Professional Documents
Culture Documents
i – Ⅱ PROJECT
for
PT. Nippon Shokubai Indonesia
PREP’
REV DESCRIPTION DATE CHKD APVD AUTHD
D
Notes:
(i)
TOKYO L JAPAN i – ⅡPROJECT Page 2 of 8
TOYO ENGINEERING CORP. TOYO WORK NO. BA 095300
L-101 ENGINEERING SPECIFICATION FOR THERMAL INSULATION Rev.0
1. GENERAL
1.1 Intent
This specification covers the specific requirements for design and materials of thermal insulation constructed by
Toyo Engineering Corp. (here in after referred to as TEC).
1.2 Scope
This specification shall be applied to the thermal insulation for equipment and piping shown on the P & I flow
diagram and utility flow diagram, but not to the thermal insulation to be supplied by the manufacturer complete
with equipment.
1.4 Units
Unless otherwise specified, SI units shall be applied as the measurement system for the drawings and documents
to be submitted. Nominal sizes of piping components shall be in accordance with inch system (NPS).
1.5 Restrictions
1.5.1 Where materials are referred to by trade names within this specification, the use of such names is intended to
describe the kind or quality of the material required and any deviation must be submitted in writing for TEC’s
approval.
1.5.2 Galvanized or zinc coated materials shall not be in contact with metal surfaces that have temperature above
370 °C. It shall not be used when, in case of fire, it could drip on stainless steel.
1.5.3 The minimum allowable value of sodium plus silicate and maximum value of chrolide content shall be in
accordance with ASTM C795 for acceptability of insulation material.
1.5.7 No insulation material shall be applied between pipe and tracer except for spacers (by others) to prevent local
overheating of the pipe.
1.5.8 Contact between dissimilar materials which might cause galvanic corrosion shall be avoided.
2. EXTENT OF INSULATION
2.1 General
2.1.1 Classification of thermal insulation and symbols to be indicated on the Engineering Drawing, P & I flow
diagram and Piping Line Schedule are as follows:
・・・
・・・
2.1.2 Thermal conductivity of thermal insulation materials shall be in accordance with applicable standard as
specified in the table of respective insulation material applications.
Hot insulation shall generally be applied to equipment and piping operating at 80 °C and above, except for the
case where heat loss is desired. Where heat loss is to be restricted, however, full heat conservation insulation
(HO) shall be applied, even when the operating temperature is below 80 °C.
2.3.1 Personnel Protection insulation (P) shall be applied to uninsulated equipment and piping operating at 65 °C
and above, within the area shown below, where operators, while working, might inadvertently come in to
contact with them.
2.3.2 Shield or guard may be provided in lieu of insulation for personnel protection, where a heat dissipation is
desirable.
2.5.1 Cold insulation (C) which material is polyurethane foam shall be applied to equipment and piping operating at
temperature below 0 °C, and calsium silicate (water proof type) shall be applied at temperature 0 °C and over
(anti-sweat), where reduction of heat gain and prevention of surface condensation is desired.
2.5.2 For such attachments and protrusions as shown below, fixed without inter-lying insulation to piping or
equipment (or to lugs) to be cold insulated, the cold insulation shall extend over the attachments or protrusions
by four (4) times the insulation thickness and there shall be minimum of 300 mm of bare metal after
termination of insulation.
2.7 Limitations
The following piping components & equipment shall not be insulated unless otherwise specified.
(1) Visible parts such as Name plate, code inspection plates, stampings, sight glass and level gauge.
(2) Shield or guard
(3) The following parts of the rotating machinery, which need a heat dissipation and cooling, unless
otherwise specified.
(1) Visible parts such as Name plate, code inspection plates, stampings, sight glass and level gauge.
(2) Shield or guard
(3) Safety valves along with its outlet piping and down stream piping of such valves as steam blow off valve,
vent and drain valve.
(4) Support-legs and inside of skirts
(1) Visible parts such as Name plate, code inspection plates, stampings, sight glass and level gauge.
TOKYO L JAPAN i – ⅡPROJECT Page 5 of 8
TOYO ENGINEERING CORP. TOYO WORK NO. BA 095300
L-101 ENGINEERING SPECIFICATION FOR THERMAL INSULATION Rev.0
3. MATERIAL
3.1 General
Material shall generally be in accordance with specified standard or applicable standard in consideration of the
following.
Specification and standard application of insulation material for hot and personnel protection services shall be as
follows :
Reference Thickness
Material Application
Code or Brand Name (mm)
Galvanized steel For towers, vessels, heat exchangers,
Sheet flanges, valves and piping with outside
0.3
ASTM A653 diameter of less than 760 mm
For towers, vessels, heat exchangers,
0.4 flanges, valves and piping with outside
diameter of 760 mm and larger
Stailess steel sheet S.S. 304 0.5 For lightening protection
Anti-vibration sheet Tombo #1616 Vendor For vibrating equipment
or equivalent Standard
3.7.1 Specification and standard application of fastening for insulation materials shall be as follows :
Dimension
Material Application
(mm)
(a) Stainless steel S.W.G. #20 For piping NPS 12 and smaller
wires Type 304 S.W.G. #18 For piping NPS 14 to NPS 18
(b) Stainless steel For piping NPS 20 and over, and
wires Type 304 0.4 x 13 cylindrical equipment with outside
diameter of 450 mm up to 900 mm
0.5 x 19 For cylindrical equipment with outside
diameter above 900 mm
(c) Fiberglass 5 For piping NPS 12 and smaller For cold insulation
Reinforced material
Pressure
Sensitive Tape
(d) Stainless steel 0.4 x 13 For piping NPS 12 and over, For fastening of the
bands Type 304 and cylindrical equipment with outside first layer when cold
diameter of 300 mm up to 900 mm insulation material
heaps up in two or
0.5 x 19 For cylindrical equipment with outside more layers.
diameter above 900 mm
TOKYO L JAPAN i – ⅡPROJECT Page 7 of 8
TOYO ENGINEERING CORP. TOYO WORK NO. BA 095300
L-101 ENGINEERING SPECIFICATION FOR THERMAL INSULATION Rev.0
3.7.2 Specification and standard application of fastening for jacketing materials shall be as follows :
Dimension
Material Application
(mm)
Galvanized 0.4 x 13 For piping NPS 30 and over, and cylindrical
steel bands equipment with outside diameter up to 900 mm
0.5 x 19 For cylindrical equipment with outside diameter
above 900 mm
Tapping Screw φ4mm X L13mm For all piping, equipment, etc
Type 304
Blind Rivet For cold isulation for top of vessel, etc.
Type 304
3.8.1 Specification and standard application of auxiliary materials for hot and personnel protection insulation shall
be as follows :
3.8.2 Specification and application of auxiliary materials for cold insulation should be as follows :
4. THICKNESS OF INSULATION
The thickness of Hot insulation, Personnel Protection and Cold insulation shall be as given in Attachment Table 1
to 5 respectively, and shall be 25 mm as a minimum excluding the thickness of jacketing materials, weatherproof
mastic, etc. Thicker thickness of insulation shall be applied from the product range when the standard thickness of
product for insulation materials does not conform to the thickness specified in the Table.
(1) The calculation of insulation thickness shall be based on normal operating inside fluid temperature.
TOKYO L JAPAN i – ⅡPROJECT Page 8 of 8
TOYO ENGINEERING CORP. TOYO WORK NO. BA 095300
L-101 ENGINEERING SPECIFICATION FOR THERMAL INSULATION Rev.0
(2) The thickness of insulation on the nozzles and other protrusions (including parts of structure) around
equipment and piping shall generally be equal to the thickness of adjoining pipe insulation.
(3) For towers, vessels, heat exchangers and rotating machinery, the insulation thickness specified as “PLANE”
in the Table shall be applied except that the thickness of pipe insulation shall be applied for the equipment
with outside diameter up to 600 mm (NPS 24) which can be regarded as pipes instead of “PLANE”.
(4) For towers in which inside operating temperature varies with height, the thickness of Hot insulation may
vary depending on the temperature.
(5) For instrument piping of which outside diameter is 15 mm (NPS1/2), the insulation thickness shall be 25
mm, and shall be equal to the thickness of adjoining pipe insulation for instrument piping in larger size.
For instrument piping below 15 mm (NPS 1/2), as a rule, glass tapes with aluminum foil shall be applied by
overlapping a half width of the tapes.
For displacement type level gages or similar instrument devices, the insulation thickness shall generally be
equal to the thickness of adjoining equipment nozzle insulation.
5. INSTALLATION PROCEDURE
Typical installation methods for insulation are shown in Appendix-1 and 2. Further detail procudere will be
established by insulation contractor.
Table 1
Hot Insulation Calcium Silicate ASTM C533 Type I (JIS A9510 2-22)
Thermal Conductivity: 0℃≦θ≦300℃ 0.0535+1.16×10^-4・θ
300℃≦θ≦600℃ 0.0612+3.38×10^-5・θ+1.95×10^-7・θ^2
[Conditions] Ambient Temperature: 22.0℃ Service hours per year: 8,000hrs Annual rate of interest: 5% Number of years of service: 15yrs Price of quantity of heat: 5\/1000W・h
[Unit] Thickness: mm Heat losst: Pipe W/m Plane W/㎡ θ: Temperature(℃) Thermal conductivity: W/m・K
Temp Pipe size 1/2B 3/4B 1B 1.1/4B 1.1/2B 2B 2.1/2B 3B 4B 5B 6B 8B 10B 12B 14B 16B 18B 20B 22B 24B PLANE
100℃ Thickness 30 35 35 40 40 45 45 50 50 55 55 60 60 60 65 65 65 65 65 65 75
Heat loss 21 22 25 26 28 30 36 37 44 48 55 63 75 87 90 101 112 122 133 144 59
150℃ Thickness 40 40 45 50 50 55 60 60 65 70 70 75 75 80 80 80 85 85 85 85 100
Heat loss 31 35 37 40 43 47 51 57 64 70 79 92 109 120 131 146 154 169 183 198 78
200℃ Thickness 45 50 55 60 60 65 70 70 75 80 85 90 90 95 95 100 100 100 100 105 125
Heat loss 43 46 49 53 57 62 68 75 85 93 101 118 139 153 167 179 197 215 233 241 91
250℃ Thickness 55 55 60 65 70 75 80 80 85 90 95 100 105 105 110 110 115 115 115 120 145
Heat loss 53 59 63 68 71 77 85 93 105 116 125 147 166 189 199 222 236 257 278 289 106
300℃ Thickness 60 65 70 75 75 80 85 90 95 100 105 110 115 120 120 125 125 130 130 130 160
Heat loss 65 69 75 81 87 94 104 111 125 138 149 174 197 218 237 255 280 296 320 344 122
350℃ Thickness 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 135 140 140 145 145 180
Heat loss 77 83 89 97 100 109 121 128 145 160 173 202 229 253 268 297 316 344 362 388 134
400℃ Thickness 70 75 80 85 90 95 100 105 115 120 125 130 135 140 145 145 150 155 155 160 200
Heat loss 90 97 104 113 118 128 142 151 166 183 198 231 261 289 306 339 362 383 414 433 145
450℃ Thickness 75 80 90 95 95 105 110 115 120 125 130 140 145 150 155 160 160 165 170 170 215
Heat loss 104 112 118 128 136 145 160 170 192 211 229 261 295 327 346 374 409 434 457 490 161
500℃ Thickness 85 90 95 100 105 110 115 120 130 135 140 150 155 160 165 170 175 175 180 180 235
Heat loss 117 125 135 146 152 166 183 195 215 237 257 293 331 366 388 419 448 486 512 549 173
550℃ Thickness 90 95 100 105 110 115 125 130 135 145 150 160 165 175 175 180 185 190 190 195 255
Heat loss 133 142 153 166 173 188 204 217 244 263 286 326 368 399 432 466 499 530 570 599 185
600℃ Thickness 95 100 105 115 115 125 130 135 145 155 160 170 175 185 190 190 195 200 205 205 270
Heat loss 150 160 173 184 195 208 230 245 270 292 317 361 408 443 469 517 553 587 620 663 201
650℃ Thickness 95 100 110 115 120 125 135 140 150 155 160 170 180 185 190 195 200 205 210 210 280
Heat loss 157 169 178 193 201 219 237 252 278 307 333 379 420 465 493 533 570 606 640 684 204
Table 2
Personnel Protection Calcium Silicate ASTM C533 Type I (JIS A9510 2-22)
Thermal Conductivity: 0℃≦θ≦300℃ 0.0535+1.16×10^-4・θ
300℃≦θ≦800℃ 0.0612+3.38×10^-5・θ+1.95×10^-7・θ^2
[Conditions] Ambient Temperature: 33℃ Heat transfer coefficient of surface: 8W/m2・K Surface temperature after insulation: 65℃
[Unit] Thickness: mm θ: Temperature(℃) Thermal conductivity: W/m・K
Temp Pipe size 1/2B 3/4B 1B 1.1/4B 1.1/2B 2B 2.1/2B 3B 4B 5B 6B 8B 10B 12B 14B 16B 18B 20B 22B 24B PLANE
100℃ Thickness 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
150℃ Thickness 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25
200℃ Thickness 25 25 25 30 30 30 30 30 30 35 35 35 35 35 35 35 35 35 35 35 40
250℃ Thickness 30 35 35 35 35 40 40 40 45 45 45 45 50 50 50 50 50 50 50 50 55
300℃ Thickness 40 40 40 45 45 45 50 50 55 55 55 60 60 60 60 65 65 65 65 65 70
350℃ Thickness 45 50 50 55 55 55 60 60 65 65 70 70 75 75 75 75 80 80 80 80 90
400℃ Thickness 55 55 60 60 65 65 70 70 75 80 80 90 90 90 90 90 95 95 95 95 110
450℃ Thickness 60 65 65 70 75 75 80 80 90 90 95 100 100 105 105 105 110 110 110 115 130
500℃ Thickness 70 70 75 80 80 90 90 95 100 105 105 110 115 120 120 125 125 130 130 130 155
550℃ Thickness 75 80 90 90 95 95 100 105 110 115 120 125 130 135 140 140 145 145 150 150 180
600℃ Thickness 90 90 95 100 105 110 115 120 125 130 135 145 150 155 155 160 160 165 165 170 210
Table 4
Table 5
Cold Insulation (Anti-sweat) Calcium Silicate (Water-proof type) JIS A9510 1-13
Thermal Conductivity: 0℃≦θ≦300℃ 0.0407+1.28×10^-4・θ
300℃≦θ≦800℃ 0.0555+2.05×10^-5・θ+1.93×10^-7・θ^2
[Conditions] Ambient Temperature: 33℃ Relative humidity: 85% Heat transfer coefficient of surface: 8W/㎡・K
[Unit] Thickness: mm θ: Temperature(℃) Thermal conductivity: W/m・K
Temp Pipe size 1/2B 3/4B 1B 1.1/4B 1.1/2B 2B 2.1/2B 3B 4B 5B 6B 8B 10B 12B 14B 16B 18B 20B 22B 24B PLANE
15℃ Thickness 21 22 23 24 25 26 27 27 28 29 30 30 31 31 32 32 32 32 33 33 34
10℃ Thickness 26 27 29 30 31 32 34 34 36 37 38 39 40 40 41 41 41 42 42 42 45
5℃ Thickness 31 32 34 36 36 38 40 41 43 44 45 47 48 49 49 50 50 51 51 51 55
0℃ Thickness 35 37 39 41 42 44 46 47 49 51 52 54 56 57 57 58 59 59 60 60 66
Appendix-1
Horizontal Pipe
g
tin
cke
ta l Ja
Me w
nd cre
pou g S
om pin
ceC Tap
an "A" lf
sist Se nt
tR
e e ala
a S
He one
ic
ove
r Sil
Silicone Sealant
eC p.)
Pip (Ty
m
a lciu
C
l
S ea
d
ire B an
W &
SS Band
or
als ) (Typ.)
er v
y p.) Int Calcium Pipe Cover (Typ.)
( T m
m
. 3 00 SS Wire or Band & Band Seal
x Detail "A"
p pro
(A Heat Resistance Compound
Silicone Sealant
Metal Jacketing
Over Lap (Min. 50mm.)
(Typ.)
(Typ.)
"B" "C"
(Typ.) Silicone Sealant
S Clip Detail "B"
Detail "C"
Self Tapping Screw
g
tin
ke
J ac
ta l cre
w
Me "A"
g S
nd pin
pou Tap
om Se
lf
ceC
an
ist
e s p.)
a tR (Ty lan
t
He S e a
one
er Sil
i c
Cov
e Silicone Sealant
Pip l
m ea
lciu S
Ca a nd
re
S Wi d & B
S Ban
or
)
r vals
e
Int
0 mm
(Typ.)
x. 30
p pro (Typ.)
(A
Over 12" NPS Note : SS Wire for up to 24" Detail "A"
: SS Band for over 24"
g
tin
ke
J ac
ta l
(Typ.) Me
nd
pou "A"
(Typ.) m
e Co t
c lan
Detail "A"
istan e a
es ne
S
a tR ico
He S il
er
Cov
e
Pip
m p)
lciu (Ty
Ca
l
S ea
Traced Line nd w
ire & Ba Scre
W g
SS Band pin
) Tap
als or lf
er v Se
Int
0 mm n g
x. 3
0 eti
ro ack
p p
ta lJ
(A Me
nd
pou "A"
m
e Co t
c n
tan ala
e sis e Se
a tR i con
He Sil
er
Cov
e
Pip p)
m
lciu (Ty
Ca
l
S ea
Traced Line n d
Wire & Ba
SS Band
als ) or
er v
Int
0 mm
0
rox. 3
p p
(A
Note : SS Wire for up to 24"
: SS Band for over 24"
g
tin
ol) cke
wo Ja
o se eta l
nd o M
ou o l (L
m p wo
Co ck
ce Ro
an
sist
e
a tR Silicone Sealant
He
er
Cov
e
Pip
m Self Tapping Screw
lciu
Ca
(Typ.)
SS Wire
S Clip
(Typ.)
(Typ.)
"A"
(Typ.)
Silicone Sealant
(Typ.)
Silicone Sealant
Silicone Sealant
Silicone Sealant
g
tin
ke
J ac
ta l
Me
nd
pou
m
Co
ce p.)
r
ve e tan nt (Ty
o sis ala
e C at R Se
Pip He on
e
i um ilic
l c S
Ca
l
Sea
d
Ban
d &
n
Ba
or
W ire
SS
als )
er v
Int
0 mm
x. 30
p pro
(A
Note : SS Wire for up to 24"
: SS Band for over 24"
Metal Jacketing
(Over Lap)
"B"
"A"
Rockwool Blanket
Silicone Sealant
TITLE Valve
Metal Jacketing Toggle Clip
Metal Jacketing
(Over Lap)
"B"
"A"
Rockwool Blanket
Silicone Sealant
TITLE Flange
Metal Jacketing
Floating ring by Twisted Wire
Calcium Board
"B"
Metal Jacketing
"C"
Silicone Sealant
Self Tapping Screw
Silicone Sealant
SS Self Tapping Screw
m
5m
12
Min. 50 mm
Detail "B"
S Clip
Nut ( By Fabricator )
Calcium Board
Three Twisted Wire
Insulation Cement
"B"
"A"
Silicone Sealant
Silicone Sealant
5 mm
12
p.)
(Ty
Detail "A"
Min. 50 mm
Detail "B"
p.)
(Ty
Self Tapping Screw Detail "C"
"C"
Calcium Board
5 mm
12
Min. 50 mm
Silicone Sealant
Silicone Sealant
Rockwool Blanket
A
Insulation Pins
Toggle Clip
"A"
Section "A-A"
A
Metal Jacketing Blind Rivet Metal Jacketing
Detail "A"
Rockwool Blanket
Insulation Pins
"B"
Detail "B"
Metal Jacketing
Silicone Sealant
Beading
"A"
TITLE BELLOWS
Body Fixed Body
"A"
Detail "A"
"A"
"B"
g
tin
ke "A"
J ac
eta l
M
tic
M as
V.B
r th t
ve Clo
n
C o s ala
e as Se (Typ.)
n Pip Gl on
e
tio le r li c l
ula t Sea Si S ea (Typ.)
In s nd
o ld J oin Ba
C &
ap
e nd Detail "A"
l tT Ba
s ea men
& ila
and s s F
B gla
or
"B"
(Typ.)
S Clip
(Typ.)
Detail "C"
"C" Silicone Sealant
Detail "B"
Vertical Line
Application Procedure for
Cold Insulation Work
FIG. C-1
g
tin
cke
ta l Ja
Me
tic
M as
V.B "A"
th al
(Typ.) s Clo dS
e
as Ba
n
Detail "A" Gl &
(Typ.) nd
r Ba lant
ove a
eC ale
r
e Se
ip S e on
n P oint ilic
la tio J S
u
In s
ld
Co p)
(Ty
pe
l t Ta
a n
& se ame
Fi l
nd
Ba glass
or
p)
(Ty
V.B Mastic
Glass Cloth
Cold Insulation Pipe Cover V.B Mastic
Metal Jacketing
Joint Sealer
Joint sealer
Glass Wool
Metal Jacketing
V.B. Mastic
Glass Cloth
V.B. Mastic
Joint Sealer
Metal Jacketing
Silicone Sealant
Glass Wool
V.B. Mastic
Glass Cloth
V.B. Mastic
Joint Sealer
Metal Jacketing
Silicone Sealant
NOTE :
Stove type elbows shall be applied where lobster back mitered elbows are not
applicable in multi - layer constructions
V.B. Mastic
Glass Cloth
Silicone Sealant
Metal Jacketing
Joint sealer
Silicone Sealant
Metal Jacketing
Joint Sealer
Silicone Sealant
V.B. Mastic Metal Jacketing
Glass Cloth
Glass Wool
Glass Wool
Multi-Layers
"C" Min.100 mm
Joint Sealer
Silicone Sealant
Silicone Sealant
Min. 50 mm
"A"
"B"
Metal Jacketing
V.B Mastic Cold Insulation Pipe Cover
Glass Cloth
Band & Band Seal
Silicone Sealant
Silicone Sealant
Min. 50mm
Detail "C"
(Typ.)
(Typ.)
Detail "A" Detail "B"
"A"
"B"
Silicone Sealant
50mm
Detail "C"
Silicone Sealant
(Typ.)
Detail "A" (Typ.) Detail "B"
Support Ring
Glass Wool
"C"
Silicone Sealant
S Clip
Silicone Sealant
Detail "C"
Blind Rivet
Silicone Sealant
0 mm
15
Blind Rivet
Min. 50mm
Silicone Sealant
Detail "A" Detail "B"
Blind Rivet
"C"
Silicone Sealant
Detail "C"
Blind Rivet
Silicone Sealant
Silicone Sealant
Detail "B"
Blind Rivet
Blind Rivet
Silicone Sealant
Detail "A"
"B"
"A"
Glass Wool
T.L. Line
Vapour Stop
"B"
Band Seal
Detail "B"
Detail "A"
Glass Cloth
V.B. Mastic
"B"
"A"
V.B. Mastic
Glass Cloth
Floating ring by Twisted Wire
(Typ.) Silicone Sealant
Silicone Sealant
Silicone Sealant
0 mm
15
Detail "A"
Min. 50mm
Detail "B"
V.B. Mastic
Joint Sealer
Detail "C"
0 mm
15
Min. 50mm
Blind Rivet
Detail "A" Detail "B"
V.B. Mastic
Glass Cloth
V.B. Mastic
Metal Jacketing
"A"
"B"
Silicone Sealant
Band & Band seal
p.)
(Ty
Silicone Sealant
Detail "B"
Detail "A"
Metal Jacketing
Glass Wool
T
Joint Seale r
Silicone Sealant
Joint Sealer
NOTE :
Insulation adhesive and/or bamboo skewer may be used for temporary fastening