller than number of conductors shall
HIGH DENSITY continuous lengths (2) Within a building the conduit will not be raceway size 15 mm shall not exceed that permitted by
POLYETHYLENE from a reel damaged and the not be used. the percentage fill specified in
CONDUIT: TYPE (3) In hazardous internal diameter of the Table 1,
HDPE CONDUIT (2) In locations (classified) locations conduit will not be (b) Maximum. HDPE Chapter 9.
subject to severe effectively reduced. conduit larger than
A nonmetallic corrosive influences (4)Where subject to Bends shall be raceway size 100 mm Bushings. Where a conduit
raceway of circular and where subject ambient temperatures in permitted to be made shall not be used. enters a box, fitting, or other
cross section, with to chemicals for excess of 50°C unless manually without enclosure, a bushing or
associated couplings, which the conduit is listed otherwise auxiliary equipment, Each length of HDPE adapter shall be provided to
connectors, and listed and the radius of the shall be clearly and protect the wire from abrasion
fittings for the (5) For conductors or curve to the centerline durably marked at least unless the box, fitting, or
installation of (3) In cinder fill cables operating at a of such bends shall not every 3 000 mm . The enclosure design provides
electrical conductors. temperature higher be less than shown in type of material shall also equivalent protection.
(4) In direct burial than the HDPE conduit Table 3.54.2.15. be included in the
installations in earth listed operating marking. Grounding. Where equipment
or concrete temperature rating Number in One Run. grounding is required, a
There shall not be more separate equipment grounding
than the equivalent of conductor shall be installed in
four quarter bends (360 the conduit.
degrees total) between
pull points, for
example, conduit
bodies and boxes.
Method of Uses Permitted Uses Not Bending Radius Construction
Wiring Permitted

ARTICLE 3.26 — Type IGS cable shall be Type IGS cable shall Where the coilable Terminations and splices for Type IGS cable shall
permitted for use not be used as interior nonmetallic conduit be identified as a type that is suitable for maintaining the gas
under ground, including wiring or be exposed and cable is bent for pressure within the conduit. A valve and cap shall be provided
direct burial in the earth, as in contact with installation purposes or is for each length of the cable and conduit to check the gas
INTEGRATED the following: buildings. flexed or bent during shipment pressure or to inject gas into the conduit.
GAS SPACER or installation, the radii of
CABLE: TYPE (1) Service-entrance bends measured to the inside The conductors shall be solid aluminum rods, laid parallel,
IGS conductors of the bend shall not be less consisting of one to nineteen 13 mm diameter rods. The
than specified in Table minimum conductor size shall be 125 mm2, and the maximum
A factory assembly (2) Feeder or branch-circuit 3.26.2.15. size shall be 2375 mm2.
of one or more conductors
conductors, each A run of Type IGS cable Fittings. Terminations and splices for Type IGS cable shall be
individually between pull boxes or identified as a type that is suitable for maintaining the gas
insulated and terminations shall not contain pressure within the conduit. A valve and cap shall be provided
enclosed in a loose more than the equivalent of for each length of the cable and conduit to check the gas
fit, nonmetallic four quarter bends (360 pressure or to inject gas into the conduit.
flexible conduit as degrees total), including those
an integrated gas bends located immediately Insulation. The insulation shall be dry kraft paper tapes and a
spacer cable rated at the pull box or terminations. pressurized sulfur hexafluoride gas (SF6), both approved for
0 through 600 electrical use. The nominal gas pressure shall be 138 kPa gauge.
volts.
Conduit. The conduit shall be a medium density polyethylene
identified as suitable for use with natural gas rated pipe.

Table 3.26.2.15 Minimum Radii of Bends (IGS)

Raceway Size Minimum Radii


mm
50 600
80 900
100 1150
Method of Wiring Uses Permitted Securing and Supporting Construction.

(a) All Atmospheric Conditions Size (a) Securely Fastened. Each IMC shall be Dissimilar Metals. Where
ARTICLE 3.42 and Occupancies. Use of IMC (a) Minimum. IMC smaller securely fastened within 900 mm of each practicable, dissimilar metals in
shall be permitted under all than raceway size 15 mm outlet box, junction box, device box, cabinet, contact anywhere in the system
INTERMEDIATE atmospheric conditions and shall not be used. conduit body, or other conduit termination. shall be avoided to eliminate the
METAL CONDUIT occupancies. (b) Maximum. IMC larger Fastening shall be permitted to be increased possibility of galvanic action.
TYPE IMC than 100 mm shall not be to a distance of 1 500 mm where structural Aluminum fittings and enclosures
(b) Corrosion Environments. used. members do not readily permit fastening shall be permitted to be used with
A steel threadable IMC, elbows, couplings, and within 900 mm. Where approved, conduit IMC.
raceway of fittings shall be permitted to be Standard Lengths. The shall not be required to be securely fastened
circular cross section installed in concrete, in direct standard length of IMC shall within 900 mm of the service head for Reaming and Threading. All cut
designed for the contact with the earth, or in areas be 3 000 mm, including an above-the-roof termination of a mast. ends shall be reamed or otherwise
physical protection subject to severe corrosive attached coupling, and each finished to remove rough edges.
and routing of influences where protected by end shall be threaded (b) Supports. IMC shall be supported in Where conduit is threaded
conductors and cables corrosion protection and judged accordance with one of the following: in the field, a standard cutting die
and for use as an suitable for the condition. Marking with a taper of 1 in 16 shall be
equipment grounding Each length shall be clearly (1) Conduit shall be supported at intervals used.
conductor when (c) Cinder Fill. IMC shall be and durably marked at least not exceeding 3 000 mm.
installed with its permitted to be installed in or every 1 500 mm with the Bushings. Where a conduit enters
integral or associated under cinder fill where subject to letters IMC. Each length (2) Exposed vertical risers from industrial a box, fitting, or other enclosure,
coupling and permanent moisture where shall be marked machinery or fixed equipment shall be a bushing shall be provided to
appropriate fittings. protected on all sides by a layer of permitted to be supported at intervals not protect the wire from abrasion
noncinder concrete not less than 50 Bends exceeding 6 000 mm if the conduit is made unless the design of the box,
mm thick; where the conduit is not Number in One Run. up with threaded couplings, the conduit is fitting, or enclosure is such as to
less than 450 mm under the fill; or There shall not be more supported and securely fastened at the top afford equivalent protection.
where protected by corrosion than the equivalent of four and bottom of the riser, and no other means
protection and judged suitable for quarter bends (360 degrees of intermediate support is readily available.
the condition. total) between pull points,
for example, conduit bodies (3) Horizontal runs of IMC supported by
(d) Wet Locations. All supports, and boxes openings through framing members at
bolts, straps, screws, and so forth, intervals not exceeding 3 000 mm and
shall be of corrosion-resistant securely fastened within 900 mm of
materials or protected against termination points shall be permitted.
corrosion by corrosion-resistant
materials.
Method of Wiring Uses Permitted Uses Not Bends and Size and Securing and Construction.
Permitted Markings Marking Supporting

ARTICLE 3.50 (1) Where (1) Where subject Bends — Number (a) Minimum. Securely Fastened. LFMC Couplings and Connectors.
conditions of to physical in One Run. There LFMC smaller than shall be securely fastened in Angle connectors shall not be
LIQUIDTIGHT installation, damage shall not be more 15 mm electrical place by an approved means used for concealed raceway
FLEXIBLE METAL operation, or than the equivalent trade size shall not within 300 mm of each box, installations.
CONDUIT: TYPE maintenance (2) Where any of four quarter be used. cabinet, conduit body, or
LFMC require flexibility combination of bends (360 degrees other conduit termination Grounding and Bonding.
or protection from ambient and total) between pull (b) Maximum. The and shall be supported and Where used to connect
A raceway of liquids, vapors, or conductor points, for example, maximum size of secured at intervals not to equipment where flexibility is
circular cross section solids temperature conduit bodies and LFMC shall be 100 exceed 1 400 mm. required, an equipment
having an outer produces an boxes. mm electrical trade grounding conductor shall be
liquidtight, (2) in other operating size. Supports. Horizontal runs installed.
nonmetallic, hazardous temperature in Marking. LFMC of LFMC supported by Where flexibility is not required,
sunlight-resistant (classified) excess of that for shall be marked openings through framing LFMC shall be permitted to be
jacket over an inner locations where which the according to members at intervals not used as an equipment grounding
flexible metal core specifically material is 1.10.1.21. The greater than 1 400 mm and conductor.
with associated approved. approved trade size and other securely fastened within 300
couplings, connectors, information mm of termination points
and fittings for the (3) For direct required by the shall be
installation of burial where listed listing shall also be permitted.
electric conductors and marked for the marked on the
purpose conduit. Conduit
suitable for direct
burial shall be so
marked.
Method of Wiring Uses Permitted Uses Not Bends Size and Securing and Supporting Construction.
Permitted Marking

ARTICLE 3.56 (1) Where (1) Where subject How Made. Bends a) Minimum. LFNC (1) Where installed in lengths Number of
flexibility is to physical damage shall be manually smaller than raceway size exceeding 1 800 mm, the Conductors. The
LIQUIDTIGHT required for made so that 15 mm shall not be used. conduit shall be securely number of conductors
FLEXIBLE installation, (2) Where any the conduit will fastened at intervals not or cables shall not
NONMETALLIC operation, or combination of not be damaged (b) Maximum. LFNC exceeding 900 mm and within exceed that permitted
CONDUIT: TYPE maintenance ambient and and the internal larger than raceway size 300 mm on each side of every by the percentage fill
LFNC conductor diameter of the 100 mm shall not be used outlet box, junction box, cabinet, in Table 1, Chapter 9.
(2) Where temperatures is in conduit will not be or fitting.
(1) A smooth seamless protection of the excess of that for effectively LFNC shall be marked at Grounding. Where
inner core and cover contained which the LFNC is reduced. least every 600 mm (2) Securing or supporting of the equipment grounding
bonded together and conductors is approved The marking shall include conduit shall not be required is required, an
having one or more required from Bends — Number a type designation and the where it is fished, installed in assembly containing a
reinforcement layers vapors, liquids, (3) In lengths in One Run. trade size. Conduit that is lengths not exceeding 900 mm separate equipment
between the core and or solids longer than 1 800 There shall not be intended for outdoor use or at terminals where flexibility is grounding conductor
covers, designated as mm, except as more than the direct burial shall be required, or installed in lengths shall be used.
Type LFNC-A (3) For outdoor permitted by equivalent of four marked. The type, size, not exceeding 1 800 mm from a
locations 3.56.2.1(5) or quarter bends (360 and quantity of conductors luminaire (fixture) terminal LFNC-B as a prewired
(2) A smooth inner where a longer degrees total) used in prewired connection for tap conductors to manufactured
surface with integral (4) For direct length is approved between manufactured assemblies luminaires assembly shall be
reinforcement within burial where as essential for a termination points. shall be identified by provided in continuous
theconduit wall, listed and marked required degree of means of a printed tag or (3) Horizontal runs of LFNC lengths capable of
designated as Type for the purpose flexibility label attached to each end supported by openings through being shipped in a coil,
LFNC-B of the manufactured framing members at intervals reel, or carton without
5) Type LFNC-B (4) Where the assembly and either the not exceeding 900 mm and damage.
(3) A corrugated shall be permitted operating voltage carton, coil, or reel. The securely fastened within 300
internal and external to be installed in of the contained enclosed conductors shall mm of termination points shall
surface without lengths longer conductors is in be marked. be permitted.
integralre inforcement than 1 800 mm excess of 600
within the conduit where secured in volts, nominal, (4) Securing or supporting of
wall, designated as accordance with LFNC-B shall not be required
LFNC-C 3.56.2.21 (5) In any where installed in lengths not
LFNC is flame hazardous exceeding 1 800 mm from the
resistant and with (classified) last point where the raceway is
fittings and is securely fastened for
approved for the connections within an accessible
installation of ceiling to luminaire(s) [lighting
electrical conductors. fixture(s)] or other equipment.
Method of Wiring Uses Permitted Uses Not Permitted Size and Construction.
Marking

ARTICLE 3.60 (1) In dry locations (1) In hoistways (a) Minimum. FMT smaller Grounding. FMT shall be
than raceway size 15 mm shall permitted as an equipment
FLEXIBLE (2) Where (2) In storage battery rooms not be used. grounding conductor
METALLIC concealed
TUBING: TYPE (3) In hazardous (classified) locations Maximum. The maximum size
FMT 3) In accessible of FMT shall be raceway size
locations (4) Under ground for direct earth burial, or embedded in 20 mm.
A raceway that is poured concrete or aggregate
circular in cross (4) For system
section, flexible, voltages of 1 000 (5) Where subject to physical damage
metallic, and volts maximum
liquidtight without a (6) In lengths over 1 800 mm
nonmetallic jacket.

Table 3.60.2.15(a) Minimum Radii for Flexing Use


Raceway Size Minimum Radii for Flexing Use
(mm)
10 mm 250
15 mm 310
20 mm 440

Table 3.60.2.15(a) Minimum Radii for Fixed Bends


Raceway Size Minimum Radii for Flexing Use
(mm)
10 mm 90
15 mm 100
20 mm 125
Method of Uses Permitted Uses Not Bending Radius Securing and Construction. Marking.
Wiring Permitted Supporting
Type MV cables shall have Medium voltage cable shall
ARTICLE 3.28 — Type MV cable Unless identified copper, aluminum, be marked as
shall be permitted for the use, Type or copper-clad aluminum required by 3.10.1.11.
for use on MV conductors and shall comply
power systems cable shall not be with Table
MEDIUM rated up to 35 000 used as follows: 3.10.1.61 and Table 3.10.1.63
VOLTAGE volts nominal as or Table 3.10.1.64.
CABLE: TYPE follows: (1) Where exposed
MV to direct sunlight
(1) In wet or dry
locations (2) In cable trays,
A single or unless specified in
multiconductor (2) In raceways 3.92.1.3(b)(2)
solid dielectric
insulated cable (3) In cable trays as (3) Direct buried,
rated 2 001 volts or specified in unless in
higher. 3.92.1.3(b)(2) accordance with
3.0.2.20
(4) Direct buried in
accordance with
3.0.2.20

(5) In messenger-
supported wiring
Method of Wiring Uses Permitted Uses Not Permitted Securing and Supporting Construction.

ARTICLE 3.96 (a) Cable Types. The cable types in Messenger supported Messenger Support. The Grounding. The messenger
Table 3.96.2.1(a) shall be permitted to wiring shall not be used messenger shall be supported at shall be grounded as required
MESSENGER SUPPORTED be installed in messenger supported in hoistways or where dead ends and at intermediate by 2.50.4.1 and 2.50.4.7 for
WIRING wiring under the conditions described subject to physical locations so as to eliminate tension enclosure grounding.
in the article or section referenced for damage. on the conductors. The conductors
An exposed wiring support each. shall not be permitted to come into
system using a messenger wire contact with the messenger
to support insulated conductors (b) In Industrial Establishments. In supports or any structural
by any one of the following: industrial establishments only, where members, walls, or pipes.
conditions of maintenance and
(1) A messenger with rings and supervision ensure that only licensed
saddles for conductor support electrical practitioner or non licensed
electrical practitioner under the
(2) A messenger with a field- supervision of a licensed electrical
installed lashing material for practitioner service the installed
conductor support messenger supported wiring, the
following shall be permitted:
(3) Factory-assembled aerial
cable (c) Hazardous (Classified) Locations.
Messenger supported wiring shall be
(4) Multiplex cables utilizing a permitted to be used in hazardous
bare conductor, factory (classified) locations
assembled and twisted with one
or more insulated conductors,
such as duplex, triplex, or
quadruplex type of construction
Method of Uses Permitted Uses Not Bending Radius Securing and Supporting Construction.
Wiring Permitted

(1) For services, feeders, and (1) Where subject to (a) Smooth Sheath. Securing. cables shall be secured at Sheath. Metallic
ARTICLE 3.30 branch circuits physical damage (1) Ten times the external intervals not exceeding 1 800 mm. covering shall be one of
(2) For power, lighting, diameter of the metallic Cables containing four or fewer the following types:
METAL-CLAD control, and signal circuits (2) Direct burial in sheath for cable not more conductors sized no larger than 5.5 smooth metallic sheath,
CABLE: TYPE (3) Indoors or outdoors the earth than 19 mm in external mm2 (2.6 mm dia.) shall be secured corrugated metallic
MC (4) Exposed or concealed diameter within 300 mm of every box, sheath, interlocking
(5) To be direct buried where (3) In concrete cabinet, fitting, or other cable metal tape armor.
A factory assembly identified for such use (2) Twelve times the external terminations.
of one or more (6) In cable tray where (4) Where subject to diameter of the metallic The metallic sheath
insulated circuit identified for such use cinder fills, strong sheath for cable more than Supporting. cables shall be shall be continuous and
conductors with or (7) In any raceway chlorides, caustic 19 mm but not more than supported at intervals not exceeding close fitting. A
without optical fiber (8) As aerial cable on a alkalis, or vapors of 40 mm in external diameter 1 800 mm. Horizontal runs of Type nonmagnetic sheath or
members enclosed messenger chlorine or of MC cable installed in wooden or armor shall be used on
in an armor of (9) In hazardous (classified) hydrochloric acids (3) Fifteen times the external metal framing members or similar single conductor Type
interlocking metal locations as permitted diameter of the metallic supporting means shall be MC.
tape, or a smooth or (10) In dry locations and sheath for cable more than considered supported and secured
corrugated metallic embedded in plaster finish 40 mm in external diameter where such support does not exceed Supplemental protection
sheath. on brick or other masonry 1 800 mm intervals of an outer covering of
except in damp or wet (b) Interlocked-Type corrosion resistant
locations Armor or Corrugated Unsupported Cables. shall be material shall be
(11) In wet locations where Sheath. Seven times the permitted to be unsupported where permitted and shall be
any of the following external diameter of the the cable: required where such
conditions are met: metallic sheath. (1) Is fished between access points protection is needed.
a. The metallic covering is through concealed spaces in finished The sheath shall not be
impervious to moisture. (c) Shielded Conductors. buildings or structures and used as a current-
b. A lead sheath or Twelve times the overall supporting is impractical; or carrying conductor.
moisture-impervious diameter of one of the
jacket is provided under individual conductors or (2) Is not more than 1 800 mm in
the metal covering. seven times the overall length from the last point of
c. The insulated conductors diameter of the cable support to the point of
under the metallic covering multiconductor cable, connection to a luminaire (lighting
are listed for use in wet whichever is greater. fixture) or other piece of electrical
locations equipment and the cable and point
(12) Where single-conductor of connection are within an
cables are used, all phase accessible ceiling.
conductors and, where
used, the neutral conduct.
Method of Wiring Size and Securing and Construction/Installation
Uses Permitted Marking Supporting

ARTICLE 3.76 (1) For exposed work Size of Conductors. No Securing and Insulated Conductors. Insulated conductors installed in a
conductor larger than that Supporting. Metal metallic wireway shall comply with 3.76.2.14(a) and (b).
METAL (2) In concealed spaces for which the wireway is wireways shall be
WIREWAYS as permitted. designed shall be installed supported in (a) Deflected Insulated Conductors. Where insulated conductors
in any wireway. accordance with are deflected within a metallic wireway, either at the ends or where
Sheet metal troughs (3) In hazardous 3.76.2.21(a) and (b). conduits, fittings, or other raceways or cables enter or leave the
with hinged or (classified) locations as Number of Conductors. metallic wireway, or where the direction of the metallic wireway is
removable covers for permitted for Class I, The sum of the cross- (a) Horizontal deflected greater than 30 degrees, dimensions corresponding to one
housing and Division 2 locations and sectional areas of all Support. Wireways wire per terminal in Table 3.12.1.6(a) shall apply.
protecting electric for Class II, Division 2 contained conductors at shall be supported
wires and cable and Locations, and for any cross section of a where run horizontally Splices and Taps. Splices and taps shall be permitted within a
in which, conductors intrinsically safe wiring. wireway shall not exceed at each end and at wireway, provided they are accessible. The conductors, including
are laid in place after Where installed in wet 20 percent of the interior intervals not to exceed splices and taps, shall not fill the wireway to more than 75 percent of
the wireway has been locations, wireways cross-sectional area of the 1 500 mm or for its area at that point.
installed as a shall be listed for the wireway. The derating individual lengths
complete system. purpose. factors shall be applied longer than 1 500 mm Power Distribution Blocks.
only where the number of at each end or joint, (1) Installation. Power distribution blocks installed in metal wireways
(4) As extensions to current-carrying unless listed for other shall be listed.
pass transversely conductors, including support intervals. The
through walls if the neutral conductors distance between (2) Size of Enclosure. In addition to the wiring space requirement
length passing through classified as current- supports shall not in 3.76.2.47(a), the power distribution block shall be installed in a
the wall is unbroken. carrying exceeds 30. exceed 3 000 mm. wireway with dimensions not smaller than specified in the installation
Access to the instructions of the power distribution block.
conductors shall Marking. Metal wireways (b) Vertical Support.
be maintained on both shall be so marked that Vertical runs of (3) Wire Bending Space. Wire bending space at the terminals of
sides of the wall. their manufacturer’s name wireways shall be power distribution blocks shall comply with 3.12.1.6(b).
or trademark will be securely supported at
visible after installation. intervals not exceeding (4) Live Parts. Power distribution blocks shall not have exposed
Uses Not Permitted 4 500 mm and shall live parts in the wireway after installation.
not have more than
(1) Where subject to one joint between Dead Ends. Dead ends of metal wireways shall be closed.
severe physical damage supports. Adjoining
wireway sections Extensions from Metal Wireways. Extensions from wireways shall be
(2) Where subject to shall be securely made with cord pendants or with any wiring method in Chapter 3 that
severe corrosive fastened together to includes a means for equipment grounding.
environments provide a rigid joint.
Method of Wiring Uses Permitted Uses Not Bending Securing and Supporting Construction.
Permitted Radius

ARTICLE 3.32 (1) For services, feeders, (1) In underground (1) Five times (a) Horizontal Runs Through (a) Fittings. Fittings used for connecting
and branch circuits runs unless the external Holes and Notches. In other than Type MI cable to boxes, cabinets, or other
MINERAL- (2) For power, lighting, protected from diameter of the vertical runs, shall be considered equipment shall be identified for such use.
INSULATED, control, and signal physical damage, metallic sheath supported and secured where
METALSHEATHED circuits where necessary for cable not such support does not exceed (b) Terminal Seals. Where Type MI cable
CABLE: TYPE MI (3) In dry, wet, or more than 19 1 800 mm intervals. terminates, an end seal fitting shall be
continuously moist (2) Where exposed mm in external installed immediately after stripping to
A factory locations to conditions that diameter (b) Unsupported Cable. Type prevent the entrance of moisture into the
assembly of one or (4) Indoors or outdoors are destructive and MI cable shall be permitted to be insulation. The conductors extending
more conductors (5) Where exposed or corrosive to the (2) Ten times unsupported where the cable is beyond the sheath shall be individually
insulated with a highly concealed metallic sheath, the external fished between access points provided with an insulating material.
compressed refractory (6) Where embedded in unless additional diameter of the through concealed spaces in
mineral insulation and plaster, concrete, fill, or protection is metallic sheath finished buildings or structures Type MI cable conductors shall be of solid
enclosed in a other masonry, whether provided for cable and supporting is impracticable. copper, nickel, or nickel-coated copper with a
liquidtight and above or below grade greater than resistance corresponding to standard mm2 and
gastight continuous (7) In any hazardous 19 mm but not mm dia. sizes.
copper or alloy steel (classified) location more than 25
sheath. (8) Where exposed to oil mm in external
and gasoline Diameter.
(9) Where exposed to
corrosive conditions not
deteriorating to its
sheath
(10) In underground
runs where suitably
protected against
physical damage and
corrosive conditions
(11) In or attached to
cable tray
Method of Wiring Uses Permitted Uses Not Bending Securing and Construction.
Permitted Radius Supporting

ARTICLE 3.34 (a) Type NM. permitted as (a) Types NM, Bends in Types Shall be supported and Exposed Work. In exposed work,
follows: NMC, and NMS. NM, NMC, and secured by staples, cable (a) To Follow Surface. Cable shall closely follow
NONMETALLIC- (1) For both exposed and shall not be permitted NMS cable ties, straps, hangers, or the surface of the building finish or of running
SHEATHED concealed work in as follows: shall be so similar fittings at boards.
CABLE: normally dry locations To made that the intervals not exceeding (b) Protection from Physical Damage. Cable
be installed or fished in air (1) In any dwelling or cable will not 1 400 mm and within shall be protected from physical damage where
TYPES NM, NMC, voids in masonry block or structure. be damaged. 300 mm of every outlet necessary by rigid metal conduit, intermediate
AND NMS tile walls (2) Exposed in The radius box, junction box, metal conduit, electrical metallic tubing, Schedule
dropped or suspended of the curve of cabinet, or fitting. 80 PVC rigid nonmetallic conduit, or other
A factory assembly (b) Type NMC. permitted ceilings in other than the inner edge approved means. Where passing through a floor,
of two or more as follows: one and two-family of any bend (a) Horizontal Runs the cable shall be enclosed in rigid metal
insulated conductors (1) For both exposed and and multifamily during or after Through Holes and conduit intermediate metal conduit, electrical
enclosed within an concealed work in dry, dwellings installation Notches. In other than metallic tubing, Schedule 80 PVC rigid
overall nonmetallic moist, damp, or corrosive (3) As service- shall not be less vertical runs, cables nonmetallic conduit, or other approved means
jacket. locations, entrance cable than five times shall be considered to be extending at least 150 mm above the floor.
(2) In outside and inside (4) In commercial the diameter of supported and secured Where Type NMC cable is installed in shallow
Type NM. Insulated walls of masonry block or garages having the cable. where such support does chases in masonry, concrete, or adobe, the cable
conductors enclosed tile hazardous (classified) not exceed 1 400 mm shall be protected against nails or screws by a
within an overall (3) In a shallow chase in locations intervals and the steel plate at least 1.60 mm thick and covered with
nonmetallic jacket. masonry, concrete, or (5) In theaters and nonmetallic-sheathed plaster, adobe, or similar finish.
adobe protected against similar locations cable is securely (c) In Unfinished Basements. Where cable is run
Type NMC. nails or screws by a steel (6) In motion picture fastened in place by an at angles with joists in unfinished basements, it
Insulated conductors plate at least 1.60 mm thick studios approved means within shall be permissible to secure cables not smaller
enclosed within an and covered with plaster, (7) In storage battery 300 mm of each box, than two 14 mm2 or three 8.0 mm8 (3.2 mm dia.)
overall, corrosion adobe, or similar finish rooms cabinet, conduit body, conductors directly to the lower edges of the
resistant, nonmetallic (8) In hoistways or on or other nonmetallic- joists. Smaller cables shall be run either through
jacket. (c) Type NMS permitted elevators or sheathed cable bored holes in joists or on running boards. NM
as follows: escalators termination. cable used on a wall of an unfinished basement
Type NMS. Insulated (1) For both exposed and (9) Embedded in shall be permitted to be installed in conduit or
power or control concealed work in poured cement, (b) Unsupported tubing. Conduit or tubing shall utilize a
conductors with normally dry locations concrete, or Cables. Nonmetallic- nonmetallic bushing or adapter at the point the
signaling, data, and (2) To be installed or aggregate sheathed cable shall be cable enters the raceway. Metal conduit and
communications fished in air voids in (10) In hazardous permitted to be tubings and metal outlet boxes shall be grounded.
conductors within an masonry block or tile (classified) locations unsupported where the
overall nonmetallic walls cable: 3.34.2.31 Boxes and Fittings.
jacket. (1) Is fished between (a) Boxes of Insulating Material. Nonmetallic
access points through outlet boxes shall be permitted.
concealed spaces in
finished buildings or
(b) Types NM and structures and (b) Devices of Insulating Material. Switch,
NMS. Types NM and supporting is outlet, and tap devices of insulating material shall
NMS cables shall not impracticable. be permitted to be used without boxes in exposed
be used under the (2) Is not more than cable wiring and for rewiring in existing buildings
following conditions 1 400 mm from the last where the cable is concealed and fished.
or in the following point of cable support
locations: to the point of 3.34.3.1 Construction. The outer cable sheath of
(1) Where exposed to connection to a nonmetallic sheathed cable shall be a nonmetallic
corrosive fumes or luminaire (lighting material.
vapors fixture) or other piece of
(2) Where embedded electrical equipment and 3.34.3.5 Conductors. The 600 volt insulated
in masonry, concrete, the cable and point of conductors shall be sizes 2.0 mm2 (1.6 mm dia.)
adobe, fill, or plaster connection are within an through 30 mm2 copper conductors.
(3) In a shallow chase accessible ceiling.
in masonry, concrete, 3.34.3.9 Equipment Grounding. In addition to
or adobe and covered (c) Wiring Device the insulated conductors, the cable shall have an
with plaster, adobe, Without a Separate insulated or bare conductor for equipment
or similar finish Outlet Box. A wiring grounding purposes only.
(4) Where exposed or device identified for the
subject to excessive use, without a separate 3.34.3.17 Sheath. The outer sheath of
moisture or dampness outlet box, and nonmetallic-sheathed cable shall comply the
incorporating an integral following
cable clamp shall be
permitted where the (a) Type NM. The overall covering shall be flame
cable is secured in place retardant and moisture resistant.
at intervals no
exceeding 1 400 mm (b) Type NMC. The overall covering shall be
and within 300 mm flame retardant, moisture resistant, fungus
from the wiring device resistant, and corrosion resistant.
wall opening, and there
shall be at least a (c) Type NMS. The overall covering shall be
300 mm loop of flame retardant and moisture resistant. The sheath
unbroken cable or 150 shall be applied so as to separate the power
mm of a cable end conductors from the communications and
available on the interior signaling conductors. The signaling conductors
side of the finished wall shall be permitted to be shielded. An
to permit replacement. optional outer jacket shall be permitted.
Method of Wiring Uses Permitted Uses Not Permitted Bends Size and Construction.
Marking

ARTICLE 3.54 (1) For direct burial 1) In exposed locations How Made. The radius of (a) Minimum. NUCC Number of Conductors. The number of
underground the curve of the centerline smaller than raceway size conductors or cables shall not exceed that
NONMETALLIC installation (For (2) Inside buildings of such bends shall not be 15 mm shall not be used. permitted by the percentage fill in Chapter
UNDERGROUND minimum cover less than shown in Table 9.1.1.1
CONDUIT WITH requirements, see (3) In hazardous 3.54.2.15. (b) Maximum. NUCC
CONDUCTORS: Table 3.0.1.5 and (classified) locations. larger than 100 mm shall Trimming. For termination, the conduit shall
TYPE NUCC Table 3.0.2.20 under Number in One Run. not be used. be trimmed away from the conductors or
Rigid Nonmetallic There shall not be more cables using an approved method that will not
A factory assembly Conduit.) than the equivalent of four NUCC shall be clearly and damage the conductor or cable insulation or
of conductors or quarter bends (360 degrees durably marked at jacket. All conduit ends shall be trimmed
cables inside a (2) Encased or total) between termination least every 3 000 mm inside and out to remove rough edges.
nonmetallic, smooth embedded in points
wall conduit with a concrete Bushings. Where the NUCC enters a box,
circular cross section fitting, or other enclosure, a bushing or
(3) In cinder fill adapter shall be provided to protect the
conductor or cable from abrasion unless the
(4) In underground design of the box, fitting, or enclosure
locations subject to provides equivalent protection.
severe corrosive Table 9.1.1.1 Percent of Cross Section of
influences and where Conduit and Tubing for Conductors Splices and Taps. Splices and taps shall be
subject to chemicals made in junction boxes or other enclosures
for which the
assembly is Number of Conductors All Conductor Types Grounding. Where equipment grounding is
specifically approved required, an assembly containing a separate
equipment grounding conductor shall be
1 53 used.
2 31
Over 2 40 Conductor Fill. The maximum number of
conductors or cables in NUCC shall not
exceed that permitted by the percentage fill in
Table 9.1.1.1.1
Method of Wiring Clearances Securing and Supporting
Uses Permitted
ARTICLE 398 Open wiring on Open conductors shall be separated (a) Dry Locations. In dry locations, where not exposed to physical damage,
insulators shall be at least 50 mm from metal conductors shall be permitted to be separately enclosed in flexible nonmetallic tubing.
OPEN WIRING ON permitted only for raceways, piping, or other The tubing shall be in continuous lengths not exceeding 4 500 mm and secured to the
INSULATORS industrial or conducting material, and from any surface by straps at intervals not exceeding 1 400 mm.
agricultural exposed lighting, power, or
An exposed wiring establishments on signaling conductor, or shall be (b) Entering Spaces Subject to Dampness, Wetness, or Corrosive Vapors.
method using cleats, systems of 600 volts, separated therefrom by a Conductors entering or leaving locations subject to dampness, wetness, or corrosive
knobs, tubes, and nominal, or less, as continuous and firmly fixed vapors shall have drip loops formed on them and shall then pass upward and inward
flexible tubing for the follows: nonconductor in addition to the from the outside of the buildings, or from the damp, wet, or corrosive location, through
protection and support insulation of the conductor. Where noncombustible, nonabsorbent insulating tubes.
of single insulated (1) Indoors or any insulating tube is used, it shall
conductors run in or outdoors be secured at the ends. Where (c) Exposed to Physical Damage. Conductors within 2 100 mm from the floor shall be
on buildings. practicable, conductors shall pass considered exposed to physical damage. Where open conductors cross ceiling joists
(2) In wet or dry over rather than under any piping and wall studs and are exposed to physical damage, they shall be protected by one of
locations subject to leakage or the following methods:
accumulations of moisture.
(3) Where subject to 1) Guard strips not less than 25 mm nominal in thickness and at least as high as the
corrosive vapors In Accessible Attics. Conductors insulating supports, placed on each side of and close to the wiring.
in unfinished attics and roof spaces
(4) For services shall comply with the following (2) A substantial running board at least 13 mm thick in back of the conductors with
(a) Accessible by Stairway or side protections. Running boards shall extend at least 25 mm outside the conductors,
Permanent Ladder. Conductors but not more than 50 mm, and the protecting sides shall be at least 50 mm high and at
Uses Not shall be installed along the side of least 25 mm nominal in thickness.
Permitted or through bored holes in floor
Open wiring on joists, studs, or rafters. Where run (3) Boxing made in accordance with 3.98.2.6(c)(1) or (c)(2) and furnished with a cover
insulators shall not be through bored holes, conductors in kept at least 25 mm away from the conductors within. Where protecting vertical
installed where the joists and in studs or rafters to a conductors on side walls, the boxing shall be closed at the top and the holes through
concealed by the height of not less than 2 100 mm which the conductors pass shall be bushed.
building structure above the floor or floor joists shall
be protected by substantial running (4) Rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit, or
boards extending not less than 25 electrical metallic tubing. When installed in metal piping, the conductors shall be
mm on each side of the conductors. encased in continuous lengths of approved flexible tubing.
Running boards shall be securely
fastened in place. Running boards (a) Conductor Sizes Smaller Than 8.0 mm2(3.2 mm dia.). Conductors smaller than
and guard strips shall not be 8.0 mm2 (3..2 mm dia.) shall be rigidly supported on noncombustible, nonabsorbent
required for conductors installed insulating materials and shall not contact any other objects. Supports shall be installed
along the sides of joists, studs, or as follows:
rafters.
(1) Within 150 mm from a tap or splice
(b) Not Accessible by Stairway or (2) Within 300 mm of a dead-end connection to a lampholder or Receptacle
Permanent Ladder. (3) At intervals not exceeding 1 400 mm and at closer intervals sufficient to provide
Conductors shall be installed along adequate support where likely to be disturbed
the sides of or through bored holes
in floor joists, studs, or rafters. (b) Conductor Sizes 8.0 mm2(3.2 mm dia.) and Larger. Supports for conductors 8.0
mm2 (3.2 mm dia.) or larger installed across open spaces shall be permitted up to 4 500
mm apart if noncombustible, nonabsorbent insulating spacers are used at least every
1 400 mm to maintain at least 65 mm between conductors. Where not likely to be
disturbed in buildings of mill construction, 8.0 mm2(3.2 mm dia.) and larger
conductors shall be permitted to be run across open spaces if supported from each
wood cross member on approved insulators maintaining 150 mm between conductors.

(c) Industrial Establishments. In industrial establishments only, where conditions of


maintenance and supervision ensure that only licensed electrical practitioner or non
licensed electrical practitioner under the supervision of a licensed electrical practitioner
service the system, conductors of sizes 125 mm2 and larger shall be permitted to be run
across open spaces where supported at intervals up to 9 000 mm.

(d) Mounting of Conductor Supports. Where nails are used to mount knobs, they
shall not be smaller than ten penny. Where screws are used to mount knobs, or where
nails or screws are used to mount cleats, they shall be of a length sufficient to penetrate
the wood to a depth equal to at least one-half the height of the knob and the full
thickness of the cleat. Cushion washers shall be used with nails.

(e) Tie Wires. 8.0 mm2 (3.2 mm dia.) or larger conductors supported on solid knobs
shall be securely tied thereto by tie wires having an insulation equivalent to that of the
conductor.
Method of Uses Permitted Bends and Size and Securing and Supporting Construction.
Wiring markings Marking

(a) All Atmospheric Conditions and Bends — How (a) Minimum. Securing and Supporting. RMC Reaming and Threading. All cut
ARTICLE 3.44 Occupancies. Made. Bends of RMC smaller shall be installed as a complete ends shall be reamed or
Shall be permitted under all RMC shall be so than 15 mm system and shall be securely otherwise finished to remove
RIGID METAL atmospheric conditions and made that the conduit shall not be fastened in place and supported in rough edges. Where conduit is
CONDUIT: TYPE occupancies. Ferrous raceways and will not be damaged used. accordance below. threaded in the field, a standard
RMC fittings protected from corrosion and so that the cutting die with a 1 in 16 taper
solely by enamel shall be permitted internal diameter of (b) Maximum. (a) Securely Fastened. RMC shall shall be used.
A threadable only indoors and in occupancies not the conduit will not RMC larger be securely fastened within 900 mm
raceway of circular subject to severe corrosive influences. be effectively than 150 mm of each outlet box, junction box, Bushings. Where a conduit enters
cross section reduced. The radius shall not be device box, cabinet, conduit body, or a box, fitting, or other
designed for the (b) Corrosion Environments. RMC, of the curve of any used. other conduit termination. Fastening enclosure, a bushing shall be
physical protection elbows, couplings, and fittings shall field bend to the shall be permitted to be increased to provided to protect the wire from
and routing of be permitted to be installed in centerline of the Marking. Each a distance of 1 500 mm where abrasion unless the design of the
conductors and concrete, in direct contact with the conduit shall not be length shall be structural members do not readily box, fitting, or enclosure is such as
cables and for use as earth, or in areas subject to severe less than indicated in
clearly and permit fastening within 900 mm. to afford equivalent protection
an equipment corrosive influences where protected Table 2, Chapter 9. durably Where approved, conduit shall not
grounding by corrosion protection and judged identified be required to be securely fastened (Threadless. Threadless couplings
conductor when suitable for the condition. Bends — Number in in every 3 000 within 900 mm of the service head and connectors used with conduit
installed with its One Run. There shall mm. for above-the-roof termination of a shall be made tight. Where buried
integral or (c) Cinder Fill. RMC shall be not be more than the mast. in masonry or concrete, they shall
associated coupling permitted to be installed in or under equivalent of four Standard be the concrete tight type. Where
and appropriate cinder fill where subject to permanent quarter bends (360 Lengths. The (b) Supports. RMC shall be installed in wet locations, they
fittings. moisture where protected on all degrees total) standard length supported in accordance with one of shall comply with 3.14.2.1(a).
sides by a layer of non-cinder between pull points, of RMC shall be the following: Threadless couplings and
RMC is generally concrete not less than 50 mm thick; for example, conduit 3 000 mm, connectors shall not be used on
made of steel where the conduit is not less than 450 bodies and boxes. including an (1) Conduit shall be supported at threaded conduit ends unless listed
(ferrous) with mm under the fill; or where protected attached intervals not exceeding 3 000 mm. for the purpose.
Protective coatings by corrosion protection and judged coupling, and
or aluminum suitable for the condition. each end shall (2) The distance between supports Running Threads. Running
(nonferrous). be threaded. for straight runs of conduit threads shall not be used on
Special use types (d) Wet Locations. All supports, Longer or shall be permitted in accordance conduit for connection at
are silicon bronze bolts, straps, screws, and so forth, shorter lengths with Table 3.44.2.21(b)(2), provided couplings.
and stainless steel shall be of corrosion-resistant with or without the conduit is made up with threaded
materials or protected against coupling and couplings, and such supports prevent Grounding. RMC shall be
corrosion by corrosion-resistant threaded or transmission of stresses to permitted as an equipment
materials unthreaded shall termination where conduit is grounding conductor.
be permitted. deflected between supports.
(3) Exposed vertical risers from
industrial machinery or fixed
equipment shall be permitted to be
supported at intervals not exceeding
6 000 mm if the conduit is made up
with threaded couplings, the conduit
is supported and securely fastened at
the top and bottom of the riser, and
no other means of intermediate
support is readily available.

(4) Horizontal runs of RMC


supported by openings through
framing members at intervals not
exceeding 3 000 mm and securely
fastened within 900 mm of
termination points shall be
permitted.

Table 3.44.2.21(b)(2) Supports for Rigid Metal Conduit


Conduit Size Maximum Distance Between
(mm) Rigid Metal Conduit Supports
(mm)
15–20 3000
25 3600
32-40 4200
50-65 4800
80 and larger 6000
Method of Wiring Uses Permitted Uses Not Permitted Bends Size and Securing and Construction.
Marking Supporting

ARTICLE 3.52 (a) Concealed. RNC a) Hazardous Bends — How (a) Minimum. RNC RNC shall be installed Number of Conductors.
shall be permitted in Locations. Made. shown in smaller than 15 mm. as a complete system. The number of conductors
RIGID walls, floors, and (1) In hazardous Table 2, Chapter 9. shall not exceed that
NONMETALLIC ceilings. locations. (b) Maximum. RNC (a) Securely Fastened. permitted by the
CONDUIT: TYPE Bends — Number larger than raceway RNC shall be securely percentage fill specified in
RNC (b) Corrosive (b) Support of in One Run. size 150 mm shall not fastened within Table 1,
Influences. RNC shall Luminaires There shall not be be used. 900 mm of each outlet
A nonmetallic raceway be permitted in locations (Fixtures). For the more than the box, junction box, Expansion Fittings.
of circular cross subject to severe support of equivalent of four Marking. Each device box, conduit Expansion fittings for
section, with integral or corrosive influences and Luminaries (fixtures) quarter bends (360 length of RNC shall body, or other conduit RNC shall be provided to
associated couplings, where subject to or other equipment. degrees total) be clearly and termination. compensate for thermal
connectors, and fittings chemicals for which the between pull durably marked at expansion and contraction
for the installation of materials are specifically (c) Physical Damage. points, for least every 3 000 (b) Supports. RNC where the length change is
electrical conductors approved. Where subject to example, conduit mm. The type of shall be supported as expected to be 6 mm or
and cables. physical damage bodies and boxes. material shall also be required in Table greater in a straight run
(c) Cinders. RNC shall unless identified for included in the 3.52.2.21(b). Horizontal between securely mounted
be permitted in cinder such use. marking unless it is runs of RNC supported items such as boxes,
fill. visually identifiable. by openings through cabinets, elbows, or other
(d) Ambient For conduit framing members at conduit terminations.
(d) Wet Locations. RNC Temperatures. Where recognized for use intervals not exceeding
shall be permitted in subject to ambient above ground, these those in Table Bushings. Where a conduit
portions of dairies, temperatures in excess markings shall be 3.52.2.21(b) and enters a box, fitting, or
laundries, canneries, or of 50°C . permanent. For securely fastened within other enclosure, a bushing
other wet locations and conduit limited to 900 mm of termination or adapter shall be
in locations where (e) Insulation underground use points shall be provided to protect the
walls are frequently Temperature only, these markings permitted. wire from abrasion unless
washed, the entire Limitations. For shall be sufficiently the box, fitting, or
conduit system including conductors or cables durable to remain enclosure design provides
boxes and fittings used operating at a legible until the equivalent protection.
therewith shall be temperature higher material is installed.
installed and equipped so than the RNC listed Conduit shall be Grounding. Where
as to prevent water from operating temperature permitted to be equipment grounding is
entering the conduit. All rating. surface marked to required, a separate
supports, bolts, straps, indicate special equipment grounding
screws, and so forth, (f) Theaters and characteristics of the conductor shall be installed
shall be of corrosion- Similar Locations. In material. in the conduit.
resistant materials or be theaters and similar
protected against locations.
corrosion by approved
corrosion-resistant
materials.

(e) Dry and Damp


Locations. RNC shall be
permitted for use in dry
and damp locations.

(f) Exposed. RNC shall


be permitted for exposed
work where not subject
to physical damage if
identified for such use.

(g) Underground
Installations. For
underground
installations.

Table 3.52.2.21(b) Support of Rigid Nonmetallic Conduit (RNC)

Conduit Raceway Size Maximum Spacing Between


(mm) Supports
(mm)
15-25 900
32-50 1 500
65-80 1 800
90-125 2 100
150 2 400
Method of Wiring Uses Permitted Uses Not Permitted Bends Construction.

ARTICLE 3.40 — (1) For use underground, including (1) As service-entrance cable Type UF cable shall be so Conductors. The conductors shall
direct burial in the earth. made that the cable is not be sizes 2.0 mm2 (1.6 mm dia.)
UNDERGROUND (2) In commercial garages damaged. The radius of the copper or 3.5 mm2 (2.0 mm dia.)
FEEDER AND (2) As single-conductor cables. curve of the inner edge aluminum or copperclad
BRANCH-CIRCUIT Where installed as single conductor (3) In theaters and similar locations of any bend shall not be less aluminum through 100 mm2.
CABLE: TYPE UF cables, all conductors of the feeder than five times the diameter
grounded conductor or branch circuit, (4) In motion picture studios of the cable. Equipment Grounding. In
A factory assembly of including the grounded conductor and addition to the insulated
one or more insulated equipment grounding conductor, if (5) In storage battery rooms conductors, the cable shall be
conductors with an any. permitted to have an insulated or
integral or an overall (6) In hoistways or on elevators or bare conductor for equipment
covering of nonmetallic (3) For wiring in wet, dry, or escalators grounding purposes only.
material suitable for corrosive locations.
direct burial in the earth. (7) In hazardous (classified) Sheath. The overall covering shall
(4) Installed as nonmetallic-sheathed locations be flame retardant; moisture,
cable. Where so installed, the fungus, and corrosion resistant; and
installation and conductor shall be of (8) Embedded in poured cement, suitable for direct burial in the
the multiconductor type. concrete, or aggregate where earth.
embedded in plaster.
(5) For solar photovoltaic systems in
accordance with 6.90.4.1. (9) Where exposed to direct rays of
the sun, unless identified as
(6) As single-conductor cables as the sunlight resistant
nonheating leads for heating cables.
(10) Where subject to physical
(7) Supported by cable trays. Type damage
UF cable supported by cable trays
shall be of the multiconductor type. (11) As overhead cable, except
where installed as messenger
supported wiring.