You are on page 1of 1

27th November -21

Consultants: Amee Associates


Client: Dhriva Foods Pvt. Ltd.
PEB Specifications for DHRIVA FOODS PVT. LTD. AT GALLOPS INDUSTRIAL PARK , BAWLA
ROAD

1. PEB Building size : 36.195 (Steel Line ) x 26.740 ( Steel Line )


2. PEB Columns start from -250 mm from Floor
3. Brick Wall up to 3 mt & above Cladding on three sides
4. Brick Wall up to 5.20 mt & above Cladding on 4th side wall ( Passage side )
5. Sky Light Polycarbonate sheet 2 mm th. : 2.5 % on Roof & on three side walls.
6. Purlins & Girths : Pre Galvanized 120 GSM
7. Solar Panel provision on South side slope only & load 20 KN/ SqM
8. Turbo Vents: 600 mm Dia. – 10 Nos.
9. Canopy : 1 No. 7.2 mt ( one bay ) x 3 mt projection with Sofit
10. Framed Opening : 1 No. 3 mt W x 4 mt H
11. Jack Beams : On Grid C & E : 4 Nos. as shown in drawing
12. ROD BRACING not allowed wherever Opening / Doors are shown.
13. R.W. Pipes shall be 1100 mm below FFL.
14. Need to mention make of Steel, Sheets & Accessories
15. Need to submit both Options: Bird Proof & without Bird proof (Regular).
16. Painting : 100 DFT Epoxy
17. Minimum thickness of Primary members : 4 mm & Secondary members : 1.5 mm
18. SESMIC Zone : III OR AS PER IS CODE
19. Wind Speed : 39 M/S OR AS PER IS CODE
20. Roof: 0.47 mm th. Bare Galvalume sheet 550 MPa Yield Strength, Wall Sheeting: 0.50 mm th.
Color Galvalume 550 MPa yield Strength
21. Eaves Height: 8 mt. from FFL
22. Deflection Criteria : Vertical Deflections : L / 180, Horizontal : H/90, For Purlins : L /150,
Girth : L /150
23. Design Code : ASIC -2005
24. Load combinations & Serviceability: MBMA-2006.
25. Need to give Guarantee for No Water leakages for 5 Years & Structural Stability for 25 years.

You might also like