Turbo-generator have been built in America in sizes exceeding 100,000 kVA output at 1,800
and 3,600 rpm. Machines of European design have been built in single units larger than 100,000
kVA output at speeds of 1,500 and 3,000 rpm. With the great weight of the slotted rotors, carrying
insulated exciting coils and travelling at very high peripheral velocities, new problems have arisen,
and those problems should be seriously studied by anyone proposing to take up the design of
modern electrical machinery. Engineering textbooks may constitute a basis of necessary
knowledge; but, with the rapid advance in this field of electrical engineering, the information of
greatest value (apart from what the manufacturing firms deliberately withhold) is to be found in
current periodical publications, including the papers and discussions appearing in the journals of
the engineering societies.
Since it will not be possible to discuss the mechanical details of turbo-generator designs in
these pages, a machine of small size (4500 kVA) has been chosen, and the peripheral speed of the
rotor will not be permitted to exceed 18,000 fpm. The mechanical difficulties will, therefore, not
be so great as in some of the larger machines running at higher peripheral velocities, and the
electrical features of the design will be considered alone, reference being made to mechanical
details only as occasion may arise.
Although this problem deals with the design of an armature for a high speed machine provided
with a cylindrical field magnet, an attempt will be made to ender it of use in the design pf armatures
for slow speed salient-pole machines, and with this end in view, the items in the design sheets as
shown on page 199 are arranged so as to cover both types of machines.
CALCULATIONS
Items 1 to 3: With a frequency of 60 cycles per sec and a speed of 1,800 rpm, the number of
poles is;
2 𝑥 60 𝑥 60
𝑝= =4
1,800
Since the air gap is not likely to be much less than 1 in., let us decide upon an internal diameter
of the armature D = 35 in., (Item 11) and determine the exact dimensions of the rotor after the air
gap has been decided upon.
4500000
𝛪= = 787.296 𝑎𝑚𝑝𝑠
√3 𝑥 3,300
and, if was select the star connection of phases, this is also the current per phase winding (Item 8).
Referring to Art. 71 for values of the specific loading, we find that the average value there
suggested is ԛ = 750.
𝜋 𝑥 35
𝑟= = 27.49 𝑖𝑛.
4
1
(𝑇𝐼)𝑎 = [(27.49 𝑥 800 ) 𝑥 ] = 10996
2
Referring to Art. 72, we can get a preliminary idea of the required length of air gap. We shall,
in this design, deliberately select a high value for the air gap flux density and, if necessary, saturate
the teeth of the rotor while keeping the density in the armature teeth within reasonable limits to
prevent excessive hysteresis and eddy-current loss. Let us try 𝐵𝑔" = 39,000 𝑙𝑖𝑛𝑒𝑠 𝑝𝑒𝑟 𝑠𝑞. 𝑖𝑛., which
is higher than the upper limit of
DESIGN SHEET FOR ARMATURE A-C GENERATOR
(Dimensions in inches unless otherwise stated)
Assumed or
Symbols Final values
approximate values
800 𝑥 27.49 7
𝛿 = 1.25 = 0.704, 𝑜𝑟 (𝑠𝑎𝑦) 𝑖𝑛.
39,000 10
In case of medium-speed salient-pole designs, the peripheral velocity would be decided upon
by merely selecting the upper limit of 8,000 fpm as given in Art. 68. This has to be considered in
connection with the pole pitch (see Art. 71), a preliminary diameter of rotor being selected in
keeping with what seems to be a reasonable pole pitch. A few rough calculations will very soon
show whether or not the tentative value of r will lead to a suitable axial length of armature core.
Items 15 to 20. On the basis of ԛ = 800, the number of conductors per phase would be
1 𝜋 ∗ 800 ∗ 27.49
𝑍= ( ) = 29.25
3 787.296
With three slots per pole per phase, and three conductors in each slot, we have Z = 3 x 3 x 4 =
36, which is close enough to the desired value. Furthermore, the fact that each slot will contain
three conductors, so odd number, means that only a single-layer winding is possible; a double-
layer winding always involves an even number of conductors per slot. Each of the six coils per
phase will, therefore, have three turns in series [(36⁄(2𝑥6)) = 3]. To construct such a single layer
winding in a 36-slot core requires a coil span of 9 slots; i.e., the coil pitch must be from slot 1 to
slot 10, from an odd-numbered to an even-numbered slot. Such a pitch, one slot beyond full pitch,
is electrically equivalent to a fractional pitch winding each of whose coils is one slot short of full
pitch or 180 electrical degrees. Therefore, 𝑘 ′ = sin(160⁄2) = 0.985. Also, with three slots per
A complete diagram showing the coil arrangement and winding connections is given in Fig. 03.
For Item 19 we have 𝜆 = 27.49⁄9 = 3.054 𝑖𝑛., giving a corrected value for peripheral loading
of
787.3 𝑥 3
ԛ= = 773.4 (𝑎𝑝𝑝𝑟𝑜𝑥)
3.054
Items 21 to 24. For the purpose of calculating the flux required on open circuit, we may use
formula (64a) of Art. 69, where 𝐸𝑝𝑒𝑟 𝑝ℎ𝑎𝑠𝑒 = 3,300⁄ . The required flux per pole is, therefore.
√3
3,300 𝑥 108
ɸ= = 4.202 𝑥 107 𝑚𝑎𝑥𝑤𝑒𝑙𝑙𝑠
√3 𝑥 2.22 𝑥 0.9456 𝑥 60 𝑥 36
Figure 1. Winding Diagram of the Proposed Design
With the assumed value of 39,000 lines per sq. in., for 𝐵𝑔" , the axial length of armature core
will be
4.202 𝑥 107
𝑙𝑎 = = 39.2 𝑖𝑛. , 𝑜𝑟 (𝑠𝑎𝑦) 39 𝑖𝑛.
39,000 𝑥 27.49
This is a short armature for a machine with a rotor of 33.95 in. in diameter; but it is what we
are aiming at, and, if the field winding can be accommodated in the space available, the design
should be satisfactory.
We shall attempt to ventilate this generator by means of axial air ducts only, which is
admittedly not in accordance with modern practice for the larger steam-turbine-driven generators
but should be satisfactory in connection with this machine of comparatively small size. If, then,
there are no radial air spaces, the net length of iron in the armature core will be approximately
𝑙𝑛 = 0.92(39 𝑖𝑛. ) = 35.9 𝑖𝑛. (Art 16); but these dimensions cannot be finally decided upon until
the slot proportions and tooth densities have been settled.
Items 25 to 30. As previously pointed out, a single-layer winding must be used (see Art. 73).
The current density in the armature windings cannot be determined by the empirical formula of
Art. 74, because this is not applicable to speeds higher than 8000 fpm, and, in any case, the
conditions of cooling in an enclosed machine with forced ventilation are not the same as for a self-
ventilating generator. In a turbo-alternator there is usually plenty for the armature conductors, the
chief trouble being with the rotor winding which may have to be worked at a high current density.
There is no definite rule for the most suitable current density in the armature conductors, the
permissible copper cross section being dependent on the length of armature core, the position and
area of the vent ducts, and supply of air that can economically be passed through the machine.
The specific loading will be obviously having some effect on the allowable current density in the
copper, and, as a guide in making a preliminary estimate, we may use the formula
1,600,000
∆=
773.4
which gives us for item 26 a current density of 2,069 amp per sq. in. of armature copper.
It is well to laminate the conductors in a direction parallel to the slot-leakage flux, and we may
build up each conductor of four flat strips each 2⁄3 by 0.14 in., giving a total cross-section of 0.38
There will be 12 copper strips in each slot, the total thickness including the cotton insulation
being about 1.92 in. To determine the slot insulation, formula (16) in Art. 13 cannot be used since
it applies to machine which agrees with modern practice is
The slot insulation will, therefore, be 50 + (3,300⁄55) = 110 𝑚𝑖𝑙𝑠, and the total slot space
for winding and insulation will be in 0.89 in., wide by 2.14 𝑖𝑛. deep. The thickness of wedge might
be 3⁄8 𝑖𝑛., and we shall, in this design, allow an extra slot depth of 1 1⁄2 𝑖𝑛., above the wedge,
with a view to increasing the slot inductance, and so limiting the instantaneous rush of current n
the event of a short circuit. The increased armature inductance might have been obtained by using
a smaller width and greater depth of copper conductor; but, in as much as the width of tooth will
probably be sufficient, the proposed design of slot (as shown in Fig. 94) has the advantage that the
eddy-current loss in the armature inductors will be very small.
The width of copper strip has been selected to fit into the 0.89-in., slot, because this seems to
provide a suitable cross section for the stator tooth. Thus, a section halfway down the tooth, or
(say) 2 in., from the top, will have a diameter of 39 in., and the average width of tooth will be
(𝜋 𝑥 39)⁄ "
[ 36] − 0.89 = 2.513 𝑖𝑛. On the basis of 𝐵𝑔 = 38,000 𝑙𝑖𝑛𝑒𝑠 𝑝𝑒𝑟 𝑠𝑞. 𝑖𝑛. and sinusoidal
flux distribution over the pole pitch, the “apparent” tooth density (item 30) would be
Items 31 to 35. Assuming a flux density of 55,500 lines per sq. in., in the armature core (see
Art. 79), the net radial depth of stamping below slots will be
4.202 𝑥 107
= 10.54 𝑖𝑛.
2 𝑥 55,500 𝑥 35.9
The actual radial depth should be greater than this to allow for the reduction of section due
to the presence of axial ducts. In this particular machine it is proposed to ventilate, if possible, with
axial ducts only, and a fairly large cross section of air passages must, therefore, be allowed. An
adequate supply of air will probably be obtained if the total cross section of air duck through the
body of the stampings in square inches not less than 0.005 x cubic inches of iron stator below slots.
In this case the volume of iron in the stator ring will be approximately 𝜋(43 +
10.54) 𝑥 10.54 𝑥 35.9 = 63644 𝑐𝑢 𝑖𝑛. ; and the total cross section of air ducts in the stampings
should be 0.005 x 63644 = 318.22 sq. in.
The actual radial depth of stamping below the teeth can be calculated by assuming that the
318.22
air ducts reduce the gross depth by an amount equal to ,
𝑎𝑣𝑒𝑟𝑎𝑔𝑒 𝑐𝑖𝑟𝑐𝑢𝑚𝑓𝑒𝑟𝑒𝑛𝑐𝑒
318.22
𝑜𝑟 (𝑠𝑎𝑦) = 1.911 𝑖𝑛. Let us make the depth 𝑅𝑑 (Item 32) = 12 in., and provide vent ducts
𝜋 𝑥 53
arranged generally as shown Fig. 95, where there are 10 holes per slot, each 1 1⁄4 𝑖𝑛. in diameter,
π
making a total air duct cross section in the armature stampings (4 ) x (1.25)2 x 10 x 36 =
441.79 𝑠𝑞 𝑖𝑛.
Items 36 to 39. In a machine of so large an output as the one under consideration, the weight
and cost of copper should be determined by making a drawing of the armature coils and carefully
measuring the length required.
Since this design is being worked out for the purpose of illustration only, we shall use the
formula (71) of page 188 and assume the length per turn of armature winding (item 36) to be
It will be safer to use the figure 167 in. for this mean length, because all the coils will probably
be bent back and secured in position by insulated clamps in order to resist the mechanical forces
which tent to displace or bend the coils when a short circuit occurs.
The cross section of the conductors (four strips parallel) is 0.38 sq. in., or 483,800 cir mils. The
number of turns per phase is 18, and, since the resistance per circular-mil-inch at 60°C is 1 ohm,
(167 𝑥 18)⁄
the resistance per phase at 60°C is 483,800 = 0.00621 𝑜ℎ𝑚. The IR drop per phase
(Item 38) is 0.00621 x 787.296 = 4.89, or (say) 5.34 volts, in order to include the effect of eddy
currents in the conductors. The 𝐼 2 𝑅 loss in armature winding (item 39) is 3 x 0.00621 x (787.296)2
= 11,547.5 watts, which should be increased about 50 per cent (see Art. 79) to cover sundry
indeterminate load losses. The total full-load armature copper loss may, therefore, be estimated
at (1.5*11547.5)= 17.321 kW, or 0.3849 per cent of the rated full-load kilovolt-ampere output.
Items 40 and 41. These are included because they would be required in connection with the
design of the self-ventilated, slow-speed, open-type generator for which the calculations are made
generally as for a dc generator (refer to Art. 60). In the case of a turbo-alternator cooled by forced
ventilation, the necessary supply of air to be passed through the machine windings, have been
determined.
Items 42 and 43. The reactive voltage drop per phase due to the cutting of the end flux cannot
be predetermined accurately; but we may use the empirical formula (75) of Art. 78, wherein the
symbols have the following numerical values:
The equivalent average projections of the winding beyond the ends of the slots may be
computed by nothing that, with a mean length per turn of 167 in., the average projection beyond
ends of slots will be
Since we have a single-layer winding, the factor 𝜋⁄2 must be introduced into the formula
(75), whence with the current 𝐼𝑐 = 700 the reactive voltage due to cutting of end flux, with full-
load current per phase, is-
𝜋
787.296 𝑥 𝑥 3√2 𝑥 3.5(0.9456)2 60(3 𝑥 3)2 4 𝑥 21.6 𝑥 10−8 = (𝑠𝑎𝑦) 70 𝑣𝑜𝑙𝑡𝑠
2
We are now in a position to draw a vector diagram similar to Fig. 90 and calculate the length
of the vector 𝑂𝐸𝑑 which represents the full-load developed voltage and is, therefore, a measure
of the flux actually cut by the conductors at full-load. (The flux entering the teeth through the air
gap is somewhat greater, since it must include the slot-leakage flux which is not cut by the
conductors and, therefore, does not produce an emf in the armature windings.). The numerical
values of the component vectors are:
The angle Ѳ is 31°47’18”, since the power factor cos Ѳ is specified as 85 per cent. Thus, the full-
load developed voltage (item 43) is
The design of the field magnet (rotor) for this machine will be taken up at the close of the next
chapter.