Professional Documents
Culture Documents
During the trip some failures can occur impacting the performance on temperature control.
Many times we experienced the most common words from the drivers: “no cooling”
“no cooling” can be related to certain number of conditions, not only no refrigerant or
something related to the refrigeration circuit.
For example:
If the unit is running and the diesel runs out, the unit will stop and the driver will call and
report “no cooling”
Refrigeration
Engine shut down
Starting
Nylon gear
Operator issue
Battery
RPM
Temperature
A41- Engine Stalled
NO PROPER IssuesVACUUM A31 – Failed to start
Auto - mode
THE BIGGEST MISTAKE OF THE REFRIGERATION
“no cooling”
TECHNICIAN
A30 – Fail to Run 1,5 A13 – High Discharge
minimum time
HOUR pressure
3 HOURS
A38 / A39 – Check A51 – Alternator not
engine RPM charging
A28 – Check
refrigeration System
Evacuation
• A/C & Refrigeration systems are designed to operate with only oil and
refrigerant flowing through them.
When a refrigeration system is installed and/or serviced, air and moisture
enter the system.
• Oxygen, nitrogen and moisture (all make up our air or atmosphere) are detrimental
to system operation.
Degassing:
Dehydration:
• Moisture brakes down POE oil in HFC systems, (like R404a) causing premature
failure of the oil.
• Because POE breaks down into its fundamental components, it loses the
lubrication properties leading to compressor failures and it can clog the
metering device and contaminate line sets.
• Moisture refrigerant and mineral oils form acids that will cause system failure
due to copper plating and damage to compressor windings.
Vacuum gauge:
When moisture (humidity) enters a system or condenses, the only way it can be
removed is in vapor state.
• Internal restrictions
• External restrictions
• No it is not, because water trapped in the circuit is also at 5°C and in liquid
form!
Decreasing the pressure to quickly raises the freezing point of water creating
a phenomenon called deposition.
Meaning, water will turn to ice before evaporation is complete.
In the same way that computers, mobile phones, etc. operate with a software,
also the cooling units with microprocessor need software, and Software requires
updates.
Whenever there is a software update, means that something better is coming to
optimize the unit.
Updates may be related to: APX ADVANCE
• Valve control logic
• Fuel consumption
• Cooling performance
• Correct errors
Tru-Tech &
& Tru-View
Tru-View
22-60891-01
12-00534-00 12-00503-00 22-04253-00 (1,8 meter)
(Program/Configuration card) (Download card) 22-04253-01 (6,1 meters)
VECTOR CSMV
VECTOR AND X4 EVXV
P/N: 07-00375-00SV
X4 CSMV
STEPPER VALVE TESTER
07-00525-00 07-00524-00
07-00526-00
• TRIGGER–ON:
Compressor discharge pressure is over 465 PSIG (32 Bars)
• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.
• RESET CONDITION:
Auto Reset after 15 minutes if the compressor discharge pressure falls below 350 PSIG
(23.8 Bars), or alarm may be manually reset via keypad or by turning the unit off,
then back on again.
ELECTRICAL CIRCUIT
• TRIGGER–ON:
AC Current Sensor 1 is greater than 40A or AC Current Sensor 2 is greater than 40A for 3
seconds
• UNIT CONTROL:
Engine operation: alarm will not activate.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.
• RESET CONDITION:
Auto reset after 15 minutes if the AC current sensor readings are less than 38 amps or
alarm may be manually reset via keypad or by turning unit off then back on.
2. CHECK POWER SOURCE VOLTAGE (IF USED WHEN ALARM OCCURRED) PSCON
a. Check voltage at PSCON L1-L2, L1-L3, L2-L3 PSCON2
Should be 440 to 580 VAC
GENCON
NOTE: If there is a “0” amperage reading while testing, check the fuses for the concerned component
AGM stands for Absorbent Glass M at, which is a material that holds acid in place like a sponge.
Specifically, they're made with Spiralcell® Technology - an advanced form of AGM technology
Advantages:
Dual function battery : starting and deep cycling
Comparison:
Cranking performance
Vibration resistance
Charging acceptance
Self discharge
Gassing
Acid stratification
Internal resistance
Note:
AGM battery resists to high temperatures, that’s why is so important that all Vector units are equipped with this
battery, specially in Middle East.
Usage of a regular flooded battery will lead to, premature failure of the battery charger, Start/Stop failure during
regulation period increasing fuel consumption, and a short life time of the battery.
• TRIGGER–ON:
Voltage at the microprocessor is less than 10 VDC
(except when the engine starter is engaged)
• UNIT CONTROL:
Unit Shutdown & Alarm.
Alarm condition only if activated while starting unit.
• RESET CONDITION:
Auto Reset after 15 minutes when the voltage at the microprocessor is between
11 - 14 VDC, or alarm may be manually reset via keypad or by turning the unit off,
then back on again.
BATTERY CHARGER
NOTE 2: Many electrical circuits may be tested by leaving all compartment switches in the “O” (OFF) position and turning the RS to the
START/RUN position. At least one compartment must be in the “1” (ON) position. In this mode, RCR will be energized and the main
display will show “OFF”.
Before troubleshooting
the manifold gauges must be connected to the refrigeration system
• TRIGGER–ON (A):
Both UL1 and UL2 are energized AND unit is in engine mode AND in low speed AND
compressor is running AND low suction pressure shutdown delay in configurations has
elapsed since energizing UL1 AND Suction Pressure is less than 0.3 Bar
• UNIT CONTROL:
Engine operation: alarm only or (if configured for shutdown) engine and unit shutdown
and alarm.
Standby operation: alarm only or (if configured for shutdown) refrigeration system
shutdown and alarm with PSCON still energized.
• RESET CONDITION:
If alarm only: auto reset when either UL1 or UL2 is de-energized.
If unit and system shut down and alarm: auto reset after 15 minutes.
Alarm may be manually reset via keypad or by turning the unit OFF, then ON again.
NOTE: Microprocessor suction pressure reading has a maximum value of 100 psig (6.9 bar)
6. CHECK CSMV
a. Check compressor suction modulation valve
b. Check airflow (with unit running).
Even airflow through the entire coil No “dead” spots
UNLOADER REAR CSMV
7. EVAPORATOR SECTION
a. Check evaporator section, return air bulkhead, air chute, cleanliness of evap. coil
Good Air Flow, Return air not restricted, Air chute in good condition,
No damage to blower wheel, Evap. coil clean, Evap. fan rotation ok
• TRIGGER ON:
The refrigeration system is running and the discharge pressure is less than 5 PSIG
(0.34 Bar) higher than suction pressure for more than 10 minutes
• UNIT CONTROL:
Engine operation: alarm only or (if configured for shutdown) engine and unit
shutdown and alarm.
Standby operation: alarm only or (if configured for shutdown) refrigeration system
shutdown and alarm with PSCON still energized.
• RESET CONDITION:
Auto reset when discharge pressure is more than 20 PSIG (1.36 Bars) above
the suction pressure when in alarm only, or auto reset after 15 minutes when shutdown is
configured or alarm may be manually reset via keypad or by turning the unit off, then back
on again.
4. CHECK COMPRESSOR.
a. Perform Pump-Down Test. (Never on Vector 1550)
Must pump down to 5 PSI and hold for minimum of 1 minute.
b. Cover condenser and build-up discharge pressure.
Must be able to pump up to 400 PSI.
c. Disassemble and inspect compressor valve plates, reeds, pistons, etc.
Must be intact, clean, and in good working order.
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A30 Vector – Fail to Run minimum time
• TRIGGER–ON:
Engine has shut down on an alarm 3 times without having run for at least 15
minutes between each shutdown (not including Door or Remote Switch shut downs) AND
unit is in automatic start mode.
• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.
• RESET CONDITION:
Alarm may be manually reset via keypad or by turning the unit off, then back on again.
• TRIGGER–ON:
In engine mode, engine has tried to start 3 times unsuccessfully in the auto start mode.
• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: this alarm will not activate in standby operation.
• RESET CONDITION:
Change unit to standby operation or alarm may be manually reset via keypad or by turning
the unit off, then back on again.
INLET STRAINER
8. CHECK ENGINE
a. Check engine compression
9. CHECK RPM SENSOR RPM Sensor
a. Check sensor
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A35 Vector – Check Starter Circuit
• TRIGGER–ON:
Engine speed fails to reach 50 RPM during 2 start attempts.
• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: this alarm will not activate in standby operation.
• RESET CONDITION:
Change unit to standby operation or alarm may be manually reset via keypad or
by turning the unit off, then back on again.
3. CHECK STARTER
a. Inspect starter and wiring.
No damage or corrosion,
Wiring and battery cable must be clean and tight
b. Check resistance of starter motor
(Less than 1 ohm but more than 0)
c. Check amperage draw of starter STARTER
(270 – 380 amps)
• TRIGGER–ON:
Controller is set for high engine speed operation, and engine RPM are:
Less than 1650, or greater than 2075 for more than 60 seconds (120 seconds if micro calls
for a change from low speed to high speed, or when unit starts).
• UNIT CONTROL:
Engine operation: alarm only.
Standby operation: this alarm will not activate in standby operation.
• RESET CONDITION:
Auto Reset if controller is set for high speed operation and RPM is between 1670 and
2050 for 60 seconds or change unit to standby operation or alarm may be manually reset
via keypad or by turning the unit off, then back on again.
• TRIGGER–ON:
Multi-temp: In engine mode and Alarm 130 (RPM SENSOR) is not active and engine rpm is
less than 1250 or greater than 2000 for 5 minutes or engine rpm drops to less than 1200
for 5 seconds after the engine rpm has been greater than 1250 for 3 seconds.
• UNIT CONTROL:
Engine operation: alarm only or (if configured for shutdown) engine and unit shutdown and
alarm.
Standby operation: this alarm will not activate in standby operation.
• RESET CONDITION:
Auto Reset if engine rpm is greater than 1250 and less than 2000 for 5 minutes or after 15
minutes if the engine has been shutdown or change unit to standby operation or alarm
may be manually reset via keypad or by turning the unit off, then back on again.
ENGINE STALLED
• TRIGGER–ON:
In engine mode, the engine is running, RPM sensor is good, and engine speed is less than
10 RPM; or the engine is running, RPM sensor alarm is ON, and the Oil Pressure switch
contacts are open.
• UNIT CONTROL:
Unit shutdown in electric.
Alarm only in standby.
• RESET CONDITION:
Auto Reset after 15 minutes, or alarm may be manually reset via keypad or by turning the
unit off, then back on again.
INLET STRAINER
• TRIGGER–ON:
Unit is running on either engine or standby and the current flow is more than
-1.0 amps (discharge) between the battery charger and the battery for 3 continuous
minutes.
• UNIT CONTROL:
Engine operation: alarm only or (if configured for shutdown)engine and unit shutdown and
alarm.
Standby operation: alarm only.
• RESET CONDITION:
Auto Reset (if not shut down) when alternator is charging if not shutdown or change unit to
standby operation or alarm may be manually reset via keypad or by turning the unit off,
then back on again.
IMPORTANT: Single phase battery charger 20 Amps its not interchangeable with the 3 Phase
battery Charger 40 Amps.
Note:
Always when mounting a new charger check the configuration, if it is configured to
“No temp. sensor, 1ph/20Amps or 3ph/ 40Amps”
If the right Battery cCharger is not selected it will interfere with the Start-Stop functioning
causing more fuel consumption
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 Vector – Alternator not charging
1. CHECK FUSES FOR BATTERY CHARGER
a. Check fuses (old units 2 fuses , new units 3 fuses)
Previous Layout
Current Sensor
• UNIT CONTROL:
Engine and standby operation:
If the micro is configured for shutdown and the setpoint for Compartment 2 is in the
perishable range - unit shutdown and alarm.
If the micro is configured for shutdown and the setpoint for Compartment 2 is in the frozen
range, only Compartment 2 will shut off. Otherwise, alarm only.
• RESET CONDITION:
Auto Reset or Alarm may be manually reset via Keypad or by turning the unit off, then back
on again..
2. DEFROST EVAPORATOR
a. Initiate Manual Defrost Cycle
Must terminate automatically.
7. CHECK EMPTY PALLETS OR CRATES, CAUSING A53 AND ALSO HIGH FUEL CONSUPTION
a. Remove empty pallets and Crates
• TRIGGER–ON:
The real time clock in the Data Recorder does not contain a valid date.
• UNIT CONTROL:
Engine and standby operation: alarm only.
• RESET CONDITION:
Auto Reset when the Data Recorder Real Time Clock is reset, or alarm may be manually
reset by turning the unit off, then back on again.
NOTE:
Datalogger date and time must be always correct.
In case quality department ask for a download of a specific date, if the date and time are incorrect it will be very
difficult to track the required data.
2. RESET MICROPROCESSOR
a. Turn main switch off for 30 seconds, then turn on.
Microprocessor powers up OK
b. Check for valid Real Time Clock reading in Data Menu
Valid date and time in memory.
Alarm is cleared automatically
c. Real Time Clock can not be changed.
Replace microprocessor
3. MICROPROCESSOR DEFECTIVE
a. Download previous data using Download PC Card, or Tru-Tech.
Data retrieval OK
b. Replace microprocessor & set Configurations, Functional Parameters, Enter hours from
removed microprocessor, set Maintenance Hour Meters, and Data Recorder Setup.
New microprocessor in place
• TRIGGER–ON:
Compressor Motor Overheated (IPC) circuit is open.
• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.
• RESET CONDITION:
Auto Reset when motor overload input is within limits, or change to engine
operation, or alarm may be manually reset via keypad or by turning the unit off, then back
on again.
OGF
• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.
• RESET CONDITION:
Auto Reset in engine mode.
Alarm may be manually reset via Keypad or, alarm may be reset by turning the unit off,
then back on again.
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A100 Vector – Overload Ground Fault
OGF
• TRIGGER–ON:
If the compressor is on and AC Current Sensor 1 or 2 is less than 5 amps for 10 seconds OR
If the difference between AC Current 1 and AC Current 2 is greater than 10 amps for 10
seconds
• UNIT CONTROL:
Engine and standby operation: alarm only.
• RESET CONDITION:
Change unit to standby operation when AC Current Sensor 1 and 2 is greater
than 7 amps for 5 minutes AND difference between AC Current 1 and AC Current 2 is less
than 7 amps for 5 minutes OR alarm may be manually reset via keypad or by turning the
unit off, then back on again.
NOTE:
This alarm is activated usually when a contactor is not energized or is energized but the Fuse on AC 1 or
AC 2 are blown.
CURRENT TRANSFORMER
NOTE: A faulty Current Transformer will also activate the alarm 128
• TRIGGER ON:
"Check Suction Temperature Sensor" and/or "Check Evaporator Temperature Sensor"
alarms are not active (refer to alarm 127 and/or 131 first) and:
Compressor suction superheat (Compressor Suction Temperature (CST) minus saturated
temperature for Compressor Suction Pressure (CSP) is less than 5°C for more than 2
minutes.
• UNIT CONTROL:
Engine operation: Shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.
• RESET CONDITION:
Auto reset after 15 minutes, or alarm may be manually reset via keypad or by turning the
unit off, then back on again.
NOTE:
Microprocessor suction (CSP) and evaporator (EVOP) pressure readings have a maximum value of 7.5 bar (100 psig)
The actual suction pressure must be lower than 100 psig in order to perform this test.
4. CHECK EVXV
a. Check operation of EVXV
• TRIGGER ON:
If the compressor compression ratio is greater than 21:1 for 20 seconds.
• UNIT CONTROL:
Engine operation: Engine and unit shutdown and alarm.
Standby operation: Refrigeration system shutdown and alarm with PSCON still energized.
• RESET CONDITION:
Auto reset when compression ratio is less than 21 for 3 minutes or, alarm may be manually
reset via keypad or by turning the unit off, then back on again.
NOTE:
A24 is a shut down alarm that will shut compressor down in the event the compression ratio has been higher than
>21:1 for 20 seconds.
If compression ratio >= 21:1 engage bypass mode (de-energize economizer solenoid valve (ESV) and energize
unloader bypass valve (USV).
This override will be active until the compression ratio is <= 19:1
Control Changes: Unit will switch from Economized to Bypass to reduce CR.
• TRIGGER ON:
The compressor is running and the suction pressure has been greater than 6.7 bar (98 psig)
for more than 10 minutes.
• UNIT CONTROL:
Engine operation: alarm only or (if configured for shut down) engine and unit shutdown
and alarm.
Standby operation: alarm only or (if configured for shutdown) refrigeration system
shutdown and alarm with PSCON still energized.
• RESET CONDITION:
Auto reset when suction pressure is less than 75 psig (5.1 bar) for 5 minutes and
configured for Alarm Only in standby operation or Auto Reset after 30 minutes if in engine
operation if configured as a Shutdown Alarm or, alarm may be manually reset via keypad or
by turning the unit off, then back on again.
NOTE:
Microprocessor suction (CSP) and evaporator (EVOP) pressure readings have a maximum value of 7.5 bar (100 psig).
The actual suction pressure must be lower in order to perform this test.
6. CHECK COMPRESSOR
a. Check compressor for excessive vibration or noise
Replace compressor
• TRIGGER ON:
The refrigeration system is running and the discharge pressure is less than 0.34 bar (5 psig)
higher than suction pressure for more than 30 seconds.
• UNIT CONTROL:
Engine operation: alarm only or (if configured for shutdown) engine and unit shutdown and
alarm.
Standby operation: alarm only or (if configured for shutdown) refrigeration system
shutdown and alarm with PSCON still energized.
• RESET CONDITION:
Auto reset when discharge pressure is more than 1.36 bar (20 psig) above the suction
pressure when in alarm only, or auto reset after 30 minutes when shutdown is configured
or alarm may be manually reset via keypad or by turning the unit off, then back on again.
NOTE:
Microprocessor suction (CSP) and evaporator (EVOP) pressure readings have a maximum value of 100 psig (7.5 bar)
The actual suction pressure must be lower than 100 psig in order to per-form this test.
4. CHECK COMPRESSOR
a. Check compressor for excessive vibration or noise
Replace compressor
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A75 Vector 1550 – Compressor Motor Overload
• TRIGGER-ON:
If alarm A22, A27 and/or A28 was triggered with current below 5.5 amps, this alarm will
also trigger or on restart from alarm A22, A27 and/or A28 trigger on if compressor current
does not rise above 1 amp.
• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.
NOTE:
The compressor motor is fitted with an internal line break that may have caused this alarm.
The line break is an auto reset device. Additional time may be required to reduce winding temperature to the reset
temperature of this device.
• RESET CONDITION:
Auto reset after 30 minutes alarm may be manually reset via keypad or by turning the unit
off, then back on again.
MMM
PCM
SVM DM
1. Using a spark plug gap wire gauge set the tolerances of the coupling can be measured (image 1)
2. Insert the spark plug gap wire gauge between the Nylon coupling and the steel gear (Image 2)
You may have to slightly move the engine flywheel to ensure the steel drive teeth are to one side of the Nylon coupling
If you can insert a 0.030” (0.762mm) or larger gauge thickness in to the gap between the nylon coupling and the steel gear,
This procedure can be carried out with the coupling still installed to the unit (Image3).
If any work on the unit is needed and the compressor has to be removed the procedure can be carried out as in (Image 2)
BLACK DOT
• ACTIVATION:
Compressor discharge pressure switch (HPS) contacts are open.
HPS contacts open when the discharge pressure rises to 465 psig (32 bar).
• UNIT CONTROL:
Shutdown and alarm.
• RESET CONDITION:
Auto reset after 15 minutes if the compressor discharge pressure falls below 350 psig
(24 bar), or alarm may be manually reset using the display mounted keys or by turning the
unit off, then back on again.
CDT
4. CHECK REFRIGERANT CHARGE HIGH PRESSURE SWITCH
6,8 Kg R404a CDP
Must be correct.
7. PERFORM PRE-TRIP
a. Run Pre-trip and check for alarms.
Any active alarms must be corrected and cleared before proceeding.
• ACTIVATION:
Voltage at the main microprocessor is less than 10 VDC
(except when the engine starter is engaged).
• UNIT CONTROL:
Shutdown and alarm. Alarm condition only if activated while starting unit.
• RESET CONDITION:
Auto reset after 15 minutes when the voltage at the main microprocessor is
between 11 - 14 VDC, or alarm may be manually reset using the display mounted keys or
by turning the unit off, then back on again.
GROUND CONNECTIONS
• ACTIVATION:
The compressor is operating with the suction pressure less than -3 psig (-0.20 bar) for
more than the LP SHUTDOWN DELAY Configuration (up to 5 minutes) with RAT above
-23.3°C or less than -8 psig (-0.53 bar) with RAT at any temperature.
• UNIT CONTROL:
Alarm only or (if configured for shutdown) shutdown and alarm.
• RESET CONDITION:
Auto reset after 15 minutes if suction pressure is more than -2 psig (-0.13bar) or alarm
may be manually reset using the display mounted keys or by turning the unit OFF,
then ON again.
• UNIT CONTROL:
Condition 1 = If the DTT and/or SAT temperatures are cool enough to allow a defrost the
unit will go into defrost. Following the defrost, if activation criteria for Condition 1 reoccur
within 45 minutes of the defrost cycle, alarm or alarm and shutdown as Configured. If,
following the defrost and the 45 minute wait time the activation criteria for Condition 1
reoccur the unit will go into defrost again.
If the DTT and SAT temperatures are too warm to allow a defrost, alarm or alarm and
shutdown as Configured.
Condition 2 = Alarm or alarm and shutdown as Configured
• RESET CONDITION:
Auto reset when discharge pressure is more than 20 psig (1.26 bar) above the suction
pressure for five minutes, or alarm has been active and unit has been shutdown more
then 14 minutes or alarm may be manually reset using the display mounted keys or by
turning the unit off, then back on again.
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A28 X4 – Check Refrigeration System
1. CHECK COMPRESSOR DRIVE COUPLING
Verify that compressor coupling (nylon gear) is intact and the compressor crankshaft is
turning.
Repair as required.
4. CHECK COMPRESSOR.
a. Perform Pump-Down Test.
Must hold a vacuum and not equalize in a short period of time.
b. Cover condenser and build-up discharge pressure.
Must be able to raise pressure to 400 psig (27.2 bar).
c. Disassemble and inspect compressor valve plates, cylinder suction valves, cylinder
discharge valves and pistons, etc.
Must be intact, clean, and in good working order
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A30 X4 – Fail to Run minimum time
• ACTIVATION:
If Configured STANDARD: The unit has shutdown on an alarm 3 times without having run
for at least 15 minutes between each shutdown (not including door switch shutdowns).
If Configured RAIL: The unit has shutdown on an alarm and attempted to restart for the
Configured number of times without having run for at least 15 minutes between each
shutdown (not including door switch shutdowns).
• UNIT CONTROL:
Alarm only or shutdown and alarm.
• RESET CONDITION:
Alarm may be manually reset using the display mounted keys or by turning the unit off,
then back on again.
If the Configuration is set to Rail Mode, this alarm will reset after 4 hours and a rail alarm
reset will be recorded in the data recorded. .
• ACTIVATION:
The engine has tried to start three times unsuccessfully.
• UNIT CONTROL:
Shutdown and alarm.
• RESET CONDITION:
Alarm may be manually reset using the display mounted keys or by turning the
unit off, then back on again.
If the Configuration is set to Rail Mode, this alarm will reset after 4 hours.
Rail alarm reset will be recorded in the data recorder.
4. CHECK ENGINE CONTROL UNIT (ENCU) AND FUEL SPEED ACTUATOR (FSA)
a. Check voltage from fuse F3 through PCM−34 and SP−6 to ENCU−22
Verify correct fuse.
Must have minimum 11 VDC with the battery connected and SROS in the OFF position.
b. Check voltage from 3MM-9 to ENCU−44.
Must have minimum 11 VDC with SROS in the START/RUN position.
If no: Energize the run relay output using component test mode and retest.
c. Check for ground at ENCU-19 and ENCUGND−A (at the battery negative cable connection).
Must have good ground.
If not: Check connectors and wiring between terminals.
No damage, moisture or corrosion.
Fuel Speed Actuator
d. Inspect fuel/speed actuator (FSA),
engine speed sensor (ENSSN) and engine speed control
unit (ENCU) connector pins & terminals.
No physical damage to components.
No damage or corrosion in connectors.
e. Check resistance & amp draw of FSA.
(2.8 Ohms ±10% @20°C)
(4 Amps Max)
f. Check FSA plunger.
Must move in and out freely Engine Speed Sensor
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A31 X4 – Fail to Start Auto Mode
8. CHECK ENGINE
Check engine compression.
• ACTIVATION:
Engine speed fails to reach 50 rpm during 2 start attempts.
• UNIT CONTROL:
Shutdown and alarm.
• RESET CONDITION:
Alarm may be manually reset using the display mounted keys or by turning the
unit off, then back on again.
2. CHECK FUSE
Check fuse F−10 Fuse must be good.
If required, replace fuse
4. CHECK STARTER
a. Inspect starter and wiring. (See wiring schematic)
No damage or corrosion. Wiring and battery cable must be clean and tight
b. Check voltage to starter motor.
Must be above 10 VDC while cranking.
c. Check resistance of starter motor.
(Less than 1 ohm but more than 0)
d. Check amperage draw of starter.
(270 – 380 amps)
STARTER CONNECTIONS
• ACTIVATION:
The control system is calling for high speed operation, and engine speed is less than
1650 rpm, or greater than 1950 rpm for more than 60 seconds (120 seconds when the
control system calls for a change from low to high speed, or when unit first starts).
• UNIT CONTROL:
Alarm only.
• RESET CONDITION:
Auto reset if control system is calling for high speed operation and the speed is within 1670
and 1930 rpm for 60 seconds or alarm may be manually reset using the display mounted
keys or by turning the unit off, then back on again.
1. High Ambient.
If ambient temperature is 48.9°C or above during the engine starting sequence, the unit will run in low speed for the
first 2 minutes of operation.
This applies to Heat and Cool modes only - not Defrost.
4. Defrost.
The engine Is generally in high speed but will run in low speed during the high ambient pump down and at the end of
the defrost cycle while the refrigerant control solenoids are realigned.
8. Air Flow.
When operating with a perishable setpoint and the AIR FLOW Functional Parameter is set to HIGH, the engine will
operate in high speed.
• ACTIVATION:
Alarm 00130(Check Engine Speed Sensor) is not active and engine speed is less than 1200
rpm or greater than 1950 for 5 minutes.
• UNIT CONTROL:
Alarm only or (if configured for shutdown) shutdown and alarm.
• RESET CONDITION:
Auto reset if engine speed is within the specified range for 5 minutes or alarm
may be manually reset using the display mounted keys or by turning the unit off, then back
on again.
• ACTIVATION:
The control system is calling for the engine to run, Engine speed sensor is good, and
engine speed is less than 10 rpm; or the A00130 (Check Engine Speed Sensor) alarm is ON,
and the Oil Pressure switch contacts are open.
• UNIT CONTROL:
Shutdown and alarm.
• RESET CONDITION:
Auto Restart after 15 minutes, or Alarm may be manually reset using the display mounted
keys or by turning the unit off, then back on again.
INLET STRAINER
INLET FILTER
5. CHECK ENGINE CONTROL UNIT (ENCU) AND FUEL SPEED ACTUATOR (FSA)
a. Check voltage from fuse F3 through PCM−34 and SP−6 to ENCU−22
Verify correct fuse.
Must have minimum 11 VDC with the battery connected and SROS in the OFF position.
b. Check voltage from 3MM-9 to ENCU−44.
Must have minimum 11 VDC with SROS in the START/RUN position.
If no, energize the run relay output using component test mode and retest.
c. Check for ground at ENCU-19 and ENCUGND−A (at the battery negative cable connection).
Good ground. If not, check connectors and wiring between terminals.
No damage, moisture or corrosion.
d. Inspect fuel/speed actuator (FSA), engine speed sensor (ENSSN) and engine speed control
unit (ENCU) connector pins & terminals.
ENCU FSA
No physical damage to components.
No damage or corrosion in connectors.
e. Check resistance & amp draw of FSA.
(2.8 Ohms ±10% @20°C)
(4 Amps Max)
f. Check FSA plunger.
Must move in and out freely.
9. CHECK ENGINE
a. Check Injection pump timing.
Timing must be correct.
b. Check engine valve adjustment.
Rocker arm clearance must be correct.
c. Check engine compression.
Compression must be above 400 psig (27.2 bar).
• ACTIVATION:
Unit is running and the current flow is more than -1.0 amps (discharge) between the
alternator and the battery for 3 continuous minutes.
• UNIT CONTROL:
Alarm only or if Alternator Check Shutdown Configuration is set to “YES” shutdown
and alarm.
• RESET CONDITION:
Auto reset (if not shutdown) when alternator is charging or alarm may be
manually reset using the display mounted keys or by turning the unit off,
then back on again.
GROUND CONNECTIONS
• ACTIVATION:
Main microprocessor cannot communicate internally.
• UNIT CONTROL:
Shutdown all modules except the display and alarm.
(The alarm will only display if the display module is communicating.)
Main microprocessor status LED will illuminate steady green (not pulsing).
• RESET CONDITION:
Auto reset when internal communication is restored, alarm reset or alarm may be manually
reset by turning the unit off, then back on again..
• ACTIVATION:
Activate alarm if:
Condition 1 = At engine start if the engine throttle sensor value is less than 90 %.
Condition 2 = After start if the sensor value does not drop below 90% within 5 seconds.
Condition 3 = At engine shutoff if the sensor value does not drop below 10% within 5
seconds.
• UNIT CONTROL:
Alarm only. Control system will modulate CSMV and activate unloaders as required.
• RESET CONDITION:
Alarm may be manually reset using the display mounted keys or by turning the unit off,
then back on again.
NOTE:
This alarm can be activated if the Small cable from the Starter to ENCU-21 is connected on the
wrong connection of the starter together with the battery cable.
2. Replace Sensor
Replace sensor with know good component.
Calibrate sensor and ENCU.
RPS
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation