You are on page 1of 144

Advanced trailer training

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Transport refrigeration units are designed to keep the product temperature at required
Setpoint from the loading site until the its destination.

During the trip some failures can occur impacting the performance on temperature control.

Many times we experienced the most common words from the drivers: “no cooling”

“no cooling” can be related to certain number of conditions, not only no refrigerant or
something related to the refrigeration circuit.

For example:
If the unit is running and the diesel runs out, the unit will stop and the driver will call and
report “no cooling”

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Top Brake Downs leading to Temperature Issues

Top brake downs faced by Almarai combined in groups

Refrigeration
Engine shut down
Starting
Nylon gear
Operator issue
Battery
RPM

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Temperature issues

A16 – Battery voltage


too low 6 HOURS
45 A23100 - No Comm From A18 – Low refrigerant
MINUTES Micro To Outpbd1 pressure
A14 – Electric Circuit
1 HOUR

A100 – Overload 4 HOURSA35 – Check Starter


Ground Fault circuit

Temperature
A41- Engine Stalled
NO PROPER IssuesVACUUM A31 – Failed to start
Auto - mode
THE BIGGEST MISTAKE OF THE REFRIGERATION
“no cooling”
TECHNICIAN
A30 – Fail to Run 1,5 A13 – High Discharge
minimum time
HOUR pressure
3 HOURS
A38 / A39 – Check A51 – Alternator not
engine RPM charging
A28 – Check
refrigeration System

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Evacuation

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
What is Vacuum?

Evacuation

• A/C & Refrigeration systems are designed to operate with only oil and
refrigerant flowing through them.
When a refrigeration system is installed and/or serviced, air and moisture
enter the system.

• Oxygen, nitrogen and moisture (all make up our air or atmosphere) are detrimental
to system operation.

• Removal of the air and other non-condensable is called degassing and


removal of the moisture is called dehydration.

• Removal of both is typically referred to as evacuation.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Evacuation
Proper evacuation after initial installation or after service where the
system has been opened to atmosphere is critical to proper
operation of refrigeration system.

Non condensables is the first issue

Degassing:

• Evacuation is a two step process of degassing and dehydration.


• Degassing removes non condensables (ex. air) which cause increased head
pressures and increased operating cost.

• Where high temperatures are frequent, non condensables combined with


moisture will also cause oil failure, decreased capacity and increased
compressor wear and potential failure.

• Losses associated with improper evacuation can be very high.


CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Evacuation

Moisture is the second issue.

Dehydration:

• Moisture brakes down POE oil in HFC systems, (like R404a) causing premature
failure of the oil.

• Because POE breaks down into its fundamental components, it loses the
lubrication properties leading to compressor failures and it can clog the
metering device and contaminate line sets.

• This could result in the need for complete system replacement.

• Moisture refrigerant and mineral oils form acids that will cause system failure
due to copper plating and damage to compressor windings.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Evacuation

Vacuum gauge:

Is used to determine the level of atmosphere


(degassing and dehydration) in the system.

Quick and deep evacuation of an refrigeration system simply comes down to


correct practices including proper installation and assembly, keeping out the
moisture during fabrication and of course the right tools hoses and gauges to
measure the level of degassing and dehydration.

When moisture (humidity) enters a system or condenses, the only way it can be
removed is in vapor state.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Evacuation

It is almost impossible to state the exact amount of time required to evacuate


any system.
Some factors that can influence evacuation time are listed below.

• How large system is

• The amount of moisture contained in system

• The ambient temperature

• Internal restrictions

• External restrictions

• Evacuation time can be significantly reduced by larger diameter hoses and


shorter hoses.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Evacuation - Conclusion
Let’s take an example:

• Do you think that vacuuming a refrigeration system in a 5°C ambient is


possible?

• No it is not, because water trapped in the circuit is also at 5°C and in liquid
form!
Decreasing the pressure to quickly raises the freezing point of water creating
a phenomenon called deposition.
Meaning, water will turn to ice before evaporation is complete.

When the ambient temperature is below +15 ⁰C


• If ambient temperature is to low, moisture could condense inside the system.
• This can be prevented by using heat lamps to rise the temperature slightly
above +15 ⁰C to prevent condensation. Apply as much heat as possible to the
system, keeping it as uniform as possible.
• This will accelerate the evaporation process of the water.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Software
Due to a process of evolution , today is possible to control the cooling units
with electronics.

In the same way that computers, mobile phones, etc. operate with a software,
also the cooling units with microprocessor need software, and Software requires
updates.
Whenever there is a software update, means that something better is coming to
optimize the unit.
Updates may be related to: APX ADVANCE
• Valve control logic
• Fuel consumption
• Cooling performance
• Correct errors

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Tools for APX and Advance System Troubleshooting

Tru-Tech &
& Tru-View
Tru-View

22-01690-00 (3 meters) 07-00439-00


22-01690-01 (10 meters) (Card Reader) 12-00814-00
(APX ONLY)

22-60891-01
12-00534-00 12-00503-00 22-04253-00 (1,8 meter)
(Program/Configuration card) (Download card) 22-04253-01 (6,1 meters)

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Stepper Valve Tester Tool

VECTOR CSMV
VECTOR AND X4 EVXV

P/N: 07-00375-00SV

X4 CSMV
STEPPER VALVE TESTER

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
X4 Troubleshooting
Recommended Tools for APX System Troubleshooting

07-00525-00 07-00524-00

07-00526-00

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Vector 1950 Troubleshooting

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Vector 1950 Troubleshooting

PREVIOUS CONTROL BOX LAYOUT

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Vector 1950 Troubleshooting

LATEST CONTROL BOX LAYOUT LATEST CONTROL BOX LAYOUT


WHIT STANDARD CONTACTORS WHIT ELECTRONIC CONTACTORS

WITH AUXILIARY RELAYS WITHOUT AUXILIARY RELAYS

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A13 Vector – High Discharge pressure

Before any Refrigeration troubleshooting


the manifold gauges must be connected to the refrigeration system

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A13 Vector – High Discharge pressure

HIGH DISCHARGE PRESSURE (ALARM 75 WILL ACTIVATE)

• TRIGGER–ON:
Compressor discharge pressure is over 465 PSIG (32 Bars)

• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.

• RESET CONDITION:
Auto Reset after 15 minutes if the compressor discharge pressure falls below 350 PSIG
(23.8 Bars), or alarm may be manually reset via keypad or by turning the unit off,
then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A13 Vector – High Discharge pressure
1. CHECK SYSTEM PRESSURES
a. Install Manifold Gauges and check and compare compressor discharge & suction
pressures with those shown on the microprocessor controller.
Suction & Discharge Pressures must have the same reading on gauges & on micro display.
Pressures must be in the normal range for ambient & box temperature conditions.
NOTE: Microprocessor suction pressure reading has a maximum value of 100 psig (6.9 Bar)
2. CHECK AIRFLOW THROUGH CONDENSER COIL
a. Inspect condenser / radiator fins.
Fins must be straight.
90% or more of the coil surface must be undamaged. No “dead” air spaces.
Condenser / Radiator coil must be clean..
Wash the condenser with pressurized water until the water running out from the condenser is clean

3. CHECK FOR REFRIGERANT OVERCHARGE


a. Check refrigerant level in the receiver tank.
Refrigerant charge: Vector 1950 & 1850 with MCHX
* 5kg for Single temperature units
* 7,3 kg for multi temp 2 compartments
* Depending on unit model, always reefer to serial number plate.
b. Check airflow (with unit running). Even airflow through the entire coil No “dead” spots
c. Check condenser fan rotation/operation.
Both fans should operate correctly.
Air should be directed in through the grill, and into the engine compartment.
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A13 Vector – High Discharge pressure

4. CHECK HP1 SWITCH


a. Inspect switch & connector pins & terminals
No physical damage to switch.
No damaged or corroded pins in plug.
b. Check switch operation
Contacts open when compressor discharge pressure is above cut-out point ± 10 PSIG (±0.68 Bar)
Contacts closed when compressor discharge pressure is below cut-in point ± 10 PSIG (±0.68 Bar)

5. CHECK HP1 SWITCH HARNESS


a. Inspect harness & control box connector pins & terminals (See wiring schematic)
No physical damage to harness.
No damaged or corroded pins
b. Check for shorted circuit in harness, and continuity through the harness.
Energize Circuit.
Battery voltage reading (12-13 VDC) between wire HP1A-SPKS and between HP1B to Ground.

6. Perform Pretrip Check


a. Run Pretrip & check for alarms.
Any active alarms must be corrected and cleared before proceeding.

7. SEE REFRIGERATION TROUBLE SHOOTING


Discharge Pressure must be in normal range for the current ambient and box temperature conditions.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A14 Vector – Electric Circuit

ELECTRICAL CIRCUIT

• TRIGGER–ON:
AC Current Sensor 1 is greater than 40A or AC Current Sensor 2 is greater than 40A for 3
seconds

• UNIT CONTROL:
Engine operation: alarm will not activate.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.

• RESET CONDITION:
Auto reset after 15 minutes if the AC current sensor readings are less than 38 amps or
alarm may be manually reset via keypad or by turning unit off then back on.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A14 Vector – Electric Circuit

1. CHECK GENERATOR VOLTAGE (IF USED WHEN ALARM OCCURRED)


a. Check voltage at GENCON L1-L2, L1-L3, L2-L3
Should be 440 to 580 VAC
AC CURRENT SENSOR

2. CHECK POWER SOURCE VOLTAGE (IF USED WHEN ALARM OCCURRED) PSCON
a. Check voltage at PSCON L1-L2, L1-L3, L2-L3 PSCON2
Should be 440 to 580 VAC
GENCON

3. CHECK VOLTAGE OUTPUT FROM CONTACTORS CCON


a. Check voltage at GENCON T1-T2, T1-T3, T2-T3
Should be 440 to 580 VAC
b. Check voltage at CCON with compressor operating.
T1-T2, T1-T3, T2-T3 Should be 440 to 580 VAC

4. VERIFY AC CURRENT SENSOR ACCURACY


a. Turn all compartment switches OFF, and RS ON.
Unit AC Current #1 and #2 reading in Data List must be 0.0 ± 1.0 amp.

Control Box Latest Version


CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A14 Vector – Electric Circuit

5. CHECK HIGH VOLTAGE COMPONENTS AMP DRAW

a. Check condenser fan amp draw on all 3 legs.


Amperage reading must be similar on all 3 phases
b. Check evaporator fan motor amp draw for Compartment 1 on all 3 legs.
Amperage reading must be similar on all 3 phases
c. Check evaporator fan motor amp draw for Compartment 2 on all 3 legs.
Amperage reading must be similar on all 3 phases
d. Check compressor amp draw on all 3 legs.
Amperage reading must be similar on all 3 phases
e. Check Compartment 1, 2 Heater amp draw for HTCON1
Amperage reading must be similar on all 3 phases
f. Check Compartment 1, 2 Heater amp draw for HTCON2
Amperage reading must be similar on all 3 phases

NOTE: If there is a “0” amperage reading while testing, check the fuses for the concerned component

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A16 Vector - Battery Voltage to Low
Before we continue to troubleshooting please note that AGM battery is recommended
for Carrier Vector units

AGM battery explanation:

AGM stands for Absorbent Glass M at, which is a material that holds acid in place like a sponge.
Specifically, they're made with Spiralcell® Technology - an advanced form of AGM technology

Advantages:
 Dual function battery : starting and deep cycling

 Fast recharge battery technology :high current permitted

 Stable capacity over lifetime

 Extremely vibration resistant

Installable in multiple positions

 Green technology : no acid spilling, easy to recycle

 Best ratio CCA / weight, in lead battery technology

 No restriction for any transportation mode

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A16 Vector - Battery Voltage to Low

Comparison:

Battery type Regular flooded battery Vector AGM Battery

Cranking performance

High temperature resistance

Low temperature performance

Vibration resistance

Charging acceptance

Deep cycle performance

Self discharge

Gassing

Acid stratification

Internal resistance

Note:
 AGM battery resists to high temperatures, that’s why is so important that all Vector units are equipped with this
battery, specially in Middle East.

 Usage of a regular flooded battery will lead to, premature failure of the battery charger, Start/Stop failure during
regulation period increasing fuel consumption, and a short life time of the battery.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A16 Vector - Battery Voltage to Low

BATTERY VOLTAGE TOO LOW

• TRIGGER–ON:
Voltage at the microprocessor is less than 10 VDC
(except when the engine starter is engaged)

• UNIT CONTROL:
Unit Shutdown & Alarm.
Alarm condition only if activated while starting unit.

• RESET CONDITION:
Auto Reset after 15 minutes when the voltage at the microprocessor is between
11 - 14 VDC, or alarm may be manually reset via keypad or by turning the unit off,
then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A16 Vector - Battery Voltage to Low - Troubleshooting

1. CHECK FOR ALARM 51


a. Check for Alternator Not Charging Alarm
Alarm conditions must be corrected and the alarm cleared to continue

2. CHECK BATTERY VOLTAGE


a. Inspect battery cable ends and posts.
Must be clean and tight
b. Test voltage at battery with unit off.
Must be above 11 VDC
c. Test voltage at battery with unit running.
Must be above 11 VDC
d. Perform load test on battery.
(Follow battery manufacturer’s procedure)

BATTERY CHARGER

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A16 Vector- Battery Voltage to Low - Troubleshooting

3. CHECK VOLTAGE AT MICROPROCESSOR


a. Check voltage reading at microprocessor input ( MP QC1 (+) to MP QC2 (-)).
Energize circuit. (See Note 2).
Must be above 11 VDC
b. Check voltage reading on microprocessor display.
Must be within 0.5 VDC of reading obtained in 3a (above)

NOTE 2: Many electrical circuits may be tested by leaving all compartment switches in the “O” (OFF) position and turning the RS to the
START/RUN position. At least one compartment must be in the “1” (ON) position. In this mode, RCR will be energized and the main
display will show “OFF”.

MP QC2 : Input Ground


MP QC1 : Input +12VDC from battery

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A18 Vector – Low Refrigerant Pressure

Before troubleshooting
the manifold gauges must be connected to the refrigeration system

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A18 Vector – Low Refrigerant Pressure

• TRIGGER–ON (A):
Both UL1 and UL2 are energized AND unit is in engine mode AND in low speed AND
compressor is running AND low suction pressure shutdown delay in configurations has
elapsed since energizing UL1 AND Suction Pressure is less than 0.3 Bar

• UNIT CONTROL:
Engine operation: alarm only or (if configured for shutdown) engine and unit shutdown
and alarm.
Standby operation: alarm only or (if configured for shutdown) refrigeration system
shutdown and alarm with PSCON still energized.

• RESET CONDITION:
If alarm only: auto reset when either UL1 or UL2 is de-energized.
If unit and system shut down and alarm: auto reset after 15 minutes.
Alarm may be manually reset via keypad or by turning the unit OFF, then ON again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A18 Vector – Low Refrigerant Pressure – Troubleshooting

1. CHECK REFRIGERANT CHARGE


a. Check for undercharged system
Sight glass must be full

2. CHECK SYSTEM PRESSURES


a. Install Manifold Test Set and check and compare compressor discharge & suction
pressures with those shown on the microprocessor controller.
Suction pressure must be above 3 PSIG (0.2 Bar)
Suction & Discharge Pressures must have the same reading on gauges & on micro display.

NOTE: Microprocessor suction pressure reading has a maximum value of 100 psig (6.9 bar)

3. MANUALLY DEFROST UNIT


a. Defrost unit and terminate automatically.
Typical defrost cycle time is 5-20 minutes.
Suction pressure should rise gradually during cycle.
Check AMPS consumption on all 3 phases on HTCON1-2

4. PERFORM PRE-TRIP CHECK


a. Run Pre-Trip & check for alarms.
Any active alarms must be corrected and cleared before proceeding.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A18 Vector – Low Refrigerant Pressure – Troubleshooting

5. CHECK UNLOADER OPERATION UNLOADER FRONT


a. Check front and rear unloaders See Alarms 85 and 86

6. CHECK CSMV
a. Check compressor suction modulation valve
b. Check airflow (with unit running).
Even airflow through the entire coil No “dead” spots
UNLOADER REAR CSMV
7. EVAPORATOR SECTION
a. Check evaporator section, return air bulkhead, air chute, cleanliness of evap. coil
Good Air Flow, Return air not restricted, Air chute in good condition,
No damage to blower wheel, Evap. coil clean, Evap. fan rotation ok

8. CHECK EXPANSION VALVE (EVXV)


a. Check Coil position and if it is fully inserted,
Check connector

9. CHECK EXPANSION VALVE FOR COMPARTMENT 2


a. Check valve superheat.

STEPPER VALVE TESTER


CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A28 Vector – Check Refrigeration System
CHECK REFRIGERATION SYSTEM

• TRIGGER ON:
The refrigeration system is running and the discharge pressure is less than 5 PSIG
(0.34 Bar) higher than suction pressure for more than 10 minutes

• UNIT CONTROL:
Engine operation: alarm only or (if configured for shutdown) engine and unit
shutdown and alarm.
Standby operation: alarm only or (if configured for shutdown) refrigeration system
shutdown and alarm with PSCON still energized.

• RESET CONDITION:
Auto reset when discharge pressure is more than 20 PSIG (1.36 Bars) above
the suction pressure when in alarm only, or auto reset after 15 minutes when shutdown is
configured or alarm may be manually reset via keypad or by turning the unit off, then back
on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A28 Vector – Check Refrigeration System
1. VERIFY COMPRESSOR IS RUNNING.
a. Check compressor Amp draw - CCON T1-T2, T1-T3, T2-T3.

2. CHECK SYSTEM PRESSURES


a. Install Manifold Gauges and check and compare compressor discharge & suction pressures
with those shown on the microprocessor controller.
Suction pressure must be above 3 PSIG (0.2 Bar)
Suction & Discharge Pressures must have the same reading on gauges & on micro display.
NOTE: Microprocessor suction pressure reading has a maximum value of 100 psig (6.9bar)

3. PERFORM PRE-TRIP CHECK


a. Run pre-trip & check for alarms.
Any active alarms must be corrected and cleared before proceeding.

4. CHECK COMPRESSOR.
a. Perform Pump-Down Test. (Never on Vector 1550)
Must pump down to 5 PSI and hold for minimum of 1 minute.
b. Cover condenser and build-up discharge pressure.
Must be able to pump up to 400 PSI.
c. Disassemble and inspect compressor valve plates, reeds, pistons, etc.
Must be intact, clean, and in good working order.
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A30 Vector – Fail to Run minimum time

FAILED TO RUN MINIMUM TIME

• TRIGGER–ON:
Engine has shut down on an alarm 3 times without having run for at least 15
minutes between each shutdown (not including Door or Remote Switch shut downs) AND
unit is in automatic start mode.

• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.

• RESET CONDITION:
Alarm may be manually reset via keypad or by turning the unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A30 Vector – Fail to Run minimum time

1. CHECK FOR ALARMS


a. Check for shut down alarms.
Alarm conditions must be corrected and the alarm(s) cleared to continue.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A31 Vector – Fail to Start Auto Mode

FAILED TO START - AUTO MODE

• TRIGGER–ON:
In engine mode, engine has tried to start 3 times unsuccessfully in the auto start mode.

• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: this alarm will not activate in standby operation.

• RESET CONDITION:
Change unit to standby operation or alarm may be manually reset via keypad or by turning
the unit off, then back on again.

INLET STRAINER

NOTE: Common failure is the strainer blocked in fuel inlet


CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A31 Vector – Fail to Start Auto Mode
1. CHECK FUEL LEVEL IN TANK
a. Check fuel gauge on tank. Fill tank if needed.

2. CHECK FOR ALARMS


a. Check for the following alarms:
71 Check for Bad F2 or F3 Fuse alarm , 40 Check Glow Plugs alarm,
35 Check Starter Circuit alarm
Alarm conditions must be corrected and the alarm cleared to continue Fuel Solenoid

3. CHECK FUEL SOLENOID


a. Check run relay. Unit in component test mode - run relay ON.
b. Check Run Relay LED Must be ON.
c. Check voltage to fuel solenoid. 12 VDC between FSC-C (-) & FSH-A (hold)
With engine starter energized. 12 VDC between FSC-C (-) & FSP-B (pick)
d. Inspect solenoid & connector pins & terminals
No damage to solenoid, No damaged or corroded pins
e. Inspect harness & control box connector pins & terminals (See wiring schematic)
No physical damage to harness, No damaged or corroded pins
f. Check resistance of solenoid.
Red-Black Wires: 11.1 to 13.4 Ohms, 0.25 - 2.0 Amps
White-Black wires: Resistance Can not be accurately measured with Coil Commander in circuit. 30.0 to 40.0 Amps
g. Check operation of solenoid.
Plunger must move in when energized
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A31 Vector – Fail to Start Auto Mode

4. CHECK FUEL SYSTEM


a. Check fuel system prime. No air in fuel system
b. Check fuel flow. Unrestricted fuel flow through system
c. Check voltage to glow plugs. Glow Plug switch ON, Manual Start Mode More than 11 VDC
5. CHECK ENGINE AIR–INTAKE SYSTEM
a. Check air filter indicator Flag. Must not be visible.
b. Inspect air intake system Hoses & tubes in good condition. No kinks or restrictions

6. CHECK FOR CORRECT ENGINE OIL


a. Check for correct oil viscosity (weight) for conditions.
Must be correct for ambient conditions

7. CHECK ENGINE EXHAUST SYSTEM


a. Inspect the exhaust system.
Must be clear and un-obstructed

8. CHECK ENGINE
a. Check engine compression
9. CHECK RPM SENSOR RPM Sensor
a. Check sensor
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A35 Vector – Check Starter Circuit

CHECK STARTER CIRCUIT

• TRIGGER–ON:
Engine speed fails to reach 50 RPM during 2 start attempts.

• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: this alarm will not activate in standby operation.

• RESET CONDITION:
Change unit to standby operation or alarm may be manually reset via keypad or
by turning the unit off, then back on again.

NOTE: Common failure is the strainer blocked in fuel inlet


CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A35 Vector – Check Starter Circuit
1. CHECK FUEL SYSTEM
a. Check fuel gauge and fuel tank level.
Fill tank as needed
b. Check fuel flow.
Unrestricted fuel flow through system. Fuel not gelled
c. Check fuel system prime.
No air in fuel system
d. Check fuel system check valve from filter to injection pump.
Check valve must hold fuel and not leak back

2. CHECK STARTER RELAY CIRCUIT SSR


a. Check operation of starter solenoid relay. Energize Circuit.
Relay contacts closed when SSR85 is grounded.
b. Check relay socket and terminals.
No signs of discoloration from overheating, No corrosion
c. Check voltage to starter solenoid relay
Negative lead on 85, Positive lead on 86 = 12 VDC
Negative lead on Ground, Positive lead on 87 & 30 = 12 VDC
d. Inspect wiring to starter solenoid and starter motor
No physical damage to wiring or battery cable end. No damaged or corroded terminals.
e. Check voltage to starter solenoid. Must be above 11.5 VDC
f. Check voltage to starter motor. Must be above 10 VDC while cranking
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A35 Vector– Check Starter Circuit

3. CHECK STARTER
a. Inspect starter and wiring.
No damage or corrosion,
Wiring and battery cable must be clean and tight
b. Check resistance of starter motor
(Less than 1 ohm but more than 0)
c. Check amperage draw of starter STARTER
(270 – 380 amps)

4. CHECK BATTERY VOLTAGE


a. Inspect battery cable ends and posts
Must be clean and tight
No corrosion
b. Test voltage at battery with unit off.
Must be above 11 VDC
c. Perform load test on battery
(Follow battery manufacturer’s procedure)

5. CHECK FOR CORRECT ENGINE OIL


a. Check for correct oil viscosity (weight) for conditions
Must be correct for ambient conditions
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A38 Vector – Check High Speed RPM

CHECK HIGH SPEED RPM

• TRIGGER–ON:
Controller is set for high engine speed operation, and engine RPM are:
Less than 1650, or greater than 2075 for more than 60 seconds (120 seconds if micro calls
for a change from low speed to high speed, or when unit starts).

• UNIT CONTROL:
Engine operation: alarm only.
Standby operation: this alarm will not activate in standby operation.

• RESET CONDITION:
Auto Reset if controller is set for high speed operation and RPM is between 1670 and
2050 for 60 seconds or change unit to standby operation or alarm may be manually reset
via keypad or by turning the unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A38 Vector – Check High Speed RPM

1. VERIFY THAT CORRECT MODEL NUMBER IS SELECTED


a. Compare model number from unit I.D. label and model number in Micro Data List.
The model numbers must be the same.
Speed Solenoid

2. CHECK SPEED SOLENOID LINKAGE


a. Check speed solenoid plunger.
Must move in and out freely
b. Check engine speed arm & linkage.
Must move freely

3. FORCE HIGH SPEED OPERATION


a. Change setpoint if necessary to more than 5.6°C away from setpoint.
Controller will call for High Speed operation.
b. Check operation of Speed Relay LED 27.
Must be ON
c. Check voltage to speed solenoid.
Must be 12-14 VDC

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A38 Vector – Check High Speed RPM
4. CHECK SPEED CIRCUIT
a. Inspect harness & control box connector pins & terminals (See wiring schematic)
No physical damage to harness.
No damaged or corroded pins or terminals
b. Check resistance of speed solenoid (1.5 to 2.5 Ohms)
c. Check amp draw of speed solenoid (3.0 - 8.0 Amps)

5. CHECK ENGINE RPM


a. Check actual engine RPM using hand held tachometer
Adjust engine linkage setting as needed.
b. Compare actual RPM with those shown on display.
Both readings within ± 50 RPM

6. CHECK ENGINE AIR–INTAKE SYSTEM


a. Check air filter indicator.
Flag must not be visible.
b. Inspect air intake system Hoses & tubes in good condition.
No kinks or restrictions

7. CHECK ENGINE EXHAUST SYSTEM


a. Inspect the exhaust system.
Must be clear and unobstructed
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A39 Vector – Check Engine RPM

CHECK ENGINE RPM

• TRIGGER–ON:
Multi-temp: In engine mode and Alarm 130 (RPM SENSOR) is not active and engine rpm is
less than 1250 or greater than 2000 for 5 minutes or engine rpm drops to less than 1200
for 5 seconds after the engine rpm has been greater than 1250 for 3 seconds.

• UNIT CONTROL:
Engine operation: alarm only or (if configured for shutdown) engine and unit shutdown and
alarm.
Standby operation: this alarm will not activate in standby operation.

• RESET CONDITION:
Auto Reset if engine rpm is greater than 1250 and less than 2000 for 5 minutes or after 15
minutes if the engine has been shutdown or change unit to standby operation or alarm
may be manually reset via keypad or by turning the unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A39 Vector – Check Engine RPM

1. CHECK FOR ENGINE STALLED ALARM


a. Check for Alarm 41.
When both alarms are present, unit may have been run out of fuel.

2. CHECK SPEED SOLENOID & LINKAGE Speed Solenoid


a. Check speed solenoid plunger.
Must move in and out freely
b. Check engine speed arm & linkage.
Must move freely

3. CHECK FUEL SYSTEM


a. Check for Alarm 1 (If fuel Level sensor is installed).
Check fuel tank level.
Fill tank as needed
b. Check fuel flow.
Unrestricted fuel flow through system
Fuel not gelled
c. Check fuel system prime.
No air in fuel system

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A39 Vector – Check Engine RPM

4. CHECK ENGINE AIR–INTAKE SYSTEM


a. Check air filter indicator.
Flag must not be visible.
b. Check air filter.
Must be clean.
c. Inspect air intake system Hoses and tubes in good condition.
No kinks or restrictions.

5. CHECK LOW SPEED ENGINE RPM


a. Check actual engine RPM using hand held tachometer
Adjust engine linkage setting as needed.
b. Compare actual RPM with those shown on display
Both readings within ± 50 RPM

6. CHECK HIGH SPEED ENGINE RPM


a. Check actual engine RPM using hand held tachometer
Adjust engine linkage setting as needed.
b. Compare actual RPM with those shown on display
Both readings within ± 50 RPM

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 Vector – Engine Stalled

ENGINE STALLED

• TRIGGER–ON:
In engine mode, the engine is running, RPM sensor is good, and engine speed is less than
10 RPM; or the engine is running, RPM sensor alarm is ON, and the Oil Pressure switch
contacts are open.

• UNIT CONTROL:
Unit shutdown in electric.
Alarm only in standby.

• RESET CONDITION:
Auto Reset after 15 minutes, or alarm may be manually reset via keypad or by turning the
unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 Vector – Engine Stalled

1. CHECK FUEL SYSTEM


a. Check for Alarm 1 (If fuel Level sensor is installed).
Fill tank as needed BLEEDING SCREW
b. Check fuel gauge and fuel tank level.
Fill tank as needed
c. Check fuel flow.
Unrestricted fuel flow through system. Fuel not gelled
d. Check fuel system prime.
No air in fuel system
e. Check fuel system check valve from filter to
injection pump.
Check valve must hold fuel and not leak back

MANUAL FUEL PUMP

INLET STRAINER

NOTE: Common failure is the strainer blocked in fuel inlet


CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 Vector – Engine Stalled

2. WAS ENGINE SHUT OFF MANUALLY?


a. Check for external cause Correct problem.

3. CHECK FOR RPM SENSOR ALARM


a. Check for Alarm 130 (CHECK ENGINE RPM SENSOR)
When both Alarm 41 and (usually) Alarm 130 are present, there is insufficient fuel to run
engine.

4. CHECK ENGINE OIL PRESSURE SWITCH


a. Inspect switch, connector pins, and terminals.
No physical damage to switch.
No damaged or corroded pins in plug.
b. Check engine oil switch operation.
Contacts closed when oil pressure is above 15 PSIG (1.02 Bars).
Contacts open when oil pressure is below 12 PSIG (0.82 Bars).

OIL PRESSURE SWITCH


5. CHECK FOR BAD F2 OR F3 FUSE ALARM
a. Check for Alarm 71 Alarm conditions.
Must be corrected and the alarm cleared to continue.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 Vector – Engine Stalled

6. CHECK FUEL SOLENOID


a. Check run relay.
Unit in Component Test mode - Run Relay ON.
b. Check Run Relay.
LED Must be ON
c. Check voltage to fuel solenoid.
12 VDC between FSC-C (ground) and FSH-A (hold)
With engine starter energized. Fuel Solenoid
12 VDC between FSC-C (ground) and FSP-B (pick)
d. Inspect solenoid, connector pins, and terminals.
No damage to solenoid.
No damaged or corroded pins.
e. Inspect harness, control box connector pins, and terminals. (See wiring schematic).
No physical damage to harness.
No damaged or corroded pins.
f. Check resistance of solenoid
Red-Black Wires: 11.1 to 13.4 Ohms, 0.25 - 2.0 Amps
White-Black wires: Resistance Can not be accurately measured with Coil Commander in circuit. 30.0 to 40.0 Amps
g. Check operation of solenoid Plunger.
Must move in when energized.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 Vector – Engine Stalled

7. CHECK ENGINE RPM


a. Check actual engine RPM using hand held tachometer.
Adjust engine linkage setting as needed.
b. Compare actual RPM with those shown on display.
Both readings within ± 50 RPM.

8. CHECK ENGINE AIR–INTAKE SYSTEM


a. Check air filter indicator.
Flag must not be visible.
b. Inspect air intake system Hoses & tubes in good condition.
No kinks or restrictions

9. CHECK ENGINE EXHAUST SYSTEM


a. Inspect the exhaust system.
Must be clear and unobstructed

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 Vector – Engine Stalled
10. CHECK ENGINE
a. Check Injection pump timing.
Timing must be correct
b. Check engine valve adjustment.
Rocker arm clearance must be correct
c. Check engine compression.
Compression must be above 400 PSIG (27.2 Bar)

11. CHECK REFRIGERATION SYSTEM


a. Check discharge & suction pressures
Must be within normal operating range for conditions

12. CHECK ELECTRICAL SYSTEM FOR OVERLOAD


a. Generator or motor electrical overload (short to ground, phase to phase short).
Ohm the electrical components and circuits to ground.
Repair and replace damaged parts as necessary

13. CHECK SOFTWARE VERSION AND CONFIGURATIONS


a. Check unit software and configurations
Software must be the latest version.
Configuration must be the correct for the unit model

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 Vector – Alternator not charging

ALTERNATOR NOT CHARGING

• TRIGGER–ON:
Unit is running on either engine or standby and the current flow is more than
-1.0 amps (discharge) between the battery charger and the battery for 3 continuous
minutes.

• UNIT CONTROL:
Engine operation: alarm only or (if configured for shutdown)engine and unit shutdown and
alarm.
Standby operation: alarm only.

• RESET CONDITION:
Auto Reset (if not shut down) when alternator is charging if not shutdown or change unit to
standby operation or alarm may be manually reset via keypad or by turning the unit off,
then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 Vector – Alternator not charging
PLEASE NOTE:
There is 3 different version of battery charger

1. BLACK VERSION: 2 phases, without temp. sensor. 20 amps.


(Used on Vector 1800 till 1850)

2. ALUMINIUM VERSION: 2 phases with temp. sensor, 20 amps.


(Replaces the black version)

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 Vector – Alternator not charging
3. ALUMINIUM VERSION: 3 phases with temp. sensor, 40 amps

Implemented on Serial Numbers:


RC037035 for VECTOR 1850
ZC038004 for VECTOR 1550

IMPORTANT: Single phase battery charger 20 Amps its not interchangeable with the 3 Phase
battery Charger 40 Amps.

Note:
Always when mounting a new charger check the configuration, if it is configured to
“No temp. sensor, 1ph/20Amps or 3ph/ 40Amps”

If the right Battery cCharger is not selected it will interfere with the Start-Stop functioning
causing more fuel consumption
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 Vector – Alternator not charging
1. CHECK FUSES FOR BATTERY CHARGER
a. Check fuses (old units 2 fuses , new units 3 fuses)
Previous Layout

FUSE BATTERY CHARGER

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 Vector – Alternator not charging
1. CHECK FUSES FOR BATTERY CHARGER
a. Check fuses (old units 2 fuses , new units 3 fuses)
Latest Layout

FUSE BATTERY CHARGER

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 Vector – Alternator not charging
2. CHECK MICROPROCESSOR CURRENT SENSOR
a. Check micro current value Power up micro in PC Mode.
Must be -2.0 to 1.5A with no load.

3. CHECK WIRE DIRECTION THROUGH CURRENT SENSOR


a. Visually inspect wire at current sensor
Must go through current sensor in the direction of the arrow on the sensor toward F-5 (80A) fuse.

Current Sensor

Wire Direction Indicator

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 Vector – Alternator not charging
3. CHECK BATTERY CHARGER WIRING
a. Check output & ground wire (unit OFF) BATTERY CHARGER
Negative lead on Ground terminal
Positive lead on Output terminal = same as battery voltage.
b. Check battery charger input Must be between 350 VAC and 575 VAC
Must be between the two red Wires
c. Inspect harness & control box connector pins & terminals
No physical damage to harness.
No damaged or corroded pins
d. Check output wire (unit running)
Must have 13 or more VDC (when tested against -battery post)
e. Check ground wire (unit running)
Must have 13 or move VDC (when tested against +battery post)

4. CHECK FOR ADD–ON EQUIPMENT DRAWING TOO MUCH CURRENT


a. Check amperage of added–on components & accessories
All add–on components & accessories must draw less than 20 Amps

5. PERFORM PRE-TRIP CHECK


a. Run pre-trip & check for alarms.
Any active alarms must be corrected and cleared before proceeding.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A53 Vector – Box Temperature Out-of-Range
• TRIGGER–ON:
Alarm Only:
Condition One: If the unit is not running in Sleep Mode and Compartment One box
temperature has been in range ±1.5°C for perishable setpoints or ±1.5°C for frozen
Setpoints at least once since the unit was started and is now further away from setpoint
than the limit set in the functional parameters for the Out-of-Range Value 2°, 3°, or 4°C for
30 continuous minutes OR
Condition Two: If SAT is configured ON and Compartment One is running in cool and the
DeltaT (SAT minus RAT) is not greater than 0.5°C for 30 continuous minutes or if
Compartment One is running in heat and the SAT2 is not greater than the RAT2 for 30
continuous minutes. OR
Condition Three: If a shutdown alarm occurs and the RAT2 temperature is further away
from setpoint than the limit set in the functional parameters for the Out-of-Range value
2°, 3°, or 4°C for more than 30 continuous minutes regardless if Compartment One box
temperature has been in-range.

Shut Down & Alarm:


Condition One: When configured for shutdown the unit will shut down when the
conditions for Alarm Only Condition One are met for 45 continuous minutes.
Condition Two: When configured for shutdown the unit will shut down when the
conditions for Alarm Only Condition Two are met for 30 continuous minutes.
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A53 Vector – Box Temperature Out-of-Range

• UNIT CONTROL:
Engine and standby operation:
If the micro is configured for shutdown and the setpoint for Compartment 2 is in the
perishable range - unit shutdown and alarm.
If the micro is configured for shutdown and the setpoint for Compartment 2 is in the frozen
range, only Compartment 2 will shut off. Otherwise, alarm only.

• RESET CONDITION:
Auto Reset or Alarm may be manually reset via Keypad or by turning the unit off, then back
on again..

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A53 Vector – Box Temperature Out-of-Range

1. CHECK COMPARTMENT DOORS


a. Inspect all trailer compartment doors
Must be closed, no air leakage

2. DEFROST EVAPORATOR
a. Initiate Manual Defrost Cycle
Must terminate automatically.

3. CHECK FOR LOW REFRIGERANT PRESSURE ALARM


a. Check for alarm 18 Alarm.
Conditions must be corrected and the alarm cleared to continue

4. CHECK REFRIGERANT LEVEL


a. Visually check refrigerant level in receiver tank.
Must be at correct level.

5. CHECK EVAPORATOR AIRFLOW ALARM


a. Check for alarm 56.
Must be corrected and cleared to continue

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A53 Vector – Box Temperature Out-of-Range

6. PERFORM PRE-TRIP CHECK


a. Run pre-trip & check for alarms.
Any active alarms must be corrected and cleared before proceeding.

7. CHECK SYSTEM PRESSURES


a. Install Manifold Test Set and check system pressures.
Suction & Discharge Pressures must be in the normal range.
Suction & Discharge Pressures must have the same reading on gauges & on micro display.

7. CHECK EMPTY PALLETS OR CRATES, CAUSING A53 AND ALSO HIGH FUEL CONSUPTION
a. Remove empty pallets and Crates

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A60 Vector – Datalogger Time Wrong

DATALOGGER TIME WRONG

• TRIGGER–ON:
The real time clock in the Data Recorder does not contain a valid date.

• UNIT CONTROL:
Engine and standby operation: alarm only.

• RESET CONDITION:
Auto Reset when the Data Recorder Real Time Clock is reset, or alarm may be manually
reset by turning the unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A60 Vector – Datalogger Time Wrong
1. CHECK REAL TIME CLOCK
a. Check Real Time Clock in the Data List, or using Tru-Tech.
Must show correct date and time. Change as needed (Configuration List).

NOTE:
Datalogger date and time must be always correct.
In case quality department ask for a download of a specific date, if the date and time are incorrect it will be very
difficult to track the required data.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A60 Vector – Datalogger Time Wrong

2. RESET MICROPROCESSOR
a. Turn main switch off for 30 seconds, then turn on.
Microprocessor powers up OK
b. Check for valid Real Time Clock reading in Data Menu
Valid date and time in memory.
Alarm is cleared automatically
c. Real Time Clock can not be changed.
Replace microprocessor

3. MICROPROCESSOR DEFECTIVE
a. Download previous data using Download PC Card, or Tru-Tech.
Data retrieval OK
b. Replace microprocessor & set Configurations, Functional Parameters, Enter hours from
removed microprocessor, set Maintenance Hour Meters, and Data Recorder Setup.
New microprocessor in place

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A75 Vector – Compressor Motor Overheated

• TRIGGER–ON:
Compressor Motor Overheated (IPC) circuit is open.

• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.

• RESET CONDITION:
Auto Reset when motor overload input is within limits, or change to engine
operation, or alarm may be manually reset via keypad or by turning the unit off, then back
on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A75 Vector – Compressor Motor Overheated
1. CHECK FOR A-13 (CHECK DOWNLOAD)
a. A13 will always cause this alarm to activate
Review steps for A13 and correct if necessary. IP CONNECTIONS

2. CHECK FOR POWER AT MP1


a. If no power (0VDC)
Test IP circuit from compressor motor to microprocessor
b. If 12VDC
Continue troubleshooting

3. CHECK COMPRESSOR MOTOR CONTACTOR


a. Inspect the three contacts behind the top cover
If the contactor buttons are blue due to chattering caused by a defective compressor internal protection device,
replace the contactor.
b. Check tightness of the contactor wire connections
Tighten with screwdriver and check for discoloration of wires.

4. CHECK MOTOR OPERATION


a. Turn the unit ON in Engine or Standby mode
Check voltage and current on each phase (must be less than 22 amps)
b. If current is high
Run pre-trip to check if unloaders and current are excessive
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A100 Vector – Overload Ground Fault
• TRIGGER–ON:
The RS switch is ON and the overload and ground fault detector (OGF)is reading more
than 40 Amps on any A/C current leg OR there is A/C voltage leaking to ground of more
than 150 mAmps.

OGF

• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.

• RESET CONDITION:
Auto Reset in engine mode.
Alarm may be manually reset via Keypad or, alarm may be reset by turning the unit off,
then back on again.
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A100 Vector – Overload Ground Fault

1. CHECK FOR ELECTRICAL OVERLOAD


a. Check amp draw from GENCON if running on engine or PSCON2 if running on standby.
Must be less than 40 Amps
PSCON2 GENCON
2. CHECK FOR HIGH VOLTAGE SHORT TO GROUND
a. Check for ohm reading from T1, T2 and T3 of ALL
High voltage contactors to ground OGF
Reading must be greater than 25.000 Ohms

3. PERFORM PRE-TRIP CHECK


a. Run pre-trip Note during which test Alarm 100 occurs
b. Further test circuit from Step a.
If necessary use a megohmmeter to test

4. CHECK OVERLOAD / GROUND FAULT DEVICE


a. With the engine OFF and standby power disconnected,
turn the RS switch one of the compartment switches ON
Must have 12 VDC at HC19 and 2MP26

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A100 Vector – Overload Ground Fault

OGF

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A128 Vector – Unbalanced A/C Amps

• TRIGGER–ON:
If the compressor is on and AC Current Sensor 1 or 2 is less than 5 amps for 10 seconds OR
If the difference between AC Current 1 and AC Current 2 is greater than 10 amps for 10
seconds

• UNIT CONTROL:
Engine and standby operation: alarm only.

• RESET CONDITION:
Change unit to standby operation when AC Current Sensor 1 and 2 is greater
than 7 amps for 5 minutes AND difference between AC Current 1 and AC Current 2 is less
than 7 amps for 5 minutes OR alarm may be manually reset via keypad or by turning the
unit off, then back on again.

NOTE:
This alarm is activated usually when a contactor is not energized or is energized but the Fuse on AC 1 or
AC 2 are blown.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A128 Vector – Unbalanced A/C Amps

1. Perform Pre-trip Check


a. Run pre-trip & check for alarms
Any active alarms must be corrected and cleared before proceeding.

2. Check Current Draw


a. Use a clamp around A/C ammeter to check amps at power wires
Must be ±1.0 Amp of reading in Data List.
b. Check A/C amps with compressor running
Must be greater than 5 Amps.
c. Compare A/C Amp readings between L1-L2-L3
Maximum allowable difference is 10 Amps.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A128 Vector – Unbalanced A/C Amps

CURRENT TRANSFORMER

NOTE: A faulty Current Transformer will also activate the alarm 128

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Vector 1550 Troubleshooting

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Vector 1550 Troubleshooting

PREVIOUS CONTROL BOX LAYOUT

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Vector 1550 Troubleshooting

LATEST CONTROL BOX LAYOUT LATEST CONTROL BOX LAYOUT


WHIT STANDARD CONTACTORS WHIT ELECTRONIC CONTACTORS

WITH AUXILIARY RELAYS WITHOUT AUXILIARY RELAYS

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A22 Vector 1550 – Low Suction Superheat

LOW SUCTION SUPERHEAT

• TRIGGER ON:
"Check Suction Temperature Sensor" and/or "Check Evaporator Temperature Sensor"
alarms are not active (refer to alarm 127 and/or 131 first) and:
Compressor suction superheat (Compressor Suction Temperature (CST) minus saturated
temperature for Compressor Suction Pressure (CSP) is less than 5°C for more than 2
minutes.

• UNIT CONTROL:
Engine operation: Shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.

• RESET CONDITION:
Auto reset after 15 minutes, or alarm may be manually reset via keypad or by turning the
unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A22 Vector 1550 – Low Suction Superheat

1. CHECK SYSTEM PRESSURES


a. Install Manifold Gauges and check and compare compressor discharge, suction and
evaporator outlet pressure with those shown on the microprocessor display.
Pressures must have the same reading on gauges & on microprocessor display.

NOTE:
Microprocessor suction (CSP) and evaporator (EVOP) pressure readings have a maximum value of 7.5 bar (100 psig)
The actual suction pressure must be lower than 100 psig in order to perform this test.

2. CHECK EVAPORATOR SECTION


a. Check evaporator section, return air bulkhead, air chute, cleanliness of evap. coil and
airflow.

3. PERFORM PRE-TRIP CHECK


a. Clear Active Alarm list, then run Pre-trip & check for any new alarms.
Any active alarms must be corrected and cleared before proceeding.

4. CHECK EVXV
a. Check operation of EVXV

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A24 Vector 1550 – COMPRESSION RATIO EXCEEDED

COMPRESSION RATIO EXCEEDED

• TRIGGER ON:
If the compressor compression ratio is greater than 21:1 for 20 seconds.

• UNIT CONTROL:
Engine operation: Engine and unit shutdown and alarm.
Standby operation: Refrigeration system shutdown and alarm with PSCON still energized.

• RESET CONDITION:
Auto reset when compression ratio is less than 21 for 3 minutes or, alarm may be manually
reset via keypad or by turning the unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A24 Vector 1550 – COMPRESSION RATIO EXCEEDED

1. LOOK FOR HIGH DISCHARGE OR LOW SUCTION PRESSURE CAUSES.


Discharge and suction pressures must be in normal range for the current ambient and
refrigerated compartment temperature conditions.

NOTE:
A24 is a shut down alarm that will shut compressor down in the event the compression ratio has been higher than
>21:1 for 20 seconds.

If compression ratio >= 21:1 engage bypass mode (de-energize economizer solenoid valve (ESV) and energize
unloader bypass valve (USV).
This override will be active until the compression ratio is <= 19:1

Control Changes: Unit will switch from Economized to Bypass to reduce CR.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A27 Vector 1550 – High Suction Pressure

HIGH SUCTION PRESSURE

• TRIGGER ON:
The compressor is running and the suction pressure has been greater than 6.7 bar (98 psig)
for more than 10 minutes.

• UNIT CONTROL:
Engine operation: alarm only or (if configured for shut down) engine and unit shutdown
and alarm.
Standby operation: alarm only or (if configured for shutdown) refrigeration system
shutdown and alarm with PSCON still energized.

• RESET CONDITION:
Auto reset when suction pressure is less than 75 psig (5.1 bar) for 5 minutes and
configured for Alarm Only in standby operation or Auto Reset after 30 minutes if in engine
operation if configured as a Shutdown Alarm or, alarm may be manually reset via keypad or
by turning the unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A27 Vector 1550 – High Suction Pressure

1. CHECK SYSTEM PRESSURES


a. Install Manifold Test Set and check and compare compressor discharge & suction pressures
with those shown on the microprocessor.
Suction & Discharge Pressures must have the same reading on gauges & on microprocessor display.
Pressures must be in the normal range for ambient & refrigerated compartment temperature conditions.

NOTE:
Microprocessor suction (CSP) and evaporator (EVOP) pressure readings have a maximum value of 7.5 bar (100 psig).
The actual suction pressure must be lower in order to perform this test.

2. CHECK FOR REFRIGERANT OVERCHARGE


a. Check refrigerant level in the receiver.
Generally, level should be between upper & lower sight glasses with a refrigerated compartment temperature of
1.0°C or lower.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A27 Vector 1550 – High Suction Pressure
3. CHECK TRANSDUCER WIRING
a. Inspect transducer & connector pins & terminals. (See wiring schematic.)
No physical damage to sensor.
No damaged or corroded pins in plug or sensor.
b. Energize sensor circuit.
c. Check for voltage at the transducer plug between pins A (+) and B (ground).
Voltage should be approximately 12 VDC.

d. Reconnect the transducer plug.


Check for voltage between 1MP-29 and ground. CSP
Voltage should be greater than 0.24 VDC and less than 5 VDC.

4. PERFORM PRE-TRIP CHECK


a. Clear Active Alarm list, then run Pre-trip & check for any new alarms.
Any active alarms must be corrected and cleared before proceeding.

5. CHECK EVAPORATOR EXPANSION VALVE (EVXV)


a. Check operation of valve.

6. CHECK COMPRESSOR
a. Check compressor for excessive vibration or noise
Replace compressor

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A28 Vector 1550 – High Suction Pressure

CHECK REFRIGERATION SYSTEM

• TRIGGER ON:
The refrigeration system is running and the discharge pressure is less than 0.34 bar (5 psig)
higher than suction pressure for more than 30 seconds.

• UNIT CONTROL:
Engine operation: alarm only or (if configured for shutdown) engine and unit shutdown and
alarm.
Standby operation: alarm only or (if configured for shutdown) refrigeration system
shutdown and alarm with PSCON still energized.

• RESET CONDITION:
Auto reset when discharge pressure is more than 1.36 bar (20 psig) above the suction
pressure when in alarm only, or auto reset after 30 minutes when shutdown is configured
or alarm may be manually reset via keypad or by turning the unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A28 Vector 1550 – High Suction Pressure
1. VERIFY COMPRESSOR IS RUNNING.
a. Check compressor Amp draw - CCON T1-T2, T1-T3, T2-T3.
Check all three voltage legs.
Readings must be in the range.
Full Load Amps (FLA): 10.4 amps
CCON
2. CHECK SYSTEM PRESSURES
a. Install Manifold Gauges and check and compare compressor discharge & suction pressures
with those shown on the microprocessor display.
Suction pressure must be above 3 psig (0.2 bar)
Discharge pressure must be more than 5 psig (0.3 bar) higher than the suction pressure.
Suction & Discharge Pressures must have the same reading on gauges & on microprocessor display.

NOTE:
Microprocessor suction (CSP) and evaporator (EVOP) pressure readings have a maximum value of 100 psig (7.5 bar)
The actual suction pressure must be lower than 100 psig in order to per-form this test.

3. PERFORM PRE-TRIP CHECK


a. Clear Active Alarm list, then run Pre-trip & check for any new alarms.
Any active alarms must be corrected and cleared be-fore proceeding.

4. CHECK COMPRESSOR
a. Check compressor for excessive vibration or noise
Replace compressor
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A75 Vector 1550 – Compressor Motor Overload

• TRIGGER-ON:
If alarm A22, A27 and/or A28 was triggered with current below 5.5 amps, this alarm will
also trigger or on restart from alarm A22, A27 and/or A28 trigger on if compressor current
does not rise above 1 amp.

• UNIT CONTROL:
Engine operation: engine and unit shutdown and alarm.
Standby operation: refrigeration system shutdown and alarm with PSCON still energized.

NOTE:
The compressor motor is fitted with an internal line break that may have caused this alarm.
The line break is an auto reset device. Additional time may be required to reduce winding temperature to the reset
temperature of this device.

• RESET CONDITION:
Auto reset after 30 minutes alarm may be manually reset via keypad or by turning the unit
off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A75 Vector 1550 – Compressor Motor Overload

1. CHECK FOR A-22. A27 AND/OR A28 (CHECK DOWNLOAD)


a. A22, A27 and/or A28 will always cause this alarm to activate
Review steps for triggered alarms and correct if necessary.

2. CHECK COMPRESSOR OPERATION


a. Start unit.
Check voltage and current on each phase, must be greater than 0 and less than 16 amps.
(Compressor is operating.)

3. CHECK COMPRESSOR MOTOR CONTACTOR


a. Check condition and wiring
Repair/replace as required.

4. CHECK MOTOR WINDINGS


a. Check phase to phase
Full Load Amps (FLA): 10.4 amps
Winding Resistance: 2.26 Ohms per leg

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
X4 Troubleshooting

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
APX Module Locations

MMM

PCM

SVM DM

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
X4 Troubleshooting

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Drive Coupling

 The engine drives the compressor directly through a Drive Coupling


(nylon drive gear and compressor drive gear)

Nylon Drive Gear

Compressor Drive Gear

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Drive Coupling Inspection
Drive couple must be inspected every Service interval or Annually

1. Using a spark plug gap wire gauge set the tolerances of the coupling can be measured (image 1)
2. Insert the spark plug gap wire gauge between the Nylon coupling and the steel gear (Image 2)
You may have to slightly move the engine flywheel to ensure the steel drive teeth are to one side of the Nylon coupling

If you can insert a 0.030” (0.762mm) or larger gauge thickness in to the gap between the nylon coupling and the steel gear,

then the coupling will need replacing.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Drive Coupling Inspection
Drive couple must be inspected every Service interval or Annually

This procedure can be carried out with the coupling still installed to the unit (Image3).
If any work on the unit is needed and the compressor has to be removed the procedure can be carried out as in (Image 2)

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
Drive Coupling
Drive Gear

When installing a nylon drive gear, always:

a. Install with black dot facing steel gear.


NOTE: Nylon gear has a cut with a slight angle,
if installed backward there is a risk of premature failure.
b. Use new bolts and locking tabs included in drive gear kit.
c. Use Loctite or a similar thread locking compound
on threads of drive gear bolts.
d. DO NOT USE
Never-Seez or any other lubricating compound
on the nylon drive gear or compressor steel gear.
The gear must be assembled dry.
e. Torque the (6 bolt) nylon drive gear bolts
30 ft-lbs (40.6 Nm.)

BLACK DOT

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A13 X4 – High Discharge pressure

HIGH DISCHARGE PRESSURE

• ACTIVATION:
Compressor discharge pressure switch (HPS) contacts are open.
HPS contacts open when the discharge pressure rises to 465 psig (32 bar).

• UNIT CONTROL:
Shutdown and alarm.

• RESET CONDITION:
Auto reset after 15 minutes if the compressor discharge pressure falls below 350 psig
(24 bar), or alarm may be manually reset using the display mounted keys or by turning the
unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A13 X4 – High Discharge pressure

1. IF ALARM OCCURS DURING PRE-TRIP TEST 12, 13 OR 14


Check SV1 is opening.
During Pre-trip tests 12, 13 and 14, SV1 may be de-energized for 1 second to reduce discharge pressure.
If SV1 fails to actually open during the 1 second that it is de-energized this alarm may occur.
Repair SV1 as required.

2. CHECK SYSTEM PRESSURES


Install manifold gauge set and check and compare compressor discharge & suction
pressures with those shown in Unit Data.
If discharge pressure is in normal range, proceed to step 5.

3. CHECK AIRFLOW THROUGH RADIATOR & CONDENSER COIL


a. Inspect condenser & radiator. 90% or more of the coil surface must be undamaged.
Condenser/Radiator coil must be clean.
b. WASH THE CONDENSER WITH PRESSURIZED WATER
Water running out from the condenser must be clean
b. Check airflow (with unit running).
Even airflow through the entire coil. No “dead” spots

c. Check upper and lower fan belt tension & condition.


No Glazing, no cracking, no slipping.
Replace if required.
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A13 X4 – High Discharge pressure

CDT
4. CHECK REFRIGERANT CHARGE HIGH PRESSURE SWITCH
6,8 Kg R404a CDP
Must be correct.

5. CHECK HIGH PRESSURE SWITCH POWER AND WIRING


a. Inspect switch, connector pins & terminals.
No physical damage to switch.
No damaged or corrosion in connections.
b. Disconnect switch connector and check for power at the A position
(includes J1, SROS and SP−9).
Minimum 11 VDC.
If not, check connectors and wiring between terminals.
No damage, moisture or corrosion.
c. Check continuity from the switch connector B position to PCM−15 (includes SP−5).
Must have good continuity.
If not, check connectors and wiring between terminals.
No damage, moisture or corrosion.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A13 X4 – High Discharge pressure

6. CHECK HPS SWITCH


a. With discharge pressure below the switch closing pressure
Opens, on pressure rise, at : 465 +/- 10 psig (32 +/- 0.7 bar)
Closes, on pressure fall, at: 350 +/- 10 psig (24 +/- 0.7 bar)
Disconnect switch connector and check continuity across switch.
Switch must be closed.
b. Check switch operation.
Test switch

7. PERFORM PRE-TRIP
a. Run Pre-trip and check for alarms.
Any active alarms must be corrected and cleared before proceeding.

8. REFER TO REFRIGERATION TROUBLESHOOTING


a. Discharge pressure must be in range for the current ambient and refrigerated
compartment conditions.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A16 X4 - Battery Voltage to Low

BATTERY VOLTAGE TOO LOW

• ACTIVATION:
Voltage at the main microprocessor is less than 10 VDC
(except when the engine starter is engaged).

• UNIT CONTROL:
Shutdown and alarm. Alarm condition only if activated while starting unit.

• RESET CONDITION:
Auto reset after 15 minutes when the voltage at the main microprocessor is
between 11 - 14 VDC, or alarm may be manually reset using the display mounted keys or
by turning the unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A16 X4 - Battery Voltage to Low
NOTE:
Alarms, BATTERY LOW and ALTERNATOR NOT CHARGING
can be activated after replacing the starter motor, if the Ground sequence on the starter
motor bolt is not respected.

GROUND CONNECTIONS

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A16 X4 - Battery Voltage to Low

1. CHECK FOR ALARM 00051 (ALTERNATOR NOT CHARGING)


PCM
2. CHECK BATTERY VOLTAGE
a. Inspect battery cable ends and posts.
Must be clean and tight.
b. Test voltage at battery with unit off.
Must be above 11 VDC.
c. Test voltage at battery with unit running.
Must be above unit off reading (alternator charging).
d. Perform load test on battery.
Follow battery manufacturer’s procedure.

3. CHECK CONNECTIONS TO MAIN MICROPROCESSOR


a. Check connections at PCM-T1, T2 & T3. T1 T2 T3
No damage or corrosion at connections.
b. Check voltage reading at 3MM-23 & 3MM-34.
Must be above 11 VDC.
c. Check Unit Data voltage reading at unit display.
Must be within 0.5 VDC of reading obtained at 3MM-23 & 3MM-34.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A18 X4 – Low Refrigerant Pressure

Before any Refrigeration troubleshooting


the manifold gauges must be connected to the refrigeration system

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A18 X4 – Low Refrigerant Pressure

LOW REFRIGERANT PRESSURE

• ACTIVATION:
The compressor is operating with the suction pressure less than -3 psig (-0.20 bar) for
more than the LP SHUTDOWN DELAY Configuration (up to 5 minutes) with RAT above
-23.3°C or less than -8 psig (-0.53 bar) with RAT at any temperature.

• UNIT CONTROL:
Alarm only or (if configured for shutdown) shutdown and alarm.

• RESET CONDITION:
Auto reset after 15 minutes if suction pressure is more than -2 psig (-0.13bar) or alarm
may be manually reset using the display mounted keys or by turning the unit OFF,
then ON again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A18 X4 – Low Refrigerant Pressure

1. Check Airflow Through Evaporator Coil/Section


a. Inspect coil.
90% or more of the coil surface must be undamaged.
Coil must be clean.
b. Check airflow (with unit running).
Even airflow through the entire coil. No “dead” spots.
c. Check return air bulkhead, air chute.
Good air flow. Return air not restricted. Air chute in good condition.
d. Check fan clutch.
Must be fully engaged.
e. Check upper and lower fan belt tension & condition.
No Glazing, no cracking, no slipping.

2. Check Refrigerant Charge


Must be correct.

3. Check System Pressures


Install manifold gauge set and check and compare compressor discharge, suction and
evaporator outlet pressure to the Unit Data readings.
Suction pressure must be above −3 psig (−0.2 bar).

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A28 X4 – Check Refrigeration System
• ACTIVATION:
Condition 1 = When system has been operating in Pulldown for more than five minutes and
the delta-t (SAT - RAT) is between -1.7°C and +2.8°C.
Condition 2 = Discharge pressure is not at least 5 psig (0.34 bar) higher than suction
pressure for more than 10 minutes.

• UNIT CONTROL:
Condition 1 = If the DTT and/or SAT temperatures are cool enough to allow a defrost the
unit will go into defrost. Following the defrost, if activation criteria for Condition 1 reoccur
within 45 minutes of the defrost cycle, alarm or alarm and shutdown as Configured. If,
following the defrost and the 45 minute wait time the activation criteria for Condition 1
reoccur the unit will go into defrost again.
If the DTT and SAT temperatures are too warm to allow a defrost, alarm or alarm and
shutdown as Configured.
Condition 2 = Alarm or alarm and shutdown as Configured

• RESET CONDITION:
Auto reset when discharge pressure is more than 20 psig (1.26 bar) above the suction
pressure for five minutes, or alarm has been active and unit has been shutdown more
then 14 minutes or alarm may be manually reset using the display mounted keys or by
turning the unit off, then back on again.
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A28 X4 – Check Refrigeration System
1. CHECK COMPRESSOR DRIVE COUPLING
Verify that compressor coupling (nylon gear) is intact and the compressor crankshaft is
turning.
Repair as required.

2. CHECK SENSORS AND/OR TRANSDUCERS


Using an accurate temperature measurement device or pressure measurement device,
check SAT, RAT, CDP EVOP and CSP readings.
Readings must be the same on measurement device & Unit Data.

3. PERFORM PRE-TRIP CHECK


Clear Active Alarm list, then run Pre-trip & check for any new alarms.
Any active alarms must be corrected and cleared before proceeding.

4. CHECK COMPRESSOR.
a. Perform Pump-Down Test.
Must hold a vacuum and not equalize in a short period of time.
b. Cover condenser and build-up discharge pressure.
Must be able to raise pressure to 400 psig (27.2 bar).
c. Disassemble and inspect compressor valve plates, cylinder suction valves, cylinder
discharge valves and pistons, etc.
Must be intact, clean, and in good working order
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A30 X4 – Fail to Run minimum time

FAILED TO RUN MINIMUM TIME

• ACTIVATION:
If Configured STANDARD: The unit has shutdown on an alarm 3 times without having run
for at least 15 minutes between each shutdown (not including door switch shutdowns).
If Configured RAIL: The unit has shutdown on an alarm and attempted to restart for the
Configured number of times without having run for at least 15 minutes between each
shutdown (not including door switch shutdowns).

• UNIT CONTROL:
Alarm only or shutdown and alarm.

• RESET CONDITION:
Alarm may be manually reset using the display mounted keys or by turning the unit off,
then back on again.
If the Configuration is set to Rail Mode, this alarm will reset after 4 hours and a rail alarm
reset will be recorded in the data recorded. .

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A30 X4 – Fail to Run minimum time

1. CHECK FOR ALARMS


a. Check for shut down alarms.
Alarm conditions must be corrected and the alarm(s) cleared to continue.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A31 X4 – Fail to Start Auto Mode

FAILED TO START - AUTO MODE

• ACTIVATION:
The engine has tried to start three times unsuccessfully.

• UNIT CONTROL:
Shutdown and alarm.

• RESET CONDITION:
Alarm may be manually reset using the display mounted keys or by turning the
unit off, then back on again.
If the Configuration is set to Rail Mode, this alarm will reset after 4 hours.
Rail alarm reset will be recorded in the data recorder.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A31 X4 – Fail to Start Auto Mode

1. CHECK FOR ADDITIONAL ALARMS


If this alarm is activated in conjunction with other alarms
(00041,00072, 00078, 00079, 00080, 00085 or 00086) check F5 & 10.
Fuses must be good.
Replace fuse(s) as required, clear alarms, restart and check for repeat alarm(s).

2. CHECK FOR LOW FUEL LEVEL


Check fuel level in the fuel tank.
Add fuel as needed to the fuel tank.

3. CHECK FOR ALARMS


Check for the following alarms: 40 (Check Glow Plug), 35 (Check Starter Circuit)
Alarm conditions must be corrected and the alarm cleared to continue.

EPH (GLOW PLUG)

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A31 X4 – Fail to Start Auto Mode

4. CHECK ENGINE CONTROL UNIT (ENCU) AND FUEL SPEED ACTUATOR (FSA)
a. Check voltage from fuse F3 through PCM−34 and SP−6 to ENCU−22
Verify correct fuse.
Must have minimum 11 VDC with the battery connected and SROS in the OFF position.
b. Check voltage from 3MM-9 to ENCU−44.
Must have minimum 11 VDC with SROS in the START/RUN position.
If no: Energize the run relay output using component test mode and retest.
c. Check for ground at ENCU-19 and ENCUGND−A (at the battery negative cable connection).
Must have good ground.
If not: Check connectors and wiring between terminals.
No damage, moisture or corrosion.
Fuel Speed Actuator
d. Inspect fuel/speed actuator (FSA),
engine speed sensor (ENSSN) and engine speed control
unit (ENCU) connector pins & terminals.
No physical damage to components.
No damage or corrosion in connectors.
e. Check resistance & amp draw of FSA.
(2.8 Ohms ±10% @20°C)
(4 Amps Max)
f. Check FSA plunger.
Must move in and out freely Engine Speed Sensor
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A31 X4 – Fail to Start Auto Mode

5. CHECK ENGINE AIR-INTAKE SYSTEM


a. Check air cleaner indicator.
Flag must not be visible.
b. Inspect air intake system.
Hoses & tubes in good condition.
No kinks or restrictions.

6. CHECK FOR CORRECT ENGINE OIL


Check viscosity is correct for ambient conditions.

7. CHECK ENGINE EXHAUST SYSTEM


Inspect the exhaust system.
Must be clear and unobstructed.

8. CHECK ENGINE
Check engine compression.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A35 X4 – Check Starter Circuit

CHECK STARTER CIRCUIT

• ACTIVATION:
Engine speed fails to reach 50 rpm during 2 start attempts.

• UNIT CONTROL:
Shutdown and alarm.

• RESET CONDITION:
Alarm may be manually reset using the display mounted keys or by turning the
unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A35 X4 – Check Starter Circuit

1. CHECK STARTING SEQUENCE


Check to see if engine starts, runs for a few seconds then shuts off.
If NO: continue with Step 3.
If YES: check engine speed sensor. Refer to the procedure for alarm 00130.

2. CHECK FUSE
Check fuse F−10 Fuse must be good.
If required, replace fuse

3. CHECK STARTER SOLENOID CIRCUIT


a. Place SROS in the START/RUN position.
After buzzer sounds, check for power at the starter solenoid and 3MM-12.
Minimum 11 VDC. If not, check connectors and wiring between terminals.
No damage, moisture or corrosion.
b. Inspect wiring to starter motor. (See wiring schematic)
No physical damage to wiring or battery cable end.
No damage or corrosion in connections.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A35 X4 – Check Starter Circuit

4. CHECK STARTER
a. Inspect starter and wiring. (See wiring schematic)
No damage or corrosion. Wiring and battery cable must be clean and tight
b. Check voltage to starter motor.
Must be above 10 VDC while cranking.
c. Check resistance of starter motor.
(Less than 1 ohm but more than 0)
d. Check amperage draw of starter.
(270 – 380 amps)

5. CHECK BATTERY VOLTAGE


a. Inspect cable ends and posts.
Must be clean and tight, no corrosion.
b. Test voltage at battery with unit off.
Minimum 11 VDC.
c. Perform load test on battery.
Follow battery manufacturer’s procedure.

STARTER CONNECTIONS

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A35 X4 – Check Starter Circuit
6. CHECK ENGINE CONTROL UNIT (ENCU) AND FUEL SPEED ACTUATOR (FSA)
a. Check voltage from fuse F3 through PCM−34 and SP−6 to ENCU−22
Verify correct fuse. Must have minimum 11 VDC with the battery connected and SROS in the OFF position.
b. Check voltage from 3MM-9 to ENCU−44.
Must have minimum 11 VDC with SROS in the START/RUN position.
If no: Energize the run relay output using component test mode and retest.
c. Check for ground at ENCU-19 and ENCUGND−A (at the battery negative cable connection).
Must have a good ground connection.
If not: check connectors and wiring between terminals. No damage, moisture or corrosion.
d. Inspect fuel/speed actuator (FSA), engine speed sensor (ENSSN) and engine speed control
unit (ENCU) connector pins & terminals.
No physical damage to components.
ENCU FSA
No damage or corrosion in connectors.
e. Check resistance & amp draw of FSA.
(2.8 Ohms ±10% @20°C)
(4 Amps Max)
f. Check FSA plunger.
Must move in and out freely.

7. CHECK FOR CORRECT ENGINE OIL


Check viscosity is correct for ambient conditions.
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A38 X4 – Check High Speed RPM

CHECK HIGH SPEED RPM

• ACTIVATION:
The control system is calling for high speed operation, and engine speed is less than
1650 rpm, or greater than 1950 rpm for more than 60 seconds (120 seconds when the
control system calls for a change from low to high speed, or when unit first starts).

• UNIT CONTROL:
Alarm only.

• RESET CONDITION:
Auto reset if control system is calling for high speed operation and the speed is within 1670
and 1930 rpm for 60 seconds or alarm may be manually reset using the display mounted
keys or by turning the unit off, then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A38 X4 – Check High Speed RPM

1. Force High Speed Operation


Place unit in continuous run, adjust setpoint below -12°C and set the Air Flow Functional
Parameter to HIGH.
System should run in high speed. (If not, check speed overrides, NEXT SLIDE.)
Ensure System is calling for high speed when performing steps 3 & 4.

2. Check Engine Speed


a. Check actual engine speed using hand held tachometer.
Speed must be within range shown above.
b. Compare actual speed with that shown in Unit Data.
Readings within ± 50 rpm.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A38 X4 – Check High Speed RPM (Speed Overrides)

1. High Ambient.
If ambient temperature is 48.9°C or above during the engine starting sequence, the unit will run in low speed for the
first 2 minutes of operation.
This applies to Heat and Cool modes only - not Defrost.

2. Low Suction/High Discharge Pressure.


If UL1 has unloaded and the suction pressure is less than 3 PSIG (0.2 bar) for at least 20 seconds or the discharge
pressure is greater than the calculated maximum for more than five seconds, the engine will be forced to run in low
speed for a minimum of five minutes.
After five minutes, the engine can return to high speed if suction pressure is greater than 3 PSIG (0.2 bar) for 30 seconds
or discharge pressure is less than the calculated maximum for 30 seconds.

3. Engine Coolant Warm-Up.


The engine will run in low speed until the coolant is above 26°C.

4. Defrost.
The engine Is generally in high speed but will run in low speed during the high ambient pump down and at the end of
the defrost cycle while the refrigerant control solenoids are realigned.

5. Door/Remote Switch Configuration.


If the DOOR/REMOTE SWITCH Configuration is set for low speed, the engine will run in low speed when the
door/remote switch is open/active.

6. RAT & SAT Alarms.


When the A122 - “CHECK RETURN AIR SENSOR” and A123 - “CHECK SUPPLY AIR SENSOR” alarms are both active at the
same time the control system will enter Cargo Protect Mode.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A38 X4 – Check High Speed RPM (Speed Overrides)

7. Frozen Setpoint Override.


If the setpoint is in the frozen range and the temperature is below setpoint, the engine will operate in low speed.

8. Air Flow.
When operating with a perishable setpoint and the AIR FLOW Functional Parameter is set to HIGH, the engine will
operate in high speed.

9. Product Shield High Air.


The engine is forced to high speed if the PRODUCT SHIELD HIGH AIR Configuration is active, refer to Section 4.10.3

10. High Speed Delay.


Whenever the engine starts, the unit will remain in low speed according to the Continuous or Start-Stop High Speed
Delay Functional Parameter setting.

11. Start-Stop Frozen Range.


When in Start-Stop Operation with a setpoint in the frozen range after the minimum run time has expired, the engine
will be forced to high speed if the refrigerated compartment temperature is not yet down to setpoint.

12. High Speed Delay.


Whenever the engine is in low speed, transition to high speed will be delayed for the HIGH SPEED DELAY Configuration
setting.

13. Range Protect.


When the unit is operating in Range Protect and the compartment temperature is inside the protected range, while all
other conditions to allow an off cycle are not met the engine will operate in low speed.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A38 X4 – Check High Speed RPM

3. Check Fuel/Speed Actuator (FSA)


Check FSA plunger.
Must move in and out freely, refer to engine manual.

4. Check Engine Air-Intake System


a. Check air cleaner indicator.
Flag must not be visible.
b. Inspect air intake system. Hoses & tubes in good condition.
No kinks or restrictions.

5. Check Engine Exhaust System


Inspect the exhaust system.
Must be clear and unobstructed.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A39 X4 – Check Engine RPM

CHECK ENGINE RPM

• ACTIVATION:
Alarm 00130(Check Engine Speed Sensor) is not active and engine speed is less than 1200
rpm or greater than 1950 for 5 minutes.

• UNIT CONTROL:
Alarm only or (if configured for shutdown) shutdown and alarm.

• RESET CONDITION:
Auto reset if engine speed is within the specified range for 5 minutes or alarm
may be manually reset using the display mounted keys or by turning the unit off, then back
on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A39 X4 – Check Engine RPM

1. CHECK FUEL/SPEED ACTUATOR (FSA)


Check FSA plunger.
Must move in and out freely, refer to engine manual.

2. CHECK ENGINE AIR-INTAKE SYSTEM


a. Check air cleaner indicator.
Flag must not be visible.
b. Inspect air intake system.
Hoses & tubes in good condition.
No kinks or restrictions.

3. FORCE LOW SPEED OPERATION


Set the High Speed Delay Functional Parameter to 10 minutes and restart unit.
System should run in low speed. (If not, check speed overrides, Slides.)
Ensure System is calling for low speed when performing step 4.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A39 X4 – Check Engine RPM

4. CHECK LOW SPEED ENGINE RPM


a. Check actual engine speed using hand held tachometer.
Speed must be within range provided above.
b. Compare actual speed with that shown in Unit Data.
Readings within ± 50 rpm.

5. FORCE HIGH SPEED OPERATION


Place unit in continuous run, adjust setpoint above -12°C and set the Air Flow Functional
Parameter to HIGH.
The System should run in High Speed. (If not, check speed overrides, Slides.)
Ensure System is calling for high speed when performing step 6.

6. CHECK HIGH SPEED ENGINE RPM


a. Check actual engine speed using hand held tachometer.
b. Compare actual speed with that shown in Unit Data.
Both readings within ± 50 rpm.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 X4 – Engine Stalled

• ACTIVATION:
The control system is calling for the engine to run, Engine speed sensor is good, and
engine speed is less than 10 rpm; or the A00130 (Check Engine Speed Sensor) alarm is ON,
and the Oil Pressure switch contacts are open.

• UNIT CONTROL:
Shutdown and alarm.

• RESET CONDITION:
Auto Restart after 15 minutes, or Alarm may be manually reset using the display mounted
keys or by turning the unit off, then back on again.

INLET STRAINER

NOTE: Common failure is the strainer blocked in fuel inlet


CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 X4 – Engine Stalled

1. CHECK FOR ADDITIONAL ALARMS


a. If this alarm is activated in conjunction with other alarms (00031, 00072, 00078, 00079,
00080, 00085 or 00086) check F5 & F10.
Fuses must be good.
Replace fuse(s) as required, clear alarms, restart and check for repeat alarm(s).

2. CHECK FOR ALARM 00130 (CHECK ENGINE SPEED SENSOR)


a. Check for alarm 00130. When alarms 00130 and 00041 occur at the same time, generally
the engine has run out or is running out of fuel.
This causes the engine speed to surge and drop.
Check fuel tank and add fuel as necessary.
Check fuel lines between the fuel tank and the fuel pump inlet for air leakage.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 X4 – Engine Stalled

3. CHECK START/RUN-OFF SWITCH & CIRCUIT


a. Check SROS.
Must be in the START/RUN position
b. Check two way communication equipment.
Must be set to allow operation and calling for operation.

4. CHECK FUEL SYSTEM


a. Check for Alarm 00001(Low Fuel Level Warning) SROS
Fill tank as needed.
b. Check fuel flow. BLEEDING SCREW
Unrestricted fuel flow through system.
Pump screen(s) clean.
Fuel not gelled.
c. Check fuel system prime.
No air in fuel system.

MANUAL FUEL PUMP

INLET FILTER

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 X4 – Engine Stalled

5. CHECK ENGINE CONTROL UNIT (ENCU) AND FUEL SPEED ACTUATOR (FSA)
a. Check voltage from fuse F3 through PCM−34 and SP−6 to ENCU−22
Verify correct fuse.
Must have minimum 11 VDC with the battery connected and SROS in the OFF position.
b. Check voltage from 3MM-9 to ENCU−44.
Must have minimum 11 VDC with SROS in the START/RUN position.
If no, energize the run relay output using component test mode and retest.
c. Check for ground at ENCU-19 and ENCUGND−A (at the battery negative cable connection).
Good ground. If not, check connectors and wiring between terminals.
No damage, moisture or corrosion.
d. Inspect fuel/speed actuator (FSA), engine speed sensor (ENSSN) and engine speed control
unit (ENCU) connector pins & terminals.
ENCU FSA
No physical damage to components.
No damage or corrosion in connectors.
e. Check resistance & amp draw of FSA.
(2.8 Ohms ±10% @20°C)
(4 Amps Max)
f. Check FSA plunger.
Must move in and out freely.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 X4 – Engine Stalled

6. CHECK ENGINE SPEED SENSOR (ENSSN)


Inspect harness, connector pins & terminals. (See wiring schematic Section 10.)
No physical damage to harness.
No damage, moisture, or corrosion in connectors.

7. CHECK ENGINE AIR-INTAKE SYSTEM


a. Check air cleaner indicator.
Flag must not be visible.
b. Inspect air intake system.
Hoses & tubes in good condition.
No kinks or restrictions.

8. CHECK ENGINE EXHAUST SYSTEM


Inspect the exhaust system.
Must be clear and unobstructed.

Engine Speed Sensor Fuel Speed Actuator

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A41 X4 – Engine Stalled

9. CHECK ENGINE
a. Check Injection pump timing.
Timing must be correct.
b. Check engine valve adjustment.
Rocker arm clearance must be correct.
c. Check engine compression.
Compression must be above 400 psig (27.2 bar).

10. CHECK REFRIGERATION SYSTEM


Check discharge & suction pressures.
Must be within normal operating range for conditions.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 X4 – Alternator not charging

• ACTIVATION:
Unit is running and the current flow is more than -1.0 amps (discharge) between the
alternator and the battery for 3 continuous minutes.

• UNIT CONTROL:
Alarm only or if Alternator Check Shutdown Configuration is set to “YES” shutdown
and alarm.

• RESET CONDITION:
Auto reset (if not shutdown) when alternator is charging or alarm may be
manually reset using the display mounted keys or by turning the unit off,
then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 X4 – Alternator not charging
NOTE:
Alarms, BATTERY LOW and ALTERNATOR NOT CHARGING
can be activated after replacing the starter motor, if the Ground sequence on the starter
motor bolt is not respected.

GROUND CONNECTIONS

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 X4 – Alternator not charging
1. CHECK WATER PUMP/ALTERNATOR BELT
Check belt tension & condition No Glazing, no cracking, no slipping.
Replace if required

2. CHECK CURRENT TRANSFORMER (CT)


a. Check current value.
Power up control system in PC Mode.
Check Unit Data.
Must be -2.0 to 1.5A with no load.
b. Check CT power from main microprocessor.
+5 VDC from terminal 2MM-29 to PCM-31
c. Check CT ground to main microprocessor.
Check wiring from terminal 2MM-23 to PCM-30
d. Check CT signal to main microprocessor.
Check wiring from terminal 2MM-12 to PCM-29.

3. CHECK ALTERNATOR WIRING & OUTPUT


a. Check output & ground wiring (unit OFF).
Ground from alternator G terminal to PCM-T2
Positive from alternator B+ terminal to PCM-T3
b. Check output (unit running).
When the unit is started, voltage at the battery will begin near 12.0 VDC,
and slowly rise toward 13.5 VDC as the battery charges.
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A51 X4 – Alternator not charging
4. CHECK FOR ADD-ON EQUIPMENT DRAWING TOO MUCH CURRENT
Check amperage of added-on components& accessories.
Total current draw including the actual unit current draw and all add-on components & accessories must be less
than alternator rating.

5. PERFORM PRE-TRIP CHECK


Clear Active Alarm list, then run Pre-trip & check for any new alarms.
Any active alarms must be corrected and cleared before proceeding

CONTINUOUS DIESEL COOL

INTELLISET PRETRIP HOUR UNIT


METERS DATA

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A23100 X4 – NO COMM FROM MICRO TO OUTPBD1

NO COMM FROM MICRO TO OUTPBD1

• ACTIVATION:
Main microprocessor cannot communicate internally.

• UNIT CONTROL:
Shutdown all modules except the display and alarm.
(The alarm will only display if the display module is communicating.)
Main microprocessor status LED will illuminate steady green (not pulsing).

• RESET CONDITION:
Auto reset when internal communication is restored, alarm reset or alarm may be manually
reset by turning the unit off, then back on again..

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A23100 X4 – NO COMM FROM MICRO TO OUTPBD1

1. REPLACE MAIN MICROPROCESSOR


Download data and replace main microprocessor.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A03001 X4 – Engine Load Calibration

ENGINE LOAD CALIBRATION

• ACTIVATION:
Activate alarm if:
Condition 1 = At engine start if the engine throttle sensor value is less than 90 %.
Condition 2 = After start if the sensor value does not drop below 90% within 5 seconds.
Condition 3 = At engine shutoff if the sensor value does not drop below 10% within 5
seconds.

• UNIT CONTROL:
Alarm only. Control system will modulate CSMV and activate unloaders as required.

• RESET CONDITION:
Alarm may be manually reset using the display mounted keys or by turning the unit off,
then back on again.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A03001 X4 – Engine Load Calibration

NOTE:
This alarm can be activated if the Small cable from the Starter to ENCU-21 is connected on the
wrong connection of the starter together with the battery cable.

CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED


Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation
A03001 X4 – Engine Load Calibration

1. Check Sensor Power And Wiring


a. Inspect sensor, connector pins & terminals.
No physical damage to sensor.
No damaged or corrosion in connections.
b. If required, power sensor by placing the unit in PC Mode, check for power.
Voltage reading between connector position 1 (positive) and position 3 (negative) should be 5 volts DC.
Check connectors and wiring between terminals.
No damage, moisture or corrosion.
c. Check for continuity from connector terminal 3 to ENCU−7 Good continuity.
If not, check connectors and wiring between terminals.
No damage, moisture or corrosion.

2. Replace Sensor
Replace sensor with know good component.
Calibrate sensor and ENCU.

RPS
CARRIER PROPRIETARY & CONFIDENTIAL - NO COPYING OR DISTRIBUTION PERMITTED
Any unauthorized reproduction, disclosure, or distribution of copies by any person of any portion of this work may be a viola tion of copyright laws, could result in the awarding of damages for infringement, and may result in further civil and criminal p enalties. All rights reserved. © 2014 Carrier Corporation

You might also like