S-03710 P54161-Rev. 1-AS F 8506-Steam Drum
S-03710 P54161-Rev. 1-AS F 8506-Steam Drum
Process Specification
for
AS F 8506
Steam Drum
Operating Data
Boiler Feed Water Inlet
Operating temperature 210 °C Operating pressure 60.7 kg/cm² g
Liquid flow 19736 kg/h Liquid density 856 kg/m³
Boiler Blow-Down Outlet
Operating temperature 275 °C Operating pressure 59.6 kg/cm² g
Liquid flow 395 kg/h Liquid density 759 kg/m³
Steam Outlet
Operating temperature 275 °C Operating pressure 59.6 kg/cm² g
Gas flow 19341 kg/h Gas density 30.5 kg/m³
Gas molecular weight 18.02 kg/kmol
Vessel
Mechanical Design Conditions
Fluid description Boiler water/saturated steam
Design temperature (min.) -10 °C Design pressure (min.) FV kg/cm² g
Design temperature (max.) 287 °C Design pressure (max.) 71.4 kg/cm² g
Vessel
Inner diameter 1800 mm Tangent to tangent distance 6950 mm
Construction code ASME Stress relieving According to code
Construction material CS Corrosion allowance 3.2 mm
Insulation purpose Hot Insulation thickness 150 mm
Vessel head type Ellipsoidal
Longitudinal partitioning baffles
Number of partitioning baffles 1 Center to baffle distance 360 mm
Baffle length 6050 mm
Liquid levels from vessel bottom
Maximum level 1130 mm Low level 880 mm
High level 1070 mm Minimum level 675 mm
Normal level 1005 mm Min. measurable level 275 mm
Demister
Type York mesh type 709 or similar
Material SS316
Effective length 1150 mm Effective width 400 mm
Mounting Thickness 150 mm
Outlet Vapor Distributor for Demister
Height above demister 150 mm Free height above distrib. plate Min. 60 mm
Hole pitch type Hole pitch 50 mm
Hole diameter 11 mm Number of holes 184
Hole distribution : Length direction: 23, width direction: 8
Information contained herein is confidential; it may not be used for any purpose other than for which it has been
issued, and may not be used by or disclosed to third parties without written approval of Haldor Topsøe A/S.
RESEARCH | TECHNOLOGY | CATALYSTS
YPF, La Plata
Buenos Aires, Argentina
Document ID
WSA Plant for H2S gas and spent acid S-03710 P54161 1
Job no. Doc. no. Rev.
Page Item no.
Steam Drum
3 of 5
AS F 8506
Ambient Conditions
Minimum ambient temperature -5 °C Minimum ambient pressure kg/cm²
Normal ambient temperature 16 °C Normal ambient pressure 1.0 kg/cm²
Maximum ambient temperature 40 °C Maximum ambient pressure kg/cm²
Remarks
1 A3, boiler water/steam inlet from process gas cooler.
2 A4, boiler water/steam inlet from waste heat boiler 1st pass.
3 A5, boiler water/steam inlet from waste heat boiler 2nd pass.
4 B3, boiler water outlet to process gas cooler.
5 B4, boiler water outlet to waste heat boiler 1st pass.
6 B5, boiler water outlet to waste heat boiler 2nd pass.
7 Safety valve numbers and nozzle size to be determined by safety valve supplier, taking all relevant codes into consideration.
S1 V1 B1 P1 S2 A1-2
Maximum level
L1 L3 L5
B2
High level
Normal level
1800
M1
Low level
1130
1070
H1 Minimum level
1005
A5 A4 A3
880
Minimum measurable level
675
L2 L4 L6
275
B3 B4 B5
6950
360
B2
A3-5
Demister details
Steam outlet
Min. 60
Distribution plate Demister
150
150
400
Steam outlet
1150