You are on page 1of 3

R&D digest

Quality of oil makes the difference


ABB discovers the solution to transformer breakdowns
Combined efforts by ABB specialists in Part of a winding with copper Copper sulphide deposits
power transformer technology and sulphide deposits on both When a failed winding was entirely dis-
1
chemistry have discovered a new reason conductor insulation and on a assembled turn-by-turn, a new piece of
for extreme caution when selecting the spacer. evidence was discovered. In some loca-
proper transformer oil. These new find- tions there was a shiny deposit on the
ings are based on a better understand- spacers and the conductor insulation,
ing of the phenomena that takes place especially in the wedges between
in oil filled transformers. spacer and conductor 1 . This deposit
was identified as copper sulphide, Cu2S.
The chemistry of the insulating oil has an
even greater impact on the life of the Influence on dielectric strength
transformer than was predicted by previ- The electric conductivity of Cu2S is sig-
ous knowledge, especially in combination nificantly higher than the conductivity of
with repetitive transients arising from, for paper and oil. This means that the pres-
example extreme numbers of line faults ence of Cu2S may change the electric
on an HVDC line. As a result, new firm field distribution, thereby decreasing the
recommendations and diagnostic meth- The investigation electric withstand strength inside the
ods will support all customers in elimi- The first step involved looking for any windings. In order to check this, a series
nating a previously not understood cause possible manufacturing or design defi- of tests on turn-to-turn models was car-
of transformer breakdowns. ciencies. A careful inspection of the ried out. These models were so called
windings revealed nothing in the area ‘pig-tail’ models. Conductors/spacers
Among the various causes for a power of the breakdown to indicate any manu- from a scrapped winding were investi-
transformer breakdown, ABB has investi- facturing mistakes. gated and both Cu2S –contaminated
gated one that is not very common, but materials and unaffected materials were
can nevertheless occur depending on The design was scrutinized with current tested.
materials and operating conditions. With state-of-the-art design tools. The voltage
a very large installed base of AC and transient behaviour of the windings The tests were performed using AC-volt-
HVDC transformers combined with ex- was evaluated by using both calcula- age. Both partial discharge (PD) initia-
tensive field experience, ABB was able to tions and measurements. The measure- tion voltage and breakdown voltage
investigate, in depth, this uncommon ments were performed by RSO (Recur- were registered.
type of transformer failure that have been rent Surge Oscillation). These two The results of these tests show that:
limited to a few geographical locations. methods gave approximately the same PD initiation voltage and the break-
result. The strength of the insulation down voltage of the Cu2S-coated
Some similarities were found between against repetitive transients was also material are significantly reduced as
transformers that had broken down. verified by experiments. The turn-to- compared to the uncoated material 2 .
These similarities were: turn insulation was subject to repetitive Uncoated and unaffected insulation
Frequent and high amplitude tran- voltage transients with a wave shape has the same strength as a brand new
sients similar to those caused by line faults. insulation.
Failures occurred in normal operation Not one breakdown occurred during
– shortly after external transients. this experiment even though the peak The outcome of the test showed that
However, no direct external cause for voltage of the transients was twice as the PD-initiation level, using coated
the breakdown was identified high as the measured value, and the materials, was reduced to levels compa-
Turn-to-turn breakdowns in windings number of transients corresponded to rable to the ones occurring during volt-
No break down paths to earth in the millions of line faults. The windings age transients.
transformers should resist these transients with a
Based on these observations the investi- considerable margin. It was concluded Impact from transients
gation was launched with only one goal that no design deficiency is causing the Although Cu2S lowers the PD-initiation
in mind: To find the ‘transformer killer’! breakdowns. level, depositions of copper sulphide on

ABB Review
3/2004 61
R&D digest
the windings alone are not sufficient to will in fact remain at normal service ings. It is the following chain of events
create a short circuit or partial discharge voltage until the insulation breaks that eventually leads to the formation of
between two turns. For either of these down, leading to a turn-to-turn fault. copper sulphide:
to happen, the insulation has to be fur- 1. The oil dissolves copper oxide.
ther degraded by frequent repetitive Mechanism of Cu2S formation 2. Dissolved copper reacts with mercap-
transients. Indeed, such transients may Copper is available in large quantities in tans and forms oil-soluble copper
occur in HVDC applications. a transformer, but the question remains mercaptides.
as to where the sulphur that reacts with 3. The copper mercaptides are trans-
An HVDC transformer is exposed to a the copper comes from. Before answer- ported by oil, and where conditions
commutation process when the current ing this, a few words about oil chem- are right they decompose forming
is transferred from one phase to an- istry is required. Transformer oil is basi- Cu2S and an oil-soluble organic
other. A rapid increase in terminal volt- cally a highly refined mineral oil. It con- residue.
age during this process results in fast sists mainly of a mixture of hydrocar-
voltage transients in the windings which bons, ie, compounds containing only The key reactions can be represented as
locally stress the insulation. carbon and hydrogen. There are also,
however, compounds containing other Cu2O + 2RSH => 2 CuSR + H2O
These transients may be high but even elements, eg,. oxygen, nitrogen and sul- (net of steps 1 and 2 above)
the worst transients in operation will be phur. Most compounds containing sul-
significantly lower than the transients im- phur can react with copper under ex- 2 CuSR => Cu2S + RSR
posed on the winding during dielectric treme conditions. However, only the (step 3 above)
testing of the transformer before delivery. mercaptans have any significant reactiv-
ity under normal conditions. Mercaptans where RSH is a mercaptan and R is any
The control angle (firing angle) a is react readily with many metals, for ex- alkyl or other hydrocarbon radical.
critical when it comes to the severity of ample copper, to form mercaptides. There are of course many different R’s.
the transients. The firing voltage intro- Some aspects of the chemistry of mer-
duce transients proportional to sin a. captans have been thoroughly studied The reactions above can, to some ex-
and present an explanation for our find- tent, take place in any transformer.
In normal continuous opera- Problems occur, however,
tion the rectifier valves are when low-refined oils of un-
fired at a ≈ 15 ° and the volt- Weibull diagrams mercaptans for PD initiation
inhibited or trace-inhibited
age stress is low. 2 type are used.
voltage level.

However, the HVDC convert- If all steps 1–3 take place in


ers have the possibility to the immediate vicinity of the
99
continuously operate at 95 copper conductor, copper sul-
90
higher control angles. An ex- 80 phide will only be found on
70
traordinary and serious event 60 the innermost paper. How-
50
is the a–90 operation that ever, if some copper is trans-
Probability (%)

40
causes very high stresses on 30 ported away from the copper
the turn-to-turn insulations. 20 surface, the final decomposi-
This operation occurs, for ex- 10
tion may take place else-
ample, during line faults D A where. For this process com-
5
which are normally rare and ponents in oil other than the
3
of short duration 3 . mercaptans will come into
2
play. Basic nitrogen com-
1
Thus, the road to this type of pounds and early oxidation
0.5 1.0 2.0 5.0 10.0 20.0 50.0
breakdown is as follows: products, such as peroxides,
PD-initiation voltage ( kV )
A PD partial discharge will be will help mobilize the copper.
ignited in the Cu2S contami- As a rule, not only do poorly
nated insulation during the Series A relates to uncoated (healthy) insulation while series D shows refined oils contain more mer-
transients. This discharge will the behavior of an insulation coated with Cu2S. captans than high-grade oils,
ultimately not extinguish. It they also contain considerably

62 ABB Review
3/2004
R&D digest
more of these other harmful manufacturing measures and
components. 3 The voltage transient during a-90 operation. on field diagnostics/mainte-
nance services.
Copper sulphide precipitation,
like the type found in some of Brief summary of
the disassembled transform- 350
UR-UN conclusions
ers, has been reproduced in Aggressive oil produces
u ( kV )

the laboratory from mercap- 250 copper sulphide.


tan-rich oil and also by di- 150
Copper sulphide weakens
rectly adding a copper mer- the insulation.
50
captide to oil. Repetitive transients further
58 58.2 58.4 58.6 58.8 59 59.2 59.4 59.6 59.8 60
degrade the insulation. In the
t (ms)
The mercaptan content of case of HVDC, transients aris-
new transformer oils may vary ing from a-90 operation or
widely, from 0,2 to 10 ppm. transients from continuous
The wave shape is similar to a standard lightning impulse surge.
The mercaptan content is sig- High Mvar operation are suffi-
nificantly reduced in trans- cient to initiate partial dis-
former oil that has been in charges.
use for several years since it is con- for transformer insulation diagnosis is A partial discharge PD in the de-
sumed by the reaction with metals. the Dielectric Frequency Response graded insulation will not extinguish.
measurements (DFR) method. This is a When the insulation is sufficiently de-
In addition to the oil, other potential development of the traditional power graded, partial discharge will con-
sources of mercaptan sulphur in a trans- factor method or tan d measurement tinue at normal service voltage levels.
former have been investigated. So called method. Instead of just measuring at A partial discharge leads to a turn-to-
‘leaching experiments’ showed that only power frequency, the capacitances and turn fault and transformer break-
insignificant amounts could be traced. losses are measured as a function of fre- down.
quency, typically from a few mHz to
This leads to the conclusion that only 1000 Hz. Compared to earlier research and find-
low refined virgin oil can be the origin ings on aggressive oils, we have now
of the ‘transformer killer’ – Cu2S. The DFR is sensitive to moisture in the been able to explain the chemical
cellulose and to oil conductivity, but process in greater detail. In addition, we
Diagnostic Methods can also be used to detect contamina- now know why certain service condi-
tion on the surface of cellulose insula- tions in combination with unsuitable
Mercaptan content tion. Even though DFR cannot directly oils degrade the insulation faster.
By a simple chemical analysis we can detect the copper sulphide contamina-
measure the mercaptan content of oil. tion inside the winding coils, it will The final conclusion is that the ‘quality
However, this is really only meaningful show if copper sulphide deposits have of oil makes the difference’.
for virgin oil as the mercaptans are con- contaminated the transformer in other
sumed with time. places. The presence of the contamina-
tion will show up in the DFR spectrum
Oil Fingerprinting with a characteristic profile.
It is not always known which type of oil Jan Hajek
a transformer contains. However, at our To best interpret the DFR results, Mats Dahlund
disposal is a range of fingerprinting knowledge about the design and the di- Lars Pettersson
techniques that makes it possible to dis- electric properties of the insulation ma- ABB Power Technologies AB
tinguish between different products. terials is important. ABB is the leading Power Transformers
Oils known to cause problems can be company in modeling and understand- Ludvika, Sweden
recognized, as well as those with a ing DFR measurements. jan.hajek@se.abb.com
clean track record.
Gunnar Bennstam
On top of this, ABB is continuously
ABB AB
DFR measurement working to better serve our customers
Ludvika, Sweden
An important electric test method used with effective failure-proof design/

ABB Review
3/2004 63

You might also like