Professional Documents
Culture Documents
Storage requirements
Chapter 15- Protection of palletized, solid-piled, Bin box, shelf, or back to back shelf
storage of plastic and rubber commodities
Chapter 16- Protection of Rack storage of class 1 through class 4 Commodities
Chapter 17- Protection of Rack storage of plastic and rubber commodities
Chapter 18- Protection of rubber Tire Storage
Chapter 19- Protection of Roll Paper
requirements
Chapter 24 – Water Supplies
Chapter 25- System Acceptance
Chapter 26- Marine systems
Chapter 27 – System Inspection, Testing and Maintenance.
The size of the bubble and the expansion rate of the liquid
establish the operating temperature of the sprinkler.
10
6.2 : Sprinklers
• Cl. 6.2. – Special Coating
# 6.2.6.1 – Corrosion Resistance
Listed corrosion resistance sprinklers shall be installed in locations where chemicals,
moisture, or other corrosive vapors sufficient to cause corrosion of such devices exits.
Example locations :
(1) Paper mills
(2) Packing houses
(3) Tanneries
(4) Alkali plants Attempting to remove the paint from a sprinkler by scraping
or by use of chemical paint removers could cause unseen
(5) Organic fertilizer plants etc. damage that could adversely affect the operation of the
sprinkler
CFI-1 Exam Preparation- Mehboob Shaikh(CFPS, CFI, AMIE) 11
6.2 : Sprinklers
• Cl. 6.2. – Special Coating
# 6.2.6.4- Protective Covering
Where Protected in accordance with 6.2.6.4.1 (regarding spray areas, rooms etc.)
Cellophane bags having thickness of 0.003 inch or less or thin paper bag shall be
used.
The gauges required need only be approved, not listed, as with other
system components whose failure does not cause a detrimental effect on
the proper operation of the sprinkler system
CFI-1 Exam Preparation- Mehboob Shaikh(CFPS, CFI, AMIE) 19
7.1 : Wet Pipe System
# 7.1.1 – Pressure Gauges
.
#7.1.2.1 - shall be provided with a listed relief valve not less than
½ in. (12 mm) in size and set to operate at 175 psi (12.1 bar) or 10
# 7.2.3.7.1
# 7.2.3.7.2
# 7.2.3.7.3
When dry pipe sprinkler systems are ‘trip tested’ for acceptance, the
following events occur after the inspectors test valve is opened.
1. Air pressure begins to drop in the system as a result of the open
inspectors test valve. The loss of air pressure in the system causes the
dry pipe valve to trip at its designed air/water ratio, or when an
optional accelerator trips the valve on loss of air pressure.
2. When the valve trips, water begins to fill the system by compressing
trapped air and forcing air from the inspector’s test connection.
3. Water reaches the test connection and a steady water discharge is
established.
FF Design- Mehboob Shaikh(CFPS, CFI, AMIE)
The dry pipe valve trip pressure
• Different models of dry pipe valves trip at different water to air
pressure ratios.
• A typical Water to Air Ratio = 5.5 : 1
1128.6 gallon (4272 liter) capacity (20 lines by 20 lines sprinklers) 410.8 gallon (1555 liter) capacity (10 lines by 10 lines sprinklers)
• All of the trapped air in the system has to be vented from the
sprinkler prior to water arrival.
• In the smaller system, there are no pockets of air to compress, or
non-flowing volumes for the water front to push the air except out of
the open sprinkler.
• The single open sprinkler cannot exhaust air as fast as the 6"(150mm)
riser can fill the system causing back pressure of air and slowing the
fill rate of water.
#7.4.4.1 Where more than 275 sprinklers are required in a single fire area,
the system shall be divided into sections of 275 sprinklers or fewer by means
of check valves.
#7.4.4.2 Where the system is installed in more than one fire area or story,
not more than 600 sprinklers shall be supplied through any one check valve.
#7.4.4.3 Each section shall have a 11⁄4 in. (32 mm) drain on the system side
of each check valve supplemented by a dry pipe system auxiliary drain.
(5) When sprinklers are specifically tested and test results demonstrate that deviations
from clearance requirements to structural members do not impair the ability of the
sprinkler to control or suppress a fire, their positioning and locating in accordance with the
test results shall be permitted.
(6) Clearance between sprinklers and ceilings exceeding the maximums specified in this
standard shall be permitted, provided that tests or calculations demonstrate comparable
sensitivity and performance of the sprinklers to those installed in conformance with these
sections.
(7) Furniture, such as portable wardrobe units, cabinets, trophy cases, and similar features
not intended for occupancy, does not require sprinklers to be installed in them. This type of
feature shall be permitted to be attached to the finished structure.
(8)Sprinklers shall not be required to be installed within electrical equipment, mechanical
equipment, or air handling units not intended for occupancy
As = S x L
If 2C > D then 2C = L
# 8.5.2.1.1 (2)
If D > 2C then D = L
123 ft
5 ft
15 ft
38 ft
80 ft
12.5 ft
5.5 ft
5 ft
5 ft
79
8.6 to 8.13 – Sprinkler Specific
Requirements
Cross Main
Riser
Branch lines and sprinklers are
fed from only one direction
What is it ….?
According to NFPA 13,2019, Chapter 27, Cl. 27.5 (cl 27.5.1 through
27.5.1.6)
General Rules,
Cl. 27.5.1-
The demonstrated effectiveness of pipe schedule systems is limited to
their use with 1⁄2 in. (15 mm) orifice sprinklers. The use of other size
orifices can require hydraulic calculations to prove their ability to
deliver the required amount of water within the available water supply.
Cl. 27.5.1.1-
The pipe schedule sizing provisions shall not apply to hydraulically
calculated systems
Cl. 27.5.1.2 –
Sprinkler systems having sprinklers with K-factors other than 5.6
nominal, listed piping material other than that covered in Table 7.3.1.1,
extra hazard Group 1 and Group 2 systems, and exposure protection
systems shall be hydraulically calculated.
Must be by hydraulic calculation
FF Design- Mehboob Shaikh(CFPS, CFI, AMIE)
Pipe Schedule Method
Cl. 27.5.1.3 –
Cl. 27.5.1.4 –
Size of Risers
Each system riser shall be sized to supply all sprinklers on the riser on
any one floor as determined by the standard schedules of pipe sizes
Cl. 27.5.1.5–
According to NFPA 13,2019, Chapter 27, Cl. 27.5.2 (cl 27.5.2.1 through
27.5.2.6)
Branch Lines
Cl. 27.5.2.1 - Branch lines shall not exceed eight sprinklers on either
side of a cross main Provided,
That pipe sizing is increased to reduce the pressure drop along the run
of pipe upto 9 and 10 Nos of sprinklers
According to NFPA 13,2019, Chapter 27, Cl. 27.5.2 (cl 27.5.2.1 through
27.5.2.6)
Pipe Sizes
According to NFPA 13,2019, Chapter 27, Cl. 27.5.2 (cl 27.5.2.1 through
27.5.2.6)
Pipe Sizes
Cl. 27.5.2.2.2- Each area requiring more sprinklers than the number
specified for 31⁄2 in. (90 mm) pipe in Table 27.5.2.2.1 and without
subdividing partitions (not necessarily fire walls) shall be supplied by
mains or risers sized for ordinary hazard occupancies.
According to NFPA 13,2019, Chapter 27, Cl. 27.5.2 (cl 27.5.2.1 through
27.5.2.6)
Pipe Sizes
Cl. 27.5.2.5 - Branch lines and cross mains supplying sprinklers installed
entirely above or entirely below ceilings shall be sized in accordance
with Table 27.5.2.2.1.
According to NFPA 13,2019, Chapter 27, Cl. 27.5.2 (cl 27.5.2.1 through
27.5.2.6)
Pipe Sizes
According to NFPA 13,2019, Chapter 27, Cl. 27.5.2 (cl 27.5.2.1 through
27.5.2.6)
Pipe Sizes
According to NFPA 13,2019, Chapter 27, Cl. 27.5.2 (cl 27.5.2.1 through
27.5.2.6)
Pipe Sizes
• Cl. 27.5.2.3- Where sprinklers are installed above and below ceilings
and such sprinklers are supplied from a common set of branch lines
or separate branch lines from a common cross main, such branch
lines shall not exceed eight sprinklers above and eight sprinklers
below any ceiling on either side of the cross main.
According to NFPA 13,2019, Chapter 27, Cl. 27.5.2 (cl 27.5.2.1 through
27.5.2.6)
Pipe Sizes
• Cl. 27.5.2.4- Unless the requirements of 27.5.2.5 are met, pipe sizing
up to and including 21⁄2 in. (65 mm) shall be as shown in Table
27.5.2.4 utilizing the greatest number of sprinklers to be found on any
two adjacent levels.
According to NFPA 13,2019, Chapter 27, Cl. 27.5.2 (cl 27.5.2.1 through
27.5.2.6)
Pipe Sizes
• Cl. 27.5.2.5- Branch lines and cross mains supplying sprinklers
installed entirely above or entirely below ceilings shall be sized in
accordance with Table 27.5.2.2.1
According to NFPA 13,2019, Chapter 27, Cl. 27.5.2 (cl 27.5.2.1 through
27.5.2.6)
Pipe Sizes
• Cl. 27.5.2.6- Where the total number of sprinklers above and below a
ceiling exceeds the number specified in Table 27.5.2.4 for 21⁄2 in. (65
mm) pipe, the pipe supplying such sprinklers shall be increased to 3
in. (75 mm) and sized thereafter according to the schedule shown in
Table 27.5.2.2.1 for the number of sprinklers above or below a ceiling,
whichever is larger.
According to NFPA 13,2019, Chapter 27, Cl. 27.5.3 (cl 27.5.2.1 through
27.5.3.10)
According to NFPA 13,2019, Chapter 27, Cl. 27.5.3 (cl 27.5.2.1 through
27.5.3.10)
According to NFPA 13,2019, Chapter 27, Cl. 27.5.3 (cl 27.5.2.1 through
27.5.3.10)
According to NFPA 13,2019, Chapter 27, Cl. 27.5.3 (cl 27.5.2.1 through
27.5.3.10)
• Where the distance between sprinklers on the branch line exceeds 12
ft (3.7 m) or the distance between the branch lines exceeds 12 ft (3.7
m), the number of sprinklers for a given pipe size shall be in
accordance with Table 27.5.3.5.
According to NFPA 13,2019, Chapter 27, Cl. 27.5.3 (cl 27.5.2.1 through
27.5.3.10)
• Where sprinklers are installed above and below ceilings and such
sprinklers are supplied from a common set of branch lines or separate
branch lines supplied by a common cross main, such branch lines
shall not exceed eight sprinklers above and eight sprinklers below any
ceiling on either side of the cross main
123
Room Design Method (continued)
• Light Hazard
• Doors must have automatic or self closers, or
• Calculations must include two sprinklers from each adjoining space for no opening
protection
• A minimum lintel of depth of 8 in. (200 mm) is required for openings and the
opening shall not exceed 8 ft. (2.4 m) in width
• It shall be permitted to have a single opening of 36 in. (900 mm) or less without a
lintel, provided there are no other openings to adjoining spaces.
• Ordinary and Extra Hazard
• Doors must have automatic or self closers with appropriate fire resistance ratings.
• Corridors/Narrow Rooms
• When protected with a single-row of sprinklers, calculate maximum of 5 sprinklers
or 75 feet
The selection of the room and communicating space
sprinklers to be calculated shall be that which produces
the greatest hydraulic demand
124
Room Design Method Example
Which room is the most demanding? Light Hazard, no door closers
1 6 2 2 2 10
2 2 2 2 2 6
3 8 3 2 2 12
4 4 2 2 1 7
5 4 4 2 2 1 2 11
7 1 2 2 2 5
8 1 1 1 2
9 1 2 2 1 2 6
10 3 4 2 2 1 2 10
11 3 6 2 2 1 1 1 2 12
12 1 1 2 3
13 1 1 2 3
14 1 1 2 3
15 6 3 2 1 2 11
Limitations of Room Design method
• All Rooms shall be enclosed with walls having a fire resistance equal
to water supply duration as per the given table
• The Annex states that “walls may terminate at a substantial
suspended ceiling”, leaving it up to the Authority Having Jurisdiction
to decide what “substantial” means
• This method is really intended for the Light Hazard occupancy where
a high degree of compartmentation is more common
• While requirements are set forth for walls and horizontal openings,
there is no mention of vertical protection if you have a multi-story
building
CFPS Exam Preparation- Mehboob Shaikh(CFPS, CFI, AMIE)
Limitations of Room Design method
• If there were some kind of unprotected vertical opening in the room,
perhaps an open dumb waiter, Do not use the room design method.
• With the room design method, a careful review of the original
sprinkler design is needed when Walls are moved or eliminated.
Where Two different are located in the same warehouse, there are 3
methods to deal with it.
1. Analyze all the requirements for each storage situation and protect the
building with the most demanding of each of the requirements (more
flexibility to move high hazard commodity anywhere in the warehouse)
2. Segregate the storage commodities in separate parts of the warehouse
and protect the space above each commodity with sprinkler protection
appropriate for that commodity.
3. Segregate the storage commodities in separate parts of the warehouse
but not install any kind of barrier between the sprinklers at the ceiling
Cl. 12.3(3)
Storage that,
• Does not exceed 12 ft (3.66 m) in height
• Incidental to another occupancy use group.
• Will not constitute more than 10 percent of the building area or 4000
ft2 (372 m2) of the sprinklered area, whichever is greater.
• Will not exceed 1000 ft2 (93 m2) in one pile or area, and each such
pile or area will be separated from other storage areas by at least 25
ft (7.62 m).
Meeting this definition will result in an occupancy (ordinary or extra hazard)
method of protection rather than a storage method of protection
CFI-1 Exam Preparation- Mehboob Shaikh(CFPS, CFI, AMIE) 134
Thank You