Professional Documents
Culture Documents
No.236/5,Ganewala Road,Mabima,Heiynthuduwa.
A
VEE POWER Tel :- +94112489615 / +94112489616
Hotline :- +94722330333
Fax :- +94112489617
A
Fabrication
L-1 L-2 L-3 N Mounting Location INDOOR
C C
Internal Partition FORM-1
NAVAL DOCKYARD TRINCOMALEE Nature of Painting Marine Paint with Zn rich Primer
Painting
Largest Transportable Section Interier
Client Width Height Depth Exterier
700mm 1600mm 600mm Powder Thickness
D
MOD D
Accessibilty of Panel FS WM
Sheet Thickness
Top Bottom Left Right Back Frame 1.50mm 1.2mm/1.5mm/2mm
System Voltage
**ALL DIMENSIONS ARE IN mm Operating Voltage (L-N) 230VAC-50Hz
Drawing Number Job Number
Control Supply 230VAC-50Hz
F F
Approved By:-
MAYURAN
A A
700 600
700
VEE POWER
Solutions (Pvt)Ltd
Electrical Panels & Enclosure Manufacturer
L1 L2 L3
Al GLAND PLATE
DIGITAL POWER ANALYZER EARTH FAULT RELAY
R
! DP- 21
DELAB
A mA
Al GLAND PLATE
Pre-Alarm
Output
MODE
Trip Fault
Fault Start
MODE I> I>>
1 : I n>(A)
2 : t>(Sec)
3 : I n>>(A)
b : Most Recent Trip Event
C1~c6 : Previous Trip Event
d : Last Trip Elapsed Time
B B
E1~E4 : Fault Event
F : Info (Over / Op Hr [ x1000]) MODE
RESET
SELECT,
UNDO
SET
TEST
Hold 5 Sec
for test trip
600
Al GLAND PLATE
Al GLAND PLATE
C C
TOP VIEW
1500
1500
1600
1600
700
D D
Al GLAND PLATE
E E
100
BOTTOM VIEW
FRONT ELEVATION SIDE VIEW
F DOOR CLOSED WITH SIDE PANEL F
Project Designed Assembled & Supplied by Design Tool Design By:- VEE POWER Panel Identification Client Page Description
Revision No.
RE-CONSTRUCTION DB-JETTY (JDB) MOD General Arrangement
OF
QUAY
AT
VEE POWER VEE Power Solutions (Pvt) Ltd.
No.236/5,Ganewala Road,Mabima,Heiynthuduwa.
Tel :- +94112489615 / +94112489616
Checked By:-
Approved By:-
MAYURAN
04Q3
04Q4
04Q2
04Q3
SPACE
SPACE
EARTH BAR
B B
04Q6
04Q5
04Q7
04Q9
04Q10
04Q11
04Q8
04Q2
CBCT
C CTs C
1500
1500
1500
1600
1600
1600
04Q1
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
FUSE
L/1 L/1 L/2 L/2 L/3 L/3 L/N L/N
E/B
SA
D MAIN BUS BAR SET D
HRC 1-3
E E
100
100
100
FRONT ELEVATION FRONT ELEVATION SIDE VIEW
COVER PLATE FIXED COVER PLATE REMOVED WITHOUT SIDE PANEL
F F
Project Designed Assembled & Supplied by Design Tool Design By:- VEE POWER Panel Identification Client Page Description
Revision No.
RE-CONSTRUCTION DB-JETTY (JDB) MOD General Arrangement
OF
QUAY
AT
VEE POWER VEE Power Solutions (Pvt) Ltd.
No.236/5,Ganewala Road,Mabima,Heiynthuduwa.
Tel :- +94112489615 / +94112489616
Checked By:-
Approved By:-
MAYURAN
FROM MSB
2X4CX120mm2 CU/XLPE/PVC
BOTTOM ENTRY
A A
2A RD YE BU
FUSE
SURGE
ARRESTER
HRC FUSE 100kA
A2
4P,MCCB
B 630A,55kA B
SHT
-04Q01
A1
EARTH
LEAKAGE
ZCT'S RELAY
FUSE
C 2A C
DIGITAL
POWER
ANALYZER
CT's
600/5A DPA
D 01 02 03 04 05 06 07 08 09 10 11 12 13 14 D
-04Q02 -04Q03 -04Q04 -04Q05 -04Q06 -04Q07 -04Q08 -04Q09 -04Q10 -04Q11 -04Q12 -04Q13
100A,25KA 60A,25KA 60A,25KA 60A,25KA 60A,25KA 60A,25KA 100A,25KA 32A,3P 60A,25KA 32A,3P 20A 3P 32A,2P
MCCB,3P MCCB,3P MCCB,3P MCCB,3P MCCB,3P MCCB,3P MCCB,3P MCCB,10kA MCCB,3P MCCB,10kA MCB,10kA MCCB,10kA
1X4CX10mm2 CU/XLPE/SWA/PVC
1X4CX10mm2 CU/XLPE/SWA/PVC
1X4CX10mm2 CU/XLPE/SWA/PVC
1X4CX10mm2 CU/XLPE/SWA/PVC
1X4CX10mm2 CU/XLPE/SWA/PVC
1X4CX25mm2 CU/XLPE/SWA/PVC
1X4CX10mm2 CU/PVC/PVC+ECC
1X4CX6mm2 CU/PVC/PVC+ECC
1X4CX4mm2 CU/PVC/PVC+ECC
1X2CX6mm2 CU/PVC/PVC+ECC
FEEDER PILLAR 06 (FP-06)
SPACE(BLANK)
SPACE(BLANK)
TOP ENTRY
TOP ENTRY
TOP ENTRY
TOP ENTRY
TOP ENTRY
TOP ENTRY
TOP ENTRY
TOP ENTRY
TOP ENTRY
TOP ENTRY
TOP ENTRY
TOP ENTRY
(J-PP-01)
F F
Project Designed Assembled & Supplied by Design Tool Design By:- VEE POWER Panel Identification Client Page Description
Revision No.
RE-CONSTRUCTION OF DB-JETTY (JDB) MOD SINGLE LINE DIAGRAM
QUAY AT NAVAL DOCKYARD
TRINCOMALEE VEE POWER VEE Power Solutions (Pvt) Ltd.
No.236/5,Ganewala Road,Mabima,Heiynthuduwa.
Tel :- +94112489615 / +94112489616
Checked By:-
Approved By:-
MAYURAN