CALCULATIONS FOR DRY PRESSURISED AND EXHAUST VENTILATION SYSTEM

OUTSIDE DESIGN CONDITION


1 Outside DBT( Tout) in C 36.3 :- Max. Average temp as per data shown below
0
2 Maximum Temperature Rise( ∆ T) in C 3
3 Inside DBT(Tin) in 0C 39.3
4 Density Correction Factor 0.94

EQUIPMENT HEAT LOAD


1 Inverter Rating (KW) 500.00
2 Euro efficiency (%) 98.20
3 Loss as heat in inverter (KW) 9.165
4 Loss in Aux power consumption(KW) 0.413
5 Total loss as heat (KW) 9.58
6 Total loss as heat for two inverters(KW ) 19.16

7 Loss in UPS (KW) 0.40


8 Loss in LT panel (KW) 0.10
9 Total loss as heat in inverter room 19.66

Design Input Calculation


S.No. Building Equipmen Lighting Total Volume of  Air  Air  Air Qty as Max. of 
t Heat Load Heat Load the Changes Requirement Per Air  air 
Load Building per Hour  as per heat Changes requirem
load ent as per 
heat load

& as per 
air 
chan es
Heq Hlgt HT V ACPH QH QA Q
KW KW KW Cu.M CMH CMH CMH
=1W/Sq =Heq+Hlgt =A* =HT *1000/(C P =V * =max of 
ft height of  * ∆T * Density ACPH QH and QA
building of air*Density
Correction
factor)
1.0 Inverter Room
1.1 Inverter Room 19.66 0 19.66 99.48 15 20442 1492 20442