Professional Documents
Culture Documents
CITIMAX SERIES
500, 700
2
62-69091-00
4.6.3 Checking the refrigerant charge ................................................................................... 39
4.7 REPLACING THE COMPRESSOR ....................................................................................... 39
4.8 CHECKING AND REPLACING FILTER DRIER .................................................................... 40
4.9 CHECKING AND REPLACING HIGH PRESSURE CUTOUT SWITCH ............................... 40
4.9.1 Replacing high pressure cutout switch ........................................................................ 40
4.9.2 Checking high pressure cutout switch ......................................................................... 40
4.10. CHECKING AND REPLACING FAN MOTOR BRUSHES .................................................. 41
4.11 EVAPORATOR COIL-CLEANING ....................................................................................... 41
4.12 CONDENSER COIL-CLEANING ......................................................................................... 41
4.13 HOT GAS (TWO-WAY) SOLENOID AND CONDENSER CLOSING SOLENOID (TWO WAY)
...................................................................................................................................................... 42
4.13.1 Replacing solenoid coil .............................................................................................. 42
4.13.2 Replacing solenoid valve internal parts ..................................................................... 42
4.14 ADJUSTING THE COMPRESSOR PRESSURE REGULATING VALVE (CPR) ............... 42
4.15 THERMOSTATIC EXPANSION VALVE .............................................................................. 43
4.16 MICROPROCESSOR ........................................................................................................... 44
SECTION 5 .......................................................................................................................................... 47
TROUBLE SHOOTING ....................................................................................................................... 47
5.1 REFRIGERATION .................................................................................................................. 47
5.1.1 Unit will not cool ........................................................................................................... 47
5.1.2 Unit runs but has insufficient cooling ........................................................................... 47
5.1.3 Unit operates long or continuously in cooling .............................................................. 47
5.1.4 Unit will not heat or heating insufficient........................................................................ 48
5.1.5 Defrost malfunction ...................................................................................................... 48
5.1.6 Abnormal pressure ....................................................................................................... 48
5.1.7 Abnormal noise ............................................................................................................ 49
5.1.8 Cab command malfunction .......................................................................................... 49
5.1.9 No evaporator air flow or restricted air flow ................................................................. 49
5.1.10 Expansion valve malfunction..................................................................................... 50
5.1.11 Malfunction hot gas (two-way) solenoid ..................................................................... 50
5.2 Fault alarm ............................................................................................................................. 51
5.2.1 EE alarm ....................................................................................................................... 51
5.2.2 BAT alarm ..................................................................................................................... 52
5.2.3 Err alarm ....................................................................................................................... 52
5.2.4 A01/A02 alarm .............................................................................................................. 53
5.2.5 A04 alarm ..................................................................................................................... 54
5.2.6 A06 alarm ..................................................................................................................... 54
5.2.7 A07 alarm ..................................................................................................................... 55
5.2.8 A09 alarm ..................................................................................................................... 55
5.2.9 A11 alarm ..................................................................................................................... 56
SECTION 6 .......................................................................................................................................... 57
EXTRACT FROM MATERIAL SAFETY DATA BULLETIN ................................................................. 57
6.1 POE OIL.................................................................................................................................. 57
6.2 FORANE R404A/R134a ......................................................................................................... 59
SECTION 7 .......................................................................................................................................... 62
ELECTRICAL SCHEMATIC WIRING DIAGRAMS.............................................................................. 62
3
62-69091-00
SECTION 1
SAFETY INSTRUCTIONS
This manual contains safety and service instructions to follow in order to prevent any accident.
Stickers have been placed on the product for your safety.
Working at height:
Take all necessary safety precautions when accessing this refrigeration unit:
use safe ladders, working platforms with appropriate guards.
4
62-69091-00
Electricity:
When this refrigeration unit is running in electrical operation, some devices
are powered up especially in the electrical control box.
Before servicing refrigeration unit, make sure the main power is on the
DISCONNECTION position. Ensure this refrigeration unit is disconnected
from battery. Lock–out / Tag–out can be performed as described above.
Before working in the electrical control box, it is required to control the
lack of tension.
WHEN IT IS NECESSARY TO WORK IN THE ELECTRICAL
CONTROL BOX UNDER TENSION, PEOPLE MUST BE QUALIFIED
FOR WORKS UNDER LOW OR HIGH VOLTAGE.
Always use adequate tools and Personal Protective Equipment when
working on electrical devices: safety gloves and safety glasses.
Refrigerant:
The refrigerant contained in this refrigeration unit can cause frostbite, severe
burns or blindness in case of projection and direct contact with the skin or
eyes. In contact with flame or heat refrigerant generate toxic gas.
Refrigerant handling must be done by qualified people. Keep any flame, any
lighted object or any source of sparks away from the refrigerant unit.
Always use Personal Protective Equipment when handling refrigerant:
safety clothes, safety gloves and safety glasses.
Cuttings:
Beware when handling or operating closed from parts that could be sharp
(coils, evaporators, clamps for example).
Always use adequate safety gloves when doing any maintenance on this
refrigeration unit.
Environment:
Think about protection of environment during all the life of this
refrigeration unit. To prevent environmental damages NEVER release
refrigerant in the atmosphere, NEVER throw coolant, oil, battery and
chemicals in the nature. It must be recuperate and recycle according to
current regulations. When disposing this refrigerant unit do it in an
environmentally sound way and in accordance with current regulations.
5
62-69091-00
CAUTION
Under no circumstances should anyone attempt to repair the Logic or Display Boards. Should a
problem develop with these components, contact your nearest Carrier Transicold dealer for
replacement.
Under no circumstances should a technician electrically probe the processor at any point, other
than the connector terminals where the harness attaches. Microprocessor components operate at
different voltage levels and at extremely low current levels. Improper use of voltmeters, jumper
wires, continuity testers, etc. could permanently damage the processor.
Most electronic components are susceptible to damage caused by electrical static discharge
(ESD). In certain cases, the human body can have enough static electricity to cause resultant
damage to the components by touch. This is especially true of the integrated circuits found on the
truck/trailer microprocessor.
6
62-69091-00
SECTION 2
DESCRIPTION
2.1 INTRODUCTION
R-134a Weight
Model compressor
LB KG Evaporator Condenser
CITIMAX 500 R134a 8.82 4.0 TM21 35kg 58kg
7
62-69091-00
8
62-69091-00
Figure 2-1 CITIMAX 500 condenser
9
62-69091-00
Figure 2-2 CITIMAX 500 evaporator
10
62-69091-00
11
62-69091-00
Figure 2-3 CITIMAX 700 condenser
12
62-69091-00
Figure 2-4 CITIMAX 700 evaporator
13
62-69091-00
Figure 2-5 Electrical control box of CITIMAX
14
62-69091-00
2.2 COMPRESSOR REFERENCE DATA
Model TM 16 TM 21 TM21
R404A R404A R134a
Unit type
CITIMAX 500 CITIMAX 700 CITIMAX 500
Discharge volume 163 cc 215cc 215cc
Cylinder number 6 10 10
Weight 7 .1 kg 8.1 kg 8.1kg
Refrigerant oil volume 450 ml 490ml 490ml
Refrigerant oil type POE EAL 68 POE EAL 68 POE EAL 68
15
62-69091-00
2.4 ELECTRICAL DATA
Operating
Bearing lubrication Horse power Speed
current
12V factory lubricated 93W 8-11A 2800rpm
Operating
Bearing lubrication Horse power Speed
current
12V factory lubricated 89W 8-10A 2200rpm
ft-lb 22 13 7 7 13 18 44~60
16
62-69091-00
2.6 SAFETY DEVICES
System components are protected from damage caused by unsafe operating conditions by
automatically shutting down the unit when such conditions occur. This is accomplished by the
safety devices listed in Table 2-2.
Automatic
Unsafe Conditions Safety Devices restart with Device setting
fault cleared
Cutoff:
-0.2±0.19 bar
1. Excessive drop in (R404A)
low pressure switch YES
pressure -0.45±0.21 bar
(R134a)
Timer 5mn
2. Excessive current fuse on electronic board(refer to Table 2-
NO refer to Table 2-3、2-4
draw control circuit 3、2-4)
3. Excessive current
draw evaporator fan Motor fuse(refer to Table 2-3、2-4) No refer to chart 2-3、2-4
motor
4. Excessive current
draw condenser fan Motor fuse(refer to chart 2-3、2-4) No refer to Table 2-3、2-4
motor
Cutoff:
5. Excessive
compressor discharge High pressure switch (HP1) YES 32 bar (R404A)
pressure 24.5 bar (R134a)
Timer 5 mn
Fuse Refer to Table 2-3、2-
6. Current over load NO
(refer to Table 2-3、2-4) 4
Cutout/cut-in
8. Low battery
Microprocessor YES 10V for 12V unit
voltage
20V for 24V unit
17
62-69091-00
2.6.1 Fuses
Table 2-3 Fuse-CITIMAX 500/700 12VDC
Fuse
500 1A 70A 20A 20A 20A 25A / 10A
capacity
Fuse
700 1A 80A 20A 20A 20A 25A 25A 10A
capacity
Fuse
500 1A 50A 15A 15A 15A 20A / 7.5A
capacity
Fuse
700 1A 50A 15A 15A 15A 20A 20A 7.5A
capacity
notes:
(a) The fuse is located near the ignition switch in drive cab.
(b) The fuse is located in electrical control box.
(c) The fuse is located close to the vehicle battery.
18
62-69091-00
2.7 CAB Control description 7. + key
This functional accessory simplifies all
control operations. From your seat, you 8. OFF key
can carry out all the control operations:
shut-down, automatic start-up, adjusting 9. ON key
the set point, defrost, program to
10. Unit operation display
customize unit operation to your own Green (left half):
requirements, manage error messages in Green led ON : cooling
event of malfunction. mode Green led OFF: null
mode (regulation)
You can display the box temperature and Green led flashing: heating
see whether the set point is being mode
Red : malfunction (right
maintained by checking the green
half)
indicator. The indicator lights up red in
the event of malfunction. When the 2.7.1 Operation principal
battery voltage is too low, a fail-save
CITIMAX 500 / 700 are powered on
safety system shuts down the unit. Unit
Road mode by the vehicle battery
restart is automatic and time-delayed if
(alternator)
the voltage rises to the normal level.
After starting up, the refrigeration unit
19
62-69091-00
out during regulation. When transporting In the event of difficulty on start up,
fragile loads such as fresh meat, check that:
vegetables and cheese, it is possible to -The main road fuse has not blown. If it
program the microprocessor to obtain is ok, contact your Carrier Service centre
continuous ventilation by the evaporator -The temperature selected by the cab
during regulation. control has not been affected.
20
62-69091-00
1. Press the key to shut-down the keys to display minimum setpoint.
unit.
2. Press the or key to change
2. Press simultaneously the AND minimum setpoint: 0°C, -20°C or -29°C
(default value -29°C).
keys during 5 seconds to display
last selected defrost interval. 3. Press the key to display
differential parameter.
3. Press the or key to change
the defrost time: 4. Press the or key to adjust the
10 to 45 mn: increase or decrease time differential value: Dif1 (1°C), Dif2
(10, 15, 20, 25, 30 and 45) (2°C), Dif3 (3°C) (default value Dif2).
21
62-69091-00
–ACTIVE malfunctions – AXX
An alarm is active when a problem occurs on the unit, the red LED is flashing speedily.
b. Direct display
Note
Direct display malfunction messages are displayed instead of temperature read-out
as soon as the malfunction is detected, and remain displayed as long as malfunction
persists.
The unit does not run until the malfunction has disappeared or been corrected.
Programming mistake of
Err the maximum setpoint by No - Setpoint
user
Setpoint lower that
--- maximum setpoint but in No - Setpoint
the range -29°C / +30°C
22
62-69091-00
2.8 COMPRESSOR PRESSURE receiver. The refrigerant then flows through
the filter-drier, where an absorbent keeps it
REGULATING VALVE
dry and clean. The refrigerant then flows
This CPR valve is installed on the suction through a sight glass with moisture
line of compressor to limit the suction and indication and then to the liquid / gas heat
then avoid overloading of compressor. For exchanger.
CPR settings refer to section 2.3. The liquid enters to the thermostatic
The suction pressure is controlled to avoid expansion valve (with external pressure
overloading engine during high box equalizer) which regulates the flow rate of
temperature operation. refrigerant towards the evaporator in order
to obtain maximum use of the evaporator
2.9 HOT GAS SOLENOID – HGV heat transfer surface.
(TWO-WAY) The evaporator tubes have aluminium fins to
The hot gas solenoid is normally closed (NC) increase heat transfer; therefore heat is
and is only powered in defrost and heating removed from the air circulated through the
modes and 40 seconds before start-up if box evaporator. This cold air is circulated
temperature is higher than –5ºC. throughout the truck to maintain the box at
the desired temperature.
2.10 CONDENSER CLOSING The transfer of heat from the air to the low
SOLENOID –MHV (TWO-WAY) temperature liquid refrigerant causes the
liquid to vaporize. The steam at low
The condenser closing solenoid is normally
temperature and pressure enters the heat
open (NO) in cooling mode. It is closed in
exchanger then enters the compressor
defrost and heating mode to increase the
pressure regulating valve (CPR) which
capacity.
regulates refrigerant pressure entering the
compressor, where the cycle starts over.
2.11 REFRIGERANT CIRCUIT
DURING COOLING The discharge pressure is regulated with
HP2. For refrigerant R404a If P>22 bars
When cooling, the unit operates as a vapor
HP2 is switch on and the fan works. When
compression refrigeration system. The main
the pressure decreases at 17 bars, HP2 is
components of the system are the
switch off and the fan is off.
reciprocating compressor, air-cooled
condenser, thermostatic expansion valve, For refrigerant R134a If P>12 bars, HP2 is
evaporator, and hot gas solenoid (two-way). switch on and the fan works. When the
pressure decreases at 9 bars HP2 is switch
The compressor raises the pressure and
off and the fan is off.
temperature of the refrigerant and forces it
into the condenser tubes.
The condenser fan circulates surrounding air
2.12 REFRIGERANT CIRCUIT
over the outside of the condenser tubes. Heat DURING HEAT AND DEFROST
transfer is thus established from the When refrigerant vapor is compressed to a
refrigerant gas (inside the tubes) to the air high pressure and temperature in a
condenser (flowing over the tubes). The compressor, the mechanical energy
condenser tubes have fins designed to necessary to operate the compressor is
improve the transfer of heat. This removal of transferred to the gas it is being compressed.
heat causes the refrigerant to liquefy; liquid This energy is referred to as the heat of
refrigerant flows from the condenser to the compression and is used as the source of
23
62-69091-00
heat during the defrost and heating mode. way) energizes, opening a port which allows
heated refrigerant vapor to flow directly to
Case 1: With condenser closing solenoid the evaporator coil.
option.
The main difference between heating and
When the microprocessor activates heating defrosting is that, when in heating mode all
or defrost, the hot gas HGV (two-way) the evaporator fans continue to run, blowing
solenoid energizes, and (if HP2 is switch off) the air around the heated coils to heat the
the condenser closing solenoid MHV product. When defrosting, the evaporator
energizes, closing the port to the condenser fans stop, allowing the heated vapor to
and opening a port which allows heated defrost any ice build-up there may be.
refrigerant vapor to flow directly to the
evaporator coil. For refrigerant R404a If P>22 bars HP2 is
switch on; When the pressure decreases at
Case 2: Without condenser closing solenoid 17 bars, HP2 is switch off.
option. For refrigerant R134a If P>12 bars, HP2 is
switch on; When the pressure decreases at 9
When the microprocessor activates heating bars, HP2 is switch off.
or defrost, the hot gas solenoid HGV (two-
24
62-69091-00
25
62-69091-00
26
62-69091-00
27
62-69091-00
28
62-69091-00
29
62-69091-00
30
62-69091-00
31
62-69091-00
SECTION 3
OPERATION
Start the vehicle engine
3.1 CONTROL AND STARTING Press the ON key to start the
UP unit (start-up is time-delayed
for 40 seconds). The digital
display of the cab command
displays the box temperature.
Check the temperature set-
point is correct by pressing the
SET key; the set-point
temperature is highlighted on
the digital display.
Enter a new set-point if necessary (see
temperature set-point adjustment).
In the event of difficulty on start-up,
check that:
● The fuses have not blown.
● The temperature selected by the cab
Unit shut-down
3.1.1 Start and stop the unit Turn off the ignition
Check the belt tension of the compressor key or press the OFF
drive belts before starting the unit. key.
Start-up and box temperature
control
Heating
32
62-69091-00
3.1.3 COOLING
There are two control ranges, Frozen and
Perishable. The frozen range is active with The unit will only heat when the controller
set points at or below -12°C (+10°F) and the is set above -12°C (+10°F) as the heat relays
Perishable range is active at set points above are electronically locked out with set points
-12°C (+10°F). at or below -12°(+10°F).
The controller automatically selects the The microprocessor automatically selects
mode necessary to maintain box temperature the mode necessary to maintain box
at set point. temperature at set point. In pull down the
heating modes are as follows (Figure 3-1
3.1.4 HEATING and Figure 3-2).
See section 2.12 for a description of the
heating cycle.
Figure 3-1 Thermostat operating sequence, set-point higher than –12ºC (+10ºF)
33
62-69091-00
3.1.5 DEFROST
See section 2.12 for a description of heat and defrost cycles.
Injection valve INV is controlled by discharge temperature, when discharge temperature is more
than 127ºC (260ºF), injection valve switches on, when discharge temperature is less than 105 ºC
(212ºF), injection valve switches off.
34
62-69091-00
SECTION 4
SERVICE
35
62-69091-00
•Check the tightness of bolts 4.2.1 Belt tension gauge (compressor)
and screws and that the unit is A belt tension gauge provides an accurate
correctly fastened onto the box.
Initial
•Check pressure leak.
and easy method of adjusting belts to their
service proper tension. Properly adjusted belts give
•Check that the road
compressor RPM long lasting and efficient service. Too much
•Check compressor belt tension. tension shortens belt and bearing life, and
•Clean up battery and battery too little tension causes slippage and exces-
clamps sive belt wear. It is also important to keep
•Check belt compressor tension belts and sheaves free of any foreign
•Replace compressor belt every material which may cause the belts to slip.
3000 hours
•Check refrigerant leaks
The Belt Tension gauge can be used to
Service A •Check all electrical adjust all belts. The readings which we
connections specify for Carrier Transicold units are
•Check the cooling mode applicable only for our belts and application,
•Check the defrost operation as the tension is dependent on the size of the
•Check the operation of the cab belt and distance between sheaves. When
control using this gauge, it should be placed as close
•Clean up condenser coil
as possible to the midpoint between two
•Replace idler pulley bearings if
Service B
any.
sheaves.
•Replace filter drier. When installing a new V-belt the tension
Every year •Clean up the expansion valve should be somewhat higher than specified
orifice filter. and readjusted after allowing the unit to run
•Replace compressor oil - only for some time.
use Polyolester oil (POE)
Every approved by Carrier Transicold.
TWO years •Replace refrigerant.
•Replace orifice expansion
valve
36
62-69091-00
4.3 REMOVING THE NOTE
REFRIGERANT CHARGE Important: only the correct
refrigerant cylinder must be
connected to pressurize the system.
Any other gas or vapor will
contaminate the system which will
require additional purging and
evacuation of the high side
(discharge) of the system.
37
62-69091-00
the vacuum pump. Wait a few minutes to be
4.5.3 Evacuation and dehydration sure the vacuum holds.
procedure
a. Remove refrigerant using a refrigerant e. Break the vacuum with clean dry
recovery system. refrigerant. Use refrigerant that the unit calls
b. The recommended method to evacuate for. Raise system pressure to
and dehydrate the system is to connect three approximately 2 psig.
evacuation hoses to the vacuum pump and f. Remove refrigerant using a refrigerant
refrigeration unit as shown in Figure 4-2 (do recovery system.
not use standard service hoses as they are g. Repeat steps d. to f.
not suited for evacuation purposes). Also, as h. Evacuate unit to 500 microns. Close off
shown, connect an evacuation manifold vacuum pump valve and stop pump. Wait
with special evacuation hoses five minutes to see if vacuum holds. This
c. Open the vacuum pump and electronic checks for residual moisture and/or leaks.
vacuum gauge valves, start the pump, for a i. With a vacuum still in the unit, the
while, Shut off the pump and check to see if refrigerant charge may be drawn into the
the vacuum holds. This operation is to test system from a refrigerant container on
the evacuation setup for leaks, repair if weight scales. The correct amount of
necessary. refrigerant may be added by observing the
d. Open the vacuum pump and electronic scales (see table 2-1).
vacuum gauge valves again. Evacuate unit
until the electronic vacuum gauge indicates NOTE
2000 microns. Close the electronic vacuum Vacuum duration must be at least 8
gauge and vacuum pump valves. Shut off hours.
38
62-69091-00
NOTE
4.6 CHARGING THE The refrigerant R404A must be
REFRIGERATION SYSTEM charged from liquid valve and not
vapor. The refrigerant R404A is a
4.6.1 Installing a complete charge blend. Charging by the vapor valve
a. Dry the refrigeration circuit and create a will change the properties of the
high vacuum (see section 4.5). refrigerant and affect cooling capacity.
b. Place refrigerant cylinder on scale and
connect charging line from cylinder to 4.6.3 Checking the refrigerant charge
manifold. Purge charging line at outlet valve. Start unit in cooling mode. Run
Purge charging line at inlet manifold. approximately ten minutes. Partially block
c. Note weight of refrigerant cylinder. Be off air flow to condenser coil so discharge
sure that the unit is stopped during this pressure rise to 22 bars (R404A) or 12bar
operation. (R134a).
d. Open liquid valve on refrigerant cylinder. The charge is correct if there are no bubbles
Allow the liquid refrigerant to flow into the at the liquid line sight glass.
unit until the correct weight of refrigerant
has been added as indicated by scales.
4.7 REPLACING THE
NOTE COMPRESSOR
It is possible that all liquid may not be
pulled into the circuit, as outlined in a. Read carefully the following
step (d) above. In this case, close the instructions, strict observance of these
cylinder valve front seat and start the procedures are essential for operator
unit. Refrigerant will accumulate in safety.
the receiver and liquid of the ● do not switch on compressor with
refrigerant cylinder will be sucked by terminal box open.
the compressor. ● remove terminal box cover only with
e. When refrigerant cylinder weight (scale) power source disconnected.
indicates that the correct charge has been ● before compressor installation, slowly
added, close the manifold valves. open the plug on the discharge valve and
vent the nitrogen holding charge.
4.6.2 Adding a partial charge ● ensure that suction and discharge
valves are open before starting the
a. Place refrigerant cylinder on scale and
compressor.
note weight.
● do not touch the compressor shortly
b. Connect charging line from the cylinder
after stopping as surface temperatures
to the manifold. Charge proper volume
will be dangerous.
refrigerant to remove air.
● do not operate the compressor with
c. Start the unit with the compressor turning
hydrocarbon gases.
at 2400 rpm.
b. Evacuate the unit. Repeat the steps in
d. Turn down refrigerant cylinder valve.
section 4.3.
e. Add refrigerant by small quantity.
c. Installation
f. Repeat the step 4.6.3.
To install the compressor, reverse the
procedure outlined when removing the
compressor. Refer to section 2.5 for torque
values.
39
62-69091-00
Pump down the unit, see section 4.5 then
charge system, see section 4.6.
40
62-69091-00
4.10. CHECKING AND than “new” cartons. The fiber dust and
REPLACING FAN MOTOR particles are drawn into the evaporator
where they lodge between the evaporator
BRUSHES
fins. If the coil is not cleaned on a regular
The fan motor brushes should be checked basis, sometimes as often as after each trip,
periodically for cleanliness and wear to the accumulation can be great enough to
maintain proper operation of the fan motors. restrict air flow, cause coil icing, repetitive
defrosts and loss of unit capacity. Due to the
“washing” action of normal defrost the fiber
dust and particles may not be visible on the
face of the coil but may accumulate deep
within.
It is recommended to clean the evaporator
coil on a regular basis, not only to remove
cardboard dust, but to remove any grease oil
film which sometimes coats the fins and
prevents water from draining into the drain
Figure 4-4 Fan motor brushes
pan.
To check brushes proceed as follows:
Cardboard fiber particles after being wetted
a. With unit off and battery disconnected,
and dried several times can be very hard to
remove brush cap (item 1; 2 per motor).
remove. Therefore, several washings may be
See Figure 4-4.
necessary.
b. Remove brushes (item 2; 2 per motor)
and check the length of the brush. If the
a. Spray coil with a mild detergent solution
length is less than 1/4 inch (6 mm) the
such as any good commercial-grade
brushes should be replaced (after
automatic dish washer detergent and let the
checking collector).
solution stand for a few minutes. Reverse
c. Blow out the brush holder with low
flush (opposite normal air flow) with clean
pressure air to remove any carbon dust
water at mild pressure. A garden hose with
in the holder. This dust could prevent a
spray nozzle is usually sufficient. Make sure
good contact between the brushes and
drain lines are clean.
collector.
b. Run unit until defrost mode be initiated to
d. Remove the back cover of the motor and
check for proper draining from drain pan.
inspect the collector. If the commutator
is heavily grooved, polish it using fine
sandpaper; do not use abrasive paper. 4.12 CONDENSER COIL-
Wipe out any accumulation of greasy CLEANING
material using a clean rag dampened Remove all foreign material from the
with solvent. Reassemble the motor; condenser coil by reversing the normal air
install new brushes and replace cap. flow. (Air is pulled in through the front and
discharges over the unit.) Compressed air or
4.11 EVAPORATOR COIL- water may be used as a cleaning agent. It
CLEANING may be necessary to use warm water mixed
with any good commercial dishwasher
The use of recycled cardboard cartons is
detergent. Rinse coil with fresh water if a
increasing. The recycled cardboard cartons
detergent is used.
create much more fiber dust during transport
41
62-69091-00
4.13 HOT GAS (TWO-WAY) refrigerant must be evacuated.
SOLENOID AND CONDENSER a. Remove and store the refrigerant charge
CLOSING SOLENOID (TWO in an evacuated container (see section
4.3).
WAY) b. Remove coil snap cap, voltage cover and
4.13.1 Replacing solenoid coil coil assembly. Remove the valve body
head.
It is not necessary to pump the unit down to
c. Check for foreign material in valve body.
replace the coil (see Figure 4-5).
d. Check for damaged plunger and O-ring.
a. Remove coil snap cap, voltage plate and
If O-ring is to be replaced, always put
coil assembly. Disconnect leads and remove
refrigerant oil on O-rings before
coil junction box if necessary.
installing.
b. Verify coil type, voltage and frequency.
This information appears on the coil voltage e. Tighten enclosing tube. If the valve has
plate and the coil housing. been removed from the circuit, check for
c. Place new coil over enclosing tube and eventual leaks.
then install voltage plate and snap cap. f. Install coil assembly, voltage cover and
snap cap.
g. Evacuate and dehydrate the circuit.
h. Install a complete refrigerant charge.
i. Start unit and check operation.
42
62-69091-00
follows : line and outlet line from expansion valve.
a. Install a low-pressure gauge. 4. The thermal bulb is located below the
b. Remove cap (item 1) from CPR valve. center of the suction line. This area must be
c. With an 8 mm Allen wrench, loosen the clean to ensure positive bulb contact. Strap
jam nut (Figure 4-6, item 2.). thermal bulb to suction line and insulate
d. Using the 8 mm Allen wrench, adjust the both.
setting screw. To raise the suction 5. Braze the equalizer tubes to expansion
pressure turn the set ting screw (item 3.) valve.
clockwise; to lower the suction pressure, 6. Evacuate by placing vacuum pump on
turn the setting screw counterclockwise. suction and receiver tank service valve.
Refer to section 2.3 for CPR valve 7. Recharge unit.
setting. 8. Check superheat.
e. When the setting has been adjusted,
tighten the jam nut securely against the b. Measuring superheat
setting screw (item3.). This will prevent NOTE
any movement of the setting screw due The expansion valve and bulb
to vibrations in the unit. Replace the cap. location are shown in Figure 4-7.
1. Remove insulation from expansion valve
bulb and suction line.
4.15 THERMOSTATIC 2. Loosen one TXV bulb clamp and make
EXPANSION VALVE sure area under clamp (above TXV bulb)
is clean.
MOP expansion valve characteristics: 3. Place thermocouple above (parallel)
–Rule: in order to avoid the compressor TXV bulb and then secure loosened
overcharge, a MOP expansion valve clamp making sure both bulbs are firmly
(expansion valve with limited flow) is used. secured to suction line as shown in
–Operating: this kind of expansion valve can Figure 4-7.
not open more than MOP setpoint. Any
temperature increase of the sensor can not
open more the expansion valve.
The thermal expansion valve is an automatic
device which maintains constant superheat
of the refrigerant gas leaving the evaporator
regardless of suction pressure. The valve
functions are: (a) automatic response of
refrigerant flow to match the evaporator load
and (b) prevention of liquid refrigerant
entering the compressor. Unless the valve is
defective, it requires adjustment, but
maintenance must be done every year in
order to clean the orifice filter. Figure 4-7 Thermostatic expansion valve
a. Replacing expansion valve bulb and thermocouple
1. Remove refrigerant charge. 4. Connect an accurate gauge to the ¼”
2. Remove insulation from expansion valve port on the suction service valve.
bulb and then remove bulb from suction 5. Run unit until stabilize, set controller
line. temperature lower 5.5ºC than box
3. Loosen inlet nut and unbraze equalizer
43
62-69091-00
temperature.
6. From the temperature/pressure table, handle a photograph. This not only
determine the saturation temperature precludes the possibility of ESD damage,
corresponding to the evaporator outlet but also lowers the possibility of physical
pressure. damage to the electronic components.
7. Note the temperature of the suction gas Although the microprocessor boards are
at the expansion valve bulb. fairly rugged when assembled, they are
8. Subtract the saturation temperature more fragile when separated and should
determined in Step 7 from the average always be handled carefully.
temperature measured in Step 6. The When welding is required on the unit frame,
difference is the superheat of the suction or on the front area of the trailer, ALL
gas. wiring to the microprocessor MUST be
disconnected. When welding is per formed
4.16 MICROPROCESSOR on other areas of the truck and van, the
Although there is less danger of electrical welder ground connection MUST be in close
static discharge ESD damage in the outdoor proximity to the area being welded. It is also
environment, where the processor is likely a good practice to remove both battery
to be handled, proper board handling cables before wedding on either the unit
techniques should always be stressed. frame or the truck to prevent possible
Boards should always be handled by their damage to other components such as the
edges, in much the same way one would alternator and voltage regulator.
44
62-69091-00
Table 4-2 R404A temperature-pressure
45
62-69091-00
Table 4-4 R134a Temperature-pressure
46
62-69091-00
SECTION 5
TROUBLE SHOOTING
5.1 REFRIGERATION
5.1.1 Unit will not cool
INDICATION/TROUBLE POSSIBLE CAUSES REFERENCE SECTION
Clutch defective Check
Compressor malfunction Compressor defective 4.7
Belt malfunction Check
Defrost cycle has not terminated 5.1.5
Refrigeration system Abnormal pressure 5.1.6
Hot gas (two-way)solenoid
5.1.11
malfunction
47
62-69091-00
5.1.4 Unit will not heat or heating insufficient
INDICATION/TROUBLE POSSIBLE CAUSES REFERENCE SECTION
Abnormal pressure 5.1.6
Refrigeration Temperature controller malfunction 2.7
Hot gas (two-way)solenoid
5.1.11
malfunction
Clutch defective Check
Compressor
Compressor defective 4.7
5.1.6.1 Cooling
REFERENCE
INDICATION/TROUBLE POSSIBLE CAUSES
SECTION
Condenser coil dirty 4.12
High discharge pressure The refrigerant is mixed with other gases or
Replace
refrigerant over charge
Compressor worn or broken 4.7
Hot gas (two way) solenoid malfunction 5.1.11
Low discharge pressure Clutch malfunction Check
Belt malfunction Check
Low refrigerant charge 4.6
CPR valves worn or broken 4.14
High suction pressure
Hot gas (two way) solenoid malfunction 5.1.11
CPR valves worn or broken 4.14
Filter-drier partially plugged 4.8
Low refrigerant charge 4.6
Low suction pressure
Expansion valve malfunction 5.1.10
No evaporator air flow or restricted air flow 5.1.9
Excessive frost on coil Check
Compressor defective 4.7
Suction and discharge
Belt malfunction Check
pressures tend to equalize
when unit is operating Clutch malfunction Check
Hot gas (two way) solenoid malfunction 5.1.11
48
62-69091-00
5.1.6.2 Heating
REFERENCE
INDICATION/TROUBLE POSSIBLE CAUSES
SECTION
Over charged system 4.6.3
Condenser fan or HP2 pressure switch
4.9.2
High discharge pressure defective
The refrigerant is mixed with other gases Check
Condenser fan defective Check
Compressor worn or broken 4.7
Clutch malfunction Check
Low discharge pressure
Belt malfunction Check
Low charged system 4.6
Low charged system 4.6
Low suction pressure
CPR valve worn or broken 4.14
49
62-69091-00
5.1.10 Expansion valve malfunction
REFERENCE
POSSIBLE CAUSES
SECTION
External equalizer line plugged Clean
Ice formation at valve seat 4.5
Low suction pressure with high Wax, oil or dirt plugging valve or orifice 4.15
superheat
Broken capillary 4.15
Power assembly failure or partial Replace
Loss of element /bulb charge Replace
Superheat setting too high 4.15
Superheat setting too low 4.15
Low superheat and liquids lugging Choose the wrong type of expansion valve 4.15
in compressor
Improper bulb location or installation 4.15
REFERENCE
INDICATION/TROUBLE POSSIBLE CAUSES
SECTION
No power to valve Check
Improper wiring or loose connections Check
Valve improperly assembled 4.13
Valve does not function properly Coil or coil sleeve improperly assembled 4.13
Movement of plunger restricted due to :
a. Corroded or worn parts
4.13
b. Foreign material lodged in valve
c. Bent or dented enclosing tube
Valve shifts but refrigerant Foreign material lodged under seat 4.13
continues to flow Defective seat Check
50
62-69091-00
5.2 Fault alarm
Please refer to section 2.7, the following is the way to solve malfunction.
5.2.1 EE alarm
51
62-69091-00
5.2.2 BAT alarm
52
62-69091-00
5.2.4 A01/A02 alarm
53
62-69091-00
5.2.5 A04 alarm
54
62-69091-00
5.2.7 A07 alarm
55
62-69091-00
5.2.9 A11 alarm
56
62-69091-00
SECTION 6
EXTRACT FROM MATERIAL SAFETY DATA BULLETIN
6.1 POE OIL
1. PRODUCT AND COMPANY IDENTIFICATION
CARRIER SHANGHAI
3. FIRE-FIGHTING MEASURES
EXTINGUISHING MEDIA:
Carbon dioxide, foam, dry chemical and water fog
SPECIAL FIRE FIGHTING PROCEDURES:
Water or foam may cause frothing. Use water to keep fire exposed containers cool. Water spray
may be used to flush spills away from exposure. Prevent runoff from fire control or dilution from
entering streams, sewers, or drinking water supply.
SPECIAL PROTECTIVE EQUIPMENT:
For fires in enclosed areas, fire fighters must use self-contained breathing apparatus.
UNUSUAL FIRE AND EXPLOSION HAZARDS:
None. Flash point C (F): 232 (450) (ASTM D–92). Flammable limits – LEL: NA, UEL: NA.
NFPA HAZARD ID:
health: 0,
flammability: 1,
reactivity: 0
HAZARDOUS DECOMPOSITION PRODUCTS:
carbon monoxide
57
62-69091-00
see section 6.
8. DISPOSAL CONSIDERATIONS
WASTE DISPOSAL:
EVEN THOUGH THIS PRODUCT IS READILY BIODEGRADABLE, IT MUST NOT BE
INDISCRIMINATELY DISCARDED INTO THE ENVIRONMENT.
This product is suitable for burning in an enclosed, controlled burner for fuel value and for
recycling at an approved facility. In addition, it can be disposed of at an approved waste disposal
facility. Land farming and processing through sewage treatment facilities may be available
disposal options but necessary approvals must first be obtained from appropriate regulatory
authorities. Specific characteristics of the waste at the time of disposal may affect the availability
of the above options.
The complete data sheets are available from Carrier Shanghai on request.
58
62-69091-00
6.2 FORANE R404A/R134a
1. Refrigerant R404A
CARRIER SHANGHAI
2. Refrigerant R134a:
CARRIER SHANGHAI
3.HAZARDS IDENTIFICATION
EMERGENCY OVERVIEW
Colorless liquified gas with faint ether odor.
WARNING
LIQUID AND GAS UNDER PRESSURE, OVERHEATING AND OVERPRESSURIZING
MAY CAUSE GAS RELEASE OF VIOLENT CYLINDER BURSTING. MAY
DECOMPOSE ON CONTACT WITH FLAMES OR EXTREMELY HOT METAL
SURFACES TO PRODUCE TOXIC AND CORROSIVE PRODUCTS. VAPOR
REDUCES OXYGEN AVAILABLE FOR BREATHING AND IS HEAVIER THAN AIR.
HARMFUL IF INHA LED AND MAY CAUSE HEART IRREGULARITIES,
UNCONSCIOUSNESS OR DEATH. LIQUID CONTACT WITH EYES OR SKIN MAY
CAUSE FROSTBITE.
59
62-69091-00
POTENTIAL HEALTH, EFFECTS
Skin contact and inhalation are expected to be the primary routes of occupational exposure to
this material. As with most liquified gases, contact with the rapidly volatilizing liquid can cause
frostbite to any tissue. High vapor concentrations are irritating to the eyes and respiratory tract
and may result in central nervous system (CNS) effects such as headache, dizziness, drowsiness
and, in severe exposure, loss of consciousness and death. The dense vapor of this material may
reduce the available oxygen for breathing. Prolonged exposure to an oxygen deficient
atmosphere may be fatal. Inhalation may cause an increase in the sensitivity of the heart to
adrenaline, which could result in irregular or rapid heartbeats. Medical conditions aggravated by
exposure to this material which could result in irregular or rapid heartbeats. Medical conditions
aggravated by exposure to this material include heart disease or compromised heart
function.
4. FIRST AID MEASURES
EYE CONTACT
Immediately flush with plenty of water. Get medical attention if irritation persists.
SKIN CONTACT
Flush exposed skin with lukewarm water (not hot), or use other means to warm skin slowly. Get
medical attention if frostbitten by liquid or if irritation occurs.
INGESTION
Not applicable. Product is a gas at ambient temperatures.
INHALATION
Remove to fresh air. If not breathing, give artificial respiration. If breathing is difficult, give
oxygen. Get medical attention. DO NOT GIVE ADRENALINE, EPINEPHRIN OR
SIMILAR DRUGS FOLLOWING EXPOSURE TO THIS PRODUCT.
60
62-69091-00
7. HANDLING AND STORAGE
HANDLING
Avoid breathing gas. Avoid contact with eyes, skin and clothing. Keep container closed. Use
only with adequate ventilation. Do not enter confined spaces unless adequately ventilated.
STORAGE
Do not apply direct flame to cylinder. Do not store cylinder in direct sun or expose it to heat
above 48ºC (120ºF).
Do not drop or refill this cylinder. Keep away from heat, sparks and flames.
Recover, reclaim or recycle when practical. Dispose of in accordance with federal, state and
local regulations.
Note : chemical additions to, processing of, or otherwise altering this material may take this
waste management information incomplete, inaccurate, or otherwise inappropriate. Furthermore,
state and local waste disposal requirements may be more restrictive or otherwise different from
federal laws and regulations.
The complete data sheets are available from Carrier Shanghai on request.
61
62-69091-00
SECTION 7
ELECTRICAL SCHEMATIC WIRING DIAGRAMS
The following general safety notices supplement the specific warnings and cautions appearing
elsewhere in this manual. They are recommended precautions that must be understood and
applied during operation and maintenance of the equipment covered herein.
62
62-69091-00
63
62-69091-00