1.1 Specifications
1. G Series Control Panels Table 1: D8129 Specifications
The D8129 OctoRelay Module allows the addition of
relay outputs to the system in groups of eight to the G-
Series Control Panels (D9412G/D7412G/D7212G). On Power Nominal 12 VDC supplied by the control
the D9412G, up to 128 OctoRelay outputs (relay panel
numbers 1 to 128) can be added to the system using 16 Current Idle 20 mA
Required Maximum 200 mA (all relays
OctoRelay modules. The D7412G allows up to 64
energized)
relay outputs. Review the Power Outputs section in the
D9412G/D7412G Operation and Installation Guide Wire D8112 16 AWG to 22 AWG
Requirement Series (1.5 mm to 0.8 mm) from
(P/N: 43488) to be sure to provide enough power for 8112 Series Control Panel
the OctoRelays and other powered devices that will be to D8129 (up to 61 m
connected to the system. [200 ft.])
The D7212G supports up to 24 output relays (three G Series 16 AWG to 22 AWG
D8129 OctoRelay Modules). Review the Power Outputs (D9412G/ (1.5 mm to 0.8 mm) from
D7412G/ G Series Control Panel to
section in D7212G Operation and Installation Guide D7212G) D8129 (up to 1.5 m [5 ft.])
(P/N: 4998138544).
Relay Output Form “C” dry contact (1.0 Amp at
OctoRelays for relay numbers 1 to 64 connect to 12 VDC). During pulsed output, relay
ZONEX 1, Terminal 28. OctoRelays for relay numbers maintains closure for minimum of 1 second
65-128 connect to ZONEX 2, Terminal 26 (D9412G
only). See Figure 1 and Figure 2.
1.2 D8129 Configuration
Five switches on the OctoRelay determine the relay
Alarm output, auxiliary relay, sensor reset, arming
numbers for the eight relay outputs. Table 2 shows the
status, point status, alarm memory, or remote functions
switch settings.
can be assigned to the OctoRelay outputs individually.
See the Relay Parameters section in the D9412G/D7412G Table 2: D8129 OctoRelay Switch Settings
Program Entry Guide (P/N: 47775) and the D7212G
Program Entry Guide (P/N: 4998138538) for
programming details. Relay D8129 DIP Switch Connect to Control
Number Setting Panel:
The D8129 relay outputs are not 1 to 8 OFF-ON-ON-ON-ON ZONEX 1 Terminal 28
supervised and cannot be used in fire or 9 to 16 ON-OFF-ON-ON-ON ZONEX 1 Terminal 28
combined fire/burglary installations for 17 to 24 OFF-OFF-ON-ON-ON ZONEX 1 Terminal 28
primary indicating devices. 25 to 32 ON-ON-OFF-ON-ON ZONEX 1 Terminal 28
33 to 40 OFF-ON-OFF-ON-ON ZONEX 1 Terminal 28
41 to 48 ON-OFF-OFF-ON-ON ZONEX 1 Terminal 28
49 to 56 OFF-OFF-OFF-ON-ON ZONEX 1 Terminal 28
57 to 64 ON-ON-ON-OFF-ON ZONEX 1 Terminal 28
D9412G Only
65 to 72 OFF-ON-ON-ON-ON ZONEX 2 Terminal 26
73 to 80 ON-OFF-ON-ON-ON ZONEX 2 Terminal 26
81 to 88 OFF-OFF-ON-ON-ON ZONEX 2 Terminal 26
89 to 96 ON-ON-OFF-ON-ON ZONEX 2 Terminal 26
97 to 104 OFF-ON-OFF-ON-ON ZONEX 2 Terminal 26
105 to ON-OFF-OFF-ON-ON ZONEX 2 Terminal 26
112
113 to OFF-OFF-OFF-ON-ON ZONEX 2 Terminal 26
120
121 to ON-ON-ON-OFF-ON ZONEX 2 Terminal 26
128
Reset Pin
Disable All Except Battery
Charging And Programming
ZONEX OUT 2 26
5
ZONEX IN 2 25
ZONEX POWER + 24
ZONEX COMMON 23
Point 8 PROG
GND FAULT CONN
Detect
D 4 GND
E
N
A
S
A
I
AUX
3
B B
L
21 22 E
L
E
GRN DATA
1 2 3 4 5 6 7 8
1 Pin
RED Low Battery Battery
amming
E CONNECTIONS
CLASS 2 TRANS POWER + 32
1 16.5 VAC 40 VAC
Part No. D1640
Internally Fuse
Requires Unsw DATA BUS A 31
2 Do Not Share
BATTERY N 29
4 COMMON
Maximum Charging
Current 1.4 Amps.
5 BATTERY POSITIVE ONLY ZONEX OUT 1 28
PR
6 RELAY A AL ZONEX IN 1 27
7 RELAY B
Re
3
8 RELAY C
GND
9 COMMON
AUX 2
10 EARTH GRO DATA
GROUND FAUL
PROG
CONN
1 2 3 4 5 6 7 8
3 3
4 4
2.2 Installation
The OctoRelay Module is designed for mounting as Figure 4: D8129 Wire Connections
follows:
• As a local installation, inside the control panel
1 2
enclosure
• As a remote installation, in a separate security 31 DATA
enclosure
4 AUX
When mounting the D8129 inside the enclosure (such
as the D8103, D8108A, D8109, or the D203), align the
3 GND
module with any of the four mounting locations and
secure the module in place with three mounting screws,
1 - D8112 Terminal
or use a D137 Mounting Bracket. See Figure 3.
2 - D8129 Terminal
Figure 3: Mounting the D8129 2.4 Relay Outputs
Each relay output provides a Normally-Open and a
1 Normally-Closed output. Three terminals are available
4 in each relay output position: (1) Normally-Open, (2)
Common [pole], and (3) Normally-Closed. The
silkscreen on the edge of the D8129 circuit board
clearly identifies the function of each terminal and the
relay output number.
The middle terminal of each output position is the pole
of the relay and is labeled COMM. When the relay is
in an inactive state, the Normally-Closed terminal
(labeled NC) has continuity with the COMM terminal.
When the relay is in an active (energized) state, the
5 3
Normally-Open terminal (NO) has continuity with the
2 COMM terminal.