You are on page 1of 1

8 7 6 5 4 3 2 1

C
L Wall
THIS PRINT IS THE PROPERTY OF SMV ENGINEER'S IT IS TO BE USED ONLY FOR THE PURPOSE FOR WHICH IT WAS LENT AND MUST NOT BE USED ON ANY DETERIMENTAL TO THE INTEREST OF THIS COMPANY AND IT IS SUBJECT TO RETURN ON DEMAND.

225 125 100

50 M16 ANCHOR BOLT


FFL 300 DEEP

50
POCKETS
E E

250
300
100THK. COMPACTED 9 NOS
COARSE SAND TYP
75 x 75 x 300 DEEP POCKETS
100THK. PCC (1:4:8) FOR M16 x 250 LONG ANCHOR BOLT
8 0@150 C/C
WELL COMPACTED FGL RING (IN VENDER SCOPE)
SOIL / MURRUM
6-12 0 M
A OF
BE
300

RC
RC BE
NGL OF AM
HOLD FAST (STUD) OD
75x75x75 DEEP
350

D
SHEAR POCKETS

BC
UP TO GOOD SOIL

A
D @ 450 C/C D
620
MINIMUM 1000

BRICK MASONRY
IN CM 1:5

A
50

FOUNDATION PLAN
230

450
1:75

Z:\02. Current Projects\2019\(5) INDIAIN JOBS\519012_Bluetex\2) Drawings\2. STRUCTURE\519012-RC-ST-01_LAYOUT & DETAIL OF FOUNDATIONS FOR FIRE WATER STORAGE TANK.dwg
200 150

PCC (1:4:8)

TRENCH FILLING WITH 200 THK. SAND FILLING


WELL COMPACTED
C COARSE SAND WELL COMPACTED EARTH C
225 375 375
750

SECTION -A
FOUNDATION DETAIL FOR FIRE WATER
STORAGE TANK
1:20

R0 03.03.2020 ISSUED FOR CONSTRUCTION MIRAL ASP

B REV.NO. DATE DESCRIPTION DRAWN CHECKED

NOTE: CLIENT :
BLUETEX INDIA PVT LTD.
ABBREVIATIONS. 1. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS ARE IN METERS UNLESS
SPECIFIED OTHERWISE.
FGL = FINISHED GROUND LEVEL 2. ALL REINFORCEMENT SHALL BE FE 500D TMT BARS CONFORMING TO IS:432.
3. ALL CONCRETE GRADE SHALL BE M:25 MACHINE MIXED & MACHINE CONSULTANT: SMV ENGINEERS
NGL = NATURAL GROUND LEVEL 2ND FLOOR, MAHARSHI COMPLEX,
VIBRATED.
FFL = FINISHED FLOOR LEVEL NEAR SARDAR PATEL BAVLA, AHMEDABAD-380014
4. LAYOUT AND DIMENSION TO BE CHECKED WITH VENDOR AS WELL AS PHONE: 079-48901473 EMAIL:admin@smvengineers.com
// = PARALLEL ARCHITECT DRAWINGS & IF ANY AMBIGUITY IS THERE, CONTACT ENGINEER
A
THK = THICKNESS IN-CHARGE PRIOR TO PROCEED. DRAWN MIRAL 03.03.2020 TITLE:- LAYOUT & DETAIL OF FOUNDATIONS
= 5. READ THIS DRAWING IN CONJUNCTION WITH DRAWING NO
TYP = TYPICAL CHECKED PVP 03.03.2020 FOR FIRE WATER STORAGE TANK
RSPL-BVL-GAD-01.
TOC TOP OF CONCRETE 6. FOR ALL RC WORK CLEAR COVER TO MAIN REINFORCEMENT SHALL BE APPROVED ASP 03.03.2020 SHEET NO. JOB. NO. DRG. NO. REV.
BCD = BOLT CENTER DIA. a. BEAM - 30mm
8 7 6 5 4 SCALE 1:50 01 OF 15 519012 519012-RC-ST-01 R0
PAPER SIZE: A2

You might also like