Professional Documents
Culture Documents
EVAPORATOR
TXV BULB
CONDENSER TXV
RECEIVER
i 62--11150
TABLE OF CONTENTS
62--11150 ii
TABLE OF CONTENTS (Cont)
iii 62--11150
TABLE OF CONTENTS (Cont)
62--11150 iv
LIST OF ILLUSTRATIONS
FIGURE NUMBER Page
Figure 1-1 Main Unit Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Figure 1- Condensing Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Figure 1- Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Figure 1- Cab Command -- Road Only Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Figure 1-5 Cab Command Two -- Units With Standby . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Figure 1-6 Refrigeration Circuit Cooling Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Figure 1-7 Refrigeration Circuit Heating and Defrost Cycle -- HGS2 Open . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Figure 1-8 Refrigeration Circuit Heating and Defrost Cycle -- HGS2 Closed . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
Figure 2-1 Cab Command -- Road Only Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Figure 2-2 Green Light Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Figure 2-3 Cab Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Figure 2-4 Green Light Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Figure 2-5 Configuration Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Figure 3-1 Operating Sequence -- Perishable Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Figure 3-2 Operating Sequence -- Frozen Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Figure 4-1 Manifold Gauge Set (R-404a) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Figure 4-2 Vacuum Pump Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Figure 4-3 Procedure for Adding A Complete Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Figure 4-4 Partial Charge Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Figure 4-5 Typical Setup For Testing Pressure Switches HP1, HP2 and LP . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Figure 4-6 Hot Gas Valve, Condenser Pressure Control Valve or Quench Valve . . . . . . . . . . . . . . . . . . . . 4-9
Figure 4-7 Compressor Pressure Regulating Valve (CPR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Figure 4-8 Thermostatic Expansion Valve Bulb And Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Figure 4-9 Cab Command/Cab Command Two Diagnostic Tool 4-10
Figure 4-10 Fan motor brushes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Figure 6-1 Electrical Schematic Wiring Diagram - Road Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Figure 6-2 Electrical Schematic Wiring Diagram - 115V/1/60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Figure 6-3 Electrical Schematic Wiring Diagram - 230V/3/60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
Figure 6-4 Electrical Schematic Wiring Diagram - 230V/1/60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
v 62--11150
LIST OF TABLES
62--11150 vi
SAFETY SUMMARY
Safety-1 62--11150
SPECIFIC WARNING AND CAUTION STATEMENTS
To help identify the label hazards on the unit and explain the level of awareness each one carries, an explanation is
given with the appropriate consequences:
DANGER -- means an immediate hazard which WILL result in severe personal injury or death.
WARNING -- means to warn against hazards or unsafe conditions which COULD result in severe personal injury or
death.
CAUTION -- means to warn against potential hazard or unsafe practice which could result in minor personal injury,
product or property damage.
The statements listed below are applicable to the refrigeration unit and appear elsewhere in this manual. These
recommended precautions must be understood and applied during operation and maintenance of the equipment
covered herein.
WARNING
Beware of unannounced starting of the unit. The unit may cycle the fans and one of the operating
compressors unexpectedly as control requirements dictate. To ensure unit is without power, remove
power plug and remove battery negative cable.
WARNING
Do not attempt to connect or remove power plug before ensuring the unit is OFF (press OFF key on
Cab Command) and external power circuit breaker is open.
WARNING
Make sure the power plug is clean and dry before connecting to any power source
WARNING
Beware of V-belt and belt-driven components as the unit may start automatically.
WARNING
Do not use a nitrogen cylinder without a pressure regulator. (See Figure 4-5) Cylinder pressure is
approximately 2350 psi (160 bar). Do not use oxygen in or near a refrigerant system as an explosion
may occur.
62--11150 Safety-2
CAUTION
Under no circumstances should anyone attempt to repair the microprocessor module or either Cab
Command module! Should a problem develop with these components, contact your nearest Carrier
Transicold dealer for replacement.
CAUTION
If starting unit for the first time after installation the compressor pressure regulating valve will need
to be reset (refer to paragraph 4.11)
CAUTION
If starting unit for the first time after installation or starting after adding/removing an optional feature
or if Owners operating parameters have changed the Configuration will need to be reset (refer to
paragraph 2.8)
CAUTION
To prevent trapping liquid refrigerant in the manifold gauge set be sure set is brought to suction
pressure before disconnecting.
CAUTION
When working with refrigerant use safety glasses and gloves to avoid burns. Hoses and copper tub-
ing can be hot when unit is running.
CAUTION
Refrigerant R404a is a blend. Charging as a vapor will change the properties of the refrigerant. Only
liquid charging through the king valve is acceptable.
CAUTION
Do not damage or over tighten the enclosing tube assembly. Also make sure all parts are placed in
the enclosing tube in proper sequence to avoid premature coil burn-out.
Safety-3 62--11150
SECTION 1
DESCRIPTION
Table 1-1
EVAPORATOR
62-11150 1-2
17
1
16
2
3
15
4
14 5
13
6
12
11
10
1-3 62-11150
1 2
3
7
8
14
9
12
13 11
10
62-11150 1-4
1.2.4 Condenser Pressure Control Valve (HGS2) 1.3 EVAPORATOR SECTION
The evaporator assembly (see Figure 1-1 and
The condenser pressure control valve (or condenser Figure 1-3) consists of two evaporator blowers, the
closing valve) is a normally open valve that is powered evaporator coil, thermostatic expansion valve, defrost
when the condenser pressure control switch (HP2) is termination thermostat, compressor pressure
closed. With the solenoid coil de-energized, the valve is regulating valve, low pressure switch and quench valve.
in the cool mode and the compressor discharge gas is
delivered to the condenser. In the cool mode, heat is 1.3.1 Thermostatic Expansion Valve
removed from the air inside the truck body and rejected
to the surrounding air. With the solenoid coil energized, The thermostatic expansion valve is an automatic de-
the valve is in the heat mode and the compressor dis- vice which controls the flow of liquid to the evaporator
charge gas is diverted to the evaporator and rejected to according to changes in superheat of the refrigerant
the air inside the truck body. leaving the evaporator. The thermal expansion valve
maintains a relatively constant degree of superheat in
1.2.5 Compressor the gas leaving the evaporator regardless of suction
pressure. Thus, the valve has a dual function; automatic
expansion control and preventing liquid from returning
The compressor withdraws refrigerant gas from the to the compressor. For TXV superheat settings see
evaporator and delivers it to the condenser at an in- Section 1.5.2. To adjust the TXV, refer to Section
creased pressure. The pressure is such that refrigerant 4.12.2.
heat can be absorbed by the surrounding air at ordinary
temperatures. 1.3.2 Compressor Pressure Regulating Valve
(CPR)
1.2.6 Receiver
The CPR valve is installed on the suction line to regulate
the suction pressure entering the compressor. The CPR
Liquid refrigerant from the condenser is delivered to the valve is set to limit the maximum suction pressure. For
receiver. The receiver serves as a liquid reservoir when CPR settings refer to section 1.5.2.
there are surges due to load changes in the system; as a
storage space when pumping down the system and as a 1.3.3 Defrost Termination Thermostat (DTT)
liquid seal against the entrance of refrigerant gas into
the liquid line. Normally closed thermal switch which monitors set-
point. As evaporator cools to setpoint, the switch closes
and signals microprocessor that defrost may be initi-
1.2.7 High Pressure Switch (HP1) ated. Switch terminates defrost by opening at predeter-
mined setpoint. For DTT settings refer to section 1.5.2.
HP1 is a normally closed switch which monitors the
system for high pressure and shuts down the unit when 1.3.4 Quench Valve (BPV)
pressure rises above predetermined setting. For HP1 The quench valve is a normally closed solenoid valve
settings see Section 1.5.2. controlled by the quench thermostat (BPT) mounted on
the road compressor discharge line. The valve allows
1.2.8 Condenser Pressure Control Switch (HP2) metered liquid refrigerant to enter the suction line in the
evaporator in order to provide compressor cooling. For
HP2 is a normally open switch which closes to signal the BPT settings refer to section 1.5.2.
microprocessor to activate the condenser fan. HP2 also 1.3.5 Evaporator Coil
cycles the condenser pressure control valve (HGS2)
and the quench valve (BPV) in addition to the condenser The evaporator is of the tube and fin type. The operation
fan in order to maintain discharge pressure for heating of the compressor maintains a reduced pressure within
capacity. For HP2 settings see Section 1.5.2. the coil. At this reduced pressure, the liquid refrigerant
evaporates at a temperature sufficiently low enough to
absorb heat from the air. Air movement over the evapo-
1.2.9 Standby Motor rator is provided by an electric fan.
The standby motor operates on nominal 1.3.6 Low Pressure Switch (LP)
115/208/230v--1ph--60hz or 230v--3ph--60hz power. An The low pressure switch is a normally closed switch
overload and short cycle protection is provided along which signals the microprocessor to shut down the unit
with automatic reset. Units are also equipped with a when the system is outside the low pressure limit. For
remote mounted power receptacle. LP settings refer to section 1.5.2.
1-5 62-11150
1.4 SYSTEM OPERATING CONTROLS AND 1.5 UNIT SPECIFICATIONS
COMPONENTS
The unit is furnished with a microprocessor control sys- 1.5.1 COMPRESSOR REFERENCE DATA
tem. Once the setpoint is entered at the Cab Command,
the unit will operate automatically to maintain the de- Model TM 15
sired temperature within very close limits. See 2.1.1. Displacement 8.91 in3 (147 cc)
No. Cylinders 6
WARNING Weight 14.8 lbs (6.7 kg)
0.53 pts (250ml) -- Road
Beware of unannounced starting of the Oil Charge
0.32 pts (150ml) -- Standby
unit. The unit may cycle the fans and one of
the operating compressors unexpectedly POE -- Mobil Arctic EAL 68
Approved oil (Carrier Part Number
as control requirements dictate. To ensure 46-60002-02)
unit is without power, remove power plug
and remove battery negative cable.
1.5.2 REFRIGERATION SYSTEM DATA
CAUTION
Under no circumstances should anyone at- a. Defrost Timer
tempt to repair the microprocessor module
Automatic triggering or at preset intervals :
or either Cab Command module! Should a 0, auto, 1h, 2h, 3h, 4h, 5h, 6h
problem develop with these components,
contact your nearest Carrier Transicold b. Defrost Termination Thermostat
dealer for replacement.
Opens at: 50_ ¦ 5_F (27_ ¦ 3_C)
Figure 1-4 Cab Command -- Road Only Units Cut-in at : 320 ¦ 10 psig (22 bar)
e. Refrigerant charge
Refer to Table 1-1.
62-11150 1-6
h. Low Pressure Switch (LP) i. Quench Valve Thermostat (BPT)
Cutout at : 6.0 inHg ¦ 6 (-0.2 bar) Opens at: 220_ ¦ 7_F (105_ ¦ 4_C)
Cut-in at : 14.5 psig ¦ 3 psig (1 bar) Closes at: 248_ ¦ 7_F (120_ ¦ 4_C)
1.5.3 ELECTRICAL DATA
a. Fan Motors
Evaporator Fan Motor (EFM) Condenser Fan Motor (CFM)
Bearing Lubrication Factory Lubricated Bearing Lubrication Factory Lubricated
Horse Power 100w 70w
Operating Amps 7--9 amps Operating Amps 7.5 amps
Speed 2100 rpm (rated) Speed 2350/2600 rpm
1-7 62-11150
1.7 SAFETY DEVICES
System components are protected from damage caused by unsafe operating conditions by automatically shutting
down the unit when such conditions occur. This is accomplished by the fuses and safety devices listed in the following
table.
Table 1-3 Safety Devices
Automatic
restart
Unsafe Conditions Safety Device
with fault
Device setting
cleared
1 Excessive drop in pressure Automatic reset of low YES Cutout : --2.9 psig (-0.2 bar)
pressure switch Timer 5 min
2 Excessive current draw on all mi-
croprocessor outputs (evaporator Electronic relay YES Self-protected opening
and condenser fan)
3 Excessive current draw com- Overload relay YES See electrical wiring diagram
pressor or standby motor
4 Excessive compressor discharge Automatic reset of High
pressure pressure switch (HP1, YES Timer 5 min
HP3)
5 Excessive current draw unit on Standby fuse (FS) (a) NO 30A
standby
6 Excessive current draw unit on Road fuse (FR) NO 40A
road
7 Excessive current draw unit on Main Road fuse (FR1) (b) NO 50A
road
8 Excessive current draw control Fuse on electronic board NO 1A (Time Delayed)
circuit (Field Replaceable) (c)
F1, F2 115/1/60 6.3A (Time Delayed)
9 Connection
C i error on primary
i F1 ,F2 230/1/60 NO
transformer 4A (Time Delayed)
F1, F2 230/3/60
10 Excessive compressor motor or
standby motor winding tempera- Internal Thermal Overload YES Self-protected opening
ture
11 Clutch malfunction - road (exces- Electronic relay YES Self-protected opening
sive current draw)
12 Clutch malfunction - road (insuffi- Electronic relay YES Detection of min. threshold
cient current draw) at 750 mA
Display on Cab Command
13 Double power supply (road + Microprocessor YES until one of the 2 power sup-
standby) plies have been discon-
nected.
14 Low battery voltage Microprocessor YES Cutout/cut-in at 10 V
Main Standby Fuse Block 25A
(FB) 115/1/60
Excess current draw of AC cir- Main Standby Fuse Block 12A
15 (FB) 230/1/60 YES
cuits
Main Standby Fuse Block 10A
(FB) 230/3/60
62-11150 1-8
1.8 REFRIGERANT CIRCUIT The liquid than enters the thermostatic expansion valve
(with external pressure equalizer) which regulates the
1.8.1 REFRIGERANT CIRCUIT DURING COOLING flow rate of refrigerant towards the evaporator in order to
obtain maximum use of the evaporator heat transfer
When cooling (See Figure 1-6), the unit operates as a surface.
vapor compression refrigeration system. The main
components of the system are the reciprocating The evaporator tubes have aluminium fins to increase
compressor, air-cooled condenser, thermostatic heat transfer; therefore heat is removed from the air
expansion valve, direct expansion evaporator and the circulated through the evaporator. This cold air is
hot gas solenoid. circulated throughout the truck to maintain the cargo at
the desired temperature.
The compressor raises the pressure and temperature of The transfer of heat from the air to the low temperature
the refrigerant and forces it through the discharge check liquid refrigerant causes the liquid to vaporize. The
valve and condenser pressure control valve into the vapor passes through the “Liquid/Suction” heat
condenser tubes. The discharge check valves prevent exchanger where it absorbs more heat from the high
reverse flow through the non operating compressor. temperature liquid.
When operating on the road compressor, the flow also The vapor at enters the compressor pressure regulating
passes through an oil separator where oil is removed valve (CPR) which regulates refrigerant pressure
and returned to the compressor. entering the compressor to prevent overloading of the
compressor.
The condenser fan circulates surrounding air over the
outside of the condenser tubes. Heat transfer is thus The quench valve (BPV) opens as required to maintain
established from the refrigerant gas (inside the tubes) to a maximum discharge temperature of 127_C (260°F).
the condenser air (flowing over the tubes). The 1.8.2 REFRIGERANT CIRCUIT DURING HEAT AND
condenser tubes have fins designed to improve the DEFROST
transfer of heat. This removal of heat causes the
refrigerant to liquefy. Liquid refrigerant flows from the When refrigerant vapor is compressed to a high
condenser to the receiver. pressure and temperature in a compressor, the
mechanical energy necessary to operate the
The receiver stores the additional charge necessary for compressor is transferred to the gas as it is being
low ambient operation and for heating and defrost compressed. This energy is referred to as the ”heat of
modes. compression ” and is used as the source of heat during
the heating or defrost cycle (See Figure 1-7 and
The refrigerant leaves the receiver and flows through a Figure 1-8).
manual receiver shut-off valve (king valve).
When the microprocessor activates heating or defrost,
The refrigerant then flows through the filter-drier, where the hot gas solenoid valve (HGS1) energizes (opens). If
an absorbent keeps it dry and clean and then through a the condenser pressure control switch (HP2) is open,
sight glass. The sight glass is fitted with an indicator that the condenser pressure control valve (HGS2) energizes
changes color to indicate moisture content of the to close the line to the condenser. If pressure rises to the
refrigerant. cut--in setting of HP2 (See Section 1.5.2), HGS2
The refrigerant then flows through the subcooler which de--energizes to pressurize the condenser and force
removes additional heat from the liquid to improve more refrigerant into the circuit, increasing heating
system efficiency and then through the liquid line check capacity.
valve. The check valve serves to prevent reverse flow of
refrigerant during the heating/defrost cycle. The main difference between heating and defrosting is
that when in heating mode the evaporator fans continue
The refrigerant then flows to the “Liquid/Suction” heat to run circulating the air throughout the truck to heat the
exchanger. Here, the liquid is further reduced in product. When defrosting, the evaporator fans stop,
temperature by giving off some of its heat to the suction allowing the heated vapor to defrost any ice build-up on
gas. the coil.
1-9 62-11150
23 DISCHARGE
LIQUID
SUCTION LINE
TXV EQUALIZER LINE
21
22
24 20
18
19
25 11
10 17 15
16
26
27
12 14
4 5
6 13
7
3
7 3
2
1
8
62-11150 1-10
23
DISCHARGE
LIQUID
SUCTION LINE
TXV EQUALIZER LINE
21
22
24 20
18
25 19
11 17
10 15
16
26 27
12 14
4
5 6 13
7 3
3
7
2
1
8
1-11 62-11150
23 DISCHARGE
LIQUID
SUCTION LINE
TXV EQUALIZER LINE
21
22
20
24 18
19
25
10 17
11 15
16
26
27 12 14
4 5
3 13
6 7
7
2
1
8
62-11150 1-12
SECTION 2
OPERATION
WARNING
Beware of unannounced starting of the unit. The unit may cycle the fans and one of the operating
compressors unexpectedly as control requirements dictate.
2.1 CONTROL SYSTEM The driver can display the box temperature, and see
whether the setpoint is being maintained by checking
2.1.1 Introduction the green indicator. The indicator lights up red in the
event of a malfunction.
CAUTION When the battery voltage is too low, a fail-safe system
shuts down the unit. Unit restart is automatic and
Under no circumstances should anyone at- time-delayed if the voltage rises to the normal level.
tempt to service the microprocessor com-
ponents or either Cab Command module. 2.1.4 Road Only -- Cab Command
Should a problem develop with the control
system, contact your nearest Carrier Trans-
icold dealer for replacement components.
2-1 62-11150
b. Unit operating LEDs Unit data and function modification keys
Green Light Status The SET key, together with the + and --
keys, enables display and modification
Under normal operation, the green LED will indicate the of unit operating data.
temperature control status as follows:
The display scrolls through parameters
each time the SET key is pressed.
Steady green
COOLING
LED Increase key for selected data
NULL
Green LED is
BAND
OFF SETPOINT
62-11150 2-2
b. Unit operating LEDs c. Keypad
Green Light Status The keypad consists of six keys that enable the operator
Under normal operation, the green LED will indicate the to activate various functions, display operating data and
temperature control status as follows: modify operating parameters.
Figure 2-4 Green Light Status Increase key for selected data
Red Light Status
For all alarms, except out--of--range alarms A12 and
A13 (See Table 2-1), the steady red unit indicating LED NOTE
will light until the alarm is cleared. At that point the If no buttons are depressed within 5 seconds of
steady green indicator LED will light and the alarm will pressing the ON key, the system reverts to box
become inactive. temperature.
When the unit has been running for at least 15 minutes
after setpoint has been reached and goes
out--of--range, the red LED will flash according to the
following chart:
ALARM
A12
9°F (5°C)
SETPOINT
- 1.8°F (-- 1°C)
ALARM
A13
2-3 62-11150
d. Additional Key Functions 2.2 START--UP
To access additional key functions, press and hold the 2.2.1 Inspection
SET key for 5 seconds. The microprocessor will provide Before starting the truck engine or connecting standby
a set of additional functions as the SET key is pressed power check the following
additional times after the 5 second hold. The sequence a. Check condenser coil for cleanliness.
for the additional functions is as follows:
b. Check condition of refrigerant hoses.
c. Check condition and tension of compressor belt(s).
Press SET for 5 sec. : this enables
access to the alarm codes d. Check condition of condenser fan blade, motor and
brushes.
e. Check truck battery fluid level.
Press to display the alarm list f. Check truck battery and terminal connections -- clean
and tighten as necessary.
Press again to display software ver- g. Check defrost water drains from evaporator.
sions h. Check evaporator coil for cleanliness.
i. Check condition of evaporator blower wheels and
Press to display the cab command motor.
software version 2.2.2 Starting -- Road Only Units -- Cab Command
62-11150 2-4
2.2.3 Starting -- Road/Standby Units -- Cab 1) Start--up Process
Command Two Start--up on Road with cool setpoint and box temp
>--5°F (--20.6°C):
Depending on desired mode of operation, either start
the vehicle engine or connect the standby power plug. a. 0 time: ON key pushed
b. 20 seconds: HGS1 ON (pressure equalization)
Press the ON key to start the unit c. 40 seconds: CLHR ON (Road clutch)
(start-up is time-delayed for 40
seconds). d. 50 seconds: HGS1 OFF/ fans ON (unit in cool)
The digital display of the cab com- Start--up on Standby with cool setpoint and box
mand displays the box tempera- temp >--5°F (--20.6°C):
ture.
a. 0 time: ON key pushed
Check that temperature set-point b. 15 seconds: HGS1 ON (pressure equalization)
is correct by pressing the SET
key; the set-point temperature is c. 40 seconds MC ON (Standby contactor coil)
highlighted on the digital display. d. 50 seconds: HGS1 OFF/ fans ON (unit in cool)
Start--up on Road with heat setpoint and box temp
>--5°F (--20.6°C):
NOTE a. 0 time: ON key pushed
During start up, the evaporator motor speed in- b. 20 seconds: HGS1/ HGS2/ CLHR ON
creases continuously to selected speed over a c. 45 seconds: fans/ BPV ON (unit in heat)
30 seconds time period. Start--up on Standby with heat setpoint and box
temp >--5°F (--20.6°C):
CONNECT POWER FOR STANDBY a. 0 time: ON key pushed
b. 10 seconds: HGS1/ HGS2 ON
If the unit is to be operated in the standby mode, connect
power as follows: c. 20 seconds: MC/ fans/ BPV ON (unit in heat)
Start--up on Road with cool setpoint and box temp
<--5°F (--20.6°C):
a. 0 time: ON key pushed
WARNING b. 20 seconds: CLHR / fans ON (unit in cool)
Start--up on Standby with cool setpoint and box
Do not attempt to connect or remove power temp <--5°F (--20.6°C):
plug before ensuring the unit is OFF (press
OFF key on Cab Command) and external a. 0 time: ON key pushed
power circuit breaker is open. b. 10 seconds: MC/ fans ON (unit in heat)
Start--up on Standby with heat setpoint and box
temp <--5°F (--20.6°C):
a. 0 time: ON key pushed
WARNING b. 10 seconds: HGS1/ HGS2/ MC ON
c. 15 seconds: fans/ BPV ON (unit in heat)
Make sure the power plug is clean and dry Start--up on Road with heat setpoint and box temp
before connecting to any power source <--5°F (--20.6°C):
a. 0 time: ON key pushed
a. Check that the external power source corresponds to b. 20 seconds: HGS1/ HGS2/ CLHR ON
the characteristics of the unit (see paragraph 1.5.3 2.2.4 Minimum Shut--Down Time On Standby
step c.). Make sure external power source circuit
breaker is open.
The minimum shut-down for the standby compressor is
b. Make sure unit is OFF by pressing the OFF button on 5 minutes after reaching setpoint.
the Cab Command Two.
After this minimum shut-down period, the unit restarts
c. Plug the power cord into unit receptacle.
when the temperature goes out of the cycling range by ±
d. Close external power source circuit breaker. 1.8. 3.6 or 5.4°F (± 1, 2 or 3°C).
2-5 62-11150
2.3 SETPOINT ADJUSTMENT a. Manual Defrost
Check that box temperature is 40°F (4.4°C) or lower.
2.3.1 Road Only and Road/Standby Units -- Cab
Command and Cab Command Two Press manual defrost key to
initiate manual defrost.
It is possible to increase or decrease the setpoint by
whole numbers until the required setpoint is displayed. If
display stays highlighted, this indicates the setpoint
displayed has not been validated. b. Defrost Termination Safety
If the defrost cycle does not terminate after 45 minutes,
The new setting for the setpoint is validated by pressing the cycle terminates automatically and displays alarm
the SET key. code A14.
62-11150 2-6
Table 2-1 Alarm Messages
Road Only Road/Standby Malfunction Description
Codes
Red LED flashes
X A00 No malfunction.
Unit in operation.
X A01/A02 High or Low pressure switch
X A01 Low pressure switch (LP)
X A02 High pressure switch
X A03 Standby compressor thermal overload open
X X A04 Road compressor clutch (CLHR) malfunction
X A05 Standby contactor (MC) high amp draw
X X A06 Condenser fan motor (CFM) high amp draw
X X A07 Evaporator Fan low rotational speed
A08 (Not applicable)
X X A09 Hot gas valve (HGS1) high amp draw
X X A10 Quench valve (BPV) high amp draw
Condenser pressure control valve (HGS2) high
X X A11 amp draw
X X A12 High temperature alarm
X X A13 Low temperature alarm
X X A14 Defrost cycle is greater than 45 minutes
Setpoint adjusted out of the range --20.2 to
X X A15 86°F (--29°C/+30°C) or below the programmed
low threshold
Evaporator drain line heater (DWR)
X A16 malfunction (option)
Transformer/Rectifier thermal overload (RBT)
X A17 open
X A18 Control fault, electric heat (option)
Low pressure switch jumper (microprocessor
X A20 terminal 6 to SP2) open
X A21 Compressor contactor (MC) open circuit
X A22 Condenser fan motor (CFM) open circuit
2-7 62-11150
Alarm Messages -- Continued
Road Only Road/Standby Malfunction Description
Codes
Hot water solenoid valve (HWV) open circuit
X A23 (option)
X A24 Hot gas valve (HGS1) open circuit
X A25 Quench valve (BPV) open circuit
Condenser Pressure Control Valve (HGS2)
X A26 open circuit
Evaporator drain line heater (DWR) open
X A27 circuit (option)
X A28 Relay fault, electric heat (option)
X X BAT Low battery voltage
Functional parameters have not been set or
have been lost. Press and hold the SET key to
X 2EP clear the alarm. Refer to Section 2.7.1 to set
parameters.
Probe malfunction or evaporator temperature
X X EE out of limits [--49° to 174°F (--45° to 79°C)]
X X Err Programming error on part of operator
Setpoint lower than maximum setpoint but in
X X ------ the range of --20°F to 86°F.
------
------ Dual power supply (road and standby units
X
------ only -- Cab Command Two)
2.5.3 Clearing Past Alarm Messages 2.6 CHECKING THE EEPROM VERSION
The alarm list provides information on current alarms
and past alarms which may be helpful in trouble
shooting unit problems. Once all the alarm information Start up unit
has been noted and service is complete, the alarm list
may be cleared. Press the SET key for 5 seconds. Press
a. To clear the past alarm messages: again to display eeprom version number.
Press the ON, the + and
Press SET key to return to box
the -- keys at the same temperature.
time.
a. To clear the active alarm messages:
Turn unit OFF and then back ON.
62-11150 2-8
2.7 MODIFICATION OF FUNCTIONAL 6 hours) using the (+) or (--) keys. Selection MUST be
PARAMETERS validated by pressing the SET key.
2.7.1 Road Only Units -- Cab Command 3. The next steps must be performed with the unit ON:
2-9 62-11150
2.7.2 Road/Standby Units -- Cab Command Two c.Defrost Parameters
The procedure to adjust the unit functional parameters
is as follows: Shut-down unit.
1) The minimum setpoint parameter is displayed. The The defrost interval parameter is displayed next. This
minimum setpoint can be selected by scrolling setting determines the length of time between defrosts:
through available options [--20.2°F (--29°C), 68°F
(20°C), 32°F (0°C)] using the (+) or (--) keys. Factory
setting is --20°F. Selection MUST be validated by 0 : complete deletion of defrost.
pressing the SET key.
AUT : The microprocessor calculates the time --
2) The maximum setpoint parameter is displayed. The factoring in length of last defrost, time between two
maximum setpoint can be selected by scrolling
through available options [68°F (20°C), 86°F (30°C)] defrost cycles in relation to setpoint and cargo.
using the (+) or (--) keys. Factory setting is 68°F.
Selection MUST be validated by pressing the SET 0.5 to 0.9 : decreases the microprocessor calculated
key. time between defrosts by 1/2 normal (0.5) to 9/10 nor-
3) The null mode differential temperature is displayed mal (0.9).
next. This setting determines the temperature differ-
ence between box temperature and setpoint that con- 1.1 to 1.5 : increases the microprocessor calculated
trols compressor cycling. The differential can be se-
lected by scrolling through available options [1.8°F time between defrosts by 1.1 times normal (1.1) to 1 1/2
(1°C), 3.6°F (2°C), or 5.4°F (3°C)] using the (+) or (--) times normal (1/5).
keys. Factory setting is 3.6°F (2°C). Selection MUST
be validated by pressing the SET key. 1 H, 2 H,... 6 H : Forced interval between each defrost
4) The ON/OFF (Continuous airflow) parameter for the expressed in hours.
evaporator fans is displayed next. This feature deter-
mines whether the evaporator fan is on or off when
the unit cycles off upon reaching setpoint. The factory
setting is OFF. Change setting by using the (+) or (--) Press SET for 5 seconds : enables
keys. Selection MUST be validated by pressing the access to alarm messages.
SET key.
In the event of more than one alarm,
5) The return air temperature will be displayed after the press the + and -- keys to list them.
above sequence.
62-11150 2-10
2.8 MICROPROCESSOR CONFIGURATION -- NUMBER OF EVAPORATOR FANS
ROAD/STANDBY ONLY
(CAB COMMAND TWO) FAn1 : 1 fan
FAn2 : 2 fans
CAUTION FAn3 : 3 fans
If starting unit for the first time after installa- Press the + or -- keys to change FAn1,
FAn2 or FAn3.
tion or starting after adding/removing an
optional feature or if Owners operating pa-
rameters have changed, the Configuration Press the SET key to validate and go to
the next configuration.
will need to be reset.
To access the configuration menu, use a small tool, FAN SPEED
such as a paper clip, to press the configuration button
located inside the hole on the rear of the Cab Command SPd-- : 1st speed mini
Two module (see Figure 2-5). Press the button only SPd= : 2nd speed medium
once to enter the menu. All changes are made with the SPd : 3rd speed maxi
keypad.
Press the + or -- keys to change SPd--,
Configuration SPd= or SPd
button
Press the SET key to validate and go to
the next configuration.
2 or 3 ET MODE
2 Et : cool, null
3 Et : cool, null, heat
Press the + or -- keys to change
2 Et or 3 Et.
Figure 2-5 Configuration Button Note :
TEMPERATURE UNIT 35X -- 3ET
Ut_C : Celsius degree display
Press the SET key to validate and go to
Ut_F : Fahrenheit degree display the next configuration.
Press the + or -- keys to change Ut_C or
Ut_F. OPTIONAL ROAD HEATING KIT
hrOF : option road heating kit not
Press the SET key to validate and go to installed
the next configuration. hrOn : option road heating kit
installed
UNIT VOLTAGE
Press the + or -- keys to change hrOF or
PS12 : unit voltage 12 V hrOn.
PS24 : unit voltage 24 V
Press the SET key to validate and go to
Press the + or -- keys to change PS12 the next configuration.
or PS24.
2-11 62-11150
OPTIONAL STANDBY HEAT KIT 2.9 STOPPING THE UNIT
hSOF : standby heating kit not
installed Press the OFF key or turn the ignition
key to off position.
hSOn : standby heating kit installed
DOOR SWITCH
drOF : door switch (option) not
installed
drOn : door switch (option) installed
NOTE
If no key is activated after validating a configu-
ration, the system reverts to box temperature
display and the configuration procedure is
aborted. Only validated changes are recorded.
62-11150 2-12
SECTION 3
TEMPERATURE CONTROL
3.1 SEQUENCE OF OPERATION
General operation sequences for cooling, null, and
heating are provided in the following paragraphs. The
microprocessor automatically selects the mode
necessary to maintain box temperature at setpoint. COOL
+5.4_F (+3_C )
3.1.1 Cooling Mode
or +3.6_F (+2_C )
a. With return air temperature above setpoint and de- or +1.8_F (+1_C)
creasing, the unit will be cooling with the compressor
and evaporator fans operating. (See Section 1.8.1 for UNIT STOPPED SETPOINT
a description of the refrigeration circuit during cool-
ing.) The condenser fan will operate under the control
of the condenser pressure control switch (HP2). The
green unit operating LED will operate in accordance --1.8_F (--1_C)
with Figure 2-4. If discharge pressure rises to HP2 or --3.6_F (--2_C)
setting (See Section 1.5.2), the condenser fan motor HEAT
or --5.4_F (--3_C)
(CFM) will turn on for a minimum of 3 minutes.
(setting)
b. If discharge temperature increases to the setpoint of
the quench thermostat (BPT), the thermostat will
close, energizing the quench valve (BPV). This will al-
low liquid into the suction line in order to cool the com- Figure 3-1 Operating Sequence -- Perishable
pressor. Once the discharge temperature decreases Mode
to the setpoint of the BPT, the thermostat will open, 3.1.3 Frozen Mode
DE--energizing the BPV.
The unit operates in the frozen mode with setpoints at or
c. Once temperature decreases to the setpoint the unit below 10°F (--12°C). Operation in the frozen mode is the
will enter the null mode. If the continuous air flow pa- same as in the perishable mode except no heating takes
rameter is set to ON, the evaporator fans will continue place.
to operate with all other components OFF. If the con-
tinuous air flow parameter is OFF, the evaporator
fans and all other components will be OFF. A 5 min-
ute delay is required before restart is allowed.
+5.4_F (+3_C )
d. If temperature increases during the null mode, the COOL or +3.6_F (+2_C )
unit will restart in cooling.
or +1.8_F (+1_C )
3.1.2 Heating Mode
If temperature continues to decrease the unit will en-
ter the heating mode with the compressor and evapo- SETPOINT
rator fans operating, the hot gas solenoid valve
(HGS1) energized (open), the condenser pressure UNIT STOPPED --1.8_F (--1_C)
control valve (HGS2) energized (closed) and the
quench valve (BPV) energized (open). If discharge or --3.6_F (--2_C)
pressure rises to the HP2 setting (See Section 1.5.2) or --5.4_F (--3_C)
HGS2 will de--energize (open) and BPV will de--ener-
(setting)
gize (closed) for a minimum of 1 minute. If discharge
pressure remains the same or rises the condenser
fan motor (CFM) will turn on. (See Section 1.8.2 for a
description of the refrigeration circuit during heat and
defrost.) Figure 3-2 Operating Sequence -- Frozen Mode
3-1 62-11150
3.2 DEFROST CYCLE During defrost, the evaporator fans shut down and
operation of the condenser fan is controlled by the
Defrost is an independent cycle overriding cooling and microprocessor. The end of the cycle is controlled by the
heating functions to melt frost and ice from the opening of the defrost termination thermostat (See
evaporator when necessary. Defrost may be initiated by Section 1.5.2 for DTT settings. The same logic for
the microprocessor or manually by the operator once component control that applies to heating also applies to
the defrost termination thermostat has closed at defrost. (See Section 1.8.2 for a description of the
approximately 38°F (3.3°C). In defrost mode, the refrigeration circuit during heat and defrost.)
microprocessor displays “dF” on the cab command and
set-point is no longer displayed. 3.3 MINIMUM OFF TIME
Once the unit has cycled off, it will remain off for the
minimum off time of 5 minutes. This prevents rapid
cycling due to changes in air temperature. Air
temperature in the box changes rapidly but it takes time
for the product temperature to change.
62-11150 3-2
SECTION 4
SERVICE
WARNING
Beware of unannounced starting of the unit. The unit may cycle the fans and one of the operating
compressors unexpectedly as control requirements dictate. To ensure unit is without power, re-
move power plug and remove battery negative cable.
4.1 PREVENTATIVE MAINTENANCE Table 4-4 Preventive Maintenance Schedule
Standby
Regular servicing is required in order to optimize the life Service Service Service Service
and reliability of your unit. The recommended scheduled Hours
A B C D
maintenance intervals and categories are provided in
Table 4-3 while descriptions of the service procedures 100 G
to be carried out under each category are provided in 1000 G G
Table 4-5
2000 G G G
Table 4-1 Preventative Maint. After Start--up 3000 G G
Check condenser and evaporator fan rotation and 4000 G G G G
for proper air flow. 5000 G G
Check cab command for proper unit cycling and 6000 G G G
correct display of all indicator lights.
7000 G G
Check for unusual noise or vibration
Check that refrigerant is visible in liquid line sight- Table 4-5 Service Category Descriptions
glass. Service A 1. Check the tension of the alternator
belt(s).
2. Check that the vehicle engine runs
correctly at low speed and that the
Table 4-2 Preventative Maint. After 15 minutes or compressor mounting kit is correctly
more of operation tightened and that belt tension is cor-
rect.
Check that refrigerant is visible in liquid line sight- 3.Check the tightness of bolts and
glass. screws and that the unit is correctly
Check compressor oil level fastened onto the box.
Check for proper temperature control 4.Check tension of alternator/compres-
sor belt.
Check temperature cycling operation Service B 1. Clean condenser & the evaporator
Put unit into manual defrost mode. coils. (Paragraphs 4.17 & 4.18)
Verify unit terminates defrost mode. 2. Replace the road compressor belt.
3. Check and, if required, replace the
filter-drier. (Paragraph 4.8)
p
4. Check the operation of cab com-
mand
mand.
Table 4-3 Preventive Maintenance Schedule
5. Check the defrost:
DCut-in
Road DFan shut-down
DCut-out
Miles Service Service Service Service DDefrost water drain(s)
A B C D
Service C 1. Check the operation of the evapora-
3000 G tor and condenser fans. Change the
18000 G G condenser motor brushes. The
evaporator of this unit is equipped with
36000 G G G brushless fan motors therefore, brush
54000 G G maintenance is not required.
72000 G G G G 2. Change the compressor oil. Use
polyol ester oil (POE) approved by
90000 G G CARRIER. Refer to paragraph 1.5.1.
108000 G G G Service D 1. Change the removable fuses and
126000 G G capacitors (if any) in the control box.
4-1 62-11150
4.2 INSTALLING R-404a MANIFOLD GUAGE SET 4. Install both service valve stem caps (finger-tight
only).
A manifold gauge/hose set is required for service of
models covered within this manual. The manifold Low Pressure 1 High Pressure
gauge/hose set is available from Carrier Transicold. Gauge Gauge
(Carrier Transicold P/N 07-00314-00, which includes
items 1 through 4, Figure 4-1). To perform service using
the manifold gauge/hose set, do the following:
4.2.1 Preparing Manifold Gauge/Hose Set For Use
a. If the manifold gauge/hose set is new or was
exposed to the atmosphere it will need to be eva-
cuated to remove contaminants and air as follows: Opened Closed
(Backseated ) (Frontseated)
b. Connect high and low side hoses to blank connec- Hand Valve Hand Valve
tions on back of manifold gauge set and midseat
both hand valves. 2
To Low Side To High Side
c. Connect the yellow hose to a vacuum pump and an Access Valve Access Valve
R-404a cylinder.
d. Evacuate to 10 inHg (254mmHg) and then charge 3
with R-404a to a slightly positive pressure of 1.0 psig BLUE 3
(0.07 Bar). RED
e. Front seat both manifold gauge set hand valves and
disconnect from cylinder. The gauge set is now
ready for use. 3
4 2 YELLOW 4
4.2.2 Connecting Manifold Gauge/Hose Set
To connect the manifold gauge/hose set for reading 6 5
pressures, do the following: (Blue Knob) (Red Knob)
a. Remove service valve stem cap and check to make 1. Manifold Gauge Set
sure it is backseated. Remove access valve cap. 2. Hose Fitting (0.5-16 Acme)
b. Connect the refrigeration hose (see Figure 4-1) to 3. Refrigeration and/or Evacuation Hose
the access valve. . (SAE J2196/R-134a)
4. Hose Fitting w/O-ring (M14 x 1.5)
c. Read system pressures. 5. High Side Field Service Coupler
d. Repeat the procedure to connect the other side of 6. Low Side Field Service Coupler
the gauge set.
4.2.3 Removing the Manifold Gauge Set Figure 4-1 Manifold Gauge Set (R-404a)
1. While the compressor is still ON, backseat the high 4.3 PUMPING DOWN OR REMOVING THE
side service valve. REFRIGERANT CHARGE
2. Midseat both hand valves on the manifold gauge set
and allow the pressure in the manifold gauge set to
be drawn down to low side pressure. This returns CAUTION
any liquid that may be in the high side hose to the
system. When working with refrigerant use safety
glasses and gloves to avoid burns. Hoses
and copper tubing can be hot when unit is
CAUTION running.
NOTE
To prevent trapping liquid refrigerant in the Once the system is open, it must be evacuated
manifold gauge set be sure set is brought to and dehydrated. (See section 4.5)
suction pressure before disconnecting.
NOTE
3. Backseat the low side service valve. Frontseat both To avoid damage to the earth’s ozone layer, use
manifold set hand valves. Remove the refrigeration a refrigerant recovery system whenever remov-
hoses from the access valves. ing refrigerant.
62-11150 4-2
a. Pumping the Unit Down b. Removing the Refrigerant Charge
To service the filter-drier, expansion valve, CPR valve or Connect a refrigerant recovery system (Carrier P/N
evaporator coil, pump most of refrigerant into MVS--115--F--L--CT (115V) or MVS--240--F--L--CT
condenser coil and receiver as follows: (240V) ) to the unit to remove refrigerant charge. Refer
to instructions provided by the manufacturer of the re-
1. Backseat suction and discharge service valve (turn frigerant recovery system.
counterclockwise) to close off gauge connection and 4.3.1 Refrigerant Removal From A Non--operative
attach manifold gauges to valves. Standby Compressor
2. Open valves two turns (clockwise). Purge gauge To remove the refrigerant from a standby compressor
line. that is not operational, do the following:
3. Close the receiver outlet (king) valve by turning a. Attach a manifold gauge set to the standby compres-
clockwise. Start unit and run in high speed cooling. sor service valve access ports. Ensure both service
Place Run-stop switch in the STOP position when valves are frontseated.
unit reaches 0.1 kg/cm@ (1 psig). b. Recover refrigerant with a refrigerant recovery sys-
4. Frontseat (close) suction service valve and the re- tem.
frigerant will be trapped between the compressor c. Service or replace components as required and leak
suction service valve and the manual shutoff (King) check the compressor. (See Section 4.4).
valve. 4.3.2 Pumping The Unit Down If Standby Is
5. Before opening up any part of the system, a slight Available
positive pressure should be indicated on the pres- To service the filter-drier, moisture-liquid indicator, liquid
sure gauge. line check valve, expansion valve, quench valve,
evaporator coil, compressor pressure regulating valve,
6. When opening up the refrigerant system, certain suction bypass valve, pump the refrigerant into the high
parts may frost. Allow the part to warm to ambient side as follows:
temperature before dismantling. This avoids internal
condensation which puts moisture in the system. a. Attach manifold gauge set to standby compressor
service valves.
7. When service has been completed. Open (back-
seat) King valve and midseat suction service valve. b. Start the unit and run in standby cooling mode for 10
to 15 minutes. Frontseat the king valve. Place the
8. Leak check connections with a leak detector. (Refer emergency switch in the OFF position when the suc-
to section 4.4) tion reaches a positive pressure of 1.0 psig (0.01 bar).
9. Start the unit in cooling and check for nonconden- c. Frontseat the standby suction service valve. The
sibles. refrigerant will be trapped between the standby com-
pressor suction service valve and the liquid line valve.
10.Check the refrigerant charge. (Refer to section d. Before opening up any part of the system, a slight
4.6.1) positive pressure should be indicated on the pressure
gauge. If a vacuum is indicated, emit refrigerant by
NOTE cracking the liquid line valve momentarily to build up a
slight positive pressure.
Store the refrigerant charge in an evacuated
container if the system must be opened be- e. When opening up the refrigerant system, certain
parts may frost. Allow the part to warm to ambient
tween the compressor discharge valve and re- temperature before dismantling. This avoids internal
ceiver. condensation which puts moisture in the system.
f. After repairs have been made, be sure to perform a
refrigerant leak check (refer to paragraph 4.4), and
NOTE evacuate and dehydrate the low side (refer to para-
Whenever the system is opened, it must be eva- graph 4.5.4).
cuated and dehydrated. (Refer to section 4.5.3) g. Check refrigerant charge (refer to paragraph 4.6.1).
4-3 62-11150
4.4 REFRIGERANT LEAK CHECKING 4.5.2 Preparation
a. Evacuate and dehydrate only after pressure leak test.
(Refer to paragraph 4.4).
b. Essential tools to properly evacuate and dehydrate
any system include a good vacuum pump (5 cfm =
CAUTION 8m#H volume displacement, P/N 07-00176-01) and a
good vacuum indicator such as a thermocouple vacu-
um gauge (vacuum indicator). (Carrier P/N
Refrigerant R404a is a blend. Charging as a 0700414--00).
vapor will change the properties of the re-
frigerant. Only liquid charging through the NOTE
king valve is acceptable. Use of a compound gauge is not recommended
because of its inherent inaccuracy.
62-11150 4-4
3
2
1
4
7
5
5 8
6
4-5 62-11150
4.6 CHARGING THE REFRIGERATION SYSTEM b. Place refrigerant 404a cylinder on scale. Connect the
discharge gauge field coupler of the manifold test set
to the king valve access port. Connect the suction
pressure hose of the manifold gauge set to the man-
CAUTION ifold dead head port. Connect a charging line be-
tween the center tap of the second gauge set and the
Refrigerant R404a is a blend. Charging as a refrigerant drum. Midseat discharge knob. Open the
vapor will change the properties of the re- liquid valve on the drum and purge all hoses. Front-
frigerant. Only liquid charging through the seat discharge knob
king valve is acceptable. c. Note weight of refrigerant cylinder.
d. Open liquid valve on refrigerant cylinder. Open king
4.6.1 Checking The Refrigerant Charge valve half way and allow the liquid refrigerant to flow
into the unit until the correct weight of refrigerant has
Start unit in cooling mode. Run approximately ten been added as indicated by scales. (See Section
minutes. Partially block off air flow to condenser coil 1.5.1 for correct charge.)
increase the area blocked until compressor discharge
pressure is raised to approximately 325 psig (22 bars). NOTE
The charge is correct if there are no bubbles at the liquid It may be necessary to finish charging the unit
line sight glass. using the partial charge method, due to pres-
4.6.2 Installing A Complete Charge (See sure rise in the high side of the system. (Leave
Figure 4-3) gauges and hoses in place and refer to para-
graph 4.6.3)
NOTE
The ambient (air entering the condenser) air e. If scale indicates the correct charge has been added,
close liquid line valve on drum and manifold valves.
temperature should be above 40°F (4.4°C)
f. Backseat the king valve, remove charging hoses and
a. Evacuate the refrigeration circuit and leave in a deep check charge in accordance with paragraph 4.6.1.
vacuum (refer to paragraph 4.5). g. Check for noncondensables.
27
4
62-11150 4-6
4.6.3 Adding A Partial Charge (See Figure 4-4)
1 2
2
3
1
4-7 62-11150
4.7 CHECKING FOR NON--CONDENSABLES 4.9.2 Checking Switches
a. A schraeder valve is located under each switch to al- 1. Cylinder valve and gauge
low removal and installation without removing the re- 2. Pressure regulator
frigerant charge. 3. Nitrogen cylinder
4. Pressure gauge (0 to 400 psig = 0 to 28 bars)
b. Remove switch and test in accordance with para- 5. Bleed-off valve
graph 4.9.2. 6. 1/4 inch connection
Figure 4-5 Typical Setup For Testing Pressure
c. Replace or reinstall switch. Switches HP1, HP2 and LP
62-11150 4-8
4.10 HOT GAS SOLENOID VALVE (HGS1),
CONDENSER PRESSURE CONTROL VALVE
(HGS2) AND QUENCH VALVE (BPV)
CAUTION
4.10.1 Replacing Solenoid Coil Do not damage or over tighten the enclos-
ing tube assembly. Also make sure all parts
It is not necessary to remove the refrigerant charge
when replace the coil (see Figure 4-6). are placed in the enclosing tube in proper
sequence to avoid premature coil burn-out.
a. Remove coil snap cap, voltage plate and coil assem-
bly. Disconnect leads and remove coil junction box if
necessary. e. Tighten enclosing tube. If valve has been removed
from the circuit, check for leaks.
b. Verify coil type, voltage and frequency. This informa-
tion appears on the coil voltage plate and the coil f. Install coil assembly, voltage cover and snap cap.
housing. g. Evacuate, dehydrate and recharge unit. Refer to
c. Place new coil over enclosing tube and then install paragraphs 4.5.3 and 4.6.2.
voltage plate and snap cap. h. Start unit and check operation.
1
2 1 2 3
3
4-9 62-11150
4.12 THERMOSTATIC EXPANSION VALVE 1
MOP expansion valve characteristics :
4
5 2
SRule : in order to avoid compressor overcharge, a
MOP expansion valve (expansion valve with limited
flow) is used. 3
SOperating : the expansion valve will not open more
than the MOP setpoint. Any temperature increase at
the bulb should not open the expansion valve further.
The thermal expansion valve is an automatic device
which maintains constant superheat of the refrigerant
gas leaving the evaporator regardless of suction 1. Suction Line 3. Thermocouple
pressure. The valve functions are: (a) automatic (end view) 4. TXV Bulb
response of refrigerant flow to match the evaporator 2. TXV Bulb Clamp 5. Nut and Bolt (Clamp)
load and (b) prevention of liquid refrigerant entering the
compressor. Figure 4-8 Thermostatic Expansion Valve Bulb
And Thermocouple
Unless the valve is defective, it requires no adjustment,
but maintenance must be done every year in order to 4.12.3 Checking The TXV Orifice Strainer
clean the orifice strainer. Refer to paragraph 4.12.3. Pump the unit down (refer to paragraph 4.3.2). Remove
the bottom connection on the TXV. Remove the strainer
4.12.1 Replacing expansion valve and check for obstruction or damage. Clean or replace
strainer assembly and tighten connection at bottom of
a. Pump the unit down. Refer to paragraph 4.3.2. valve. Evacuate unit (refer to paragraphs 4.5.4).
b. Remove insulation from expansion valve bulb and
then remove bulb from suction line. 4.13 COMPRESSOR OIL TYPE
c. Loosen inlet nut and unbraze equalizer line and outlet The compressor(s) are supplied with CARRIER
line from expansion valve. POLYESTER (POE) oil. Ensure compressor is marked
with a factory sticker indicating the correct oil has been
d. The thermal bulb is located below the center of the installed. Oils of PAG type are strictly incompatible with
suction line. This area must be clean to ensure posi- the operation of this unit, never use an oil other than that
tive bulb contact. Strap thermal bulb to suction line approved by CARRIER.
and insulate both.
4.14 DIAGNOSTIC TOOL
e. Braze the equalizer tubes to expansion valve.
f. Evacuate, dehydrate and recharge unit.
g. Check superheat (refer to paragraph 1.5.2).
4.12.2 Measuring superheat
a. Remove insulation from expansion valve bulb and
suction line. See Figure 4-8
b. Loosen one TXV bulb clamp and make sure area un- REMOTE
der clamp (above TXV bulb) is clean. PRIMARY
TOOL
TOOL
c. Place thermocouple above (parallel to) the TXV bulb
and then secure loosened clamp making sure both
bulbs are firmly secured to suction line as shown in Figure 4-9 Cab Command/Cab Command Two
Figure 4-8 Diagnostic Tool
(CTD P/N 07--00440--00)
d. Connect an accurate gauge to the ¼” port on the suc- a. Testing a cab command cable that is already
tion service valve. installed on the unit and routed into the truck cab re-
e. Run unit until stabilized at --4_F (-20_C) box tempera- quires the use of both pieces of the diagnostic tool.
ture. b. Unplug the cab command cable from the micropro-
f. From the temperature/pressure chart (Table 4-6), de- cessor and also from the back of the cab command
termine the saturation temperature corresponding to module.
the evaporator outlet pressure. c. Plug one end of the cable into the primary tool and
the other end into the remote tool.
g. Note the temperature of the suction gas at the expan-
sion valve bulb. d. Begin the test by turning on the power switch and ob-
serving the sequence of green lights. As each circuit
h. Subtract the saturation temperature determined in is tested, the corresponding light is illuminated. If a
Step f. from the average temperature measured in fault is found in the cable, the light that corresponds
Step g.. The difference is the superheat of the suction to that particular circuit is not illuminated.
gas. Refer to paragraph 1.5.2 for superheat setting.
e. To test a cable that is not installed on a unit, simply
i. If required adjust superheat by turning the adjusting plug each end of the cable into the primary tool and
screw located under the cap on the side of the valve. perform the test as above.
62-11150 4-10
4.15 MICROPROCESSOR To check brushes proceed as follows :
a. With unit off and battery disconnected, remove brush
cap (item 1, Figure 4-10; 2 per motor).
Although there is less danger of electrical static
discharge (ESD) damage in the outdoor environment, b. Remove brushes (item 2; 2 per motor) and check the
where the processor is likely to be handled, proper length of the brush. If the length is less than 1/4 inch (6
board handling techniques should be stressed. Boards mm) the brushes should be replaced.
should always be handled by their edges, in much the c. Blow out the brush holder with low pressure air to re-
same way one would handle a photograph. This not only move any carbon dust in the holder. This dust could
precludes the possibility of ESD damage, but also prevent a good contact between the brushes and
lowers the possibility of physical damage to the commutator.
electronic components. Although the microprocessor d. Remove the back cover of the motor and inspect the
boards are fairly rugged when assembled, they are commutator. If the commutator is heavily grooved,
more fragile when separated and should always be polish it using fine sandpaper; do not use abrasive pa-
handled carefully. per. Wipe out any accumulation of greasy material us-
ing a clean rag dampened with solvent. Reassemble
When welding is required on the unit frame, or on the the motor; install new brushes and replace cap.
front area of the trailer, ALL wiring to the microprocessor
MUST be disconnected. When welding is performed on 4.17 EVAPORATOR COIL CLEANING
other areas of the truck and van, the welder ground The use of recycled cardboard cartons is increasing.
connection MUST be in close proximity to the area being The recycled cardboard cartons create much more fiber
welded. It is also a good practice to remove both battery dust during transport than ”new” cartons. The fiber dust
cables before welding on either the unit frame or the and particles are drawn into the evaporator where they
truck to prevent possible damage to other components lodge between the evaporator fins. If the coil is not
such as the alternator and voltage regulator. cleaned on a regular basis, sometimes as often as after
each trip, the accumulation can be great enough to
restrict air flow, cause coil icing, repetitive defrosts and
loss of unit capacity. Due to the ”washing” action of
4.16 CHECKING AND REPLACING CONDENSER normal defrost the fiber dust and particles may not be
FAN MOTOR BRUSHES visible on the face of the coil but may accumulate deep
within.
To maintain proper operation of the fan motors, the fan It is recommended to clean an the evaporator coil on a
motor brushes should be checked periodically for regular basis, not only to remove cardboard dust, but to
cleanliness and wear . remove any grease oil film which sometimes coats the
fins and prevents water from draining into the drain pan.
Cardboard fiber particles after being wetted and dried
several times can be very hard to remove. Therefore,
several washings may be necessary.
a. Spray coil with a mild detergent solution such as any
good commercial-grade automatic dish washer de-
tergent and let the solution stand for a few minutes.
Reverse flush (opposite normal air flow) with clean
water at mild pressure. A garden hose with spray
2 nozzle is usually sufficient. Make sure drain lines are
clean.
b. Run unit until defrost mode be initiated to check for
1 proper draining from drain pan.
4.18 CONDENSER COIL CLEANING
Remove all foreign material from the condenser coil by
reversing the normal air flow. (Air is pulled in through the
1. Brush Cap 2. Brush front.) Compressed air or water may be used as a
cleaning agent. It may be necessary to use warm water
mixed with any good commercial dishwasher detergent.
Figure 4-10 Fan motor brushes Rinse coil with fresh water if a detergent is used.
4-11 62-11150
Table 4-6. R-404a Temperature--Pressure Chart
62-11150 4-12
SECTION 5
TROUBLESHOOTING
WARNING
Beware of unannounced starting of the unit. The unit may cycle the fans and one of the operating com-
pressors unexpectedly as control requirements dictate. To ensure unit is without power, remove
power plug and remove battery negative cable.
CAUTION
Under no circumstances should anyone attempt to service the microprocessor (see section 4.15) or
either Cab Command module. Should a problem develop with the microprocessor, contact your near-
est Carrier Transicold dealer for replacement.
5.1 INTRODUCTION
Under normal circumstances, unit problems will be indicated by an active or inactive alarm in the alarm list. Suggested
troubleshooting actions for each alarm indication are provided in Table 5-1. Suggested corrective actions for
mechanical type problems are listed under subject headings in Table 5-2.
Table 5-1 Alarm Indications
5-1 62-11150
Table 5-1 Alarm Indications -- Continued
62-11150 5-2
Table 5-1 Alarm Indications -- Continued
5-3 62-11150
Table 5-2 Mechanical Indications
62-11150 5-4
Table 5-2 Mechanical Indications -- Continued
5-5 62-11150
Table 5-2 Mechanical Indications -- Continued
Low superheat and liquids lug- Superheat setting too low 4.12.2
ging in compressor External equalizer line plugged Repair
Pin and seat of expansion valve eroded or held open by 4.12
foreign material
Fluctuating suction pressure Improper bulb location or installation 4.12
Insulation missing from sensing bulb Replace
Low superheat setting 4.12.2
High superheat Expansion valve setting 4.12.2
5.4.2 Malfunction Hot Gas Solenoid or Condenser Pressure Regulating Valve
Valve does not function properly No power to valve Check
Improper wiring or loose connections Check
Valve improperly assembled 4.10
Coil or coil sleeve improperly assembled
Movement of plunger restricted due to:
a. Corroded or worn parts
b. Foreign material lodged in valve
c. Bent or dented enclosing tube
Valve shifts but refrigerant Foreign material lodged under seat 4.10
continues to flow Defective seat
5.4.3 Standby Compressor Malfunction
Standby compressor fails to start Motor contactor defective Replace
Motor Overload open Check
Improper power supply Correct
5–minute timer active Check
Standby compressor fails to start Defective start capacitor Check/Replace
1∅ Only Defective start relay Replace
Standby motor starts, then stops Motor Overload open Check
Standby motor starts, then stops Defective start capacitor Check/Replace
-- 1∅ Only Defective start relay Replace
62-11150 5-6
SECTION 6
SCHEMATIC DIAGRAMS
WARNING
Beware of unannounced starting of the unit. The unit may cycle the fans and one of the operating
compressors unexpectedly as control requirements dictate. To ensure unit is without power, re-
move power plug and remove battery negative cable.
CAUTION
Under no circumstances should anyone attempt to service the microprocessor (see section 4.15) or
either Cab Command Module. Should a problem develop with the microprocessor, contact your
nearest Carrier Transicold dealer for replacement.
6.1 INTRODUCTION
Schematic diagrams for the unit models listed in Table 1-1 are provided herein.
6-1 62-11150
LOCATION SYMBOL DESCRIPTION LOCATION IN UNIT
B--6 CC CAB COMMAND CAB
B--4 CFM CONDENSER FAN MOTOR CONDENSER
62--11150
B--11 CLHR CLUTCH ENGINE COMPARTMENT
J--7/L--7/M--7 EFM 1, 2 EVAPORATOR FAN MOTOR EVAPORATOR
L--6 EFMR RELAY FOR EFM EVAPORATOR
M--6 FEFM FUSE FOR EFM EVAPORATOR
B--10 FI IGNITION FUSE ENGINE COMPARTMENT
B--12 FR1 ROAD FUSE CONDENSER/BATTERY
B--5 HGS1 HOT GAS SOLENOID VALVE CONDENSER
B--2 HP1 HIGH PRESSURE SWITCH CONDENSER
B--3 HP2 CONDENSER PRESSURE SWITCH CONDENSER
B--9 BPT QUENCH THERMOSTAT ROAD COMPRESSOR
J--5 BPV QUENCH VALVE EVAPORATOR
J--2 LP LOW PRESSURE SWITCH EVAPORATOR
B--5 HGS2 CONDENSER PRESSURE CONTROL VALVE CONDENSER
F--2 MP MICROPROCESSOR BOARD CONDENSER
6-2
J--3 RAS RETURN AIR SENSOR EVAPORATOR
J--2 DTT DEFROST TERMINATION THERMOSTAT EVAPORATOR
F--12 MP FUSE MICROPROCESSOR BOARD FUSE CONDENSER
B--3 SKS SKIN SWITCH CONDENSER
Figure 6-1 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61397--00 Rev A
NOTES:
1. UNIT SHOWN IN “OFF” POSITION.
2. WIRE IDENTIFICATION SYSTEM:
COLOR: WHITE -- DC CONTROL CIRCUITS
GREEN -- DC GROUND CIRCUITS
RED -- POSITIVE BATTERY CIRCUITS
BLACK -- NEGATIVE BATTERY CIRCUITS
3. ADDRESS SYSTEM: EXAMPLE: MP43/C8--A
INDICATES A WIRE BETWEEN MICROPROCESSOR
MP (PIN43) AND PLUG C8 (PINA).
6-3
SWITCH SYMBOL INDICATES MOMENTARY CONTACTS
INDICATES A WIRE GROUND
BPT
INSULATING PLUG
COMPONENT CONNECTION NUMBER OR LETTER
SWITCH THERMAL PROTECTOR
1A
50A 25A
ROAD ONLY
62--11150
Figure 6-2 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61397 Rev A
NOTES:
1. UNIT SHOWN IN “OFF” POSITION.
INDICATES A SOLDERED SPLICE POINT SWITCH SYMBOL INDICATES MOMENTARY CONTACTS
2. WIRE IDENTIFICATION SYSTEM:
COLOR: WHITE -- DC CONTROL CIRCUITS PIN CONNECTION INDICATES A WIRE GROUND
GREEN -- DC GROUND CIRCUITS LIGHT LINES INDICATE WIRES IN THE SYSTEM INDICATES A CHASSIS GROUND
RED -- POSITIVE BATTERY CIRCUITS NORMALLY CLOSED CONTACTS INDICATES OPTIONS
BLACK -- NEGATIVE BATTERY CIRCUITS INDICATES A CONNECTION, WIRE, LUG, ETC.
NORMALLY OPEN CONTACTS
3. ADDRESS SYSTEM: EXAMPLE: MP43/C8--A INSULATING PLUG
INDICATES A WIRE BETWEEN MICROPROCESSOR MULTIPLE PLUG CONNECTION NUMBER COMPONENT CONNECTION NUMBER OR LETTER
MP (PIN43) AND PLUG C8 (PINA). JUNCTION BLOCK CONNECTION SWITCH THERMAL PROTECTOR
LOCATION SYMBOL DESCRIPTION LOCATION IN UNIT LOCATION SYMBOL DESCRIPTION LOCATION IN UNIT
C--11 AR ALARM RELAY (OPTION) EXTERNAL B--4 HP2 COND. PRESSURE CONTROL SWITCH CONDENSER
B--12 BPT QUENCH THERMOSTAT ROAD COMPR. B--5 HGS1 HOT GAS SOLENOID VALVE CONDENSER
J--5 BPV QUENCH VALVE EVAPORATOR B--5 HGS2 COND. PRESSURE CONTROL VALVE CONDENSER
B--6 CC CAB COMMAND CAB J--2 LP LOW PRESSURE SWITCH EVAPORATOR
M--13 C1 SMOOTHING CAPACITOR STANDBY BOX J--12/N--7 MC MOTOR CONTACTOR STANDBY BOX
B--4 CFM CONDENSER FAN MOTOR CONDENSER F--2 MP MICROPROCESSOR BOARD CONDENSER
6-4
B--11 CLHR ROAD CLUTCH ENGINE COMP. O--7, J--12 OL OVERLOAD RELAY CONDENSER
L--11 CLHS STANDBY CLUTCH CONDENSER
P--9 CP PERMANENT CAPACITOR STANDBY BOX Q--4 PSR POWER SUPPLY RECEPTACLE EXTERNAL
K--12/M--13 CR CLUTCH RELAY STANDBY BOX L--13 R DISCHARGE RESISTOR STANDBY BOX
0--9 CS1 START CAPACITOR STANDBY BOX J--3 RAS RETURN AIR SENSOR EVAPORATOR
K--13 CT CLUTCH TIMER STANDBY BOX N--13 RB RECTIFIER BRIDGE CONDENSER
L--13 D DIODE STANDBY BOX R--7 SBM STANDBY MOTOR CONDENSER
B--12 DS1 DOOR SWITCH (OPTION) EXTERNAL Q--10 STR START RELAY STANDBY BOX
J--2 DTT1 DEFROST KLIXON EVAPORATOR Q--13 TR TRANSFORMER CONDENSER
J--5 DWR1 DRAIN WATER RESISTOR (OPTION) EVAPORATOR C--9 SKS SKIN SWITCH CONDENSER
J--7,J--8 EFM1,2 EVAPORATOR FAN MOTOR EVAPORATOR
R--10 F1 PRIMARY TRANSFORMER FUSE STANDBY BOX
O--4 FB FUSE BLOCK STANDBY BOX
M--12 FC STANDBY CLUTCH FUSE STANDBY BOX
B--10 FI IGNITION FUSE ENGINE COMP.
C--13 FR, FR1 ROAD FUSE CONDENSER/BATT.
I--13 FS STANDBY FUSE CONDENSER
62--11150
B--3 HP1 HIGH PRESSURE SWITCH CONDENSER
25A
1.5KW
6-5
1A
6.3AT
5A
30A
50A 40A
430VA
115V/1/60Hz
62--11150
Figure 6-3 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61459 Rev --
NOTES:
1. UNIT SHOWN IN “OFF” POSITION. INDICATES A SOLDERED SPLICE POINT SWITCH SYMBOL INDICATES MOMENTARY CONTACTS
2. WIRE IDENTIFICATION SYSTEM: PIN CONNECTION INDICATES A WIRE GROUND
COLOR: WHITE -- DC CONTROL CIRCUITS LIGHT LINES INDICATE WIRES IN THE SYSTEM INDICATES A CHASSIS GROUND
GREEN -- DC GROUND CIRCUITS NORMALLY CLOSED CONTACTS INDICATES OPTIONS
RED -- POSITIVE BATTERY CIRCUITS INDICATES A CONNECTION, WIRE, LUG, ETC.
NORMALLY OPEN CONTACTS
BLACK -- NEGATIVE BATTERY CIRCUITS INSULATING PLUG
3. ADDRESS SYSTEM: EXAMPLE: MP43/C8--A MULTIPLE PLUG CONNECTION NUMBER COMPONENT CONNECTION NUMBER OR LETTER
INDICATES A WIRE BETWEEN MICROPROCESSOR
JUNCTION BLOCK CONNECTION SWITCH THERMAL PROTECTOR
MP (PIN43) AND PLUG C8 (PINA).
LOCATION SYMBOL DESCRIPTION LOCATION IN UNIT LOCATION SYMBOL DESCRIPTION LOCATION IN UNIT
C--11 AR ALARM RELAY (OPTION) EXTERNAL J--12/N--7 MC MOTOR CONTACTOR STANDBY BOX
B--12 BPT QUENCH THERMOSTAT ROAD COMPR. F--2 MP MICROPROCESSOR BOARD CONDENSER
J--5 BPV QUENCH VALVE EVAPORATOR O--7, J--12 OL OVERLOAD RELAY STANDBY BOX
B--6 CC CAB COMMAND TWO CAB P--2, P--4 PSR POWER SUPPLY RECEPTACLE EXTERNAL
M--13 C1 SMOOTHING CAPACITOR STANDBY BOX L--13 R DISCHARGE RESISTOR STANDBY BOX
B--4 CFM CONDENSER FAN MOTOR CONDENSER J--3 RAS RETURN AIR SENSOR EVAPORATOR
Q--9,Q--10 C230 COUPLING CONNECTOR STANDBY BOX N--13 RB RECTIFIER BRIDGE CONDENSER
C400
6-6
B--11 CLHR ROAD CLUTCH ENGINE COMP. R--7 SBM STANDBY COMPRESSOR MOTOR CONDENSER
J--2 DTT DEFROST TERMINATION THERMOSTAT EVAPORATOR Q--13 TR TRANSFORMER CONDENSER
L--13 D DIODE STANDBY BOX F--13 MP FUSE MICROPROCESSOR BOARD FUSE CONDENSER
B--12 DS1 DOOR SWITCH (OPTION) EXTERNAL C--9 SKS SKIN SWITCH CONDENSER
J--5 DWR1 DRAIN WATER RESISTOR (OPTION) EVAPORATOR
J--7,J--8 EFM1,2 EVAPORATOR FAN MOTOR EVAPORATOR
R--10, S--10 F1, 2 PRIMARY TRANSFORMER FUSE STANDBY BOX
O--4 FB FUSE BLOCK STANDBY BOX
M--12 FC CLUTCH FUSE STANDBY BOX
B--10 FI IGNITION FUSE ENGINE COMP.
C--13 FR, FR1 ROAD FUSE CONDENSER/BATT.
I--13 FS STANDBY FUSE CONDENSER
C--1 FSBP SUCTION BYPASS FUSE EVAPORATOR
B--3 HP1 HIGH PRESSURE SWITCH CONDENSER
B--4 HP2 COND. PRESSURE CONTROL SWITCH CONDENSER
B--5 HGS1 HOT GAS SOLENOID VALVE CONDENSER
B--5 HGS2 CONDENSER PRESSURE CONTROL VALVE CONDENSER
62--11150
J--2 LP LOW PRESSURE SWITCH CONDENSER
10A
1.5KW
6-7
3.7A
6.5A
F2
4AT
3.15AT
1A
5A
62--11150
Figure 6-4 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61345 Rev C
NOTES:
1. UNIT SHOWN IN “OFF” POSITION. INDICATES A SOLDERED SPLICE POINT SWITCH SYMBOL INDICATES MOMENTARY CONTACTS
2. WIRE IDENTIFICATION SYSTEM: PIN CONNECTION INDICATES A WIRE GROUND
COLOR: WHITE -- DC CONTROL CIRCUITS LIGHT LINES INDICATE WIRES IN THE SYSTEM INDICATES A CHASSIS GROUND
GREEN -- DC GROUND CIRCUITS NORMALLY CLOSED CONTACTS INDICATES OPTIONS
RED -- POSITIVE BATTERY CIRCUITS INDICATES A CONNECTION, WIRE, LUG, ETC.
BLACK -- NEGATIVE BATTERY CIRCUITS NORMALLY OPEN CONTACTS
INSULATING PLUG
3. ADDRESS SYSTEM: EXAMPLE: MP43/C8--A MULTIPLE PLUG CONNECTION NUMBER COMPONENT CONNECTION NUMBER OR LETTER
INDICATES A WIRE BETWEEN MICROPROCESSOR
JUNCTION BLOCK CONNECTION SWITCH THERMAL PROTECTOR
MP (PIN43) AND PLUG C8 (PINA).
LOCATION SYMBOL DESCRIPTION LOCATION IN UNIT LOCATION SYMBOL DESCRIPTION LOCATION IN UNIT
C--11 AR ALARM RELAY (OPTION) EXTERNAL B--4 HP2 COND. PRESSURE CONTROL SWITCH CONDENSER
B--12 BPT QUENCH THERMOSTAT ROAD COMPR. B--5 HGS1 HOT GAS SOLENOID VALVE CONDENSER
J--5 BPV QUENCH VALVE EVAPORATOR B--5 HGS2 CONDENSER PRESSURE CONTROL CONDENSER
VALVE
B--6 CC CAB COMMAND TWO CAB J--2 LP LOW PRESSURE SWITCH CONDENSER
M--13 C1 SMOOTHING CAPACITOR STANDBY BOX J--12/N--7 MC MOTOR CONTACTOR STANDBY BOX
B--4 CFM CONDENSER FAN MOTOR CONDENSER F--2 MP MICROPROCESSOR BOARD CONDENSER
B--11 CLHR ROAD CLUTCH ENGINE COMP. O--7, J--12 OL OVERLOAD RELAY STANDBY BOX
6-8
L--11 CLHS STANDBY CLUTCH CONDENSER P--2, P--4 PSR POWER SUPPLY RECEPTACLE EXTERNAL
P--9 CP PERMANENT CAPACITOR STANDBY BOX L--13 R DISCHARGE RESISTOR STANDBY BOX
K--12/M--13 CR CLUTCH RELAY STANDBY BOX J--3 RAS RETURN AIR SENSOR EVAPORATOR
O--9 CS STARTING CAPACITOR STANDBY BOX N--13 RB RECTIFIER BRIDGE CONDENSER
K--13 CT CLUTCH TIMER STANDBY BOX R--7 SBM STANDBY COMPRESSOR MOTOR CONDENSER
J--2 DTT DEFROST TERMINATION THERMOSTAT EVAPORATOR Q--10 STR STARTING RELAY STANDBY BOX
L--13 D DIODE STANDBY BOX Q--13 TR TRANSFORMER CONDENSER
B--12 DS1 DOOR SWITCH (OPTION) EXTERNAL F--13 MP FUSE MICROPROCESSOR BOARD FUSE CONDENSER
J--5 DWR1 DRAIN WATER RESISTOR (OPTION) EVAPORATOR C--9 SKS SKIN SWITCH CONDENSER
J--7,J--8 EFM1,2 EVAPORATOR FAN MOTOR EVAPORATOR
R--10 F1 PRIMARY TRANSFORMER FUSE STANDBY BOX
O--4 FB FUSE BLOCK STANDBY BOX
M--12 FC CLUTCH FUSE STANDBY BOX
B--10 FI IGNITION FUSE ENGINE COMP.
C--13 FR, FR1 ROAD FUSE CONDENSER/BATT.
I--13 FS STANDBY FUSE CONDENSER
C--1 FSBP SUCTION BYPASS FUSE EVAPORATOR
62--11150
B--3 HP1 HIGH PRESSURE SWITCH CONDENSER
12A
1.5KW
6-9
1A
4AT
5A
430VA
230V/1/60Hz
62--11150
Figure 6-5 Electrical Schematic Wiring Diagram - Based On Dwg. No. 62-61347 Rev C
INDEX
A D
Defrost, 2-6
Abnormal Noise, 5-5
Defrost Cycle, 3-2
Abnormal Pressure, 5-5
Defrost Malfunction, 5-4
Accessing Alarm Messages, 2-6 Defrost Termination Thermostat, 1-6
Alarm Display, 2-6 Defrost Timer, 1-6
Alarm Indications, 5-1 Description, 1-1
Diagnostic Tool, 4-10
Alarm Messages, 2-7
Display, 2-1, 2-2
C E
Electrical Data, 1-7
Cab Command, 2-1
Evacuation And Dehydration, 4-4
Cab Command Malfunction, 5-5 Evaporator, 1-5
Charging The Refrigeration System, 4-6 Evaporator Coil Cleaning, 4-11
Checking The Eeprom Version, 2-8 Evaporator Fan Motor, 1-7
Expansion Valve, 5-6
Clearing Past Alarm Messages, 2-8
Compressor, 1-6
Compressor, 1-5
F
Filter Drier, 1-1
Compressor Pressure Regulating Valve, 4-9
Filter--drier, 4-8
Compressor Pressure Regulating Valve (Cpr) 1-6
Frozen Mode, 3-1
Compressor Pressure Regulating Valve (Cpr), 1-5
Condenser Coil Cleaning, 4-11
H
Condenser Fan Motor, 1-7
Heating Mode, 3-1
Condenser Fan Motor Brushes, 4-11 High Pressure Safety Switch, 1-5
Condenser Pressure Control Solenoid , 4-9 High Pressure Switch , 4-8
Condenser Pressure Control Valve , 1-5 High Pressure Switch (Hp1), 1-6
Hot Gas Solenoid, 4-9
Condenser Pressure Switch, 4-8
Hot Gas Valve, 1-7
Condenser Pressure Switch, 1-5
Hot Gas Valve 1, 1-1
Condenser Pressure Switch (Hp2), 1-6
Condenser/Subcooler, 1-1
I
Connect Power, 2-5
Inspection, 2-4
Control System, 2-1 Insufficient Cooling, 5-4
Cooling Mode, 3-1 Introduction, 1-1, 5-1, 6-1
Index-1 62--11150
INDEX
O
Operation, 2-1
T
Temperature Control, 3-1
Temperature--pressure Chart , 4-12
P Thermal Expansion Valve, 1-5
Preventative Maintenance, 4-1 Thermostatic Expansion Valve, 4-10
Pumping Down, 4-2 Thermostatic Expansion Valve, 1-6
Pumping The Unit Down, 4-3 Torque Values, 1-7
Pumping The Unit Down, 4-3 Troubleshooting, 5-1
Txv Orifice Strainer, 4-10
Q
Quench Valve, 1-5, 1-7 U
Unit Data And Function Modification Keys, 2-2
62--11150 Index-2
North America Central America
Carrier Transicold and Mexico
700 Olympic Drive Ejercito Nacional No. 418 Carrier Transicold Division,
Athens, GA 30601 USA Piso 9, Torre Yumal Carrier Corporation
Tel: 1--706--357--7223 Col. Chapultepec Morales Truck/Trailer Products Group
Fax: 1--706--355--5435 11570 Mexico, D.F. P.O. Box 4805
Tel: (5255) 9126.0300 Syracuse, N.Y. 13221 U.S A
Fax: (5255) 9126.0373
www.carrier.transicold.com