Professional Documents
Culture Documents
Version: V3.30
ZTE CORPORATION
No. 55, Hi-tech Road South, ShenZhen, P.R.China
Postcode: 518057
Tel: +86-755-26771900
Fax: +86-755-26770801
URL: http://support.zte.com.cn
E-mail: support@zte.com.cn
LEGAL INFORMATION
Copyright © 2014 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited. Additionally, the contents of this document are protected by
contractual confidentiality obligations.
All company, brand and product names are trade or service marks, or registered trade or service marks, of ZTE
CORPORATION or of their respective owners.
This document is provided “as is”, and all express, implied, or statutory warranties, representations or conditions
are disclaimed, including without limitation any implied warranty of merchantability, fitness for a particular purpose,
title or non-infringement. ZTE CORPORATION and its licensors shall not be liable for damages resulting from the
use of or reliance on the information contained herein.
ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications
covering the subject matter of this document. Except as expressly provided in any written license between ZTE
CORPORATION and its licensee, the user of this document shall not acquire any license to the subject matter
herein.
ZTE CORPORATION reserves the right to upgrade or make technical change to this product without further notice.
Users may visit the ZTE technical support website http://support.zte.com.cn to inquire for related information.
The ultimate right to interpret this product resides in ZTE CORPORATION.
Revision History
II
III
IV
Figures............................................................................................................. I
Tables ............................................................................................................ III
Glossary .......................................................................................................VII
VI
Intended Audience
This manual is intended for the following engineers and technicians:
l Element Management System (EMS) supervision engineers
l Maintenance engineers
Chapter Contents
Appendix B, Describes how to define the NE address and configure the route of the NE
NE Address management server during networking.
Definition and Route
Configuration
Appendix C, Describes the operations for upgrading the Agent program of the NCP/ENCP
Configuration board.
Description of
NCP/ENCP Agent
Program
Appendix D, Describes the operations for initializing and upgrading the NE of the ANCP
Initialization and board.
Upgrade of NE
with ANCP/ANCPB
Board
Appendix E, Simple Describes the simple commissioning methods, including simple commissioning
Commissioning through Telnet and simple commissioning through EMS.
Appendix F, Board Describes the board replacement issues, including preparations, operational
Replacement procedure, and precautions.
Appendix G, Board Describes indicator statuses when the boards are operating, being powered
Indicator Status on and initiated, waiting for configuration, and in a 1 : N protection group.
Related Documentation
The following documents are related to this manual:
Manual Contents
Unitrans ZXMP S385 (V3.30) SDH Based Describes the system architecture, system
Multi-Service Node Equipment Product features, system functions, technical
Description specifications, and application example.
Unitrans ZXMP S385 (V3.30) SDH Based Describes the equipment hardware, including
Multi-Service Node Equipment Hardware cabinet, power distribution box, power monitoring
Description box, subrack, boards, interfaces, and indicators.
Unitrans ZXMP S385 (V3.30) SDH Based Describes the equipment installation procedures,
Multi-Service Node Equipment Installation including installation preparation, hardware
Manual installation, cable layout, installation inspection,
and power on/off operations.
Unitrans ZXMP S385 (V3.30) SDH Based Describes the handling methods for the
Multi-Service Node Equipment Maintenance equipment alarms and performance events.
Manual (Volume II) Alarms and Performances
II
Unitrans ZXMP S385 (V3.30) SDH Based Describes the analyses and solutions for some
Multi-Service Node Equipment Maintenance common faults.
Manual (Volume III) Troubleshooting
Conventions
This manual may contain the following symbols. The meanings are as listed as follows:
Symbol Meaning
Indicates a suggestion or hint to make things easier or more productive for the
Tip
reader.
III
IV
Three safety levels are indicated: danger, warning, and caution. Presented below are their
meanings.
1-1
Danger!
Casualties or a major accident such as equipment damage may occur if you ignore this
safety warning.
Warning!
A major or severe accident or equipment damage may occur if you ignore this safety
warning.
Caution!
An accident or equipment damage may occur if you ignore this safety warning.
1-2
2-1
Sharp nose pliers It is used to trim the cable with fine cable
diameter, bend single-stranded conductor
joint, strip plastic insulation layer, and nip small
accessories.
2-2
• In the engineering practice, select tools with appropriate specifications in accordance with actual re
quirements.
Name Remark
absolute alcohol -
air-laid paper -
soldering-tin cord -
rosin -
insulating tape -
strap
fiber-pigtail jumper
Instruments/Meters
For common instruments/meters used in equipment room, refer to Table 2-3.
2-3
Name Remark
Meters for It includes thermometers and hygrometers for detecting the equipment operating
Environment environment.
Monitoring
Instru- It includes a digital multimeter, an optical power meter, an optical attenuator and a
ments/Meters PDH (Plesiochronous Digital Hierarchy) bit error tester.
for Mainte- l Digital multimeter
nance
l Optical attenuator
l Flange
• In the engineering practice, select tools with appropriate specifications in accordance with actual re
quirements.
2-4
Caution!
All the instruments/meters must be checked and calibrated before using, to ensure their
accuracies and good conditions.
Note:
For further information about the usage of instrument/meter, refer to its operating
instruction.
Forbidden Action
l Do not smoke, eat, or play games.
l Do not talk loudly in the equipment room.
l Do not put personal articles around in the equipment room.
l Do not perform any irrelevant operations to the job.
l Do not bring inflammable or explosive articles into the equipment room.
2-5
Forbidden Action
l The person on the previous shift must stay on duty until the person on the next shift
arrives.
l If faults occur during shift handover, the persons of both shifts must not pass the buck.
2-6
2-7
the transmitting optical interface and the receiving sensitivity of the receiving optical
interface.
l Be sure to cover fiber pigtail connectors with dust caps once unplugged.
l Do not look straight into the optical interface on the optical board to protect your eyes
from being burnt by laser.
l Use dust-free paper dipped in absolute alcohol to clean fiber pigtail connectors
carefully. Do not use ordinary industrial alcohol, medical alcohol or water.
l When replacing an optical board, be sure to unplug the fiber pigtails on it before un-
plugging this optical board.
2-8
3-1
Item Specification
• The temperature and humidity are measured 1.5 m above the floor and 0.4 m in front of the equipm
ent.
Note:
Clear height of the equipment room refers to the vertical distance from the bottom of the
beam or air duct to the upper surface of the antistatic floor.
Class D (Lowest class) 6000 V (combined wave) -48 V power supply rectifier
3-2
à Because the AC power distribution board and the DC power cabinet are in the
same equipment room, the distance between Class B and Class C lightning
protection units should meet the following decoupling distance requirements.
When the protection grounding bar is laid independently, the distance between
Class B and Class C lightning protection units cannot be less than 5 m. When
the protection grounding bar and the power cords are laid in parallel, the distance
between Class B and Class C lightning protection units should not be less than
15 m.
à If the required decoupling distance cannot be satisfied due to some restrictions
in the equipment room, additional decoupling inductor should be installed before
the Class C lightning protection unit by 1.5μH/m.
à Bunched copper wires with cross section area not less than 95 mm2 which are
joined by the Main Earthing Terminal (MET) or Floor Equipotential Earthing
Terminal Board (FEB) should be used as the grounding cables of the Class
B lightning protection unit, and the grounding cables of the Class C lightning
protection unit.
Keep the length of grounding cables as short as possible.
l For the lightning protection requirements of ZXMP S385 power input port and
input/output port of E1, Ethernet, alarm, and orderwire signals, refer to Table 3-4.
3-3
Calculate the actual air condition capacity in accordance with the equipment room area and
the equipment heat quantity. Refer to related engineering design specification documents
for calculation method.
Install the air conditioning system before powering on/debugging the ZXMP S385
equipment. Ensure that the air conditioning system works properly.
3-4
3-5
3-6
Steps
Generate an alarm manually through setting Reverse Preload in the Alarm Standby list:
1. Right-click an NE. Select NE Manager. The NE Manager dialog box is displayed.
2. Unfold the NE Operation tree in the bottom left pane. Select Alarm Configuration >
Alarm Standby Configuration.
3. Select the corresponding board from the Select Card list.
4. Set Alarm Standby to be Reverse Preload in the Alarm Standby list.
4-1
5. Click Apply.
Note:
If the electric tributary board port is set to be Reverse Preload, a "signal loss" alarm will
be generated.
Inspection Criteria
When an alarm occurs, the ZXMP S385 and the column head cabinet should be able to
generate the alarm sound.
Troubleshooting
1. Verify that the ring interception switch is in the "Normal" state.
2. Check the cable connections of the ring trip switch.
3. If the alarm of the ZXMP S385 is connected externally to the column head cabinet,
check the external alarm cable connection.
Steps
Observe the status of the indicators on the top of the cabinet.
4-2
Inspection Criteria
When the equipment operates normally, only the green cabinet indicator on the cabinet is
on. For the meanings of the indicators, refer to Table 4-1.
ON OFF
Red light Critical alarm indicator A critical alarm is No critical alarm in the
generated in the equipment
equipment, normally
with an audio alarm.
Yellow light General alarm indicator A major or minor alarm No major or minor
is generated in the alarm in the equipment
equipment
Note:
When the red indicator or the yellow indicator of the cabinet is on, check the board
indicators and notify the EMS operators at the central site quickly to check the alarm and
performance of the equipment.
Steps
Observe the status of the indicator lights of the board.
Inspection Criteria
Refer to the appendix Board Indicator Status for status of board indicators.
4-3
Troubleshooting
When the red/yellow indicator light of the board is on, notify the EMS operators at the
central site quickly to check the alarm/performance message of the equipment and board.
Operation Steps
Observe the operational status of the fan.
Inspection Criteria
The fan runs stably at a regular rotation speed, and buzzes continuously without strange
sound.
Troubleshooting
1. If the fan rotates at an irregular speed or has strange sound, check immediately
whether foreign substance exists in the fan box, and whether the fan is damaged.
2. If the fan does not run, check immediately if the fan in the plug-in box is damaged.
3. Any one of the three fan boxes is faulty, immediately eliminate the faults or replace the
fan box.
Steps
1. Press the clips at both sides of the dustproof unit to remove the front panel, see Figure
4-1.
4-4
2. Use a brush to scrub dust on the front panel and the filter mesh.
3. Take out the dustproof card from the unit, see Figure 4-2.
1. Dustproof card
4. Clean the air filter mesh with water, and air dry it.
5. Insert the dustproof card into the dust unit.
6. Ensure sure that the clips are locked well. Mount the front panel.
Inspection Criteria
The front panel and the air filter mesh of the dustproof unit are free from dust.
Note:
When the front panel and the dust filer mesh are dusty, clean them in the above-mentioned
way.
4-5
Steps
1. Verify that the grounding system is normal.
2. Verify that the grounding resistance satisfies related standards.
Inspection Criteria
The grounding facilities should comply with related engineering specifications.
Troubleshooting
Correct grounding facilities as per engineering specifications.
Steps
1. In respect of idle traffic channels between two sites, the test can be performed on the
idle channels to test the traffic channel quality between two sites.
2. If there is no idle traffic channel between two sites, a traffic channel originally used for
protection can be temporarily disconnected, when the traffic is small, for accepting an
error test and checking the quality of traffic channels between the two sites.
3. If both of the above two circumstances are not applicable, use the EMS software to
query the service performance and alarms, and ensure the quality of traffic channels
between the two sites.
Inspection Criteria
No bit error exists on any traffic channel.
4-6
Steps
1. Hold the front door and turn the locks on the right and left sides of the subrack to the
– End of Steps –
Prerequisite
l The boards have been inserted.
l The cables are laid.
Steps
1. Hold the filler door and insert the pin on right side of the door into the hole on the
subrack. At the same time, insert the pin on the left side of the subrack into the groove
on the left side of the door.
2. Push the door inward and upward till it fits well with the subarck.
4-7
3. Turn the locks on the right and left sides of the subrack to the horizontal position, where
is labeled.
Figure 4-4 displays how to mount the door.
– End of Steps –
Caution!
If the ground wire of the equipment to be installed has not been connected, the
antistatic wrist strap connected to the cabinet cannot apply and another effective
antistatic approach is necessary.
l Normally, some desiccants are placed in the antistatic protection bag for the board to
absorb moisture in the air inside it and keep it dry.
4-8
l If the board is moved from a place with low temperature and humidity to another place
with higher temperature and humidity, wait at least 30 minutes before unpacking, lest
the moisture will be accumulated on the board surface to damage the board.
l While plugging a board, maintain the board upright with proper force to avoid bending
the contact pins. While plugging an optical interface board, pay special attention not
to damage the optical interface and the fibers in the board.
l Avoid plugging/unplugging boards of ZXMP S385 while power is on.
l When the user install 2 M service boards on the subrack, it is recommended to insert
them into the middle slots first, and then the slots on both sides.
4-9
CSA, CSE, CSF, CSC, CSG 8, 9 The slot 8 and slot 9 must be configured
with the same boards, such as CSA
board.
OW 17 –
4-10
ANCP, ENCP, NCP, ANCPB 18, 19 The slot 18 and slot 19 must be
configured with the same boards, such
as ANCP board.
QxI 66 –
SCI 67 –
OADD 1 to 7, 10 to 16 –
OADC 1 to 7, 10 to 16 –
Table 4-3 Available Slots for Optical/Electrical Line Boards and Service Boards
of ZXMP S385
OL64 1 to 7, 10 to 16 –
4-11
Note:
l For the available slots for E3/T3 service boards, refer to Table 4-4.
4-12
Table 4-4 Available Slots for E3/T3 Service Boards of ZXMP S385
ESE3x6 62 to 65, 68 to Should be inserted in the slot of the upper-layer interface board
71 (interface switching board) that corresponds to the service
board.
l For the available slots for E1/T1 service boards, refer to Table 4-5.
Table 4-5 Available Slots for E1/T1 Service Boards of ZXMP S385
EIE1x63, EIT1x63, BIE1 61 to 65, 68 to à BIE1 board only serves for the 1:N (N≤9)
72 protection of E1 electrical service.
4-13
OPE1Z 1 to 7, 10 to 16 –
l For the available slots for Ethernet service boards, refer to Table 4-6.
Table 4-6 Available Slots for Ethernet Service Boards of ZXMP S385
TGE2B, TGSAx8 1 to 7, 10 to -
16
RSEB 2 to 5, 12 to -
15
BIE3 61, 72 à Only serves for the 1:N (N≤4) protection of FE ser-
vice
4-14
4-15
l The available slots in master and expansion subracks for ATM service board AP1x8
are: 1 to 7 and 10 to 16.
Steps
1. Take out the board from the antistatic bag and verify that there is no mechanical
damage. Since there are multiple CMOS components on the board, proper and
reliable antistatic measure such as wearing antistatic wrist is necessary before
touching the board.
2. In accordance with the slot layout and available slots for boards specified in the design
document, insert the board into the corresponding slot of the equipment subrack.
4-16
3. To plug a board, place the ejector lever at horizontal position by pressing the spring
plate of ejector lever. Grasp the upper and lower ejector levers, and push in the board
exactly along the guide rail. The board must be kept vertical throughout the process,
and apply appropriate force. Figure 4-6 shows how to plug a lower-level board.
4. When the board is about to get into position, clamp the bayonet of ejector lever with
front beam of the subrack, push the ejector lever up/down wards with both hands
exerting proper force unless the ejector lever stands upright and produces the locking
sound of "clatter". The board connector should be fully inserted into the motherboard
socket. In this case, the board panel should be parallel with the outer frame of the
board area in the cabinet. Now, the board insertion is complete.
Caution!
Do not insert the board forcibly, and avoid bending the motherboard pins. Insert the
board along the slot, do not touch the adjacent boards to avoid short-circuit.
– End of Steps –
Steps
1. Hold the upper and lower ejector levers, and press down the lever spring plates, move
the levers up/down wards with appropriate force to free the board from the slot. Figure
4-7 shows how to unplug a lower-level board.
4-17
2. Pinch the board ejector lever with thumb and forefinger of one hand, at the same time
hold the board panel with the other hand, and smoothly pull the board out of the slot.
– End of Steps –
Prerequisite
The filer door is removed.
Steps
1. Take out the board from the antistatic bag and verify that there is no mechanical
damage. Since there are multiple CMOS components on the board, proper and
reliable antistatic measure such as wearing antistatic wrist is necessary before
touching the board.
2. In accordance with the slot layout and available slots for boards specified in the design
document, insert the board into the corresponding slot of the equipment subrack.
3. To plug a board, place the ejector lever at horizontal position by pressing the spring
plate of ejector lever. Grasp the upper and lower ejector levers, and push in the board
exactly along the guide rail. The board must be kept vertical throughout the process,
and apply appropriate force. Figure 4-8 shows how to plug an upper-level board.
4-18
4. When the board is about to get into position, clamp the bayonet of ejector lever with
front beam of the subrack, push the ejector lever up/down wards with both hands
exerting proper force unless the ejector lever stands upright and produces the locking
sound of "clatter". The board connector should be fully inserted into the motherboard
socket.
5. Clockwise screw the captive fasteners. In this case, the board panel should be parallel
with the outer frame of the board area in the cabinet. Now, the board insertion is
complete.
Caution!
Do not insert the board forcibly, and avoid bending the motherboard pins. Insert the
board along the slot, do not touch the adjacent boards to avoid short-circuit.
– End of Steps –
Prerequisite
The filer door is removed.
Steps
1. Anti-clockwise the captive fasteners.
4-19
2. Hold the upper and lower ejector levers, and press down the lever spring plates, move
the levers up/down wards with appropriate force to free the board from the slot. Figure
4-9 shows how to unplug aboard.
3. Pinch the board ejector lever with thumb and forefinger of one hand, at the same time
hold the board panel with the other hand, and smoothly pull the board out of the slot.
– End of Steps –
Steps
1. Before plugging the pigtail, clean the pigtail connector using dust-free paper with
absolute alcohol. Be careful to wipe it in one direction.
2. When plugging the pigtail, nip the pigtail connector with your thumb and index finger,
make the locating piece of the connector rightward, make the connector and the optical
line board (or optical interface board) become the angle of 45°, align the connector with
the optical interface of the optical line board or the optical interface board.
3. Insert the pigtail with proper force to the optical interface, see Figure 4-10.
4-20
– End of Steps –
Steps
1. Hold the pigtail connector with your thumb and index finger, and press down the spring
piece on the connector.
2. Pull out the connector with moderate force.
3. Cover the connector with a dustproof cap as soon as it is unplugged, to avoid dust
pollution.
– End of Steps –
4-21
2. Measure the attenuation of the fiber pigtail before the test, to ensure that this fiber
pigtail has good transmission performance. For optical boards using single-mode and
multi-mode optical interfaces, use different fiber pigtails for test accordingly.
3. If necessary, the attenuation values of the optical connector and the testing fiber can
be considered known, serving to amend the mean optical launched power read from
the optical power meter. For higher test accuracy, take the average value of multiple
test results, and then amend it with the attenuation values of the optical connector and
the testing fiber.
Steps
1. Connect one end of the fiber pigtail to the optical transmit interface of the tested optical
board, and the other end to the test input interface of the optical power meter, see
Figure 4-11.
Caution!
The optical launched power of the optical board may exceed the maximum input optical
power of the optical power meter. To avoid damage to the optical power meter, add
optical attenuation between the optical transmit interface of the optical board and the
test input interface of the optical power meter.
2. Set the optical receive wavelength of the optical power meter to be the same as the
optical transmit wavelength of the tested optical line board.
3. Read the stable optical power value (dBm) of the optical power meter. If no optical
attenuator is added, this value is the optical launched power of this optical line board.
4-22
If an optical attenuator is added, this value plus the optical attenuation value is the
optical launched power of this optical line board.
– End of Steps –
Steps
1. Set the receiving optical wavelength of the optical power meter to the same as the
tested optical wavelength.
2. Select at the local site the fiber pigtail that connects to the transmitting optical interface
of the adjacent site. Normally, this fiber pigtail is connected to the receiving optical
interface of the optical line board at the local site. Connect the fiber pigtail to the test
input interface of the optical power meter. Read the stable optical power value of the
optical power meter, meaning, the optical received power of this optical line board.
– End of Steps –
4-23
4-24
Steps
1. Create a user to control user management authority.
In the NetNumen U31 R22 EMS client, select Security > User Management.
Right-click the user tree on the right pane, select Create User from the shortcut menu.
Assign unique username, user ID and password for each EMS operator, and assign
different user levels according to the specific operation authorities of each user
(read-only, read and write, or without management).
2. Change the login password of the EMS operators periodically.
5-1
Note:
Because system administrators possess all the operation authorities, any improper
operation made by them may cause severe consequences. In routine maintenance, you
must not log into the EMS as a system administrator. Instead, you may log into the EMS
as a system monitor for routine maintenance.
Inspection Criteria
1. The EMS operators can log into the EMS with an assigned username, and have the
assigned operation authorities.
2. The EMS operators can change the login password periodically.
Troubleshooting
1. If the EMS operators have wrong operation authorities or cannot change the password,
they must request the system administrator to check the user configuration data or
reset the user authorities and password.
2. If EMS connection is faulty, check the lists as follows:
l Verify that network cables are normal, and Verify that the cable type (straight cable
or crossover cable) is correct.
l Verify that the network adapter of EMS computer is normal.
l Check the optical connection of the network. Make sure that optical connection
between NEs is normal without any circuit problems.
l Verify that EMS configuration data is normal.
l Verify that NE configuration data is normal.
Steps
After the user logs in to the NetNumen U31 R22 EMS client, the Topology Management
window is displayed. Check the status of all NEs and links.
After the user log in to the NetNumen U31 R22 EMS client, the Topology Management
window is displayed automatically. Otherwise, open the Topology Management window
in one of the following ways:
5-2
Inspection Criteria
l The NE icon must be green indicating that the NE is online.
l There is no alarm icon on NE icons.
l Links are normal. The connection lines between NEs are full lines.
Troubleshooting
l The NE is off-line.
à If there is an off-line sign in the upper-left corner of the NE icon, EMS has
issued an off-line command on the NE. Set it to be on-line.
à If there is a link-broken sign in the upper-left corner of the NE icon, the EMS
and NE communicate improperly.
If the EMS is faulty, check the following items.
1. Verify that network cables are normal, and Verify that the cable type (straight
cable or crossover cable) is correct.
2. Verify that the network card of the computer where EMS works properly.
3. Check the optical fiber connection to ensure that the optical fiber connection
between two NEs is normal.
4. Verify that EMS configuration data is normal.
5. Verify that NE configuration data is normal.
l If there are alarm signs on NE icons, query the detailed alarm messages and handle
the alarms through the Current Alarm dialog box or the Fault Management window.
à If the NE icon is in red , the highest level of current alarms of the NE is
critical.
à If the NE icon is in orange , the highest level of current alarms of the NE is
major.
à If the NE icon is in yellow , the highest level of current alarms of the NE is
minor.
5-3
Steps
1. Perform one of the following operations. The Rack Chart window is displayed.
l In the topology, double-click the NE to be checked.
l In NE Tree or topology, right-click the NE to be checked. Select Open Rack Chart
from the shortcut menu.
2. Click in the upper-left pane of the Rack Chart window. The Board Selection tab
and Legend tab are unfolded.
3. Query the board operating status in accordance with Legend.
Inspection Criteria
The board is in white and has no status sign.
Troubleshooting
l The board is in one of the alarm colors, indicating that there is an alarm on the board.
Query detailed alarm information and handle the alarm through the Current Alarm
dialog box or Fault Management window.
à If the board is in red , the highest level of current alarms of the board is
critical.
à If the board is in orange , the highest level of current alarms of the board
is major.
à If the board is in yellow , the highest level of current alarms of the board is
minor.
à If the board is in blue , the highest level of current alarms of the board is
warning.
l The icon indicates that the board status is unknown. Check the communication
between the NE and the EMS to ensure that the NE is online and the communication
is normal.
l The icon indicates that the board status is out of position. Verify that the board is
installed correctly and whether it is in good contact with the backplane.
5-4
l The icon indicates that loopback is set on the board. Verify that the loopback must
be removed as required.
l The icon indicates that the board is the master board, but it is not in operational
status. Check the board and handle the fault.
Steps
l Querying the current alarms, historical alarms and lock alarms of all NEs.
1. In the menu bar of the EMS client, select Fault > Active Alarm Monitoring. The
Fault Management window is displayed.
2. In the Management tree in the left pane, double-click Alarm Query > Active
Alarms > All Active Alarms to query the alarms of all NEs.
3. In the Management tree in the left pane, double-click Alarm Query > History
Alarms > History Alarm Within One Day, Alarm Query > History Alarms >
History Alarm Within Three Days, or Alarm Query > History Alarms > Lock
Alarm Search to query the historical alarms or lock alarms of all NEs.
l Querying the current alarms, historical alarms and lock alarms of an NE.
5-5
In NE Tree in the Fault Management window, right-click the NE. Select Active
Alarms, Unacknowledged Active Alarms, Active Alarms Within One Hour,
Active Alarms Within One Day, Locked Alarm Search, History Alarm Within
One Day, History Alarm Within Three Days, or All the History Alarms from the
shortcut menu.
Inspection Criteria
l The NE has no current alarm message.
l The NE has no unconfirmed historical alarm message.
Note:
5-6
Steps
1. You can open the Performance Data Query dialog box in one of the following ways:
l In the menu bar of the EMS client, select Performance > Performance Data
Query.
l Click the icon.
l Right-click NE Tree or any NE in the topology. Select Performance Management
> Performance Data Query from the shortcut menu.
l In the menu bar of the EMS client, select Statistics > Performance Statistics >
Performance Data Query.
2. In the Performance Data Query dialog box, set the Indices Selection, Object
Selection , and Time Selection.
3. Click OK.
Inspection Criteria
The EMS client window displays the queried performance data.
The NE has no performance over-threshold event.
Steps
1. In the menu bar of the EMS client, select Fault > Active Alarm Monitoring. The Fault
Management window is displayed.
2. In the Management tree in the left pane, double-click Alarm Query > Active Alarms
> Current Switch Event to query the current switches.
3. In the Management tree in the left pane of the window, double-click Alarm Query >
History Alarms > >History Switch Event to query the history switch events.
5-7
Steps
1. Right-click an NE in the NE Tree or topology in the Topology Management window.
2. Click Data Synchronization from the shortcut menu. The Data Synchronization
dialogue box is displayed.
3. Select the Compare tab.
4. Select data items to be uploaded in the Compare Data Item area box.
5. Click Compare.
Inspection Criteria
If the NE database is consistent with the data in EMS database, the Result area box
indicates that the comparison is successful.
Troubleshooting
The NE database is not consistent with the data in EMS database.
l If the current NE database is in compliance with the user requirements, take the data
in NE database as the basis.
In the Data Synchronization dialog box, select the Upload tab. Select the data items
to be uploaded. Click Upload.
l If the data of EMS is in compliance with the user requirements, take the data of EMS
as the basis.
In the Data Synchronization dialog box, select the Download tab. Select the data
items to be downloaded. Click Download.
Caution!
It is risky to upload or download data, be cautious.
5-8
Steps
1. On the menu bar of the EMS client window, select Security > Log Management.
2. Select the corresponding operations from the Log Management tree as required.
If Then
Querying the operation logs Select Operation Log > Operation Log Today or Operation
Log > >All Operation Log.
Querying the security logs Select Security Log > Security Log Today or Security Log >
>All Security Log.
Querying the system logs Select System Log > System Log Today or System Log >
All System Log.
Inspection Criteria
l No illegal login.
l No user operations affecting system operation or service functions.
l No high-level errors in the system logs.
Troubleshooting
l When any illegal user or operation is found, use the user management function of the
EMS software to check the user identity and the authority settings, and change the
user password quickly.
l When a high-level error appears in the system log, process the error in accordance
with the "Details" of EMS record.
5-9
Steps
1. On the menu bar of the EMS client window, select Statistics > BN > xTN
Configuration Report > NE Configuration Report.
Note:
You can select the NE configuration, connection information, board configuration, and
board statistics report as required. Becuase all reports are printed in the same way,
the section takes the method for printing NE configuration report as an example.
Inspection Criteria
Reports are printed properly.
5-10
Steps
1. On the menu bar of the EMS client window, select Maintenance > System Backup
and Restore. The System Backup and Restore dialog box is displayed.
Note:
You can back up the entire database, basic data, or files. This section takes the file
backup as an example.
2. In the Backup and Restore tree, click Backup > Backup File. The Config
Parameters of Backup dialog box is displayed.
3. Select Backup File Download Path at Client. Enter the directory for saving the
backup file on the client.
4. Click Execute to start the backup.
5-11
Caution!
Do not save the backup data in the hard disk of the EMS host. Save the backup data in a
mobile storage device instead. Failure to comply can result in data loss if a fault occurs to
the hard disk.
Inspection Criteria
When the backup is completed, the Executed Result area box indicates that the client
has downloaded the backup file successfully. The backup files are saved in the specified
directory.
Note:
If the file does not exist, backup again.
Database Description
Common platform database Includes the basic data on the common application
platform database, such as resource data, safety data,
and topology data.
Common alarm database Includes the basic data on the common application
alarm database, such as alarm codes, alarm rules,
setting suggestions on alarm processing, setting
level redefinition, querying customized alarms, and
customized alarm statistics.
5-12
Database Description
Common performance database Includes the basic data on the common application
performance database, such as measurement tasks,
threshold tasks, querying templates, template tasks,
and definitions of performances models.
During network maintenance, restore the EMS data by using the backup data in case of
network fault or data loss.
Steps
1. 1 On the menu bar of the EMS client window, select Maintenance > System Backup
and Restore. The System Backup and Restore dialog box is displayed.
2. In the Backup and Restore tree, select Restore > Restore Basic Data. The Restore
Basic Data dialog box is displayed.
3. Click Start. The Basic Data Restoration dialog box is displayed.
4. Select the backup files in the Basic Data Restoration dialog box.
Note:
You can select the backup files stored on the computer where the EMS client runs or
on an FTP server.
5. (Optional) Select the Back up the current data before the restoration? If you
choose to back up the current data first, the system will automatically... check
box as required.
6. Click Execute.
Note:
When the basic data is being recovered, the EMS server stops operating and the EMS
client does not operate.
Inspection Criteria
The basic data is recovered.
After the basic data is recovered, NMS server automatically restarts. A dialog box is
displayed. Click OK. The system will close the EMS client window and a Login dialog
box is displayed automatically.
5-13
Note:
If the basic data cannot be recovered because the version of backup data is earlier than
the current EMS version, upgrade the EMS version.
Steps
1. On the menu bar of the EMS client window, select Maintenance > System Backup
and Restore. The System Backup and Restore dialog box is displayed.
Note:
You can restore the log data, alarm data and performance data in the same way. This
section takes the log data recovery as an example.
2. In the Backup and Restore tree, select Restore > >Restore Log Data. The Config
Parameters of Restore dialog box is displayed.
3. Click Choose. Select the directory for saving the data to be recovered.
4. Select Execute.
Inspection Criteria
The current data of network is recovered.
Note:
If the data cannot be recovered because the version of backup data is earlier than the
current EMS version, upgrade the EMS version.
5-14
Steps
You can open the NE Time Management window in one of the following ways:
l In the Topology Management window, right-click an NE. Select NE Time
Management from the shortcut menu.
l Right-click an NE from the NE Tree in the left pane of Topology Management window.
Select NE Time Management from the shortcut menu.
l Open the NE Manager dialog box.
1. Right-click an NE in the NE Tree or the topology in the Topology Management
window. Select NE Manager from the shortcut menu, the NE Manager dialog box is
displayed.
2. Unfold the NE Operation tree in the bottom left pane of the dialog box, select Clock
Time Configuration > NE Time Management.
Inspection Criteria
The NE time and EMS are synchronized.
Note:
If the times of NE and EMS are not synchronized, click Verify Time to synchronize NEs
and EMS.
5-15
5-16
Board NCP/ENCP/A- When normal, the green indicator NOM If no alarm is generated,
indicators NCP/ANCPB flashes (once per second). record "normal".
observation board If any alarm is generated,
When the yellow indicator ALM1 is lit, the
record the detailed alarm
NE/board generates an major or minor alarm.
indicator status.
When the red indicator ALM2 is lit, critical
If a service board generates
(severe) NE/board alarms are generated.
an alarm, the slot number
of the alarm board must be
recorded.
A-1
A-2
Summary of the indicator status: (Sum up the indicator status in this period and record the troubleshooting details.)
Tested by: Check time:
A-3
Perfor- Querying the current 15 min/24 When performances are normal, the
mance hour performance performance value is 0.
monitoring
Querying the history 15 min/24
hour performance
Summary of maintenance: (Sum up the equipment and EMS status in this period and record whether the faults
have been cleared. If the faults have been solved, the troubleshooting methods should also be recorded to provide
reference for future maintenance work.)
Tested by: Check time:
• Alarm colors vary with EMS types. This table takes NetNumen T31 as an example to describe the alarms.
A-4
Check orderwire Dial the central site orderwire (Verify that the call is connected and
telephones phone whether the voice quality is normal)
(Non-central site)
The central site dials back the (Verify that the call is connected and
local orderwire phone whether the voice quality is normal)
Check orderwire Dial site A orderwire phone (Verify that the call is connected and
telephones (Central whether the voice quality is normal)
site)
Dial-back (Verify that the call is connected and
whether the voice quality is normal)
Dial site B orderwire phone (Verify that the call is connected and
whether the voice quality is normal)
Dial site C orderwire phone (Verify that the call is connected and
whether the voice quality is normal)
Summary of maintenance (Summing up the check results in this period and recording the troubleshooting details)
Check by: Check date:
• The central site needs to dial the orderwire telephones of all the sites in the subnet to test the orderwire voice quality,
while an ordinary site only needs to dial the central site for test.
A-5
The Last Change This Change Recorded into the Changed Checked Check Date
Date Date Memorandum or not By By
Note:
For irregular checks of system configuration, security log, report printing, and data backup,
the maintenance forms can be made in accordance with the above forms.
A-6
Note:
When configuring NE initial information, the IP addresses of this NE and the EMS host must
be determined and written into the NE NCP board, which allow no random modification
when the equipment operates normally.
The definition of the NE IP address is the same as that of the common IP address.
However, the meaning of each byte in NE IP address is redefined. The configuration
principle and byte meanings vary with different mask format.
NE IP byte 1.byte 2.byte 3.byte 4 1. The NE IP address contains three parts: area code, NE code, and
address NCP board number. Byte 1 serves as the area code, some address
bits of byte 2 and byte 3 serve as the NE code, and the remaining
address bits and byte 4 form the NCP board number.
2. The area ID combined with NE ID corresponds to the network
address. The NCP board number corresponds to the host address.
B-1
Subnet 255.byte 2.byte 3.0 The result got from the logic AND operation of NE IP address and subnet
mask mask defines the specific meaning of each byte in NE IP address.
Area ID 1. Represents for the area that the 1. It ranges from 1 to 223
NE belongs to. 2. Area 192 is defined as the backbone area that connects
2. It is byte 1 of the NE IP address. to other areas. Normally, it is recommended that the area
IDs ranging from 193~201 are to be used for non-backbone
areas.
3. The Non-backbone areas use backbone network to
communicate among themselves, and any other form of
connection shall not exist among them.
4. It is recommended cannot be more than 64 NEs in one area.
The maximum number of NEs in single area is 128.
NE ID The result got from the logic AND In the same area, each NE must have a unique NE ID.
operation of bytes 2, 3 of the NE
IP, and the corresponding bytes of
subnet mask.
Board ID 1. The board ID of the NCP board. 1. The NCP board number needs manual definition. The
It stands for the host ID of NE, numbers of other boards in an NE are automatically
and needs manual definition. allocated in accordance with the NCP board number. In
2. The NCP board number is the addition, numbers of various boards in the same NE must
result got from the logic AND be unique, while those in different NEs can be the same.
operation of bytes 2, 3, 4 of the 2. The NCP board number must range from 9 to 100, and 18
NE IP, and the reverse code is recommended.
of corresponding bytes in the
subnet mask.
byte 1.byte 2.byte 3.byte 4 255.255.255.0 Byte 1 is the area ID, byte 2 and byte 3 form the NE ID, and
byte 4 is the NCP board number.
255.255.0.0 Byte 1 is the area ID, byte 2 is the NE ID, and byte 3 and byte
4 form the NCP board number.
B-2
Taking three NEs as example, when different subnet masks are used, the NE IP addresses
are allocated as listed in Table B-4.
Subnet Mask NE 1 NE 2
Tip:
VLSM addressing and CIDR techniques need support from the equipment version. Consult
ZTE maintenance personnel for detailed version information.
NE IP byte 1.byte 2.byte 3.byte 4 1. It consists of three parts: area ID, ECC subnet ID, and NE ID.
address 2. Each NE needs to be allocated with an IP address. In the
same ECC subnet (an interconnected ECC network), the NE
IP address must be unique.
Subnet byte 1.byte 2.byte 3.byte 4 1. The result got from the logic AND operation of NE IP address
mask and subnet mask defines the specific meaning of each byte
in NE IP address.
2. Byte 1, byte 2 and byte 3 are generally 255s, and byte 4 can
be set between 0 to 255 randomly.
B-3
Table B-6 Definitions of Area ID, ECC Subnet ID, and NE ID (VLSM)
Area ID 1. Represents for the area that the NE 1. For a complicated ECC subnet, the multi-area
belongs to. configuration must be used due to the limitation of
2. It is byte 1 of NE IP address NE processing capability and the requirement of
dynamic route protocol.
2. Refer to the description of area ID in the "FLSM
Addressing" section for division principle and
requirement of the area ID.
ECC subnet ID 1. Represents for the ECC subnet ID A complicated ECC subnet can contain multiple areas.
that the NE belongs to
2. It is byte 2 of NE IP address
193.193.193.5
193.193.193.9
193.193.193.13
193.193.193.17
193.193.193.21
193.193.193.25
..........................
193.193.193.249
193.193.193.253
Where, byte 1 is the area ID; byte 2 represent for the ECC subnet ID; the result got from
the logic AND operation of byte 3, 4 of the NE IP address, and corresponding bytes of the
subnet mask represents for the NE ID.
B-4
Suppose the NE IP address, i.e. the NCP board IP address is "byte 1. byte 2. byte 3.
byte 4", then the IP addresses of other boards are allocated to numbers ranging from
"byte 1. byte 2. byte 3. (byte 4+1)" to "byte 1. byte 2. byte 3. (byte 4+PortNum)".
l If byte 4 of the subnet mask is not zero, the board IP address is allocated at byte 2.
Suppose the NE IP address is "byte 1. byte 2. byte 3. byte 4", then the IP addresses
of other boards are allocated to numbers ranging from "byte 1. (byte 2+1). byte 3.
byte 4" to "byte 1. (byte 2+PortNum). byte 3 .byte 4".
Note:
Because the NCP board IP address is invisible to EMS, it will not affect the outside network,
which means it will not conflict with the outside network address. Therefore, it is only
necessary to ensure that the addresses inside the SDH internal communication network
are unique. In the same ECC network, the fourth bytes of subnet masks being zero and
being non-zero must not coexist.
B-5
Example
Scheme 1: Dividing areas in accordance with Figure B-1 can simplify connections between
areas, and the NEs belonging to the backbone area are relatively few.
l NEs 1, 2, 3, 4, 5, 6, and 8: they are relatively centralized, among which there are
multiple connections, and they form a mesh topology. Therefore, they are allocated
into area 193.
l NEs 9, 11, and 12: they are relatively centralized and form a ring topology. Therefore,
they are allocated into area 194.
l NEs 7 and 10: there is only one single connection between areas 193 and 194 via
NEs 7 and 10. Therefore, NEs 7 and 10 are taken out as the backbone area (area
192) for connecting other areas.
For area definitions and NE IP address configurations, refer to Table B-7.
B-6
NE NE IP Address
NE 2 193.1.2.18
NE 3 193.1.3.18
NE 4 193.1.4.18
NE 5 193.1.5.18
NE 6 193.1.6.18
NE 8 193.1.8.18
NE 11 194.1.11.18
NE 12 194.1.12.18
NE 10 192.1.10.18
• The network mask is 255.255.255.0 and the EMS host address is 193.1.1.1.
Example
Scheme 2: Because the NEs in Figure B-1 are relatively few, all the NEs can be simply
allocated into one area (for example, they may all be allocated into area 193), in which the
backbone area is not needed.
Their NE addresses are listed in Table B-8.
Table B-8 NE IP Address Configurations of the NEs Allocated into Area 193
NE NE IP Address NE
Access NE 1 193.1.1.18 NE 2
NE 3 193.1.3.18 NE 4
NE 5 193.1.5.18 NE 6
NE 7 193.1.7.18 NE 8
NE 9 193.1.9.18 NE 10
NE 11 193.1.11.18 NE 12
• The network mask is 255.255.255.0 and the EMS host address is 193.1.1.1.
B-7
Note:
Although allocating all NEs into the same area is simple, the efficiency of ECC route
algorithm will be affected if the number of NEs is large. Therefore, this method only applies
to applications with a small number of NEs. Normally, the maximum number of NEs in one
area must not exceed 120.
IP address Defines the EMS host 1. The result got from the logic AND operation of the EMS host IP
network address. Employs address and the subnet mask must be within the same network
the IP address format: byte section as the access NE, i.e. the EMS host and the gateway
1.byte 2.byte 3.byte 4. NE must have the same network ID.
2. The EMS host ID must be less than the gateway NE host ID
(i.e. the NCP board number). The EMS host ID is suggested
to range from 1 to 9, starting from 1. The IP address of the
EMS host must not conflict with the IP address of any NE in
the network.
Subnet mask Defines the subnet mask The subnet mask is suggested to be the same as the subnet mask
of the EMS host. Used of access NE.
to divide network section
by performing logic AND
operation with the EMS host
IP address.
Gateway Defines the gateway address Set the access NE as the gateway NE.
address of the EMS host.
Consider the networking shown in "Example of Network Address Coding of NEs", for
example, bind an IP address 193.1.1.1 which is within the same network section as
gateway NE 1, with the network adapter of EMS host; thus ensuring that EMS host can
reach the access NE. Define the gateway NE address as 193.1.1.18, thus ensuring that
EMS host can reach area 193.
B-8
Set the routes on the EMS host to reach NEs in area 192 and area 194.
Tip:
Therefore, it is recommended to set static route or default route for the EMS host, so as
to filter out IP packets that are irrelevant to the network, thus increases the operating
efficiency of EMS.
2. Set default route or static route directing to the NE that directly connects with the EMS
host. Delete other routes that are repeatedly configured. As an example, consider the
network shown in "Example of Network Address Coding of NEs", the method of setting
default route or static route for EMS host is as follows:
a. Set the default route
The three static routes mean that all IP packets accessing the networks 193.1,
194.1, and 192.1 shall pass NE 1 whose IP address is 193.1.1.18.
B-9
Note:
Once the computer is restarted, all the routes added by the command of route add will be
lost. Use the command of route add Cp to permanently add one route to the computer.
l Command line
For the commonly used command lines to set route, refer to Table B-11.
B-10
Note:
Once the computer is restarted, all the routes added by the command lines will be
lost. Modify the configuration file and save the changes to permanently add one route
to the computer.
ROUTE_GATEWAY[0]=193.1.1.18
ROUTE_COUNT[0]=1
ROUTE_ARGS[0]=
B-11
ROUTE_ARGS[1]=
à Solaris platform
Modify the configuration files listed in Table B-13 in the document editor.
The configuration commands in the file will automatically apply and be saved
permanently after the system is restarted.
/etc/netmasks 1. Set the subnet mask for the added IP 192.192.1.0 255.255.255.0
address 192.192.66.0 255.255.255.0
2. Format: Network_ID Subnet_mask 168.69.74.0 255.255.255.0
/etc/hostname.eri 1. Set the logic IP address. One Define the file of /etc/hostname.er
0:x hostname.eri0:x file needs to be i0:1 as hknttsdh. Define the file of
added for each added IP address (x /etc/hostname.eri0:2 as almftp
starts from one)
2. Format: Host_name
/etc/rc2.d/zteRout 1. Add static route.This file will be route add net 192.192.0.0
er automatically loaded when the system Cnetmask 255.255.192.0
starts. The file name is S96zteRouter. 192.192.1.6 1
The name zteRouter can be defined at route add net 192.192.64.0
your will except existed file name in the Cnetmask 255.255.192.0
/etc/rc2.d directory 192.192.66.18 1
2. Format to add one route: route add[ route add net 168.65.0.0
host | net ] destination 168.69.74.1 5
gateway
B-12
Tip:
The initial ZXMP S385 equipment cannot connect to the EMS terminal computer for
network configuration or network management until the Agent application has been
downloaded to the NCP board and the initial parameters have been configured.
1. The ZXMP S385 equipment reserves two slots for NCP board (No. 18 and No. 19
slots. Generally, No. 18 slot is called the master slot, and No. 19 slot is called
the standby slot). Therefore two NCP boards or ENCP boards can be installed
simultaneously to implement the 1+1 protection for NCP/ENCP boards.
2. The NCP board has an Ethernet interface (debugging interface), see Figure C-1.
C-1
The Ethernet interface is used to connect the NCP board working in the Download
status. QxI board also has an Ethernet interface (EMS Qx interface) which is used
to connect the NCP board working in the master status. Refer to the sections of
"Functions of BOOTROOM Module on NCP" and "NCP Board State Switching" for
the work states of NCP board.
3. If two NCP boards are installed simultaneously, one NCP board is the master board
and the other is the standby board at any moment during normal operating. The
Ethernet port of QxI board only communicates with the master board, i.e. it can only
connect one NCP board (the master NCP board) at any moment.
c. Read and set the system parameters (especially the MAC address).
C-2
C-3
Context
Figure C-3 shows the flowchart of local upgrade preparations.
C-4
Steps
1. Ensure that the correct BOOTROM chip is plugged on NCP board.
3. Set the DIP switch on NCP board to all ON state (Download state). And the NE IP
address is 192.192.192.11 with the subnet mask of 255.255.255.0.
C-5
4. Connect the Ethernet interface of the EMS computer and the Qx interface of the NCP
board with a network cable, and ensure that the connection is correct.
5. Set the IP address and subnet mask of the EMS computer.
IP address: 192.192.192.X (0 < X < 255 and X ≠ 11)
Subnet mask: 255.255.255.0
6. Execute the ping 192.192.192.11 command on the EMS computer to confirm that
the EMS computer can connect to NCP.
l If it is unnecessary to completely clear the NE data or reconfigure the NE, the
upgrade preparations are completed.
l If it is necessary to completely clear the NE data and reconfigure the NE, follow
the steps below:
7. Perform the following operation to clear the NE data, and configure the NE again.
b. The system prompts to enter user name and password which are both empty, and
then press the Enter key directly. The DOS prompt ZTE+> is displayed.
c. Input the command d-erase -d1 to erase the database, see Figure C-4.
d. Input the commands d-erase -p1 and d-erase -p2 to erase the chip area which
saves the application program, see Figure C-5.
Figure C-5 Erase the Chip Area which Saves the Application Program
e. Input the commands d-erase -f1 and d-erase -f2 to erase the chip area which
saves the logic program, see Figure C-6.
C-6
Figure C-6 Erase the Chip Area Which Saves the Logic Program
f. Input the command d-cfgnet to configure the NE related information, see Figure
C-7. For the input principles of each item, refer to Table C-2.
MAC Address Input the physical address of the NE. It is mandatory and should
be unique for each NE.
Warning!
Press the Enter key directly if there is no modification. Do not quit in the middle
of the procedure, otherwise the NCP board will stay in the infinite waiting state.
g. Input the command d-reboot to reboot the NCP board, and the NE information
configuration will apply. Upgrade preparations are completed.
– End of Steps –
C-7
Context
Tip:
If the NE data has been cleared during the upgrade preparation, this step can be skipped.
Steps
1. Execute the command telnet 192.192.192.11 on the EMS computer.
2. The system prompts to enter user name and password which are both empty, and then
press the Enter key. The DOS prompt ZTE+> is displayed.
3. Input the command d-erase -d1 to erase the database.
– End of Steps –
Steps
1. Execute the command ftp 192.192.192.11 under the directory containing the
Agent program or logic on the computer, and then input the user name and password,
which are both empty.
2. Press the Enter key until the prompt ftp> is displayed. All the following operations
are completed under this prompt.
3. Execute the following commands in turn to download the board application/logic and
verify that the downloaded file is correct.
a. ftp> bin
C-8
Note:
After the put command is executed, the size of the downloaded file will return
(bytes sent). Verify that the downloaded file size is consistent with the local file. If
not consistent, re-download the file.
c. ftp> bye
//Exit the ftp connection.
Note:
The application/logic of NCP board must be transferred to the NCP board in the binary
mode.
– End of Steps –
Example
Suppose the Agent program NCP-ZXMP S385-PRG-V1.01R1P05.BIN is downloaded
from the computer to the NE, the operations are shown in Figure C-8.
C-9
Context
This operation is to upgrade the application/logic on CF card into the application/logic area.
Steps
1. Execute the command telnet 192.192.192.11. Input the username and password
as prompted.
2. Press the Enter key until the prompt ZTE+> is displayed. All the following operations
are completed under this prompt.
3. Execute the command d-upgrade to upgrade the board application/logic into the
application/logic area respectively.
Subrack-NO. 1 or 2, generally 1.
Slot-NO. The slot number of the board. It is an integer ranging from 1 to 19. It is
18 or 19 for the NCP board.
-p The parameter for NCP application delivery, followed by the board application
file name.
-f The parameter for NCP logic delivery, followed by the board logic file name.
– End of Steps –
Example
To upgrade the program in the Figure of "Local Downloading of NCP Application to NE" in
the section of "Downloading the Application/Logic" into the application/logic area, perform
the operation, see Figure C-9.
C-10
Steps
1. Execute the command telnet 192.192.192.11. Input the username and password
as prompted, which are both empty.
Subrack-NO. 1 or 2, generally 1.
Slot-No. The slot number of the board. It is an integer ranging from 1 to 19. It is 18 or
19 for the NCP board.
C-11
Tip:
If the version is abnormal, it is necessary to re-perform the operations described in the
sections "Downloading the Application/Logic" and "Upgrading the Application/Logic"
until the version queried is normal.
– End of Steps –
Example
Verify the version of the application in section "Downloading the Application/Logic", see
Figure C-10.
Table C-5 Descriptions of Parameters that Need to be Verified for Local Upgraded
Board Program Version
download date File downloaded time Should be consistent with the actual
time when the file is downloaded
download version File version downloaded Should be consistent with the actual
downloaded file version
C-12
file length The size of the downloaded file Should be consistent with the actual
downloaded file size
Context
Tip:
If only one NCP board is configured on ZXMP S385, skip this step.
Caution!
The IP address, subnet mask, and MAC address of the standby NCP board must be the
same as those of the master NCP board.
Steps
1. Re-perform the steps described in the sections from"C.3.2 Local Upgrade
Preparations" to "C.3.6 Verifying the Application/Logic After Local Upgrade", to
upgrade the standby NCP board.
– End of Steps –
C-13
Steps
1. Set the DIP switches of both NCP boards to non-all ON and also non-all OFF state
(Running state). Reset the NCP board and it enters the Running state.
Note:
During local upgrade, the user can restart or reset the NCP board and press the bell-off
button continuously to enter the Download state. Then, unplug the NCP board and
re-insert it into the slot, and it enters the Running state.
2. Set the IP address of EMS computer to be within the same network segment as the
NE IP address.
3. Execute the command ping NE IP to confirm if the NE can be pinged through.
4. In the Topology Management view of the NetNumen T31 EMS, select the NE to be
upgraded.
5. Select Device Config > Data Synchronization. The Data Synchronization dialog
box is displayed.
a. Click the Download tab.
b. Select the items to be downloaded, and then click Download. The Confirm dialog
box is displayed.
C-14
Note:
After the above procedures, the database has been cleared without any services
available, so there is no such a problem as service interruption.
c. In the Confirm dialog box, click Yes to confirm downloading. The Confirm dialog
box of downloading NE properties is displayed.
d. Click Yes to download the NE property information. After the NE property
information has been downloaded successfully, the Message dialog box is
displayed.
Note:
l After the NE information has been downloaded successfully, the node will
automatically restart.
l It is unnecessary to download the database when upgrading the logic.
l To upgrade the EMS, click the Upload tab.
– End of Steps –
C-15
C-16
Steps
1. Use network cable to connect the Ethernet interface of EMS computer with the
Ethernet interface of QxI board.
2. Execute the ping NE-IP command at the EMS terminal. Confirm that the EMS
terminal communicates normally with the NE, and that the ECC of the NE to be
upgraded is smooth.
3. Confirm that the Agent program version to be downloaded complies with the current
EMS version. Ensure the validity and consistency of the versions.
– End of Steps –
Steps
l On the EMS computer, execute the command telnetNE IP.
l Input the user name of zte and password of ecc in accordance with the system prompt.
l Press Enter until the prompt ZTE+> is displayed. The system indicates User zte
logged in if login succeeds, otherwise, the system indicates Sorry! Password
Incorrect!.
l Execute the command a-get-sysinfo state to view the information of the current master
NCP board, see Figure C-12
– End of Steps –
Example
In Figure C-12, address: 11201: 11201 is a hexadecimal code, where the third and fourth
bits (12) are equal to 18 in decimal code after conversion, indicating that the current master
NCP board is in slot 18.
C-17
Steps
1. Execute the command ftp NE-IP under the directory containing the Agent program
or logic on the computer. Input zte for username and ecc for password in accordance
with the system prompts.
2. Press the Enter key until the prompt ftp> appears. All the following operations are
completed under this prompt.
3. Execute the following commands to download the board application/logic.
a. ftp> bin
//Set the file transfer mode to binary mode.
b. ftp> put file_name_of_the_application/logic
//Download the board application/logic.
c. ftp> ls -l
Check if the downloaded file size is consistent with the local file. If not consistent,
re-download the file.
d. ftp> bye
//Exit ftp connection.
– End of Steps –
Steps
1. Execute the command telnet NE-IP. Input zte for username and ecc for password
according to the system prompts.
2. Press Enter until the prompt ZTE+> is displayed.
3. Execute the command d-upgrade to upgrade the board application/logic. Refer to
the section "Upgrading the Application/Logic" in Local Upgrade part for detailed
procedures of upgrading the application/logic.
Checkpoint:
When executing the d-upgrade command, the Slot-No. parameter should be the slot
number of the master NCP board queried in the section "Confirming the Address of
the Master NCP Board".
– End of Steps –
C-18
Example
To upgrade the program file NCP-ZXMP S385-PRG-V1.01R1P05.BIN that has been
downloaded to the NE (with IP address of 213.17.1.166) into the application area, the
operations are shown in Figure C-13.
Steps
1. Execute the command d-get-status under the prompt of ZTE+>.
Command Format: d-get-status Subrack-NO. Slot-NO. Board-CPU-NO.
2. Verify if the version of the upgraded application/logic in the standby area is normal
based on the executed command result.
C-19
Note:
If the version is abnormal, it is necessary to perform the operations in the section
"Downloading the Application/logic" and the section "Upgrading the Application/Logic"
again, until the version queried is normal.
– End of Steps –
Example
To verify the program file in the section "Upgrading the Application/Logic", the result is
shown in Figure C-14.
C-20
download date File downloaded time Should be consistent with the actual
time when the file is downloaded
download version File version downloaded Should be consistent with the actual
downloaded file version
file length The size of the downloaded file Should be consistent with the actual
downloaded file size
Steps
1. Execute the command d-try under the prompt of ZTE+> to perform the try run of the
application/logic.
Command Format: d-try Subrack-NO. Slot-NO. Board-CPU-NO. {-p|-f}
For Parameter Description, refer to Table C-7.
Subrack-NO. 1 or 2, generally 1.
Slot-No. The slot number of the board. It is an integer ranging from 1 to 19. It is
18 or 19 for the NCP board.
C-21
2. When executing the command, the system will prompt: Do you want to upgrade
the DB area?Yes[y]/No[n].
l Select y to clear the NCP database;
l Select n to not to clear the NCP database.
When the d-try command completes, the NCP board is reset, and the communication
with the computer is interrupted. The ECC will be interrupted for about one to two
minutes, and during this time the EMS cannot manage this NE. If there are two NCP
boards, after the reset, the system will switch to another NCP board first.
– End of Steps –
Example
To try run the program file in the section "Upgrading the Application/Logic", see Figure
C-15.
Steps
1. Execute the telnet NE-IP command on the EMS computer, and input the user name
of zte and password of ecc in accordance with the system prompts.
2. Press Enter until the prompt ZTE+> is displayed.
3. Execute the a-get-sysinfo state command, to verify that the communication state of
the standby NCP board is normal, and confirm the master NCP address according to
the command result. For the operation example, refer to the section "Confirming the
Address of the Master NCP Board".
4. Execute the command d-get-status under the prompt of ZTE+> to verify if the version
of the upgraded application/logic in the original standby area is normal.
C-22
Tip:
If the version is abnormal, it is necessary to perform the operations in the section
"Downloading the Application/logic" and the section "Upgrading the Application/Logic"
again, until the version queried is normal.
– End of Steps –
Example
To verify the program file in section "Try Run of the Application/Logic", see Figure C-16.
Figure C-16 Verifying the Program that Passed the Try Run
For the parameters in the original standby area (labeled as program number: 0x02)
that need to be verified, refer to Table C-8.
C-23
Table C-8 Parameters in the Original Standby Area that Need to be Verified after the
Try Run
download date File downloaded time Should be consistent with the result
in Figure C-16.
download version File version downloaded Should be consistent with the result
in Figure C-16.
file length Size of the downloaded file Should be consistent with the result
in Figure C-16.
Context
After the application/logic is downloaded and upgraded, you need to activate it within 15
minutes after the try run.
Execute the command d-active under the prompt of ZTE+> to activate the application/logic.
Command Format: d-active Subrack-NO. Slot-NO. Board-CPU-NO. {-p|-f}
For Parameter Description, refer to Table C-9
Subrack-NO. 1 or 2, generally 1.
Slot-No. The slot number of the board. It is an integer ranging from 1 to 19. It is 18 or
19 for the NCP board.
C-24
Caution!
If the application/logic is not activated within 15 minutes after the try-run, or it is not
activated before resetting the NCP board, it will go back to the original application/logic.
Steps
1. For the program activation operation, see Figure C-17.
– End of Steps –
Steps
1. Execute the command d-get-status under the prompt of ZTE+>.
Command Format: d-get-status Subrack-NO. Slot-NO. Board-CPU-NO.
– End of Steps –
Example
To verify the activated application/logic in the original standby area, the operation and result
are shown in Figure C-18.
C-25
For the parameters in the original standby area (labeled as program number: 0x02)
that need to be verified, refer to Table C-10.
download date File downloaded time Should be consistent with the result in
"Verifying the Application/Logic After
Remote Upgrade"
download version File version downloaded Should be consistent with the result in
"Verifying the Application/Logic After
Remote Upgrade"
status master indicates the master The status of the area labeled as program
status number: 0x01 should change to slave
C-26
file length Size of the downloaded file Should be consistent with the result in
"Verifying the Application/Logic After
Remote Upgrade"
Note:
If only one NCP board is configured on ZXMP S385, skip this step.
Steps
1. Execute the telnet NE-IP command on the EMS computer, and input the user name
of zte and password of ecc according to the system prompts.
2. Press Enter until the prompt ZTE+> is displayed.
3. Execute the command d-set-ncpbackstat under the prompt ZTE+> to switch to the
standby NCP board, see Figure C-19.
C-27
Steps
1. In the T31 Topology Management view, select the NE to be upgraded.
2. Select Common Config > Data Synchronization from the main menu. The Data
Synchronization dialog box is displayed.
5. Click Yes.
C-28
Note:
After the NE information has been downloaded successfully, the node will
automatically restart.
For the detailed procedure of downloading database, refer to the section "Downloading
the Database Locally".
– End of Steps –
Steps
1. In the Topology Management view of the NetNumen T31 EMS, double-click the
upgraded NE. The Card Management dialog box is displayed.
2. Right-click the NCP board, and select Card Current Version to be queried with the
version.
3. Check the version information of the NCP board. If the information displayed
is consistent with the downloaded application/logic, it indicates that the newly
downloaded application/logic is operating normally.
– End of Steps –
C-29
C-30
D.1 Overview
An ASON equipment (NE) needs to be initialized before providing ASON functions. The
initialization procedure, which also includes the load of application and logical programs,
is implemented when the NE is set to download state.
Note:
The initialization procedures of ANCP board and ANCPB board are same. This section
uses the ANCP board as an example to describe the initialization procedure.
D-1
Context
Figure D-2 shows the preparation flow before local initialization.
D-2
Steps
1. Check BootROM chip and CF card on the ANCP board of the NE to be initialized, and
application/logical programs and ASON configuration files to be used as well.
a. Make sure that the BootROM chip on the ANCP board is correct. Each kind of
ANCP board has its special BootROM chip.
D-3
b. Make sure that the CF card is correctly inserted on the ANCP board.
c. Make sure that right application/logical programs and ASON configuration files are
available.
Caution!
Two ASON configuration files, ason.ini and nbase.ini, are necessary for ZXMP
385 V3.XX or ZXONE 5800 V1.XX, no matter whether the equipment needs ASON
function or not. They are released corresponding to ANCP board version and can not
be modified. These two files are uploaded by means of an FTP utility. Make sure
that they are available during the initialization because the ANCP board can not work
normally without them.
Note:
ANCP board has the following two statuses:
l Download status: Switch all pins of the DIP switch S1 on the ANCP board to
"ON" position to set the ANCP board to download status. The default IP address
of corresponding NE is 192.192.192.11 in download status. And in this status,
the available network interface is Qx interface on the ANCP board, which can be
connected to the EMS computer for local initialization.
l Running status: Switch the pins of the DIP switch S1 on the ANCP board and
make sure that some of them are at "ON" position and the other at the opposite
position, to set the ANCP board to running status. And in this status, the available
interface for remote initialization is the network interface on QxI board.
2. Switch all pins of the DIP switch S1 on the ANCP board to "ON" position to set
the ANCP board to download status. In the download status, the IP address of
corresponding NE is 192.192.192.11, and the subnet mask is 255.255.255.0.
3. Connect the network interface of the EMS computer to Qx interface on the front panel
of ANCP board with a network cable and make sure that the connection is correct and
firm.
4. Add an IP address and subnet mask on the EMS computer following the principles
listed below:
l IP address: 192.192.192.X (0<X<255 and X≠11)
l Subnet mask: 255.255.255.0
5. Ping the ANCP board (192.192.192.11) on the EMS computer and check whether the
connection between the computer and the board is normal.
D-4
l Yes→Step 7
l No→End
7. Input the command d-reboot after the prompt ZTE+> to reboot the ANCP board.
A prompt message Connection to host lost appears after successful reboot.
8. Configure the IP address, subnet mask and MAC address of the NE as follow.
a. Input the command telnet 192.192.192.11.
You are required to input the user name and password.
b. Input the user name zte and password ecc, and then press Enter key.
A prompt ZTE+ appears.
c. Input the command d-cfgnet after the prompt ZTE+ and then input the IP address,
subnet mask and MAC address one by one when prompted.
The following table describes related parameters of an NE that should be
configured, including the IP address, subnet mask and MAC address of the NE.
Parameter Requirement
MAC Address It must be configured. Make sure that the MAC address of
each NE is unique in the network.
Caution!
Each of the three parameters must be configured. If you want to keep the
previous configuration, just press Enter key without input other information. Do
not drop out the configuration, which will result that the ANCP board always waits
for configuration .
D-5
Steps
1. Switch all the pins of the DIP switch S1 on the ANCP board to "ON" position to set the
ANCP board to download status.
2. Input the command telnet 192.192.192.11 on the EMS computer.
You are required to input the user name and password.
3. Input the user name zte and password ecc, and then press Enter key.
A prompt ZTE+ is displayed.
4. Input the command d-erase -d1 after the prompt ZTE+ to clear the database in the CF
card of the ANCP board.
– End of Steps –
D-6
Steps
1. Input the command ftp 192.192.192.11 in the DOS command line window on the
EMS computer.
2. Input the user name zte and the password ecc when prompted to log in to the ANCP
board.
A prompt ftp> appears after successful login.
3. Input the command bin after the prompt ftp> to set the file transfer format.
4. Input the command put application/logical program or configuration
file path (including file name) to transfer the application/logical program
or configuration file to the CF card.
5. Input the command ls –l to verify that the size of file transferred to the CF card is
consistent with the one on the EMS computer.
6. Input the command bye to exit the FTP utility.
– End of Steps –
Steps
1. Input the command telnet 192.192.192.11 in DOS command line window on the
EMS computer
2. Input the user name zte and password ecc, and then press Enter key.
A prompt ZTE+ appears.
3. Input a command following the format below to load the application/logical program to
the ANCP board.
ZTE+>d-upgrade Subrack No. Slot No. Board CPU No. -p application file name or -f
logical program file name
The following table describes the parameters in the d-upgrade command.
Parameter Description
Subrack No. The number of subrack where the ANCP board is installed. It
is generally 1.
Slot No. The number of slot in which the board is installed. The slot No.
of ANCP board is 18.
D-7
Parameter Description
Note:
– End of Steps –
D-8
Context
Figure D-3 shows the preparation flow before remote initialization.
Steps
1. Check and make sure that the connection between the EMS computer and the access
NE is normal.
D-9
2. Set the IP address of the EMS computer, which should be in the same network
segment as the access NE, and set the subnet mask of the EMS computer as
255.255.255.0.
3. Ping the access NE on the EMS computer to check whether the connection between
them is normal.
If it is unsuccessful to ping the access NE, check the running status of the access NE
and the network cable connecting it to the EMS computer.
4. Ping the NE to be initialized on the EMS computer to make sure that the route to the
NE is normal.
If it is unsuccessful to ping the NE, perform the following checkups.
a. Log in to the access NE via the telnet utility on the EMS computer, and check the
route table of the access NE to find whether the table contains the route information
of the NE to be initialized. If no, check for ECC fault.
b. Check the route information on the EMS computer. If there is no route information
of the NE, add it.
– End of Steps –
Steps
1. Check and make sure that the NE to be initialized is in running status, which means
that the pins of the DIP switch on its ANCP board are not switched to the same position.
2. Input the command ftp 192.192.20.18 in the DOS command line window on the
EMS computer.
3. Input the user name zte and the password ecc when prompted, to log in the remote
NE.
A prompt ftp> appears.
4. Input the command bin after the prompt ftp> to set the file transfer format.
5. Input the command put application/logical program or configuration
file path (including file name) to transfer the application/logical program
or configuration file to the CF card in the NE's ANCP board.
6. Input the command ls –l to verify that the size of file transferred to the CF card is
consistent with the one on the EMS computer.
7. Input the command bye to exit the FTP utility.
– End of Steps –
D-10
Context
Suppose the IP address of the ANCP board is 192.192.20.18 and the program file name
is "ANCP-ZXMPS385–PRG-V3.00R1P07.bin".
Steps
1. Input the command telnet 192.192.20.18 in the DOS command line window on the
EMS computer.
2. Input the user name zte and then the password ecc when prompted.
A message User zte logged in appears after successful login. You can input the
command help to check available commands related to upgrade operations, see
Figure D-4.
D-11
Note:
l You can check the help information of this command by inputting d-upgrade in the
command line.
l Change –p to –f if the program is a logical program.
Note:
6. Input n if it is unnecessary to clear the database, see Figure D-6, and then the trial run
of the program starts.
D-12
Caution!
If it is necessary to clear the database, input y instead. Then all NE information in the
ANCP board will be erased.
Caution!
Observe the running status of the board during the trial run of the program. Perform
the next step in time after making sure that the board is working normally. Or else, the
board will run the original program before loading the new program after 15 minutes.
After the command is successfully executed, both the try-run type and status are
shown as try-run, see Figure D-7. If the command fails, status are shown as slave
instead, which means that the older version program is running.
D-13
9. Input the command d-active 1 18 1 -p, and input y when prompted to active the
loaded program, see Figure D-8.
Note:
D-14
10. Input the command d-get-status to check whether the status of the board turns into
master, which makes it unnecessary to reset the ANCP board.
– End of Steps –
Prerequisite
Before the loading procedure, make sure that the application/logical program files are
available in the CF card of the active ANCP board.
Context
Suppose the IP address of the active ANCP board is 192.192.20.18. For dual ANCP
boards, we load the application/logical programs to the standby one first. After the loading
procedure completes, the standby ANCP board becomes the active one. Then switch the
active one into the standby status. Repeat the loading procedure to load the programs to
the original active ANCP board.
Steps
1. Input the command telnet 192.192.20.18 in the DOS command line window on the
EMS computer.
2. Input the user name zte and then the password ecc when prompted.
A message User zte logged in appears after successful login.
3. Input the command a-set-debugon on.
4. Input the password ecc
5. Input the command a-get-sysinfo state to check the information of the active ANCP
board so as to get the slot No. of the standby ANCP board, see Figure D-9.
address: 11201 in the above figure contains the slot number information "12" of the
active ANCP board, which is a hexadecimal number. It indicates that the active ANCP
D-15
board is installed in slot 18. Then we can conclude that the standby ANCP board is
installed in slot 19.
6. Input a command following the format below to load the application/logical program to
corresponding program region of the standby ANCP board.
ZTE+> d-upgrade Subrack No. Slot No. Board CPU No. -p application file name or -f
logical program file name
The following table describes the parameters in the d-upgrade command.
Parameter Description
Subrack No. The number of subrack where the ANCP board is installed. It is
generally 1.
Slot No. The number of slot in which the board is installed. The slot No. of
ANCP board is 18 or 19.
-f It indicates that the logical program file following it will be written to the
board.
From the result of Step 3, we know the slot No. of the standby ANCP board is 19.
Figure D-10 shows corresponding command to load the application program for
example.
Figure D-11 shows corresponding command to load the logical program for example.
D-16
Figure D-11 Remote Loading Example of Logical Program (Standby ANCP Board)
Verify the following information shown on the window: download date, download
version, status, upgrade database, start address and file length.
8. Input the command d-try 1 19 1 –p to try running the loaded application program.
When prompted with Do you want to upgrade the DB area?Yes[y]/No[n]: y, input y.
D-17
The standby ANCP board restarts and runs the loaded program, which results in the
communication interruption with the active ANCP board for 1 to 2 minutes. During this
period, you can not perform any operation on the standby ANCP board via the active
one.
Note:
Change –p to –f if the program is a logical program.
9. After the standby ANCP board restarts successfully, input the command d-get-status
1 19 1 to check the trail run result, seeFigure D-13.
D-18
Caution!
Observe the running status of the board during the trial run of the program. Perform
the next step in time after making sure that the board is working normally. Or else, the
board will run the original program before loading the new program after 15 minutes.
Note:
Change –p to –f if the program is a logical program.
11. Input the command d-get-status 1 19 1 to verify the activation of program, see Figure
D-15.
D-19
l upgrade database: turns into "NO", which means the loading procedure
completes
l start address: start address of the program region
l file length: same as the trial run result
l try-run elapsed time: reserved
l try-run remained time: reserved
12. Input the command d-set-ncpstate back to switch the active ANCP board into the
standby status, see Figure D-16.
13. Repeat Step 4 to Step 9 to load the programs to the original active ANCP board, which
has been switched into a standby one in Step 10.
Caution!
Be cautious that the slot No. of the board is 18 and therefore the slot No. in
corresponding commands should be 18 but not 19 during the loading procedure.
– End of Steps –
Steps
1. Switch the pins of the DIP switch S1 on the ANCP board and make sure that some
of them are on "ON" position while the others are not, so as to reset the ANCP board
and set it to the running status.
Note:
If an ANCP board has been set into the download status by means of restart or ring
trip button during the local initialization, it can be set into the running status by being
pulled out from corresponding slot and inserted into the slot again.
2. Set the IP address of the EMS computer, which should be in the same network
segment as the IP address of the NE where the ANCP board is installed.
D-20
3. Ping the NE on the EMS computer to check whether the communication between the
EMS and the NE is normal.
4. In the operation window of the EMS NetNumen T31, select the NE in the Topology
Management view and select Common Config > Data Sync.. The Data Sync. dialog
box is displayed.
5. Click Download tab in the Data Sync. dialog box.
6. Tick the check box(es) corresponding to the items to be downloaded and then click
Download button.
An alert box pops up to prompt you to confirm the download operation.
7. Click Yes to start the download of database.
After successful download, a message box pops up to prompt the success information.
Note:
It is unnecessary to download database when there is only logical program with new
version is loaded to the ANCP board during upgrade.
– End of Steps –
Steps
1. Double-click the NE to be checked in the Topology Management view. The Card
Management dialog box is displayed.
2. Right-click the ANCP board to be queried in the Card Management dialog box,
and then select the shortcut menu. The Card Run-time Version message box is
displayed.
The Card Run-time Version message box shows the version information of the
selected ANCP board, including PCB version, FPGA (logical program) version
and software (application program) version. The consistency between the version
information and the that of the actually-loaded programs indicates that the loaded
programs are normally running in the ANCP board.
– End of Steps –
D-21
D-22
E.1 Overview
Simple commissioning is a remote initial configuration method for the equipment without
the necessity for getting to the site where the equipment is located.
Application Scenario
For the application scenario of simple commissioning, see Figure E-1.
NE1, NE2, NE3, and NE4 are existing equipment in the network. NE5 and NE6 are
equipment to be enabled. NE1 is connected with the EMS, so that NE5 and NE6 can
be enabled remotely from NE1.
Operating Principle
When a new device is added in the network, data can be transmitted in the underlayer
channel of the Data Communications Channel (DCC), as long as the new equipment and
existing equipment are connected by fibers, and share the same rate. In that case, users
E-1
can execute the underlayer DCC commands on the existing equipment to perform the
initial configuration for the new equipment, and manage the new equipment on the EMS.
Requirements
The following requirements should be satisfied during the simple commissioning:
l Both the access NEs and the NEs to be enabled support simple commissioning.
l EMS version: NetNumen U31 R22 V12.11.40 -B06 or later
l Equipment version: ENCP-ZXMPS385-PRG-V2.50R3P05.bin or later
l All NEs are powered on, and operating normally. The fiber connections are correct.
l The NEs to be enabled have already been created on the EMS. The NE addresses
have been planed.
Note:
In the ZXMP S385, only the ENCP board supports the simple commissioning function.
Operation Flow
For the operation flow of the simple commissioning, see Figure E-2.
E-2
Prerequisite
l All NEs are powered on, and operating properly. The fiber connections are correct.
l The NEs to be commissioned have already been created on the EMS. The NE
information have been planed.
E-3
Context
For the network planning, see Figure E-3.
Steps
1. Verify that the DCC on NE5 which is to be enabled is proper.
a. On the EMS computer, execute the telnet 192.168.2.18 command to log in to NE2.
b. Enter the user name (zte) and password (ecc). Press Enter. The prompt ZTE+>
is displayed.
c. Execute the ecc-cmd ckchan 5 1 command to check the DCC status of port 1 of
the board in slot 5.
l If the connection is properly, go to Step 2.
l If the connection is overtime, check the fiber connection or DCC configuration
and eliminate DCC faults.
2. Disable the OSPF protocol of NE2.
a. ZTE+>ecc-cmd enable-ospf 5 1 1 // Disable the OSPF protocol of port 1 of the
board in slot 5.
Note:
The last "1" in this command indicates that OSFP protocol will be disabled. If it is
a "0", it indicates that the OSPF protocol will be enabled.
E-4
6. Reset NE2.
Execute the ZTE+>d-reboot command.
After NE2 is reset, users can manage NE5 on the EMS.
– End of Steps –
Prerequisite
l All NEs are powered on, and operating normally. The fiber connections are correct.
l The NEs to be commissioned have already been created on the EMS. The NE
information have been planed.
Context
For the network planning, see Figure E-4.
E-5
Steps
1. Verify that the DCC on NE5 which is to be enabled is normal.
a. On the EMS computer, execute the telnet 192.168.2.18 command to log in to NE2.
b. Enter the user name (zte) and password (ecc). Press Enter. The prompt ZTE+>
is displayed.
c. Execute the ecc-cmd ckchan 5 1 command to check the DCC status of port 1 of
the board in slot 5.
l If the connection is normal, jump to Step 2.
l If the connection is overtime, check the fiber connection or DCC configuration
to eliminate DCC faults.
2. Disable the OSPF protocol of NE2.
a. In the Topology Management view, right-click NE2, and select NE Manager from
the shortcut. The NE Manager dialog box is displayed.
b. In the NE Operation navigation tree, select System Config > DCN Management
> OSPF Enable Set. The OSPF Enable Set screen is displayed.
c. Select the corresponding board and port of NE2, and set OSPF Use State to
Disable.
Parameter Configuration
E-6
Parameter Configuration
d. Click Apply.
3. Reset NE2.
a. In the Topology Management view, double-click NE2. The Card Management
dialog box is displayed.
b. Right-click the ENCP board, and select Reset Board from the shortcut. The Reset
Board dialog box is displayed.
c. Set the reset mode to Soft Reset or Hard Reset. Click Apply.
4. Configure the IP address and subnetwork mask of NE5, and the domain where NE5
is located.
a. In the Topology Management view, right-click NE2, and select NE Manager from
the shortcut. The NE Manager dialog box is displayed.
b. In the NE Operation navigation tree, select System Config > DCN Management
> Device Easy Open. The Device Easy Open screen is displayed.
c. Select the corresponding board and port of NE2, and configure the IP address and
subnetwork mask of NE5, and the domain where NE5 is located.
Parameter Configuration
d. Click Apply.
NE5 will be reset automatically.
5. Enable the OSPF protocol of NE2.
E-7
The operations are the same as those in Step 2. For the OSPF configuration of NE2,
refer to Table E-3.
Parameter Configuration
6. Reset NE2.
a. In the Topology view, double-click NE2. Board View is displayed.
b. Right-click the ENCP board, and select Board Reset from the shortcut. The
Board Reset dialog box is displayed.
c. Set reset mode to be Hard Rest or Soft Rest as required. Click Apply.
After NE2 is reset, users can manage NE5 on the EMS.
– End of Steps –
E-8
F-1
The board replacement steps in the flowchart are described in detail as below:
To ensure normal working of the system after replacement with the spare board, pay
attention to the following precautions:
a. Determine the spare board type according to the board to be replaced, and make
sure its model is consistent with the board to be replaced.
F-2
b. Check if the spare board has any apparent damage, and ensure that it works
normally.
c. Make sure that the PCB version and software version of the spare board are
compatible with the current NE and EMS.
d. When the board to be replaced is configured as warm backup mode (such
as the CSA board), ensure that the software and hardware versions of both
active/standby boards are completely consistent after replacement.
2. Preparing a label
The label is used to identify the board that has been unplugged during the replacement.
The label size is decided by the maintenance personnel. The label contents include the
site name, equipment name, fault cause, board name, handling process, the handling
person, and time.
3. Switching the service
For the board configured with service protection or backup, the service function
processed by it should be switched to the standby board, so that the service is not
interrupted by board unplugging.
While unplugging the board without service protection or backup, the service function
of this board would be interrupted.
4. Unplugging the board
Caution!
Board unplugging operation may interrupt the service, or even can stop the working of
the whole NE. Ensure to make enough preparations before the operation.
Before unplugging the board, unplug the fiber pigtail and cable connected to the board
panel.
5. Labeling the faulty board
Stick the prepared label onto the PCB of the faulty board unplugged.
6. Plugging the board
Plug and install the spare board, and restore connections of the fiber pigtails and
cables to the board.
7. Recovering the service function
Once the spare board is installed, its service function should be recovered
immediately. Check the board/equipment working status. Verify the normal working of
both the equipment and the service functions to ensure successful board replacement.
Otherwise, perform troubleshooting till the equipment work and service functions
become normal.
F-3
Context
Taking NCP board as an example, the board replacement procedure is described as
follows:
Steps
1. Prepare the spare board and label as described in the section "Flowchart of Board
Replacement". Ensure the compatibility among the BOOTROM and main program of
the NCP board, and the EMS software.
2. Unplug the board that needs to be replaced and paste the label.
3. Set DIP-switch of the spare NCP board to full ON state, and plug the board into the
sub-rack. Then execute the command ping 192.192.192.11 on the EMS computer
to check if it can ping the NE successfully.
4. Download the application and initial parameters via FTP, which are consistent with
the original NCP board. Refer to the Unitrans ZXMP S385 (V3.10) SDH Based
Multi-Service Node Equipment Maintenance Manual (Volume III) Troubleshootings
for the details of NCP program download.
5. Set the fourth digit of the DIP switch on the NCP board to OFF, and write the NE
configuration data into the NCP board with EMS software. Refer to the Unitrans
ZXMP S385 (V3.10) SDH Based Multi-Service Node Equipment Maintenance Manual
(Volume III) Troubleshootings for the details of configuration data download.
6. After replacement, select the NE that has replaced the NCP board in the operation
window at the EMS client. If the NCP time can be extracted, it indicates that the NCP
board is successfully replaced.
– End of Steps –
F-4
Steps
1. Prepare the spare board and label it as described in the section "Flowchart of Board
Replacement". The two CSA/CSE/CSF/CSC boards of warm-backup configuration
must have consistent PCB versions.
2. If the CSA/CSE/CSF/CSC boards are configured in the warm backup mode,
switch the system clock to the other CSA/CSE/CSF/CSC board through EMS,
unplug the CSA/CSE/CSF/CSC board to be replaced, attach the label, plug the
spare board, and switch the system clock to the plugged CSA/CSE board. If the
CSA/CSE/CSF/CSC board is not configured in the warm backup mode, directly
unplug the CSA/CSE/CSF/CSC board, attach the label, and plug the spare board.
– End of Steps –
Steps
1. Prepare the spare board and label as described in the section "Flowchart of Board
Replacement".
2. Unplug the board to be replaced, attach the label, and plug the spare board.
3. Confirm that the replacement is successful.
After replacement, the green NOM indicator on the board flashes slowly and regularly,
and the orderwire phone and data service are normal. These indicate that the board
replacement is successful.
– End of Steps –
F-5
Context
The optical line board (OL1x4,OL1x8, OL4x2, OL4x4, OL16, OL16x4, OL16x8, OL64,
OL64x2, or OL64FEC/OL64FECx2) is hot pluggable.
l Its replacement will interrupt the service in case of unprotected networking.
l In protected networking if switched to protection mode, the service will not be inter-
rupted.
Note:
The board replacement when the multiplex section switching ring is configured is too
complex to describe. Conduct this kind of board replacement under the guidance of ZTE
maintenance engineers.
Steps
1. Board replacement without service protection configured
a. Prepare the spare board and label as described in the section "Flowchart of Board
Replacement".
b. Unplug the fiber pigtail connected to the optical interface, unplug the board to be
replaced, attach the label, plug the spare board, and connect the fiber pigtail.
c. Confirm that the replacement is successful.
After replacement, the green NOM indicator light on the board flashes slowly and
regularly; and the green TX and RX indicator lights, corresponding to the optical
interface for the original service, are constantly on. These indicate that the service
is normal and the board replacement is successful.
2. Board replacement with path protection configured
a. Prepare the spare board and label as described in the section "Flowchart of Board
Replacement".
b. Unplug the fiber pigtail connected to the optical interface, unplug the board to be
replaced, attach the label, plug the spare board, and connect the fiber pigtail.
c. Confirm that the replacement is successful.
After replacement, the green NOM indicator light on the board flashes slowly and
regularly; and the green TX and RX indicator lights, corresponding to the optical
interface for the original service, are constantly on. These indicate that the service
is normal and the board replacement is successful.
– End of Steps –
F-6
Steps
1. Prepare the spare board and label as described in the section "Flowchart of Board
Replacement".
2. Unplug the board to be replaced, attach the label, and plug the spare board.
3. Confirm that the replacement is successful.
If the green indicator NOM on the board blinks slowly and regularly after replacement,
and the service performance is normal, it indicates the board is successfully replaced.
– End of Steps –
Steps
1. Prepare the spare board and label as described in the section "Flowchart of Board
Replacement".
2. Unplug the board to be replaced, attach the label, and plug the spare board.
3. Confirm that the replacement is successful.
If the green indicator NOM on the board blinks slowly and regularly after replacement,
and the service performance is normal, it indicates the board is successfully replaced.
– End of Steps –
Steps
1. Prepare the spare board and label as described in the section "Flowchart of Board
Replacement".
2. Unplug the board to be replaced, attach the label, and plug the spare board.
3. Confirm that the replacement is successful.
If the green indicator NOM on the board blinks slowly and regularly after replacement,
and the service performance is normal, it indicates the board is successfully replaced.
– End of Steps –
F-7
Steps
1. Prepare the spare board and label as described in the section "Flowchart of Board
Replacement".The OEL1x16 board provides optical interface and electrical interface,
so make sure to select the corresponding interface module according to the interface
type.
2. Unplug the fiber pigtail or cables connected on the front panel of board. Unplug the
board to be replaced, attach the label, plug the spare board, and connect the fiber
pigtail.
Steps
1. Prepare the spare board and label as described in the section "Flowchart of Board
Replacement".
2. Unplug the fiber pigtail or cables connected on the front panel of board. Unplug the
board to be replaced, attach the label, plug the spare board, and connect the fiber
pigtail.
3. Confirm that the replacement is successful.
After replacement, the green NOM indicator light on the board flashes slowly and
regularly. It indicates that the board performance is normal, and the board replacement
is successful.
– End of Steps –
F-8
Steps
1. Prepare the spare board and label as described in the section "Flowchart of Board
Replacement".
2. Unplug the fiber pigtail or cables connected on the front panel of board. Unplug the
board to be replaced, attach the label, plug the spare board, and connect the fiber
pigtail.
3. Confirm that the replacement is successful.
After replacement, the green NOM indicator light on the board flashes slowly and
regularly. It indicates that the board performance is normal, and the board replacement
is successful.
– End of Steps –
Steps
1. Prepare the spare board and label it as described in the section "Flowchart of
Board Replacement". The two SMI boards of warm-backup configuration must have
consistent PCB versions. Be aware about the compatibility of BOOTROM, major
program and EMS software.
2. If SMI board is configured as hot backup, switch the system clock to another SMI board
via EMS. Unplug the SMI board to be replaced, attach the label, plug the spare board,
and switch the system clock to the new SMI board. If SMI board is not configured as
hot backup, directly unplug the SMI board to be replaced, attach the label, and plug
the spare board.
3. Unplug the board that needs to be replaced and paste the label.
Result
After replacement, the green NOM indicator light on the board flashes slowly and
regularly. It indicates that the service performance is normal, and the board replacement
is successful.
F-9
F-10
Table G-1 Relations Between NCP/ENCP/ANCP Running Status and Indicator Status
• Flashing once a second means that an indicator is on for half second and then off for half second
periodically.
• The symbol "-" indicates an uncertain status.
Note:
G-1
Table G-2 Relations Between CSA/CSE Running Status and Indicator Status
• Flashing once every two seconds means that an indicator is on for one second and then off for one second periodic
ally. Flashing once a second means that an indicator is on for half second and then off for half second periodically.
• The ALM1 yellow indicator flashes only during board self-check and program download.
• The symbol "-" indicates an uncertain status.
Table G-3 describes the relations between the CSF/CSC running status and the indicator
status.
G-2
Table G-3 Relations Between CSF/CSC Running Status and Indicator Status
G-3
• Flashing once every two seconds means that an indicator is on for one second and then off for one second periodic
ally. Flashing once a second means that an indicator is on for half second and then off for half second periodically.
• The ALM1 yellow indicator flashes only during board self-check and program download.
• The symbol "-" indicates an uncertain status.
Table G-4 Relations Between OW Board Running Status and Indicator Status
• Flashing once a second means that an indicator is on for half second and then off for half second
periodically.
• The symbol "-" indicates an uncertain status.
G-4
• Flashing once every two seconds means that an indicator is on for one second and then off for one
second periodically. Flashing once a second means that an indicator is on for half second and then
off for half second periodically.
• The symbol "-" indicates a particular status.
Table G-6 Relations Between Indicators and the OAD Board Running Status
• Flashing once every two seconds means that an indicator is on for 1 second and then off for 1 second
periodically.
• The ALM1 yellow indicator flashes only during board self-check and program download.
• The symbol "-" indicates an uncertain status.
G-5
• Flashing once every two seconds means that an indicator is on for 1 second and then off for 1 second periodically.
• The ALM1 yellow indicator flashes only during board self-check and program download.
• The symbol "-" indicates an uncertain status.
Table G-8 Relations Between Electrical Tributary Board Running Status and Indicator
Status
• Flashing once a second means that an indicator is on for half second and then off for half second
periodically.
• The symbol "-" indicates an uncertain status.
G-6
Table G-9 Relations between OPE1Z Board Running Status and Indicators' Status
Note:
l Flashing (0.5 Hz) means the indicator is ON for 1 second and is OFF for the other 1
second.
l Flashing (1 Hz) means the indicator is ON for 0.5 second and is OFF for the other 0.5
second.
l The ALM1 yellow indicator flashes only during board self-check and program
download.
l "-" indicates uncertain status.
l When the optical interface is not configured with services, the indicator status is
uncertain.
G-7
Table G-10 Relations Between Optical Line Board Running Status and Indicator Status
• Flashing once every two seconds means that an indicator is on for one second and then off for one second periodic
ally. Flashing once a second means that an indicator is on for half second and then off for half second periodically.
• The symbol "-" indicates an uncertain status.
G-8
Table G-11 Relations Between OEL1x16 Running Status and Indicator Status
• Flashing once every two seconds means that an indicator is on for 1 second and then off for 1 second
periodically.
• The ALM1 yellow indicator flashes only during board self-check and program download.
• The symbol "-" indicates an uncertain status.
Table G-12 Relations Between TGE2B/TGSAx8 Running Status and Indicator Status
• Flashing once a second means that an indicator is on for half second and then Not lit for half second periodically.
• The symbol "-" indicates an uncertain status.
G-9
Table G-13 describes the relations between the SEC/SEE/SEEU/RSEB board running
status and the indicator status.
Table G-13 Relations Between SEC/SEE/SEEU/RSEB Running Status and Indicator Status
• Flashing once a second means that an indicator is on for half second and then Not lit for half second periodically.
• The symbol "-" indicates an uncertain status.
Table G-14 describes the relations between the SE10G2 board running status and the
indicator status.
Table G-14 Relations Between the SE10G2 Board Operation Status and Indicator Status
G-10
• Flashing once every two seconds means that an indicator is lit for one second and then no lit for one
second periodically. Flashing 1.5 times per second means that an indicator is lit for 1/3 second and
then not lit for 1/3 second periodically.
• The ALM1 yellow indicator flashes only during board self-check and program download.
• The symbol "-" indicates an uncertain status.
Table G-15 describes the relations between the SEG4 board running status and the
indicator status.
Table G-15 Relations Between the SEG4 Board Operation Status and Indicator Status
G-11
• Flashing once every two seconds means that an indicator is lit for one second and then no lit for one
second periodically. Flashing 1.5 times per second means that an indicator is lit for 1/3 second and
then not lit for 1/3 second periodically.
G-12
• The ALM1 yellow indicator flashes only during board self-check and program download.
• The symbol "-" indicates an uncertain status.
Table G-16 Relations Between AP1x8 Operating Status and Indicator Status
• Flashing once every two seconds means that an indicator is on for 1 second and then off for 1 second periodically.
• The ALM1 yellow indicator flashes only during board self-check and program download.
• The symbol "-" indicates a particular status.
G-13
DOWNLOAD All ON After power-on, three indicators flash quickly for 14 times,
and BOOT can normally execute self-test for memory.
If the self-test fails, the red indicator is reset after flashing
10 times. Otherwise, the yellow indicator and red indicator
will be ON.
RUN Not all ON not all 1. After power-on, three lights flash once, and test if the
OFF NCP/ENCP/ANCP/ANCPB board can be powered on
normally.
2. Three lights quickly flash, and self-test for memory
is executed.
3. NCP program will be decompressed and uploaded
to memory after the green indicator lights up for 4
seconds. After uploading, the green indicator goes
out.
4. The NOM indicator flashes twice per second after
three lights go out for about 60 seconds. If an alarm
occurs, the alarm indicator lights up.
• Flashing twice per second means that the indicator is ON for one second and is OFF for another one
second.
Table G-18 Indicator Status of Other Boards During Power-On and Initialization
1 Board power-on The red, yellow and green indicators light up for one second, and
then go out for another one second.
2 RAM self-test l The green, yellow and red lights flash (1.5 times/second), and
other lights are all OFF.
l If memory self-test fails, the red light flashes (1.5 times/second),
and other lights are all OFF.
G-14
3 Loading l Green light flashes (5 times/second), and other lights are all OFF
application (if boards have application programs, load from local memory;
program if the programs need to be upgraded, download from the NCP
board).
l If program or FPGA file for uploading cannot be found, yellow
light flashes (5 times/second), and other lights are all OFF.
l If problems occur when writing Flash, red light flashes (5
times/second), and other lights are all OFF.
4 Downloading l The red and green lights flash (1.5 times/second), and other
FPGA program lights are all OFF.
and chip self-test l If FPGA downloading fails, the yellow light flashes (1.5
times/second), and other lights are all OFF.
l If self-test for chips fails, the red light flashes (1.5 times/second),
and other lights are all OFF.
l If detection for board address fails, the red and yellow lights flash
(1.5 times/second), and other lights are all OFF.
5 Critical l The red and yellow lights are OFF, while the green light is ON.
configuration l If no configuration information are received within 10 seconds,
report again.
l After receiving the commands for property configuration, the
yellow indicator lights up. If all the information are not completely
received within 30 seconds, repeat the process described above.
After completely receiving commands for critical configuration,
the yellow light goes out.
6 Preheat l The green light flashes (1.5 times/second), the red and yellow
lights are OFF, and no alarm status display on the other indicators
(such as the interface status indicator of optical line board).
l The process of preheat is 2 minutes. At the same time, process
the commands from EMS, and detect the alarms without
reporting, lighting up and switching. Wait for other boards to be
in the status of normal running.
7 Running normally The green light flashes twice per second. At the same time, detect
alarms, which are indicated by default.
G-15
After configuration, the NOM indicator light flashes quickly for two minutes, and then it
periodically flashes once every two seconds, and the ALM2 indictor light indicates the
alarm status of board.
G-16
II
III
IV
VI
FLSM
- Full Length Subnetwork Mask
FTP
- File Transfer Protocol
IP
- Internet Protocol
LOS
- Loss of Signal
MAC
- Media Access Control
MODEM
- Modulator-Demodulator
NTP
- Network Time Protocol
OA
- Optical Amplifier
OSPF
- Open Shortest Path First
VII
PCB
- Printed Circuit Board
PDH
- Plesiochronous Digital Hierarchy
SDH
- Synchronous Digital Hierarchy
VLSM
- Variable Length Subnet Mask
VIII