Professional Documents
Culture Documents
D I S T R I B U T I O N S O LU T I O N S
UniGear 550
Medium-voltage air-insulated
switchgear up to 17.5 kV
UniGear 550
006 – 009 Description
016 – 019 Safety
—
UniGear 550
Description
• Each UniGear 550 panel consists of a single unit Characteristics of UniGear 550
which can be equipped with a vacuum circuit-
breaker as well as with all the accessories Range
available for conventional switchgear units • Up to 12-17.5 kV, …1 250 A, …31.5 kA
• Approved to be used for special applications • Standard IEC
such as marine, navy and type tested for IEC, • GOST and GB/DL Standards
GB/DL and GOST standards • Highly customized versions
• The panel incorporates a cubicle in its upper
level to house auxiliary instrumentation Safety
• Units can be coupled together directly with the • Fitted with safety interlocks
other products of the UniGear family • Internal arc classification IAC AFLR
• The switchgear does not require rear access for • Classified LSC-2B, PM
installation or maintenance, all the operations • CB racking with closed door
are carried out from the front
Flexibility
• Wide range of applications
• Vacuum circuit-breaker
• Ring core, block type instruments transformers
or sensors
• Wall and free-standing solution
Quality
• ABB quality
• Large installed base
• Installed in high number of countries
Design includes
• Protection and control
• Earthing switch
• Integrated capacitor banks
• Bay computer
ART I CL E OR CH AP T ER T I TL E 7
Applications Marine
• Drilling platforms
Utilities and Power Plants • Off-shore oil rigs
• Power generation stations • Cruise ships
• Substations • Container ships
• Main and auxiliary switchgear • Tankers
• Cable ships
Industry • Ferries
• Pulp and Paper
• Cement Transport
• Textiles • Airports
• Food • Ports
• Automotive • Railways
• Quarrying • Underground transport
• Petrochemical
• Oil and gas Infrastructure
• Metallurgy • Shopping malls
• Rolling mills • Hospitals
• Mines • Large infrastructure and civil works
8 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Description
UniGear 550 is medium voltage switchgear with a metal enclosure,
suitable for indoor installations. Metal partitions segregate the
compartments from each other and the live parts are air-insulated.
The innovative feature of this panel is its size. In The panel is designed to allow the insertion of
fact, it only measures 550 mm in width which fixed voltage transformers, positioned at the rear
makes it a very compact and versatile product of the panel itself and also to allow the use of a
that is ideal for applications where space is withdrawable VT truck.
restricted. The capacitive signal for indicating voltage
UniGear 550 is designed so that it can be presence is connected directly to the insulators
connected directly to the other versions of which support the busbars on the cable sides.
UniGear, such as ZS1, 500R and MCC. The surge arresters can also be inserted in the
UniGear 550 has the same overall dimensions cable area.
(height and depth) and the same main busbars The UniGear 550 switchgear is fitted with all the
arrangement as UniGear ZS1 with a maximum interlocks and accessories needed to guarantee a
current of 4 000 A. high level of safety for equipment and personnel,
For this panel, positioning against the wall is as well as reliable operation.
possible. In fact, the switchgear does not require
access from the rear for installation or Normal operation conditions
maintenance. All the service operations are The rated characteristics of the switchgear are
carried out from the front. guaranteed under the following ambient
UniGear 550 has undergone all the tests required conditions:
by the International Standards (IEC) and local
standards organizations (for example the Chinese • Minimum ambient temperature: – 5 °C
GB/DL and Russian GOST standards). • Maximum ambient temperature: + 40 °C
In addition, UniGear 550 has completed the series
of certifications required by the regulations of For different temperature ranges, please contact
the major shipping registers (LR, DNV, RINA, BV your ABB sales representative.
and GL) for use of the switchgear in Marine and
Navy installations. Ambient humidity:
The UniGear 550 reflects all the construction
characteristics of the UniGear ZS1. • maximum 24 h average of relative humidity
As a standard solution, it is possible to connect 95% RH
up to three single-core cables per phase • maximum 24 h average of water vapour
(maximum cross-section of 185 mm2), or two pressure 2.2 kPa
cables per phase (maximum cross-section • maximum monthly average of relative humidity
of 300 mm2). The connection height of the cables 90% RH
in relation to the floor is 600 mm. • maximum monthly average of water vapour
The circuit-breaker is the vacuum type Vmax/L in pressure 1.8 kPa
a withdrawable version.
UniGear 550 uses ring core current transformers The normal operational altitude is up to 1 000 m
as the standard solution, which are fixed onto “CT above sea level. For higher altitude applications,
Rods”. please contact your ABB sales representative.
As an optional solution, block type current Presence of normal, non-corrosive and
transformers are available. uncontaminated atmosphere.
9
Electrical characteristics
Rated voltage [kV] 12 12 17.5
Rated insulation voltage [kV] 12 12 17.5
Rated power frequency withstand voltage [kV / 1 min] 28 38 38
Rated lightning impulse withstand voltage [kV] 75 95 95
Rated frequency [Hz] 50 / 60 50 / 60 50 / 60
Rated short time withstand current [kA / 3 s] …31.5 …31.5 …31.5
Internal arc withstand current [kA / 1 s] …31.5 …31.5 …31.5
Main busbar rated current [A] ...4 000 ...4 000 ...4 000
Circuit-breaker rated current [A] ...1 250 ...1 250 ...1 250
GB/DL version is available with higher request in dielectric characteristics (42 kV) and short time withstand current (4 s)
10 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
IEC Classification
With the release of the IEC 62271-200 standard, new definitions and
classifications of Medium Voltage switchgear have been introduced.
UniGear 550 is classified as LSC-2B because the • Level of the fault current (16...31.5 kA)
busbar, circuit-breaker and cable compartments • Duration of the fault (0.1...1 s)
are physically and electrically segregated.This is • Escape routes for the hot and toxic gases
the category that defines the possibility of produced by combustion of materials
accessing the circuit-breaker compartment with • Dimensions of the room, with special attention
the busbars and cables energized. to the height
—
UniGear 550
Design features
Protection relay
with IEC 61850
Busbar
Low voltage
compartment
compartment
Apparatus
compartment
Current transformer
Cable
Voltage transformer
compartment
14 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Fully type-tested
UniGear 550 switchgear has undergone all the tests required by the
international (IEC) Standards and local Standards organizations (for
example, the Chinese GB/DL and Russian GOST standards).
In addition, the tests required by the main Description of IEC type tests
shipping registers (LR, DNV, RINA, BV and GL)
have been carried out for use of the switchgear in Short-time and peak withstand current
marine installations. The test shows that the main power and the
As indicated in these standards, the tests were earthing circuits resist the stresses caused by the
carried out on the switchgear units considered passage of the short-circuit current without any
most sensitive to the effects of the tests and damage.
therefore the results were extended across the It should also be noted that both the earthing
whole range. system of the withdrawable circuit-breaker and
Each switchgear unit is subjected to routine tests the earthing busbar of the switchgear are
in the factory before delivery. subjected to the test.
These tests are intended to provide a functional The mechanical and electrical properties of the
check of the switchgear based on the specific main busbar system and of the top and bottom
characteristics of each installation. branch connections remain unchanged even in
the case of a short-circuit.
IEC type tests
• Short-time and peak withstand current Temperature rise
• Temperature rise The temperature rise test is carried out at the
• Internal arc capability rated current value of the switchgear unit and
• Dielectric test shows that the temperature does not become
• Making and breaking capacity of circuit-breaker excessive in any part of the switchgear unit.
• Earthing switch making capacity During the test, both the switchgear and the
• Mechanical operations of circuit-breaker and circuit-breaker or contactor it may be fitted with
earthing switch are checked.
• IP protection degree
Internal arc capability
IEC routine factory tests Please refer to chapter Safety
• Visual inspection and check
• Mechanical sequence operations Dielectric test
• Cabling check These tests verify that the switchgear has
• Electrical sequence operations sufficient capability to withstand the lightning
• Power frequency withstand voltage impulse and the power frequency voltage.
• Measurement of the resistance of the main The power frequency withstand voltage test is
circuits carried out as a type test, but it is also a routine
• Secondary insulation test test on every switchgear unit manufactured.
Special type tests required by shipping registers Circuit-breaker making and breaking capacity
for marine application The circuit-breaker or contactor is subjected to
• High ambient temperatures (+ 45°C) the rated current and short-circuit current
• Inclination breaking tests.
• Vibration Furthermore, it is also subjected to the opening
and closing of capacitive and inductive loads,
capacitor banks and/or cable lines.
15
Earthing switch making capacity Type tests required by the shipping registers
The earthing switch of the UniGear 550
switchgear can be closed under short-circuit. High ambient temperature
Although, the earthing switch is normally The service conditions for the electrical
interlocked to avoid being operated on circuits apparatus in marine installations are generally
which are still live. more severe than those in normal land
However, should this happen for any one of applications.
several reasons, personnel safety would be fully Temperature is a main factor and for this reason
safeguarded. the shipping register regulations require the
switchgear to be able to operate at higher
Mechanical operations ambient temperatures (45 °C or higher) than
The mechanical endurance tests on all the those stated in the IEC Standards (40 °C).
operating parts ensures the reliability of the
apparatus. General experience in the electro- Inclination
technical sector shows that mechanical faults are The test is carried out by inclining the switchgear
one of the most common causes of a fault in an for a defined time up to 25° alternately on all four
installation. sides and operating the apparatus.
The circuit-breaker is tested by carrying out a The test proves that the switchgear is able to
high number of operations - higher than those resist these extreme service conditions and that
which are normally carried out by installations in all the apparatus it contains can be operated
the filed. without any problems and without being
Furthermore, the switchgear components are damaged.
part of a quality control program and samples are
regularly taken from the production lines and Vibration
subjected to mechanical life tests to verify that The reliability and sturdiness of the UniGear 550
the quality is identical to that of the components switchgear has been definitively proved by the
subjected to the type tests. result of the withstand test to mechanical
stresses due to vibration. The service
IP protection degree conditions on shipping installations and marine
The IP protection degree is the resistance offered platforms require the switchgear to work in
by the UniGear 550 against penetration of solid environments strongly affected by vibrations,
objects and liquids. such as those caused by the motors on large
This degree of resistance is indicated by the cruise ships or the drilling plants of oil rigs.
prefix IP followed by two charachters (i.e. IP4X).
The first number identifies the degree of • 1 mm amplitude in the frequency range between
protection against the entrance of solid objects, 2 and 13.2 Hz
the second one is related to liquids. • 0.7 g acceleration amplitude in the frequency
range between 13.2 and 100 Hz
16 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Safety
When developing modern medium voltage switchgear, personnel
safety must necessarily take priority.
This is why the UniGear 550 switchgear has been Unless suitably protected, these phenomena have
designed and tested to withstand an internal arc very serious consequences for the personnel,
due to a short-circuit current of the same current such as wounds (due to the shock wave, flying
level as the maximum short-time withstand level. parts and the doors opening) and burns (due to
The tests show that the metal housing of UniGear emission of hot gases).
550 switchgear is able to protect personnel near The internal arc test verifies that the
the switchgear in the case of a fault which evolves compartment doors remain closed and that no
as far as striking an internal arc. components are ejected from the switchgear
even when subjected to very high pressures, and
An internal arc is a highly unlikely fault, although that no flames or incandescent gases penetrate,
it can theoretically be caused by various factors, thereby ensuring safety of the personnel near the
such as: switchgear.
The test also ensure that no holes are produced in
• Insulation defects due to quality deterioration external accessible parts of the housing, and
of the components. The reasons can be adverse finally, that all the connections to the earthing
environmental conditions and a highly polluted circuit remain intact, hence guaranteeing the
atmosphere. safety of personnel who may access the
• Overvoltages of atmospheric origin or switchgear after the fault.
generated by the operation of a component The IEC 62271-200 Standard describes the
• Inadequate training of the personnel in charge methods to be used for carrying out the test and
of the installation the criteria which the switchgear must conform
• Breakage or tampering of the safety interlocks to.
• Overheating of the contact area, due to the The UniGear 550 switchgear fully conforms to all
presence of corrosive agents or when the the five criteria indicated by the IEC standards.
connections are not sufficiently tightened
• Entry of small animals into the switchgear (i.e. The IAC classification is proved by the test
through cable entrance) according to the following designations:
• Material left behind inside the switchgear
during maintenance activities • General: classification IAC (Internal Arc
Classified)
The characteristics of the UniGear 550 • Accessibility: A, B or C (switchgear accessible to
switchgear notably reduce the incidence of these authorized personnel only (A), to all (B), not
causes for faults, but some of them may not be accessible due to installation (C)
eliminated completely. • F, L, R: access from the front (F – Front), from
The energy produced by the internal arc causes the sides (L – Lateral) and from the rear (R –
the following phenomena: rear)
• Test values: test current in kiloamperes (kA),
• Increase in the internal pressure and duration in seconds (s)
• Increase in temperature
• Visual and acoustic effects The parameters of each specific plant mean that
• Mechanical stresses on the switchgear evacuation of the hot gases and incandescent
structure particles must be checked very carefully in order
• Melting, decomposition and evaporation of to ensure and maintain personnel safety.
materials
17
—
Arc duration and
kA2 s
damage caused
Melting
of Steel
Melting of
Copper
Melting of
Cables
—
UniGear 550
Safety
The UniGear 550 switchgear is fitted with all the interlocks and
accessories needed to guarantee the highest level of safety and
reliability for both installation and personnel.
Padlocks
The circuit-breaker [11] and cables [12]
compartment doors can be locked in the closed
position by means of padlocks. These can be
applied to both door closing versions –with
central handle (standard) or screws (optional).
The operations for apparatus racking-in/out [13]
and earthing switch opening/closing [14] can be
prevented by applying the padlocks to the
insertion slots of the relevant operating levers.
19
6 Apparatus racking-in lock Can only be removed with the truck in the racked-out position
7 Earthing switch closing lock Can only be removed with the earthing switch open
8 Earthing switch opening lock Can only be removed with the earthing closed
Insertion of the apparatus raking-in/out crank
9 Can always be removed
lever
10 Insertion of the earthing switch operating lever Can always be removed
Padlocks
Accessory devices
The device locks the shutters in the closed position when the
apparatus is removed from the compartment. The operator
20 Shutters fail-safe
cannot open the shutters manually. The shutters can only be
operated by the apparatus truck or the service trucks.
—
UniGear 550
Vacuum circuit-breaker
—
UniGear 550
Earthing switch
ST-UG Earthing switch The switching speed and torque achieved are
UniGear 550 panel is equipped with the ST-UG independent of the action of the operating
type earthing switch. This device is a patented mechanism.
switch with rectilinear movement. A manual operating lever is provided for
It is fitted with a snap action operating operation of the switch.
mechanism for positive high speed closing and it
is dimensioned to conduct the rated short circuit Earthing switch has been tested for two closing
making current when closed under load. operations at 100% of the rated short-circuit
making current.
The speed of the snap action closing operation is Device is provided with auxiliary switches for
independent of the controls. signalling the open and closed positions,
operated by the rod mechanism.
The switch is equipped with an earthing blade The following are available on request:
which connects the three phases via the earthing
pins mounted on the copper bars of the cable • Locking magnet
connecting system. • Key locks for open and closed positions
The earthing bar is electrically connected to earth • Padlock
by a stranded copper conductor.
The snap action closing mechanism of the
earthing switch functions independently of the
rotation of the drive shaft.
—
UniGear 550
Instrument transformers
— Ring core current transformer The current transformers are normally fitted on
01 Current
transformer TPU The ring core current transformer can be air or the load side of the apparatus compartment for
— resin insulated and is used to supply metering measurement of the phase currents of the
02 Voltage
transformer TJC and protection devices. switchgear unit. Fitting on the supply side of the
— The transformer can feature either a closed or apparatus compartment is also possible (busbar
03 Ring core current
transformers split core. The ring core transformer with split applications) for measuring the busbar currents
core is used for detecting earth fault currents and or for realising particular protection schemes.
can be easily mounted around the incoming The ABB range of current transformers is
cables. An air insulated ring core transformer is designated TPU.
used for measuring the phase current and it is
placed over the insulated CT rod. Bushing type current transformer
They conform to the IEC 61869-1, IEC 61869-2 As an another alternative, UniGear 550 can also
which have fully replaced previous standard IEC be furnished with bushing type current
60044-1. transformers, making this switchgear suitable for
The CT rods are designed to be equipped with a markets influenced by British Standards (BS).
maximum of two current transformers per phase
(metering and protection) and with the following Voltage transformers
dimensional requirements: The voltage transformers are of the epoxy resin
From 50 A to 200 A: insulated type and are used to supply
measurement and protection devices.
• Minimum internal diameter: 59 mm They are available for fixed assembly or for
• Maximum external diameter: 200 mm installation on removable and withdrawable
• Maximum height: 100 mm trucks.
They conform to the IEC 61869-1, IEC 61869-3
From 250 A to 1 250 A: which have fully replaced previous standard IEC
60044-2.
• Minimum internal diameter: 69 mm Their dimensions are in accordance with the DIN
• Maximum external diameter: 147 mm 42600 Standard.
• Maximum height: 75 mm These transformers can have one or two poles,
with performance and precision classes suited to
Block type current transformers the functional requirements of the instruments
The block type current transformers are epoxy connected to them.
resin insulated and used to supply the When they are installed on removable or
measurement devices and protection withdrawable trucks they are fitted with medium
instruments. These transformers have a wound voltage protection fuses.
core with one or more cores, with performance The withdrawable trucks also allow replacement
and accuracy classes suitable for the installation of the fuses with the switchgear in service. Truck
requirements. racking-out with the door closed automatically
They conform to the IEC 61869-1, IEC 61869-2 operates closure of a metallic segregation shutter
which have fully replaced previous standard IEC between the live parts of the switchgear and the
60044-1. instrument compartment.
Their dimensions are in accordance with the DIN Fixed voltage transformers can be installed
42600 Standard, in the Medium and Long Size directly on the main busbar system in a dedicated
versions up to 1 250 A. compartment (busbar applications).
The current transformers can also be provided The ABB range of voltage transformers is
with a capacitive socket for connection to voltage designated TJC, TDC,TJP.
signalling devices.
23
— —
01 02
—
03
24 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Current and voltage sensors
The sensor technology has been used in ABB since the beginning of
the 1990s and there are more than 120 000 sensors installed and
operating to date.
—
Performance
comparison between
conventional current Secondary 1 ABB sensor
transformer and output
current sensor
1 Us
Saturation level
2
2
Standard CT
is
— —
01 02
26 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Cable terminations
— —
01 02
—
UniGear 550
Distribution automation
ABB’s power protection philosophy system and the damage and danger caused by a
Having delivered protection relays to more than network fault. Substation automation provides
100 countries, ABB fully understands the need for remote control and monitoring capabilities,
diverse protection philosophies that meet local which speed up the location of faults and the
legislation, safety requirements and engineering restoration of the power supply. Fast operation of
practice. Therefore, ABB has developed a power the protection relays also minimizes post-fault
protection philosophy that not only serves the load peaks. Together with voltage dips, post-fault
specific needs and requirements of diverse power load peaks increase the risk of the disturbance
systems, but also creates confidence and peace spreading to healthy parts of the network. The
of mind for both the power system owners and sensitivity of the protection must be adequate to
users. detect relatively high resistance earth faults and
short-circuits in the most distant parts of the
The main purpose of a protection relay system is network. Reliable selectivity is essential to limit
to recognize any abnormal power system the loss of power supply to as small a part of the
condition(s), or abnormally operating system network as possible, and to allow the faulted part
component(s). Based on the information of the network to be reliably located. Corrective
gathered, the protection system will initiate actions can then be directed to the faulty part of
corrective actions that return the system to its the network, so that the power supply can be
normal operating state. This provides a safe restored as quickly as possible.
environment for all.
The protection system must have a high degree
Protection relays are activated when something of reliability. This also means that if, for example,
abnormal has happened in the power system; the circuit breaker (CB) fails to operate, the
they do not prevent network faults from arising. back-up protection will clear the fault. Substation
Selecting the right protection functions and automation (SA) puts the operator in complete
methods improves the performance and the control of the substation. In addition, SA
reliability of the protection system, thus improves the power quality of the transmission
minimizing the effects of network faults and and distribution network under normal operation,
preventing the disturbance from spreading to the but especially in a disturbance situation and
healthy parts of the network. during substation maintenance activities. An SA
or SCADA brings the full benefits of digital
Advantages of a complete protection system technology into protection and control of the
Close attention must be paid to operating speed, networks. The protection relays are easily set-up
sensitivity, selectivity and reliability of the and parameterized through easy and safe access
protection system. There is a strong correlation from the operator’s workplace.
between the operating speed of the protection
30 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
—
01
32 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
Relion 640
The base functionality in REX640 can be
enhanced with additional application packages
for feeder protection, such as fault locator, line
differential protection and line distance
protection.
Please see dedicated chapter on page 64.
—
— 03
01
—
04
—
02
34 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
— For more information, please refer to the • Transformer Protection and Control RET620
01 Transformer protection
and control RET615, following documentation: Product Guide
Transformer protection • Transformer Protection and Control RET615 • Transformer Protection and Control RET630
and control RET620 and
Transformer protection Product Guide Product Guide
and control RET630 • Voltage Protection and Control REU615 Product • Multiapplication Protection and Control REX640
—
02 Multiapplication Guide Product Guide
Protection and
Control REX640
—
01
—
02
36 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
— For more information, please refer to the • Motor Protection and Control REM620 Product
01 Basic range:
Motor protection and following documentation: Guide
control REM601 • Motor Protection and Control REM611 Product • Motor Protection and Control REM630 Product
—
02 Medium range: Guide Guide
Motor protection • Motor Protection and Control REM615 Product • Multiapplication Protection and Control REX640
and control REM611,
Motor protection and Guide Product Guide
control REM615
—
03 High range:
Motor protection
and control REM620,
Motor protection and
control REM630
—
04 Multiapplication
Protection and
Control REX640
— —
01 02
—
03
—
04
38 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
—
01
—
02
40 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
—
01
—
02
—
03
42 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
Product offering
The recommended products for capacitor bank
protection are part of ABB’s Relion® product
family. The Relion product family offers the
widest range of products for the protection,
control, measurement and supervision of power
systems for IEC and ANSI applications.
43
— —
01 02
—
01
44 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
Protection and control REX640 The available packages support the following
REX640 makes protecting all your assets in applications:
advanced power generation and distribution • Feeder protection
applications easy. The fully modular design allows - Line differential protection
unequaled customization and modification - Line distance protection
flexibility, and easy adaptation to changing - Interconnection protection
protection requirements throughout the relay life - Fault locator
cycle. This is asset management at its best. • Power transformer protection
- Two and three-winding differential protection
Complete application coverage with one device - On-load tap-changer control
for optimal cost-effectiveness • Machine protection
REX640 is the outcome of a long-standing - Asynchronous machines
evolution, building on ABB’s strong heritage of - Synchronous machines
freely configurable multifunctional relays. The • Shunt capacitor protection
ability to cover the full range of utility and • Busbar protection
industrial applications and manage multiple • Automatic synchronization
applications simultaneously, with the same - Generator circuit breaker
device, guarantees flexible, versatile and cost- - Non-generator circuit breaker
efficient protection solutions. • Petersen coil control
REX640 has been designed to support the • Arc protection with supervised sensors
increasing digitalization of substations. REX640 - Loop and lens-type sensors
thereby supports a variety of digital switchgear
solutions and is suitable for both single and Fully modular hardware and software for
double‑busbar applications. REX640 offers as maximum flexibility for the entire relay lifetime
many as 20 current and voltage measurement The modularity and scalability of both software
channels in total, supporting both conventional and hardware allow you to create your own,
instrument transformers and sensors, not to unique relay for your specific protection
mention the ability to receive four streams of requirements. The ready-made application
sampled measured values (SMV) via IEC 61850- packages make ordering your relay smooth and
9-2 LE-based process bus communication. easy.
As the newest member of ABB’s Relion® When requirements change, so will REX640.
protection and control family of relays, REX640 Adapting to changing protection requirements is
further reinforces Relion’s position as the range flexible and easy – the software and hardware can
of relays to rely on. be modified anytime. In addition, new software
and hardware developments will be continuously
New application package concept for maximum and easily accessible – throughout the relay’s
convenience and flexibility entire life cycle.
REX640 introduces an entirely new application
package concept, by offering a variety of ready-
made application packages to choose from.
The application packages include various
protection and control functions, which can be
flexibly combined to create protection solutions
that meet your unique protection requirements.
45
— Intuitive human-machine interface for enhanced REX640 – innovative, flexible and easy to use
01 Protection and
control REX640 user experience • Complete application coverage with one device
— A novel, application-driven approach to the local for optimal flexibility and cost-effectiveness
02 Phasor diagram of
a three winding power human-machine interface (LHMI) allows support • Ready-made application packages for
transformer on the LHMI for entirely new applications. The unique, 7-inch convenient and smooth ordering
—
03 New application color touch screen visualizes power distribution • Customization freedom with modular and
package concept process information in an entirely new way. This scalable design
results in increased situational awareness and • Fully modular hardware and software for
maximum usability. maximum flexibility throughout the entire relay
Ready-made application-based pages minimize life cycle
the need for graphical engineering, which saves • Easy adaption to changing protection
both time and efforts. The LHMI pages can also requirements
be customized, if necessary, for optimum • Continuous access to the latest software and
freedom. hardware developments
• Ready-made application-based LHMI pages –
saving both time and efforts
• Increased situational awareness and optimal
usability with application-driven LHMI
• Designed to support the increasing
digitalization of substations
— —
01 02
—
03
46 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
—
02
48 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
— Centralized protection and control Depending on the chosen product options, the
Smart Substation Control
and Protection SSC600 Advances in communication systems, including device is adapted for:
— time synchronization, their integration to • Protection for overhead line and cable feeder in
Substation Merging
Unit SMU615 substation applications and the standardization isolated neutral, resistance earthed,
— of protocols have facilitated the operation and compensated and solidly earthed networks.
01 Example of centralized
protection and control the diagnosis of failures in complex grids and • Protection, control, measurement and
have enabled new possibilities for protection and supervision of asynchronous motors in
control schemes. These advances have opened manufacturing and process industry.
space for the implementation of the centralized • Transformer protection and control for power
protection and control system. transformers, unit and step-up transformers
including power generator-transformer blocks
The centralized protection and control concept is in utility and industry power distribution
based on the concentration of substation systems.
protection and control in a single device and the
utilization of communication networks to Substation Merging Unit SMU615
converse between different components, bays, SMU615 is a dedicated substation merging unit
substations and the related operators. The most intended for measuring current and voltage
substantial protection philosophy change in the signals from the instrument transformers and
system is the total or partial shift of functions merging them into the standard digital output
from the bay level, i.e., from the relays, to the format that other devices can further use for
station level in the substation. various power system protection application
purposes. SMU615 itself includes no protection
Product offering functionality but it offers the physical interface
into the switchgear primary equipment, that is,
ABB Ability™ Smart Substation Control and circuit breaker, disconnector and earthing switch.
Protection for electrical systems SSC600 is a SMU615 is a member of ABB’s Relion® product
smart substation device designed for protection, family and is characterized by the compactness,
control, measurement and supervision of utility simplicity and withdrawable-unit design.
substations and industrial switchgear and
equipment. The design of the device has been For more information, please refer to the
guided by the IEC 61850 standard for following documentation:
communication and interoperability of substation • Smart Substation Control and Protection
automation devices. It is fully integrable with SSC600 Product Guide
Relion series IEDs for creating a complete • Substation Merging Unit SMU615 Product Guide
solution. Optional functionality is available at the
time of order for both software and hardware, for
example, special application packages and
additional communication modules.
49
—
01
—
02
—
03
GOOSE GOOSE
SMU615
50 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
—
01 Substation Substation automation connectivity can be established with gateway
Management Unit
ABB’s protection and control relays are an integral functionality between the substation devices and
COM600S
part of substation automation systems. The external higher-level systems such as the Network
substation automation system, together with the Control Center (NCC) or a process such as the
protection relays, lay the foundation for all the Distributed Control System (DCS) using
higher-level remote functions, such as advanced IEC 60870-5, DNP3, Modbus or OPC-based
power system management and the monitoring protocols.
of the condition of the equipment, when it is in
service. Substation-level systems are easy to use The COM600 series hardware platform is based
and to adapt to customer-specific requirements. on ruggedized mechanics with no moving parts
subject to wear and tear. The compact and robust
Increased competition is driving many power design is well adapted to harsh environments.
providers to focus on system productivity, with
the aim to reduce costs and increase customer The COM600 series comprises of two products:
satisfaction. To reach this goal, an upgrade of an • COM600S for Substation Automation (for IEC
aging infrastructure is usually involved. Updating and ANSI markets)
to substation automation offers the opportunity • COM600F for Feeder Automation (for ANSI
to reduce operational and maintenance costs, markets only)
increase plant productivity with the help of
enhanced schemes, as well as condition The COM600S has the capability to function as a
monitoring for the apparatus (e.g., circuit combined substation HMI, gateway and process
breakers, power transformers). controller in a small to medium-sized substation
automation installation. Its HMI feature enables
Product offering substation monitoring and operations. It
The COM600 series offers versatile substation integrates various units to provide access to real-
management units. These units are deployed time data. It also records process data in its
together with protection and control relays and historian to enable access to past data. Its logic
other communication devices to realize smart processor enables implementation of substation-
substation and grid automation solutions in level automation tasks. The gateway functionality
utility and industrial distribution networks. The provides a provision to communicate data from
COM600 series units perform the combined role protection and control relays in the substation
of a user interface, a communication gateway and and COM600S itself to higher-level systems and
an automation platform in a single physical unit. vice versa.
The COM600 series accommodates web For more information, please refer to the
technology-based functionality, which provides following documentation:
access to substation devices and processes via a • COM600S Substation Management Unit
web browser-based human machine interface Product Guide
(HMI). All standard substation monitoring and
control aspects can be handled using the web-
HMI.
—
02 Remote I/O Remote I/O concept Product offering
unit RIO600
ABB’s remote I/O concept introduces a new way The remote I/O unit RIO600 is designed to ex-
of extending the I/O capabilities of protection re- pand the digital and analog I/O of ABB’s Relion®
lays. The concept is aimed at increasing the hard- series protection relays and to provide I/O for the
ware functionality of the protection relays, while COM600 series devices using IEC 61850 commu-
still maintaining the relay’s compact design. This nication.
way remote I/O can be used, when it is needed.
The information between the remote I/O units RIO600 is designed using a modular architecture
and the main protection relay is exchanged over where the amount and type of I/O ports can be
the latest communication standard IEC 61850. added through modules. The RIO600 modules
This enables easy integration into the systems can be stacked on a standard DIN rail to achieve
and is in line with the latest standards. the required configuration.
The remote I/O concept also benefits from in- RIO600 is built on an industrial hardware plat-
stalling the I/O units as close as possible to the form, which provides the same reliability, perfor-
place where the signals need to be digitalized, mance and real-time functionality as ABB’s pro-
thus limiting extensive wiring within the switch- tection relays, withstanding extreme
gear, substation or plant. Digitalization of the sig- temperatures, electromagnetic interference and
nals allows users to use information wherever stringent industry standards.
needed, without the need of installing additional
auxiliary relays or terminals. IEC 61850 enables RIO600 provides an additional I/O within the
signals supervision, thus faster recognition of switchgear itself by using the Ethernet-based
any errors and proactive operation, if these con- IEC 61850 horizontal GOOSE communication. The
ditions happen during a critical process. signals can be transmitted within the switchgear
and to the automation systems. Similarly, signals
from the automation systems can be executed
through RIO600 connected to numerical protec-
tion relays.
—
02
52 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
Distribution automation
Selection table
In the table:
x = function supported
o = function available as option
1
= color touch screen 605
605
605
605
615
615
615
615
615
611
611
611
611
REG615 IEC
REM615 IEC
REM611 IEC
RED615 IEC
REU611 IEC
REB611 IEC
RET615 IEC
REF615 IEC
REF611 IEC
REM601
REF601
REJ603
REJ601
Standard
ANSI X X X
IEC X X X X X X X X X X X X X
Application
Arc fault protection application O O O O
Busbar application X
Back-up application X X O X X
Capacitor bank application
Feeder application X X X X X X X
Generator application X
Motor application X O X X
Power management/load-shedding application
Transformer application O X X
Functionality
Autorecloser X X X X X X
Circuit breaker controllability X X X X X X X X X X X
Condition monitoring X X X X X X X X X X
Current-based protection X X X X X X X X X X X X
Distance protection
Fault locator X X
Generator differential protection X X
LCD display with Single Line Diagram (SLD) X X X X X
Line differential protection (in-zone transformer X
support)
Load-shedding
Motor differential protection X
On-load tap changer control
Power quality X X X
Self-powered protection relay X
Synchro-check X X
Generator/non-generator CB synchronizing
Transformer differential protection X X
Voltage based protection X X X X X X
Withdrawable release mechanism X X X X X X X X X
X
X
X
X
X
X
X
X
X
X
X
X
O
REU615 IEC 615
X
X
X
X
X
X
X
X
O
O
REV615 IEC 615
X
X
X
X
X
X
X
X
X
X
X
O
REF615 ANSI 615
X
X
X
X
X
X
X
X
X
X
X
X
O
REF615R ANSI 615
X
X
X
X
X
X
X
X
O
REM615 ANSI 615
X
X
X
X
X
X
X
X
X
O
RET615 ANSI 615
X
X
X
X
X
X
X
X
X
X
X
O
REF620 IEC 620
X
X
X
X
X
X
X
X
X
X
O
REM620 IEC 620
X
X
X
X
X
X
X
X
X
X
X
O
RET620 IEC 620
X
X
X
X
X
X
X
X
X
X
O
REF620 ANSI 620
X
X
X
X
X
X
X
X
X
O
REM620 ANSI 620
X
X
X
X
X
X
X
X
X
X
O
RET620 ANSI 620
X
X
X
X
X
X
X
X
X
X
X
X
X
REF630 IEC 630
X
X
X
X
X
X
X
X
REM630 IEC 630
X
X
X
X
X
X
X
X
X
X
RET630 IEC 630
X
X
X
X
X
X
X
X
X
X
X
REG630 IEC 630
X
X
X
X
X
X
X
X
X
X
X
X
X
X
O
O
O
O
O
O
O
O
O
O
O
O
O
O1
REX640 640
X
X
X
X
X
X
X
X
O
O
O
O
O
O
O
O
O
O
O
SSC600 SSC
X
X
X
O
53
SMU615 615
54 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
Distribution automation
Selection table
In the table:
x = function supported
o = function available as option
1
= color touch screen 605
605
605
605
615
615
615
615
615
611
611
611
611
REG615 IEC
REM615 IEC
REM611 IEC
RED615 IEC
REU611 IEC
REB611 IEC
RET615 IEC
REF615 IEC
REF611 IEC
REM601
REF601
REJ603
REJ601
Hardware
Analog inputs (CTs/VTs) 4/0 4/0 4/0 4/0 4/0 4/1 4/0 0/5 4/5 4/5 7/5 4/5 7/5
Analog inputs (sensor channels/CTs) 3/1 3/1 3/1 6/1 6/1 6/1
Binary inputs/outputs 4/6 4/6 0/2 4/6 4/6 10/9 4/6 4/6 18/13 18/13 16/10 16/12 14/12
RTD/mA inputs 2/1 2/1 2/1 6/2 6/2
mA outputs
Communication protocols
DNP 3.0 X X X X X
IEC 60870-5-103 X X X X X X X X
IEC 61850 X X X X X X X X X
Modbus X X X X X X X X X X X X
Profibus X X X X X
Communication media
Ethernet (RJ-45) X X X X X X X X X
Ethernet (LC) X X X X X X X X X
Ethernet redundant solutions (HSR/PRP/RSTP) X X X X X X X X X
Serial (RS 232/485, ST conn.) X X X X X X X X X X X X
55
SSC
640
620
620
620
620
620
620
630
630
630
630
615
615
615
615
615
615
615
REF615R ANSI
REM620 ANSI
REM615 ANSI
RET620 ANSI
REF620 ANSI
RET615 ANSI
REF615 ANSI
REM620 IEC
REM630 IEC
REG630 IEC
REU615 IEC
RET620 IEC
RET630 IEC
REV615 IEC
REF620 IEC
REF630 IEC
SMU615
REX640
SSC600
4/5 7/5 7/6 4/5 7/4 7/6 4/5 7/5 8/9 7/8 7/4 10/4 4/5 8/4 8/3 8/4 12/10 4/3
6/1 6/2 6/1
14/12 14/12 18/13 11/7 18/13 14/13 32/18 20/14 16/17 32/18 14/13 16/17 50/45 50/45 50/45 50/45 56/42 8/9
6/2 6/2 6/2 2/1 6/2 12/4 8/3 14/5 2/1 8 8 8 8 20/4
4 4 4 4 4
X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X
X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X O O
X X X X X X X X X X X X X X O
X X X X X X X X X X X X X X X X X
56 U N I G E A R 5 5 0 M E D I U M - V O LTA G E A I R - I N S U L AT E D S W I TC H G E A R U P TO 17. 5 K V
—
UniGear 550
Distribution automation
—
01 Load-shedding substations. Reactive load-shedding reacts • Underfrequency load-shedding as a backup to
controller PML630
based on measuring the system frequency and/or fast and slow load-shedding (reactive load-
voltage. The system as such can contain several shedding)
triggering levels for these values. Each triggering
level corresponds to one of the load-shedding A network power deficit occurs when a power
priority classes or steps, for example, activation source such as a generator or a grid transformer
of the first triggering level, which sheds the loads trips. There could also be a power shortage, when
belonging to priority class 1. Typically two or a network becomes isolated due to trip of a bus
three priority classes or steps are used. coupler or a bus tie breaker. All load-shedding
Restoration of the shed feeders can take place functions can be active concurrently.
manually or automatically, in a pre-programmed
scenario. Selectivity against protection functions For more information, please refer to the
has to be secured, for example, the load-shedding following:
system has to have a change to operate before • Load-shedding controller PML630 Product
the protection system is initiated. Guide
• Distribution automation solutions web page
Active load-shedding is mostly used in industrial (http://new.abb.com/medium-voltage/
distribution networks. Active load-shedding distribution-automation/distribution-
reacts based on measuring power, current values automation-solutions)
on supply and load feeders (key feeders
included). The load-shedding system knows the Solution offering
present loading situation and calculates shedding The Compact Power Management System (cPMS)
priorities for different network scenarios, such as is a load-shedding power management solution
tripping or overloading of a generator or a built on Relion PML630, Substation Management
network power source. Knowing the individual Unit COM600S, Remote I/O unit RIO600 and the
loads of feeders, only the necessary amount of Relion 615, 620 or 630 series feeder relays.
load (feeders) will be shed. The reactive load-
shedding system can work as a back-up for active Relion Interactive Selection Guide
load-shedding. The Relion Interactive Selection Guide (ISG) helps
you select the protection relay type that is the
Product offering most suitable for your application. It also
ABB’s Relion® protection relays are characterized provides links to relevant documentation online.
by functional scalability and flexible The Relion ISG is available at
configurability to perform reactive and active http://abb.relionisg.com
load-shedding.
—
UniGear 550
Distribution automation
—
01 CSingle line diagram Automatic transfer systems Synchronized automatic transfer system
(SLD) of medium-
voltage switchgear
Automatic transfer systems (ATS) are used to Protection relays from Relion® product family can
architecture applied, ensure maximum service continuity, supplying be used in medium-voltage switchgear to
suitable for carrying
out automatic and
the power users uninterruptedly. manage automatic and manual transfer between
manual transfer (ATS). All this is possible using various systems based different incoming feeders. The time needed for
on different kinds of techniques. The most automatic transfer carried out by means of the
common of these are outlined below, with the Relion family protection relays is between 200 to
relevant average transfer times: 300 ms (including the circuit breaker operating
times). The time can vary within the range
Delayed: 1500 ms indicated in relation to the complexity of the
Depending on the residual voltage: 400-1200 ms software transfer logics.
Synchronized ATS: 200-500 ms Switchgear equipped with Relion protection
High speed transfer device: 100 ms relays, suitably configured, are complete and
High speed transfer system: 30 ms efficient systems able to manage transfer
between one power supply system and an
The first two systems are the simplest and can alternative one, or to reconfigure the network,
also be achieved with conventional logics and passing from double radial distribution to a
instruments. They guarantee average transfer simple system, in a fully automatic way.
times and can therefore be used in installations It is also possible to carry out the same operation
where voltage gaps are not particularly critical. manually from a remote control station, or from
The other three systems: (1) synchronized the front of the switchgear under user super
automatic transfer system, (2) high speed vision. Manual transfer means making the
transfer device and (3) high speed transfer passage parallel, by means of the synchronism
system require microprocessor-based apparatus control function (synchro-check) implemented
with high technology content. They guarantee from the protection relay, the power supply lines
fast transfer times. They are used in plants where are closed simultaneously with synchronization of
the process is particularly critical, in which slow the voltage vectors to then return to being
transfers would cause serious malfunction or disconnected when the transfer has taken place.
interruption of the process itself. The applications described do not require
ABB offers all types of transfer systems, from the additional instruments.
simplest to the most complex.
—
01
59
—
02 An example SUE 3000 - High speed transfer device / High Corresponding to its multifaceted areas of
of a switchgear
configuration
speed transfer system application, the SUE 3000 is set up for different
— Voltage decrease or complete supply switchgear arrangements.
03 SUE 3000 High
Speed Transfer Device
interruptions represent the most crucial and
critical problems for the quality of energy supply Permanent network comparisons
today. The SUE 3000 High Speed Transfer Device An exceptionally important characteristic, that
guarantees an optimal safeguarding of energy clearly distinguishes SUE 3000 from competing
supply. The device ensures, in combination with concepts, is that synchronicity criteria are
the existing circuit breakers, the continued power continuously available, as they are computed
supply and protects the subsidiary process from online. This is the reason that, in case of an
expensive stoppage time. Further, the operation initiation, the appropriate transfer mode is
of the installation is considerably simplified already determined and can be immediately
through the possibility of manually-initiated initiated. This means that the probability of a fast
transfers for targeted clearings. transfer is considerably enhanced. Systems which
wait for the instant of initiation to start the
To achieve the fastest possible transfer time of determination of the network status are not
30 ms the High Speed Transfer System has to be capable to perform a fast transfer with minimum
used. This system is a combination of the interruption time.
SUE 3000 device, special trigger devices and very
fast magnetic circuit breakers. Transfer modes and times
Feeder 1 Feeder 2 Four different transfer modes are available in
Protection Protection detail: (1) fast transfer, (2) transfer at the 1st
Relay Relay
Feeder 1 Feeder 2
phase coincidence, (3) residual voltage transfer
and (4) time-operated transfer. When a fault
occurs, fast transfer is the optimal transfer mode
for ensuring that only a minimum interruption of
Trip Trip the voltage supply occurs. With fast transfer
mode, the total transfer time, counting from a
fault in the main feeder until the standby feeder is
SUE 3000
cut in, is less than 100 ms.
—
UniGear 550
UniGear 550 Digital
With UniGear Digital you gain unprecedented flexibility for any
application.
The digital solution takes full advantage of well- Lower environmental impact
proven components: current and voltage sensors, • Lowers energy consumption up to 250 MWh**
protection and control relays with IEC 61850 which represents saving of 23 700 EUR
digital communication to ensure a reliable and • Saves up 150 tons of CO2**, that is equal to
efficient electrical network. emissions produced by mid-size European car
driven for 1 250 000 km
UniGear Digital benefits
Protection relay
with IEC 61850
Busbar
Low voltage compartment
compartment
Apparatus
compartment
Current sensor
Voltage sensor
Cable
compartment
—
Single-line diagram
of typical units
Withdrawable
Withdrawable
—
UniGear 550
Single-line diagrams
Withdrawable
IF - Incoming/outgoing feeder BT - Bus-tie R - Riser RM - Riser with measurements
Withdrawable
Key to components
Standard components Accessories Alternative solutions
63
Graphical symbols
Circuit-breaker Socket and plug Voltage transformers Current transformers Fuse Earth
—
UniGear 550
Technical data
(1) The height of the unit is a function of the height of the low voltage compartment, available in the 665 and 1 060 mm versions.
(2) Others solutions are available, please contact ABB representative.
—
ABB Ltd.
Distribution Solutions
Electrification business
P.O. Box 8131
CH-8050 Zurich
Switzerland
abb.com/mediumvoltage
abb.com/contactcenters