No.236/5,Ganewala Road,Mabima,Heiynthuduwa.
A
VEE POWER Tel :- +94112489615 / +94112489616
Hotline :- +94722330333
Fax :- +94112489617
A
SANKEN ELS HSL JOINT VENTURE Incoming Outgoing Enclosure Type WELDED
Cable Entries
BOTTOM BOTTOM Mounting Type FREE STANDING
Fabrication
L-1 L-2 L-3 N Mounting Location OUTDOOR
C C
Internal Partition FORM-1
NAVAL DOCKYARD TRINCOMALEE Nature of Painting Marine Paint with Zn rich Primer
Painting
Largest Transportable Section Interier
Client Width Height Depth Exterier
600mm 1500mm 500mm Powder Thickness
D
MOD D
Accessibilty of Panel FS WM
Sheet Thickness
Top Bottom Left Right Back Frame 1.50mm 1.2mm/1.5mm/2mm
(AOPV-01 AND OPV -01) **ALL LIVE PARTS ARE SHROUDED Operating Voltage (L-L) 400VAC-50Hz
System Voltage
**ALL DIMENSIONS ARE IN mm Operating Voltage (L-N) 230VAC-50Hz
Drawing Number Job Number
Control Supply 230VAC-50Hz
F F
Approved By:-
MAYURAN
HESHAN
(AOPV-01 AND OPV -01)
Drawing Number
VD22061
Job Number
VE-22-03-141
R0
Customer Hotline :- +94722330333 Prepared By:- THISARA
SANKEN ELS HSL JOINT
VENTURE
Solutions (Pvt)Ltd Fax :- +94112489617
E-Mail :- info@veepower.lk
Web :- www.veepower.lk
Date:- 25/03/2022 Serial Number Quantity
Sheet No.
A A
800 700
800
600 500
600
25
50
VEE POWER
FEEDER PILLAR 01 Solutions (Pvt)Ltd
POWER AVAILABLE
L1 L2 L3
B B
EARTH LEAKAGE RELAY EARTH LEAKAGE RELAY
R R
! DP- 10 ! DP- 10
DELAB DELAB
A A
mA mA
Pre-Alarm Pre-Alarm
Output Output
MODE MODE
C C
1400
1400
1500
1500
TOP VIEW
D 650 D
600
100
FRONT ELEVATION SIDE VIEW
F BOTTOM VIEW OUTER DOOR CLOSED WITH SIDE PANEL F
Project Designed Assembled & Supplied by Design Tool Design By:- VEE POWER Panel Identification Client Page Description
Revision No.
RE-CONSTRUCTION OF QUAY AT FEEDER PILLAR 01 MOD General Arrangement
NAVAL DOCKYARD TRINCOMALEE
VEE POWER VEE Power Solutions (Pvt) Ltd.
No.236/5,Ganewala Road,Mabima,Heiynthuduwa.
Tel :- +94112489615 / +94112489616
Checked By:-
Approved By:-
MAYURAN
HESHAN
(AOPV-01 AND OPV -01)
Drawing Number
VD22061
Job Number
VE-22-03-141
R0
Customer Hotline :- +94722330333 Prepared By:- THISARA
SANKEN ELS HSL JOINT VENTURE Solutions (Pvt)Ltd Fax :- +94112489617
E-Mail :- info@veepower.lk
Web :- www.veepower.lk
Date:- 25/03/2022 Serial Number Quantity
Sheet No.
700.00
A 800.00 800.00 A
600.00 500.00
600
05F1
05F2
05F3
05F5
05F4
POWER AVAILABLE
L1 L2 L3
B B
EARTH LEAKAGE RELAY EARTH LEAKAGE RELAY
11 12 13 14 15 16
R R
! DP- 10 ! DP- 10
DELAB DELAB
A mA
A
mA
Pre-Alarm Pre-Alarm
Output Output
MODE MODE
10
Trip Fault Trip Fault
Fault Start Fault Start
9
MODE I> I>> MODE I> I>>
1 : I n>(A) 1 : I n>(A)
2 : t>(Sec) 2 : t>(Sec)
3 : I n>>(A) 3 : I n>>(A)
b : Most Recent Trip Event b : Most Recent Trip Event
C1~c6 : Previous Trip Event C1~c6 : Previous Trip Event
d : Last Trip Elapsed Time d : Last Trip Elapsed Time
E1~E4 : Fault Event E1~E4 : Fault Event
F : Info (Over / Op Hr [ x1000]) MODE F : Info (Over / Op Hr [ x1000]) MODE
RESET RESET
SELECT, SELECT,
UNDO UNDO
SET SET
04Q3
04Q2
TEST TEST
N N
ZCT
C C
1400
04Q1
E/B
1500
06SA
D D
E/B
06HRC1-3
E E
100
F
FRONT ELEVATION FRONT ELEVATION SIDE VIEW
F
INNER DOOR CLOSED INNER DOOR OPENED WITHOUT SIDE PANEL
Project Designed Assembled & Supplied by Design Tool Design By:- VEE POWER Panel Identification Client Page Description
Revision No.
RE-CONSTRUCTION OF QUAY AT FEEDER PILLAR 01 MOD General Arrangement
NAVAL DOCKYARD TRINCOMALEE
VEE POWER VEE Power Solutions (Pvt) Ltd.
No.236/5,Ganewala Road,Mabima,Heiynthuduwa.
Tel :- +94112489615 / +94112489616
Checked By:-
Approved By:-
MAYURAN
HESHAN
(AOPV-01 AND OPV -01)
Drawing Number
VD22061
Job Number
VE-22-03-141
R0
Customer Hotline :- +94722330333 Prepared By:- THISARA
SANKEN ELS HSL JOINT VENTURE Solutions (Pvt)Ltd Fax :- +94112489617
E-Mail :- info@veepower.lk
Web :- www.veepower.lk
Date:- 25/03/2022 Serial Number Quantity
Sheet No.
FROM MSB
A 2X4CX120mm2 CU/XLPE/SWA/PVC A
BOTTOM ENTRY
SURGE
ARRESTER
HRC FUSE 100kA
RD YE BU
2A
SP,MCB
A1
-04Q01
630A,55KA
C
4P,MCCB C
A2
01 02
A2
A2
3P,MCCB 3P,MCCB
630A,55KA 400A,36KA
D D
SHT SHT
-04Q02 -04Q03
A1
A1
EARTH EARTH
LEAKAGE LEAKAGE
ZCT'S RELAY ZCT'S RELAY
E E
TERMINAL CONNECTION
TERMINAL CONNECTION
BOTTOM ENTRY
BOTTOM ENTRY
450 TPN + E
260A TPN+E
F F
Project Designed Assembled & Supplied by Design Tool Design By:- VEE POWER Panel Identification Client Page Description
Revision No.
RE-CONSTRUCTION OF QUAY AT FEEDER PILLAR 01 MOD SINGLE LINE DIAGRAM
NAVAL DOCKYARD TRINCOMALEE
VEE POWER VEE Power Solutions (Pvt) Ltd.
No.236/5,Ganewala Road,Mabima,Heiynthuduwa.
Tel :- +94112489615 / +94112489616
Checked By:-
Approved By:-
MAYURAN
HESHAN
(AOPV-01 AND OPV -01)
Drawing Number
VD22061
Job Number
VE-22-03-141
R0
Customer Hotline :- +94722330333 Prepared By:- THISARA
SANKEN ELS HSL JOINT VENTURE Solutions (Pvt)Ltd Fax :- +94112489617
E-Mail :- info@veepower.lk
Web :- www.veepower.lk
Date:- 25/03/2022 Serial Number Quantity
Sheet No.