You are on page 1of 4

TECHNICAL PARTICULARS AND GUARANTEES

PEMBANGUNAN GI 150 kV RENGAT


EXT. 1 TRANSFORMER BAY (1 X 60 MVA) 1 COUPLER BAY

TPG 7 : 150 KV STRING INSULATOR (CAP AND PIN INSULATOR UNIT)

NO. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

I Insulator Disc
1 Manufacturer To be mentioned GIG

2 Designation U 120 B U 120 B


3 Appropriate IEC Standars 60305 60305, 60383-1
4 Material of Insulator Porcelain or Toughened Glass Toughened Glass
5 Dimension mm x mm 255 (max.) x 146 255 x 146
6 Minimum nominal creepage distance mm 320 320
7 Electromechanical or mechanical failing load kN 120 120
8 Type of coupling mm 16 16
9 Impulse puncture testing in air kV To be mentioned 110
10 Power Frequency Withstand Voltage :
- Minimum wet power-frequency withstand voltage test kV 40 40
11 Impulse Withstand Voltage (1.2 x 50 us) :
- Minimum positive lightning impulse withstand voltage test kV 110 110
- Minimum negative lightning impulse withstand voltage test kV 110 110
12 Net weight of one unit kg To be mentioned 3.9
13 Colour of the insulator :
- Porcelain Brown N/A - We Proposed Glass Type
- Glass To be mentioned Green

MANUFACTURER'S SIGNATURE MANUFACTURER'S SIGNATURE

(.....................................) (.....................................) 1 dari 8


TECHNICAL PARTICULARS AND GUARANTEES
PEMBANGUNAN GI 150 kV RENGAT
EXT. 1 TRANSFORMER BAY (1 X 60 MVA) 1 COUPLER BAY

TPG 7 : 150 KV STRING INSULATOR (CAP AND PIN INSULATOR UNIT)

NO. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

Single Single Single Single


Suspension set Tension set Suspension set Tension set

II Insulator sets
1 Number of strings and dics per string :
- For Medium Polution (U 120 B) unit 1 x 12 1 x 12 1 x 12 1 x 12
2 Length of string when stretched mm To be mentioned To be mentioned 2879 3153
3 Minimum Overall creepage distance mm 3840 3840 3840 3840
4 Net weight of one set kg To be mentioned To be mentioned 62.8 62.8
5 Ultimate breaking strength of string kN 1 x 120 1 x 120 1 x 120 1 x 120
6 Withstand voltage without arcing horn :
- Wet power-frequency withstand voltage test kV To be mentioned To be mentioned 40 40
- Dry lightning impulse withstand voltage test (1.2 x 50 us) kV To be mentioned To be mentioned 110 110
7 Withstand voltage with arcing horn :
- Wet power-frequency withstand voltage test kV To be mentioned To be mentioned 40 40
- Dry lightning impulse withstand voltage test (1.2 x 50 us) kV To be mentioned To be mentioned 110 110

8 Arcing horn gap (approximately) :

- For Medium Pollution (U 120 B) mm 1400 1400 1400 1400

MANUFACTURER'S SIGNATURE MANUFACTURER'S SIGNATURE

(.....................................) (.....................................) 2 dari 8


TECHNICAL PARTICULARS AND GUARANTEES
PEMBANGUNAN GI 150 kV RENGAT
EXT. 1 TRANSFORMER BAY (1 X 60 MVA) 1 COUPLER BAY

TPG 7 : 150 KV STRING INSULATOR (CAP AND PIN INSULATOR UNIT)

NO. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

III Single Tension Insulator String

1 Number of strings and dics per string (for Jumper) 1 x 12 1 x 12

2 Length of string when streched mm To be mentioned 3153

3 Minimum Overall creepage distance mm 3840 3840

4 Wet weight of one set kg To be mentioned 62.8

5 Ultimate breaking strength of string kN 1 x 120 1 x 120

6 Withstand voltage without arcing horn :


- Wet power-frequency withstand voltage test kV To be mentioned 40
- Dry lightning impulse withstand voltage test (1.2 x 50 us) kV To be mentioned 110

IV Single Suspension Insulator String

1 Number of strings and dics per string (for Jumper) 1 x 12 1 x 12

2 Length of string when streched mm To be mentioned 2879

3 Minimum Overall creepage distance mm 3840 3840

4 Wet weight of one set kg To be mentioned 62.8

5 Ultimate breaking strength of string kN 1 x 120 1 x 120

6 Withstand voltage without arcing horn :


- Wet power-frequency withstand voltage test kV To be mentioned 40
- Dry lightning impulse withstand voltage test (1.2 x 50 us) kV To be mentioned 110

MANUFACTURER'S SIGNATURE MANUFACTURER'S SIGNATURE

(.....................................) (.....................................) 3 dari 8


TECHNICAL PARTICULARS AND GUARANTEES
PEMBANGUNAN GI 150 kV RENGAT
EXT. 1 TRANSFORMER BAY (1 X 60 MVA) 1 COUPLER BAY

TPG 7 : 150 KV STRING INSULATOR (CAP AND PIN INSULATOR UNIT)

NO. DESCRIPTION UNIT REQUIRED PROPOSED AND GUARANTEE

V Fittings
1 Supension Clamps Trunion & Strain
Manufacturer's name To be mentioned PLP
Materials (Body) Aluminium Alloy Aluminium Alloy
Type To be mentioned Trunion & Strain
Applied conductor Comply with conductor type Yes
Armour rod No
Ultimate breaking strength kN To be mentioned 80 KN
Slip strength kN To be mentioned 5 - 30 % UTS Conductor
2. Tension Clamps Copression Type
Manufactures's name To be mentioned PLP
Material :
* Dead end body and jumper connector Aluminium Alloy Aluminium Alloy
Minimum tensile strength :
* Dead end clamp kN To be mentioned 25% UTS Conductor
Ultimate breaking strength kN To be mentioned 95% UTS Conductor

VI Document to be submitted for all materials


Type and Routine Test Certificates acc. To IEC - To be submitted Yes
Catalog, drawing or other references - To be submitted Yes

MANUFACTURER'S SIGNATURE MANUFACTURER'S SIGNATURE

(.....................................) (.....................................) 4 dari 8