You are on page 1of 65

SERVICE MANUAL

CITIMAX SERIES
500, 700

CARRIER TRANSICOLD DIVISION


No.1235, Yecheng Road, Shanghai, China
TABLE OF CONTENTS
SECTION 1 ............................................................................................................................................ 4
SAFETY INSTRUCTIONS ..................................................................................................................... 4
SECTION 2 ............................................................................................................................................ 7
DESCRIPTION....................................................................................................................................... 7
2.1 INTRODUCTION ...................................................................................................................... 7
2.2 COMPRESSOR REFERENCE DATA.................................................................................... 15
2.3 REFRIGERATION SYSTEM DATA....................................................................................... 15
2.4 ELECTRICAL DATA ............................................................................................................... 16
2.5 TORQUE VALUES ................................................................................................................. 16
2.6 SAFETY DEVICES ................................................................................................................. 17
2.6.1 Fuses ............................................................................................................................ 18
2.7 CAB Control description ......................................................................................................... 19
2.7.1 Operation principal ....................................................................................................... 19
2.7.2 to start the unit .............................................................................................................. 20
2.7.3 to stop the unit .............................................................................................................. 20
2.7.4 to change setpoint temperature ................................................................................... 20
2.7.5 to change defrost parameters ...................................................................................... 20
2.7.6 to display other data (alarms, software version, box Tº).............................................. 21
2.7.7 to change default parameters ...................................................................................... 21
2.7.8 Fault alarm display ....................................................................................................... 21
2.8 COMPRESSOR PRESSURE REGULATING VALVE ............................................................ 23
2.9 HOT GAS SOLENOID – HGV (TWO-WAY) ........................................................................... 23
2.10 CONDENSER CLOSING SOLENOID –MHV (TWO-WAY) ................................................. 23
2.11 REFRIGERANT CIRCUIT DURING COOLING ................................................................... 23
2.12 REFRIGERANT CIRCUIT DURING HEAT AND DEFROST ............................................... 23
SECTION 3 .......................................................................................................................................... 32
OPERATION ........................................................................................................................................ 32
3.1 CONTROL AND STARTING UP ............................................................................................ 32
3.1.1 Start and stop the unit .................................................................................................. 32
3.1.2 Compressor start up intervals ...................................................................................... 32
3.1.3 COOLING ..................................................................................................................... 33
3.1.4 HEATING...................................................................................................................... 33
3.1.5 DEFROST .................................................................................................................... 34
3.2 control of fan and valves......................................................................................................... 34
SECTION 4 .......................................................................................................................................... 35
SERVICE.............................................................................................................................................. 35
4.1 UNIT MAINTENANCE ............................................................................................................ 35
4.1.1 Unit maintenance schedules ........................................................................................ 35
4.1.2 Description of maintenance operations........................................................................ 35
4.2 BELT MAINTENANCE AND ADJUSTMENT ......................................................................... 36
4.2.1 Belt tension gauge (compressor) ................................................................................. 36
4.3 REMOVING THE REFRIGERANT CHARGE ........................................................................ 37
4.4 REFRIGERANT LEAK CHECKING ....................................................................................... 37
4.5 EVACUATION AND DEHYDRATION .................................................................................... 37
4.5.1 General ......................................................................................................................... 37
4.5.2 Preparation ................................................................................................................... 37
4.5.3 Evacuation and dehydration procedure ....................................................................... 38
4.6 CHARGING THE REFRIGERATION SYSTEM ..................................................................... 39
4.6.1 Installing a complete charge ........................................................................................ 39
4.6.2 Adding a partial charge ................................................................................................ 39

2
62-69091-00
4.6.3 Checking the refrigerant charge ................................................................................... 39
4.7 REPLACING THE COMPRESSOR ....................................................................................... 39
4.8 CHECKING AND REPLACING FILTER DRIER .................................................................... 40
4.9 CHECKING AND REPLACING HIGH PRESSURE CUTOUT SWITCH ............................... 40
4.9.1 Replacing high pressure cutout switch ........................................................................ 40
4.9.2 Checking high pressure cutout switch ......................................................................... 40
4.10. CHECKING AND REPLACING FAN MOTOR BRUSHES .................................................. 41
4.11 EVAPORATOR COIL-CLEANING ....................................................................................... 41
4.12 CONDENSER COIL-CLEANING ......................................................................................... 41
4.13 HOT GAS (TWO-WAY) SOLENOID AND CONDENSER CLOSING SOLENOID (TWO WAY)
...................................................................................................................................................... 42
4.13.1 Replacing solenoid coil .............................................................................................. 42
4.13.2 Replacing solenoid valve internal parts ..................................................................... 42
4.14 ADJUSTING THE COMPRESSOR PRESSURE REGULATING VALVE (CPR) ............... 42
4.15 THERMOSTATIC EXPANSION VALVE .............................................................................. 43
4.16 MICROPROCESSOR ........................................................................................................... 44
SECTION 5 .......................................................................................................................................... 47
TROUBLE SHOOTING ....................................................................................................................... 47
5.1 REFRIGERATION .................................................................................................................. 47
5.1.1 Unit will not cool ........................................................................................................... 47
5.1.2 Unit runs but has insufficient cooling ........................................................................... 47
5.1.3 Unit operates long or continuously in cooling .............................................................. 47
5.1.4 Unit will not heat or heating insufficient........................................................................ 48
5.1.5 Defrost malfunction ...................................................................................................... 48
5.1.6 Abnormal pressure ....................................................................................................... 48
5.1.7 Abnormal noise ............................................................................................................ 49
5.1.8 Cab command malfunction .......................................................................................... 49
5.1.9 No evaporator air flow or restricted air flow ................................................................. 49
5.1.10 Expansion valve malfunction..................................................................................... 50
5.1.11 Malfunction hot gas (two-way) solenoid ..................................................................... 50
5.2 Fault alarm ............................................................................................................................. 51
5.2.1 EE alarm ....................................................................................................................... 51
5.2.2 BAT alarm ..................................................................................................................... 52
5.2.3 Err alarm ....................................................................................................................... 52
5.2.4 A01/A02 alarm .............................................................................................................. 53
5.2.5 A04 alarm ..................................................................................................................... 54
5.2.6 A06 alarm ..................................................................................................................... 54
5.2.7 A07 alarm ..................................................................................................................... 55
5.2.8 A09 alarm ..................................................................................................................... 55
5.2.9 A11 alarm ..................................................................................................................... 56
SECTION 6 .......................................................................................................................................... 57
EXTRACT FROM MATERIAL SAFETY DATA BULLETIN ................................................................. 57
6.1 POE OIL.................................................................................................................................. 57
6.2 FORANE R404A/R134a ......................................................................................................... 59
SECTION 7 .......................................................................................................................................... 62
ELECTRICAL SCHEMATIC WIRING DIAGRAMS.............................................................................. 62

3
62-69091-00
SECTION 1
SAFETY INSTRUCTIONS

This manual contains safety and service instructions to follow in order to prevent any accident.
Stickers have been placed on the product for your safety.

BEFORE USING THIS REFRIGERANT UNIT, read carefully all safety


information explained in this manual and indicated on the product. Be sure
that everybody who will use this refrigeration unit has been trained to use it in
a safe way.
DURING THE USE OR MAINTENANCE OF THIS
REFRIGERATION UNIT, the notes on safety are to be considered.

Personal Protective Equipment:


Always use adequate Personal Protective Equipment before doing anything
on this refrigerant unit, as explained in this manual.

Working at height:
Take all necessary safety precautions when accessing this refrigeration unit:
use safe ladders, working platforms with appropriate guards.

Belts and fans:


This refrigeration unit is equipped with Auto–start / stop, it
may start at any time and without warning.
When the unit is running beware of belts and fans that are
moving.
Before servicing refrigeration unit, make sure the main
power is on the DISCONNECTION position. Ensure the
unit will not restart. Lock–out / Tag–out can be performed
as described above.
When there is protective structure (fan grid or guard for
example) make sure they are in place. Never remove them
when the refrigeration unit is running. Always keep your
hands, body parts, clothes, hairs and tools far from moving
parts.

4
62-69091-00
Electricity:
When this refrigeration unit is running in electrical operation, some devices
are powered up especially in the electrical control box.
Before servicing refrigeration unit, make sure the main power is on the
DISCONNECTION position. Ensure this refrigeration unit is disconnected
from battery. Lock–out / Tag–out can be performed as described above.
Before working in the electrical control box, it is required to control the
lack of tension.
WHEN IT IS NECESSARY TO WORK IN THE ELECTRICAL
CONTROL BOX UNDER TENSION, PEOPLE MUST BE QUALIFIED
FOR WORKS UNDER LOW OR HIGH VOLTAGE.
Always use adequate tools and Personal Protective Equipment when
working on electrical devices: safety gloves and safety glasses.

Refrigerant:
The refrigerant contained in this refrigeration unit can cause frostbite, severe
burns or blindness in case of projection and direct contact with the skin or
eyes. In contact with flame or heat refrigerant generate toxic gas.
Refrigerant handling must be done by qualified people. Keep any flame, any
lighted object or any source of sparks away from the refrigerant unit.
Always use Personal Protective Equipment when handling refrigerant:
safety clothes, safety gloves and safety glasses.

Burning with hot and cold:


When this refrigeration unit is running or even after, different components
can be very cold or hot (exhaust pipe, tubes, coils, receiver, accumulator or
engine for example)
Beware when operating closed from cold or hot components.
Always use adequate safety gloves when doing any maintenance on this
refrigeration unit.

Cuttings:
Beware when handling or operating closed from parts that could be sharp
(coils, evaporators, clamps for example).
Always use adequate safety gloves when doing any maintenance on this
refrigeration unit.

Environment:
Think about protection of environment during all the life of this
refrigeration unit. To prevent environmental damages NEVER release
refrigerant in the atmosphere, NEVER throw coolant, oil, battery and
chemicals in the nature. It must be recuperate and recycle according to
current regulations. When disposing this refrigerant unit do it in an
environmentally sound way and in accordance with current regulations.

5
62-69091-00
CAUTION

Under no circumstances should anyone attempt to repair the Logic or Display Boards. Should a
problem develop with these components, contact your nearest Carrier Transicold dealer for
replacement.
Under no circumstances should a technician electrically probe the processor at any point, other
than the connector terminals where the harness attaches. Microprocessor components operate at
different voltage levels and at extremely low current levels. Improper use of voltmeters, jumper
wires, continuity testers, etc. could permanently damage the processor.
Most electronic components are susceptible to damage caused by electrical static discharge
(ESD). In certain cases, the human body can have enough static electricity to cause resultant
damage to the components by touch. This is especially true of the integrated circuits found on the
truck/trailer microprocessor.

6
62-69091-00
SECTION 2
DESCRIPTION
2.1 INTRODUCTION

CITIMAX 500 CITIMAX 700


R134a R404A R404A
12V 24V 12V 24V 12V 24V
Fresh Frozen

Table 2-1 shows the configuration of


CITIMAX units, such as refrigerant volume,
compressor type, evaporator and condenser
weight.
The unit is directly driven by the engine of
the vehicle when in operation on the road.
The standard control system is a
microprocessor controller. Once the
controller (remote Command within the cab
of the truck) is set at the desired temperature,
the unit will operate automatically to
CITIMAX 500/700 units are simple, tried maintain the desired temperature within very
and tested design; low-cost purchase and close limits.
operation to equip large and middle size The control system automatically selects
delivery vehicles. cooling and heating cycles as necessary to
It is manufactured as a split system, enabling maintain the desired temperature.
it to adapt to any vehicle and any The evaporator assembly consists of an
configuration. evaporator coil, an expansion valve, one
Please note CITIMAX 500 / 700 are heat exchanger.
available in next versions: The condenser assembly is consist of a
MCHX, a receiver, an accumulator,
condenser fan, hot gas solenoid, injection
valve, CPR, an optional condenser closing
solenoid.
Table 2-1 module table
R-404A Weight
Model compressor
LB KG Evaporator Condenser
CITIMAX 500 R404A 6.17 2.8 TM16 30kg 58kg
CITIMAX 700 R404A 8.82 4.0 TM21 35kg 62kg

R-134a Weight
Model compressor
LB KG Evaporator Condenser
CITIMAX 500 R134a 8.82 4.0 TM21 35kg 58kg

7
62-69091-00
8
62-69091-00
Figure 2-1 CITIMAX 500 condenser

1. Frame 8. MCHX 14.Low pressure switch


2. Harness 9. Accumulator 15.Defrost valve
3. Fan blade 10.Receiver 16. High pressure switch
4. Condenser motor 11.Electrical control box HP2
5. Injection valve 17.High pressure switch
12.Oil separator
6. Sight glass HP1
7. Filter drier 13.CPR

9
62-69091-00
Figure 2-2 CITIMAX 500 evaporator

1.Fan blade 5.Distributor


2.Motor
3.Heat exchanger
4.Expansion valve

10
62-69091-00
11
62-69091-00
Figure 2-3 CITIMAX 700 condenser

1. Frame 8. MCHX 14.Low pressure switch


2. Harness 9. Accumulator 15.Defrost valve
3. Fan blade 10.Receiver 16. High pressure switch
4. Condenser motor 11.Electrical control box HP2
5. Injection valve 17.High pressure switch
12.Oil separator
6. Sight glass HP1
7. Filter drier 13.CPR

12
62-69091-00
Figure 2-4 CITIMAX 700 evaporator

1.Fan blade 5.Distributor


2.Motor
3.Heat exchanger
4.Expansion valve

13
62-69091-00
Figure 2-5 Electrical control box of CITIMAX

1. Relay 4. RAT cable


2. Fuse 5. Control cable
3. PCB board

14
62-69091-00
2.2 COMPRESSOR REFERENCE DATA
Model TM 16 TM 21 TM21
R404A R404A R134a
Unit type
CITIMAX 500 CITIMAX 700 CITIMAX 500
Discharge volume 163 cc 215cc 215cc
Cylinder number 6 10 10
Weight 7 .1 kg 8.1 kg 8.1kg
Refrigerant oil volume 450 ml 490ml 490ml
Refrigerant oil type POE EAL 68 POE EAL 68 POE EAL 68

2.3 REFRIGERATION SYSTEM g. R134a low pressure switch


DATA
Cutout at: -0.45±0.21bars (-6.5±3psig)
a. Defrost Timer
Cut-in at: 0.45±0.21bars (6.5±3psig)
00: No defrost
h. Refrigerant charge volume
Set defrost intervals:
1h,1.5h,2h,2.5h,3h,4h,5h and 6h. Refer to chart 2-1.
b. R404a High Pressure switch (HP1) i. Compressor Pressure Regulating Valve
(CPR)
Cutout at: 32 bars (465 ±10 psig)
Cut-in at: 25 bars (360 ±10 psig) Adjustment on heat or defrost mode
CPR setting
c. R404a Control Pressure switch (HP2) Model
bar psig
Cutout at: 17 bars (245 ±10 psig) R404
Cut-in at: 22 bars (320 ±10 psig) 2.6(2400rpm) 38±1
CITIMAX 500
d. R404a low pressure switch R404
3.9(2400rpm) 57±1
CITIMAX 700
Cutout at: -0.2 bar (-2.9 psig±3 psi)
Cut-in at: 1 bar (14.5 psig±3 psi) R134a unit without CPR.
e. R134a high pressure switch (HPl) j. Thermostatic expansion valve and
Cutout at: 24.5bars (355±10psig) Orifice
Cut-in at: 20bars (290±10psig) TES2/Orifice nº 3/ (CITIMAX 500 R404A)
f. R134a high pressure control switch TES2/Orifice nº 4/ (CITIMAX 700 R404A)
(HP2) TEN2/Orifice nº 4/ (CITIMAX 500 R134a)

Cutout at: 9bars (130±10psig) k. Quench valve


Cut-in at: 12bars (175±10psig) Opens at: 127ºC (260ºF)
Closes at: 105ºC (212ºF)

15
62-69091-00
2.4 ELECTRICAL DATA

a. Evaporator fan motors

Operating
Bearing lubrication Horse power Speed
current
12V factory lubricated 93W 8-11A 2800rpm

24V factory lubricated 93W 4-6A 2800rpm

b. Condenser fan motor

Operating
Bearing lubrication Horse power Speed
current
12V factory lubricated 89W 8-10A 2200rpm

24V factory lubricated 89W 4-6A 2200rpm

2.5 TORQUE VALUES

Compressor Evaporator Evaporator Condenser- Condenser Condenser Mounting


pulley fan motor fan blade frame motor fan blade bolts

kg-m 3.0 1.8 1.0 1.0 1.8 2.5 6~8

ft-lb 22 13 7 7 13 18 44~60

16
62-69091-00
2.6 SAFETY DEVICES
System components are protected from damage caused by unsafe operating conditions by
automatically shutting down the unit when such conditions occur. This is accomplished by the
safety devices listed in Table 2-2.

Table 2-2 safety devices

Automatic
Unsafe Conditions Safety Devices restart with Device setting
fault cleared
Cutoff:
-0.2±0.19 bar
1. Excessive drop in (R404A)
low pressure switch YES
pressure -0.45±0.21 bar
(R134a)
Timer 5mn
2. Excessive current fuse on electronic board(refer to Table 2-
NO refer to Table 2-3、2-4
draw control circuit 3、2-4)
3. Excessive current
draw evaporator fan Motor fuse(refer to Table 2-3、2-4) No refer to chart 2-3、2-4
motor
4. Excessive current
draw condenser fan Motor fuse(refer to chart 2-3、2-4) No refer to Table 2-3、2-4
motor
Cutoff:
5. Excessive
compressor discharge High pressure switch (HP1) YES 32 bar (R404A)
pressure 24.5 bar (R134a)
Timer 5 mn
Fuse Refer to Table 2-3、2-
6. Current over load NO
(refer to Table 2-3、2-4) 4

7. Clutch malfunction Electronic relay YES Self-protected opening

Cutout/cut-in
8. Low battery
Microprocessor YES 10V for 12V unit
voltage
20V for 24V unit

17
62-69091-00
2.6.1 Fuses
Table 2-3 Fuse-CITIMAX 500/700 12VDC

Evaporator Evaporator Evaporator Condenser Condenser


CITIMAX Ignition Main Logic
fan motor fan motor fan motor fan fan motor
12VDC switch fuse board
1 2 3 motor1 2

notes (a) (c) (b)

Fuse
500 1A 70A 20A 20A 20A 25A / 10A
capacity
Fuse
700 1A 80A 20A 20A 20A 25A 25A 10A
capacity

Table 2-4 Fuse-CITIMAX 500/700 24VDC

Evaporator Evaporator Evaporator Condenser Condenser


CITIMAX Ignition Main Logic
fan motor fan motor fan motor fan motor fan motor
24VDC switch fuse board
1 2 3 1 2

notes (a) (c) (b)

Fuse
500 1A 50A 15A 15A 15A 20A / 7.5A
capacity
Fuse
700 1A 50A 15A 15A 15A 20A 20A 7.5A
capacity
notes:
(a) The fuse is located near the ignition switch in drive cab.
(b) The fuse is located in electrical control box.
(c) The fuse is located close to the vehicle battery.

18
62-69091-00
2.7 CAB Control description 7. + key
This functional accessory simplifies all
control operations. From your seat, you 8. OFF key
can carry out all the control operations:
shut-down, automatic start-up, adjusting 9. ON key
the set point, defrost, program to
10. Unit operation display
customize unit operation to your own Green (left half):
requirements, manage error messages in Green led ON : cooling
event of malfunction. mode Green led OFF: null
mode (regulation)
You can display the box temperature and Green led flashing: heating
see whether the set point is being mode
Red : malfunction (right
maintained by checking the green
half)
indicator. The indicator lights up red in
the event of malfunction. When the 2.7.1 Operation principal
battery voltage is too low, a fail-save
CITIMAX 500 / 700 are powered on
safety system shuts down the unit. Unit
Road mode by the vehicle battery
restart is automatic and time-delayed if
(alternator)
the voltage rises to the normal level.
After starting up, the refrigeration unit

by pressing the key, unit start-up


and shut-down are automatic.

An open-type compressor is driven by


the engine of the vehicle. The vehicle
battery (alternator) powers the
evaporator and condenser fans. The unit
automatically shuts down when the
engine is switched off with the ignition
key.
Controller
The unit can be completely shut down
1. Display – 3 digits
2. Standby operation LED manually by pressing the key on
(not used) the cab command.

3. Road operation LED Temperature control

4. Manual defrost key As soon as the set-point temperature has


been reached, temperature control is
5. – key obtained by shut down and start-up of
the electro-magnetic clutch.
6. Set key
Condenser fan is controlled by the
microprocessor and evaporator fan(s) cut

19
62-69091-00
out during regulation. When transporting In the event of difficulty on start up,
fragile loads such as fresh meat, check that:
vegetables and cheese, it is possible to -The main road fuse has not blown. If it
program the microprocessor to obtain is ok, contact your Carrier Service centre
continuous ventilation by the evaporator -The temperature selected by the cab
during regulation. control has not been affected.

Defrost - Frozen version only 2.7.3 to stop the unit


- For a short stop (ex. delivery): switch
Defrost operation is fully automatic but off by the vehicle ignition key.
can be manually controlled.
- Defrost cycles are fully controlled by - For a long stop: press the key.
the integrated microprocessor.
- During the defrost cycle, the 2.7.4 to change setpoint
evaporator fan shuts down. The temperature
condenser fan is controlled by the Important
microprocessor. If, when settings are adjusted, no key
- Defrost cycle termination is controlled is activated within 5 sec. the system
by a timer. reverts to displaying the box
- During the defrost cycle, the cab temperature. All changes made are
command display indicates "d F". recorded.
Heating – Frozen version only
If the cab command is built into the
vehicle control panel , the command
Heating is provided by hot gas system.
unit must be located as far as possible
The evaporator fan operates, the
from the heating ducts. Maximum
condenser fan is controlled by the
temperature of exposure: 70°C.
microprocessor.

2.7.2 to start the unit 1. Press the key to display setpoint


temperature.
1. Start the vehicle engine.

2. Start the unit by pressing the 2. Press the or key to change


key. Start-up is time-delayed for 40 the setpoint.
seconds.
3. Press the key to return to box
3. The digital display (1.) of the cab temperature display.
control displays the box temperature.
2.7.5 to change defrost
4. Check the temperature setpoint is parameters
Important
correct by pressing the key. The If, when settings are adjusted, no key
setpoint temperature is highlighted on is activated within 5 sec. the system
the digital display. reverts to displaying the box
temperature. All changes made are
5. Enter a new setpoint if necessary (See recorded.
To change setpoint temperature).

20
62-69091-00
1. Press the key to shut-down the keys to display minimum setpoint.
unit.
2. Press the or key to change
2. Press simultaneously the AND minimum setpoint: 0°C, -20°C or -29°C
(default value -29°C).
keys during 5 seconds to display
last selected defrost interval. 3. Press the key to display
differential parameter.
3. Press the or key to change
the defrost time: 4. Press the or key to adjust the
10 to 45 mn: increase or decrease time differential value: Dif1 (1°C), Dif2
(10, 15, 20, 25, 30 and 45) (2°C), Dif3 (3°C) (default value Dif2).

4. Press the key to display defrost 5. Press the Key to display


interval: 00: inhibit defrost function. 1 H, evaporator fan operating mode during
1.5H, 2 H, 2.5H, 3h, 4H, 5H and 6 H off-cycle.
5. Press the key to return to box 6. Press the or key to change the
temperature display. evaporator fan operating mode : FOFF
or F On(default value FOFF).
2.7.6 To display other data (alarms,
software version, box Tº)
7. Press the key,to return to box
temperature display.
1. Press the key during 5 seconds
to enable access to malfunction codes 2.7.8 Fault alarm display
(see “Fault alarm display”). a. Access by the SET key
2. Press or key to display
1. Press the key during 5 seconds
alarms.
to access to malfunction codes.
3. Press the key to display 2. Press or key to display alarms.
software version.
3. To scroll through the alarm list, use
4. Press the key to return to box
temperature display the key.
2.7.7. to change default
parameters

1. Press simultaneously the , and

21
62-69091-00
–ACTIVE malfunctions – AXX

An alarm is active when a problem occurs on the unit, the red LED is flashing speedily.

MALFUNCTION CODE – Red LED flashes


Code Description Unit shutdown Checking
No malfunction – Unit in
A00
operation
Low pressure switch
A01/A02 open/ High pressure
switch open Yes
A04 Clutch compressor fault
A06 Condenser fault No Contact your
A07 Evaporator fan fault No Service Center
Defrost valve (HGV)
A09 No
fault
Liquid injection quench
A10 No
valve fault (INV)
Setpoint adjusted out of
A15 Yes
the range -29°C / +30°C

b. Direct display

Note
Direct display malfunction messages are displayed instead of temperature read-out
as soon as the malfunction is detected, and remain displayed as long as malfunction
persists.
The unit does not run until the malfunction has disappeared or been corrected.

Code Description Unit shutdown Checking


Evaporator temperature
EE
probe (open circuit) - Evaporator probe
and connections
Yes - Battery
BAT Battery low voltage alarm voltage/12VDC
alternator/connections

Programming mistake of
Err the maximum setpoint by No - Setpoint
user
Setpoint lower that
--- maximum setpoint but in No - Setpoint
the range -29°C / +30°C

22
62-69091-00
2.8 COMPRESSOR PRESSURE receiver. The refrigerant then flows through
the filter-drier, where an absorbent keeps it
REGULATING VALVE
dry and clean. The refrigerant then flows
This CPR valve is installed on the suction through a sight glass with moisture
line of compressor to limit the suction and indication and then to the liquid / gas heat
then avoid overloading of compressor. For exchanger.
CPR settings refer to section 2.3. The liquid enters to the thermostatic
The suction pressure is controlled to avoid expansion valve (with external pressure
overloading engine during high box equalizer) which regulates the flow rate of
temperature operation. refrigerant towards the evaporator in order
to obtain maximum use of the evaporator
2.9 HOT GAS SOLENOID – HGV heat transfer surface.
(TWO-WAY) The evaporator tubes have aluminium fins to
The hot gas solenoid is normally closed (NC) increase heat transfer; therefore heat is
and is only powered in defrost and heating removed from the air circulated through the
modes and 40 seconds before start-up if box evaporator. This cold air is circulated
temperature is higher than –5ºC. throughout the truck to maintain the box at
the desired temperature.
2.10 CONDENSER CLOSING The transfer of heat from the air to the low
SOLENOID –MHV (TWO-WAY) temperature liquid refrigerant causes the
liquid to vaporize. The steam at low
The condenser closing solenoid is normally
temperature and pressure enters the heat
open (NO) in cooling mode. It is closed in
exchanger then enters the compressor
defrost and heating mode to increase the
pressure regulating valve (CPR) which
capacity.
regulates refrigerant pressure entering the
compressor, where the cycle starts over.
2.11 REFRIGERANT CIRCUIT
DURING COOLING The discharge pressure is regulated with
HP2. For refrigerant R404a If P>22 bars
When cooling, the unit operates as a vapor
HP2 is switch on and the fan works. When
compression refrigeration system. The main
the pressure decreases at 17 bars, HP2 is
components of the system are the
switch off and the fan is off.
reciprocating compressor, air-cooled
condenser, thermostatic expansion valve, For refrigerant R134a If P>12 bars, HP2 is
evaporator, and hot gas solenoid (two-way). switch on and the fan works. When the
pressure decreases at 9 bars HP2 is switch
The compressor raises the pressure and
off and the fan is off.
temperature of the refrigerant and forces it
into the condenser tubes.
The condenser fan circulates surrounding air
2.12 REFRIGERANT CIRCUIT
over the outside of the condenser tubes. Heat DURING HEAT AND DEFROST
transfer is thus established from the When refrigerant vapor is compressed to a
refrigerant gas (inside the tubes) to the air high pressure and temperature in a
condenser (flowing over the tubes). The compressor, the mechanical energy
condenser tubes have fins designed to necessary to operate the compressor is
improve the transfer of heat. This removal of transferred to the gas it is being compressed.
heat causes the refrigerant to liquefy; liquid This energy is referred to as the heat of
refrigerant flows from the condenser to the compression and is used as the source of

23
62-69091-00
heat during the defrost and heating mode. way) energizes, opening a port which allows
heated refrigerant vapor to flow directly to
Case 1: With condenser closing solenoid the evaporator coil.
option.
The main difference between heating and
When the microprocessor activates heating defrosting is that, when in heating mode all
or defrost, the hot gas HGV (two-way) the evaporator fans continue to run, blowing
solenoid energizes, and (if HP2 is switch off) the air around the heated coils to heat the
the condenser closing solenoid MHV product. When defrosting, the evaporator
energizes, closing the port to the condenser fans stop, allowing the heated vapor to
and opening a port which allows heated defrost any ice build-up there may be.
refrigerant vapor to flow directly to the
evaporator coil. For refrigerant R404a If P>22 bars HP2 is
switch on; When the pressure decreases at
Case 2: Without condenser closing solenoid 17 bars, HP2 is switch off.
option. For refrigerant R134a If P>12 bars, HP2 is
switch on; When the pressure decreases at 9
When the microprocessor activates heating bars, HP2 is switch off.
or defrost, the hot gas solenoid HGV (two-

24
62-69091-00
25
62-69091-00
26
62-69091-00
27
62-69091-00
28
62-69091-00
29
62-69091-00
30
62-69091-00
31
62-69091-00
SECTION 3
OPERATION
Start the vehicle engine
3.1 CONTROL AND STARTING Press the ON key to start the
UP unit (start-up is time-delayed
for 40 seconds). The digital
display of the cab command
displays the box temperature.
Check the temperature set-
point is correct by pressing the
SET key; the set-point
temperature is highlighted on
the digital display.
Enter a new set-point if necessary (see
temperature set-point adjustment).
In the event of difficulty on start-up,
check that:
● The fuses have not blown.
● The temperature selected by the cab

Unit shut-down
3.1.1 Start and stop the unit Turn off the ignition
Check the belt tension of the compressor key or press the OFF
drive belts before starting the unit. key.
Start-up and box temperature
control

3.1.2 Compressor start up intervals


The minimum time between two compressor starts is 5 minutes.
Cooling

Heating

32
62-69091-00
3.1.3 COOLING
There are two control ranges, Frozen and
Perishable. The frozen range is active with The unit will only heat when the controller
set points at or below -12°C (+10°F) and the is set above -12°C (+10°F) as the heat relays
Perishable range is active at set points above are electronically locked out with set points
-12°C (+10°F). at or below -12°(+10°F).
The controller automatically selects the The microprocessor automatically selects
mode necessary to maintain box temperature the mode necessary to maintain box
at set point. temperature at set point. In pull down the
heating modes are as follows (Figure 3-1
3.1.4 HEATING and Figure 3-2).
See section 2.12 for a description of the
heating cycle.

DECREASE IN TEMPERATURE INCREASE IN TEMPERATURE

Figure 3-1 Thermostat operating sequence, set-point higher than –12ºC (+10ºF)

Figure 3-2 Thermostat operating sequence, set-point lower than–12ºC(+10ºF)

33
62-69091-00
3.1.5 DEFROST
See section 2.12 for a description of heat and defrost cycles.

3.2 control of fan and valves


Table 3-1 Management of fan and valve
HGV HP2
EFM CFM condenser MHV CLHR
hot gas pressure
evaporator fan fan solenoid compressor
solenoid switch
ON OFF OFF OFF ON OPEN
cooling ON
ON OFF OFF ON CLOSED
3mn minimum
ON OFF ON ON ON OPEN
Heating if
set-point OFF
ON if
≥-12ºC ON 1mn ON ON CLOSED
MHV=OFF+1mn
minimum
OFF OFF ON ON ON OPEN
defrost OFF
ON if
OFF 1mn ON ON CLOSED
MHV=OFF+1mn
minimum

Injection valve INV is controlled by discharge temperature, when discharge temperature is more
than 127ºC (260ºF), injection valve switches on, when discharge temperature is less than 105 ºC
(212ºF), injection valve switches off.

34
62-69091-00
SECTION 4
SERVICE

Please follow the schedules

Table 4-1 Unit maintenance schedule


Initial Service Service
km Mile
service A B
5000 3000 ■
30000 18000 ■
60000 36000 ■ ■
90000 54000 ■
120000 72000 ■ ■
150000 90000 ■
180000 108000 ■ ■
210000 126000 ■

Refrigerant: type R134a / R404A


Road compressor oil type: The
compressors are supplied with CARRIER
POLYOLESTER (POE) oil. The presence of
a sticker indicates that oil-change has been
correctly carried out in our Carrier
Transicold plant.
Oils of PAG type are strictly incompatible
with the operation of our unit: never use oil
other than that approved by Carrier.
Oil analysis: on request, we can analyze
your compressor oil.
To do this, we send a small drum with a
4.1 UNIT MAINTENANCE label on which you should indicate: the type
of compressor, the lapse time or mileage
4.1.1 Unit maintenance schedules
since the last oil change, the type of Carrier
Regular servicing is required in order to equipment, the date of initial operation.
optimize the service life and reliability of
your unit. Service operations are to be 4.1.2 Description of maintenance
carried out according to the following operations
schedule.

35
62-69091-00
•Check the tightness of bolts 4.2.1 Belt tension gauge (compressor)
and screws and that the unit is A belt tension gauge provides an accurate
correctly fastened onto the box.
Initial
•Check pressure leak.
and easy method of adjusting belts to their
service proper tension. Properly adjusted belts give
•Check that the road
compressor RPM long lasting and efficient service. Too much
•Check compressor belt tension. tension shortens belt and bearing life, and
•Clean up battery and battery too little tension causes slippage and exces-
clamps sive belt wear. It is also important to keep
•Check belt compressor tension belts and sheaves free of any foreign
•Replace compressor belt every material which may cause the belts to slip.
3000 hours
•Check refrigerant leaks
The Belt Tension gauge can be used to
Service A •Check all electrical adjust all belts. The readings which we
connections specify for Carrier Transicold units are
•Check the cooling mode applicable only for our belts and application,
•Check the defrost operation as the tension is dependent on the size of the
•Check the operation of the cab belt and distance between sheaves. When
control using this gauge, it should be placed as close
•Clean up condenser coil
as possible to the midpoint between two
•Replace idler pulley bearings if
Service B
any.
sheaves.
•Replace filter drier. When installing a new V-belt the tension
Every year •Clean up the expansion valve should be somewhat higher than specified
orifice filter. and readjusted after allowing the unit to run
•Replace compressor oil - only for some time.
use Polyolester oil (POE)
Every approved by Carrier Transicold.
TWO years •Replace refrigerant.
•Replace orifice expansion
valve

Warning: Battery clamps must be well


positioned and tightened after cleaning up.

4.2 BELT MAINTENANCE AND


ADJUSTMENT
Figure 4-1 Belt tension gauge
(Part Number 07-00203)

Belt tension depends on each kit. In each kit


installation instruction, we indicate the belt
tension.

36
62-69091-00
4.3 REMOVING THE NOTE
REFRIGERANT CHARGE Important: only the correct
refrigerant cylinder must be
connected to pressurize the system.
Any other gas or vapor will
contaminate the system which will
require additional purging and
evacuation of the high side
(discharge) of the system.

4.5 EVACUATION AND


DEHYDRATION
4.5.1 General
Moisture is the deadly enemy of refrigerant
Connect a refrigerant system to the unit to systems. The presence of moisture in a
remove refrigerant charge. Refer to refrigeration system can have many
instruction provided by the manufacture of undesirable effects. The most common are
the refrigerant recovery system. copper plating, acid sludge formation,
“freezing-up” of metering devices by free
water, and formation of acids, resulting in
4.4 REFRIGERANT LEAK metal corrosion.
CHECKING
Once the recovery system is OPEN and 4.5.2 Preparation
repairs completed, leak check the unit by a. Evacuate and dehydrate only after
proceeding as follows: pressure leak test. (Refer to section 4.4).
a. The recommended procedure for finding b. Essential tools to properly evacuate and
leaks in a system is with a halide torch or dehydrate any system include a good
electronic leak detector. Testing joints with vacuum pump (5cfm =8m3/h volume
soapsuds is satisfactory only for locating displacement, code 07-00176-01) and a
large leaks. good vacuum indicator such as a thermo-
b. If system is without refrigerant, charge couple vacuum gauge (vacuum indicator).
system with refrigerant to build up pressure c. Keep the ambient temperature above
between 2.1 to 3.5bar (30 to 50 psig). 15.6°C (60°F) to speed evaporation of
Remove refrigerant cylinder and check for moisture. If ambient temperature is lower
leak all connections. than 15.6°C (60°F), ice might form before
c. Remove refrigerant using a refrigerant moisture removal is complete. Heat lamps or
recovery system and repair any leaks. alternate sources of heat may be used to
Evacuate and dehydrate the unit. (Refer to raise system temperature.
section 4.5) Charge unit with refrigerant.
(Refer to section 4.6) NOTE
Use of a compound gauge is not
recommended because of its
inherent inaccuracy.

37
62-69091-00
the vacuum pump. Wait a few minutes to be
4.5.3 Evacuation and dehydration sure the vacuum holds.
procedure
a. Remove refrigerant using a refrigerant e. Break the vacuum with clean dry
recovery system. refrigerant. Use refrigerant that the unit calls
b. The recommended method to evacuate for. Raise system pressure to
and dehydrate the system is to connect three approximately 2 psig.
evacuation hoses to the vacuum pump and f. Remove refrigerant using a refrigerant
refrigeration unit as shown in Figure 4-2 (do recovery system.
not use standard service hoses as they are g. Repeat steps d. to f.
not suited for evacuation purposes). Also, as h. Evacuate unit to 500 microns. Close off
shown, connect an evacuation manifold vacuum pump valve and stop pump. Wait
with special evacuation hoses five minutes to see if vacuum holds. This
c. Open the vacuum pump and electronic checks for residual moisture and/or leaks.
vacuum gauge valves, start the pump, for a i. With a vacuum still in the unit, the
while, Shut off the pump and check to see if refrigerant charge may be drawn into the
the vacuum holds. This operation is to test system from a refrigerant container on
the evacuation setup for leaks, repair if weight scales. The correct amount of
necessary. refrigerant may be added by observing the
d. Open the vacuum pump and electronic scales (see table 2-1).
vacuum gauge valves again. Evacuate unit
until the electronic vacuum gauge indicates NOTE
2000 microns. Close the electronic vacuum Vacuum duration must be at least 8
gauge and vacuum pump valves. Shut off hours.

Figure 4-2 evacuation connection method

38
62-69091-00
NOTE
4.6 CHARGING THE The refrigerant R404A must be
REFRIGERATION SYSTEM charged from liquid valve and not
vapor. The refrigerant R404A is a
4.6.1 Installing a complete charge blend. Charging by the vapor valve
a. Dry the refrigeration circuit and create a will change the properties of the
high vacuum (see section 4.5). refrigerant and affect cooling capacity.
b. Place refrigerant cylinder on scale and
connect charging line from cylinder to 4.6.3 Checking the refrigerant charge
manifold. Purge charging line at outlet valve. Start unit in cooling mode. Run
Purge charging line at inlet manifold. approximately ten minutes. Partially block
c. Note weight of refrigerant cylinder. Be off air flow to condenser coil so discharge
sure that the unit is stopped during this pressure rise to 22 bars (R404A) or 12bar
operation. (R134a).
d. Open liquid valve on refrigerant cylinder. The charge is correct if there are no bubbles
Allow the liquid refrigerant to flow into the at the liquid line sight glass.
unit until the correct weight of refrigerant
has been added as indicated by scales.
4.7 REPLACING THE
NOTE COMPRESSOR
It is possible that all liquid may not be
pulled into the circuit, as outlined in a. Read carefully the following
step (d) above. In this case, close the instructions, strict observance of these
cylinder valve front seat and start the procedures are essential for operator
unit. Refrigerant will accumulate in safety.
the receiver and liquid of the ● do not switch on compressor with
refrigerant cylinder will be sucked by terminal box open.
the compressor. ● remove terminal box cover only with
e. When refrigerant cylinder weight (scale) power source disconnected.
indicates that the correct charge has been ● before compressor installation, slowly
added, close the manifold valves. open the plug on the discharge valve and
vent the nitrogen holding charge.
4.6.2 Adding a partial charge ● ensure that suction and discharge
valves are open before starting the
a. Place refrigerant cylinder on scale and
compressor.
note weight.
● do not touch the compressor shortly
b. Connect charging line from the cylinder
after stopping as surface temperatures
to the manifold. Charge proper volume
will be dangerous.
refrigerant to remove air.
● do not operate the compressor with
c. Start the unit with the compressor turning
hydrocarbon gases.
at 2400 rpm.
b. Evacuate the unit. Repeat the steps in
d. Turn down refrigerant cylinder valve.
section 4.3.
e. Add refrigerant by small quantity.
c. Installation
f. Repeat the step 4.6.3.
To install the compressor, reverse the
procedure outlined when removing the
compressor. Refer to section 2.5 for torque
values.

39
62-69091-00
Pump down the unit, see section 4.5 then
charge system, see section 4.6.

4.8 CHECKING AND


REPLACING FILTER DRIER
Checking filter-drier
Check for any obstruction of the filter-drier
by feeling the inlet and outlet connections of
the liquid line on the filter cartridge. If the
temperature of the outlet connection seems
lower than the temperature of the inlet
connection, replace the filter-drier.

Replacing the filter-drier


Remove the drier mounting clip, then
replace the filter-drier.

4.9 CHECKING AND


REPLACING HIGH PRESSURE Figure 4-3 Typical setup for testing high
CUTOUT SWITCH pressure switch HP1, HP2

4.9.1 Replacing high pressure cutout a. Remove switch.


switch b. Connect ohmmeter or continuity light
–Remove defective switch. across switch terminals. Ohmmeter will
–Install the new switch. indicate resistance and continuity light
will be lighted if switch is closed (HP1 /
4.9.2 Checking high pressure cutout or open (HP2) after relieving pressure.
switch c. Connect switch to a cylinder of dry
nitrogen (see Figure 4-3)
d. Set nitrogen pressure regulator higher
than cut-out point on switch being tested.
Pressure switch cut-in points are shown
in sections 2.3.
e. Close valve on cylinder and open bleed-
off valve.
f. Open cylinder valve. Slowly close bleed-
off valve and increase pressure until the
switch opens. If light is used, light will
go out and if an ohmmeter is used, the
meter will indicate open. Open pressure
on gauge. Slowly open bleed-off valve
(to decrease pressure) until switch closes
(light will light or ohmmeter will move).

40
62-69091-00
4.10. CHECKING AND than “new” cartons. The fiber dust and
REPLACING FAN MOTOR particles are drawn into the evaporator
where they lodge between the evaporator
BRUSHES
fins. If the coil is not cleaned on a regular
The fan motor brushes should be checked basis, sometimes as often as after each trip,
periodically for cleanliness and wear to the accumulation can be great enough to
maintain proper operation of the fan motors. restrict air flow, cause coil icing, repetitive
defrosts and loss of unit capacity. Due to the
“washing” action of normal defrost the fiber
dust and particles may not be visible on the
face of the coil but may accumulate deep
within.
It is recommended to clean the evaporator
coil on a regular basis, not only to remove
cardboard dust, but to remove any grease oil
film which sometimes coats the fins and
prevents water from draining into the drain
Figure 4-4 Fan motor brushes
pan.
To check brushes proceed as follows:
Cardboard fiber particles after being wetted
a. With unit off and battery disconnected,
and dried several times can be very hard to
remove brush cap (item 1; 2 per motor).
remove. Therefore, several washings may be
See Figure 4-4.
necessary.
b. Remove brushes (item 2; 2 per motor)
and check the length of the brush. If the
a. Spray coil with a mild detergent solution
length is less than 1/4 inch (6 mm) the
such as any good commercial-grade
brushes should be replaced (after
automatic dish washer detergent and let the
checking collector).
solution stand for a few minutes. Reverse
c. Blow out the brush holder with low
flush (opposite normal air flow) with clean
pressure air to remove any carbon dust
water at mild pressure. A garden hose with
in the holder. This dust could prevent a
spray nozzle is usually sufficient. Make sure
good contact between the brushes and
drain lines are clean.
collector.
b. Run unit until defrost mode be initiated to
d. Remove the back cover of the motor and
check for proper draining from drain pan.
inspect the collector. If the commutator
is heavily grooved, polish it using fine
sandpaper; do not use abrasive paper. 4.12 CONDENSER COIL-
Wipe out any accumulation of greasy CLEANING
material using a clean rag dampened Remove all foreign material from the
with solvent. Reassemble the motor; condenser coil by reversing the normal air
install new brushes and replace cap. flow. (Air is pulled in through the front and
discharges over the unit.) Compressed air or
4.11 EVAPORATOR COIL- water may be used as a cleaning agent. It
CLEANING may be necessary to use warm water mixed
with any good commercial dishwasher
The use of recycled cardboard cartons is
detergent. Rinse coil with fresh water if a
increasing. The recycled cardboard cartons
detergent is used.
create much more fiber dust during transport

41
62-69091-00
4.13 HOT GAS (TWO-WAY) refrigerant must be evacuated.
SOLENOID AND CONDENSER a. Remove and store the refrigerant charge
CLOSING SOLENOID (TWO in an evacuated container (see section
4.3).
WAY) b. Remove coil snap cap, voltage cover and
4.13.1 Replacing solenoid coil coil assembly. Remove the valve body
head.
It is not necessary to pump the unit down to
c. Check for foreign material in valve body.
replace the coil (see Figure 4-5).
d. Check for damaged plunger and O-ring.
a. Remove coil snap cap, voltage plate and
If O-ring is to be replaced, always put
coil assembly. Disconnect leads and remove
refrigerant oil on O-rings before
coil junction box if necessary.
installing.
b. Verify coil type, voltage and frequency.
This information appears on the coil voltage e. Tighten enclosing tube. If the valve has
plate and the coil housing. been removed from the circuit, check for
c. Place new coil over enclosing tube and eventual leaks.
then install voltage plate and snap cap. f. Install coil assembly, voltage cover and
snap cap.
g. Evacuate and dehydrate the circuit.
h. Install a complete refrigerant charge.
i. Start unit and check operation.

4.14 ADJUSTING THE


COMPRESSOR PRESSURE
REGULATING VALVE (CPR)
The CPR valve is not factory pre-set and
need adjustment. It is necessary to adjust the
valve during commission, proceed with the
following outline:
When adjusting the CPR valve, the unit
must be running in heating or defrost mode.
This will ensure a suction pressure above the
proper CPR setting.

Figure 4-5 Hot gas (two-way) solenoid or


Condenser closing solenoid (Two-way)

4.13.2 Replacing solenoid valve


internal parts
If the hot gas solenoid is to be replaced, or if Figure 4-6 Compressor pressure
a service operation is scheduled on the regulating valve
internal components of the valve, the To adjust the CPR valve, proceed as

42
62-69091-00
follows : line and outlet line from expansion valve.
a. Install a low-pressure gauge. 4. The thermal bulb is located below the
b. Remove cap (item 1) from CPR valve. center of the suction line. This area must be
c. With an 8 mm Allen wrench, loosen the clean to ensure positive bulb contact. Strap
jam nut (Figure 4-6, item 2.). thermal bulb to suction line and insulate
d. Using the 8 mm Allen wrench, adjust the both.
setting screw. To raise the suction 5. Braze the equalizer tubes to expansion
pressure turn the set ting screw (item 3.) valve.
clockwise; to lower the suction pressure, 6. Evacuate by placing vacuum pump on
turn the setting screw counterclockwise. suction and receiver tank service valve.
Refer to section 2.3 for CPR valve 7. Recharge unit.
setting. 8. Check superheat.
e. When the setting has been adjusted,
tighten the jam nut securely against the b. Measuring superheat
setting screw (item3.). This will prevent NOTE
any movement of the setting screw due The expansion valve and bulb
to vibrations in the unit. Replace the cap. location are shown in Figure 4-7.
1. Remove insulation from expansion valve
bulb and suction line.
4.15 THERMOSTATIC 2. Loosen one TXV bulb clamp and make
EXPANSION VALVE sure area under clamp (above TXV bulb)
is clean.
MOP expansion valve characteristics: 3. Place thermocouple above (parallel)
–Rule: in order to avoid the compressor TXV bulb and then secure loosened
overcharge, a MOP expansion valve clamp making sure both bulbs are firmly
(expansion valve with limited flow) is used. secured to suction line as shown in
–Operating: this kind of expansion valve can Figure 4-7.
not open more than MOP setpoint. Any
temperature increase of the sensor can not
open more the expansion valve.
The thermal expansion valve is an automatic
device which maintains constant superheat
of the refrigerant gas leaving the evaporator
regardless of suction pressure. The valve
functions are: (a) automatic response of
refrigerant flow to match the evaporator load
and (b) prevention of liquid refrigerant
entering the compressor. Unless the valve is
defective, it requires adjustment, but
maintenance must be done every year in
order to clean the orifice filter. Figure 4-7 Thermostatic expansion valve
a. Replacing expansion valve bulb and thermocouple
1. Remove refrigerant charge. 4. Connect an accurate gauge to the ¼”
2. Remove insulation from expansion valve port on the suction service valve.
bulb and then remove bulb from suction 5. Run unit until stabilize, set controller
line. temperature lower 5.5ºC than box
3. Loosen inlet nut and unbraze equalizer

43
62-69091-00
temperature.
6. From the temperature/pressure table, handle a photograph. This not only
determine the saturation temperature precludes the possibility of ESD damage,
corresponding to the evaporator outlet but also lowers the possibility of physical
pressure. damage to the electronic components.
7. Note the temperature of the suction gas Although the microprocessor boards are
at the expansion valve bulb. fairly rugged when assembled, they are
8. Subtract the saturation temperature more fragile when separated and should
determined in Step 7 from the average always be handled carefully.
temperature measured in Step 6. The When welding is required on the unit frame,
difference is the superheat of the suction or on the front area of the trailer, ALL
gas. wiring to the microprocessor MUST be
disconnected. When welding is per formed
4.16 MICROPROCESSOR on other areas of the truck and van, the
Although there is less danger of electrical welder ground connection MUST be in close
static discharge ESD damage in the outdoor proximity to the area being welded. It is also
environment, where the processor is likely a good practice to remove both battery
to be handled, proper board handling cables before wedding on either the unit
techniques should always be stressed. frame or the truck to prevent possible
Boards should always be handled by their damage to other components such as the
edges, in much the same way one would alternator and voltage regulator.

44
62-69091-00
Table 4-2 R404A temperature-pressure

Table 4-3 Sensor resistance (RAS)

45
62-69091-00
Table 4-4 R134a Temperature-pressure

46
62-69091-00
SECTION 5
TROUBLE SHOOTING

5.1 REFRIGERATION
5.1.1 Unit will not cool
INDICATION/TROUBLE POSSIBLE CAUSES REFERENCE SECTION
Clutch defective Check
Compressor malfunction Compressor defective 4.7
Belt malfunction Check
Defrost cycle has not terminated 5.1.5
Refrigeration system Abnormal pressure 5.1.6
Hot gas (two-way)solenoid
5.1.11
malfunction

5.1.2 Unit runs but has insufficient cooling


INDICATION/TROUBLE POSSIBLE CAUSES REFERENCE SECTION
Compressor defective 4.7
Compressor
Belt malfunction Check
Abnormal pressure 5.1.6
Refrigeration system Expansion valve malfunction 5.1.10
No or restricted evaporator airflow 5.1.9

5.1.3 Unit operates long or continuously in cooling


INDICATION/TROUBLE POSSIBLE CAUSES REFERENCE SECTION
Hot Load Insufficient pull down time
Box
Defective box insulation or air leak Correct
Abnormal pressure 5.1.6
Refrigeration system
Temperature controller malfunction 2.7

47
62-69091-00
5.1.4 Unit will not heat or heating insufficient
INDICATION/TROUBLE POSSIBLE CAUSES REFERENCE SECTION
Abnormal pressure 5.1.6
Refrigeration Temperature controller malfunction 2.7
Hot gas (two-way)solenoid
5.1.11
malfunction
Clutch defective Check
Compressor
Compressor defective 4.7

5.1.5 Defrost malfunction


INDICATION/TROUBLE POSSIBLE CAUSES REFERENCE SECTION
Automatic defrost will not Hot gas valve Replace
initiate Electronic board malfunction Check defrost parameters
Manual defrost will not Electronic board defective Replace
initiate Check box temperature Check
Defrost cycle initiates but does Hot gas (two-way)solenoid
5.1.11
not defrost malfunction
Frequent defrost Wet load Check defrost parameters

5.1.6 Abnormal pressure

5.1.6.1 Cooling
REFERENCE
INDICATION/TROUBLE POSSIBLE CAUSES
SECTION
Condenser coil dirty 4.12
High discharge pressure The refrigerant is mixed with other gases or
Replace
refrigerant over charge
Compressor worn or broken 4.7
Hot gas (two way) solenoid malfunction 5.1.11
Low discharge pressure Clutch malfunction Check
Belt malfunction Check
Low refrigerant charge 4.6
CPR valves worn or broken 4.14
High suction pressure
Hot gas (two way) solenoid malfunction 5.1.11
CPR valves worn or broken 4.14
Filter-drier partially plugged 4.8
Low refrigerant charge 4.6
Low suction pressure
Expansion valve malfunction 5.1.10
No evaporator air flow or restricted air flow 5.1.9
Excessive frost on coil Check
Compressor defective 4.7
Suction and discharge
Belt malfunction Check
pressures tend to equalize
when unit is operating Clutch malfunction Check
Hot gas (two way) solenoid malfunction 5.1.11

48
62-69091-00
5.1.6.2 Heating
REFERENCE
INDICATION/TROUBLE POSSIBLE CAUSES
SECTION
Over charged system 4.6.3
Condenser fan or HP2 pressure switch
4.9.2
High discharge pressure defective
The refrigerant is mixed with other gases Check
Condenser fan defective Check
Compressor worn or broken 4.7
Clutch malfunction Check
Low discharge pressure
Belt malfunction Check
Low charged system 4.6
Low charged system 4.6
Low suction pressure
CPR valve worn or broken 4.14

5.1.7 Abnormal noise


REFERENCE
INDICATION/TROUBLE POSSIBLE CAUSES
SECTION
Loose mounting bolts and belt Tighten
Worn bearings 4.7
Compressor
Liquids lugging 5.1.10
Insufficient oil Check/4.7
Loose mounting bolts Tighten
Condenser or evaporator fan
Bearings defective Replace

5.1.8 Cab command malfunction


REFERENCE
INDICATION/TROUBLE POSSIBLE CAUSES
SECTION
System is out of power Check
Cab command non-
Microprocessor malfunction 4.16
operational
Microprocessor/Cab command cable Change

5.1.9 No evaporator air flow or restricted air flow


REFERENCE
INDICATION/TROUBLE POSSIBLE CAUSES
SECTION
Frost on coil or dirty Check
Evaporator coil blocked
Fan motor malfunction Check
Evaporator fan loose or defective Check
No or partial evaporator air Evaporator fan rotating backwards Check
flow Evaporator air flow blocked in box Check
Fan motor malfunction Check

49
62-69091-00
5.1.10 Expansion valve malfunction

REFERENCE
POSSIBLE CAUSES
SECTION
External equalizer line plugged Clean
Ice formation at valve seat 4.5
Low suction pressure with high Wax, oil or dirt plugging valve or orifice 4.15
superheat
Broken capillary 4.15
Power assembly failure or partial Replace
Loss of element /bulb charge Replace
Superheat setting too high 4.15
Superheat setting too low 4.15
Low superheat and liquids lugging Choose the wrong type of expansion valve 4.15
in compressor
Improper bulb location or installation 4.15

Improper bulb location or installation 4.15


Fluctuating suction pressure Low superheat setting 4.15
Choose the wrong type of expansion valve Replace

5.1.11 Malfunction hot gas (two-way) solenoid

REFERENCE
INDICATION/TROUBLE POSSIBLE CAUSES
SECTION
No power to valve Check
Improper wiring or loose connections Check
Valve improperly assembled 4.13
Valve does not function properly Coil or coil sleeve improperly assembled 4.13
Movement of plunger restricted due to :
a. Corroded or worn parts
4.13
b. Foreign material lodged in valve
c. Bent or dented enclosing tube
Valve shifts but refrigerant Foreign material lodged under seat 4.13
continues to flow Defective seat Check

50
62-69091-00
5.2 Fault alarm
Please refer to section 2.7, the following is the way to solve malfunction.

5.2.1 EE alarm

51
62-69091-00
5.2.2 BAT alarm

5.2.3 Err alarm

52
62-69091-00
5.2.4 A01/A02 alarm

53
62-69091-00
5.2.5 A04 alarm

5.2.6 A06 alarm

54
62-69091-00
5.2.7 A07 alarm

5.2.8 A09 alarm

55
62-69091-00
5.2.9 A11 alarm

56
62-69091-00
SECTION 6
EXTRACT FROM MATERIAL SAFETY DATA BULLETIN
6.1 POE OIL
1. PRODUCT AND COMPANY IDENTIFICATION
CARRIER SHANGHAI

2. FIRST AID MEASURES


EYE CONTACT:
Flush thoroughly with water. If irritation occurs, call a physician.
SKIN CONTACT:
Wash contact areas with soap and water. High pressure accidental injection through the skin
requires immediate medical attention for possible incision, irrigation and/or debridement.
INHALATION:
Not expected to be a problem.
INGESTION:
Not expected to be a problem. However, if greater than 1/2 liter (pint) ingested, seek medical
attention.

3. FIRE-FIGHTING MEASURES
EXTINGUISHING MEDIA:
Carbon dioxide, foam, dry chemical and water fog
SPECIAL FIRE FIGHTING PROCEDURES:
Water or foam may cause frothing. Use water to keep fire exposed containers cool. Water spray
may be used to flush spills away from exposure. Prevent runoff from fire control or dilution from
entering streams, sewers, or drinking water supply.
SPECIAL PROTECTIVE EQUIPMENT:
For fires in enclosed areas, fire fighters must use self-contained breathing apparatus.
UNUSUAL FIRE AND EXPLOSION HAZARDS:
None. Flash point C (F): 232 (450) (ASTM D–92). Flammable limits – LEL: NA, UEL: NA.
NFPA HAZARD ID:
health: 0,
flammability: 1,
reactivity: 0
HAZARDOUS DECOMPOSITION PRODUCTS:
carbon monoxide

4. ACCIDENTAL RELEASE MEASURES


PROCEDURES IF MATERIAL IS RELEASED OR SPILLED:
Small spills can be absorbed with fire retardant treated sawdust, diatomaceous earth, etc.
Contain and remove larger spills for salvage or disposal according to applicable
regulation.
ENVIRONMENTAL PRECAUTIONS:
Prevent spills from entering storm sewers or drains and contact with soil.
PERSONAL PRECAUTIONS:

57
62-69091-00
see section 6.

5. HANDLING AND STORAGE


STORAGE:
do not store in open or unlabelled containers. Store away from strong oxidizing agents or
combustible material.

6. EXPOSURE CONTROLS / PERSONAL PROTECTION


VENTILATION:
No special requirements under ordinary conditions of use and with adequate ventilation.
RESPIRATORY PROTECTION:
No special requirements under ordinary conditions of use and with adequate ventilation.
EYE PROTECTION:
Normal industrial eye protection practices should be employed.
SKIN PROTECTION:
No special equipment required. However, good personal hygiene practices should always be
followed.

7. STABILITY AND REACTIVITY


HAZARDOUS DECOMPOSITION PRODUCTS:
Carbon monoxide (in case of fire)

8. DISPOSAL CONSIDERATIONS
WASTE DISPOSAL:
EVEN THOUGH THIS PRODUCT IS READILY BIODEGRADABLE, IT MUST NOT BE
INDISCRIMINATELY DISCARDED INTO THE ENVIRONMENT.
This product is suitable for burning in an enclosed, controlled burner for fuel value and for
recycling at an approved facility. In addition, it can be disposed of at an approved waste disposal
facility. Land farming and processing through sewage treatment facilities may be available
disposal options but necessary approvals must first be obtained from appropriate regulatory
authorities. Specific characteristics of the waste at the time of disposal may affect the availability
of the above options.

The complete data sheets are available from Carrier Shanghai on request.

58
62-69091-00
6.2 FORANE R404A/R134a
1. Refrigerant R404A

1.1 PRODUCT AND COMPANY IDENTIFICATION

CARRIER SHANGHAI

Product name: Forane (R) 404A

Chemical family: hydrofluorocarbons


Chemical formula: CF3CH2F/CF3CH2F/CF3CH3
Chemical name: 1,1,1,2-tetrafluoroethane (HFC-134a)/ Pentafluoroethane (HFC-125)/ 1,1,1-
trifluoroethane (HFC-143a).

1.2 COMPOSITION / INFORMATION ON INGREDIENTS


BLEND OF FORANE 125, 143a, 134a
This product is not hazardous to health as define by the European Union dangerous substances
and preparations directives.

2. Refrigerant R134a:

2.1 PRODUCT AND COMPANY IDENTIFICATION

CARRIER SHANGHAI

Product name: Forane (R) 134a


Chemical family: hydrofluorocarbons
Chemical formula: CH 2 FCF 3
Chemical name: Tetrafluoroethane

R404A and R134a:

3.HAZARDS IDENTIFICATION
EMERGENCY OVERVIEW
Colorless liquified gas with faint ether odor.

WARNING
LIQUID AND GAS UNDER PRESSURE, OVERHEATING AND OVERPRESSURIZING
MAY CAUSE GAS RELEASE OF VIOLENT CYLINDER BURSTING. MAY
DECOMPOSE ON CONTACT WITH FLAMES OR EXTREMELY HOT METAL
SURFACES TO PRODUCE TOXIC AND CORROSIVE PRODUCTS. VAPOR
REDUCES OXYGEN AVAILABLE FOR BREATHING AND IS HEAVIER THAN AIR.
HARMFUL IF INHA LED AND MAY CAUSE HEART IRREGULARITIES,
UNCONSCIOUSNESS OR DEATH. LIQUID CONTACT WITH EYES OR SKIN MAY
CAUSE FROSTBITE.

59
62-69091-00
POTENTIAL HEALTH, EFFECTS
Skin contact and inhalation are expected to be the primary routes of occupational exposure to
this material. As with most liquified gases, contact with the rapidly volatilizing liquid can cause
frostbite to any tissue. High vapor concentrations are irritating to the eyes and respiratory tract
and may result in central nervous system (CNS) effects such as headache, dizziness, drowsiness
and, in severe exposure, loss of consciousness and death. The dense vapor of this material may
reduce the available oxygen for breathing. Prolonged exposure to an oxygen deficient
atmosphere may be fatal. Inhalation may cause an increase in the sensitivity of the heart to
adrenaline, which could result in irregular or rapid heartbeats. Medical conditions aggravated by
exposure to this material which could result in irregular or rapid heartbeats. Medical conditions
aggravated by exposure to this material include heart disease or compromised heart
function.
4. FIRST AID MEASURES
EYE CONTACT
Immediately flush with plenty of water. Get medical attention if irritation persists.

SKIN CONTACT
Flush exposed skin with lukewarm water (not hot), or use other means to warm skin slowly. Get
medical attention if frostbitten by liquid or if irritation occurs.

INGESTION
Not applicable. Product is a gas at ambient temperatures.

INHALATION
Remove to fresh air. If not breathing, give artificial respiration. If breathing is difficult, give
oxygen. Get medical attention. DO NOT GIVE ADRENALINE, EPINEPHRIN OR
SIMILAR DRUGS FOLLOWING EXPOSURE TO THIS PRODUCT.

5. FIRE FIGHTING MEASURES


EXTINGUISHING MEDIA
Use extinguishing media appropriate to surrounding fire conditions.
FIRE FIGHTING INSTRUCTIONS
Stop the flow of gas if possible. Use water spray on person making shut-off and on containers
and cylinders. Fire fighters and others who may be exposed to products of combustion should
wear full fire fighting turn out gear(full Bunker Gear) and self-contained breathing apparatus.
Fire fighting equipment should be thoroughly decontaminated after use.

FIRE AND EXPLOSION HAZARDS


Some mixtures of HCFCs and / or HFCs, and air or oxygen may be combustible if pressurized
and exposed to extreme heat or flame.

6. ACCIDENTAL RELEASE MEASURES


IN CASE OF SPILL OR LEAK
Use Halogen leak detector or other suitable means to locate leaks or check atmosphere. Keep
upwind. Evacuate enclosed spaces and disperse gas with floor-level forced-air ventilation.
Exhaust vapors outdoors. Do not smoke or operate internal combustion engines. Remove flames
and heating elements.

60
62-69091-00
7. HANDLING AND STORAGE
HANDLING
Avoid breathing gas. Avoid contact with eyes, skin and clothing. Keep container closed. Use
only with adequate ventilation. Do not enter confined spaces unless adequately ventilated.
STORAGE
Do not apply direct flame to cylinder. Do not store cylinder in direct sun or expose it to heat
above 48ºC (120ºF).
Do not drop or refill this cylinder. Keep away from heat, sparks and flames.

8.EXPOSURE CONTROLS / PERSONAL PROTECTION


EYE / FACE PROTECTION
Where there is potential for eye contact, wear chemical gloggles and have eye flushing
equipment available.
SKIN PROTECTION
Wear appropriate chemical resistant protective clothing and chemical resistant gloves to prevent
skin contact. Consult glove manufacturer to determine appropriate type glove material for given
application. Rinse contaminated skin promptly. Wash contaminated clothing and clean protective
equipment before reuse. Wash skin thoroughly afte r handl0ing.
RESPIRATORY PROTECTION
Avoid breathing gas. When airborne exposure limits are exceeded, use respiratory protection
equipment appropriate to the material and / or its components (full facepiece recommended). For
emergency and other conditions where exposure limit may be significantly exceeded, use an
approved full face positive-pressure, self-contained breathing apparatus or positive-pressure
airline with auxiliary self-contained air supply.

9. STABILITY AND REACTIVITY


INCOMPATIBILITY
Avoid contact with strong alkali or alkaline earth metals, finely powdered metals such as
aluminum, magnesium or zinc and strong oxidizers, since they may react or accelerate
decomposition.
HAZARDOUS DECOMPOSITION PRODUCTS
Thermal decomposition products include hydrogen fluoride, hydrogen chloride, carbon
monoxide, carbon dioxide and chlorine.

10. DISPOSAL CONSIDERATIONS


WASTE DISPOSAL

Recover, reclaim or recycle when practical. Dispose of in accordance with federal, state and
local regulations.

Note : chemical additions to, processing of, or otherwise altering this material may take this
waste management information incomplete, inaccurate, or otherwise inappropriate. Furthermore,
state and local waste disposal requirements may be more restrictive or otherwise different from
federal laws and regulations.

The complete data sheets are available from Carrier Shanghai on request.

61
62-69091-00
SECTION 7
ELECTRICAL SCHEMATIC WIRING DIAGRAMS
The following general safety notices supplement the specific warnings and cautions appearing
elsewhere in this manual. They are recommended precautions that must be understood and
applied during operation and maintenance of the equipment covered herein.

62
62-69091-00
63
62-69091-00

You might also like