Professional Documents
Culture Documents
SEPARATION
TECHNOLOGIES
Jean-PaulGourlia
Pierre Trambouze
still the chief type of gas-liquid contactor used today. Their reliability, tough-
ness and usually low cost make them unique. Their function is to contact the
vapor with the liquid phase by creating successive zones of contact and sepa-
ration for the two streams as they circulate overall counter-currently all along
the column. Although the basic principle is identical for most plates, many dif-
ferent types are proposed by builders who have imagined numerous variations
to improve performance over the years.
Liquid -
t
0 0 0 0 0 0 0 0 0 0 0 0
3 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0
I I\
Liquid
AA
Figure
1.1 Diagram indicating the chief geometrical characteristics o f a plate.
tact that takes place. Later on in the text, gas and liquid velocities will be seen
to be so high that a froth or an emulsion may be formed, the liquid may even
be completely atomized. Without considering this extreme case, it should be
noted that the vapor always entrains some liquid with it in the form of
droplets. The size of the droplets determines how rapidly they fall back into
the bubbling liquid. The spacing must therefore be chosen so a s to allow max-
imum liquid disengagement. Additionally, the vapor inevitably undergoes pres-
sure drop as it rises.
6 Chapter 1 GAS-LIOUID CONTACTORS FOR DISTILLATION: PLATE C3LUMNS
j/
Right downcomer
\
7
Outlet weir
Clearance
under downcomer
j Active area
Inlet weir \
Figure
Open section 1.2 Diagram showing how plates
L are stacked up inside a column
with different downcomer wall
Sloped apron downcomer geometries.
I
_____________-_
Downcomer pan
Stepped apron
downcomer
’
I
t
The liquid stream, which moves downward by gravity from one plate to the
next, enters via the inlet downcomer, passes over the active zone and then
goes down the outlet downcomer. In the same way as the vapor leaving the
contact area automatically entrains liquid, the liquid leaving the plate is a mix-
ture of vapor and liquid whose characteristics depend on the way the plate
operates. One of the functions of the downcomer is to allow the liquid to be
degassed before it is reinjected into the plate below. The liquid therefore
requires a certain residence time in the downcomer to reach this objective.
Likewise, the average aeration factor of the liquid must be taken into account
to know the exact downcomer height occupied and thereby keep it from
becoming saturated.
Chapter 1. GAS-LlQUID CONTACTORS FOR DISTILLATION: PLATE COLUMNS 7
Figure I
This description of plate operation suggests that column and plate sizing
entails a compromise among all these interdependent parameters so that all
the components work properly.
Other types of design have been proposed. As shown in Figure 1.4, it is pos-
sible for example to have radial flow. This technology is used for very large
diameter columns such a s vacuum columns. Other ways of handling streams
can be found (Union Carbide/Linde plates, helicoidal plates, etc.) whose aim is
to improve the efficiency of these internals (see Vol. 2, Chapter 4). They will
not be described here.
to entrain droplets increases. Increased plate spacing can offset this up to the
point where the amount and size of droplets are such that they are entrained
to the plate above. This situation should obviously be avoided. In conclusion,
the diameter of the column must be selected so that the vapor rate remains
between the two qualitatively explained limits.
A second important factor is the hydrodynamic equilibrium that is gener-
ated on a plate. Each phase flow involves pressure drops which must balance
each other in order to comply with the gas overhead constraint for each plate.
A hydraulic model is generally used to carry out this analysis. Figure 1.5 shows
one of these models with the mechanisms expressed in relation to the clear
liquid.
The vapor passing through the plate and the liquid layer causes a pressure
drop (hp) which depends on the liquid and vapor flow rates, the physical prop-
erties of the two phases and the dimensional characteristics of the plate. It is
the sum of the pressure drop that occurs when the vapor passes through the
plate orifices (perforation, valve, bubble cap) and the height of clear liquid
(hCJ on the plate. It should be noted that the least pressure drop imbalance in
the orifices causes uneven distribution of the vapor stream, thereby reducing
separation efficiency.
.-.
!
!
I
A
0
Hd - - - J . hod
~ ~~
!
0 0 0 0 0 0 0 0 0 0 0 0
I
! I 0 0 0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0 0 0
It \
!
!
!
!
h p = h, + h,,
Hd = h,
h
h L = h +hod + 3
2
+ hL+ h p
I .-- .-- . -
I
Liquid
.-. .-. . -. .i
-
Figure
1.5 Schematic diagram of the hydrodynamic equilibrium of a plate.
10 Chapter 1 G A S - h J l D CONTACTORS FOR D/STlLLATlON: PLATE COLUMNS
The flow of liquid on the plate depends on the weir but also on the pres-
sure drop generated by obstacles (valves or bubble caps) and vapor break-
throughs. This means that there is a liquid gradient on the plate upstream from
the weir. The liquid height at the outlet downcomer is equal to the sum of the
height (h) of the outlet weir and the height of the crest (hod). The gradient term
is added to the liquid height at the inlet.
The height of clear liquid (Hd) in the downcomer offsets the height on the
plate, the difference in pressure between the two plates a s well a s the pressure
drop due to the liquid feed system t o the plate (hs). The total height of the
vapor/liquid mixture in the downcomer is greater due to the average aeration
factor p, and is therefore equal to Hd@.p is generally considered to be close t o
0.6 during normal operation. This is why the height of clear liquid must never
be greater than 50% of the height of the downcomer.
These considerations show the interactions between the various compo-
nents of the plate. For example, an increase in the liquid flow rate causes more
liquid retention due to the crest height. As a result, there is a simultaneous
increase in the vapor pressure drop as well as in the height of clear liquid in
the downcomer. The downcomer may then overflow: the column will fill up
with liquid and separation efficiency will fall to zero.
To summarize, for a plate to operate normally, two parameters must be
controlled: vapor phase velocity and liquid flow rate or more exactly the flow
rate per unit of outlet weir length. Inappropriate choices may cause hydraulic
malfunctions that will be detrimental to performance. Without the list below
defining any order of occurrence, a distinction is usually made between mal-
functions as follows:
-
~
Figure
1.6 Example of the acceptable operating domain for a plate.
~
@) Weeping. Sieve and valve plates are by nature not fluid-tight, so there is
always a slight liquid leakage which remains within acceptable limits and does
not affect efficiency too much. However, below a certain vapor flow rate hydro-
static thrust is no longer sufficient and the liquid flows down through the ori-
fices. This leakage, or weeping, is extremely deleterious since it causes back
mixing. It is detrimental to operate when weeping occurs as it corresponds to
vapor pressure drop through the orifices in the active area exactly equal to the
static height of liquid on the plate. Weeping does not occur with bubble cap
plates because the caps form a siphon that keeps the liquid from passing
through the orifices.
Dumping is an accentuation of the situation described above. The liquid
leaking through the orifices becomes excessive and causes a dramatic loss of
efficiency. It marks the lowermost limit of the flexibility domain for the plate.
The satisfactory operating range of a plate can be plotted as shown in
Figure 1.6. The shaded zone delimits the stability domain, i.e. the extreme flow
rate conditions under which operation is acceptable.
Plate behavior will now be discussed in various situations that deviate from
the design range of liquid and vapor flow rates in order to illustrate these def-
initions.
Higher vapor flow rate. The ejection velocity through the orifices in the
active area increases and may cause a variety of phenomena such as
blowing, greater liquid height on the plates leading to flooding and/or
more pressure drop that may cause saturation of downcomers. In any
case, excessive liquid will be entrained to the plates above, lowering effi-
ciency.
12 Chapter 1 GAS-LIQUID CONTACTORS FOR DISTILLATION: PLATE COLUMNS
Higher liquid flow rate. An overly high liquid flow can cause flooding of
downcomers due to insufficient disengagement. In addition, if the vapor
flow rate is low, excessive weeping may occur related to the increase in
static liquid load on the plates. Furthermore, it may result in poor liquid
distribution on the active area of the plates, once again causing lost effi-
ciency.
Lower vapor flow rate. An overly low vapor flow rate may cause weep-
ing or even dumping and a loss of efficiency related to less effective gas-
liquid contact.
Lower liquid flow rate. An overly low liquid flow rate can cause blowing
of the liquid if the vapor flow is too high or may possibly make the vapor
pass through the downcomers. Once again, the result is lower efficiency.
A B
D
' r
'-
1 Figure
I .7 Simplified diagram of a distillation column plate.
A. Bubble cap plate. B. Sieve plate with downcomer. C. Circular valve plate.
Chapter 1 GAS-LIQUID CONTACTORS FOR DISTILLATION: PLATE COLUMNS 13
These two types of plate are of the same nature. They have a contact zone
on the plate where the liquid is held back by a weir while the vapor rises from
under the plate through the orifices, passing through the layer of liquid. The
liquid circulates from top to bottom of the column and from one plate to the
next by vertical downcomers. The two types of plate differ only in the pres-
ence or absence of valves that can close off the contact zone orifices. The
valves are in the open position when the column is operating at its design
capacity. They close partially or can totally come back down to seal off the ori-
fices when the vapor flow decreases, thereby limiting liquid leakage. Sieve and
valve plates have a number of common characteristics and consequently the
same sizing criteria will be applied to both. There are also sieve plates without
downcomers, but they are very seldom used.
The limits depend mainly on the perforation diameter, which was restricted
to 4.76 mm for a long time. Today 1/2" perforations (1.25 cm) are considered
acceptable and allow flooding limits to be extended. The ratio between plate
thickness (e,) and orifice diameter (dJ is usually between 0.1 and 0.7. The ori-
fices are laid out in an equilateral triangle pattern with spacing equal to 2 or 3
times their diameter. Under these conditions, the orifice surface area A ,
accounts for 5 to 20% of the total plate surface area.
A variation on the model is the jet plate that generates a horizontal stream
of vapor from the orifices. This solution is designed to push the liquid and
thereby handle its flow better. It helps minimize dead zones and therefore
reduces the dispersion that characterizes the liquid flow. Reducing dispersion
was seen to improve Murphree efficiency in Volume 2, Chapter 4.
-
Figure
1.8A Norton valves.
Chapter 1 . GAS-LIQUID
CONTACTORS FOR DISTILLATION: PLATE COLUMNS 15
poses his own range (Fig. 1.8A to C): e.g. Glitsch proposes the V and A series,
Norton the L and M types and Koch the A and T series. Only the Glitsch V and
A types will be described here as they are very representative of all the prod-
ucts available on the market.
V-1: standard valve for general use. Very simple construction and low
cost. The three legs fixed to the valve slide freely in the plate orifice.
Indented shapes keep the valves from sticking to the plate and insure a
minimum opening that is favorable to stability (Fig. 1.8B).
V-4: the orifice is equipped with a collar that is formed in or contoured on
the plate and serves as a venturi. This design allows a considerable
reduction in pressure drop at the entrance under the valve. The valve
may be a model V-1.
A-1: the orifice may or may not be equipped with a collar. It is covered by
a lightweight valve above which another valve of variable weight with
three legs of variable length functions as a counterweight. The whole sys-
tem moves inside a cage that serves as a guide and travel stop. The valve
opens in two stages. For low vapor flow rates, the lower valve alone is
actuated. If the flow rate increases, the upper valve lifts up. This type of
valve is recommended when the liquid flow rate is very low, whereas V
valves give at least as good performance in most other situations.
The diameter of the orifices perforated in the plate constituting the plate is
often 38.9 mm. Valve thickness is listed according to the following calibers:
Thickness
Caliber
20
18
16 1.525
14 1.875
12
10
The most common thickness ranges from 1.5 to 3.5 mm. Calibers 14 and 16
are the most widely used.
The valves corresponding to 38.9 mm orifices have a diameter of 4.79 cm
and a lifted height of about 1 cm. The layout on the plate is in an equilateral
triangle pattern 76 mm (3") on a side, or exceptionally 114 and 152 mm.
Valve
Formed collar
Tray orific
Contoured collar
Travel stop
.Variable
counterweight
Light weight
orifice valve
-- Orifice collar
(optional)
Model A-1
Figure
1.8B Glitsch valves.
Liquid is retained on the plate due to the dynamic balance of liquid and
vapor flows through the holes. Liquid retention is usually low. As long a s the
flow rates d o not deviate much from design values, plate efficiencyis satisfac-
tory but low however, since the gas-liquid contact time is short. This type of
plate is reserved for use with systems prone t o fouling or producing a solid
deposit.
Chapter 1 GAS-LIQUID CONTACTORS FOR DISTILLATION: PLATE COLUMNS 17
Figure .'
Fixed valve
usable with or
without a down-
comer.
V-O
It must be possj le to dismantle all of these plates, which are made of car-
bon steel or steel alloy depending on product sourness. Consequently, they
are composed of elements that can pass through a manhole, i.e. with a width
of 40 to 45 cm.
Today 70% of the market share is held down by valve plates, 25% by sieve
plates with downcomers and only around 5% by bubble cap plates.
Accordingly, this presentation will focus on sieve and valve plates and all the
data required for complete calculation of a column will be given. Those read-
ers interested in bubble cap plates can refer to the previous edition of this vol-
ume (Wuithier, 1972).
Table 1.1 adapted from Kister (1992) summarizes the compared character-
istics of different types of plate and can serve as a guide in choosing the type
that is best suited to a specific duty.
us,= c
J PL - Pv
-
pv
where Usr is the vapor velocity (m/s) at flooding in an empty vessel.
This capacity parameter depends chiefly on the physicochemical charac-
teristics of the phases, but also on the geometrical characteristics of the col-
umn. A large number of charts have been proposed to correlate C to the flow
1
- - - T=36" or 90crn
-
-
2
-
-
- . -- . -.
T=24"
T=18"
T=12"
T = 9"
T = 6"
or 60crn
or 45crn
or 30cm
or 23crn
or 15crn
-.
ul
E 0.1
5
0.01
0.01 0.1 10
This velocity value defining column flooding limits applies only to non-
foaming mixtures. To take this into account, the corrective term SF is conven-
tionally used t o modulate this approach. A series of values based on experi-
ence is found in the literature (Kister, 1992; Glitsch, 1993). Table 1.2 proposes
a number of values taken from these references.
System SF factor
Non-foaming 1
Depropanizer 0.9
H,S stripper 0.9
Hot carbonate regenerator 0.9
Oil absorber 0.85
Topping 0.85-1
Vacuum tower for residue 0.85-1
Amine regenerator 0.85
Caustic soda washing 0.65
Amine absorber 0.73-0.8
System giving a stable foam 0.3-0.6
1 Table 1
Performance reduction factor according to the physical system involved
LY
A position at 80%flooding, i.e. a velocity equal to 0.8 times Us, is generally
used to determine column diameter. The value is totally arbitrary and is cho-
sen so as to minimize column diameter and therefore investment, while main-
taining a safety margin to insure proper column operation. The choice can be
modified by other criteria such a s the need for good flexibility or a required
product quality, should any doubt remain as to the thermodynamic model
used for simulation. Whatever the value may be, it fixes the area of the open
section (AN) designed for vapor passage, i.e. the cross-section of the column
minus the area occupied by the downcomers. Assuming roughly 15% of the
total column cross-section is occupied by downcomers:
xD2 Qv
AN = 0.85 -= -
4 0.8U,,
where Qv is the vapor flow rate (m3/s).
checked to make sure that the two constraints guaranteeing proper plate oper-
ation have been observed, i.e.:
there is sufficient height for good liquid and vapor disengagement;
the clear liquid height in the downcomer is less than 50% of the spacing.
The spacing choice can be modified locally due to the presence of man-
holes required for inspection.
a+bxU,-G
P=
a+cxU,&
I :It Flooding
Apparent
Foamability Examples
residence time (s)
~
n
table:
15-18 18-2 1
Average
Low Topping,
Light products
absorbers 12-15
9-12 12-15 15-18
High Amines, glycols 6-8
h, = 16.5 (%
QL )
2
Chapfer 1 GAS-LlOUlO CONTACTORS FOR DISTILLATION: PLATE COLUMNS 23
The linear velocity in this zone is approximately 0.5 m/s, but it must be
reduced for foaming systems. The flow area at the base of the downcomer is
generally between 1/2 and 113 of the cross-section at the top of the down-
comer.
( )
hod = 66.4 -QL 2/3
This formula is correct for the liquid in free fall behind the weir. If the liq-
uid stream touches the wall or if the liquid flow is disturbed approaching the
weir, a corrective coefficient Fd must be incorporated which depends on the
relationship between the length of the weir (L,), the inside diameter of the col-
umn (DT) and the liquid flow rate (QJ:
LdIDT Maximum F d
1 1.10
0.9 1.18
0.8 1.21
0.7 1.23
0.6 1.24
0.5 1.25
When the liquid flow rate is too low, the flow no longer occurs evenly along
the weir. Weirs with rectangular or sawtooth shaped edges can be used to
solve this problem. Equations 1.6 and 1.7 can be used for rectangular patterns
by calculating QL on the basis of the lower part of the cutouts, while the cor-
rective factor F, is calculated on the basis of the total length of the weir. The
sawtooth pattern is usually made up of adjacent equilateral triangles with a
height h,. Equation 1.8 can be applied when the flow covers the teeth
(hod > h,,), whereas Eq. 1.9 is valid when the teeth are exposed (hod < h,). The
ratio (L,/h,) takes the number of weir teeth into account.
QL 1
- = 7.32.10-* - [h:: - (hod - h,)2.5]
Ld h,
24 Chaoler 1 GAS-LIQUID C@NTACTORS FOR DISTILLATION. PLATE COLUMNS
h2S
QL od
- = 6.81.10-4 -
Ld h"
For circular weirs with a diameter d d in cm, the height of liquid is calculated
with the following formula:
Ld
< t
Figure
1.11 1 Geometrical relations between the
differentelements o f a circle used
for calculating weir lengths and
downcomer areas.
Chapler 1 GAS-LIQUID
CONTACTORS FOR DISTILLATION: PLATE COLUMNS 25
The length of a chord (Ld) can be found based on the half-angle at the cen-
ter 0:
The area A D of the segment of the circle limited by the chord is found by:
H = [ l -COS (a)] -
DT ( l. llc )
2
These relations are used to calculate Hand Ld based on the required down-
comer cross-section and number of passes (NP). Tables can be found in the lit-
erature giving values of & and A D (downcomer cross-section) versus Hand DT
(Perry, 1984). The curves in Figure 1.12 can also be used to find these param-
eters. The table below gives examples of the percent of cross-section occupied
by each downcomer versus number of passes (see Fig. 1.13).
1 100
2 50 100
3 34 66
4 25 50 50
5 20 40 40
3
TLP= NP x(l+x(:)) (1.12)
0.9
0.8
.
0.7
0.6
,,
,
I
0.5 I
I
I
I
I
I
0.4 - I
I
I
I
I
0.3
0.2
0.1
Figure
1.12 Curves giving the ratios L d D r and H/Dr versus the percent of the column
cross-section occupied by downcomers.
The value of TLP fixes the number of orifices that can be located in the
active part of the plate. TLP values lower than 40 cm are not recommended.
Weir height is often approximately 5 cm but can vary widely from 1 cm for vac-
uum columns to 15 cm for reactions in the liquid phase.
I-
Figure
1.13 Differentarrangements possible depending on the number o f passes.
28 Chapter 1. GAS-L~OUID
CONTACTORS FOR DiSTfLLATfON: PLATE COLUMNS
The liquid gradient (h,,) is usually calculated for the plate without the vapor
flow rate and then a correction coefficient is inserted, which depends on vapor
velocity and density.
Since the liquid gradient is lower for sieve and valve plates than for bubble
cap plates, it is often disregarded in calculating the vapor pressure drop.
Total opening: Pv U 2,
h, = K2 - (1.16)
PL
Valve thicknesses vary between 0.94 and 3.4 mm, while the density of the
metal they are made of (p,) can vary from 4510 kg/m3 for titanium to
11340 kg/m3 for lead. The density of stainless steel is approximately
8 000 kg/m3.
The velocity through the orifices is calculated based on the total number
of valves (NU) and the vapor flow rate:
u,= NU
- Qv (1.17)
x So
So is the equivalent cross-section of an orifice, for example 11.9 cm2 for com-
mon valves.
The maximum number of valves NU in multi-part plates with a 3" triangular
layout can be roughly assessed as follows:
2. The equivalent height of liquid (hCJ that the vapor has to pass through
when it leaves the orifice:
hcl = P x h, (1.18)
P aeration factor, given by Eq. 1.4
h, average height of liquid on the plate.
h, is then calculated as follows:
h
h, = h + hod+ A! (1.19)
2
h height of the weir.
The pressure drop per plate is therefore:
hp = h, + h,, (1.20)
The pressure balance around the plate can thus be written:
H d = h, + h, + hp (1.21)
30 Chapter 1. GAS-LIOUID
CONTACTORS FOR DISTILLATION: PLATE COLUMNS
Hd is the height of clear liquid in the downcomer, which must not exceed
50%of the plate spacing.
1.3.8 Entrainment
As mentioned earlier, entrainment reduces plate efficiency.Whatever the plate
regime (bubbles, jets, emulsion, froth or foam) the result is practically the
same, i.e. the formation of liquid droplets (of a variety of sizes) entrained by
the vapor. An increase in the vapor flow rate obviously accentuates this. In
contrast, entrainment passes through a minimum when the liquid flow rate
increases, and the minimum corresponds to a change in regime on the plate.
There are a number of correlations designed to estimate the entrainment ratio
Y, among which the Fair correlation (1961) which is often mentioned in the lit-
erature. The entrainment ratio, Y , expressed a s a fraction of the total liquid
flow rate, can be read in Figure 1.14.
Figure
1.3.9 Weeping
For bubble caps, a tiny amount of weeping comes from the purge holes (diam-
eter from 1 t o 1.5 cm) required to drain the column during shutdowns. This
constant leakage is not detrimental t o satisfactory plate operation. For sieve
Chapter 1 . GAS-LIQUID CONTACTORS FOR DISTILLATION: PLATE COLUMNS 31
or valve plates however, liquid may constantly leak through the orifices which
are not fluid-tight. This leakage, called “weeping” must remain below a certain
acceptable rate. The lower the vapor flow rate, the more weeping occurs. The
conditions for weeping to be at a minimum can be estimated by writing a force
balance around a plate orifice (Kister, 1992):
h, + h, = h + hod (1.22)
h, corresponds to the capillary pressure and is calculated as follows:
0
h, = 4.09 - (1.23)
PLd,
From this equation, Fair proposed a correlation with the following form:
h, + h, 2 f ( h + hod)
that can be expressed by the following approximate relation:
h, + h, 3
[ (ti 11+
(h + hod) 0.125 + 2.33 - - 0.1
This correlation, established for sieve plates, may also be used for valve
plates by employing the value of the valve slot surface area for A,.
1.3.10 Efficiency
Several basic plate efficiency concepts were discussed in Volume 2
(Chapter 4). As a reminder, distillation columns are usually calculated by
means of theoretical stages. It is necessary to have calculation tools that take
the reality of mass and heat transfers into account. Since the contact time
between the two phases is limited, it is impossible to reach thermodynamic
equilibrium. The concept of Murphree efficiency is conventionally used. It
compares the degree of separation really achieved with the separation that
would be accomplished with a theoretical plate. If yn stands for the average
vapor composition leaving plate R , yny1that arriving from the plate below and
y*, the theoretical composition of the vapor that would be in equilibrium with
the liquid leaving the plate, Murphree defined the vapor efficiency of the plate,
EM”, by the expression:
Y n - Yn-1
*
Y n - Yn-I
) (1.25)
The liquid efficiency of the plate could be defined in the same way. It varies
from plate to plate and is not strictly speaking the same for all the components
of the mixture being processed.
Another approach consists in defining an overall efficiency E, which is the
simple ratio between the number of theoretical plates required to represent
the operation of a column and the actual number of plates. Under certain con-
ditions, EMV and E can be related by the following equation:
32 Chaoter 1 GAS-L~OU~O
CONTACTORS FOR DiSTlLLATlON: PLATE COLUMNS
(1.26)
where h is the absorption factor of the column, h = -mvM with VM,LM the molar
LM
flow rates of vapor and liquid crossing the plate and m the slope of the equi-
librium curve.
Among other hypotheses, this equation assumes a constant absorption fac-
tor. This extremely restrictive assumption has led a good many authors to seek
a formula using the variables that directly condition efficiency, i.e.:
the liquid viscosity, which influences mass transfer through the liquid-
vapor interface film;
the vapor velocity in the liquid, which acts on the contact time and the
degree of entrainment;
the liquid height that the vapor passes through in relation to the contact
time and the pressure drop;
the configuration of liquid flow on the plate;
the relative volatility of components, which governs the approach to
equilibrium: the higher it is, the better the efficiency.
For further details on this topic, the reader can consult Volume 2,
Chapter 4, where the influence of types of liquid and vapor flow is considered
in particular.
It is widely accepted that viscosity is the determining factor and the
O’Connell correlation (Kister, 1992) is often used:
E = 0.492 ( j ~ ~ ~ t ) - ~ . ~ ~ ~ (1.27)
where pL is the viscosity of the liquid expressed in centipoises, and a the rel-
ative volatility of the key components at the mean column temperature. This
correlation is based on data obtained with bubble cap plates and undoubtedly
underestimates the efficiencies achieved by valve plates.
Recently Jacimovic et al. (1996) proposed a simple correlation to calculate
the Murphree efficiency emphasizing the importance of the absorption
factor h:
EM = 0.726 x h-0.299
exp (1.28)
Other more complex formulas have also been proposed based on a theo-
retical analysis of mass transfer on the plates as well as vapor and liquid flows
(AIChE, 1960). However, they give rather optimistic efficiency values (Kister,
1992). The values utilized for efficiency should always be compared with the
experimental ones obtained with a similar physical system. Generally speak-
ing, efficiency can be considered to always remain lower than 50% in absorp-
tion, due to the high viscosity at low temperature. Meanwhile, it is usually
Chapter 1 GAS-LlQUlD CONTACTORS FOR DISTILLATION: PLATE COLUMNS 33
higher than 50%in distillation. Efficiency also depends on plate operating con-
ditions, particularly the vapor flow rate. Maximum efficiency is reached at
around 30% of flooding.
Plate efficiency can obviously be related to mass transfer coefficients and
interfacial area. Even though columns are usually calculated on the basis of
theoretical plates (see Vol. 2), it may be useful to have the interfacial area and
mass transfer coefficients for certain applications, for example when a chemi-
cal reaction takes place at the same time in the column. A number of correla-
tions can be used to assess these parameters (Trambouze et al., 1984), but
they must be employed with care because they were obtained with small diam-
eter columns and particular systems. Only approximate values for these
parameters are given below:
2 x 10-2 < k , < 10-1 (m/s)
1.5 x 1 0 - ~< k , < 4.5 x 1 0 - ~ (m/s)
100 < A,, < 350 (m- '1
The choice of working pressure, along with product corrosivity and various
constraints such as wind effect, will dictate the shell thicknesses at different
heights, the grade of steel to be used and whether inner plating is required. An
example of sieve plate calculation is given below along with the equations
employed.
A bottom plate is chosen in a depropanizer processing 1000 kmol/h of feed,
60% of which is withdrawn at the top and 40% at the bottom. The plate with
maximum liquid and vapor flow rates is selected. The flow rates and proper-
ties of the phases on this plate are given below:
Fair's correlation:
G
In Figure 1.9, C = 0.36 can be read for 60 cm plate spacing.
The flooding rate 4,can be found based on Fair's equation:
Us, = 0.36 x 0.3048 - (
;)O.Z( PLP,PV 10.5
Q" = 2.13 m2
Vapor area = -
~ m a x
Taking the system into account, a linear velocity will be selected for the
liquid of 7 cm/s in the downcomers. The total downcomer cross-section
should therefore be:
QL
Liquid cross-section = - = 0.77 m2
0.07
The total column cross-section will be 2.90 m2. The diameter is then easily
calculated : D, = 1.92 m.
Subsequently, weir dimensions are calculated assuming one single pass.
Since the surface area occupied by the downcomers is 26.5% the correspond-
ing Ld/DT and HID, ratios can be read in Figure 1.12:
L,/D, = 0.925 i.e. L, = 1.78 m
HID, = 0.31 i.e. H (downcomer width) = 0.60 m
Following this, the liquid flow rate per meter of weir is calculated:
QL
- = 0.0302
Ld
which is compared with the uppermost recommended limit of 0.032 m3/m.s.
Since the calculated value is very close to the limit, it is unquestionably better
to have two passes. The dimensions of side weirs are calculated in the same
way using 13.25%of the column cross-section. Here the result is L,/D, = 0.784
and L, = 1.51 m. The side downcomer width is H , = 0.36 m. The central down-
comer can be readily calculated, since the length is 97.7% of the diameter, i.e.
L, = 1.88 and H2 = 0.41 m. The flow rate per unit of weir length is then 0.0178
on the sides and 0.0143 in the center. The results are located at the bottom of
the recommended range (0.017 to 0.032). A choice is therefore possible, but
two passes are preferable given the column diameter.
The length of flow paths (TLP) can easily be calculated:
TLP = (DT - H , - H2/2) = 0.58 m
i.e. higher than the lowermost recommended limit of 40 cm.
Then the residence time in the downcomers is calculated:
Section x T x 3600
ts = = 8.6 s
QL
which is much higher than the recommended time for such a system, i.e. 5 s.
The residence time can be shortened by inclining the flat walls of the down-
comers so that the cross-section at the base is half that at the downcomer top.
As a result, the residence time is brought down to 6.4 s, which is more than
enough.
Now the pressure drop across the plate has t o be calculated. The liquid
height above the weir is found by using Eqs. 1.6 and 1.7, i.e. h,, = 4.63 cm on
36 Chapter 1 GAS-L~QU~D
CONTACTORS FOR DlSTlLLATlON: PLATE COLUMNS
the side weirs. The aeration factor is given by Eq. 1.4: = 0.595. The clear liq-
uid height is then found:
h,, = p(h + hod) = 5.73 cm
The orifice coefficient Cv is calculated by means of Eq. 1.14: Cv = 0.78. The
pressure drop through the orifice is calculated by relation 1.13:
h, = 4.59 cm of liquid
The overall pressure drop in cm of liquid is then easily found:
h,, = h, + h,, = 10.26
Now the pressure drop (h,) can be calculated at the bottom of the down-
comer where it narrows down to 1/3 of the top cross-section:
h, = 0.73 cm of liquid
The liquid height (H,,) in the downcomer is found by Eq. 1.21, i.e. 18 cm and
consequently much lower than one-half of the plate spacing. The last point is
to check that weeping is not excessive by using Eq. 1.24:
0
h, = 4.09 -= 0.021
PL x do
h, + h, = 4.61
The second member of Eq. 1.24 is easy t o calculate = 1.9. Inequality 1.24 is
thus more than verified, indicating that the weeping ratio is negligible.
Plate efficiency is then calculated using Eq. 1.27:
E = 0.492 @L x = 0.67
The plate that was calculated above can be represented a s in Figure 1.15.
This type of calculation lends itself well t o being performed with a spreadsheet
such a s Excel, so that it can be repeated with varying operating conditions to
find the best solution.
I I
I H, I
-1
$
. - . - .- .
Figure
1.16 Diagrams showing differentdesigns for feed inlet inside a column.
A. Liquid feed inlet on a single-pass plate. B. Vapor feed inlet on a single-pass
Chapter 1 GAS-LIQUID CONTACTORS FOR DISTILLATION: PLATE COLUMNS 39
Downcomer Downcomer
width
Inlet
weir \ weir \
Downcomer
width
I Dowr
vidth
1 Figure
1.17 Examples o f design for reflux inlet on a plate.
I
~~
C
...........- .
i
0 0 0 0 0 0 0 -
From
reboiler
Liquid
I Draw-off
To
reboiler
Bottom
draw-off
At the feed inlet, plate spacing is generally greater than that used for the
rest of the column, even if only to have a manhole located at this level. A
change in the number of passes, often related to a draw-off or an inlet, also
requires increased spacing of up to around 1 meter.
Sections with different diameters are interconnected by means of a trun-
cated cone with a 30” angle.
References
AIChE Research Committee (1960) Tray efficiencies in Distillation Columns.
Fair J.R. (1961) Petro. Chern. Engr. 33, 10, 45.
Fleming P.E. et al. (1996) Pay attention to reflux/feed entry design. Chemical
Engineering Progress, Jan. 1996, 56-64.
Chapter 1 GAS-LIQUID CONTACTORS FOR DISTILLATION:
PLATE COLUMNS 41
Jacimovic B.M., Genic S.B. (1996) Use a new approach to find Murphree tray
efficiency. Chemical Engineering Progress, Aug. 1996, 46-51.
Kister H.Z. (1992) Distillation - Design. McGraw-Hill, Inc.
Perry R.H., Green Don W. (1984) Chemical Engineer's Handbook, 6th Edn.
McCraw-Hill Book Co.
Trambouze P. et al. (1988) Chemical reactors design, engineering, operation.
Editions Technip, Paris.
Wuithier P. et al. (1972) Le pe'trole : Raffinage et Ge'nie Chimique. Editions
Technip, Paris.