Professional Documents
Culture Documents
Medical Gas DBR
Medical Gas DBR
Medical Oxygen
Medical Oxygen 93 Percent USP/IP
Medical Air
Medical Nitrous Oxide
Medical Carbon Dioxide
Medical Vacuum ( Suction )
Anaesthetic Gas Scavenging System (AGSS)
Surgical Air -7
Each medical gas must be supplied from a separate system,
and it is essential that all parts of each system are gas specific
to ensure that there is no possibility of cross-connection
between any system
During the installation stage, extensive tests are carried out to verify that
there is no cross-connection.
Single MGPS line should not be used to supply Pathology departments,
dental department, general workshops or mechanical services.
ISO 7396-1/2 Origin European Nations (For ex: Italy, Spain, France, etc.)
(National Fire Protection Association) NFPA99- Origin, USA.
MANIFOLD
Duplex Control Manifold with automatic changeover connected to two
header bars High-Pressure, Low Flow System
Source for Primary supply or Secondary supply or the Emergency
Reserve supply Maximum 10 Gas Cylinders in each bank of the manifold
All the cylinders should stand vertically even during storage
Cylinders should be chained during use and standby
Each port is connected to a cylinder by flexible pigtail connections; a
header bar; and an outlet port Change over from “Duty” to the “Standby”
bank of cylinders shall be Automatic Preferably based on pneumatic
pressure Audio Visual Alarm system Average mounting Height at its
centre shall be 1650 mm from FFL
Three pressure gauges on the front of the control cabinet
Pneumatic relief valve in Hospital Distribution Line
Master alarm panel should be installed at a suitable place
• Installed at the place of duty of manifold technician
Audio-visual alarm should be there
It should be set for a 10-20% drop in the line pressure
PIPELINE NOMENCLATURE
Main Hospital Supply Pipeline or Gas Service Specific Trunk Pipeline:
from Manifold to Building
Feeder Pipeline which includes Risers: Horizontal & Vertical upto
distribution pipeline
Distribution Pipeline or Branch Pipeline: serves one floor or a part of it,
no vertical movement
Drop pipe: distribution to terminal units
PIPELINE MATERIAL
Medical Grade Copper, which is phosphorous deoxidised non-arsenical
copper conforming to BS EN 1412:1996 grade CW024A (Cu-DHP).
Seamless, round, solid drawn, sizes confirming to BS EN 13348
Suitable for installing vertically or horizontally without sagging or
distortion.
The material temper shall be as under.
For Tailpipe: R220
For Pipe of Nominal Outside Diameter (OD) 12 mm – 54 mm: R250 (half
hard)
For Pipe of OD 76 mm and above: R290 (hard)
PIPELINE INSTALLATION
All tubing, valves and fittings shall be thoroughly checked for any grease,
oil or other combustible material
Nitrogen Purge: During the brazing of pipe connections the interior of the
pipe shall be purged continuously with Nitrogen
Silver Brazing: Flux-less silver brazing alloy to be used, silver copper-
phosphorus brazing alloy CP 104 conforming to BS EN 1044:1999. Soft
solder or 50/50 solder must NEVER be used on a Medical Gas System
Before the wall outlets are installed, blow the pipes free of any
particulate Pressure Testing Locating Leaks Cross-connection Testing
Pipe sizing is determined either by Volume of Gas to be delivered or by
impact of overall pressure required.
When sizing, for Medical Vacuum, always provide pipes of one size
higher diameter to prevent clogging.
• No pipe smaller than 12 mm OD shall be used anywhere in the MGPS
Installation. No pipe smaller than 15 mm OD shall be used anywhere in
this installation in the Surgical Suite including Operating Rooms, pre-
operative and post-operative Wards.No pipe smaller than 15 mm OD
shall be used anywhere in the installation for the Medical Vacuum
Service.
All valves shall be of the lever ball type
• Flanged O-ring seal connections
Which open and close with a 90- degree rotation
• The handle should be in line with the pipeline when open
All Valves are in Open position in a commissioned MGPS system
Main Line Valve (Source Shut Off Valve):
• Provided at outlet of the supply source
• Must always be accessible to authorized persons only
Branch Valves including Riser Valves:
• Base of risers and every major branch
• Placed in secured location Line Valves Assembly (LVA)
• Provided at the defined sections
• At entry & exit of each section Zone Valves
• Provided at each fire zone
• Accessible to floor staff
• Accessible to the fire staff
• Should be marked in floor evacuation plan
Area Valve Service Unit Modules (AVSU).
• Area Valves, when provided with NIST Gas Specific Connectors, Gas
Pressure Switch, and Pressure Gauge (optional)Single Gas Service Unit
or Multi-gas Service Unit Installed at 1000mm to 1800mm height
Assist in Emergency Gas Alarm ManagementAlarm and Monitoring
Display Unit should be installed at the Nursing Station.Audio Visual
Alarm system
• Should be placed at the nursing stations
• It should display the pressure of various MGPS lines
• The alarms should be set at the critical value of the pressure drop
Terminal units shall be leak proof and allow plugging of probes from
front
• Push to insert and press-to-release mechanism for probes.
• Self-sealing valve on disengaging the probe
• Non return valve for ease of line servicing and repairing
• Colour-coded, Gas Specific front plate
• Terminal units shall be leak proofArea Valve Service Unit Modules
(AVSU).
• Area Valves, when provided with NIST Gas Specific Connectors, Gas
Pressure Switch, and Pressure Gauge (optional)Single Gas Service Unit
or Multi-gas Service UnitInstalled at 1000mm to 1800mm height
Assist in Emergency Gas Alarm Management Alarm and Monitoring
Display Unit should be installed at the Nursing Station. Mounting height
900- 1600mm from FFL, recommended 1300mm Dimensions of probes
shall be as per BS 5682:2005. It is essential that probes be machined
from stainless steel.
• Minimum clearance of 150 mm on either side Colour coding is
described in the table
Provided for dispensing gases in wards and patient care areas.
Also houses nurse call system, flow meters, infusion pumps, reading
light.Running panels along the walls.
For pipe sizing the design flow is assumed to be 40 LPM & 15 LPM
at 300 mm Hg in OT and wards respectively
Vacuum Pumps- duplex or triplex
• Tanks- two vacuum receivers
A PLC based controller with sequencing or cascading effect
Duplex filtration & isolation system, connected to the discharge (exhaust)
system with a silencer/ muffler Exhaust discharge at highest point of
building & away from any air intake Alarm to indicate vacuum pump
failure, integrate master alarm system Ward vacuum unit is equipped
with
• A regulator
• The vacuum bottle are available in various sizes from 250ml to 2 lts.
• Based on the usage bottle size may vary eg. OT needs larger bottle
size.
• Suction catheter is connected to the ward vacuum unit CENTRAL
PUBLIC.
MEDICAL AIR 4
Blending agent with Medical Oxygen when it is delivered to a patient
Considered as manufactured drug on- Site Delivered at a pressure of
370-400 Kpa Medical Compressed Air is monograph:
Oxygen II. Carbon Monoxide III.Carbon Dioxide IV.Nitrous Oxide + nitric
Oxide V.Sulphur Dioxide VI.Humidity 23.5% v/v > 10 ppm > 500 ppm >
2.5 ppm > 5 ppm Flow rate of MA4 is calculated to be 40 & 80 LPM per
point for OT and ICU respectively Compressors- Multiplex
• Oil & Moisture separator
• Air Dryer- refrigerant or Desiccant
• Air receiver
• A PLC based controller with sequencing or cascading effect
• Filtration system
• Drainage
An assembly of three filters must be placed for delivery of the clean Air:
1. Pre filter (5 or 1 μm ) 2.Fine/ Bacterial filter (0.01μm) 3.Coal Filter/
tower With the help of the filter assembly, we will be able to achieve
IS/ISO 7396-1 class air quality. Filters should be checked regularly for
clogging. The Medical Grade Air Compressors should use oil-free or oil-
less technologies to reduce post compressor treatment of compressed
air.
• Medical Grade Air Compressors deploy both Reciprocating and Rotary
Compressors Technologies. These include, but are not limited to, the
following.
TYPE OF COMPRESSORS
NIROUS OXIDE
Nitrous oxide (medical) is a colourless, odourless, tasteless gas. It is
supplied under pressure as a liquid in a cylinder with a valve to control
the outflow of gas. A variety of sizes of cylinders are available containing
different volumes of nitrous oxide. It is categorized as an inhalation gas.
There are no other ingredients. Nitrous oxide (medical) mixed with 30%
oxygen is used in general anaesthesia. It may be used with a wide
variety of other anaesthetic drugs allowing lower doses of the other
anaesthetic drugs. Nitrous oxide (medical) mixed with 50% oxygen is
used to reduce pain in a number of situations such as childbirth, dental
work and other painful procedures such as the wound and burn dressing,
the insertion of cannulae or needles into veins. It is occasionally used as
an insufflating agent in laparoscopy and as a refrigerant in cryosurgery.
Head injury. Pneumothorax.
Decompression sickness
. Following air encephalography.
Severe bulbous emphysema
. During myringoplasty
. Occluded middle ear
. Renal cyst.
Nitrous oxide should not be used as an analgesic or anaesthetic agent
for more than 24
hours, unless your doctor monitors you carefully. Take special care
with nitrous oxide (medical).
Care is needed in the handling and use of nitrous oxide (medical) gas
cylinders.
Nitrous oxide (medical) can be used if you are pregnant.
Breast-feeding.
Ask your doctor or pharmacist for advice before taking any medicines.
Nitrous oxide (medical) can be used if you are breast-feeding.
Driving and using machines.
It is recommended that you do not drive or operate machinery for 12
hours after the use
of nitrous oxide .
Nitrous oxide (medical) will be administered via inhalation and you will be
given a facemask, mouthpiece or nasal prongs to use. The facemask or
mouthpiece connected to nitrous oxide (medical) via a suitable medical
device. The device must be operated in the manner described by the
manufacturer. These systems will only be used to give you nitrous oxide
under the direct supervision of attendant and suitably trained medical
personnel. The concentration of nitrous oxide used in your treatment will
depend on the condition it is being used to treat. Your doctor will tell you
how long the treatment will nitrous oxide (medical) will last. Follow the
instructions given to you by your doctor. During use the cylinder should
be kept upright, away from heat in a well-ventilated area. Connections
for hoses, valves etc. must be kept clean and dry. If necessary, clean
only with plain water. Do not use solvents. Use clean, lint free cloths for
cleaning and drying off. Use no oil or grease on valve or associated
equipment. Do not allow naked flames near the cylinder. If you use more
nitrous oxide (medical) than you should: If you may have used more
nitrous oxide (medical) than you should, talk to a doctor or pharmacist as
soon as possible.