Professional Documents
Culture Documents
Asdasd
Asdasd
P43x/EN M/Am7
Technical Manual
Volume 1 of 2
MiCOM P433, P435
P43x/EN M/Ac7
(AFSV.12.10220 D)
Version P433 -308 -410/411 -612
P435 -308 -413/414/415 -612
Technical Manual
Volume 1 of 2
! Warning
When electrical equipment is in operation dangerous voltage will be present in certain parts of the equipment.
Failure to observe warning notices, incorrect use or improper use may endanger personnel and equipment
and cause personal injury or physical damage.
Before working in the terminal strip area, the device must be isolated. Where stranded conductors are used,
insulated crimped wire end ferrules must be employed.
The signals 'M a i n : B l o c k e d / f a u l t y ' and 'S F M O N : W a r n i n g ( L E D ) ' (permanently assigned to the LEDs
labeled 'OUT OF SERVICE' and 'ALARM') can be assigned to output relays to indicate the health of the
device. Schneider Electric strongly recommends that these output relays are hardwired into the
substation's automation system, for alarm purposes.
Any modifications to this device must be in accordance with the manual. If any other modification is made
without the express permission of Schneider Electric, it will invalidate the warranty, and may render the
product unsafe.
Proper and safe operation of this device depends on appropriate shipping and handling, proper storage,
installation and commissioning, and on careful operation, maintenance and servicing.
For this reason only qualified personnel may work on or operate this device.
The User should be familiar with the warnings in the Safety Guide (SFTY/4LM/G11 or later version), with the
warnings in Chapters 5, 9, 10 and 11 and with the content of Chapter 13, before working on the equipment. If
the warnings are disregarded, it will invalidate the warranty, and may render the product unsafe.
A protective conductor (ground/earth) of at least 1.5 mm2 must be connected to the DHMI protective
conductor terminal to link the DHMI and the main relay case; these must be located within the same
substation.
To avoid the risk of electric shock the DHMI communication cable must not be in contact with hazardous live
parts.
The DHMI communication cable must not be routed or placed alongside high-voltage cables or connections.
Currents can be induced in the cable which may result in electromagnetic interference.
Qualified Personnel
are individuals who
are familiar with the installation, commissioning and operation of the device and of the system to which it is being connected;
are able to perform switching operations in accordance with safety engineering standards and are authorized to energize and de-
energize equipment and to isolate, ground and label it;
are trained in the care and use of safety apparatus in accordance with safety engineering standards;
are trained in emergency procedures (first aid).
Note
The operating manual for this device gives instructions for its installation, commissioning and operation. However, the manual cannot
cover all conceivable circumstances or include detailed information on all topics. In the event of questions or specific problems, do
not take any action without proper authorization. Contact the appropriate Schneider Electric technical sales office and request the
necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric, including settlement of
warranties, result solely from the applicable purchase contract, which is not affected by the contents of the operating manual.
Changes after going to press
3 Operation 3-1
3.1 Modular Structure 3-1
3.2 Operator-Machine Communication 3-3
3.3 Configuration of the Measured (Function Group LOC) 3-4
Value Panels
3.4 Serial Interfaces 3-11
3.4.1 PC interface (Function Group PC) 3-11
3.4.2 Communication Interface 1 (Function Group COMM1) 3-13
3.4.3 Communication Interface 2 (Function Group COMM2) 3-22
3.4.4 Communication interface 3 (Function Group COMM3) 3-25
3.4.5 IEC 61850 Communication (Function groups IEC, 3-30
interface GOOSE and GSSE)
3.5 IRIG-B Clock Synchronization (Function Group IRIGB) 3-38
3.6 Configurable Function Keys (Function Group F_KEY) 3-39
3.7 Configuration and Operating Mode (Function Group INP) 3-42
of the Binary Inputs
3.8 Measured Data Input (Function Group MEASI) 3-44
3.8.1 Direct current input 3-45
3.8.2 Input to connect a resistance 3-48
thermometer
3.9 Configuration, Operating Mode, (Function Group OUTP) 3-49
and Blocking of the Output Relays
3.10 Measured Data Output (Function Group MEASO) 3-52
3.10.1 BCD Measured Data Output 3-55
3.10.2 Analog Measured Data Output 3-60
3.10.3 Output of ‘External’ Measured 3-66
Data
3.11 Configuration and Operating Mode (Function Group LED) 3-67
of the LED Indicators
4 Design 4-1
4.1 Designs 4-2
4.2 Dimensional Drawings 4-4
4.2.1 Surface-Mounted Case 4-4
4.2.2 Flush Mounted Case 4-5
4.2.3 Device views for Connection of Detachable HMI 4-7
4.3 Modules 4-8
7 Settings 7-1
7.1 Parameters 7-1
7.1.1 Device Identification 7-1
7.1.2 Configuration Parameters 7-5
7.1.3 Function Parameters 7-63
7.1.3.1 Global 7-63
7.1.3.2 General Functions 7-69
7.1.3.3 Parameter Subsets 7-86
7.1.3.4 Control 7-117
9 Commissioning 9-1
9.1 Safety Instructions 9-1
9.2 Commissioning Tests 9-3
10 Troubleshooting 10-1
11 Maintenance 11-1
12 Storage 12-1
Appendix
A Glossary
B List of Signals
C List of Bay Types
D Overview of Changes
The MiCOM P43x distance protection devices have been designed for selective short-
circuit protection, ground fault protection, and overload protection in medium- and high-
voltage systems. The systems can be operated as resonant-grounded, grounded-neutral
or isolated-neutral systems. The multitude of protection functions incorporated into the
devices enable the user to cover a wide range of applications in the protection of cable
and line sections, transformers and motors. Because of the specific functions provided
by the devices the following preferred areas of application have evolved:
The P43x distance protection and control devices feature the following general functions:
DEV01
to Control and monitoring of up to three switchgear units ( ) ( )
DEV03
CMD_1 12 single-pole commands ( ) ( )
SIG_1 12 single-pole signals ( ) ( )
ILOCK Interlocking logic ( ) ( )
Functional diagram
Vref
I
V
Signaling
General functions
The functions listed in the tables above are complete function groups, which may be
individually configured or cancelled (except for ILOCK), depending on the application
(e.g. included in or excluded from the protection device’s configuration).
Unused or cancelled function groups are hidden to the user (except for the configuration
parameter) and are not supported. (An exception is the function MAIN, which is always
visible.) Communication functions and measured value functions may also be
configured or excluded.
This concept provides a large choice of functions and makes wide-ranging application of
the protection devices possible, with just one model version. On the other hand simple
and clear parameter settings and adaptations to each protection scheme (and optional
control purposes) can be made.
In this way the protection and control functions (except for ILOCK) can be included in or
excluded from the configuration; they are arranged on the branch "General Functions" of
the menu tree.
Control functions
The optional control functions are designed for the control of up to three electrically
operated switchgear units equipped with plant status signaling and located in the bay of
a medium-voltage substation or a high-voltage station with basic topology. The MiCOM
P433 and P435 devices have over 80 predefined bay types stored for selection, and it is
also possible to load user-defined bay templates.
Global functions
In addition to the listed features, and extensive self-monitoring, the P43x distance
protection and control devices offer the following global functions:
Design
The distance protection devices P43x are modular in design. The plug-in modules are
housed in a robust aluminum case and are electrically interconnected via one analog
module and one digital module.
Function keys
There are six freely configurable function keys available for both the 40TE case and
84TE case devices. These may be used for easy control operation access.
Current-measuring inputs
Four voltage-measuring inputs
Up to 20 binary signal inputs (opto couplers) with user-definable function assignment
Up to 30 output relays with user-definable function assignment
One PT 100 input (optional)
One input, 0 to 20 mA (optional)
Two outputs, 0 to 20 mA (optional)
The P435 fitted in the 40TE case has the following inputs and outputs:
Current-measuring inputs
4 or 5 voltage-measuring inputs (ordering option)
Up to 16 binary signal inputs (opto couplers) with user-definable function assignment
Up to 30 output relays with user-definable function assignment
One PT 100 input (optional)
One input, 0 to 20 mA (optional)
Two outputs, 0 to 20 mA (optional)
The P435 fitted in the 84TE case has the following inputs and outputs:
Current-measuring inputs
4 or 5 voltage-measuring inputs (ordering option)
Up to 28 binary signal inputs (opto couplers) with user-definable function assignment
Up to 46 output relays with user-definable function assignment
One PT 100 input (optional)
One input, 0 to 20 mA (optional)
Two outputs, 0 to 20 mA (optional)
The nominal current and voltage values for the measuring inputs on the P43x can be set.
The nominal voltage range for the binary signal inputs (opto coupler) is 24 to 250 VDC.
The auxiliary voltage input for the power supply is also designed with an extended range.
The nominal voltage ranges are 48 to 250 VDC and 100 to 230 VAC. A 24 VDC version
is also available.
All output relays can be utilized for both signaling and command purposes.
The optional PT 100 input is lead-compensated, balanced and linearized for PT 100
resistance thermometers as per IEC 751.
Two selectable measured values (cyclically updated measured operating data and
stored measured fault data) can be output as a burden-independent direct current via
the two optional 0 to 20 mA outputs. The characteristics are defined via 3 adjustable
interpolation points allowing a minimum output current (4 mA, for example) for slave-side
open-circuit monitoring, knee-point definition for fine scaling, and a limitation to lower
nominal currents (10 mA, for example). Where sufficient output relays are available, a
selectable measured value can be output by contacts coded in BCD form.
Interfaces
Control and display:
Information is exchanged through the local control panel (HMI), the PC interface, or the
optional communication interfaces.
2 Technical Data
2.1 Conformity
Notice
Applicable to P433, version 308-410/411-612 and P435 version -308-413/414/415-612
Declaration of conformity
(As per Article 10 of EC Directive 72/73/EC)
The products designated as "P433 and P435 Distance Protection and Control Units"
have been designed and manufactured in compliance with European standards
EN 60255-6 and EN 60010-1 and with the 'EMC Directive' and the 'Low Voltage
Directive' as issued by the Council of the European Community.
Installation Position
Vertical ± 30°
Degree of Protection
Per DIN VDE 0470 and EN 60529 or IEC 529.
IP 52; IP 20 for rear connection space with flush-mounted case
(IP 10 for ring-terminal connection)
Weight
40TE case: approx. 7 kg
84TE case: approx. 11 kg
Terminals
PC interface (X6):
EIA RS232 (DIN 41652) connector, type D-Sub, 9-pin.
Environment
Temperatures
Recommended temperature range: -5 °C to +55 °C (23 °F to 131 °F)
Storage and transit: -25 °C to +70 °C (-13 °F to 158 °F)
Solar Radiation
Direct solar radiation on the front of the device must be avoided.
2.4 Tests
Type tests
All tests per EN 60255-6 / IEC 60255-6 or EN 50121-5.
Electromagnetic
compatibility (EMC)
Interference Suppression
Per EN 55022 or IEC CISPR 22, Class A.
Insulation
Voltage Test
Per EN 61010-1 or IEC 255-5, 2 kV AC, 60 s
Only direct voltage (2.8 kV DC) must be used for the voltage test on the power supply
inputs. The PC interface must not be subjected to the voltage test.
Corrosion resistance
Flowing Mixed Gas Corrosion Test
Per IEC 60068-2-60: 1995, part 2, test Ke, severity level 3
21 days at 75 % relative humidity and 30 °C
with reaction to increased concentrations of H2S, NO2, Cl2 and SO2
_______________________________________________________________
§
For this EN, ENV or IEC standard, the DIN EN, DINV ENV or DIN IEC edition,
respectively, was used in the test.
Mechanical robustness
1 (*)
Vibration Test
Per EN 60255-21-1 or IEC 255-21-1, test severity class 1
Frequency range in operation: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Frequency range during transport: 10 to 150 Hz, 1 g
Mechanical robustness
2(**)
Vibration Test
Per EN 60255-21-1 or IEC 255-21-1, test severity class 2
Frequency range in operation: 10 to 60 Hz, 0.075 mm and 60 to 150 Hz, 1.0 g
Frequency range during transport: 10 to 150 Hz, 2 g
_______________________________________________________________
(*)
Mechanical robustness 1:
Applicable to the following case variants:
- Flush mounted case, flush-mounting method 1 (without angle brackets and frame)
(**)
Mechanical robustness 2:
Applicable to the following case variants:
- Flush mounted case, flush-mounting method 2 (with angle brackets and frame)
- Surface-Mounted Case
Voltage Test
Per IEC 255-5.
2.2 kV AC, 1 s.
Only direct voltage (2.8 kV DC) must be used for the voltage test on the power supply
inputs.
The PC interface must not be subjected to the voltage test.
Measuring inputs
Current
Nominal current Inom: 1 and 5 A AC (adjustable)
Nominal burden per phase: < 0.1 VA at Inom
Load rating:
continuous: 4 Inom
for 10 s: 30 Inom
for 1 s: 100 Inom
Nominal surge current: 250 Inom
Voltage
Nominal voltage Vnom: 50 to 130 V AC (settable)
Nominal burden per phase: < 0.3 VA at Vnom = 130 V AC
Load rating: continuous 150 V AC
Frequency
Nominal frequency fnom: 50 Hz and 60 Hz (settable)
Operating range: 0.95 to 1.05 fnom
Frequency protection: 40 to 70 Hz
Special variant:
Vin > Switching threshold: VA • 5 mA ± 30 %.
Notes
The standard variant of binary signal inputs (opto couplers) is recommended in most
applications, as these inputs operate with any voltage from 19 V. Special variants with
higher pick-up/drop-off thresholds are provided for applications where a higher switching
threshold is expressly required.
The maximum voltage permitted for all binary signal inputs is 300V DC.
Resistance thermometer
Resistance thermometer: only PT 100 permitted,
Value range: -40.0 °C to +215.0 °C
3-wire configuration: max. 20 Ω per conductor.
Open and short-circuited input permitted
Open-circuit monitoring: Θ > +215 °C and Θ < -40 °C
Output relays
Binary I/O module X (6xI, 6xO):
for switchgear control
Rated voltage: 250 V DC, 250 V AC
Continuous current: 8A
Short-duration current: 30 A for 0.5 s
Making capacity: 1000 W (VA) at L/R = 40 ms
Breaking capacity: 0.2 A at 220 V DC and L/R = 40 ms,
4 A at 230 V AC and cosϕ = 0.4
IRIG-B interface
Minimum / maximum input voltage level (peak-peak): 100 mVpp / 20 Vpp
Input impedance: 33 kΩ at 1 kHz
Electrical isolation: 2 kV
2.6 Interfaces
Communication interfaces
COMM1, COMM2,
COMM3
The communication module can be provided with up to three communication channels,
depending on the module variant. Channel 1 and 3 may either be equipped to connect
wire leads or optical fibers and channel 2 is only available to connect wire leads.
Communication interface 2 can only be operated with the interface protocol based on
IEC 60870-5-103.
Transmission rate: 300 or 57600 baud (settable).
Wire Leads
Per RS 485 or RS 422, 2 kV isolation
Distance to be bridged
Point-to-point connection: max. 1200 m
Multipoint connection: max. 100 m
___________________________________________________________________
1)
Distance to be bridged given for identical optical outputs and inputs at both ends, a
system reserve of 3 dB, and typical fiber attenuation.
IEC Communication
interface
Wire Leads
IEC 61850-compliant, Ethernet-based communications:
Transmission rate: 10 or 100 Mbit/s
RJ45, 1.5 kV isolation
Maximum distance: 100 m
2.8 Settings
Distance protection
Minimum starting time: 12 ms
Starting reset time: 30 ms ± 10 ms
Directional sensitivity
up to 2 s after general starting: ∞
up to 2 s after general starting and for switching on to fault: 200 mV ± 20 mV
Shortest tripping time: approx. 19 ms
Starting and measurement resetting ratio (hysteresis): 0.95
Time-voltage protection
Operate time including output relay (measured value from nominal value to 1.2-fold
operate value or measured value from nominal value to 0.8-fold operate value):
≤ 40 ms, approx. 30 ms
Reset time (measured value from 1.2-fold operate value to nominal value or
measured value from 0.8-fold operate value to nominal value):
≤ 45 ms, approx. 30 ms
Resetting ratio for V<>: 1 to 10 % (settable)
2.9 Deviations
Definitions
Reference conditions
Sinusoidal signals at nominal frequency fnom, total harmonic distortion ≤ 2 %, ambient
temperature 20 °C (68 °F), and nominal auxiliary voltage VA,nom
Deviation
Deviation relative to the setting under reference conditions.
Distance protection
Starting V<, VNG>, VNG>>
Deviation: ± 3 %
Direction determination
Deviation: ± 3°
Measuring-circuit
monitoring
Operate values Ineg, Vneg
Deviation: ± 3 %
Time-overcurrent
protection
Operate values I>, IN>
Deviation: ± 5 %
Thermal overload
protection
Operate value
Deviations: ± 7.5 %
Over-/underfrequency
protection
Operate values f<>
Deviation: ± 30 mHz (for fnom = 50 Hz)
Deviation: ± 40 mHz (for fnom = 60 Hz)
Over-/undervoltage
protection
Operate values
V<>, Vpos<>: ± 1% (in the range: 0.6 to 1.4 Vnom)
VNG>, Vneg>: ± 1% (in the range: > 0.3 Vnom)
Power directional
protection
Operate values P<>, Q<>
Deviation: ± 5 %
Sector angle:
Deviation: 1°
PT100 Resistance
Thermometer
Deviation: ± 2 ° or ± 1 %
20 mA analog measured
data output
Deviation: ± 1 %
Output residual ripple with max. load: ± 1 %
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fnom, total harmonic distortion ≤ 2 %, ambient
temperature 20 °C (68 °F), and nominal auxiliary voltage VA,nom.
Deviation
Deviation relative to the setting under reference conditions.
Definite-time stages
Deviation ± 1 % + 20 to 40 ms
Inverse-time stages
Deviation when I ≥ 2 Iref: ± 5 % + 10 to 25 ms
or for "extremely inverse" IEC characteristics and for thermal
overload characteristics: ± 7.5 % + 10 to 20 ms
Definitions
Reference Conditions
Sinusoidal signals at nominal frequency fnom, total harmonic distortion ≤ 2 %, ambient
temperature 20 °C (68 °F), and nominal auxiliary voltage VA,nom.
Deviation
Deviation relative to the setting under reference conditions.
Operating data
measurement
Measuring input currents
Deviation: ± 1 %
Load angle
Deviation: ± 1°
Frequency
Deviation: ± 10 mHz
Internal clock
With free running internal clock:
Deviation: < 1 min/month
Overload memory
Number: The 8 most recent overload events
Scope for signals: All signals relevant for an overload event from a total of
1024 different logic state signals
Depth: 200 entries per overload event
Fault memory
Number: The 8 most recent fault events
Depth for fault values: Sampled values for all measured currents and voltages
Depth for fault values: max. number of cycles per fault can be set by user;
820 periods in total for all faults, that is 16.4 s (for fnom = 50 Hz)
or 13.7 s (for fnom = 60 Hz)
Signals
Time resolution: 1 ms
Fault values
Time resolution: 20 sampled values per period
Residual current
Dynamic range: 16 Inom
Amplitude resolution: 1.0 mAr.m.s. for Inom = 1 A
4.9 mAr.m.s. for Inom = 5 A
Voltages
Dynamic range: 150 V AC
Amplitude resolution: 9.2 mVr.m.s.
The following equation is used to calculate the specifications of a current transformer for
the offset maximum primary current:
(
Vsat = (R nom + R i ) ⋅ n ⋅ I nom = Rop + Ri ⋅ k ⋅ I1' ,max )
with:
Vsat: saturation voltage (IEC knee point)
I'1,max: non-offset maximum primary current, converted to the secondary side
Inom: rated secondary current
n: rated overcurrent factor
k: over-dimensioning factor
Rnom: rated burden
Rop actual connected operating burden
Ri internal burden
The specifications of a current transformer can then be calculated for the minimum
required saturation voltage Vsat as follows:
( )
Vsat = Rop + R i ⋅ k ⋅ I1,max
n≥
(Rop + Ri ) ⋅k ⋅
I1' ,max
=
(Pop + Pi ) ⋅k ⋅
I1' ,max
( Rnom + Ri ) Inom ( Pnom +P i ) Inom
with
Pi = Ri ⋅ Inom
2
Theoretically, the specifications of the current transformer could be calculated for lack of
saturation by inserting instead of the required over-dimensioning factor k its maximum
value:
k max ≈ 1 + ωT1
with:
ω: system angular frequency
T1: system time constant
The over-dimensioning factor 'k' necessary for the distance protection may be read from
figure 2-1. The dotted line depicts the theoretical characteristic k(T1) = 1 + ωT1.
Specifications for current transformers should be within the error limit values for class
5P. CTs class TPY per IEC 44-6 Part 6 ("Current Transformers with Anti-remanence
Cores") should preferably be used in case a HSR is applied.
3 Operation
The P43x, a numerical device, is part of the MiCOM P 30 family of devices. The device
types included in this family are built from identical uniform hardware modules.
Figure 3-1 shows the basic hardware structure of the P43x.
The external analog and binary quantities – electrically isolated – are converted to the
internal processing levels by the peripheral modules T, Y, and X. Commands and
signals internally generated by the device are connected to the external plant via
contacts through the binary I/O modules X. The external auxiliary voltage is applied to
the power supply module V, which supplies the auxiliary voltages that are required
internally.
Analog data is transferred from the transformer module T via the analog bus module B to
the processor module P. The processor module contains all the elements necessary for
the conversion of measured analog values, including multiplexers and analog/digital
converters. The analog data conditioned by the analog I/O module Y is transferred to
the processor module P via the digital bus module. Binary signals are fed to the
processor module by the binary I/O modules X via the digital bus module. The
processor handles the processing of digitized analog values and of binary signals,
generates the protective trip and signals, and transfers them to the binary I/O modules X
via the digital bus module. The processor module also handles overall device
communication. As an option, communication module A can be mounted on the
processor module to provide serial communication with substation control systems.
The control and display elements of the integrated local control panel and the integrated
PC interface are housed on control module L.
The following interfaces are available for the exchange of information between the user
and the device:
All settings and signals as well as all measurements and control functions are arranged
within the branches of the menu tree following a scheme that is uniform throughout the
device family. The main branches are:
‘Parameters’ branch
All settings are contained in this branch. This branch carries all settings, including the
device identification data, the configuration parameters for adapting the device interfaces
to the system, and the function parameters for adapting the device functions to the
process. All values in this group are stored in non-volatile memory, which means that
the values will be preserved even if the power supply fails.
‘Operation’ branch
This branch includes all information relevant for operation such as measured operating
data and binary signal states. This information is updated periodically and consequently
is not stored. In addition, various controls are grouped here, for example those for
resetting counters, memories and displays.
‘Events’ branch
The third branch is reserved for the recording of events. All information in this group is
therefore stored. In particular, the start/end signals during a fault, the measured fault
data, and the sampled fault waveforms are stored here and can be read out when
required.
Settings and signals are displayed either in plain text or as addresses, in accordance
with the user’s choice.
The configuration of the local control panel also permits the installation of Measured
Value 'Panels’ on the LCD display. Different Panels are automatically displayed for
specific system operating conditions. Priority increases from normal operation to
operation under overload conditions, operation during a ground fault, and finally to
operation following a short circuit in the system. Thus the P43x provides the measured
data relevant for the prevailing conditions.
The P43x offers Measured Value Panels, which display the measured values relevant at
a given time.
During normal power system operation, the Operation Panel is displayed. As an event
occurs, the display switches to the appropriate Event Panel - provided that measured
values have been selected for the Event Panels. In the event of overload or ground fault
events, the display will automatically switch to the Operation Panel at the end of the
event. In the event of a fault, the Fault Panel remains active until the LED indicators or
the fault memories are reset.
Operation Panel
The Operation Panel is displayed after the set return time has elapsed, provided that at
least one measured value has been configured.
The user can select which of the measured operating values will be displayed on the
Operation Panel by means of an ‘m out of n’ parameter. If more measured values are
selected for display than the LC display can accommodate, then the display will switch to
the next set of values at intervals defined by the setting at
L O C : H o l d - t i m e f o r P a n e l s or when the appropriate key on the local control panel
is pressed.
LOC: Fct.
Operation Panel
[ 053 007 ]
FT_RC: Record.
in progress S1 1 ≥1 C
[ 035 000 ]
R1
OL_RC: Record.
in progress ≥1
[ 035 003 ] Operation Panel
GF_RC: Record.
in progress
[ 035 005 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
FT_RC: Reset
record. USER
[ 003 006 ]
1: execute
FT_RC: Reset
record. EXT
[ 005 243 ]
MAIN: Reset LED
306 020
50Z01CXA_EN
Fault Panel
The Fault Panel is displayed in place of another data panel when there is a fault,
provided that at least one measured value has been configured. The Fault Panel
remains on display until the LED indicators or the fault memories are cleared.
The user can select the measured fault values that will be displayed on the Fault Panel
by setting an 'm out of n' parameter. If more measured values are selected for display
than the LC display can accommodate, then the display will switch to the next set of
values at intervals defined by the setting at L O C : H o l d - ti m e fo r P a n e l s or when
the appropriate key on the local control panel is pressed.
Measured value 3
Measured value n
Selected meas.values
LOC: Hold-time
for Panels
[ 031 075 ]
R
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1 Fault Panel
MAIN: General
reset EXT
[ 005 255 ]
FT_RC: Reset
record. USER
[ 003 006 ]
1: execute
FT_RC: Reset
record. EXT
[ 005 243 ]
MAIN: Reset LED
306 020
50Z01EJA_EN
The user can select the measured values that will be displayed on the Ground Fault
Panel by setting an 'm out of n' parameter. If more measured values are selected for
display than the LC display can accommodate, then the display will switch to the next set
of values at intervals defined by the setting at L O C : H o l d - ti m e fo r P a n e l s or when
the appropriate key on the local control panel is pressed.
Selected
measured values
LOC: Hold-time
for Panels
[ 031 075 ]
R
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1 Ground Fault Panel
MAIN: General
reset EXT
[ 005 255 ]
GF_RC: Reset
record. USER
[ 100 000 ]
1: execute
GF_RC: Reset
record. EXT
[ 005 242 ]
MAIN: Reset
LED
306 020
50Z0139 B_EN
Overload Panel
The Overload Panel is automatically displayed in place of another data panel when there
is an overload, provided that at least one measured value has been configured.
The Overload Panel remains on display until the overload ends, unless a fault occurs.
In this case the display switches to the Fault Panel.
The user can select the measured values that will be displayed on the overload panel by
setting a 'm out of n' parameter. If more measured values are selected for display than
the LC display can accommodate, then the display will switch to the next set of values at
intervals defined by the setting at L O C : H o l d - ti m e fo r P a n e l s or when the
appropriate key on the local control panel is pressed.
LOC: Fct.
Overload Panel
[ 053 005 ]
50Z0140 A_EN
Selection of the
control point
Function keys may also be configured as control keys (e.g. Local/Remote, Device
selection, Device OPEN, Device CLOSE). See figure 3-6 and section 'Configurable
Function Keys F1 to Fx (particularly as control keys)' in Chapter 6. Therefore new
settings have been added to function group LOC.
Switchgear units can be controlled from a remote location or locally. Switching between
local and remote control is achieved using either an appropriately configured function
key on the local control panel or an external key switch. The position of this key switch
is interrogated via an appropriately configured binary signal input (configuration at
M A I N : I n p . a s g . L / R k e y s w .) .
To see details on the use of a function key as a switch between local and remote control
see section 'Configurable Function Keys (Function Group F_KEY)' in Chapter 3 and
section 'Configurable Function Keys F1 to Fx (particularly as control keys)' in Chapter 6.
If only remote control is enabled then there will be a local access blocking. If only local
control is enabled then there will be a remote access blocking.
1
2
1: R <-> L
Local/Remote key 2: R & L <-> L
[006 004]
1)
F1 S1 1 ≥1 1 ≥1
& &
R1 0 ≥1 2,3 LOC: Rem.acc.block.
& active
& [ 221 004 ]
&
Local 1 LOC: Loc.acc.block.
& active
Remote 2 [ 221 005 ]
& LOC: Local &
Local & Remote 3 Remote Control
305 560
MAIN: Inp.asg.
L/R key sw.
[ 221 008 ]
Signal 1
Signal 2
m out of n
Signal 3
Signal n
Without function
Selected signal
1
Further information on function keys and their application is given in Chapter 3, section
'Configurable Function Keys (Function Group F_KEY)' and section 'Resetting Actions' as
well as in Chapter 6, section 'Configurable Function Keys F1 to Fx (general)'.
Note: There is an LED indicator situated next to each function key which – just as the
other LED indicators – is freely configurable independently of the configuration of the
function keys (e.g. there is free function assignment to red and green LED indicators).
Configuration of the
READ key
As with L O C : F c t . m e n u j m p l i s t x up to 16 functions may also be selected from
the same menu jump list at L O C : A s s i g n m e n t r e a d k e y . They are triggered in
sequence by repeatedly pressing the key.
Configuration of the
CLEAR key ('C')
Similarly to the setting at M A I N : F c t . a s s i g n . r e s e t x up to 10 reset functions
may be selected from a list at L O C : F c t. r e s e t k e y. These are carried out by
pressing the C CLEAR key. Details on the resetting functions are given in section
'Resetting Actions' of Chapter 3 'Main Functions of the P43x (Function Group MAIN)'.
If the communication module A with two communication channels is installed, settings for
two communication interfaces will be available. The setting of communication interface 1
(COMM1) may be assigned to the physical communication channels 1 or 2 (see section
"Main Functions"). If the COMM1 settings have been assigned to communication
channel 2, then the settings of communication interface 2 (COMM2) will automatically be
active for communication channel 1. Communications channel 2 can only be used to
transmit data to and from the P43x if its PC interface has been de-activated. As soon as
the PC interface is used to transmit data, communications channel 2 becomes "dead".
If tests are run on the P43x, the user is advised to activate the test mode. In this way the
PC or the control system will recognize all incoming test signals accordingly (see section
"Main Functions").
Communication between the device and a PC is through the PC interface. In order for
data transfer between the P43x and the PC to function, several settings must be made in
the P43x.
There is a support software available as an accessory for P43x control (see Chapter 13).
There are several different interface protocols available at the communication interface
1. The following user-selected interface protocols are available for use with the P43x:
In order for data transfer to function properly, several settings must be made in the P43x.
1 2 3 4 5 6 7
COMM1: Command
block. USER
[ 003 172 ]
0
1
0: No COMM1: Command
>-1 blocking
1: Yes [ 003 174 ]
COMM1: Command
block. EXT
[ 003 173 ]
COMM1: Basic
IEC870-5 enabl
[ 003 215 ] COMM1: Com-
municat. protocol
[ 003 167 ]
0
1 c
0: No c
1: Yes c
c
COMM1: Addit.
-101 enable c
[ 003 216 ]
c
0 Selected protocol COMM1: Selected
protocol
1 304 415
0: No
1: Yes
COMM1: Addit.
ILS enable
[ 003 217 ]
0
1
0: No
1: Yes
COMM1: MODBUS
enable
[ 003 220 ]
0
1
0: No
1: Yes
COMM1: DNP3
enable
[ 003 231 ]
0
1
0: No
1: Yes
COMM1: COURIER
enable
[ 103 040 ]
0
1
0: No
1: Yes
2 220 64Z51FEA
COMM1: Spontan.
sig. enable
[ 003 177 ]
COMM1: Selected
protocol
304 415
COMM1: IEC C
870-5-103
[ 003 219 ]
C
COMM1: General
enable USER
[ 003 170 ] C
1: Yes
COMM1: Command C
blocking
[ 003 174 ]
COMM1: Sig./meas.
block.USER
[ 003 076 ]
0
1
0: No COMM1: Sig./meas.
1: Yes val.block.
[ 037 075 ]
COMM1: Sig./meas.
block EXT
[ 037 074 ]
MAIN: Prot. ext.
disabled
[ 038 046 ]
45Z63FFA_EN
3-9 Communication interface 1, settings for the IEC 60870-5-103 interface protocol
C
COMM1: Command
blocking
[ 003 174 ]
C
MAIN: Test mode
[ 037 071 ]
COMM1: Sig./ C
meas.block.USER
[ 003 076 ]
0 COMM1: Communic-
Communication interface ation error
304 422
1
0: No COMM1: Sig./
meas.val.block.
1: Yes [ 037 075 ]
COMM1: Sig./meas.
block EXT
[ 037 074 ]
3-10 Communication interface 1, settings for the IEC 870-5-101 interface protocol
COMM1: Selected C
protocol
304 415
C
COMM1: General
enable USER
[ 003 170 ]
1: Yes C
COMM1: Command
blocking
[ 003 174 ] COMM1: Communic-
Communication interface ation error
304 422
MAIN: Test mode
[ 037 071 ]
COMM1: Sig./
meas.block.USER
[ 003 076 ]
1
COMM1: Sig./
0: No meas.val.block.
[ 037 075 ]
1: Yes
COMM1: Sig./meas.
block EXT
[ 037 074 ]
49Z64FHA_EN
Checking spontaneous
signals
For interface protocols based on IEC 60870-5-103, IEC 870-5-101, or ILS_C it is
possible to select a signal for test purposes. The transmission of this signal to the control
station as ‘sig. start‘ or ‘sig. end‘ can then be triggered using setting parameters.
COMM1: Sel.
spontan.sig.test
[ 003 180 ]
Signal 1
Signal 2
Signal 3
Signal n
Selected signals
COMM1: Test
spont.sig.start
[ 003 184 ]
COMM1: Spontan.
sig.start
0 [ --- --- ]
1
0: don't execute
1: execute
COMM1: Test
spont.sig. end
[ 003 186 ]
COMM1: Spontan.
sig. end
0 [ --- --- ]
1
0: don't execute
1: execute
49Z64FKA_EN
In order for data transfer to function properly, several settings must be made in the P43x.
Checking spontaneous
signals
It is possible to select a signal for test purposes. The transmission of this signal to the
control station as ‘sig. start‘ or ‘sig. end‘ can then be triggered using setting parameters.
COMM2: Sel.
spontan.sig.test
[ 103 180 ]
Signal 1
Signal 2
Signal 3
Signal n
Selected signals
COMM2: Test
spont.sig.start
[ 103 184 ]
COMM2: Spontan.
sig. start
0 [ --- --- ]
0: don’t execute
1: execute
COMM2: Test
spont.sig. end
[ 103 186 ]
COMM2: Spontan.
Sig. end
0 [ --- --- ]
0: don’t execute
1: execute
49Z64FLA_EN
Application
Communication interface 3 is designed to establish a digital communication link between
two MiCOM devices over which up to 8 binary protection signals may be transmitted.
Whereas communication interfaces 1 and 2 are designed as information interfaces to
connect to data acquisition subsystems and for remote access, communication
interface 3 is designed as a protection signaling interface that will transmit real time
signals (InterMiCOM protection signaling interface). Its main application is to transmit
signals from protective signaling (function group PSIG). In addition, any other internal or
external binary signals may also be transmitted.
Physical medium
COMM3 is provided as an asynchronous, full-duplex communication interface.
To transmit data the following physical media are available:
Digital network:
Asynchronous data interface of primary multiplexing equipment
Telegram configuration
The communication baud rate is settable (C O M M 3 : B a u d r a t e ) to adapt to the
transmission channel's requirements. Sending and receiving addresses
(C O M M 3 : S o u r c e a d d r e s s and C O M M 3 : R e c e i v i n g a d d r e s s can be set
to different values, thus avoiding that the device communicates with itself.
Binary signals 1 to 4:
Operating mode settable to 'Blocking' or 'Direct intertrip'
Binary signals 5 to 8:
Operating mode settable to 'Permissive' or 'Direct intertrip'
Speed
fast
Blocking
Permissive
slow
low
high high
Direct
Security Intertrip Dependability
47Z1030A_EN
3-18 Comparison of speed, security and dependability offered by the three operating modes.
Communication monitoring
Timer stage C O M M 3 : T i m e - o u t c o m m . f a u l t is used for monitoring the
transmission channel (this timer is re-triggered with each complete and correct received
telegram). The wide setting range allows adaptation to the actual channel transmission
times and above all this is needed for time-critical schemes such as the blocking
scheme. After the timer has elapsed, signals C O M M 3 : C o m m u n i c a t i o n s f a u l t
and
S F M O N : C o m m u n i c . f a u l t C O M M 3 are issued and the received signals are
automatically set to their user-defined default values
(C O M M 3 : D e f a u l t v a l u e r e c . x , with x = 1 to 8). As the main application for this
protective signaling the fault signal may be mapped to the corresponding input signal in
function group PSIG or GSCSG (or both) with the C O M M 3 : S i g . a s g . c o m m . f a u l t
setting.
Message
received
Blocking signals
accepted
Permissive signals
accepted
(Re-)Trigger
COMM3: Time-out
comm.fault
[120 033]
COMM3:
1 Communications
fault
[120 043]
COMM3: Time-out
link fail
[120 035]
47Z1031B_EN
Supervision of
communication
link quality
After a syntax check of each received message, InterMiCOM updates the ratio of
incorrectly received messages, based on a total of the last 1000 received messages.
The result is provided as an updating measured value C O M M 3 : N o . t e l . e r r o r s
p . u . and the overall maximum ratio can be read from
COMM3: No.t.err.,max,stored.
If the set threshold C O M M 3 : L i m i t t e l e g r . e r r o r s is exceeded the
corresponding signals C O M M 3 : L i m . e x c e e d . , t e l . e r r .
and S F M O N : L i m . e x c e e d . , t e l . e r r . will be issued. All the corrupted telegrams
are counted (C O M M 3 : N o . t e l e g r a m e r r o r s ) . This counter as well as the stored
maximum ratio of corrupted messages can be reset via
C O M M 3 : R s e t . N o . t l g . e r r . U S E R (as well as via the binary signal
C O M M 3 : R e s e t N o . t l g . e r r . E X T ).
Commissioning tools
The actual values of send and receive signals can be read from the device as physical
state signals (C O M M 3 : S t a t e s e n d x and C O M M 3 : S t a t e r e c e i v e x , with
x = 1 to 8). In addition, InterMiCOM provides 2 test facilities for the commissioning of the
protection interface.
For a loop-back test, the send output is directly linked back to the receive input.
After setting the bit pattern wanted (as an equivalent decimal number at
C O M M 3 : L o o p b a c k s e n d ) the test can be triggered via
C O M M 3 : L o o p b a c k t e s t . This bit pattern is sent for the duration of the hold time
set at C O M M 3 : H o l d t i m e f o r t e s t . For this test only, the source address is set
to ' 0 '; this value is not used for regular end-to-end communication. The test result can
be checked as long as the hold-time is running by reading the measured operating data
C O M M 3 : L o o p b a c k r e s u l t and C O M M 3 : L o o p b a c k r e c e i v e . As soon
as the hold-time has expired, the loopback test is terminated and InterMiCOM reverts to
the normal sending mode (e.g. sending the actual values of the configured send signals,
using the set source address).
Thus, in case of problems with the InterMiCOM protection signaling interface, the
loopback test can be used to verify or to exclude a defective device. The transmission
channel including the receiving device can be checked manually by setting individual
binary signals
(C O M M 3 : S e n d s i g n a l f o r t e s t ) to user-defined test values
(C O M M 3 : L o g . s t a t e f o r t e s t ). After triggering the test by
C O M M 3 : S e n d s i g n a l , t e s t , the preset binary signal is sent with the preset value
for the set hold time C O M M 3 : H o l d t i m e f o r t e s t . The 7 remaining binary
signals are not affected by this test procedure and remain to be sent with their actual
values. During the hold time, a received signal can be checked at the receiving device,
e.g. by reading the physical state signal. After the hold time has expired, the test mode
is automatically reset and the actual values of all 8 signals are transmitted again.
The IEC 61850 communication protocol is implemented by these function groups and
the Ethernet module.
Note:
Function group IEC is only available as an alternative to function group COMM1
(hardware ordering option!).
3.4.5.1 Communication Interface IEC 61850 (Function Group IEC)
As a further option the P43x now includes an interface protocol according to the Ethernet
based communication standard IEC 61850.
IEC 61850
IEC 61850 was created jointly by users and manufacturers as an international standard.
The main target of IEC 61850 is interoperability of devices. This includes the capability
of two or more intelligent electronic devices (IED), manufactured by the same company
or different companies, to exchange data for combined operation.
Now this new communication standard IEC 61850 has created an open and common
basis for communication from the process control level down to the network control level,
for the exchange of signals, data, measured values and commands.
For a standardized description of all information and services available in a field device a
data model, which lists all visible functions, is created. Such a data model, specifically
created for each device, is used as a basis for an exchange of data between the devices
and all process control installations interested in such information. In order to facilitate
engineering at the process control level a standardized description file of the device,
based on XML, is created with the help of the data model. This file can be imported and
processed further by the relevant configuration program used by the process control
device. This makes possible an automated creation of process variables, substations
and signal images.
The following documentation with the description of the IEC 61850 data model, used
with the P43x, is available:
IDC file based on XML in the SCL (Substation Configuration Description Language)
with a description of the data, properties and services, available from the device, that
are to be imported into the system configurator.
PICS_MICS_ADL file with the following contents:
PICS (Protocol Implementation Conformance Statement) with an overview of
available services.
MICS (Model Implementation Conformance Statement) with an overview of
available object types.
ADL (Address Assignment List) with an overview of the assignment of parameter
addresses (signals, measuring values, commands, etc.) used by the device with
the device data model as per IEC 61850.
Ethernet Module
The optional Ethernet module provides an RJ45 connection and a fiber optic interface
where an Ethernet network can be connected. The selection of which of the two
interfaces is to be used to connect to the Ethernet network is made by setting the
parameter I E C : E t h e r n e t m e d i a . For the optical interface on the Ethernet
communications module the user may either select the ordering option ST connector or
SC connector with 100 Mbit/s and 1300 nm. The RJ45 connector supports 10 Mbit/s
and 100 Mbit/s.
The optional Ethernet module additionally provides an RS485 interface for remote
access with the MiCOM S1 support software (function group COMM2).
Notes: The P43x can be equipped with the optional Ethernet module only as an
alternative to the standard optional communication module. Therefore the
Ethernet-based communication protocol IEC 61850 is available only as an
alternative to function group COMM1.
The setting parameters for function groups IEC, GOOSE and GSSE are not
automatically activated in the device. Activation occurs either when the command
I E C : E n a b l e c o n f i g u r a t i o n is executed or automatically when the device is
switched online at
MAIN: Device on-line.
Client Log-on
Communication in Ethernet no longer occurs in a restrictive master slave system, as is
common with other protocols. Instead, server or client functionalities, as defined in the
'Abstract Communication Service Interface' (ACSI, IEC 61870-7-2), are assigned to the
devices. A 'server' is always that device which provides information to other devices.
A client may log-on to this server so as to receive information, for instance 'reports'.
In a network a server can supply any number of clients with spontaneous or cyclic
information.
In its function as server the P43x can supply up to 16 clients with information.
Clock Synchronization
With IEC 61850 clock synchronization is effected via the SNTP protocol, defined as
standard for Ethernet. Here the P43x functions as a SNTP client.
For clock synchronization one can select between the operating modes Broadcast from
SNTP Server or Request from Server. With the first operating mode synchronization is
effected via a broadcast message sent from the SNTP server to all devices in the
network, and in the second operating mode the P43x requests the device specific time
signal during a settable cycle.
Two SNTP servers may be set. In this case, clock synchronization is preferably
performed by the first server. The second server is used only when messages are no
longer received from the first server.
When looking at the source priority for clock synchronization, which is set at the MAIN
function then, by selecting "COMM1", synchronization per IEC 61850 is automatically
active but only if this communication protocol is applied.
Control and Monitoring of
Switchgear Units
Control of switchgear units (external devices) by the P43x can be carried out from all
clients that have previously logged-on to the device. Only one control command is
executed at a time, i.e. further control requests issued by other clients during the
execution of such a command are rejected. To control external devices the following
operating modes can be set at
IEC: DEV control model:
Control service mode
Direct enh. security (Direct control with enhanced security)
SBO enh. security (SBO [Select before operate] with enhanced security)
When set to the operating mode Select before operate the switchgear unit is selected by
the client before the control command is issued. Because of this selection the
switchgear unit is reserved for the client. Control requests issued by other clients are
rejected. If, after a selection no control command is issued by the client, the P43x resets
this selection after 2 minutes have elapsed.
The switchgear units’ contact positions signaled to the clients are made with the Report
Control Blocks of the switchgear units.
Fault Transmission
Transmission of fault files is supported per "File Transfer".
Transmission of "Goose
Messages"
The so-called "Goose Message" is a particular form of data transmission. Whereas
normal server-client-services are transmitted at the MMS and TCP/IP level, the "Goose
Message" is transmitted directly at the Ethernet level with a high transmission priority.
Furthermore these "Goose Messages" can be received by all participants in the
respective sub-network, independently of their server or client function. In IEC 61850
"Goose Messages" are applied for the accelerated transmission of information between
two or more devices. Application fields are, for example, reverse interlocking, transfer
tripping or decentralized substation interlocking. In the future the "Goose Message" will
therefore replace a wired or serial protective interface.
According to IEC 61850 there are two types of "Goose Messages", GSSE and
IEC-GOOSE. GSSE is used to transmit binary information with a simple configuration by
'bit pairs', and it is compatible with UCA2. However IEC-GOOSE enables transmission
of all data formats available in the data model, such as binary information, integer values
or even analog measured values. But this will require more extensive configuration with
the help of the data model from the field unit situated on the opposite side. With
IEC-GOOSE the P43x at this time supports sending and receiving of binary information
or two-pole external device states.
Communication with the
MiCOM S1 support
software via the Ethernet
Interface
Direct access by the MiCOM S1 support software via the Ethernet interface on the
device may occur through the "tunneling principle". Transmission is carried out by an
Ethernet Standard Protocol, but this is only supported by the associated MiCOM S1
support software (specific manufacturer solution). Such transmission is accomplished
over the same hardware for the network, which is used for server-client communication
and "Goose Messages".
Available are all the familiar functions offered by the MiCOM S1 support software such
as reading/writing of setting parameters or retrieving stored data.
The various settings, measured values and signals for function group IEC are described
in chapters 7 and 8.
The setting parameters for function groups IEC, GOOSE and GSSE in the device are not
automatically activated. Activation occurs either when the command
I E C : E n a b l e c o n f i g u r a t i o n is executed or automatically when the device is
switched online with M A I N : D e v i c e o n - l i n e . In addition function group IEC must
be configured and enabled.
Sending GOOSE
With GOOSE up to 32 logic binary state signals and up to 3 two-pole states from the
maximum of 3 possible external devices associated with the P43x can be sent.
Selection of binary state signals is made by setting
G O O S E : O u t p u t n f c t . a s s i g . (n = 1 to 32). The up to 3 two-pole states of the
external devices are a fixed part of GOOSE for which there is no necessity to set
parameters. The assignment of data object indexes to logic state signals is made in the
range from 1 to 32 according to the assignment to GOOSE outputs. The two-pole state
signals from external devices 1 to 3 receive a permanent assignment of data object
indexes in ascending order from 33 to 35.
GOOSE is automatically sent with each new state change of a configured binary state
signal or an external device. There are numerous send repetitions in fixed ascending
time periods (10 ms, 20 ms, 50 ms, 100 ms, 500 ms, 1000 ms, 2000 ms). If after
2 seconds there is no further state change apparent, GOOSE is then sent cyclically at
2-second intervals.
In order to have unambiguous identification of GOOSE sent, characteristics such as the
Goose ID number, MAC address, application ID and VLAN identifier must be entered
through setting parameters. Further characteristics are the 'Dataset Configuration
Revision' with the fixed value "100" as well as the 'Dataset Reference', which is made up
of the IED name (setting in function group IEC) and the fixed string
"System/LLNO$GooseST".
VLAN Identifier: 0
VLAN Priority: 4
12Z6001A _EN
Receiving GOOSE
With GOOSE, up to 16 logic binary state signals and the two-pole contact position
signals from up to 16 external devices can be received. Configuration of the logic state
signals received (G O O S E : I n p u t n f c t . a s s i g . , where n = 1 to 16) is made on the
basis of the selection table of the binary inputs (opto coupler inputs). Contact position
signals received from external devices are listed in the selection table for interlocking
equations of the ILOCK function group, which are available to design a decentralized
substation interlock.
For each state or contact position signal to be received from an external device the
"Goose Message" must be selected that includes the information wanted by setting the
Goose ID, the Application ID and the 'Dataset Reference'. With the further setting of the
data object index and the data attribute index through parameters, the required
information from the chosen GOOSE will be selected. The device will not evaluate the
identification features VLAN identifier and ‘Dataset Configuration Revision’ that are also
included in the GOOSE received.
Each GOOSE includes time information on the duration of validity of its information.
This corresponds to the double time period to the next GOOSE repetition. If the duration
of validity has elapsed without having received this GOOSE again (i.e. because of a
communications fault), the received signals will automatically be set to their respective
default values: G O O S E : I n p u t n d e f a u l t or G O O S E : E x t . D e v . n d e f a u l t
(n = 1 to 16).
The various settings, measured values and signals for function group GOOSE are
described in chapters 7 and 8.
The setting parameters for function groups IEC, GOOSE and GSSE in the device are not
automatically activated. Activation occurs either when the I E C : E n a b l e
c o n f i g u r a t i o n command is executed or automatically when the device is switched
on-line at
M A I N : D e v i c e o n - l i n e . In addition the function group IEC must be configured and
enabled.
Sending GSSE
With GSSE up to 32 logic binary state signals can be sent. Selection of binary state
signals is made by setting
G S S E : O u t p u t n f c t . a s s i g . (n = 1 to 32). Each selected state signal is to be
assigned to a bit pair in GSSE (G S S E : O u t p u t n b i t p a i r (n = 1 to 32)), which will
transmit this state signal.
GSSE is automatically sent with each state change of a selected state signal. There will
be multiple send repetitions at ascending time periods. The first send repetition occurs
at the given cycle time set with the parameter G S S E : M i n . c y c l e . The cycles for
the following send repetitions result from a conditional equation with the increment set
with the G S S E : I n c r e m e n t parameter. Should no further state changes occur up
to the time when the maximum cycle time has elapsed (G S S E : M a x . c y c l e ) , then
GSSE will be sent cyclically at intervals as set for the max. cycle time.
In order to have unambiguous identification of a GSSE sent, the IED name is used which
was set in function group IEC.
Receiving GSSE
With GSSE up to 32 logic binary state signals can be received. Configuration of the
logic binary state signals received (G S S E : I n p u t n f c t . a s s i g . , where n = 1 to 32)
is made on the basis of the selection table of the binary inputs (opto coupler inputs).
For each state signal to be received, the GSSE message, which will include the required
information, must be selected by setting the IED name (G S S E : I E D n a m e ) .
Selection of information wanted from the selected GSSE will occur by setting the bit pair
(G S S E : b i t p a i r ) .
Each GSSE includes time information on the validity duration of its information.
This corresponds to the double time period to the next GSSE repetition. If the validity
duration has elapsed without this GSSE being received again (i.e. because of a
communications fault), the signals received will automatically be set to their respective
default value ( G S S E : I n p u t n d e f a u l t (n = 1 to 32)).
The various settings, measured values and signals for function group GOOSE are
described in chapters 7 and 8.
If, for example, a GPS receiver with IRIG-B connection is available, the internal clock of
the P43x can be synchronized to run on GPS time using the optional IRIG-B interface.
It should be noted that the IRIG-B signal holds information on the day only (day of the
current year). Using this information and the year set at the P43x, the P43x calculates
the current date (DD.MM.YY).
Synchronization readiness
If the IRIG-B interface is enabled and receiving a signal, the P43x checks the received
signal for plausibility. Implausible signals are rejected by the P43x. If the P43x does not
receive a correct signal in the long run, synchronization will not be ready any longer.
The P43x includes six additional function keys that are freely configurable. Function
keys F1 to Fx will only be enabled after the password has been entered at
F_Key: Password funct.key x.
As an example the operation of function key F1 is shown in figure 3-22. After the
password has been entered the function key will remain active for the time period set at
F _ K E Y : R e t u r n t i m e f c t . k e y s . Thereafter, the function key is disabled until the
password is entered again. The same is valid for function keys F2 to F6. Exception: If a
function key is configured as a control key a password request is only issued when the
command "Local/Remote switching" has been assigned to this function key.
Configuration of function
keys with a single function
A single function can be assigned to each function key by selecting a logic state signal at
F _ K E Y : F c t . a s s i g n m . F x (Fx: F1, F2, F3 or F4), with the exception of
L O C : T r i g . m e n u j m p x E X T (x: 1 or 2). This function is triggered by pressing
the respective function key on the P43x.
Configuration of function
keys with menu jump lists
Instead of a single function, it is possible to assign to each function key one of the two
menu jump lists created at F _ K E Y : F u n c t i o n a s s i g n m . F x (Fx: F1 to F6) by
selecting the list at L O C : T r i g . m e n u j m p x E X T (x: 1 or 2). The functions of the
selected menu jump list are triggered in sequence by repeated pressing of the assigned
function key.
Note: LED indicators including the six situated directly next to the function keys are
configured independently and in this respect there is no relationship to the respective
function key configuration.
Configuration of the
READ key
As with L O C : F c t . m e n u j m p l i s t x (x: 1 or 2) up to 16 functions may also be
selected from the same menu jump list at L O C : F c t . r e a d k e y . They are triggered
in sequence by repeatedly pressing the "READ" key.
These control functions may only be used sensibly if all four of the above commands
have been configured thus engaging four of the available six function keys.
Exception: For function keys configured as control keys the operating mode is irrelevant
and it is therefore ignored.
Handling keys
If backlighting for the LC display is switched off it will automatically light up when a
function key or the "READ" key is pressed. The assigned function will only be triggered
when the respective key is pressed a second time. This is also valid for the other keys.
F_KEY: Fct.
assignm. F1
[ 080 112 ]
Function 1 EXT
Function 2 EXT
Function 3 EXT
Function n EXT
Selected function Activate Function
F_KEY: Operating
mode F1
[ 080 132 ]
1 F_KEY: State F1
[ 080 122 ]
2
1: Key
2: Switch
3-22 Configuration and operating mode of function keys. The assigned function is either a single function or a menu jump list.
3.7 Configuration and Operating Mode of the Binary Inputs (Function Group INP)
The P43x has opto-coupler inputs for processing binary signals from the substation.
The functions that will be activated in the P43x by triggering these binary signal inputs
are defined by the configuration of the binary signal inputs. In order to ensure that
during normal operation the P43x will recognize an input signal, it must persist for at
least 20 ms. With the occurrence of a general starting this time period may have to be
increased to 40 ms under unfavorable conditions.
In this manual, we assume that the required functions (marked 'EXT' in the address
description) have been assigned to binary signal inputs by configuration.
Filter function
An additional filter function may be enabled in order to suppress transient interference
peaks at the logic signal inputs (operating modes Active "high", filt. or Active "low", filt.).
With this function enabled a status change at the binary logic input is signaled only when
the input signal remains at a steady signal level during a set number of sampling steps
(sampling step size = period / 20). The number of sampling steps is set at parameter
INP: Filter.
INP: Fct.assignm.
Uxx
[ XXX XXX ]
Function 1 EXT
Function 2 EXT
Function 3 EXT
Function n EXT
2
3
0: active "Low"
1: active "High"
2: active "Low", filt.
3: active "High",filt.
-Uxxx
&
Input signal
&
INP: Control
& U xxx
[ ZZZ ZZZ ]
&
12Z6213 A_EN
The P43x has a measured data input function involving two inputs. Direct current is fed
to the P43x through one of the inputs. The other input is designed to connect a
resistance thermometer.
The input current IDC is displayed as a measured operating value. The current that is
conditioned for monitoring purposes (IDC,lin) is also displayed as a measured operating
value. In addition, it is monitored by the Limit Value Monitoring function to determine
whether it exceeds or falls below set thresholds (see "Limit Value Monitoring").
When setting the characteristic the user must remember that only a monotonically
increasing curve is allowed (no peak or vee-shapes). If an invalid setting is entered, the
S F M O N : I n v a l i d s c a l i n g I D C signal will be generated.
1.1
IDC,lin 20 1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
IDC,lin 1 0
0 0.1 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.6 IDC / IDC, nom
IDC 1 IDC 20
D5Z52KDA
19Z5266A_EN
IDClin / IDC,nom
0.8
Interpolation points
IDC,lin20 0.7
0.6
IDC,lin4 0.5
0.4
IDC,lin3 0.3
IDC,lin2 0.2
IDC,lin1 0.1
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2
3-26 Example of a characteristic with five interpolation points (characteristic with zero suppression setting of 0.1 IDC,nom shown as a broken line)
Zero suppression
Zero suppression is defined by setting M E A S I : E n a b l e I D C p . u . If the direct
current does not exceed the set threshold, the per-unit input current I DC p.u. and the
current IDClin will be displayed as having a value of ‘ 0 ’.
The input current is monitored in order to protect the 20 mA analog input against
overloading. If it exceeds the fixed threshold of 24.8 mA, the
M E A S I : O v e r l o a d 2 0 m A i n p u t signal is issued.
Beyond the linearization described above, the user has the option of scaling the
linearized values. Thereby negative values, for example, can be displayed as well and
are available for further processing by protection functions.
Open-circuit monitoring
If there is an open measuring circuit due to a broken wire, the M E A S I : O p e n c i r c .
P T 1 0 0 signal is issued.
c
MEASI: Enabled
[ 035 008 ]
MEASI: PT100
faulty
PT 100 Analog Input [ 040 190 ]
MEASI:
Temperature p.u.
[ 004 221 ]
MEASI:
Temperature Tmax
[ 004 233 ]
49Z64H3A_EN
The P43x has output relays for the output of binary signals. The binary signal
assignment is freely configured by the user.
OUTP: Outp.rel.
block USER
[ 021 014 ]
0
OUTP: Outp.
1 ≥1 relays blocked
[ 021 015 ]
0: No
OUTP: Block 1: Yes
outp.rel. EXT
[ 040 014 ] ≥1
MAIN: Prot.
ext. disabled
[ 038 046 ]
SFMON: Hardware
fault
304 950
1 ≥1
2
3
4 -K xxx
≥1
5
6
≥1
1: ES updating
2: ES manual reset
≥1
3: ES reset (fault)
4: ES reset (syst.dist)
OUTP: State K xxx
5: NE updating & ≥1 [ zzz zzz ]
6: NE manual reset &
&
& ≥1
Signal 1
Signal 2
Signal 3 m out of n
Signal n
≥1 & ≥1
Selected signals
&
FT_RC: Record.
in progress OUTP: Latching
[ 035 000 ] 1 reset
& [ 040 088 ]
FT_RC: System
disturb. runn
[ 035 004 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OUTP: Reset
latch. USER
[ 021 009 ]
0
1 1
100 ms
0: don’t execute
1: execute
OUTP: Reset
latch. EXT
[ 040 015 ]
50Z0141 A_EN
3-30 Configuration, setting the operating mode, and blocking the output relays
Measured values made available by the P43x can be provided in BCD (binary coded
decimal) form through output relays or in analog form as direct current output. Output as
direct current can only occur if the device is equipped with analog module Y. BCD
output is always possible, whether the device is equipped with analog module Y or not.
The measured data output is reset either using a setting parameter or via an
appropriately configured binary signal input.
There is a general reset.
LED indicators reset
MEASO: Reset
output USER
[ 037 116 ]
0
1
0: don't execute
1: execute
MAIN: General
reset USER MEASO: Reset
[ 003 002 ] meas.val.outp.
1: execute 304 601
MAIN: Reset
indicat. USER
[ 021 010 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
indicat. EXT
[ 065 001 ]
49Z64H6A_EN
Scaling
Scaling is used to map the physical measuring range to the device's inherent setting
range.
Scaling of analog output is also suited for directional-signed output of some fault
measured values, in particular fault location in percent.
The user can select a measured value for output in BCD form by assigning output relays.
The selected measured value is available in BCD form for the duration of the set hold
time M E A S O : H o l d T i m e O u t p u t B C D . If the selected variable was not
measured, then there is no output of a measured value.
Output of measured
operating values
The selected measured operating value is available for the duration of the set hold time.
After the hold time has elapsed, the current value is saved and the hold time is re-
started. If the hold time has been set to "blocked", the measured operating value that
has been output will be stored until the measured data output function is reset.
The BCD display range should be set so that the value 399 is never exceeded. If this
should occur or if the measured value is outside the acceptable measuring range, then
the value for "Overflow" (all relays triggered) is transmitted.
Scaling is made with reference to the complete range of values for the selected
measured value (variable Mx). The complete range of values is defined by their end
values Mx,RL1 and Mx,RL2. (Mx,RL1 and Mx,RL2 are listed in the operating program S&R-103
- PC Access Software MiCOM S1 - under "minimum" and "maximum".)
Designation of the set "Scaled min. val. BCD" ... "Scaled max. val. BCD"
values in the data model
/Parameter/Config. parameters/
Address Description Current value
056 020 MEASO: Function group MEASO With
031 074 MEASO: General enable USER Yes
053 002 MEASO: Fct. assignm. BCD FT_DA: Fault locat. percent
010 010 MEASO: Hold time output BCD 1.00 s
037 140 MEASO: Scaled min. val. BCD 0.500
037 141 MEASO: Scaled max. val. BCD 0.813
037 142 MEASO: BCD-Out min. value 0
037 143 MEASO: BCD-Out max. value 200
The following figure displays the values output as a function of the fault location.
The BCD value and the M E A S O : V a l i d B C D v a l u e = 'Yes' signal are issued only
in the value range of 0% to 200%.
200
BCD value
0
-320% 0% 200% 320% [004.027] FT_DA:
Fault locat. percent
47Z1040A_EN
Note:
Except from radial, single circuit lines the fault location value gives a reasonable value
only for faults up to the line end. For any fault on a subsequent line the fault location is
more or less incorrect due to unknown fault current infeed in the remote substation.
It is recommended to limit the calculation of a fault location to a practical and sensible
range on the line by setting F T _ D A : O u t p . f l t . l o c a t . P S x = 'Only aft.tr.t1/t1,ze'.
The user can select two of the measured values available in the P43x for output in the
form of load-independent direct current. Three interpolation points per channel can be
defined for specific adjustments such as adjustment to the scaling of a measuring
instrument. The direct current that is output is displayed as a measured operating value.
The selected measured value is output as direct current for the duration of set hold time
M E A S O : H o l d T i m e O u t p u t A - x . If the selected variable was not measured,
then there is no output of a measured value.
Output of measured
operating values
The selected measured operating value is available for the duration of the set hold time.
After the hold time has elapsed, the current value is saved and the hold time is re-
started. If the hold time has been set to "blocked", the measured operating value that
has been output will be stored until the measured data output function is reset.
Configuration of output
relays assigned to the
output channels
The user must keep in mind that direct current output only occurs when the output relays
assigned to the output channels are configured for M E A S O : V a l u e A - x o u t p u t ,
since the output channels would otherwise remain short-circuited (see terminal
connection diagrams).
This measured value range to be output is defined by setting the following parameters:
Designation of the set "Scaled min. val. Ax" … "Scaled knee val. Ax"
values in the data model ... "Scaled max. val. Ax"
/Parameter/Config. parameters/
Address Description Current value
056 020 MEASO: Function group MEASO With
031 074 MEASO: General enable USER Yes
053 000 MEASO: Fct. assignm. A-1 MAIN:
Voltage A-B PU
010 114 MEASO: Hold time output A-1 1.00 s
037 104 MEASO: Scaled min. val. A-1 0.013 (corresponds with
0.02 Vnom)
037 105 MEASO: Scaled knee val. A-1 0.067 (corresponds with
0.10 Vnom)
037 106 MEASO: Scaled max. val. A-1 0.667 (corresponds with
1.00 Vnom)
037 107 MEASO: AnOut min. val. A-1 4 mA
037 108 MEASO: AnOut knee point A-1 16 mA
037 109 MEASO: AnOut max. val. A-1 18 mA
Note:
A check of the set characteristic and its acceptance by the device, if the setting was
properly entered, will only occur after the device, set to M A I N : D e v i c e o n - l i n e , is
switched on-line again.
Ia / mA
20
Max.
output value18
Knee point
16
output value
14
12
10
6
Min.
output value 4
2
0
0 0.02 0.1 1 1.2 1.3 1.4 1.5 Vnom
0,013 0,067 0,667 1,0Mx,scal
D5Z52KFA
19Z5265A_EN
3-37 Example of a characteristic curve for analog measured data output . In this example the range starting value is = 0; also possible is
directional-signed output (see corresponding example in section BCD Measured Data Output).
Measured data from external devices, which must be scaled to 0 ... 100%, can be written
to the following parameters of the P43x via the communications interface.
These "external" measured values are output by the P43x either in BCD data form or as
load-independent direct current, provided that the BCD measured data output function or
the channels of the analogue measured data output function are configured accordingly.
The P43x has 17 LED indicators for the indication of binary signals. Four of the LED
indicators are permanently assigned to fixed functions. The other LED indicators are
freely configurable. These freely configurable LEDs will emit either red or green or
amber light (amber is made up of red and green light and may not be configured
independently).
H 1 (green) “HEALTHY” Not configurable. H 1 indicates the operational readiness of the device
(supply voltage is present).
H 17 (red) “EDIT MODE” Not configurable. H 17 indicates the input (edit) mode. Only when the
device is in this mode, can setting parameters be changed by pressing
the “Up“ and “Down“ keys. (See Chapter 6, section 'Display and
Keypad')
H 4 (red) “TRIP COMMAND” With the P43x this LED indicator is customarily configured with function
M A I N : G e n . t r i p s i g n a l - but the configuration may be modified.
H 4 (green) ---- Function assignment to this green LED indicator is freely configurable.
H 5 to H 16 ---- For each of these LED indicators both colors (red & green) may be
configured freely and independently.
The following figures illustrate the layout of LED indicators situated on the local control
panel with case 40TE/84TE devices.
H4
H3
TRIP
ALARM
F1 H18
H2 OUT OF SERVICE
H1
H17
HEALTHY
EDIT MODE
F2 H19
H5
H6
F3 H20
H7
H8 C
G
H9
H10
G F4 H21
H11
H12
G G F5
G
H22
H13
H14
H15
H16
G F6 H23
12 Z6100B_EN
Therefore the operating modes turn out to be the 23=8 possible combinations of the
following components:
• flashing / continuous,
• energize-on-signal (ES) / normally-energized (NE),
• updating / latching with manual reset,
• energize-on-signal (ES) with reset after new fault (flashing / continuous) and
• energize-on-signal (ES) with reset after new system disturbance (flashing /
continuous),
LED: Operating
mode H xx
[ xxx xxx ]
1
2
3
4
5
6
7
8
9
10
11
-Hxx
12 (red)
1: ES updating ! G !
2: ES manual reset
3: ES reset (fault)
4: ES reset (syst.dist) ≥1
5: NE updating
6: NE manual reset
7: ES updating bl
2: ES manual reset
8: ES manual reset bl
3: ES reset (fault) LED: State H xx
& red
9: ES reset (fault) bl [ zzz zzz ]
10: ES rst (syst.dst) bl &
11: NE updating bl &
12: NE manual reset bl
& S1 1
R1
LED: Fct.assig.
Hxx red
[ yyy yyy ]
Signal 1
Signal 2
Signal 3 m out of n LED: State H xx
Signal n & green
[ zzz zzz ]
&
&
Selected signals
& S1 1
R1
LED: Fct.assig.
Hxx green
[ yyy yyy ]
Signal 1
Signal 2 -Hxx
Signal 3 m out of n (green)
Signal n
&
FT_RC: Record.
in progress
[ 035 000 ]
&
FT_RC: System
disturb. runn
[ 035 004 ]
MAIN: General
reset EXT
[ 005 255 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: Reset
LED
306 020
12Z6200 A_EN
In the acquisition of signals for control purposes, the real time acquisition (time tagging),
debouncing and chatter suppression functions are included by default. Each of these
signals can be assigned to one of three groups and for each of these groups the
debouncing time and chatter suppression can be set. Matching of these two parameters
achieves the suppression of multiple spurious pickups.
3-40 Group assignment and setting of debouncing and chatter suppression, illustrated for group 1
Debouncing
The first pulse edge of a signal starts a timer stage running for the duration of the set
debouncing time. Each pulse edge during the debouncing time re-triggers the timer
stage.
If the signal remains stable until the set debouncing time elapses, a telegram containing
the time tag of the first pulse edge is generated. As an alternative the time tag may be
generated after debouncing by setting parameter M A I N : T i m e t a g to the value
'After debounce time'.
After the set debouncing time has elapsed, the state of the signal is checked. If it is the
same as prior to the occurrence of the first pulse edge, no telegram is generated.
Time-tagged entries of the first pulse edge are only generated after debounce time has
elapsed. If these entries are saved without delay (setting of M A I N : T i m e t a g to the
value '1stEdge,OpMem unsort') they are not necessarily saved in chronological order in
the operating data memory. If above parameter has been set to the value
'1stEdge,OpMem sorted' then all entries are always saved in chronological order in the
operating data memory.
3-41 Signal flow with debouncing when time tagging occurs with the 1st pulse edge
(e.g. parameter M A I N : T i m e t a g set to the value '1stEdge,OpMem unsort' or '1stEdge,OpMem sorted'.)
Example: Set debouncing time: 50 ms
s: start
e: end
Chatter suppression
The transmission of the first telegram starts a timer stage running for the duration of the
set monitoring time. While the timer stage is elapsing, telegrams are generated for the
admissible signal changes. The number of admissible signal changes can be set.
After the first "inadmissible" signal change, no further telegrams are generated and the
timer stage is re-triggered. While the timer stage is elapsing, it is re-triggered by each
new signal change. Once the timer stage has elapsed, each signal change triggers a
telegram.
The P43x is designed to control up to three switchgear units. The bay type defines the
topology of a bay with its switchgear units.
The P43x offers a selection from pre-defined bay types. If the required bay type is not
included in the standard selection, the user can contact the manufacturer of the P43x to
request the definition of a customized bay type to download into the P43x. By applying
the bay editor from the PC Access Software MiCOM S1 the user can also define new
bay types. The number of this additional bay type will then be displayed at
MAIN: Customized bay type.
Once the user has selected a bay type, the P43x can automatically configure the binary
inputs and output relays with function assignments for the control of switchgear units.
The assignment of inputs and outputs for an automatic configuration is shown in the
List of Bay Types in the Appendix.
The secondary phase currents and voltages of the system transformers are fed into the
P43x and are – electrically isolated – converted to standardized electronics levels. Air-
gap transformers are used in the phase current path to suppress low frequency (DC
decays and offsets) signal components. The analog quantities are digitized and are thus
available for further processing.
Settings that do not refer to nominal quantities are converted by the P43x to nominal
quantities. The user must therefore set the secondary nominal currents and voltages of
the system transformers.
The connection arrangement of the measuring circuits must also be set on the P43x.
Figure 3-44 shows the standard connection. The phase of the digitized currents is
rotated by 180° by this setting.
A
B
C
MAIN: Vref,nom
V.T. sec.
[ 031 052 ]
1U
Vref
2U
X X. Y IA
IB
IB
X X. Y
IC X X. Y IC
1: Standard
IN (Y = 1)
2: Opposite
(Y = -1)
IN
X X. Y
1: Standard
(Y = 1)
2: Opposite
(Y = -1)
MAIN: VNG,nom
V.T. sec.
[ 010 028 ]
N(e)
E(n) VN-G
MAIN: Vnom
V.T. sec.
[ 010 009 ]
U
VA-G
e V
VB-G
W VC-G
N
Line
49Z6400A_EN
The P43x has an operating data measurement function for the display of the measured
currents and voltages as well as quantities derived from these measured values. Set
minimum thresholds must be exceeded for measured values to be displayed, so as to
avoid fluctuating small values from noise. If these minimum thresholds are not
exceeded, 'not measured' is displayed in place of a value. The following measured
values are displayed:
Phase currents for all three phases (as primary quantities and as per-unit quantities)
Maximum phase current (as a primary quantity and as a per-unit quantity)
Minimum phase current (as a primary quantity and as a per-unit quantity)
Delayed and stored phase currents for all three phases (as primary quantities and as
per-unit quantities
Delayed and stored maximum phase current (as primary quantitiesand as per-unit
quantities
Positive- and negative-sequence current, based on the set phase sequence
(alternative terminology: rotary field)
Residual current measured by the P43x at the T 4 transformer and calculated
residual current (as primary quantities and as per-unit quantities)
Phase-to-ground voltage (as a primary quantity)
Sum of the three phase-to-ground voltages (as a primary quantity and as a per-unit
quantity)
Phase-to-phase voltages (as primary quantities and as per-unit quantities)
Maximum phase-to-phase voltage (as a primary quantity and as a per-unit quantity)
Minimum phase-to-phase voltage (as a primary quantity and as a per-unit quantity)
Positive- and negative-sequence voltage, based on the set phase sequence
(alternative terminology: rotary field)
Neutral-point displacement voltage measured by the P43x at the T 90 transformer (as
a primary quantity and as a per-unit quantity)
Reference voltage measured by the P43x at the T 15 transformer (as a primary
quantity and as a per-unit quantity)
Active, reactive and apparent power (as primary quantities and as per-unit quantities)
Active power factor
Load angle ϕ in all three phases (as a quantity and as a per-unit quantity referred to
100°)
Angle between measured residual current and measured neutral-point displacement
voltage (as an angle and as a per-unit quantity referred to 100°)
Phase relation between calculated and measured residual current
Angle between the sum of the three phase-to-ground voltages and the measured
residual current (as an angle and as a per-unit quantity referred to 100°)
Frequency (as a quantity and as a per-unit quantity referred to fnom)
Active and reactive energy
The measured data are updated at 1 s intervals. Updating is interrupted when a general
starting signal is issued or if the self-monitoring function detects a hardware fault.
According to the following equations the P43x will determine the negative-sequence
current and positive-sequence current, taking into account the set phase sequence:
a = e j120°
a 2 = e j 240°
IA C1
IB C2
IC C3
C4
C5
C6
C7
C8
MAIN: Current A
1 p.u.
[ 005 041 ]
MAIN: Current B
2 p.u.
[ 006 041 ]
MAIN: Current C
3 p.u.
[ 007 041 ]
+ MAIN: Current
+ 4 (IP) p.u.
+ [ 005 011 ]
MAIN: Current
COMP 5 IP,max p.u.
[ 005 051 ]
MAIN: Current
6 IP,min p.u.
Imax [ 005 056 ]
MAIN: Current A
Ineg prim.
[ 005 040 ]
MAIN: Current B
Ipos prim.
[ 006 040 ]
MAIN: Current C
prim.
[ 007 040 ]
MAIN: Current
(IP) prim.
[ 005 010 ]
MAIN: Curr.
IP,max prim.
[ 005 050 ]
MAIN: Curr.
IP,min prim.
[ 005 055 ]
45Z6301A_EN
3-45 Measured operating data – phase current, part 1: phase currents, negative-sequence current, and positive-sequence current
MAIN: IA p.u.,
demand
[ 006 235 ]
MAIN: IB p.u.,
demand
[ 006 236 ]
MAIN: IC p.u.,
demand
[ 006 237 ]
MAIN: IA prim,
demand
[ 006 226 ]
MAIN: IB prim,
demand
[ 006 227 ]
MAIN: IC prim,
demand.
[ 006 228 ]
MAIN: IP,max
prim.,demand
[ 005 036 ]
MAIN: Reset
IP,max,st.USER MAIN: IA prim,
[ 003 033 ]
demand stor.
[ 006 223 ]
0
MAIN: IB prim,
1 demand stor.
[ 006 224 ]
MAIN: General 0: don`t execute
reset USER 1: execute MAIN: IC prim,
[ 003 002 ] demand stor.
1: execute [ 006 225 ]
MAIN: General
reset EXT MAIN: IP,max
[ 005 255 ] prim,demand.st.
MAIN: Reset [ 005 034 ]
IP,max,st. EXT
[ 005 211 ]
19Z6404 A_EN
3-46 Measured operating data – phase current, part 2 delayed and stored measured current values
MAIN: Current
IP,max p.u.
[ 005 051 ]
MAIN: IP,max
p.u.,delay
[ 005 037 ]
MAIN: Current
IP,max p.u.
[ 005 051 ]
MAIN: IP,max
p.u.,stored
[ 005 035 ]
MAIN: Current
IP,max p.u.
[ 005 051 ]
MAIN: IP,max
p.u.,stored
[ 005 035 ]
MAIN: Reset
IP,max,st.USER
[ 003 033 ]
MAIN: Reset
IP,max,st. EXT
[ 005 211 ] 50Z0115A_EN
According to the following equations the P43x will determine the negative-sequence
voltage and positive-sequence voltage, taking into account the set phase sequence:
V neg =
1
3
(
⋅ V A −G + a 2 ⋅ V B −G + a ⋅ V C −G )
V pos =
1
3
(
⋅ V A −G + a ⋅ V B −G + a 2 ⋅ V C −G )
Phase sequence A-C-B
(alternative terminology: anti-clockwise rotating field)
V neg =
1
3
(
⋅ V A −G + a ⋅ V B −G + a 2 ⋅ V C −G )
V pos =
1
3
(
⋅ V A −G + a 2 ⋅ V B −G + a ⋅ V C −G )
a = e j120°
a 2 = e j 240°
3-49 Determining the minimum and maximum phase-to-ground and phase-to-phase voltages as well as the negative-sequence and positive-
sequence voltages
Values for active and reactive power will always be calculated and displayed as these
quantities are required for the subsequent energy measurement. Greater deviations
in measurements may occur with low phase currents or a critical power factor value
(see Chapter "Technical Data").
The active power factor will be calculated only if the apparent power value exceeds
5% of the nominal apparent power Snom.
Load angles will be displayed only if the respective phase current exceeds 0.1 Inom
(0.025 Inom with the 'Dynamic range' set to Sensitive) and if the phase-to-ground
voltage exceeds 1.5 V.
The angle between the measured values for the residual current and the neutral-point
displacement voltage will only be displayed if the residual current exceeds 0.02 IN,nom
and the neutral-point displacement voltage exceeds 1.5 V.
The setting at M A I N : M e a s . d i r e c t i o n P , Q may be changed from 'Standard' to
'Opposite' if the user wishes to have the following measured operating data displayed
with the opposite sign (see figure 3-53):
The load angle and the angle between the measured values for the residual current and
the neutral-point displacement voltage are only determined when associated currents
and voltages exceed the defined minimum thresholds (see above for the acceptable
range).
MAIN: Active
power factor
[ 004 054 ]
MAIN: Inom C.T. MAIN: Meas.
prim. direction P,Q
[ 010 001 ] [ 006 096 ]
MAIN: Active
MAIN: Vnom V.T. power P p.u.
prim. X X. Y [ 004 051 ]
[ 010 002 ]
MAIN: Reac. power
> 0.05 Snom X X. Y Q p.u.
[ 004 053 ]
+ X X. Y MAIN: Active
+ power P prim.
+ X X. Y [ 004 050 ]
MAIN: Reac. power
1: Standard Q prim.
(Y = 1) [ 004 052 ]
MAIN: Dynamic 2: Opposite
range I (Y = -1)
[ 031 082 ]
MAIN: Hardware
fault C
306 018
MAIN: Appar.
power S p.u.
[ 005 026 ]
MAIN: Appar.
power S prim.
[ 005 025 ]
49Z6404 A_EN
3-53 Measured operating data - power, active power factor, and angle. Not displayed in the diagram: With the 'Dynamic range' set to Sensitive
the condition for phase currents changes from 'exceeding 0.1 Inom' to 'exceeding 0.025 Inom'.
Phase relation IN
The P43x checks if the phase relations of calculated residual current and measured
residual current are coherent. If the phase displacement between the two currents is
≤ 45°, then the indication ‘Equal phase’ is displayed.
Frequency
The P43x determines the frequency from the voltage VA-B. This voltage needs to
exceed a minimum threshold of 0.65 Vnom in order for the frequency to be determined.
MAIN: General C
starting
306 539
MAIN: Hardware
fault
306 018 >0.65*Vnom
MAIN: Frequency f
VA-G + C p.u.
[ 004 070 ]
VB-G -
f MAIN: Frequency f
[ 004 040 ]
12Z6209 A_EN
There are two procedures available to determine active and reactive energy. If
procedure 1 is selected, active and reactive energy are determined every 2 s
(approximately) as in software versions –601. If procedure 2 is selected, active and
reactive energy are determined every 100 ms (approximately). In this way higher
accuracy is achieved. Whenever the maximum value of 655.35 MWh or 655.35 MVAr h
is exceeded, a counter is incremented and the determination of the energy output is
restarted. The value that exceeded the range is transferred to the new cycle.
MAIN: Active
power P prim.
[ 004 050 ] MAIN: Act.energy
P(t) dt outp.prim
[ 005 061 ]
R
MAIN: No.ov/fl.
Overflow reac.en.inp
[ 009 093 ]
Transfer
45Z6302A_EN
3-56 Determining the active and reactive energy output and input
1
Determination of the active and reactive energy
Constant load and slow load variations (no
every 2 s (approximately) significant load variations within 1 second).
Reduced system loading
Phase angles below 70° (cos ϕ > 0.3 ).
The 1° maximum phase-angle error of the P43x leads to greater errors in measurement
when the phase angle increases, as shown (for the range 0° ≤ ϕ < 90°) in the following
diagram.
Fault
Fehler
5%
2%
3-57 Error of measurement in the determination of energy output resulting from the phase angle error of the P43x
For phase angles ϕ with |cosϕ| < 0.3, or when the error of measurement resulting from
the maximum phase-angle error is not acceptable, external counters should be used to
determine the energy output.
Canceling a device
function
The following conditions must be met before a device function can be cancelled or
removed:
No functions of the device function being cancelled are selected in a list setting.
If the above conditions are met, proceed through the 'Configuration' branch of the menu
tree to access the setting relevant to the device function to be cancelled. If, for example,
the "LIMIT" function group is to be cancelled, access the L I M I T : F u n c t i o n g r o u p
L I M I T parameter and set its value to 'Without'. To re-include the "LIMIT" function in
the device configuration, access the same parameter and set its value to 'With'.
The device function to which a setting, a signal, or a measured value belongs is defined
by the function group designation (example: "LIMIT"). In the following sections of this
manual, it is presumed that the device function being described is included in the
configuration.
Note: If the protection function is disabled via a binary signal input that is
configured for M A I N : D i s a b l e P r o t e c t . E X T , then no M A I N :
B l o c k e d / f a u l t y signal is issued.
The inrush stabilization function detects high inrush current flows that occur when
transformers or machines are switched on or connected. It will then block the following
functions:
The inrush stabilization function identifies an inrush current by evaluating the ratio of the
second harmonic current components to the fundamental. If this ratio exceeds the set
threshold, then the inrush stabilization function operates. Another settable current
trigger blocks inrush stabilization if the current exceeds this trigger. The setting of the
operating mode determines whether inrush stabilization will operate phase-selectively or
across all phases.
0
1
2
0: Without
&
1: Not phase-
selective
2: Phase-
selective
MAIN: Inrush
stabil. trigg
306 014
0.1 Inom
MAIN: Rush
I(2fn)/I(fn) PSx
[ * ]
fnom
I(2*fn)/I(fn)
2*fnom
fnom
2*fnom I(2*fn)/I(fn)
fnom
2*fnom I(2*fn)/I(fn)
12Z6206 A_EN
By including function blocks in the bay interlock conditions, switching operations can be
prevented independently of the switching status at the time, for example, by an external
"CB drive not ready" signal or by the trip command from an external protection device.
Two multiple blocking conditions can be defined by selecting 'm out of n' parameters.
The selected functions may then be blocked by way of an appropriately configured
binary signal input.
3.12.9 Blocked/faulty
As a result, the CB status signal needs to be assigned to one binary signal input only if
this coupling is implemented.
Extended CB status
signals
The extended monitoring of the circuit breaker (CB) status signals is now available in the
main function group. It is now possible to select whether the multiple signals
"C B c l o s e d 3 p " / "C B o p e n 3 p " or (for P435 only) pole selective "Closed" status
signals will be monitored. Simultaneous monitoring of all status signals is not feasible
and should therefore not be undertaken.
If only the M A I N : C B c l o s e d s i g . E X T binary signal input has been configured
then the M A I N : C B o p e n 3 p signal will also be issued (see Figure 3-).
Figure 3- shows the logical processing of the various input signals. The plausibility logic
will be triggered should one of the following discrepancies be detected:
A minimum of one 3-pole monitoring signal and one 1-pole monitoring signal are
configured at the same time.
Both multiple signals M A I N : C B c l o s e d s i g . E X T and
M A I N : C B o p e n 3 p E X T are present simultaneously.
For P435 only: There is no pole-selective status signal
M A I N : C B c l o s e d x E X T present (i.e. CB contact is open) but at the same time
there is a current flow exceeding 0.05 Inom in this conductor.
The plausibility logic has been modified accordingly to permit that the binary signal input
only be configured at M A I N : C B c l o s e d s i g . E X T . This makes a backward
compatible operation possible (for example in an existing plant where only this signal
has been wired).
In order to suppress triggering during transient actions, the signal issued when a
plausibility discrepancy is detected has a generally delayed pickup of 100 ms.
Besides monitoring for signaling purposes, status signals are also processed in these
functions:
&
&
MAIN: CB closed
sig. EXT MAIN: CB closed 3p
[036 051] & & [ 031 042 ]
&
&
MAIN: CB closed A
EXT MAIN: CB closed A
[031 029] & & [ 031 035 ]
MAIN: CB open A
& & [ 031 032 ]
[031 029]
configured
MAIN: CB closed B
EXT MAIN: CB closed B
[031 030] & & [ 031 036 ]
MAIN: CB open B
& & [ 031 033 ]
[031 030]
configured
MAIN: CB open C
& & [ 031 034 ]
[031 031]
configured
10 100 ms
5 0 t MAIN: CB pos.sig.
unplaus.
[ 031 041 ]
>0.05
Inom Plausibility
check
IA
IB
IC
45Z1101B_EN
3-64 Monitoring of CB status signals (The P433 does not feature pole-selective CB status signals)
The circuit breaker can be closed from the P43x by the auto-reclosing control function
(ARC), using a setting parameter or via an appropriately configured binary signal input.
The close command issued using a setting parameter or via a binary signal input is
executed only if there is no trip command 1 present and that no trip has been issued by
a protection device operating in parallel. Moreover, with the setting of
M A I N : R C i n h i b . b y C B c l o s e to 'Yes', the close command is not executed if
there is a "CB closed" position signal present. The duration of the close command is
settable.
MAIN: RC inh.by
CB cl.
[ 015 042 ]
0
1
0: No
1: Yes
MAIN: En.man.
clos.cmd.USER
[ 003 105 ]
0
1
0: No
1: Yes MAIN: Man. cl.
cmd.enabl.
[ 039 113 ]
0: don't execute
1: execute
MAIN: Reset
c. cl/tr.cUSER
[ 003 007 ]
Multiple signals 1 and 2 are formed by the programmable logic function using OR
operators. The programmable logic output to be interpreted as multiple signaling is
defined by the configuration of the binary signal input assignment with the corresponding
multiple signaling. Both an updated and a stored signal are generated. The stored
signal is reset by the following actions:
General reset
Latching reset
LED indicators reset
A command received through the communication interface.
If the multiple signal is still present at the time of a reset, the stored signal will follow the
updated signal.
MAIN: Inp.asg.
mult.sig. 1
[ 221 051 ]
Signal 1
Signal 2
Signal 3
Signal n
MAIN: Mult.
Selected signal sig. 1 active
[ 221 017 ]
MAIN: Mult.
sig. 1 stored
S1 1 [ 221 054 ]
MAIN: Inp.asg.
mult.sig. 2
[ 221 052 ] R1
COMM1: Reset
mult. sig. 1 MAIN: Mult.
[ --- --- ] sig. 2 stored
S1 1 [ 221 055 ]
COMM1: Reset
mult. sig. 2 R1
[ --- --- ]
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OUTP: Reset
latching
402 102
12Z62FMA_EN
If a ground fault has been detected by either the GFDSS function (ground fault direction
determination by steady-state values) or the TGFD function (transient ground fault
direction determination), the P43x analyzes the phase-to-ground voltages and identifies
the phase on which the ground fault has occurred.
The P43x will first determine the lowest phase-to-ground voltage. Then it will check
whether the other two phase-to-ground voltages exceed a threshold of 0.2 Vnom.
In addition, the two highest phase-to-ground voltages must exceed the lowest phase-to-
ground voltage by a factor of 1.5. If these conditions are met, a ground fault signal is
issued for the phase with the lowest phase-to-ground voltage.
During a ground fault in Petersen coil-compensated power systems, the faulted phase
determination process is stopped as soon as the faulted phase is determined. Then
there will be no further measuring done until the end of the ground fault. Thus erroneous
signaling at the end of the ground fault is avoided, as the voltages of the healthy phases
may transiently fulfill the faulty phase criteria.
B C B C B C
N N N
(G)
(G) (G)
A A A
3-67 Transient condition of ground potential from faulted phase A back to the neutral point in Petersen coil-grounded systems (Petersen coil
and ground-capacitance of the system form a 50 Hz resonant circuit)
Ground fault signals generated either by ground fault direction determination using
steady-state values (GFDSS) or transient ground fault direction determination (TGFD)
are grouped together to form multiple signals.
Starting signals
The starting signals of the distance protection and backup overcurrent time protection
functions are linked to form common starting signals. The number of general starting
signals (GS) is counted.
DIST: Starting A
303 529
MAIN: Starting A
[ 036 001 ]
BUOC: IA>
triggered
304 750
DIST: Starting
303 535
N MAIN: Starting N
[ 036 004 ]
BUOC: SN
304 757
49Z6402A_EN
BUOC: IB>
triggered
304 751
BUOC: IC>
triggered
304 752
DIST: Signal
block start.G &
303 594
DIST: Starting MAIN: Starting GF
N1 [ 036 004 ]
303 535
BUOC: SN
304 757
45Z63ASA_EN
Trip command
The P43x provides two trip commands. The functions required to trip can be selected by
setting an 'm out of n' parameter independently for each of the two trip commands. The
minimum trip command time is settable. The trip signals are present only as long as the
conditions for the signal are met.
PSIG: Trip
enable
305 157
PSIG: Trip 1
305 155
PSIG: Trip 2
305 156
DIST: General
starting
[ 036 240 ]
PSIG: Trip V<
305 158
BUOC: Trip
signal
[ 036 014 ]
MAIN: 3-pole
trip
306 013
BUOC: Operating
mode
[ 014 000 ]
2: With ARC, 3p HSR
49Z6403A_EN
MAIN: Min.dur.
trip cmd. 1
[ 021 003 ]
MAIN: Fct.assig.
trip cmd.1
[ 021 001 ]
MAIN: Manual trip
signal
[ 034 017 ]
Signal 1
m out of n
Signal 2
Signal 3
Signal n
MAIN: Trip
Selected signals signal 1
306 017
MAIN: Fct.assig.
trip cmd.2
[ 021 002 ]
45Z6303A_EN
MAIN: Trip
signal 1, B
[ 036 007 ]
MAIN: Trip B
306 010
MAIN: Trip
command 1, B
[ 036 073 ]
MAIN: Trip
signal 1, C
[ 036 008 ]
MAIN: Trip C
306 011
MAIN: Trip
command 1, C
[ 036 074 ]
DIST: Trip
zone 5
303 588
DIST: Trip
zone 6
303 621
DIST: Trip
zone 7
303 622 MAIN: Fct.assig.
DIST: Trip signal trip cmd.1
zone 8 [ 021 001 ]
[ 037 130 ]
MAIN: Manual trip
signal
[ 034 017 ]
Signal 1
m out of n
Signal 2
Signal 3
Signal n
MAIN: Trip
Selected signals signal 1
306 017
MAIN: Fct.assig.
trip cmd.2
[ 021 002 ]
m out of n
45Z6305A_EN
Direct underreaching
transfer trip
Direct transfer tripping independently of the protective signaling scheme logic (function
group PSIG) is possible by using the following input signal:
For the P435 with 1/3-pole tripping the same applies to 1-pole send signals.
Note:
The P435 should either be used with phase-selective transfer tripping (1-pole) or 3-pole
transfer tripping, but never with both transfer trip types used simultaneously.
The reason for this is that with each 1-pole trip command a 3-pole general trip
command 1 is issued. If, for instance, the M A I N : T r a n s f e r t r i p . A E X T signal is
received without a local trip signal being present, then the P435 will issue a 1-pole
M A I N : T r i p c o m m a n d 1 , A as well as the 3-pole
M A I N : G e n . t r i p c o m m a n d 1 . Since no 3-pole transfer trip signal
M A I N : T r a n s f e r t r i p . E X T was received, the P435 will send the
M A I N : S e n d t r a n s f e r t r i p signal (but not the M A I N : S e n d t r a n s f e r t r i p A
signal).
P43x P43x
45Z6304A_EN
0
1
MAIN: General 0: don't execute
reset USER
[ 003 002 ] 1: execute
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Rst.c.cl./
tripc. EXT
[ 005 210 ]
49Z64CJA_EN
0
1
MAIN: General 0: don't execute
reset USER
[ 003 002 ] 1: execute
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
c. cl/tr.c EXT
[ 005 210 ]
45Z63CJA_EN
The binary signal input configured for “tripping” is set to a logic value of ' 1 ' or the
selected trip command from the P43x is present.
At the binary signal input configured as “CB trip” a logic value of ' 1 ' is present.
The CB trip signal from an external device can also be signaled. For this task, two
binary signal inputs need to be configured as “CB trip enable ext.“ and as “CB trip ext.“.
MAIN: Inp.assign.
tripping
[ 221 010 ]
Signal 1
Signal 2
Signal 3
Signal n
Selected signal
MAIN: Prot.trip>CB
MAIN: Gen. trip tripped
command 1 [ 221 012 ]
[ 036 071 ]
0
1
MAIN: Gen. trip
command 2 2
[ 036 022 ]
3
0 3
0 Without function
1 Gen. trip command 1
2 Gen. trip command 2
3 Gen.trip command 1/2
MAIN: Inp.asg.CB
tr.en.ext
[ 221 050 ]
MAIN: CB tripped
[ 221 016 ]
Selected signal
MAIN: Inp.asg. CB
trip ext
[ 221 024 ]
Selected signal
ARC: Sig.interr.
CB trip
[ 036 040 ]
12Z6269B_EN
Before a switching unit within the bay is closed or opened by the control functions of the
P43x, the P43x first checks whether the switch command may be executed. A switch
command will be executed if the optional control enable has been issued and the
interlock conditions are met. The interlock conditions are defined in the interlocking logic
for each switching unit within the bay that is subject to control actions and for each
control direction (Open/Close). Different conditions are defined for the bay interlock
equations to operate with or without station interlock. The check of bay or station
interlock equations can be cancelled for all electrically controllable switchgear units
within a bay. If station interlocking is active, it may be cancelled selectively for each
switching unit and each control direction (see “Control and Monitoring of Switchgear
Units”).
If 'Local' has been selected as the control point, the bay and station interlocks may be
cancelled through an appropriately configured binary signal input.
3-82 General enable for switch commands issued by the control functions; activating or canceling the interlocks
The data stored in the operating data memory, the monitoring signal memory and the
event memories are date- and time-tagged. For correct time-tagging, the date and time
need to be set in the P43x.
3-85 Date/time setting and clock synchronization with minute pulses presented at a binary signal input
Synchronization source
The P43x provides numerous options to synchronize the internal clock:
o Telegram with the time of day via the communication interface COMM1/IEC (full
time)
o Telegram with the time of day via the communication interface COMM2/PC (full time)
o IRIG-B Signal (IRIGB; time of day only)
o Minute pulse presented at a binary signal input (MAIN), see figure 3- and previous
paragraph
With older device versions these interfaces had equal ranking i.e. clock synchronization
was carried out regardless of which sub-function initiated triggering. No conflicts have to
be taken into account as long as synchronization sources (communication master,
IRIG-B and minute pulse source) operate at the same time of day. Should the
synchronization sources operate with a different time basis unwanted step changes in
the internal clock may occur. On the other hand a redundant time of day synchronization
is often used so as to sustain time synchronization via IRIG-B interface even if and while
the SCADA communication is out of service.
With the current device versions a primary and a backup source for time of day
synchronization may now be set, where both provide the four options listed in the above.
M A I N : Prim.Source TimeSync
M A I N : BackupSourceTimeSync
With this feature synchronization occurs continuously from the primary source as long as
time synchronization telegrams (or minute signal pulses) are received within a time-out
period set at M A I N : T i m e s y n c . t i m e - o u t . The backup source is required if after
the set time-out there is no synchronization through the primary source.
When selecting the time telegram via IEC as the primary source the device will expect
time synchronization telegrams from server SNTP2 after server SNTP 1 has become
defective, before it will switch over to the backup source.
Time synchronization occurs solely from the primary source when the time-out stage is
blocked.
Stored data such as event logs, measured fault data etc, can be cleared in several ways.
The following types of resetting actions are possible:
Automatic resetting of the event signals provided by LED indicators (given that the
LED operating mode has been set accordingly) and of the display of measured event
data on the local control panel LCD whenever a new event occurs. In this case only
the displays on the local control panel LCD are cleared but not the internal memories
such as the fault memory.
Resetting of LED indicators and measured event data displayed on the local control
panel LCD by pressing the "CLEAR" key C located on the local control panel.
By selecting the required function at L O C : F c t . r e s e t k e y further memories
may be assigned which will then also be cleared when the "CLEAR" key is pressed.
Selective resetting of a particular memory type (e.g. only the fault memory) via setting
parameters. (For this example: Navigate to menu point
F T _ R C : R e s e t r e c o r d . U S E R and set to 'Execute', see also the exact step-
by-step description in Chapter 6 "Local Control", section 'Reset'.)
Selective resetting of a particular memory type (e.g. only the fault memory) through
appropriately configured binary signal inputs. (For this example: Assign parameter
F T _ R C : R e s e t r e c o r d . E X T to the relevant binary signal input e.g.
I N P : F c t . a s s i g n m . U 3 0 1 .)
Group resetting by setting parameters, by navigating to menu point
M A I N : G r o u p r e s e t x U S E R and setting it to 'Execute'. For this the relevant
memories (i.e. those to be reset) must be assigned to parameter
MAIN: Fct.assign. reset x.
Group resetting through appropriately configured binary signal inputs. (That is,
assign parameter M A I N : G r o u p r e s e t . x E X T to the relevant binary signal
input, e.g. I N P : F c t . a s s i g n m . U 3 0 1 after memories to be reset have been
assigned to parameter M A I N : F c t . a s s i g n . r e s e t x .)
General resetting by setting parameters (menu point
M A I N : G e n e r a l r e s e t U S E R ). All memories, counters, events etc. are reset
without any special configuration options.
Should several resetting actions have been configured for one particular memory then
they all have equal priority.
In the event of a cold restart, namely simultaneous failure of both internal battery and
substation auxiliary supply, all stored signals and values will be lost.
Further resetting possibilities are basically not distinct resetting actions but make access
especially easy to one of the resetting actions described above i.e. by configuring them
to a function key.
MAIN: General
reset USER
[ 003 002 ]
0
1 1: execute
0: don't execute
1: execute
MAIN: Reset
indicat. USER
[ 021 010 ]
0
1
0: don't execute
1: execute
≥1 MAIN: Reset LED
306 020
MAIN: Reset
indicat. EXT
[ 065 001 ]
12Z6115 A_EN
3-86 General reset, LED reset and measured event data reset
m out of n
MAIN: Group
reset 1 USER
[ * ]
1 ≥1 &
0: don't execute
1: execute
MAIN: Group
reset 1 EXT
[ * ]
MAIN: Fct.assign.
reset 1
[ * ]
m out of n
12Z61RMB_EN
3-87 "CLEAR" key on the local control panel and, as an example, group resetting of the operating data recording (e.g. as an example for the
reset signal OP_RC: Reset record. EXT); further examples for resetting signals generated in this way are:
- TGFD: Reset signal EXT
- MAIN: Reset c. cl/tr.c EXT
- MAIN: Reset IP,max,st. EXT
- MAIN Reset meas.v.en. EXT
- MT_RC: Reset record. EXT
- OL_RC: Reset record. EXT
- GF_RC: Reset record. EXT
- FT_RC: Reset record. EXT
- ARC: Reset counters EXT
- GFDSS: Reset counters EXT
- TGFD: Reset counters EXT
- MAIN: General reset EXT
- COMM3: Reset No.tlg.err.EXT
- ASC: Reset counters EXT
- f<>: Reset meas.val. EXT
- MEASI: Reset Tmax EXT
- LOGIC: Reset x EXT (x=1...8)
- MEASI: Reset output EXT
- THERM: Reset replica EXT
- OUTP: Reset latch. EXT
- MAIN: Reset latch.trip EXT
- M A I N Reset indicat. EXT
If tests are run on the P43x, the user is advised to activate the test mode so that all
incoming signals via the serial interfaces will be identified accordingly.
With the P43x, four independent parameter subsets may be pre-set. The user may
switch between parameter subsets during operation without interrupting the protection
function.
If, after the supply voltage is turned on, no logic level of ' 1 ' is present at any of the
binary signal inputs selected for the parameter subset selection, then the parameter
subset selected via the function parameter will become active once the stored time has
elapsed. The previous parameter subset remains active while the stored hold timer
stage is running.
Parameter subset selection may also occur during a general starting condition. In this
case, however, the settings for distance measurement and impedance-time
characteristics remain unchanged. They are not updated until the general starting
condition ends. When subset selection is handled via binary signal inputs, a maximum
inherent delay of approximately 100 ms must be taken into account.
Settings for which only one address is given in the following sections are equally
effective for all four parameter subsets.
Comprehensive monitoring routines in the P43x ensure that internal faults are detected
and do not lead to malfunctions.
Cyclic tests
After start-up has been successfully completed, cyclic self-monitoring tests will be run
during operation. In the event of a positive test result, a specified monitoring signal will
be issued and stored in a non-volatile memory – the monitoring signal memory – along
with the assigned date and time (see also Monitoring Signal Recording).
The self-monitoring function monitors the built-in battery for any drop below the minimum
acceptable voltage level. If the associated monitoring signal is displayed, then the
battery should be replaced within a month, since otherwise there is the danger of data
loss if the supply voltage should fail. Chapter 11 gives further instructions on battery
replacement.
Signal
The monitoring signals are also signaled via the output relay configured to
S F M O N : W a r n i n g . The output relay operates as long as an internal fault is
detected.
Device response
The response of the P43x is dependent on the type of monitoring signal. The following
responses are possible:
Signaling Only
If there is no malfunction associated with the monitoring signal, then only a signal is
issued, and there are no further consequences. This situation exists, for example,
when internal data acquisition memories overflow.
Selective Blocking
If a fault is diagnosed solely in an area that does not affect the protective functions,
then only the affected area is blocked. This would apply, for example, to the
detection of a fault on the communication module or in the area of the PC interface.
Warm Restart
If the self-monitoring function detects a fault that might be eliminated by a system
restart – such as a fault in the hardware –, then a procedure called a warm restart is
automatically initiated. During this procedure, as with any start-up, the computer
system is reset to a defined state. A warm restart is characterized by the fact that no
stored data and, in particular, no setting parameters are affected by the procedure.
A warm restart can also be triggered manually by control action. During a warm
restart sequence the protective functions and the communication through serial
interfaces will be blocked. If the same fault is detected after a warm restart has been
triggered by the self-monitoring system, then the protective functions remain blocked
but communication through the serial interfaces will usually be possible again.
Cold Restart
If a corrupted parameter subset is diagnosed during the checksum test, which is part
of the self-monitoring procedure, then a cold restart is carried out. This is necessary
because the protection device cannot identify which parameter in the subset is
corrupted. A cold restart causes all internal memories to be reset to a defined state.
This means that all the protection device settings are also erased after a cold restart.
In order to establish a safe initial state, the default values have been selected so that
the protective functions are blocked. Both the monitoring signal that triggered the
cold restart and the value indicating parameter loss are entered in the monitoring
signal memory.
The default for this timer stage is ‘blocked’ i.e. blocking of the protection device with two
identical faults occurs independently of the time elapsed since the first fault monitoring
signal was issued.
The behavior caused by sporadic faults could lead to an unwanted blocking of the device
if the monitoring signal memory has not been reset in the interim, for example, because
the substation is difficult to reach in wintertime or reading-out and clearing of the
monitoring signal memory via the communication interfaces was not enabled. To defuse
this problem it is suggested to set the function parameter to a specific time period so that
blocking will only occur if the same fault occurs again within this time period. Otherwise,
the device will continue to operate normally after a warm restart.
OP_RC: Operat.
data record.
[ 003 024 ]
MAIN: General
reset USER + OP_RC: No. oper.
[ 003 002 ] data sig.
[ 100 002 ]
1: execute R
MAIN: General
reset EXT
[ 005 255 ]
OP_RC: Reset
record. EXT
[ 005 213 ]
OP_RC: Reset
record. USER
[ 100 001 ]
0: don't execute
1: execute
12Z61CMA_EN
3-92 Operating data recording and counter for signals relevant to system operation
The monitoring signals generated by the self-monitoring function are recorded in the
monitoring signal memory. The memory buffer allows for a maximum of 30 entries.
If more than 29 monitoring signals occur without interim memory clearance, the
SFMON: O v e r f l o w M T _ R C signal is entered as the last entry. Monitoring signals
prompted by a hardware fault in the unit are always entered in the monitoring signal
memory. Monitoring signals prompted by a peripheral fault can be entered into the
monitoring signal memory, if desired. The user can select this option by setting an 'm
out of n' parameter (see 'Self-Monitoring').
If at least one entry is stored in the monitoring signal memory, this fact is signaled by the
red LED indicator H 3 on the local control panel. Each new entry causes the LED to
flash (on/off/on....).
The monitoring signal memory can only be cleared manually by a control action. Entries
in the monitoring signal memory are not cleared automatically, even if the corresponding
test in a new test cycle now shows the device to be healthy. The contents of the
monitoring signal memory can be read from the local control panel or through the PC or
communication interface. The time and date information assigned to the individual
entries can be read out through the PC or communication interface or from the local
control panel.
SFMON: Hardware
fault
304 950
Select monit.
signal
MT_RC: Reset
record. USER
[ 003 008 ]
CT30 SFMON: Overflow
≥1 MT_RC
[ 090 012 ]
0
MT_RC: No. monit.
1 ≥1 signals
[ 004 019 ]
0: don't execute
1: execute
MT_RC: Reset
record. EXT
[ 005 240 ]
12Z6155A_EN
Overload duration
In the event of an overload, the P43x determines the overload duration. The overload
duration is defined as the time between the start and end of the OL_ R C : R e c o r d . i n
p r o g r e s s signal.
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
OL_RC: Reset
record. USER
[ 100 003 ]
1: execute
50Z0137A_EN
Acquiring measured
overload data from the
thermal overload protection
Measured overload values are derived from the thermal overload protection’s measured
operating data. They are stored at the end of an overload event.
OL_RC: Record.
in progress C
[ 035 003 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
OL_RC: Reset
record. USER
[ 100 003 ]
1: execute
12Z6238A_EN
OL_RC: Record. in
progress
[ 035 003 ]
THERM: Starting OL_RC: No.
k*Iref> + overload
[ 041 108 ] [ 004 101 ]
R
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
OL_RC: Reset
record. USER
[ 100 003 ]
1: execute
45Z63DXA_EN
Time tagging
The date of each overload event is stored. The overload start or end signals are likewise
time-tagged by the internal clock. The date and time assigned to an overload event
when the event begins can be read out from the overload memory on the local control
panel or through the PC and communication interfaces. The time information (relative to
the onset of the overload) can be retrieved from the overload memory or through the PC
or communication interfaces.
Overload logging
Protection signals during an overload event are logged in chronological order with
reference to the specific event. A total of eight overload events, each involving a
maximum of 200 start or end signals, can be stored in the non-volatile overload
memories. After eight overload events have been logged, the oldest overload log will be
overwritten, unless memories have been cleared in the interim. If more than 199 start or
end signals have occurred during a single overload event, then
O L _ R C : O v e r l . m e m . o v e r f l o w will be entered as the last signal.
In addition to the signals, the measured overload data will also be entered in the
overload memory.
The overload logs can be read from the local control panel or through the PC or
communication interfaces.
OL_RC: Record. C
in progress
[ 035 003 ]
OL_RC: Overload
n
Measured value 1 recording n
1 033 020
Measured value 2
2 033 021
Measured value 3
3 033 022
Measured value n
MAIN: Time tag 4 033 023
306 021
5 033 024
1 ≥1
MAIN: General
reset USER 0: don't execute
[ 003 002 ] 1: execute
1: execute
MAIN: General
reset EXT
[ 005 255 ]
OL_RC: Reset
record. EXT
[ 005 241 ]
12Z6117 A_EN
In the event of a ground fault, the P43x acquires the following measured ground fault
data:
Resetting measured
ground fault data
After pressing the reset key ‘C’ on the local control panel, the measured ground fault
data value is displayed as 'Not measured'. However, the values are not erased and can
continue to be read out through the PC and communication interfaces.
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
GF_RC: Reset
record. USER
[ 005 242 ]
GF_RC: Reset
record. USER
[ 100 000 ]
1: execute
49Z64DWA_EN
S1 1 & C
R1
GFDSS: Grd.
fault pow./adm.
[ 009 037 ]
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
50Z0144A_EN
3-99 Measurement and storage of the ground fault duration from steady state power evaluation
Residual current
The residual current flowing when timer stage G F D S S : t V N G > elapses is stored in
memory. Also stored is the active and reactive component of the residual current
determined at the time when the directional decision is output. All measured values are
output as per-unit quantities referred to the device’s nominal current Inom.
Neutral-point displacement
voltage
The neutral-point displacement voltage present when timer stage G F D S S : t V N G >
elapses is stored in memory.
GFDSS: Grd. C
fault pow./adm.
[ 009 037 ]
GF_DA: Current
IN IN p.u.
[ 009 021 ]
R
GFDSS: Direct.
forward/LS C
[ 009 035 ]
GFDSS: Direct.
backward/BS
[ 009 036 ]
GFDSS: Current GF_DA: Curr.
IN,act p.u. IN,act p.u.
[ 004 045 ] [ 009 022 ]
& R
GF_DA: Voltage
GFDSS: VNG VNG p.u.
304 150 [ 009 020 ]
R
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
50Z0145A_EN
3-100 Residual current and neutral-point displacement voltage from steady state value evaluation
S1 1 & C
R1
50Z0148A_EN
3-101 Measurement and storing the ground fault duration as determined by steady state current evaluation
Residual current
The unfiltered and filtered residual currents that are present when the operate delay
elapses (G F D S S : O p e r a t e d e l a y IN) are stored.
GF_DA: Current IN
IN p.u.
[ 009 021 ]
R
GF_DA: Curr. IN
GFDSS: 2IN filt. p.u.
filtered [ 009 025 ]
304 159
R
MAIN: General
reset USER
[ 003 002 ]
1: ausführen
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
50Z0151A_EN
A ground fault has been detected by ground fault direction determination using
steady-state values (GFDSS).
A ground fault has been detected by transient ground fault direction determination
(TGFD).
Counting ground fault
events
Ground fault events are counted and identified by sequential numbers.
Time tagging
The date of each ground fault event is stored. A ground fault’s individual start or end
signals are likewise time-tagged. The date and time assigned to a ground fault event
when the event begins can be read out from the ground fault memory on the local control
panel or through the PC and communication interfaces. The time information (relative to
the onset of the ground fault) that is assigned to the signals can be retrieved from the
ground fault memory or through the PC or communication interfaces.
In addition to the signals, the measured ground fault data will also be entered in the
ground fault memory.
The ground fault logs can be read from the local control panel or through the PC or
communication interfaces.
GF_RC: Record. C
in progress
[ 035 005 ]
GF_RC: Ground
n flt.record. n
Measured value 1
Measured value 2 1 033 010
1 ≥1
0: don't execute
MAIN: General 1: execute
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
GF_RC: Reset
record. EXT
[ 005 242 ]
12Z6141 A_EN
When there is a primary system fault, the P43x collects the following measured fault
data:
Running time
Fault duration
Fault current
Fault voltage (short-circuit voltage)
Fault impedance (short-circuit impedance)
Fault reactance (short-circuit reactance) in percent of line reactance and in Ω
Fault angle
Fault distance
Ground fault current
Ground fault angle
Fault location in km or percentage of the protected line
Load data at end of fault
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
49Z64DMA_EN
End of fault
Acquisition at the end of the fault.
Trigger/Trip/End
Acquisition at the following points:
When an appropriately configured binary signal input is triggered during a general
starting state.
When a general trip signal is issued.
At the end of the fault.
'Always'
Calculation and output of the fault location always occurs if the other measured fault
data are also being determined.
'Only after trip t1'
Calculation and output of the fault location occurs if the P43x decides in favor of a trip
in impedance zone 1 with standard reach (non-extended zone).
'Only aft.tr.t1/t1,ze'
Calculation and output of the fault location occurs if the P43x decides in favor of a trip
in impedance zone 1 with standard and extended reach.
3-106 Enabling of measured fault data acquisition and fault location output
The ground fault data are only determined if a phase-to-ground loop has been selected
for measurement by the distance protection function. The geometric sum of the three
phase currents is displayed as the ground fault current. The ground fault angle is the
phase displacement between the ground fault current and the selected measuring
voltage.
If the fault is detected by the backup overcurrent-time protection function, then only the
fault current can be determined. The maximum phase current is displayed.
Fault current and voltage are displayed as per-unit quantities referred to Inom and Vnom.
If the measured or calculated values are outside the acceptable measuring range, the
‘Overflow’ indication will be displayed.
FT_DA: Output
meas. values C 1,2
305 050
DIST: Select.
meas.loop P-G C 2
303 543
DIST: General
starting
[ 036 240 ] FT_DA: Fault
1,3,4 1 current P p.u.
BUOC: Starting 2 [ 004 025 ]
[ 036 013 ] R
FT_DA: Flt.volt.
1 1 PG/PP p.u.
[ 004 026 ]
R
IA 2
IB Imax FT_DA: Fault loop
IC 1 angle P
[ 004 024 ]
3 R
FT_DA: Fault
4 1 impedance, sec
[ 004 023 ]
R
DIST: Select. 2 ... 3
meas.loop A-G 1
303 537 1 FT_DA: Fault
1 reactance,sec.
DIST: Select. 4 [ 004 028 ]
meas.loop B-G 2 R
303 538
< 0.2 V
DIST: Vmeas 1
303 546
2
1
DIST: α 2
MAIN: General
reset USER 1 ... 2
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
45Z6320A_EN
FT_DA: Line
length PSx
[ * ]
FT_DA: Line
reactance PSx
[ * ]
FT_DA: Outp. C
fault location
305 051
FT_DA: Fault
FT_DA: Fault location
reactance,sec. [ 004 022 ]
[ 004 028 ] R
Load impedance
Load angle
Residual current
The same measuring loop used to determine fault impedance is used to determine load
impedance and load angle. The load current and the voltage must exceed the
thresholds 0.1 Inom and 0.1 Vnom , respectively, in order for the load data to be
determined. If the thresholds are not reached or if the general starting signal of distance
protection was shorter than 60 ms, the message ‘Not measured’ will be displayed.
DIST: General 1
starting
[ 036 240 ]
60 ms 0
S1 1
R1
C 1
DIST: Select. & S
meas.loop A-G R
303 537
& S C 2
DIST: Select.
meas.loop B-G R
303 538
S C 3
DIST: Select. &
meas.loop C-G
303 539 R
& S C 6
DIST: Select.
meas.loop C-A ≥ 0.1 Inom
303 542 R
DIST: IA-kG
303 601 &
1
DIST: IB-kG
303 602 2
DIST: IC-kG
≥ 0.1 Vnom
303 603 3
4
VA-G C
VB-G
5
FT_DA: Load
VC-G imped.post-flt.
6 [ 004 037 ]
R
FT_DA:
Resid.curr. post-
IC flt
[ 004 039 ]
R
IN
MAIN: General
reset USER
[ 003 002 ]
1: execute ≥1
MAIN: General
reset EXT
[ 005 255 ]
MAIN: Reset
LED
306 020
49A6421A_EN
In addition, the user can set a logical "OR" combination of logic signals ('m out of n'
parameter) which appearance will trigger fault recording.
Fault counting
Faults are counted and identified by sequential numbers.
FT_RC: Fct.
assig. trigger
[ 003 085 ]
Signal 1
Signal 2
m out of n
Signal 3
Signal n
Selected signals
FT_RC: Trigger
USER
[ 003 041 ]
0
1 FT_RC: Record.
in progress
0: don't execute [ 035 000 ]
1: execute
MAIN: General
starting
[ 036 000 ]
MAIN: Gen. trip
signal 1
[ 036 005 ]
MAIN: Gen. trip
signal 2
[ 036 023 ]
45Z6325A_EN
Time tagging
The date that is assigned to each fault by the internal clock is stored. A fault’s individual
start or end signals are likewise time-tagged. The date and time assigned to a fault
when the fault begins can be read out from the fault memory on the local control panel or
through the PC and communication interfaces. The time information (relative to the
onset of the fault) that is assigned to the signals can be retrieved from the fault memory
or through the PC or communication interfaces.
Fault recordings
Protection signals, including the signals during the settable pre-fault and post-fault times,
are logged in chronological order with reference to the specific fault. A total of eight
faults, each involving a maximum of 200 start or end signals, can be stored in the non-
volatile fault memories. After eight faults have been recorded, the oldest fault recording
will be overwritten, unless memories have been cleared in the interim. If more than 199
start or end signals have occurred during a single fault, then
F T _ R C : F a u l t m e m . o v e r f l o w will be entered as the last signal. If the time and
date are changed during the pre-fault time, the F T _ R C : F a u l t y t i m e t a g signal is
generated.
In addition to the fault signals, the measured RMS fault data will also be entered in the
fault memory.
The fault recordings can be read from the local control panel or through the PC or
communication interfaces.
FT_RC: Record. C
in progress
[ 035 000 ]
FT_RC: Fault mem.
Signal 1 + CT200 overflow
1 [ 035 001 ]
Signal 2 1 R
Signal 3 1
Signal n 1
FT_RC: Fault
recording n
1 [ * ]
FT_RC: Pre-fault
time
[ 003 078 ]
FT_RC: Post-
fault time
[ 003 079 ]
n FT_RC: Fault
recording n
Fault memory n
1 003 000
2 033 001
3 033 002
MAIN: General
reset USER &
[ 003 002 ]
1: execute R
MAIN: General
reset EXT
[ 005 255 ]
FT_RC: Reset
record. EXT
[ 005 243 ]
FT_RC: Reset
record. USER
[ 003 006 ]
0
1 1: execute
0: don’t execute
1: execute
12Z6161 B_EN
Phase currents
Phase-to-ground voltages
Residual current measured by the P43x at the T 4 transformer
Neutral-point displacement voltage measured by the P43x at the T 90 transformer
The signals are recorded before, during and after a fault. The window length for
oscillography recording before and after the fault can be set. A maximum time period of
16.4 s (at 50 Hz) or 13.7 s (at 60 Hz) is available for recording. This period can be
divided among a maximum of eight faults. The maximum recording time per fault can be
set. If a fault, including the set pre-fault and post-fault times, lasts longer than the set
maximum recording time, then recording will terminate when the set maximum recording
time is reached.
The pre-fault time is exactly adhered to if it is shorter than the set maximum recording
time. Otherwise the pre-fault time is set to the maximum recording time minus a
sampling increment, and the post-fault time is set to zero.
If the maximum recording time is exceeded, the analog values for the oldest fault are
overwritten, but not the binary values. If more than eight faults have occurred since the
last reset, then all data for the oldest fault are overwritten.
The analog oscillography data of the fault record can only be read out through the PC or
communication interfaces.
When the supply voltage is interrupted or after a warm restart, the values of all faults
remain stored.
FR_RC: Record.
in progress C
[ 035 000 ]
FR_RC: Max.
recording time
[ 003 075 ]
FR_RC: Pre-fault
time
[ 003 078 ]
FR_RC: Post-
fault time
[ 003 079 ]
IA Analog channel 1
R
IB Analog channel 2
R
IC Analog channel 3
R
VC-G
Analog channel 6
R
IN Analog channel 7
R
VN-G
Analog channel 8
R
FR_RC: Reset
record. USER
[ 003 006 ]
1: execute ≥1
MAIN: General
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
FR_RC: Reset
record. EXT
[ 005 243 ]
12Z6220A_EN
Disabling or enabling
distance protection
Distance protection can be disabled or enabled using a setting parameter
(see figure 3-113).
The fault detection logic in distance protection serves to detect short-circuits phase-
selectively. Fault detection logic is divided into the following areas:
Overcurrent detection
Ground fault detection
Undervoltage detection
Underimpedance fault detection
The fault detection decisions of the individual areas are linked by the fault detection
logic.
Short-circuit currents that are greater than the maximum operating load currents can be
detected by the overcurrent detection logic. Undervoltage detection logic is provided for
short circuits that cannot be identified by overcurrent detection. In order to control
difficult conditions for fault detection, the P43x is also equipped with a highly angle-
dependent ‘true’ underimpedance detection logic function. Ground fault detection logic
distinguishes between grounded and ungrounded faults.
The fault detection logic starts the timer stages of the trigger levels and – as a function of
the phase-selective fault detection decision – selects the measuring loops in which the
fault impedances are determined. The fault detection logic is blocked if one of the
following conditions is met:
1 2 3 4 5 6 7
DIST: General
enable USER
[ 031 073 ]
0
1 DIST: Enabled
0: No [ 036 104 ]
1: Yes
>1
DIST: Starting
- blocked
303 500
MCMON: Meas.
circ. V faulty
[ 038 023 ]
MAIN: Protection
active
306 001
1 60 D5Z5029A_EN
Overcurrent detection
Overcurrent fault detection monitors the phase currents for values in excess of the
threshold values I>> and I>>>. The I>> threshold can be set. I>>> is equal to 2 I>>.
The thresholds are identical for all three phases.
The output signals of the I>> trigger assume a logic value of ’ 1 ’ if the threshold is
exceeded in two consecutive half-waves. In the case of the I>>> trigger only one
half-wave must exceed the threshold for the output signals to assume a logic value of
‘ 1 ’. Triggering of inrush stabilization prevents operation of the I>> trigger.
If I>> is exceeded in one phase, then it is sufficient for overcurrent detection if I>>> is
exceeded in the other phases. In this case the fault detection time is shortened since
there is no longer any need to wait for the second half-wave.
Evaluation of the trigger decisions is a function of the type of neutral-point treatment set
in the P43x. If ‘isolated neutral/resonant grounding’ or ‘short-duration grounding’ is set,
then I>> overcurrent detection occurs in the phase(s) in which the I>> threshold is
exceeded. With the setting ‘low-impedance grounding’ the following condition must also
be satisfied:
2
I≥ ⋅I
3 max
MAIN: Neutr.pt.
treat. PSx
[ * ]
1: Low-imped.
grounding
2: Isol./
res.w.start.PG
3: Isol./res.w/o
st. PG
4: Short-durat.
ground.
IA
IB
IC
DIST: I>>
triggered
303 597
I>>> = 2*I>>
DIST: I>>>
triggered
303 501
COMP
(2/3)*Imax
Imax
DIST: IA>>
triggered
303 511
DIST: IB>>
triggered
303 512
DIST: IC>>
triggered
303 513
* Parameter MAIN: Neutr.pt. DIST: I>>
treat. PSx PSx
set 1 010 048 010 054
set 2 001 076 010 074
set 3 001 077 010 094
set 4 001 078 011 014
47Z1155B_EN
5% of the current maximum phase current is added to the set threshold IN>, which
means that the operate value of the ground current function increases with an increasing
phase current level as a form of stabilization.
MAIN: Dynamic
range 1
[ 031 082 ]
2: Sensitive
range
1: Highest range
IA COMP
IB DIST: IN> sens.
C range PSx
[ * ]
IC
Imax C DIST:
range
IN> high
PSx
[ * ]
DIST: Start.
IN> triggered
303 502
|Ix|
0.05*|Imax| |Ix|+IN>
DIST: tIN>
PSx
[ * ]
DIST: Starting C
blocked DIST: tIN>
303 500 elapsed
303 503
DIST: tIN>
running
[ 036 105 ]
MAIN: Neutr.pt.
treat. PSx 0 50ms
[ * ]
4: Short-durat.
ground.
DIST: VNG>
C PSx
[ * ]
DIST: DIST:
VNG>> exceeded
303 596
VC-G
DIST: tVNG>>
MAIN: Neutr.pt. elapsed
303 506
treat. PSx
[ * ]
DIST: VNG>>
1: Low-imped. triggered
grounding [ 036 015 ]
DIST: tVNG>>
elapsed
[ 036 016 ]
* Parameter MAIN: Neutr.pt. DIST: IN> high DIST: IN> sens. DIST: tIN> DIST: VNG> DIST: VNG>> DIST: tVNG>>
treat. PSx range PSx range PSx PSx PSx PSx PSx
set 1 010 048 010 055 010 123 010 057 010 056 010 062 010 061
set 2 001 076 010 075 010 124 010 077 010 076 010 082 010 081
set 3 001 077 010 095 010 125 010 097 010 096 011 002 011 001
set 4 001 078 011 015 010 126 011 017 011 016 011 022 011 021
47Z1156B_EN
The ground fault detection mode is a function of the neutral-point treatment set in the
P43x.
M A I N : N e u t r a l - p o i n t t r e a t m e n t 'Low-impedance grounding'
Ground fault detection D I S T : S t a r t i n g G occurs with this setting when the
threshold of the IN> or VNG> trigger is exceeded. Furthermore, triggering of stage
VNG>> and the lapse of timer stage tVNG>> is signaled (see Figure 3-115).
M A I N : N e u t r a l - p o i n t t r e a t m e n t 'Isolated neutral/resonant grounding'
If the setting 'Isolated neutral/resonant grounding' is selected, instantaneous ground
fault detection D I S T : S t a r t i n g G operates in the event of multiple phase-to-
ground fault detection when the thresholds of the IN> and VNG> triggers are
exceeded. Even in the case of a single-phase fault, that is, in the event that only one
base point is detected, ground fault detection will operate, but not until tIN> has
elapsed.
M A I N : N e u t r . p t . t r e a t . = 'Short-duration grounding'
Operation here corresponds to operation with the setting 'Isolated neutral/resonant
grounding' except that in the case of a sustained ground fault the timer stage tIN>
remains activated due to the operating trigger VNG>> and therefore no longer has
any effect in the event of subsequent short-duration grounding.
MAIN: Neutr.pt.
treat. PSx
[ * ]
2: Isol./
res.w.start.PG
3: Isol./res.w/o
st. PG
4: Short-durat.
ground.
DIST: Start.
IN> triggered
303 502
DIST: Start.
DIST: Start. switch. to PG
VNG> triggered [ 040 052 ]
303 504
DIST: tIN>
elapsed
303 503
DIST: IA>>
triggered
303 511
DIST: IB>>
triggered
303 512
DIST: IC>>
triggered
303 513
DIST: VPP<
triggered
303 509
* Parameter MAIN: Neutr.pt.
treat. PSx
DIST: Start. set 1 010 048
ZPP< triggered
303 510 set 2 001 076
set 3 001 077
set 4 001 078
47Z1150B_EN
Enabling undervoltage
and underimpedance
fault detection
The undervoltage and underimpedance fault detection functions are enabled by I>(Imin)
in the corresponding measuring systems. For the two possible dynamic ranges of
current measurement, one parameter each is available for setting the fault detection
value for I>(Imin). In order to control contention problems when current and voltage
appear at the same time (branch voltage transformers), measuring system enabling is
delayed by 15 ms.
For sensitive detection of double ground faults with isolated neutral/resonant grounding,
the P43x checks to determine whether the base point current I>(Imin) is exceeded in one
phase only and whether the measured value falls below the set threshold for
underimpedance fault detection in two phases. Enabling proceeds in the phases where
the voltage is below the set threshold.
DIST: Starting
blocked
303 500
DIST: IC>(Ibl)
trigg.
303 600
DIST: V<
PSx Meas.value > Set value
[ * ] C DIST: Enable
15ms 0 V<, Z<, A
303 514
VA-G
VB-G
DIST: Enable
15ms 0 V<, Z<, C
303 516
C
Meas.value < Set value
VA-G* 3
VB-G* 3
MAIN: Neutr.pt. VC-G* 3
treat. PSx
[ * ]
2: Isol./
res.w.start.PG
4: Short-durat.
ground.
Undervoltage detection
Undervoltage fault detection monitors the phase-to-ground voltages or the phase-to-
phase voltages to determine whether they fall below the set threshold V<.
Underimpedance fault
detection
Underimpedance fault detection determines the impedances of the phase-to-ground or
phase-to-phase loops.
The underimpedance fault detection mode can be set by selecting the operating mode.
The following operating modes are possible:
All underimpedance fault detection measuring loops are blocked when the I>>> trigger
operates (see ‘Overcurrent Fault Detection’). When overcurrent or undervoltage fault
detection operates, the corresponding measuring loops are blocked phase-selectively.
If, on the basis of the settings, the reach in the backward (reverse) direction is greater
than 3 Znom, then the range is limited to 3 Znom (Znom = Vnom / Inom).
to form common phase-selective starting decisions (SA, SB, and SC) and SN1.
The phase-selective starting decisions are combined to form ‘general starting’ – and thus
produce the M A I N : G e n e r a l s t a r t i n g signal. Ground fault detection alone does
not bring about general starting.
If fault detection operates via overcurrent fault detection, single-phase fault detection
may operate without ground fault detection. In order for the measuring loops for
distance and directional measurement to be properly selected even in this case, either
SN1 or starting in another phase must be triggered as well. It is possible to specify
whether, in the case of single-phase starting, SN1 will always be triggered or whether –
depending on the magnitude of the phase currents – SN1 or starting in one phase will be
transfer-triggered.
M A I N : T r a n s f e r f o r 1 p ‘Ground’
With single-phase overcurrent fault detection, SN1 is started and transferred after the
timer stage tIN> has elapsed (see ‘Ground fault detection’ for setting).
If there is a change from single-phase overcurrent fault detection without ground to
multi-phase fault detection or single-phase-to-ground fault detection, starting will
occur instantaneously.
MAIN: Transfer for 1p
‘P or G = f(Imed,Imax)’
For single-pole overcurrent fault detection, the decision as to whether starting in one
phase or SN1 starting will be transferred depends on the Imed / Imax ratio.
The magnitude of the medium phase current must be more than 2/3 the magnitude of
the maximum current for the phase to be transfer-triggered. If the current with the
medium-sized magnitude is smaller, SN1 will be triggered after timer stage tIN> has
elapsed.
If there is a change from single-phase overcurrent fault detection without ground to
multi-phase fault detection or single-phase-to-ground fault detection, starting will
occur instantaneously.
DIST: IA>>
triggered
303 511
DIST: VB<
triggered DIST: Starting B
303 518 303 530
DIST: IB>>
triggered
303 512
DIST: VC<
triggered DIST: Starting C
303 519 303 531
DIST: Multipole
starting
DIST: Starting G 303 534
303 507
DIST: Starting
303 535
N
DIST: tIN>
PSx
[ * ]
DIST: Zero-
sequ. starting
[ 036 021 ]
MAIN: Transfer
for 1p PSx
[ * ]
1: Ground
2: P or G
=f(Imed,Imax)
IA
COMP |Imedium|/|Imax|<2/3
IB
IC
Imax |Imedium|/|Imax|>2/3
Imedium
COMP
COMP
COMP
BUOC: IN>
triggered
304 753
If a general starting condition is present, then the decisions of the following systems are
signaled:
DIST: General
starting
[ 036 240 ] DIST: Starting
I>> A
[ 040 064 ]
DIST: IA>>
triggered DIST: Starting
303 511
I>> B
[ 040 065 ]
DIST: IB>>
triggered DIST: Starting
303 512 I>> C
[ 040 097 ]
DIST: IC>>
triggered
303 513
DIST: Starting
U< A
[ 040 067 ]
DIST: VA<
triggered DIST: Starting
303 517 U< B
[ 040 075 ]
DIST: VB<
triggered DIST: Starting
303 518 U< C
[ 040 096 ]
DIST: VC<
triggered
303 519
DIST: Starting
Z< A
[ 040 070 ]
DIST: ZA< start.
triggered DIST: Starting
303 526
Z< B
[ 040 071 ]
DIST: ZB< start.
triggered
303 527
DIST: Starting
Z< C
[ 040 072 ]
DIST: ZC< start.
triggered DIST: Starting
303 528
Z<
[ 036 241 ]
49Z6432 A_EN
The P43x selects a measuring loop based on the phase-selective starting decision and
the phase preference selected. The fault impedance (short-circuit impedance) and the
fault direction are determined from the voltage and current values collected from these
measuring loops.
For three-phase starting signals with or without ground the minimum voltage value and
the associated phase-to-phase current are selected from the phase-to-phase voltages
as measured values. In case of a two-phase to ground fault detection the set phase
preference is decisive for the selection of the measured values.
Only the fundamental of the selected measured voltage is evaluated. If stabilization for
capacitive voltage transformers (CVT stabilization) has been enabled, the device checks
to determine whether the second harmonic exceeds the 0.01 Vnom threshold. If so, a
special filter designed specifically for CVTs is activated.
Phase Phase to Phase to C before A before A before C before B before A before C before B before
Priority Phase Ground A, B before C, B before A, B, B, C,
Loop Loop C, A,
Vmin Acyclic Cyclic Acyclic Cyclic Acyclic Acyclic Acyclic Acyclic
A, B, C, G IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin)
1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin
A, B, C IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin) IPP(Vmin)
1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin 1VPPmin
A, B, G IA-B IP-kG(Vmin) IA-kG IA-kG IA-kG IB-kG IB-kG IA-kG IB-kG IB-kG
1VA-B VPGmin 1VA-G 1VA-G 1VA-G 1VB-G 1VB-G 1VA-G 1VB-G 1VB-G
A, C, G IC-A IP-kG(Vmin) IC-kG IC-kG IA-kG IA-kG IA-kG IA-kG IC-kG IC-kG
1VC-A VPGmin 1VC-G 1VC-G 1VA-G 1VA-G 1VA-G 1VA-G 1VC-G 1VC-G
B, C, G IB-C IP-kG(Vmin) IC-kG IB-kG IC-kG IC-kG IB-kG IB-kG IC-kG IB-kG
1VB-C VPGmin 1VC-G 1VB-G 1VC-G 1VC-G 1VB-G 1VB-G 1VC-G 1VB-G
A, B IA-B IA-B IA-B IA-B IA-B IA-B IA-B IA-B IA-B IA-B
1VA-B 1VA-B 1VA-B 1VA-B 1VA-B 1VA-B 1VA-B 1VA-B 1VA-B 1VA-B
A, C IC-A IC-A IC-A IC-A IC-A IC-A IC-A IC-A IC-A IC-A
1VC-A 1VC-A 1VC-A 1VC-A 1VC-A 1VC-A 1VC-A 1VC-A 1VC-A 1VC-A
B, C IB-C IB-C IB-C IB-C IB-C IB-C IB-C IB-C IB-C IB-C
1VB-C 1VB-C 1VB-C 1VB-C 1VB-C 1VB-C 1VB-C 1VB-C 1VB-C 1VB-C
A, G IA-kG IA-kG IA-kG IA-kG IA-kG IA-kG IA-kG IA-kG IA-kG IA-kG
1VA-G 1VA-G 1VA-G 1VA-G 1VA-G 1VA-G 1VA-G 1VA-G 1VA-G 1VA-G
B, G IB-kG IB-kG IB-kG IB-kG IB-kG IB-kG IB-kG IB-kG IB-kG IB-kG
1VB-G 1VB-G 1VB-G 1VB-G 1VB-G 1VB-G 1VB-G 1VB-G 1VB-G 1VB-G
C, G IC-kG IC-kG IC-kG IC-kG IC-kG IC-kG IC-kG IC-kG IC-kG IC-kG
1VC-G 1VC-G 1VC-G 1VC-G 1VC-G 1VC-G 1VC-G 1VC-G 1VC-G 1VC-G
49Z6439 A_EN
The P43x determines the fault impedance and the fault direction on the basis of the
selected measured values. A voltage memory is available so that measurement will
function correctly, even with very low fault voltages.
Voltage memory
Voltage VA-B is the reference voltage for the voltage memory. If the voltage exceeds the
fixed value of 0.65 Vnom and there is no starting of the distance protection function, then
the voltage memory will be synchronized. Synchronization requires approximately
300 ms. Then a check is carried out to determine whether the frequency satisfies the
following condition:
If the condition is satisfied, the voltage memory is enabled. The frequency condition is
checked cyclically. As soon as the frequency condition is no longer met, the enable is
canceled.
If the magnitude of the reference voltage drops below 0.65 Vnom or if a starting of the
distance protection function occurs, synchronization of the voltage memory will be
terminated. The voltage memory is then free-running and remains enabled for 2 s.
DIST: I>>
triggered
303 597
f/fnom = f
+
R 0.95fnom<f<1.05fnom
1 DIST: Voltage
S1 1 memory enabled
303 549
300ms
R1
1 DIST: tVmemory
2s running
[ 040 034 ]
C C C
49Z6433 A_EN
Angle determination
When general starting of distance protection occurs, the angles ϕF and ϕS are
determined. Angle ϕF is the fault angle that is determined using the selected measuring
voltage Vmeas and the selected measuring current Imeas. Angle ϕS is determined on the
basis of the voltage stored in memory and the selected measuring current Imeas.
Since the frequency of the stored voltage can differ from the nominal frequency, a phase
correction must be made. This correction is determined by the frequency deviation and
the time that has elapsed since synchronization was terminated. Furthermore, an angle
correction based on the selected measuring loop and the setting at
M A I N : P h a s e s e q u e n c e is required. The resulting angle, ϕX, is used for further
processing.
For distance and directional measurement, the following angles are used – as a function
of the magnitude of the selected measuring voltage and the fault duration:
Fault angle ϕF
Angle ϕX
Set angle α
Enabled ϕX ϕX
Not enabled ϕF α
A decision is made for the forward direction if the angle selected for direction
determination is in the range -45° < ϕ < +135°. In the case of angles outside this range,
a decision is made for the backward (reverse) direction.
DIST: Voltage
memory enabled
303 549
DIST: General
starting
[ 036 240 ]
< 0.002 Vnom DIST: Forw. w/o
measurem.
[ 038 044 ]
DIST: Direct.
using Vmeas
[ 038 045 ]
DIST: Vmeas
303 546
DIST: Oper.val.
Vmemory PSx
[ * ]
DIST: Direct.
using memory
[ 038 047 ]
1
2
3
DIST: 1
303 552
DIST: F 2
303 550
DIST: Fault
* Parameter DIST: Oper.val.
Vmemory PSx 1 ... 3 C
135° < N < 315°
backward / BS
N [ 036 019 ]
set 1 010 109
set 2 010 116
set 3 010 117
set 4 011 118
49Z6435 A_EN
DIST: Voltage
memory enabled
303 549
DIST: General
starting
[ 036 240 ]
DIST: Vmeas
303 546
DIST: Oper.val.
Vmemory PSx
[ * ]
3
1
4
2
1 ... 4 3
1 ... 3 DIST: Z
303 553
Distance measurement
One of the following types of characteristics may be selected for distance measurement
by way of the setting at D I S T : C h a r a c t e r i s t i c :
Circle
Polygon
Circle characteristic
The fault impedance value ZF is determined using the selected measuring quantities
Vmeas and I meas. If the setting ‘Arc compensation: yes’ has been chosen, then a
correction to the measured fault impedance is calculated for angles ϕZ in the range of
−45 ° < ϕ Z < α or 135 ° < ϕ Z < ( α + 180 ° ) as follows:
ZF
Z F ,corr =
1 + sin δ
The following relation applies in the range 135 ° < ϕ Z < ( α + 180 ° ) : δ = α − ϕ Z + 180 °
In the R-X diagram, the characteristic shown in Figure 3-132 is obtained. If the
characteristic were to be measured with sine variables for the setting
‘Arc compensation: yes’, the dot-dash line would be obtained.
3-132 P43x impedance and direction characteristic for the ‘Circle’ setting
n = 1 to 6
α = 60°
Dot-dash line: with arc compensation
Dashed line: kze = 1.2 (adjustable in Zone 1 only)
The calculated impedance |Zmeas| is compared with the set impedance in the six
impedance zones. If the measured impedance is smaller than or equal to the set
impedance, then a distance decision is made for the corresponding zone(s).
DIST: Zn (circle)
PSx
[ * ]
DIST: n (circle)
PSx DIST:
[ * ] 303 552
In addition to the settings described above, the zone extension factors kze for high-speed
reclosure (HSR) and time-delay reclosure (TDR) can also be set separately for phase-to-
ground (PG) and phase-to-phase (PP) loops for impedance zone 1. The impedances
modified by zone extension factor kze are calculated as follows:
Z1,kze = k ze ⋅ Z1
The increase in reach by zone extension factor kze HSR is controlled by the following:
Protective signaling (P S I G : Z 1 e x t e n d e d )
Internal auto-reclosing control, if protective signaling is not ready or – irrespective of
the readiness of protective signaling – during the reclose command.
Switch on to fault protection (S O T F : Z 1 e x t e n d e d )
An external signal (D I S T : Z o n e e x t e n s i o n E X T ).
The impedance characteristic is extended by zone extension factor kze TDR if a time-
delay reclosure is carried out by internal auto-reclosing control.
Polygon (quadrilateral)
characteristic
The ZF fault impedance value is determined using the selected measuring quantities:
Vmeas and I meas. By multiplying this value by the cosine or sine of the angle selected for
distance measurement, ϕZ, we then calculate the fault resistance RF or fault
reactance XF.
The calculated quantities, RF and XF, are compared with the reference quantities, Rref
and Xref, of the four impedance zones. The reference quantities are determined using
the settings for determining the impedance zone(s). If both quantities lie within the set
impedance zone(s), then a distance decision is made for the corresponding zone(s).
Reactance X
Resistance R, separately for phase-to-ground and phase-to-phase loops
Angle α
Angle σ
Using these settings in the R-X diagram we obtain the characteristic shown in
Figure 3-136.
3-136 P43x impedance and directional characteristics for the ‘Polygon’ setting
Example for: Xn = 6.5 Ω
Rn = 2.0 Ω
αn = 70°
σn = -20°
n = 1 to 4
Dashed line: kze = 1.2 (adjustable in Zone 1 only)
The resistances for phase-to-ground and phase-to-phase loops can be set separately for
each zone. The different impedances are therefore compared with different impedance
characteristics.
In addition to the settings described above, the kze zone extension factors for high-speed
reclosure (HSR) and time-delay reclosure (TDR) can also be set separately for phase-to-
ground (PG) and phase-to-phase (PP) loops for impedance zone 1.
R1,kze = k ze ⋅ R1
X1,kze = k ze ⋅ X1
The increase in reach by zone extension factor kze HSR is controlled by the following:
Protective signaling (P S I G : Z 1 e x t e n d e d )
Internal auto-reclosing control, if protective signaling is not ready or – irrespective of
the readiness of protective signaling – during the reclose command.
Switch on to fault protection (S O T F : Z 1 e x t e n d e d )
An external signal (D I S T : Z o n e e x t e n s i o n E X T ).
The impedance characteristic is extended by zone extension factor kze TDR if a time-
delay reclosure is carried out by internal auto-reclosing control.
A maximum of six impedance zones and eight timer stages are available for impedance
time grading. All impedance zones can be operated in a forward direction, backward
(reverse) direction, or non-directionally. Distance-independent timer stage t7 can also
operate forward-directionally, backward- (reverse-) directionally, or non-directionally.
Timer stage t8 operates independently of distance and direction. All timer stages are
started by the general starting of distance protection.
If protective signaling is not ready but ARC is active, then a trip is issued in extended
zone 1 once the ARC tripping time has elapsed, whereas with standard reach (non-
extended zone) it is issued after timer stage t1 of distance protection has elapsed or
after the HSR tripping time of ARC has elapsed. (The shortest time setting is dominant.)
DIST: t1
PSx
[ * ]
t1,ze 0
DIST: Zone
extension HSR
[ 036 103 ]
DIST: Zone
extension TDR DIST: Timer st.1
[ 038 022 ] elapsed
303 614
DIST: t1,ze
ARC: Trip time elapsed
elapsed [ 035 079 ]
303 003
* Parameter DIST: t1
PSx
DIST: t1,ze
PSx
set 1 012 028 026 025
set 2 012 078 027 025
set 3 013 028 028 025
set 4 013 078 029 025
49Z6437 A_EN
If protective signaling is not ready but ARC is active, then the following occurs in the
‘1-/3-pole’ and ‘3-pole’ ARC modes: in extended zone 1 a trip is issued once the ARC
tripping time has elapsed, whereas with standard reach (non-extended zone) it is issued
after timer stage t1 of distance protection has elapsed or after the HSR tripping time of
ARC has elapsed. (The shortest time setting is dominant.) In the ‘1-pole’ ARC mode, a
three-pole trip occurs in zone 1 after t1 has elapsed and in extended zone 1 after timer
stage t1,ze of distance protection has elapsed. A single-pole trip is issued in extended
zone 1 once the ARC tripping time has elapsed, whereas with standard reach (non-
extended zone) it is issued after timer stage t1 of distance protection has elapsed or
after the HSR tripping time of ARC has elapsed. (The shortest time setting prevails.)
DIST: t1
PSx
[ * ]
DIST: t1,ze
MAIN: Meas.r.extd. C PSx
ext./RC [ * ]
306 002
t1,Ü 0
2: 1-/3-pole
3: 3-pole
DIST: Zone
extension HSR
[ 036 103 ]
DIST: Zone DIST: Timer st.
extension TDR 1 elapsed
303 614
[ 038 022 ]
45Z6330A_EN
DIST: t2
PSx
[ * ]
DIST: General t 0
starting DIST: t2 elapsed
[ 036 240 ] [ 036 027 ]
DIST: t3
PSx
DIST: Op. mode [ * ]
zone 4 PSx
[ * ]
t 0 DIST: t3 elapsed
[ 036 028 ]
1
2
DIST: t4
3 C PSx
[ * ]
4
5 t 0 DIST: t4 elapsed
[ 036 029 ]
6
1: Normal
2: 1p:Z1/t1(3p)3p:Z1/t4 DIST: t5
PSx
[ * ]
3: Section cable - line
4: Section line - cable t 0 DIST: t5 elapsed
5: Comp.bundle cond.eff [ 036 030 ]
6: 1p:Z1/t1, 3p:Z1/t4
DIST: t6
PSx
[ * ]
t 0 DIST: t6 elapsed
[ 036 031 ]
DIST: t7
PSx
[ * ]
t 0 DIST: t7 elapsed
[ 037 127 ]
DIST: t8
PSx
[ * ]
t 0 DIST: t8 elapsed
[ 037 128 ]
Normal
1p:Z1/t1(3p), 3p:Z1/t4
Section cable - line
Section line - cable
Compensation for bundle conductor effects
1p:Z1/t1, 3p:Z1/t4
Mode: 'Normal'
A trip signal is issued in zones 1 to 6 when the following criteria are satisfied
simultaneously:
If several timer stages and directions are set to the same values, a distance trip occurs
in the zone having the highest number.
A trip signal is issued in zone 7 if the following conditions are satisfied simultaneously:
After timer stage t8 has elapsed, a trip signal for zone 8 is issued.
With the P435 distance trips from zones 1 to 7 that are used to form the trip command
may be blocked by the power swing blocking function.
Mode:
'1p:Z1/t1(3p), 3p:Z1/t4'
With this setting, timer stage t4 is assigned to impedance zone 1. All other settings for
impedance zone 4 are irrelevant in this operating mode and thus inactive.
For single-pole starting, a zone 1 trip signal will be issued once timer stage t1 has
elapsed; for multi-pole starting, it is issued once t4 has elapsed.
3-146 Distance protection trip signals, zone 4 operating mode: '1p:Z1/t1(3p), 3p:Z1/t4'
Mode:
'Section cable – line'
This setting is selected for a mixed cable-line section provided that auto-reclosing will
occur only when there is a fault in the line area. For this mode, the cable must form the
front part of the transmission section and the line the rear part.
Timer stage t1 and direction setting N1 are assigned to impedance zones 1 and 4.
Timer stage t4 setting and direction setting N4 are inactive.
A zone 1 or zone 4 trip signal is issued if the following conditions are satisfied:
In order for the P43x to be able to determine the section in which the fault is located,
impedance zone 1 must be set to the total length of the power transmission section (e.g.
cable plus line) and impedance zone 4 to the cable length. If a distance trip for zones 1
and 4 occurs after t1 has elapsed, the auto-reclosing function will be blocked because
the fault lies in the cable section.
3-148 Distance protection trip signals, zone 4 operating mode: 'Section cable – line'
Mode:
'Section line – cable'
This setting is selected for a mixed line-cable section provided that auto-reclosing will
only occur when there is a fault in the line area. For this mode, the line must form the
front part of the transmission section and the cable the rear part.
Timer stage t1 and direction setting N1 are assigned to impedance zones 1 and 4.
Timer stage t4 setting and direction setting N4 are inactive.
The 'Distance trip Zone 1' or 'Distance trip Zone 4' decision is reached if the following
conditions are satisfied:
In order for the P43x to determine the section in which the fault is located, impedance
zone 1 must be set to the total length of the transmission section and impedance zone 4
for the length of the line. If a distance trip occurs only in after t1 has elapsed, the auto-
reclosing function will be blocked because the fault lies in the cable section.
3-150 Distance protection trip signals, zone 4 operating mode: 'Section line – cable'
Timer stage t2 and direction setting N2 are assigned to impedance zones 2 and 4.
Timer stage t4 setting and direction setting N4 are inactive.
The settings for impedance zone 2 need to be made without regard to the bundle
conductor effect. The setting values for impedance zone 4, on the other hand, need to
take the bundle conductor effect into account.
The P43x checks 30 ms after distance protection has started to determine whether the
following conditions are satisfied:
This information is then stored. The zone 4 trip signal is issued if the following
conditions are satisfied:
DIST: N2,bw
303 573
DIST: Trip zone 1
DIST: Dist.decision zone 4 303 584
303 583
DIST: t2 elapsed
[ 036 027 ]
DIST: N1,bw
303 571
DIST: N3,bw
303 575
DIST: N5,bw
303 579
DIST: N6,bw
303 615
DIST: N7,fw
303 618
DIST: N7,bw
303 617
3-152 Distance protection trip signals, zone 4 operating mode: 'Compensation for bundle conductor effects''
Mode:
'1p:Z1/t1, 3p:Z1/t4'
With this setting, timer stage t4 is assigned to impedance zone 1. All other settings for
impedance zone 4 are irrelevant in this operating mode and thus inactive.
For single-pole starting, a distance trip signal is issued in zone 1 once timer stage t1 has
elapsed; for multi-pole starting, it is issued once t4 has elapsed.
3-154 Distance protection trip signals, zone 4 operating mode: '1p:Z1/t1, 3p:Z1/t4'
Trip signal
036 009
45Z5273B_EN
3-156 D I S T : I m p e d a n c e i n zo n e 6 signal
For zone 1 the user can specify whether the distance trip in zone 1 shall be single-pole
or three-pole. This choice is separately available both for single-pole starting and for
two-pole starting without ground.
In the case of three-pole starting with or without ground or two-pole starting with ground,
there is always a three-pole distance trip in zone 1. In the case of two-pole starting
without ground - and selection of a single-pole trip for this type of starting - the zone 1
distance trip will be issued in the leading or trailing phase, depending on the setting.
This is based on the setting at M A I N : R o t a r y f i e l d . A three-pole trip can be forced
via an appropriately configured binary signal input.
If the P435 has reached a trip decision in zone 1, then a change in starting from two-pole
without ground to single-pole or two-pole with ground is ignored for 100 ms - as long as
the same phases that were involved in starting before the change are still involved.
If starting occurs in the third, previously unaffected phase, after the change in starting,
then a three-pole trip transfer occurs instantaneously.
3: 3-pole 3
1: 1-pole 1
DIST: 1-pole
starting
303 533
DIST: Trip
DIST: Starting A enable zone 1
303 529 303 593
DIST: Starting B
303 530
DIST: Starting N1
303 535
DIST: Trip
enable zone 1,B
303 591
DIST: Trip
enable zone 1,C
303 592
DIST: Trip
zone 1 DIST: Signal
303 584 block start.G
303 594
DIST: Trip
zone 1,ze
303 595
DIST: General
starting
[ 036 240 ]
DIST: t4 elapsed
[ 036 029 ]
MAIN: Blocking 1p
trip EXT Parameter DIST: Trip zone 1 DIST: Trip zone 1 DIST: Op. mode
[ 041 078 ] PG PSx PP PSx zone 4 PSx
set 1 011 050 011 054 012 000
set 2 011 051 011 055 012 050
set 3 011 052 011 056 013 000
set 4 011 053 011 057 013 050 45Z6331B_EN
The power swing blocking (PSB) function offers these options should a power swing
occur in the power system:
The user can block distance trip signals in selected distance zones. This will prevent
unwanted tripping by apparent low impedances during a power swing.
AND / OR
An asynchronous trip signal can be generated so as to end a power swing, by
initiation of islanding/system splitting..
Disabling or enabling
power swing blocking
The power swing blocking function can be disabled or enabled using a setting
parameter.
Furthermore the PSB function can be enabled individually in each parameter subset at
PSB: Enable PSx.
When the monitoring of the voltage-measuring circuit is triggered the PSB function will
be blocked.
PSB: General
enable USER
[ 014 050 ]
1
0: No
1: Yes
PSB: Enable
PSx
[ * ]
PSB: Enabled
0 [ 040 095 ]
1
PSB: Ready
0: No 304 859
1: Yes
MAIN: Protection
active * Parameter PSB: Enable
306 001
PSx
set 1 015 090
MCMON: Meas. set 2 015 091
circ. V faulty set 3 015 092
[ 038 023 ]
set 4 015 093
47Z11CBB_EN
Measurement
The P43x continuously measures the positive-sequence impedance and the apparent
power of the positive-sequence system. Because of this measurement in the positive-
sequence system, the protection function is still available during a single-pole HSR.
Blocking of selected zones of the distance protection or a power swing trip occurs only
when the measured positive-sequence impedance lies within the settable power swing
polygon.
PSB
PSB
¼AN PSB
¼BN ¼pos
¼CN
ºA
pos PSB: Z within
ºB ºpos polygon
ºC
42Z50CCA.E
3-159 Measurement
Zpos (t)
42Z50CFA.E
S pos ,2 − S pos ,1
∆Spos =
S pos ,2
If the apparent impedance lies within the swing polygon and the deviation is greater than
the value set at P S B : O p e r a t e v a l u e then a blocking of the selected distance
zones will be issued after an associated time delay, set at P S B : O p e r a t e d e l a y ,
has elapsed. This blocking signal will be prolonged by the value set at
PSP: Release delay.
In order to avoid problems arising from mutual interference the PSB function is blocked
when a starting signal is issued by zone Z1 or the overreach zone Z1,ze.
The maximum duration of this blocking has a time limit. This time limit can be set.
The PSB function is unblocked without time delay if the following current elements detect
a short circuit during a power swing:
Phase current element for measurement of symmetrical 3-pole faults:
IP > PSB: IP>
Negative-sequence current element for sensitive measurement of 2-pole faults:
Ineg > (0.1 Inom + PSB: Ineg> * IP,max)
Residual current element for sensitive measurement of ground faults:
IN > (0.1 Inom + PSB: IN> * IP,max)
The distance zones to be blocked are set at P S B : F c t . a s s i g n . b l o c k . These
zones may be selected: Zx (x = 1...8) and Z1,ze
In the ∆Z operating mode, the rate of change of the resistance component of positive-
sequence impedance, when entering the power swing polygon, is measured and
interpreted. The function decides on power swing only if the rate of change is smaller
than the ∆Rx/∆T set threshold and subsequently blocks all selected zones.
A power swing decision once made is stored until any of the following conditions is met:
The positive-sequence impedance locus exits the power swing polygon.
The set maximum blocking time has elapsed.
One of the PSB current stages has started.
The available time delay of the blocking effect may be used to holdup distance protection
blocking for a short time. This may become necessary with series-compensated lines on
which, in some cases, a relatively slow swing subsidence of the measured short circuit
impedance is observed.
With the ∆Z operating mode general blocking of the power swing function after the trip
decision by the overreach zone is no longer necessary. Only blocking by the trip
decision from zone 1 is available.
PSB: Ready
304 859
PSB: Z within
polygon
[ 036 024 ]
DIST: Trip signal
zone 1
[ 035 072 ]
DIST: Trip signal
Z1,ze
[ 035 074 ]
PSB: Operate PSB: Operate PSB: Release
value delay delay
[ 014 054 ] [ 014 052 ] [ 014 053 ]
PSB: Max.
blocking time
[ 014 055 ]
PSB: IP>
[ 014 058 ]
PSB: IP>
IA triggered
[ 036 012 ]
IB PSB: Ineg>
IC [ 014 057 ]
PSB: Ineg>
Ineg triggered
[ 036 011 ]
PSB: IN>
[ 014 056 ]
IN PSB: IN>
triggered
[ 036 010 ]
PSB: Blocking PSB: Blocking
init. EXT initiated
[ 036 069 ] [ 036 032 ]
PSB: Block.
sel. zone
304 862
Selected zone
45Z63CDA_EN
Out-of-step tripping
A power swing trip may become necessary when a power swing with low damping has to
be terminated by deliberately splitting system sections. For such a procedure the device
has two independent methods available:
The ∆Spos apparent power change exceeds the threshold set to a high value at
P S B : O p e r a t e v a l u e , t r i p for the duration set at
P S B : O p e r a t e d e l a y , t r i p and the positive-sequence impedance lies within
the power swing polygon.
This criterion may be applied with high swing frequencies (and therefore large
changes in the apparent power). The system split will then occur very early so as to
avoid system loads from high currents during the first power swing cycle.
Every 40 ms the P43x determines the apparent power change as referred to the
actual apparent power.
Spos,2 − Spos,1
∆Spos =
Spos,2
The positive-sequence impedance leaves the power swing polygon on the opposite
side (see impedance trajectory 2 in figure 3-160).
The sign for the positive-sequence impedance’s real component is stored when the
measured positive-sequence impedance locus enters the power swing polygon.
This stored sign is compared with the sign when exiting the power swing polygon.
Should the signs differ, a trip signal is issued immediately after exiting the power
swing polygon.
When this criterion is applied an instable power swing will be determined, regardless
of swing frequencies.
PSB: Ready
42Z50CEA.E
Counters
The following counters for stable power swing and instable power swing are available:
Signaling
An additional signal is issued when set counter values are reached, and such signals
may also be used for tripping.
These signals will remain present until the associated counter is reset (via
PSB: Reset counters).
These signals can also be configured to any output relay, LED indicator and signaling
outputs (e.g. InterMiCOM, GOOSE, GSSE). They are stored in the fault recording and
(depending on the extent of the configuration) (spontaneously) signaled via the process
control interface (COMM1).
In addition these signals may be configured to the trip commands so as, for example, to
cause a delayed out-of-step trip if the power swing is not dampened within an acceptable
time.
The P43x monitors the phase currents and voltages for balance during healthy system
operation. If either unbalance or the lack of measuring voltage is detected, action is
taken to prevent the unit from malfunctioning.
1) only P435
45Z6340A_EN
Ineg =
1
3
2
(
IA + a ⋅ IB + a ⋅ IC ) I
neg
=
1
3
( 2
IA + a ⋅ IB + a ⋅ IC )
0
a = e j120
0
2
a = e j240
This value is divided by the maximum phase current ⏐Imax⏐ and compared with the set
threshold operate value. If the set operate value is exceeded, a monitoring signal is
issued once the operate delay +300 ms have elapsed.
Phase-to-phase voltages are monitored for voltages that fall below the default
threshold of 0.4 ⋅ Vnom . This monitoring function is enabled when the current exceeds
0.05 ⋅ Inom in one phase.
V neg =
1
3
( 2
⋅ V A −G + a ⋅ V B − G + a ⋅ V C −G )
Phase sequence A-C-B (alternative terminology: Anticlockwise rotating field):
V neg =
1
3
( 2
⋅ V A −G + a ⋅ V B − G + a ⋅ V C −G )
0
a = e j120
0
a 2 = e j 240
This value is compared with the default threshold operate value 0.2 ⋅ Vnom / 3 . If the
threshold operate value is exceeded, a monitoring signal is issued after the operate
delay has elapsed.
If one of the monitoring functions described above operates, then distance protection is
blocked, and the device switches to backup overcurrent time protection – provided the
appropriate setting has been selected.
MAIN: Rotary
field
[ 010 049 ]
MCMON: Enabled
[ 040 094 ]
VA-G
VB-G >0.2*Vnom/ 3
C
VC-G
|Vneg|
MCMON: Operate
delay
[ 017 011 ] SFMON: Vneg>
triggered
[ 098 014 ]
t 0
MCMON: Vneg>
triggered
[ 041 079 ]
DIST: General t 0
starting S1 1 SFMON: Under-
[ 036 240 ] voltage
R1 [ 098 009 ]
MCMON: Under-
voltage
BUOC: Starting [ 038 038 ]
[ 036 013 ]
1: Vneg
2: Vneg with
curr. enab
3: Vneg w.CB
cont.enab.
MAIN: CB closed
sig. EXT
[ 036 051 ]
>0.05*Inom
C
IA
IB
IC
<0.4*Vnom
C
>0.65*Vnom
C
0 5s MCMON: Meas.
voltage o.k.
[ 038 048 ]
45Z6341A_EN
The fuse failure monitoring function must distinguish between a short circuit in the three-
phase current system and a lack of measuring voltage due to a short circuit or open
circuit (broken wire) in the secondary circuit of the voltage transformer.
A short circuit exists in the three-phase current system being monitored, if one of the
following conditions is satisfied:
The P43x uses different criteria to detect single- or two-phase faults or three-phase
faults in the secondary circuit of the voltage transformer.
A three-phase fault is present in the secondary circuit of the voltage transformer if the
following conditions are satisfied simultaneously:
The base point release for the distance protection has operated in at least one
phase.
The positive-sequence voltage has fallen below the set threshold Vpos, FF.
The positive-sequence current may only vary less than -10% or +5% within 50 ms
after the positive-sequence voltage has fallen below the set threshold Vpos<, FF.
If the above conditions are satisfied, a memory is set; it is reset when the positive-
sequence voltage exceeds the fixed threshold of 0.5 Vnom and the negative-sequence
voltage falls below the set threshold Vneg<, FF.
If the memory is set and the base point release for the distance protection has operated
in at least one phase, or if the negative-sequence voltage set threshold is exceeded, the
P43x determines that the secondary circuit of the voltage transformer is faulty. In this
case distance protection is blocked, and the device switches to backup overcurrent time
protection – provided that the appropriate setting has been selected.
MCMON: FF, V
enabled USER
[ 014 009 ]
1
0: No
1: Yes
DIST: IA>(Ibl)
trigg.
303 598
DIST: IB>(Ibl)
trigg.
303 599
DIST: IC>(Ibl)
trigg.
303 600
DIST: General 0 30 ms
starting
[ 036 240 ]
IA I/ t > 5%
IB I/ t > 5%
IC I/ t > 5%
MAIN: Rotary
field
[ 010 049 ]
MCMON: Ineg>, FF
[ 031 057 ]
MCMON: Set FF, V
304 650
|Ineg|
MCMON: Vneg>, FF
[ 031 056 ]
VA-G
|Vneg| MCMON: Vneg>, FF
VB-G trigg.
304 651
VC-G
MCMON: Vpos<, FF
[ 031 053 ]
|Vpos| 1 50 ms
45Z63FKA_EN
Fuse Failure monitoring must be able to discriminate between a short circuit in the three-
phase network being monitored and a reference voltage missing because of a short
circuit or an open circuit in the secondary circuits of the reference voltage.
A short circuit or an open circuit in the secondary circuits of the reference voltage is
present when the following conditions are met:
If the ‘Low impedance-grounding’ setting has been selected for the neutral point
treatment, ground current IN is also monitored by the settable trigger IN>, in addition to
the phase currents. If the ground current exceeds the set value, timer stage tIN> is
started. After the set time period has elapsed, a trip signal is issued. Inrush stabilization
blocks the ground starting of BUOC protection.
The setting for the operating mode controls whether the BUOC protection function will
trigger an auto-reclosure (ARC). If auto-reclosure is desired, timer stages tI> and tIN>
will be blocked when the ARC function is ready. With phase starting, the trip signal will
then be issued instantaneously; with ground starting, it will be issued after an 80 s delay.
Timer stage tIN> is also blocked by phase starting or while the ARC hold time is elapsing.
MCMON: Meas.
circ. V faulty
[ 038 023 ]
BUOC: General
enable USER
[ 014 011 ] SFMON: BUOC not
active
[ 098 002 ]
0
BUOC: Enabled
1 [ 040 093 ]
0: no
1: yes
BUOC: Operating
mode
[ 014 000 ] SFMON: BUOC
active w/o ARC
[ 098 003 ]
1
SFMON: BUOC
2 active with ARC
[ 098 004 ]
3
BUOC: Active
1: Without ARC [ 037 021 ]
2: With ARC, 3p HSR
3: With ARC, 1/3p. HSR
AWE: Ready
[ 004 068 ]
BUOC: tI>
GRUND: Rush C PSx
restr. A trig. [ * ]
[ 041 027 ]
GRUND: Rush
restr. B trig.
[ 041 028 ]
GRUND: Rush BUOC: Trip
restr. C trig. signal
[ 041 029 ] [ 036 014 ]
BUOC: I>
C PSx
MAIN: Protection [ * ] BUOC: IA>
active triggered
306 001
304 750
IA
BUOC: IB>
IB triggered
304 751
IC BUOC: IC>
triggered
304 752
BUOC: tIN>
C PSx
ARC: Dead time [ * ]
running
[ 037 002 ]
GRUND: Neutr.pt.
treat. PSx BUOC: IN>
[ * ] C PSx C
[ * ]
1: Low-imped.
grounding
BUOC: Starting
[ 036 013 ]
BUOC: SN
304 757
BUOC: IN>
triggered
304 753
To ensure rapid clearing with manual closing, the manual close signal must be applied
not only to the circuit breaker but also to the P43x. The M A I N : M a n u a l c l o s e
E X T signal must be configured separately to a binary signal input (and triggered during
the closing action) even if the close command is issued via the P43x. The manual close
signal is converted to an internal pulse, of settable duration. The pulse time can be set.
The user may specify whether the following shall occur during operation of this timer
stage:
The reach of the first impedance zone of the distance protection function is normally set
for values less than 100%. Protective signaling is used to extend protection to 100% of
the line section. This is achieved by logical linking of the signals that are transmitted by
the remote station’s protection device.
Disabling or enabling
protective signaling
The function can be disabled or enabled using setting parameters or through binary
signal inputs.
Readiness of protective
signaling
In order for protective signaling (PSIG) to function, the following requirements must be
satisfied:
It must be enabled.
There must be no external block.
There must be no transmission fault.
PSIG: Operating
mode PSx
[ * ]
2: PUTT
8: Direction
comparison
MAIN: Meas.r.extd.
ext./RC
306 002
PSIG: Trip
time elapsed
PSIG: Ready t 0 305 150
[ 037 027 ]
DIST: General
starting
[ 036 240 ]
49Z6442 A_EN
Three-ended line
application
In general the P S I G : R e c e i v e ( A ) E X T or P S I G : R e c e i v e ( B ) E X T signals
are simply used in an 'OR' combination.
In case a permissive scheme is applied to 3-ended lines, the permissive signals from
both remote end units must be received, and these two signals have then to be used in
an 'AND' combination.
Forming such an 'AND' combination externally would mean having to accept additional
delays and loss of data with respect to the transmitted signals. In order to have this
operation available and overcome the shortcomings of the usual single channel data
transmission links, the P43x features the possibility to use these two signals directly by
setting parameters P S I G : 3 e n d e d l i n e p r o t P S x to 'Yes'.
These two signals are further processed as shown in the figure below to create a new
signal (P S I G : R e c e i v e ) which is used in the various PSIG operating modes. (This
new signal replaces the P S I G : R e c e i v e E X T signal previously available in
software versions up to -611.)
If 3-ended line protection is enabled then both receive signals are linked in an 'AND'
gate, otherwise they are linked in an 'OR' gate. The latter permits the use of either the A
or the B signal, or even both signals in case of redundant signaling channels, on
2-ended lines.
PSIG: 3ended
line prot PSx
[ * ]
0
1
0: No
1: Yes
&
&
PSIG: Receive (B)
EXT
[ 006 037 ]
Parameter PSIG: 3ended
line prot PSx
set 1 006 039
set 2 006 046
set 3 006 047
set 4 006 048 47Z12
04B_EN
Monitoring the
transmission section
A transmission fault leads to a blocking of the protective signaling function (see
Figure 3-175). If protective signaling is being carried out via a signal transmission or
communication device, the device's fault signal can be connected. With protective
signaling over pilot wires or with the operating mode set to 'reverse interlocking' the
internal monitoring function will detect a fault in the transmission channel.
PSIG: Operating
mode PSx
[ * ] PSIG: Telecom.
6: DC loop faulty
operat. mode [ 036 060 ]
PSIG: Release
t. send PSx SFMON: Telecom.
[ * ] faulty/PSIG
[ 098 006 ]
DIST: General
starting
[ 036 240 ]
PSIG: Telecom.
faulty int.
305 151
PSIG: Telecom.
faulty EXT
[ 004 064 ]
Parameter PSIG: Operating PSIG: Release
mode PSx t. send PSx
set 1 015 000 015 002
set 2 024 000 024 001
set 3 024 060 024 061
set 4 025 020 025 021
45Z6347A_EN
Frequency monitoring
Failure of frequency transmission may be signaled to the P43x via an appropriately
configured binary signal input (P S I G : F r e q . m o n . t r i g . E X T ). If frequency
monitoring is enabled, the P43x – once a time-delay of approximately 20 ms has elapsed
– will generate a receive signal for a duration of 150 ms.
PSIG: Frequency
monit. PSx
[ * ]
0
1
0: No
1: Yes
PSIG: Frequ.
monit. trigg.
PSIG: Receive 20ms 0 305 152
[ 006 036 ] 1
150ms
PSIG: Freq. mon.
trig. EXT
[ 038 080 ]
Parameter PSIG: Frequency
monit. PSx
set 1 015 025
set 2 024 011
set 3 024 071
set 4 025 031 45Z6348A_EN
Transient blocking
In the event of a direction change, protective signaling will be blocked for the time set at
PSIG: tBlock PSx.
DIST: General
starting
[ 036 240 ]
* Parameter PSIG: tBlock
PSx
set 1 015 024
set 2 024 010
set 3 024 070
set 4 025 030
49Z6444 A_EN
Protective signaling
operating modes
Protective signaling can be operated in eight different modes. The following operating
modes require a signal transmission device:
For operation in the modes referred to as ‘DC loop operating mode’ and ‘reverse
interlocking’, pilot wires are required for signal transmission.
Limiting to weak-infeed
logic or echo function
If only the weak-infeed logic or the echo function will be used and no other protective
signaling functions, then this can be implemented by setting the operating mode to
‘Without’.
Direct underreaching
transfer trip
When a distance protection trip zone 1 has occurred, a signal is sent to the remote
station’s protection device. Upon receipt of the signal by the remote station, the remote
station’s circuit breaker is tripped. If transient blocking is operating, then the receive
signal will be ignored.
3-180 P433: PSIG send signal and trip signal by protective signaling in the 'direct underreaching transfer trip' operating mode
DIST: Trip
zone 1,ze
303 595
PSIG: Trip 1
305 155
PSIG: Receive
[ 006 036 ]
PSIG: Trip signal
[ 038 007 ]
PSIG: Frequ.
monit. trigg.
305 152
PSIG: Receive
PSIG: Transient (signal)
blocking [ 037 029 ]
305 154
3-181 P435: PSIG send signal and trip signal by protective signaling in the 'direct underreaching transfer trip' operating mode
PUTT (permissive
underreaching transfer trip)
When a distance protection trip zone 1 has occurred, a signal is sent to the remote
station’s protection device. On receipt of the signal by the remote station, the remote
station’s circuit breaker is subject to permissive underreaching transfer tripping (PUTT)
once the protective signaling tripping time has elapsed. The
D I S T : T r i p z o n e 1 P G P S x and D IST : T r i p z o n e 1 P P P S x settings are
taken into account by the P435. If transient blocking is operating, then the receive signal
will be ignored.
PSIG: Transient
blocking PSIG: Receive
305 154
(signal)
PSIG: Timer [ 037 029 ]
stage elapsed
305 164
MAIN: General
starting
[ 036 000 ]
3-182 P433: PSIG send signal and trip signal by protective signaling in the 'PUTT' operating mode
PSIG: Transient
blocking PSIG: Receive
305 154
(signal)
PSIG: Timer [ 037 029 ]
stage elapsed
305 164
MAIN: General
starting
[ 036 000 ]
3-183 P435: PSIG send signal and trip signal by protective signaling in the 'PUTT' operating mode
Zone extension
When a distance protection trip has occurred in zone 1, a signal is sent to the remote
station’s protection device. Upon receipt of the transmitted signal, the measuring range
of zone 1 in the remote station is increased by the zone extension factor kze HSR.
The response of the protection device in the remote station is determined by the setting
at P S I G : O p e r . m o d e t r i p P S x in the remote station.
'Direction-dependent'
After the protective signaling tripping time has elapsed, tripping occurs if distance
protection has decided in favor of 'forward direction'. The
D I S T : T r i p z o n e 1 P G P S x and D IST : T r i p z o n e 1 P P P S x settings are
taken into account by the P435. If transient blocking is operating, then the receive
signal will be ignored.
'Distance-dependent'
If the fault is located within the extended zone, then the protection device of the
remote station also decides in favor of a trip in zone 1 after the protective signaling
tripping time has elapsed. If transient blocking is operating, then the receive signal
will be ignored.
PSIG: Release
t. send PSx
[ * ]
PSIG: Transient
blocking
305 154
DIST: General
starting
[ 036 240 ]
6: 1p:Z1/t1,
3p:Z1/t4 PSIG: Receive
(signal)
MAIN: General [ 037 029 ]
starting
[ 036 000 ]
2
1
Parameter PSIG: Operating PSIG: Release PSIG: Oper. Mode DIST: Op. mode
mode PSx t. send PSx trip PSx zone 4 PSx
set 1 015 000 015 002 015 107 012 000
set 2 024 000 024 001 015 108 012 050
set 3 024 060 024 061 015 113 013 000
set 4 025 020 025 021 015 114 013 050
43Z6345A_EN
3-185 P433: PSIG send, zone extension, trip and trip enable signals issued by protective signaling in the 'Zone extension' operating mode
[ 006 036 ]
45Z6345A_EN
3-186 P435: PSIG send, zone extension, trip and trip enable signals issued by protective signaling in the 'Zone extension' operating mode
Release (permissive)
scheme
Zone extension in zone 1 of distance protection is a function of the setting at
PSIG: Oper. mode send PSx.
'Direction-dependent'
The measuring range of zone 1 of distance protection is not extended.
'Distance-dependent'
In the idle state, the measuring range of zone 1 in both protection devices is extended
by the zone extension factor kze HSR. The distance protection trip in extended
zone 1 is blocked in both protection devices.
'Direction-dependent'
If the distance protection function detects a fault in the forward direction, the P43x
sends a signal to the remote station.
'Distance-dependent'
If the distance protection function detects a fault within extended zone 1, the P43x
sends a signal to the remote station.
The response of the protection device in the remote station is determined by the setting
at P S I G : O p e r . m o d e t r i p P S x in the remote station.
'Direction-dependent'
After the protective signaling tripping time has elapsed, tripping occurs if distance
protection has decided in favor of 'forward direction'. The
D I S T : T r i p z o n e 1 P G P S x and D IST : T r i p z o n e 1 P P P S x settings are
taken into account by the P435. If transient blocking is operating, then the receive
signal will be ignored.
'Distance-dependent'
The distance protection trip in extended zone 1 is enabled, if there is a receive signal.
If the fault is located within extended zone 1, then the protection device of the remote
station also decides in favor of a trip in zone 1 after the protective signaling tripping
time has elapsed. If transient blocking is operating, then the receive signal will be
ignored.
PSIG: Ready
[ 037 027 ]
PSIG: Send
(signal)
DIST: Fault [ 036 035 ]
forward / LS
[ 036 018 ] PSIG: Send
(transm.relay)
[ 037 024 ]
DIST: Dist.
decision Z1,ze PSIG: Z1
303 563
extended
[ 035 075 ]
PSIG: Receive
[ 006 036 ]
PSIG: Frequ.
monit. trigg.
305 152
PSIG: Transient
blocking PSIG: Receive
305 154
(signal)
MAIN: General [ 037 029 ]
starting
[ 036 000 ]
2
1
Parameter PSIG: Operating PSIG: Release PSIG: Oper. Mode PSIG: Oper. Mode
mode PSx t. send PSx send PSx trip PSx
set 1 015 000 015 002 015 036 015 107
set 2 024 000 024 001 015 037 015 108
set 3 024 060 024 061 015 040 015 113
set 4 025 020 025 021 015 041 015 114
43Z6351A_EN
3-188 P433: PSIG send, zone extension, trip and trip enable signals issued by protective signaling in the 'Release scheme' (permissive)
operating mode
[ 006 036 ]
45Z6351A_EN
3-189 P435: PSIG send, zone extension, trip and trip enable signals issued by protective signaling in the 'Release scheme' (permissive)
operating mode
Blocking scheme
Zone extension in zone 1 of distance protection is a function of the setting at
PSIG: Oper. mode send PSx.
'Direction-dependent'
The measuring range of zone 1 of distance protection is not extended.
'Distance-dependent'
In the idle state, the measuring range of zone 1 in both protection devices is extended
by the zone extension factor kze HSR. The distance protection trip in extended
zone 1 is enabled in both protection devices.
'Direction-dependent'
If distance protection detects a fault in the backward (reverse) direction or – for a
directional change – for the transient blocking time (setting at
P S I G : t B l o c k P S x ), a signal is sent to the remote station.
'Distance-dependent'
If the distance protection function detects a fault within zone 6 and if the measured
direction matches the direction set for zone 6, then the P43x sends a signal to the
remote station. A signal is also sent to the remote station during transient blocking.
The response of the protection device in the remote station is determined by the setting
at P S I G : O p e r . m o d e t r i p P S x in the remote station.
'Direction-dependent'
After the protective signaling tripping time has elapsed, tripping occurs if no receive
signal is present and distance protection has decided in favor of 'forward direction'.
The D I S T : T r i p z o n e 1 P G P S x and D IST : T r i p z o n e 1 P P P S x settings
are taken into account by the P435. If transient blocking is operating, then the
receive signal will be ignored.
'Distance-dependent'
The distance protection trip in extended zone 1 is enabled if there is no receive
signal. If the fault is located within extended zone 1, then the protection device of the
remote station also decides in favor of a trip in zone 1 after the protective signaling
tripping time has elapsed. If transient blocking is operating, then the receive signal
will be ignored.
PSIG: Ready
[ 037 027 ]
PSIG: Send
DIST: Fault (signal)
backward / BS [ 036 035 ]
[ 036 019 ] PSIG: Send
(transm.relay)
PSIG: Transient [ 037 024 ]
blocking
305 154
PSIG: Frequ.
monit. trigg.
305 152
MAIN: General
starting
[ 036 000 ]
1
2
1: Direct.-dependent
2: Dist.-dependent
PSIG: Timer
stage elapsed
305 164
DIST: Fault
forward / LS
[ 036 018 ]
PSIG: Trip
enable
305 157
PSIG: Trip signal
[ 038 007 ]
DIST: Trip signal
Z1,ze
[ 035 074 ]
Parameter PSIG: Operating PSIG: Release PSIG: Oper. Mode PSIG: Oper. Mode
mode PSx t. send PSx send PSx trip PSx
set 1 015 000 015 002 015 036 015 107
set 2 024 000 024 001 015 037 015 108
set 3 024 060 024 061 015 040 015 113
set 4 025 020 025 021 015 041 015 114
43Z6352A_EN
3-191 P433: PSIG send, zone extension, trip and trip enable signals issued by protective signaling in the 'Blocking scheme' operating mode
[ 006 036 ]
45Z6352A_EN
3-192 P435: PSIG send, zone extension, trip and trip enable signals issued by protective signaling in the 'Blocking scheme' operating mode
DC loop
To set up a communications link, it is necessary to connect either the break contact or
the make contact of the transmitting relay according to the selected transmitting relay
mode ('Transm.relay make co' or 'Transm.relay break c'), to the
P S I G : R e c e i v e E X T input of the remote station by installing pilot wires.
Prot.rel. w.break c.
Prot.rel. w.break c.
Prot.rel. w.make c.
Prot.rel. w.make c.
PSIG: Send PSIG: Send
(transm.relay) (transm.relay)
[ 037 024 ] [ 037 024 ]
45Z6353A_EN
In the idle state a receive signal is present at both protection devices (DC loop closed)
and the measuring range of zone 1 is extended by the zone extension factor kze HSR.
The distance protection trip in extended zone 1 is enabled in both protection devices.
If distance protection detects a fault in the backward (reverse) direction, a signal is sent
to the remote station (DC loop open). The overcurrent fault detection logic of the
distance protection function immediately opens the DC loop without waiting for the
transfer trip timer stage to elapse or for a direction decision to be issued. The DC loop is
immediately closed again – without taking into account the reset time of the send signal
– if distance protection detects the fault to be in forward direction.
A distance protection trip in extended zone 1 is issued only after the protective signaling
tripping time has elapsed, provided that no receive signal is present (open loop).
PSIG: Ready
[ 037 027 ]
PSIG: Send
DIST: IB>> (transm.relay)
triggered [ 037 024 ]
303 512
DIST: IC>>
triggered
303 513
DIST: Fault
backward / BS
[ 036 019 ]
DIST: Fault
forward / LS
[ 036 018 ] PSIG: Z1
extended
[ 035 075 ]
PSIG: DC loop op.
mode PSx
[ * ]
1
2
1: Transm.relay
break c
2: Transm.relay
make co
PSIG: Trip
PSIG: Receive enable
[ 006 036 ] 305 157
PSIG: Frequ.
monit. trigg. PSIG: Trip signal
305 152
[ 038 007 ]
DIST: Trip signal
Z1,ze PSIG: Receive
[ 035 074 ] (signal)
MAIN: General [ 037 029 ]
starting
[ 036 000 ]
43Z6354A_EN
3-194 P433: PSIG send, zone extension and trip enable signals by protective signaling in the 'DC loop' operating mode
PSIG: Ready
[ 037 027 ]
PSIG: Send
DIST: IB>> (transm.relay)
triggered [ 037 024 ]
303 512
DIST: IC>>
triggered
303 513
DIST: Fault
backward / BS
[ 036 019 ]
DIST: Fault
forward / LS
[ 036 018 ] PSIG: Z1
extended
[ 035 075 ]
PSIG: DC loop op.
mode PSx
[ * ]
1
2
1: Transm.relay
break c
2: Transm.relay
make co
PSIG: Trip
PSIG: Receive enable
[ 006 036 ] 305 157
PSIG: Frequ.
monit. trigg. PSIG: Trip signal
305 152 [ 038 007 ]
DIST: Trip
zone 1,ze PSIG: Receive
303 595
(signal)
MAIN: General [ 037 029 ]
starting
[ 036 000 ]
45Z6354A_EN
3-195 P435: PSIG send, zone extension and trip enable signals by protective signaling in the 'DC loop' operating mode
The pilot wires are monitored for interruptions. If, during a fault-free operation, i.e. with
no distance protection general starting condition present, no signal is received from the
DC loop for a period longer than the set transmitted signal reset time plus 600 ms, then
the P S I G : T e l e c o m . f a u l t y signal is issued (see figure 3-175) and protective
signaling is blocked.
Reverse interlocking
In radial networks with single-side infeed, it is possible under certain conditions for
busbar protection to be configured by sampling the starting of feeder protection devices.
By means of appropriate interconnection, a send signal is then formed when a feeder
protection device starts. When the P43x receives this signal, distance protection tripping
in extended zone 1 is blocked. The blocking signal has a reset time delay set at
PSIG: tBlock.
45Z6355A_EN
The pilot wires are monitored. If a receive signal is present for more than 10 s without
any general starting of distance protection, then blocking of the distance protection trip in
extended zone 1 is cancelled. No new block can occur until the receive signal has
dropped out.
PSIG: Ready
[ 037 027 ]
PSIG: Operating
mode PSx
[ * ]
7: Reverse
interlocking
PSIG: Telecom
faulty int.
10s 0 305 151
S1 1
R1
DIST: General
starting
[ 036 240 ]
PSIG: Receive
(signal)
[ 037 029 ]
MAIN: General
starting
[ 036 000 ]
3-197 Trip enable and trip signal in the 'Reverse interlocking' operating mode
Direction comparison
A signal is sent to the remote station if distance protection detects a fault in the forward
direction.
Once the tripping time has elapsed, protective signaling issues a trip decision if a receive
signal is present and distance protection detects a fault in the forward direction. In the
event of a direction change, the receive signal is ignored for the PSIG : tBl o c k set
time (‘transient blocking’) so as to avoid unwanted tripping in the protection of double
circuit lines.
PSIG: Release
t. send PSx PSIG: Release
[ * ] t. send PSx
[ * ]
PSIG: Frequ.
monit. trigg.
305 152
PSIG: Timer
stage elapsed
305 164
PSIG: Transient
blocking
305 154 PSIG: Receive
(signal)
[ 037 029 ]
MAIN: General
starting
[ 036 000 ] Parameter PSIG: Operating PSIG: Release
mode PSx t. send PSx
set 1 015 000 015 002
set 2 024 000 024 001
set 3 024 060 024 061
set 4 025 020 025 021
45Z6357A_EN
3-199 PSIG send signal and trip signal by protective signaling in the 'Direction comparison' operating mode
Weak-infeed logic
The P43x features a "weak-infeed logic" function. Weak-infeed logic can either be
triggered by a binary signal input configured to P S I G : W e a k i n f . t r i g g . E X T or
by the binary signal input configured to P S I G : R e c e i v e E X T .
The weak-infeed logic checks the phase-to-ground voltages to determine whether they
fall below the P S I G : V < w e a k i n f e e d P S x set threshold. If the voltage in one
phase falls below the set threshold, then a timer stage is started. Once it has elapsed –
provided that the appropriate setting has been selected – a protective signaling trip is
issued. The D IST : T r i p z o n e 1 P G P S x setting is taken into account by the P435.
5s 0
&
VA-G
Ux1
Uxx
PSIG: Receive
[ 006 036 ]
PSIG: Frequ.
monit. trigg.
305 152
43Z6358A_EN
PSIG: V<
triggered
305 162
INP: Fct.
assignm. U xxx
[ XXX XXX ]
PSIG: Trip
V<, A
305 159
Ux1 PSIG: Trip
V<, B
Ux2 305 160
PSIG: Trip
Ux3 V<, C
305 161
Uxx
PSIG: Receive
[ 006 036 ]
PSIG: Frequ.
monit. trigg.
305 152
Parameter PSIG: V< weak PSIG: tV< PSIG: Trip signal DIST: Trip zone 1
infeed PSx PSx V< PSx PG PSx
set 1 015 020 015 019 015 021 011 050
set 2 024 006 024 005 024 007 011 051
set 3 024 066 024 065 024 067 011 052
set 4 025 026 025 025 025 027 011 053
45Z6358A_EN
Echo function
If operation with the echo function is desired, then the user may specify whether the
receive signal alone is to be employed in activating the echo pulse or whether the
receive signal and the triggering signal of the weak-infeed logic are to be used. The
conditions for activation of the echo pulse must persist for a period in excess of the set
time-delay, and distance protection starting must be absent for the echo pulse to be
activated. This time-delay is ineffective with an open circuit breaker (i.e. when the signal
MAIN : C B o p e n 3 p is present). The echo pulse is then transmitted to the remote
station for the set pulse duration. Thereafter, the transmission of the receive signal is
blocked for the set pulse duration + 1 s. This prevents a permanent signal from being
transmitted. The echo function may be disabled.
The following exception applies to the P435:If the P435 is operating with ground fault
protective signaling and if directional measurement of ground fault protection has been
enabled, the echo signal will be blocked if protective signaling (distance schemes) and
ground fault protective signaling are sharing a common transmission channel.
PSIG: Echo on
receive PSx
[ * ]
1
2
0: Without
1: On receive
2: On receive & V<
PSIG: Op. Delay PSIG: Pulse dur.
echo PSx echo PSx
[ * ] [ * ]
PSIG: V<
triggered t 0 PSIG: Send
305 162
PSIG: Receive (A) (signal)
EXT [ 036 035 ]
[ 036 048 ]
PSIG: Receive (B) 0 t+1s PSIG: Send
EXT (transm.relay)
[ 006 037 ] [ 037 024 ]
PSIG: Frequ.
monit. trigg.
305 152
MAIN: CB open 3p
[ 031 040 ]
DIST: General
starting
[ 036 240 ]
GSCSG: Ready
[ 043 057 ]
GSCSG: Channel
mode
[ 023 078 ]
2: Common
channel
GFSC: Direct.
determ.enabl.
[ 043 061 ]
PSIG: Echo on
receive PSx
[ * ]
1
2
0: Without PSIG: Op. Delay PSIG: Pulse dur.
1: On receive echo PSx echo PSx
[ * ] [ * ]
2: On receive & V<
t 0 PSIG: Send
PSIG: V< 1 (signal)
triggered [ 036 035 ]
305 162
PSIG: Receive (A)
EXT 0 t+1s PSIG: Send
[ 036 048 ] (transm.relay)
PSIG: Receive (B) [ 037 024 ]
EXT
[ 006 037 ]
PSIG: Frequ.
monit. trigg.
305 152
MAIN: CB open 3p
[ 031 040 ]
DIST: General
startingg
[ 036 240 ]
After certain faults, the auto-reclosing control function (ARC) brings about automatic
reclosing of the line section that was interrupted by a protection device.
ARC ready
ARC is ready when the following conditions are satisfied:
ARC blocking
ARC will be blocked if one of the following conditions applies:
Distance protection detects a fault in the cable section of the transmission section.
A manual close is carried out.
A switch to backup overcurrent time protection (BUOC) is made, but no ARC is to be
carried out.
A manual open command is issued.
A trip signal is issued by circuit breaker failure protection.
A trip signal is issued by ground fault protective signaling.
A trip signal is issued by ground fault tripping.
The binary signal input configured to A R C : B l o c k i n g E X T is triggered.
After all blocking conditions have dropped out, the relevant blocking time is started, and
when this time has elapsed, the block is canceled.
The general starting state formed internally or the general starting signal of a parallel
protection device, provided that a binary signal input has been configured
accordingly.
A distance protection trip (possible without general starting, such as through the
protective signaling direct transfer trip underreaching mode).
A backup overcurrent-time protection trip (BUOC trip), provided that the ARC is to be
activated by the BUOC function.
The trip signal of an external protection device, provided that the parameters of this
device have been set accordingly (A R C : P a r a l l e l t r i p P S x ).
A test HSR.
The ARC cycle is completed after the last reclaim time has elapsed.
When the ARC cycle starts, operative time 1 is started. The starting conditions for the
ARC cycle must drop out while the operative time is elapsing. This means that the
circuit breaker must have opened so that the dead time is started. If the operative time is
set at ≤ 25 ms, then ARC will not be ready in the event of starting; in the event of a trip,
the reclaim time is started.
If the starting conditions for an ARC cycle drop out after operative time 1 has elapsed but
during operative time 2, then the maximum dead time (AR C : D e a d t i m e m a x P S x ) is
started. When the dead time is started, a close request is sent to the ASC. The ASC
checks to determine whether reclosure is possible. If a positive decision is reached
during the ASC operative time and while the dead time is elapsing, then there is a close
enable, and the close command is issued.
If the ASC function determines that reclosing may not occur or if the ASC function is not
ready, then the reclaim time is started after the dead time has elapsed, and three-pole
tripping occurs (final trip).
Test HSR
A test HSR can be carried out using setting parameters or through an appropriately
configured binary signal input.
A TDR may occur after an HSR if reclosure has occurred as the result of the HSR or if
the operating mode set for the ARC allows only TDRs. This is possible only if the setting
at A R C : N o . o f p e r m i t . T D R P S x (number of permitted TDRs) is not zero.
The TDR is started if either a new general starting condition or the trip of an external
protection device (if configured accordingly) occurs while the reclaim time is elapsing.
Operative times 1 and 2 are started. If the starting conditions for the TDR drop out while
operative time 1 or 2 is elapsing, then the TDR dead time is started. After the dead time
has elapsed, a close request is sent to the automatic synchronism check function (ASC).
The ASC checks to determine whether reclosure is possible. If a positive decision is
reached during the ASC operative time, then there is a close enable, and the close
command is issued.
If the ASC function determines that reclosing may not occur, then a final trip occurs after
the ASC operative time has elapsed, and the ARC reclaim time is started.
If the fault is still present even after another reclosing, the TDR can be started again.
This process can be repeated as often as allowed by the number of permitted TDRs.
If the fault is still present after that, then a final trip occurs.
Rapid reclosure (RRC) operates along with HSR or TDR. If the P433 carries out
appropriate measurements and concludes that the line is carrying voltage and that the
line voltages are healthy, then reclosing is carried out by RRC before reclosing by HSR
or TDR.
0
1
0: no
ARC: V> RRC
1: yes C PSx
[ * ]
ARC: V> for RRC
triggered
303 014
VA-G* 3
VA-G
VB-G VB-G* 3
VC-G
VC-G* 3
MAIN: Neutr.pt.
treat. PSx
[ * ]
1: Low-imped.
grounding
If the starting conditions for rapid reclosing drop out during operative time 1, the RRC
timer stage tRRC is started. After the timer stage has elapsed, the P433 checks to
determine whether the voltages measured by distance protection were greater than or
equal to the set threshold value (A R C : V > R R C P S x ) during the last 100 ms. If this
was the case, then a close request is sent to the automatic synchronism check function
(ASC).
The ASC function will then check if reclosing is permitted. If the ASC decision is
positive, a close enable and then a close command are issued. If reclosing is not
permitted, there is a final trip.
If the ASC is disabled or deactivated or if its decisions are to be ignored, then the close
request is immediately acknowledged and a close command is issued.
If it is determined after timer stage tRRC has elapsed that the voltages were not greater or
equal to the set threshold (A R C : V > R R C P S x ), then the ARC cycle is continued by
the HSR or TDR.
43Z6398A_EN
If a second protection device is operating in parallel with the P433, then the 'trip' from
this protection device can be integrated into the ARC functional sequence – provided
that the binary signal inputs have been configured appropriately. The effect exercised by
the "Trip" of the external protection device operating in parallel depends on the setting at
A R C : P a r a l l e l t r i p P S x (see Figure 3-218 for setting).
A R C : P a r a l l e l t r i p P S x 'Without function'
The trip of the external protection device does not intervene in the functional
sequence.
A R C : P a r a l l e l t r i p P S x 'Parallel blocking without initiation'
The "Trip" of the external parallel protection device does not intervene in the TDR,
HSR or RRC functional sequence.
A R C : P a r a l l e l t r i p P S x 'Parallel blocking with initiation'
The "Trip" of the external protection device starts a TDR, HSR or RRC. The
sequence is the same as with initiation by the P433.
Zone extension (ZE) of impedance zone 1 of the distance protection function is only
initiated by the ARC if protective signaling is not ready.
If the two parameters are set for 'No' or 'Without', respectively, then there is no zone
extension.
At the end of the dead time, the P433 checks to determine whether protective signaling
has received one signal while the above-mentioned times are elapsing. If this is the
case, then the HSR is terminated normally. If protective signaling receives no signal or
more than one signal, the HSR is terminated as if the fault had been cleared during
operative time 2. This means that even with single-pole starting signals or trips reclosing
is preceded by a synchronism check by ASC.
0
1
0: No
1: Yes ARC: Switch to
tPmax
303 024
PSIG: Receive
[ 006 036 ]
ARC: Oper. time 1
running
[ 037 005 ]
ARC: Dead time 3p
running
[ 037 067 ]
ARC: Max.
dead time runn.
[ 037 069 ]
While the reclose command time is elapsing, the close command will be terminated by
either a trip or - as another option – the 'Circuit breaker close' signal (setting at
M A I N : R C i n h i b . B y C B c l ), see Fig. 3-218).
43Z63ABA_EN
ARC: Reset
counters USER
[ 003 005 ]
1
0: don’t execute
1: execute
49Z64ACA_EN
After certain faults, the auto-reclosing control function (ARC) brings about automatic
reclosing of the line section that was interrupted by a protection device.
ARC ready
ARC is ready when the following conditions are satisfied:
ARC blocked
ARC will be blocked if one of the following conditions applies:
Distance protection detects a fault in the cable section of the transmission section.
A manual close is carried out.
A switch to backup overcurrent time protection (BUOC) is made, but no ARC is to be
carried out.
A trip signal is issued by ground fault (short-circuit) protection.
A ground fault (short-circuit) protection signaling trip occurs, but no auto-reclosing is
to occur.
A manual open command is issued.
A trip signal is issued by circuit breaker failure protection.
A trip signal is issued by ground fault protective signaling.
A trip signal is issued by ground fault tripping.
The binary signal input configured to A R C : B l o c k i n g E X T is triggered.
After all blocking conditions have dropped out, the relevant blocking time is started, and
when this time has elapsed, the block is canceled.
The general starting state formed internally or the general starting signal of a parallel
protection device, provided that a binary signal input has been configured
accordingly.
A distance protection trip (possible without general starting, such as through the
protective signaling direct transfer trip underreaching mode).
A backup overcurrent-time protection trip (BUOC trip), provided that the ARC is to be
activated by the BUOC function.
The trip signal of ground fault (short-circuit) protection signaling, provided that the
ARC is to be activated by ground fault protection signaling.
The trip signal of an external protection device, provided that the parameters of this
device have been set accordingly (A R C : P a r a l l e l t r i p P S x ).
A test HSR.
The ARC cycle is completed after the last reclaim time has elapsed.
When the ARC cycle starts, operative times 1 and 2 are started. The starting conditions
for the ARC cycle must drop out while the operative times are elapsing. This means that
the circuit breaker must have opened so that the dead time is started. If both operative
times are set at ≤ 25 ms, then ARC will not be ready in the event of starting; in the event
of a trip, the reclaim time is started. After starting drops out without a subsequent trip,
ARC is immediately ready again. Operative time 1 has priority over operative time 2.
Selection of the HSR operating mode determines which dead time is started.
The following settings are possible:
1-pole
The HSR is executed only if a single-pole trip decision is reached or a single-pole test
HSR is started. A single-pole trip can only occur in impedance zone 1, brought about by
backup overcurrent-time protection (BUOC) or a parallel protection device. In the event
of a three-pole trip, no HSR is executed, and instead a final trip occurs.
If the starting conditions for the ARC cycle drop out after operative time 1 has elapsed
but during operative time 2, then the maximum dead time (AR C : D e a d t i m e m a x
PSx) is started. When the dead time is started, a close request is sent to the ASC. The
ASC checks to determine whether reclosure is possible. If a positive decision is reached
during the ASC operative time and while the dead time is elapsing, then there is a close
enable, and the close command is issued.
If the ASC function determines that reclosing may not occur or if the ASC is not
activated, then the reclaim time is started and a three-pole trip occurs (final trip).
1-/3-pole
An HSR is executed both with single-pole and three-pole trips or a corresponding test
HSR. A single-pole trip can only occur in impedance zone 1, brought about by backup
overcurrent-time protection (BUOC) or a parallel protection device.
If the ASC is disabled or deactivated, or if its decisions are to be ignored, then a close
command is issued immediately
If the starting conditions for an ARC cycle drop out after operative time 1 has elapsed but
during operative time 2, then the maximum dead time (AR C : D e a d t i m e m a x P S x ) is
started. This occurs with both single-pole and three-pole trips. When the dead time is
started, a close request is sent to the ASC. The ASC checks to determine whether
reclosure is possible. If a positive decision is reached during the ASC operative time
and while the dead time is elapsing, then there is a close enable, and the close
command is issued.
If the ASC function determines that reclosing may not occur or if the ASC function is not
ready, then the reclaim time is started after the dead time has elapsed, and three-pole
tripping occurs (final trip).
3-227 P435: Signal flow with the operating mode ‘1-/3-pole’, tripping during operative time 1
3-228 P435: Signal flow with the operating mode ‘1-/3-pole’, tripping during operative time 2, and close rejection
3-pole
ARC is carried out with both single-pole and three-pole trips. In the event of a single-
pole trip, three-pole transfer tripping occurs.
If the ASC is disabled or deactivated, or if its decisions are to be ignored, then a close
command is issued immediately.
If the starting conditions for an ARC cycle drop out after operative time 1 has elapsed but
during operative time 2, then the maximum dead time (AR C : D e a d t i m e m a x P S x ) is
started. When the dead time is started, a close request is sent to the ASC. The ASC
checks to determine whether reclosure is possible. If a positive decision is reached
during the ASC operative time and while the dead time is elapsing, then there is a close
enable, and the close command is issued.
If the ASC function determines that reclosing may not occur, then the reclaim time is
started and the 'final trip' signal is issued.
Test HSR
A single- or three-pole test HSR can be carried out using setting parameters or through
appropriately configured binary signal inputs. If a single-pole test HSR is triggered in the
3-pole operating mode, then a three-pole trip occurs.
A TDR may occur after an HSR if reclosure has occurred as the result of the HSR or if
the operating mode set for the ARC allows only TDRs. This is possible only if the setting
for A R C : N o . o f p e r m i t . T D R P S x (number of permitted TDRs) is not zero. The
TDR is always a three-pole process. This means that three-pole transfer tripping will
occur in the event of a single-pole trip.
The TDR is started if either a new general starting condition or the trip of an external
protection device (if configured accordingly) occurs while the reclaim time is elapsing.
Operative times 1 and 2 are started. If the starting conditions for the TDR drop out while
operative time 1 or 2 is elapsing, then the TDR dead time is started. After the dead time
has elapsed, a close request is sent to the automatic synchronism check function (ASC).
The ASC checks to determine whether reclosure is possible. If a positive decision is
reached during the ASC operative time, then there is a close enable, and the close
command is issued.
If the ASC function determines that reclosing may not occur, then a final trip occurs after
the ASC operative time has elapsed, and the ARC reclaim time is started.
If the fault is still present even after another reclosing, the TDR can be started again.
This process can be repeated as often as allowed by the number of permitted TDRs. If
the fault is still present after that, then a final trip occurs.
Rapid reclosure (RRC) operates along with HSR or TDR. If the P435 carries out
appropriate measurements and concludes that the line is carrying voltage and that the
line voltages are healthy, then reclosing is carried out by RRC before reclosing by HSR
or TDR.
0
1
0: no
ARC: V> RRC
1: yes C PSx
[ * ]
ARC: V> for RRC
triggered
303 014
VA-G* 3
VA-G
VB-G VB-G* 3
VC-G
VC-G* 3
MAIN: Neutr.pt.
treat. PSx
[ * ]
1: Low-imped.
grounding
If the starting conditions for rapid reclosing drop out during operative time 1, the RRC
timer stage tRRC is started. After the timer stage has elapsed, the P435checks to
determine whether the voltages measured by distance protection were greater than or
equal to the set threshold value (A R C : V > R R C P S x ) during the last 100 ms. If this
was the case, then a close request is sent to the automatic synchronism check function
(ASC). The ASC response is a function of whether a single- or three-pole trip command
has been issued.
If a three-pole trip has been activated, the ASC checks to determine whether reclosing
can occur. If the ASC decision is positive, a close enable and then a close command
are issued. If reclosing is not permitted, there is a final trip.
If the ASC is disabled or deactivated or if its decisions are to be ignored, then the close
request is immediately acknowledged and a close command is issued, even in the case
of a three-pole trip.
If it is determined after timer stage tRRC has elapsed that the voltages were not greater or
equal to the set threshold (A R C : V > R R C P S x ), then the ARC cycle is continued by
the HSR or TDR.
If a repeat trip occurs in another phase during the dead time, then this is referred to as a
secondary fault and results in three-pole tripping. This is carried out as a three-pole trip.
The response of the ARC to a secondary fault is a function of whether the secondary
fault occurs during a high-speed reclosure (HSR), a time-delay reclosure (TDR) or a
rapid reclosure (RRC).
If starting or a trip occurs again during the single-pole dead time in the same phase
as at the beginning of the ARC cycle, the ARC cycle is continued. The ARC cycle is
terminated only if the starting signal or the trip are still present immediately before the
close command is issued.
A R C : H S R o p e r . m o d e '1-/ 3 - pole'
If starting or a trip occurs again during the single-pole dead time in the same phase
as at the beginning of the ARC cycle, the ARC cycle is continued. The ARC cycle is
terminated only if a starting signal or trip is still present immediately before the close
command is issued.
If a secondary fault occurs during the single-pole dead time, then operative time 1 is
started. The single-pole dead time continues. If the secondary fault's starting
condition and trip drop out while operative time 1 is elapsing, the P435 checks to
determine whether the single-pole dead time that has already elapsed plus the set
three-pole dead time is shorter than the set single-pole dead time. If this is the case,
a switch is made to the three-pole dead time, and the ARC cycle is terminated as in
the case of a three-pole trip. If the elapsed single-pole dead time plus the set three-
pole dead time is greater than the set single-pole dead time, then final tripping occurs
and the reclaim time is started.
A secondary fault during the course of the three-pole dead time is ignored.
Termination of the ARC cycle only occurs if the starting signal or trip has not yet
dropped out immediately before the close command is issued.
If either a starting or a trip occurs again during the maximum dead time in the same
phase as at the beginning of the ARC cycle, the ARC cycle is continued. If a
secondary fault occurs in a different phase, there is a three-pole trip transfer. The
dead time and checking by the ASC function continue. If the ASC decision is that
reclosing is permissible, a close command is issued.
A R C : HSR oper. mode '3-pole'
In this HSR operating mode, a secondary fault is ignored. The ARC cycle is
terminated only if a starting signal or trip is still present immediately before the close
command is issued.
If a second protection device is operating in parallel with the P435, then the trip from this
protection device can be integrated into the ARC functional sequence – provided that the
binary signal inputs have been configured appropriately. The effect exercised by the trip
of the parallel protection device is a function of whether it intervenes in a high-speed
reclosure (HSR), a time-delay reclosure (TDR), or a rapid reclosure (RRC). In addition,
the AR C : Pa r a l l e l tr i p PSx setting is a determining factor (see Figure 3-236).
A R C : P a r a l l e l t r i p P S x 'Without function'
The trip of the external protection device does not intervene in the functional
sequence.
A R C : P a r a l l e l t r i p P S x 'Parallel blocking without initiation'
The trip of the parallel protection device does not intervene in the TDR or RRC
functional sequence.
A R C : P a r a l l e l t r i p P S x 'Parallel blocking with initiation'
The trip of the external protection device starts a TDR or RRC. The sequence is the
same as with initiation by the P435.
Zone extension (ZE) of impedance zone 1 of the distance protection function is only
initiated by the ARC if protective signaling is not ready.
If the two parameters are set for No or Without, respectively, then there is no zone
extension.
At the end of the dead time, the P435 checks to determine whether protective signaling
has received one signal while the above-mentioned times are elapsing. If this is the
case, then the HSR is terminated normally. If protective signaling receives no signal or
more than one signal, the HSR is terminated as if the fault had been cleared during
operative time 2. This means that even with single-pole starting signals or trips reclosing
is preceded by a synchronism check by ASC.
0
1
0: No
1: Yes ARC: Switch to
tPmax
303 024
PSIG: Receive
[ 006 036 ]
ARC: Oper. time 1
running
[ 037 005 ]
ARC: Dead time 1p
running
[ 037 066 ]
ARC: Dead time 3p
running
[ 037 067 ]
ARC: Max.
dead time runn.
[ 037 069 ]
While the reclose command time is elapsing, the reclose command will be terminated by
either a trip or - as another option – the 'Circuit breaker close' signal (setting at
M A I N : R C i n h i b . b y C B c l ), see Fig. 3-236).
43Z63ABA_EN
ARC: Reset
counters USER
[ 003 005 ]
1
0: don't execute
1: execute
45Z63ACA_EN
The automatic synchronism check (ASC) function allows the device to verify that before
a close or reclose command is issued synchronism exists between system sections that
are to be synchronized (paralleled) or whether one of the system sections is de-
energized. In order to check for synchronism, two voltages – generally the voltages on
the line and busbar sides – are compared for differences in frequency, angle, and
voltage. Connecting the reference voltage transformer will determine which of the
system sections will provide the reference voltage (e.g. the line side or the busbar side).
The measurement loop must be set in the P43x according to the reference voltage
connection (setting A S C : M e a s u r e m e n t l o o p P S x ) so that the correct
measurement loop voltage is selected for the comparison. In the connection example
shown in the sub-section entitled 'Conditioning of the Measured Values' (in section 'Main
Functions of the P43x'), the busbar voltage VA-B is the reference voltage.
ASC: Measurement
loop PSx
[ * ]
VA-G
VB-G
VC-G
ASC: Select.
meas.loop PG
305 008
ASC: Volt.
1: Loop A-G sel. meas.loop
[ 004 088 ]
2: Loop B-G
3: Loop C-G
4: Loop A-B
5: Loop B-C
6: Loop C-A
ASC: Voltage
Vref Vref
[ 004 087 ]
If the ASC function is disabled an uncontrolled activation enable will always be issued.
The user can also specify separately for high-speed reclosures (HSR) and time-delayed
reclosures (TDR) whether reclosure will be carried out with or without a check.
The single-pole high speed reclosure is always without a check
Close request
The ASC function can be triggered by ARC from the integrated local control panel or via
an appropriately configured binary signal input (A S C : C l o s e r e q u e s t E X T ). Close
requests via a setting parameter or a binary signal input are only accepted if no ARC
cycle is running.
The ASC operative time is started with the close request. If the close enable signal is
issued before the ASC operative time has elapsed, the close command is issued.
Otherwise an A S C : C l o s e r e j e c t i o n signal is generated for 100 ms.
Voltage-checked
Sync.-checked
Voltage/synchronism-checked
Continuous synchronism
check
Synchronism checks, e.g. monitoring of voltage and/or synchronism requirements, are
now carried out continuously during the duration of the set ASC operative time.
The following signals are updated according to their current states:
ASC: Close enable
ASC: Close enable,volt.ch
ASC: Close enable,sync.ch
ASC: Close rejection
The maximum operative time setting was extended to 6000 s (100 minutes).
Extended settings for the
close enable conditions
The close enable conditions can now be set separately for auto-reclose control and
manual close command. This makes it possible to select different operating modes as
well as different tolerance ranges.
Close enable conditions for
Auto-reclose control Manual close command
ASC: AR op. mode PSx ASC: MC op. mode PSx
ASC: AR with tCB PSx ASC: MC with tCB PSx
ASC: AR Op.mode v-chk. PSx ASC: MC op.mode v-chk. PSx
ASC: AR V> volt.check PSx ASC: MC V> volt.check PSx
ASC: AR V< volt.check PSx ASC: MC V< volt.check PSx
ASC: AR tmin v-check PSx ASC: MC tmin v-check PSx
ASC: AR V> sync.check PSx ASC: MC V> sync.check PSx
ASC: AR delta Vmax PSx ASC: MC delta Vmax PSx
ASC: AR delta f max PSx ASC: MC delta f max PSx
ASC: AR delta phi max PSx ASC: MC delta phi max PSx
ASC: AR tmin sync.chk PSx ASC: MC tmin sync.chk PSx
The automatic reclosure setting parameters become active when a close request is
issued by the integrated ARC (for a RRC, HSR or TDR) or by a close request from an
external ARC device sent to the binary signal input function
ASC: AR close request EXT.
Considering the
CB close time
In slightly asynchronous power systems setting ASC : AR w i th tC B PSx = 'Yes' or
A S C : M C w i t h t C B P S x = 'Yes' makes it possible to consider the circuit breaker
close time with the issuing of a close command.
The condition for "slightly asynchronous power systems" is given if the difference in
frequencies lies within the range of 10 mHz < ∆f < ∆fmax. If this condition and the voltage
condition (∆V < ∆Vmax) are met then the next point in time is continuously calculated at
which the phasors for Vref and the corresponding voltage of the three-phase system are
in phase (e.g. difference in voltage phase angles approaches 0°). The close command,
allowing for the set CB close time M A I N : t C B , c l o s e , is then issued sooner.
yes yes
Close with tCB 'f < 10 mHz
no no
synchronous mode, close if: asynchronous mode, synchronous mode, close if:
'V < 'Vmax close if: 'V < 'Vmax
'f < 'fmax 'V < 'Vmax 'M < 'Mmax
'M < 'Mmax 'f < 'fmax for tmin,synchr
for tmin,synchr Raise close command so that within operative time
within operative time closing takes place at 'M = 0
(taking CB close time and
internal delays into account)
within operative time
47Z1085B_EN
3-243 Functional sequence and close conditions for the Synchronism check
Voltage-checked
The synchronism-checked close enable can be bypassed using the voltage-checked
close enable without affecting the former. This allows closing if at least one side is
voltage-free/de-energized. To detect whether voltage is present or not on either side,
the three phase-to-ground voltages and the reference voltage Vref are monitored to
determine whether they exceed or fall below the set threshold values:
Depending on the operating mode selected for the voltage check, all three phase-to-
ground voltages need to exceed or fall below the set value in order to meet the condition
for voltage-checked closing. If the conditions corresponding to the set operating mode
for the voltage-checked synchronism check are met for the duration of the set minimum
time (A S C : t m i n v o l t . c h e c k ) then the close enable signal is issued.
The following operating modes for voltage checking can be selected separately for each
parameter subset:
The 'Vref & Z1 but not V' operating mode includes a further requirement, which specifies
that the close request is issued during an ARC cycle, and the cause of the fault for the
previous protective trip lies inside the reach of impedance zone 1.
As of version -612, the meaning of “Z1” for the 'Vref & Z1 but not V' operating mode was
enhanced, so that the close request is also enabled if a PSIG based Z1e trip occurs
(because in this case, too, a fault on the line is detected).
ASC: Enabled
[ 018 024 ]
ASC: Active
305 003
ASC: AR V<
C volt.check PSx
[ * ]
VA-G*√3 &
VB-G*√3
VC-G*√3
ASC: AR tmin
v-check PSx
[ * ]
ASC: Select. 1 ASC: AR Op.mode
meas.loop PG v-chk.PSx
305 008
[ * ]
2 t 0
&
Vref 1
VA-G*√3 1
&
2
2
1 ... 2 &
3
&
4
&
6
&
&
1: Vref but not V
2: V but not Vref &
3: Not V and not Vref
4: Not V or not Vref
5: Vref & Z1 but not V
PSIG: Enable & 6: N V&Vref or V& n Vref
305 157
ARC: HSR B
303 009
Parameter ASC: AR op. mode ASC: AR V> ASC: AR V< ASC: AR op.mode ASC: AR tmin
ARC: HSR C PSx volt.check PSx volt.check PSx v-chk.PSx v-check PSx
303 010
set 1 018 025 026 017 018 017 018 029 018 018
ASC: Close set 2 018 026 077 043 077 040 018 030 077 041
enable,sync.ch
[ 037 084 ] set 3 018 027 078 043 078 040 018 031 078 041
set 4 018 028 079 043 079 040 018 032 079 041
47Z1380D_EN
ASC: Enabled
[ 018 024 ]
ASC: Active
305 003
ASC: MC V<
C volt.check PSx
[ * ]
VA-G*√3 &
VB-G*√3
VC-G*√3
ASC: MC tmin
v-check PSx
[ * ]
ASC: Select. 1 ASC: MC Op.mode
meas.loop PG v-chk.PSx
305 008
[ * ]
2 t 0
&
Vref 1
VA-G*√3 1
&
2
2
1 ... 2 &
3
&
4
&
6
&
&
1: Vref but not V
2: V but not Vref &
3: Not V and not Vref
4: Not V or not Vref
5: Vref & Z1 but not V
PSIG: Enable &
305 157 6: N V&Vref or V&n Vref
DIST: Trip signal
Z1,ze
[ 035 074 ] &
DIST: Dist.
decis.Z1 stored ASC: Close
303 565 1 enable,volt.ch
ARC: Cycle 100ms [ 037 085 ]
running
[ 037 000 ] ASC: Close enable
1 [ 037 083 ]
ARC: HSR A 100ms
303 008
ARC: HSR B
303 009
Parameter ASC: MC op. mode ASC: MC V> ASC: MC V< ASC: MC op.mode ASC: MC tmin
ARC: HSR C PSx volt.check PSx volt.check PSx v-chk.PSx v-check PSx
303 010
set 1 000 056 000 064 000 068 000 060 000 072
ASC: Close set 2 000 057 000 065 000 069 000 061 000 073
enable,sync.ch
[ 037 084 ] set 3 000 058 000 066 000 070 000 062 000 074
set 4 000 059 000 067 000 071 000 063 000 075
47Z1381E_EN
Synchronism-checked
Before a close enable signal is issued, the ASC checks the voltages for synchronism.
Synchronism is recognized if the following conditions are met simultaneously:
The three phase voltages and the reference voltage must exceed the set threshold
value:
ASC: AR V> sync.check PSx ASC: MC V> sync.check PSx
The frequency difference between measuring voltage and reference voltage must not
exceed the set threshold value:
ASC: AR delta f max PSx ASC: MC delta f max PSx
The angle difference between measuring voltage and reference voltage must not
exceed the set threshold value:
ASC: AR delta phi max PSx ASC: MC delta phi max PSx
If these conditions are met for the A S C : t m i n s y n c . c h e c k set time, then a close
enable signal is issued. The ASC operating time for the determination of differences in
voltage, angle, and frequency is approximately 100 ms.
The voltage magnitude difference, angle difference, and frequency difference are stored
as measured synchronism data at the time the close enable signal is issued. In the
event of another close request, they are automatically overwritten by the new data.
ASC: Active * Parameter MAIN: Neutr.pt. ASC: AR op. mode ASC: Phi offset ASC: AR V>
305 003 treat. PSx PSx PSx sync.check PSx
ASC: AR op. mode set 1 010 048 018 025 018 034 018 011
PSx set 2 001 076 018 026 077 042 077 035
[ * ] set 3 001 077 018 027 078 042 078 035
set 4 001 078 018 028 079 042 079 035
1
* Parameter ASC: AR delta ASC: AR delta ASC: AR delta ASC: AR tmin
2 Vmax PSx f max PSx phi max PSx sync.chk PSx
3 set 1 018 012 018 014 018 013 018 015
set 2 077 036 077 038 077 037 077 039
1: Voltage- set 3 078 036 078 038 078 037 078 039
checked set 4 079 036 079 038 079 037 079 039
2: Sync.-checked
MAIN: Neutr.pt. 3: Volt./sync.-
treat. PSx checked
[ * ]
1: Low-imped.
grounding
ASC: AR V>
sync.check PSx
[ * ]
VA-G VA-G
VB-G VB-G
VC-G VC-G
ASC: Select
meas.loop PG
305 008
ASC: AR tmin
Vref Vref sync.chk PSx
[ * ]
ASC: Close
enable,sync.ch
[ 037 084 ]
ASC: Test
305 004
ASC: AR delta
ASC: Phi offset phi max PSx
PSx [ * ]
[ * ]
corr
47Z1112A_EN
ASC: Active * Parameter MAIN: Neutr.pt. ASC: MC op. mode ASC: Phi offset ASC: MC V>
305 003 treat. PSx PS PSx sync.check PSx
ASC: MC op. mode set 1 010 048 000 056 018 034 000 052
PSx set 2 001 076 000 057 077 042 000 053
[ * ] set 3 001 077 000 058 078 042 000 054
set 4 001 078 000 059 079 042 000 055
1
* Parameter ASC: MC delta ASC: MC delta ASC: MC delta ASC: MC tmin
2 Vmax PSx f max PSx phi max PSx sync.chk PSx
3 set 1 000 080 000 084 000 089 000 098
set 2 000 081 000 086 000 091 000 099
1: Voltage- set 3 000 082 000 087 000 092 000 100
checked set 4 000 083 000 088 000 093 000 101
2: Sync.-checked
MAIN: Neutr.pt. 3: Volt./sync.-
treat. PSx checked
[ * ]
1: Low-imped.
grounding
ASC: MC V>
sync.check PSx
[ * ]
VA-G VA-G
VB-G VB-G
VC-G VC-G
ASC: Select
meas.loop PG
305 008
ASC: MC tmin
Vref Vref sync.chk PSx
[ * ]
ASC: Close
enable,sync.ch
[ 037 084 ]
ASC: Test
305 004
ASC: MC delta
ASC: Phi offset phi max PSx
PSx [ * ]
[ * ]
corr
47Z1113A_EN
Voltage/synchronism-
checked
If this setting has been selected, then the close enable signal is issued if the conditions
for voltage- or synchronism-checked closing are met.
ASC: Enabled
[ 018 024 ]
ASC: CB
assignment PSx
[ * ]
No assignment
DEV01
DEV02
DEV03 ASC: AC effect.
for DEV01
305 040
Sel. DEV01
ASC: Close
enable DEV01 AC
305 041
ASC: Close enable
[ 037 083 ]
ASC: System
integrat. PSx
[ * ]
1
2
1: Autom.synchron.check
2: Autom.synchr.control
3-249 Integrating the ASC function into the control and monitoring of switchgear units
ASC: Transm.
cycle,meas.v.
[ 101 212 ]
ASC: Enabled
[ 018 024 ] C
ASC: Angle
difference
[ 004 089 ]
ASC: Frequ.
difference
[ 004 090 ]
49Z64BEA_EN
ASC counters
The following ASC signals are counted:
The counters can either be reset individually (at the address at which they are displayed)
or as a group.
ASC: Reset
counters USER
[ 003 089 ]
0: don’t execute
1: execute
47Z1377A_EN
In the event of single-phase high-resistance faults, the measured fault data are often
insufficient for fault detection and selective clearing by the distance protection function.
To cover for this situation, ‘ground fault (short-circuit) protection’ is integrated into the
protection device as a highly sensitive backup protection function. Consequently,
ground fault (short-circuit) protection is operating in parallel with and independently of
distance protection.
Disabling or enabling
ground fault (short-circuit)
protection
The function can be disabled or enabled using setting parameters or through binary
signal inputs.
GFSC: General
enable USER
[ 018 060 ]
0
1
0: No
1: Yes
GFSC: Enable
PSx
[ * ]
0 GFSC: Enabled
[ 038 094 ]
1
0: No
1: Yes
INP: Fct.
assignm. U xxx
[ xxx xxx ]
Ux1
Ux2
Ux3
Uxx
GFSC: Enable
USER
[ 003 138 ]
0
1
0: don't execute
1: execute
GFSC: Disable
EXT
[ 039 096 ]
GFSC: Disable
USER
[ 003 137 ]
0
1
0: don't execute
1: execute GFSC: Ready
[ 039 093 ]
MAIN: Protection
active
306 001
MAIN: M.c.b. trip
V EXT
[ 004 061 ]
GFSC: Blocking
EXT
[ 043 068 ]
MAIN: M.c.b. GFSC: Not ready
trip VNG EXT [ 039 094 ]
[ 002 183 ]
Starting
The digitally filtered fundamental waves of current and voltage are measured.
They are monitored to determine whether they exceed set thresholds (G F SC : IN > and
G F SC : VN G > ). If both thresholds have been exceeded, a settable timer stage
(G F S C : S t a r t . o p e r . d e l a y ) is started. Once the trigger has dropped out,
the starting persists until the settable release delay ( G F SC : Sta r t. r e l e a s . d e l a y)
has elapsed. Directional measurement is enabled if the current reaches 70 % of the set
threshold (G F SC : IN > ) and the voltage exceeds the trigger threshold
(G F SC : VN G > ).
3-253 Starting
Directional tripping
The P435 determines the angle between the residual current and the neutral-
displacement voltage for the direction determination. The measured angle is displayed.
The position of the straight line separating forward and backward (reverse) directions is
determined by setting G F SC : An g l e ϕ G . A forward or backward (reverse)-directional
decision results if the following angle conditions are met:
V C-G
Forward
direction
+
90o
phiG
phi(IG)
V G-N = -V N-G V A-G
IG
Backward (reverse)
direction
V B-G
47Z1090A_EN
Voltage-dependent or
current-dependent tripping
By setting operating mode tS, the user can choose between voltage-dependent or
current-dependent tripping. After the voltage-dependent or current-dependent time has
elapsed, a trip signal is issued either independently of the directional decision or when
there is a directional decision for the forward direction – depending on the setting at
GFSC: Criteria tS active.
Voltage-dependent tripping
Starting of ground fault (short-circuit) protection enables determination of the voltage-
dependent tripping time. Tripping time tS is calculated as follows.
2s
tS =
V N −G
10 ⋅ − 0.2
Vnom
0.6364 ⋅ 1.1⋅
3
40
35
30
Tripping time tS
25
20
15
10
0
0 1 2 3 4 5 6 7 8 9 10 11 V
Voltage ⏐VN-G⏐
47Z0129A
Current-dependent tripping
Starting of ground fault (short-circuit) protection enables determination of the current-
dependent tripping time. The user can select from a large number of characteristics (see
table below). If the current exceeds 1.05 times the set reference current, calculation of
the tripping time begins. A trip signal is issued as a function of the set characteristic.
The tripping characteristics available for selection are shown in figures 3-257 to 3-260.
1000 1000
100 100
k=10
10 10 k=10
t/s k=1
t/s
1 1 k=1
k=0.1
0.1 0.1
k=0.1
k=0.01
0.01 0.01 k=0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
D5Z50K1A D5Z50K2A
1000 1000
100 100
k=10
10 10
k=1
t/s t/s
k=10
1 1
k=0.1
k=1
0.1 0.1
k=0.01
k=0.1
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
k=0.01
I/Iref I/Iref
D5Z50K3A D5Z50K4A
100 100
10 k=10 10
k=10
t/s t/s
1 k=1 1
k=1
I/Iref I/Iref
D5Z50K5B D5Z50K6B
1000
100
10
t/s
k=10
1
k=1
0.1
k=0.1
0.01 k=0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
D5Z50K7B
Characteristic No. 7
1000 1000
100 100
10 10
t/s t/s
k=10
1 1
k=10
k=1
0.1 0.1
k=1
k=0.1
0.01 k=0.01 0.01 k=0.1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
D5Z50K8B D5Z50K9B
1000
100
k=10
10
t/s k=1
1
k=0.1
0.1
k=0.01
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
D5Z50KAB
Characteristic No. 10
1000 1000
100 100
k=10
k=10
10 10
t/s k=1 t/s
k=1
1 1
k=0.1
k=0.1
0.1 0.1
k=0.01
k=0.01
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
D5Z50KBA D5Z50KCA
Non-directional tripping
Starting of ground fault (short-circuit) protection starts settable timer stage t3. Once t3
and tS have elapsed, a trip signal is issued by ground fault (short-circuit) protection.
Note: After timer stage t1 or t2 has elapsed, a trip signal is issued and remains present until the starting drops off – even if the direction
decision changes or is reset. This latching is not shown in the diagram.
Counters
The trip signals issued by ground fault (short-circuit) protection are counted. The
counter can be reset either at the counter address or by a general reset action.
47Z13AHA_EN
An external signal transmission device is required for operation of ground fault (short-
circuit) protection signaling.
Disabling or enabling
ground fault (short-circuit)
protection signaling
The function can be disabled or enabled using setting parameters or through binary
signal inputs.
External blocking is carried out either via a binary signal input configured for
G SC SG : Bl o c k i n g EXT or via a binary signal input configured for
PSIG : Bl o c k i n g EXT , depending on the operating mode setting for the
communication channel.
The fault signal from the external signal transmission device can be either connected to
a binary signal input, configured for G SC SG : T e l e c o m . fa u l ty EXT or to a binary
signal input, configured for PSIG : T e l e c o m . fa u l ty EXT depending on the
operating mode setting for the communication channel.
Communication link
faulty signal
As of version P435 -604, the G SC SG : T e l e c o m . fa u l ty status signal was made
available in conjunction with the implementation of the protective interface.
This signal is set by the G SC SG : T e l e c o m . fa u l ty EXT logic binary input function
as well as by C O M M 3 : C o m m u n i c a t i o n s f a u l t if the
C O M M 3 : Si g .a s g . c o m m .fa u l t parameter has been set accordingly.
Tripping time
If ground fault (short-circuit) protection signaling is ready, then the tripping timer is
started by ground fault (short-circuit) protection starting.
Frequency monitoring
Failure of frequency transmission can be signaled to the P435 via an appropriately
configured binary signal input. Which inputs are activated is determined by the channel
operating mode setting at G SC SG : C h a n n e l m o d e . If ground fault (short-circuit)
protection signaling uses a different communication channel than protective signaling,
then the following occurs, as long as frequency monitoring has been enabled: when the
binary signal input configured for G SC SG : F r e q u . m o n . t r i g d . E X T is triggered, the
P435 allows an operate delay of approximately 20 ms to elapse and then generates a
receive signal for 150 ms.
Transient blocking
In the event of a directional change of ground fault (short-circuit) protection from
backward (reverse) to forward, ground fault (short-circuit) protection signaling will
generate a blocking signal for the time period set at G S C S G : t B l o c k .
Operating modes of
ground fault (short-circuit)
protection signaling and
the communication channel
Ground fault (short-circuit) protection signaling can be operated in two different modes:
Signal comparison release or Signal comparison blocking. For the communication
channel, the user can specify whether ground fault (short-circuit) protection signaling will
use a different communication channel than distance protection protective signaling or
whether the same channel will be used. If the same communication channel is being
used, then the operating mode settings for protective signaling and ground fault (short-
circuit) protection signaling must be identical. Otherwise there will be a fault signal (see
section 'Protective Signaling').
The circuit breaker in the remote station is tripped if the following conditions are satisfied:
The tripping time of the ground fault (short-circuit) protection signaling function has
elapsed.
Ground fault (short-circuit) protection has detected a fault in the backward (reverse)
direction.
1 2 3 4 5 6 7
GSCSG: Ready
[ 043 057 ]
GSCSG: Operating
mode
[ 023 079 ]
&
1
2
1: Signal comp.
release
2: Signal comp.
block.
GSCSG: Channel
mode
[ 023 078 ]
1
2
1: Independent
channel GSCSG: Release
2: Common channel time send
[ 023 076 ]
0 t GSCSG: Send
& & signal
[ 043 059 ]
GFSC: Fault &
GSCSG: Send
forward / LS internal signal
[ 039 090 ] 304 002
GSCSG: Tripping
time elaps.
[ 043 063 ]
GSCSG: Transient
blocking GSCSG: Trip
304 001 & signal
[ 043 060 ]
& >1
-
GSCSG: Receive
EXT &
[ 043 055 ]
PSIG: Receive
305 165
GSCSG: Frequ.mon.
triggered
304 000
&
GSCSG: Bl.
PSIG weak infeed
304 003
GFSC: Fault
backward / BS
[ 039 091 ]
6 150 47Z0138A_EN
3-270 GSCSG send signal and trip signal in the 'Signal comp. release' (permissive) operating mode and blocking of the weak indeed logic of
distance protection protective signaling
Signal comparison
blocking scheme
If ground fault (short-circuit) protection detects a fault in the backward (reverse) direction,
a signal is sent to the remote station. In the event of a directional change from backward
(reverse) to forward, the send signal is extended for the set duration of transient
blocking. Depending on the setting at G SC SG : Bl o c k . s i g . n o n d i r . , a send signal
is already generated if directional measurement of ground fault (short-circuit) protection
has been enabled and ground fault (short-circuit) protection has not made a forward
decision.
The circuit breaker in the remote station is tripped if the following conditions are satisfied:
1 2 3 4 5 6 7
GSCSG: Ready
[ 043 057 ]
GSCSG: Operating
mode
[ 023 079 ]
1
&
2
1: Signal comp.
release
2: Signal comp.
block.
GSCSG: Channel
mode
[ 023 078 ]
1
2
1: Independent
channel GSCSG: Release
2: Common channel time send
[ 023 076 ]
GSCSG: Block.
sig. nondir.
[ 023 089 ]
0
1 &
0: No
1: Yes
GFSC: Direct.
determ.enabl.
[ 043 061 ]
GFSC: Fault
forward / LS &
GSCSG: Trip
[ 039 090 ] signal
[ 043 060 ]
GSCSG: Tripping
time elaps. & >1
[ 043 063 ] -
GSCSG: Receive
EXT &
[ 043 055 ]
PSIG: Receive
305 165
GSCSG: Frequ.mon.
triggered
304 000
7 160 47Z0139A_EN
3-271 GSCSG send signal and trip signal in the operating mode 'Signal comp. block.''
Weak-infeed logic
Ground fault (short-circuit) protection signaling has a 'weak-infeed logic' function that
makes tripping possible if ground fault (short-circuit) protection does not start. The user
has the option to choose whether in this case the trip signal will be issued by ground
fault (short-circuit) protection signaling when there is a directional decision by ground
fault (short-circuit) protection in the forward direction or when the G F SC : VN G >
trigger value is exceeded.
Trip mode
Depending on the G SC SG : T r i p m o d e setting, ground fault (short-circuit) protection
signaling can trigger a single-pole or three-pole trip that can activate the ARC function.
If the trip mode setting is 1/3-pole trip w. HSR, then when there is single-pole starting of
the distance protection function there will be a trip in the phase in which the starting
condition is present. When there is multi-pole starting of the distance protection function,
ground fault (short-circuit) protection signaling will reach a three-pole trip decision. If one
of the other two operating modes has been set, then ground fault (short-circuit)
protection signaling always generates a three-pole trip. If the operating mode is 3p-pole
trip w/o. HSR, then the ARC will be blocked by a trip generated by ground fault (short-
circuit) protection signaling.
Echo function
When a signal is received, an echo pulse can be formed – depending on the setting –
if ground fault (short-circuit) protection has not detected a fault in the backward direction.
The receive signal must be present for a period longer than the set operate delay in
order for the echo pulse to be activated. If the circuit breaker is in the open position,
then the operate delay is not active. The echo pulse is transmitted to the remote station
for the set pulse duration. When the echo pulse is activated, a set blocking time is also
started, during the course of which a new echo pulse is prevented. This prevents a
permanent signal from being transmitted.
GSCSG: Echo
on receive
[ 023 080 ]
0
1
0: No
1: Yes
GSCSG: Channel
mode
[ 023 078 ]
1
2
1: Independent
channel GSCSG: Operate GSCSG: Pulse
delay echo duration echo
2: Common channel [ 023 081 ] [ 023 082 ]
GSCSG: Send
signal
[ 043 059 ]
GFSC: IN> GSCSG: Send
triggered S1 1 internal signal
304 002
[ 039 088 ]
R1
GSCSG: Receive
EXT
[ 043 055 ]
PSIG: Receive
305 165
GSCSG: Frequ.mon.
triggered
304 000
GFSC: Fault
backward / BS
[ 039 091 ]
MAIN: CB closed
3p
[ 031 042 ]
MAIN: CB closed
sig. EXT
[ 036 051 ]
GSCSG: tBlock
echo
[ 023 083 ]
45Z6310A_EN
When the inrush stabilization function is triggered, the first stage of DTOC protection is
blocked.
Enabling or disabling
DTOC protection
DTOC protection can be disabled or enabled using setting parameters. Moreover,
enabling can be carried out separately for each parameter subset.
1 2 3 4 5 6 7
DTOC: Blocking
tI> EXT
[ 041 060 ]
MAIN: Inrush &
stabil. trigg
306 014
MAIN: Protection
active & DTOC: tI>
306 001 c PSx
DTOC: I> [ * ]
DTOC: Enabled c PSx
[ * ]
[ 040 120 ]
t 0 DTOC: tI> elapsed
IA >
-1
IB [ 040 010 ]
47Z11ALA_EN
D5Z52ALA_EN
Ineg =
1
( 2
⋅ I + a ⋅ IB + a ⋅ IC
3 A
) Ineg =
1
⋅ (I + a ⋅ IB + a² ⋅ IC )
3 A
a = e j120°
2
a = e j240°
Monitoring the
residual current
Depending on the setting, the P43x monitors the residual current, derived from the three
phase currents or measured at the current transformer T4.
The residual current is monitored to determine whether it exceeds the set thresholds.
After the set operate delays have elapsed, a signal is issued. The operate delays may
be blocked via appropriately configured binary signal inputs.
Direction-dependent trip of
the residual current stages
The P43x determines the angle between the residual current and the neutral-
displacement voltage for the direction determination. The direction determination is
enabled when a current stage is started and the neutral-displacement voltage exceeds
the set threshold DTOC: V N G > P S x . The measured angle is displayed. The position
of the straight line separating forward and backward (reverse) directions is determined
by setting D T O C : A n g l e p h i G . A forward or backward (reverse)-directional
decision results if the following angle conditions are met:
ϕG: Setting D T O C : A n g l e p h i G
V C-G
Forward
direction
+
90o
phiG
phi(IG)
V G-N = -V N-G V A-G
IG
Backward (reverse)
direction
V B-G
47Z1090A_EN
3-281 Directional characteristic of definite-time overcurrent protection (DTOC). Angle phiG corresponds to setting D T O C : A n g l e p h i G
(004 092).
After the operate delay has elapsed, a trip signal of the respective residual current stage
is issued if the set direction matches the measured direction.
As the IN> starting in the residual current stage commences, the hold time is reset.
At the same time, the starting time is accumulated when IN> starting commences.
As the IN> starting ends, timer stage D T O C : P u l s . p r o l . I N > , i n t P S x is started
and the charging of the accumulation buffer is thereby lengthened by the set value of
the timer stage.
The accumulation result is compared to the settable limit value at
DTOC: tIN>, interm. PSx.
When the limit value is reached and the general starting signal is present, then a trip
signal is issued, D T O C : T r i p s i g . T I N > , i n t m . , which can be configured to the
trip commands 1 and 2.
MAIN: Fct.assig.trip cmd.1
(Address 021 001)
MAIN: Fct.assig.trip cmd.2
(Address 021 002)
If the limit value is reached while timer stage D T O C : P u l s . p r o l . I N > , i n t P S x
is running, then a trip will occur when the next general starting phase commences.
Each time the IN> trigger stage is reset, the set hold-time
(D T O C : H o l d - t . t I N > , i n t m P S x ) is restarted. When the hold time has elapsed
or after the hold-time logic has issued a trip
(D T O C : T r i p s i g . t I N > , i n t m .), accumulation is stopped and the accumulation
buffer is cleared.
DTOC: Puls.prol.
IN>,intPSx
[ * ]
DTOC: tIN,interm.
PSx
[ * ]
DTOC: Hold-t.
tIN>,intmPSx
[ * ]
DTOC: Pulse
prolong. runn.
305 462
DTOC: H.-time
tIN>,i. runn
[ 040 086 ]
MAIN: General DTOC: tIN>,interm.
starting elapsed
[ 036 000 ] [ 040 099 ]
49Z6449 A_EN
DTOC: Starting
IN>
[ 035 028 ]
DTOC: Pulse
prolong. runn.
305 462
DTOC: H.-time
tIN>,i. runn
[ 040 086 ]
DTOC: t2 N
305 454
Settings
49Z6450 A_EN
3-285 Signal flow for values below the accumulation limit value
DTOC: Starting
IN>
[ 035 028 ]
DTOC: Pulse
prolong. Runn.
DTOC: H.-time
tIN>,i. runn
[ 040 086 ]
DTOC: t2 N
49Z6451 A_EN
When the inrush stabilization function is triggered, the IDMT function is blocked.
Disabling or enabling
IDMT protection
IDMT protection can be disabled or enabled using a setting parameter. Moreover,
enabling can be carried out separately for each parameter subset.
IDMT: General
Enable USER
IDMT: Enable
0: No
1: Yes
IDMT: Enable
SGx
0: No
1: Yes
45Z5048A_EN
Time-dependent
characteristics
All three measuring systems operate independently of each other and can be set
separately. The user can select from a large number of characteristics (see table
below). The IDMT protection function can be operated in a directional or a non-
directional mode. The user may use either the directional decision from the distance
measuring system or the directional decision formed from negative-sequence current
and voltage. The measured value is the maximum phase current, the negative-
sequence current, or the residual current, depending on the measuring system.
The P43x calculates the negative-sequence current from the three phase current values
according to this equation. The result depends on the rotary field direction setting for
phase rotation.
Depending on the setting, the residual current to be monitored is either derived by the
P43x from the three phase currents or measured at current transformer T 4.
The protection function is triggered if 1.5 x the reference current is exceeded and the set
directional condition is satisfied. A trip signal is issued as a function of the characteristic
curve, although this trip signal can be blocked via an appropriately configured binary
signal input. The tripping characteristics available for selection are shown in
figures 3-289 to 3-292.
1000 1000
100 100
k=10
10 10 k=10
t/s k=1
t/s
1 1 k=1
k=0.1
0.1 0.1
k=0.1
k=0.01
0.01 0.01 k=0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
D5Z50K1A D5Z50K2A
1000 1000
100 100
k=10
10 10
k=1
t/s t/s
k=10
1 1
k=0.1
k=1
0.1 0.1
k=0.01
k=0.1
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
k=0.01
I/Iref I/Iref
D5Z50K3A D5Z50K4A
100 100
10 k=10 10
k=10
t/s t/s
1 k=1 1
k=1
I/Iref I/Iref
D5Z50K5B D5Z50K6B
1000
100
10
t/s
k=10
1
k=1
0.1
k=0.1
0.01 k=0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
D5Z50K7B
Characteristic No. 7
1000 1000
100 100
10 10
t/s t/s
k=10
1 1
k=10
k=1
0.1 0.1
k=1
k=0.1
0.01 k=0.01 0.01 k=0.1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
D5Z50K8B D5Z50K9B
1000
100
k=10
10
t/s k=1
1
k=0.1
0.1
k=0.01
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
D5Z50KAB
Characteristic No. 10
1000 1000
100 100
k=10
k=10
10 10
t/s k=1 t/s
k=1
1 1
k=0.1
k=0.1
0.1 0.1
k=0.01
k=0.01
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
D5Z50KBA D5Z50KCA
KI,N * Iref,N
t/s 10
t/s
1
1 10 I/Iref 100
IN/Iref,N
47Z1003B_EN
3-293 Influence of the minimum operate value and the minimum trip time on the IDMT characteristics
47Z1000A_EN
Internally 100 %
97 %
cumulated
relative trip
time 0%
Trip signal
t
47Z1002A_EN
3-295 Reset behavior of the IDMT trip signal when the ANSI/IEEE characteristics with reset behavior according to characteristic is selected
Directional measurement
The IDMT protection function determines the fault direction from the negative-sequence
voltage and current. The negative-sequence voltage and current are calculated by the
P43x based on the following equations, depending on the phase sequence setting:
V neg =
1
3
( 2
⋅ V A −G + a ⋅ V B − G + a ⋅ V C −G )
I neg =
1
( 2
⋅ I + a ⋅ IB + a ⋅ IC
3 A
)
Phase sequence A-C-B:
(alternative terminology:
Anti-clockwise rotating field):
V neg =
1
3
( 2
⋅ V A −G + a ⋅ V B − G + a ⋅ V C −G )
Ineg =
1
(
⋅ I + a ⋅ IB + a 2 ⋅ IC
3 A
)
a = e j120°
2
a = e j240°
The voltage used for directional measurement is corrected for the voltage drop at the
fault impedance. The set impedance of the phase-to-ground loops of zone 1 of the
polygon characteristic is used for correction. For directional measurement to be
enabled, the corrected negative-sequence voltage needs to exceed a minimum
threshold of 0.05 Vnom/√3, and the negative-sequence current needs to exceed a
threshold of 0.03 Inom + 0.02 Imax. The device’s decision is 'Forward direction' if the angle
lies in the range of −105° ≤ ϕ ≤ 0° .
Improved directional
measurement
for series compensated
line applications
For the IDMT function there is an improved directional measurement for compensated
line applications available.
The following settable parameter is used to correct the measuring voltage for IDMT:
VBG
Backward direction
-Vneg,corr (VAG)
-1050
Ineg
Forward direction
VCG
47Z1001A_EN
Directional setting
Each IDMT measuring system may be operated in directional or non-directional mode.
In directional mode, the directional decision that is used is either the one reached by
distance protection or the one formed by the IDMT function from the negative-sequence
current and voltage – depending on the setting. If the measuring voltage is faulty, the
measuring systems operate in non-directional mode or they are blocked - depending on
the setting.
GFDSS: Enable
PSx
[ * ]
0
1
0: no
1: yes
GFDSS: General
enable USER
[ 016 060 ]
GFDSS: Enabled
& [ 042 096 ]
0
1
0: no
1: yes
&
MAIN: Protection
active
306 001
GFDSS: Operating
mode
[ 016 090 ]
1
2
3
1: Steady-state power
2: Steady-state current
3: Steady-state admitt.
GFDSS: GF (pow.)
& ready
[ 038 026 ]
GFDSS: GF (curr.) GFDSS: GF (pow.)
eval. EXT not ready
[ 038 020 ] [ 038 027 ]
GFDSS: GF (curr.)
& ready
[ 038 028 ]
GFDSS: GF (curr.)
not ready
[ 038 029 ]
GFDSS: GF (curr.)
evaluat.
[ 039 071 ]
GFDSS: Admit-
& tance ready
[ 038 167 ]
EWATT: Eval-
uation VNG PSx
[ * ]
VN-G 2
1
VA-G
VB-G 1 ... 2 GFDSS: VN-G
304 150
VC-G
1: Calculated
2: Measured
Ground fault direction determination using steady-state values requires the neutral-point
displacement voltage and the residual current values to be able to determine a ground
fault direction. The frequency provided by the setting f/fnom is filtered from these values
by using a Fourier analysis. Three periods are used for evaluation if the time stage
G F D S S : t V N G > has been set to a time delay equal to or greater than 60 ms. This
will result in the suppression of typical ripple-control frequencies in addition to all integer-
frequency harmonics. If the time stage was set to a time delay less than 60 ms only one
period will be used for filtering.
The measurement is enabled when the time delay set at G F D S S : t V N G > and which
was triggered by VNG> has elapsed. Depending on the selected operating mode (e.g.
'cos phi circuit' or 'sin phi circuit') the sign of the active power (G F D S S : O p . m . G F
p o w . / a d m P S x 'cos phi circuit') or of the reactive power (G F D S S : O p . m . G F
p o w . / a d m P S x 'sin phi circuit') is used to determine the direction. Connection of the
measuring circuits is taken into account by the setting at G F D S S : M e a s .
d i r e c t i o n P S x . With the standard connection, a decision for ‘LS’ is reached in the
case of a ground fault on the line side and ‘BS’ in the case of a ground fault on the
busbar side.
DIST: General
starting
[ 036 240 ] t 0
GFDSS: Grd.
fault pow./adm.
[ 009 037 ]
GFDSS: VNG>
triggered
304 151
GFDSS: f/fnom
C (P.meas.) PSx
[ * ]
2 2
C C
GFDSS: Direction
LS
Q 304 153
GFDSS: Direction
BS
304 154
GFDSS: P
304 155
GFDSS: Q
304 156
Parameter GFDSS: VNG> GFDSS: f/fnom GFDSS: tVNG> GFDSS: Op.m.GF GFDSS: Meas.
PSx (P.meas.) PSx PSx pow./adm PSx direction PSx
set 1 016 062 016 091 016 061 016 063 016 070
set 2 000 233 001 044 000 230 000 236 001 002
set 3 000 234 001 045 000 231 000 237 001 003
set 4 000 235 001 046 000 232 000 238 001 004
49Z64BKA_EN
3-302 Characteristic for ground fault direction determination using steady-state values, 'cos phi circuit' operating mode
3-303 Characteristic for ground fault direction determination using steady-state values, 'sin phi circuit' operating mode
GFDSS: GF (pow.)
ready
[ 038 026 ]
GFDSS: Op.m.GF
pow./adm PSx GFDSS: IN,act>/
[ * ] C reac> LS PSx
1, 3, 4 [ * ]
1: cos phi circuit
2, 3, 4
2: sin phi circuit
GFDSS: P
304 155
IN,act 1, 3
GFDSS: VNG GFDSS: IN,act>/
filtered C reac> BS PSx
304 152 [ * ]
GFDSS: Q
304 156
IN,reac 2, 4
GFDSS: Curr.
4 IN,reac p.u.
[ 004 046 ]
3
GFDSS: Current
1 ... 2 IN,act p.u.
[ 004 045 ]
GFDSS: Direction
LS
304 153
GFDSS: Direction
BS
304 154
GFDSS: Starting
forward/LS
[ 009 040 ]
GFDSS: Trip
signal forw./LS
[ 009 031 ]
GFDSS: Sector
C angle LS PSx GFDSS: Direct.
[ * ] forward/LS
[ 009 035 ]
C GFDSS: Sector
angle BS PSx
[ * ] GFDSS: Direct.
backward/BS
[ 009 036 ]
< sector angle BS
GFDSS: GF (curr.)
not ready
[ 038 029 ]
GFDSS: Starting
backward/BS
[ 009 041 ]
Parameter GFDSS: Op.m.GF GFDSS: Sector GFDSS: Sector GFDSS: IN,act>/ GFDSS: IN,act>/
pow./adm PSx angle LS PSx angle BS PSx reac> LS PSx reac> BS PSx
set 1 016 063 016 065 016 068 016 064 016 067
set 2 000 236 000 242 000 248 000 239 000 251
set 3 000 237 000 243 000 249 000 240 000 252
set 4 000 238 000 244 000 250 000 241 000 253
3-304 Output of the direction decisions with the 'Steady-state power' operating mode
The frequency provided by the setting f/fnom is filtered from the residual current value by
using a Fourier analysis. Three periods are used for evaluation. If the residual current
value exceeds the set threshold a ground fault signal is issued after the settable operate
delay has elapsed.
GFDSS: Admittance
ready
[ 038 167 ]
GFDSS: GF (pow.)
ready
[ 038 026 ]
GFDSS: GF GFDSS: f/fnom GFDSS: IN> GFDSS: Operate GFDSS: Release
(curr.) ready C (I.meas.) PSx PSx delay IN PSx delay IN PSx
[ 038 028 ] [ * ] [ * ] [ * ] [ * ]
GFDSS: Ground
DIST: General fault (curr.)
starting [ 009 038 ]
[ 036 240 ]
t 0 0 t
IN
GFDSS: Op.
delay IN
elapsed
304 157
GFDSS: IN>
triggered
304 158
GFDSS: IN
filtered
304 159
GFDSS: Curr. IN
filt. p.u.
[ 004 047 ]
1
0: don't execute
MAIN: General 1: execute
reset USER
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
GFDSS: Reset
counters EXT
[ 005 245 ]
12Z61BRB_EN
To determine a ground fault direction the steady-state admittance evaluation requires the
neutral-point displacement voltage and the residual current values. The frequency
provided by the setting f/fnom is filtered from these values by using a Fourier analysis.
The measurement is enabled when the time delay set at G F D S S : t V N G > and which
was triggered by VNG> has elapsed. Depending on the selected operating mode (e.g.
'cos phi circuit' or 'sin phi circuit') the sign of the active power (G F D S S : O p . m . G F
p o w . / a d m P S x 'cos phi circuit') or of the reactive power (G F D S S : O p . m . G F
p o w . / a d m P S x 'sin phi circuit') is used to determine the direction. Connection of the
measuring circuits is taken into account by the setting at G F D S S : M e a s .
d i r e c t i o n P S x . With the standard connection, a decision for ‘LS’ is reached in the
case of a ground fault on the line side and ‘BS’ in the case of a ground fault on the
busbar side. Phase-angle errors of the system transformers can be compensated with
the setting at G F D S S : C o r r e c t i o n a n g l e P S x .
GFDSS: Admittance
ready
[ 038 167 ] t 80 ms
GFDSS: Grd.
fault pow./adm.
[ 009 037 ]
GFDSS: VNG>
triggered
304 151
GFDSS: f/fnom
C (P meas.) PSx
[ * ]
2 2
1: cos phi circuit 1: Standard
2: sin phi circuit 2: Opposite
GFDSS: Correction
C angle PSx
[ * ]
C C
GFDSS: Direction
LS
Q 304 153
GFDSS: Direction
BS
304 154
GFDSS: P
304 155
GFDSS: Q
304 156
Parameter GFDSS: VNG> GFDSS: f/fnom GFDSS: tVNG> GFDSS: Op.m.GF GFDSS: Correction GFDSS: Meas.
PSx (P meas.) PSx PSx pow./adm PSx angle PSx direction PSx
set 1 016 062 016 091 016 061 016 063 016 110 016 070
set 2 000 233 001 044 000 230 000 236 001 026 001 002
set 3 000 234 001 045 000 231 000 237 001 027 001 003
set 4 000 235 001 046 000 232 000 238 001 028 001 004
12Z6245 B_EN
The trip signal in forward direction issued by the ground fault direction determination
using steady-state values (GFDSS) is blocked by the auto-reclosing control function
(ARC) when this function is able to issue a trip command.
3-308 Characteristic for ground fault direction determination using steady-state admittance, 'cos phi circuit' operating mode
The trip signal in forward direction issued by the ground fault direction determination
using steady-state values (GFDSS) is blocked by the auto-reclosing control function
(ARC) when this function is able to issue a trip command.
3-309 Characteristic for ground fault direction determination using Steady-state admittance, 'sin phi circuit' operating mode
GFDSS: Admittance
ready
[ 038 167 ]
C GFDSS: G(N)> /
GFDSS: Direction LS B(N)> LS PSx
304 153 [ * ]
GFDSS:Op.m.GF
pow./adm PSx
[ * ]
1, 3, 4, 5 GFDSS: G(N)> /
1: cos phi circuit C B(N)> BS PSx
[ * ]
2, 3, 4, 5
2: sin phi circuit
GFDSS: Starting
GFDSS: P backward/BS
304 155 [ 009 041 ]
G(E) 1, 3
GFDSS: VNG filtered
304 152
GFDSS: Q
304 156
B(E) 2, 4
Y(E) 5
GFDSS: Admitt.
Y(N) p.u.
[ 004 191 ]
5 GFDSS: Conduct.
G(N) p.u.
4 [ 004 192 ]
GFDSS: Suscept.
3 B(N) p.u.
[ 004 193 ]
1 ... 2
GFDSS: Trip
signal forw./LS
[ 009 031 ]
t 0 0 t GFDSS: Direct.
forward/LS
[ 009 035 ]
t 0 0 t GFDSS: Direct.
backward/BS
[ 009 036 ]
GFDSS: GF (curr.)
not ready
[ 038 029 ]
3-310 Output of the direction decisions with the 'Steady-state admittance' operating mode
Non-directional ground
fault determination
The admittance value from the ground return is used for evaluation. If the admittance
value exceeds the set threshold a ground fault signal is issued after the settable operate
delay has elapsed.
The trip signal from the non-directional ground fault determination is blocked by the auto-
reclosing control function (ARC) when this function is able to issue a trip command.
GFDSS: Oper.delay
Y(N)elaps
304 175
t 0 0 t GFDSS: Trip
IN Y(N)>
[ 009 075 ]
GFDSS: GF (curr.)
ready
[ 038 028 ]
GFDSS: GF (pow.)
ready
[ 038 026 ] GFDSS: Trip
signal Y(N)>
[ 009 072 ]
GFDSS: Starting
Y(N)>
[ 009 074 ]
The number of ground faults and directional decisions are counted. The counters may
be reset either individually or together with other counters. (See also section 'Resetting
Actions'.)
GFDSS: Reset
counters USER
[ 003 004 ]
1 ≥1
MAIN: General 0: don’t execute
reset USER 1: execute
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
GFDSS: Reset
counters EXT
[ 005 245 ]
12Z6191 B_EN
The ground fault tripping function is used to immediately switch off a line after it is
connected if it is unbiased and contains a ground fault. If the line is biased, then no trip
occurs.
In order to determine whether the line is biased, the P43x monitors the phase-to-phase
voltage VA-B on the line side for values exceeding the fixed threshold of 0.7 Vnom.
The neutral-point displacement voltage, VN-G, on the busbar and the line sides is used
as the criterion for a ground fault. The neutral-displacement voltage on the line side is
monitored by the P43x. The threshold can be set (see 'Distance Protection' and 'Ground
Fault Detection'). On the busbar side, monitoring must be handled by an external
device. The signal from this external device is passed on to the P43x through an
appropriately configured binary signal input (G F T R P : V N G > t r i g g e r e d E X T ).
A trip occurs if the following conditions are satisfied simultaneously within 100 ms after
voltage recovery:
Ground fault tripping will be blocked if there is a fault in the voltage measuring circuits.
Ground fault protection signaling (GFSIG) operates only in conjunction with ground fault
direction determination using steady-state values (GFDSS). The GFSIG function is used
for selective clearance of ground faults. The directional decisions issued by the GFDSS
function are transmitted to the device at the remote station.
They can be transmitted by way of a signal transmission device or over pilot wires. If
pilot wires are used for ground fault protection signaling, they are continuously checked
by an internal monitoring function. The communication link involving pilot wires is
formed by linking either the make contact or the break contact of the transmitting relay,
depending on the transmitting relay mode selected (' Transm.relay make co' or '
Transm.relay break c'), to the G F S I G : R e c e i v e E X T input of the remote station.
The pilot wire loop is closed during normal operation of the power system. If both
devices detect a ground fault in the forward direction (LS), the pilot wire loop remains
closed. A trip signal is issued once the set operate delay has elapsed.
The pilot wire DC loop will be opened if the GFDSS function detects a ground fault in
backward (reverse) direction (BS). If the device at the remote station detects a ground
fault in forward direction (LS), the protection device does not trip as the pilot wire DC
loop is already open. The send signal is reset after a settable time delay has elapsed.
If a single-pole ground fault occurs while the pilot wire DC loop is disrupted then a trip
will occur, regardless of the received signal.
Testing the
communications link
The communications link can be tested. For this purpose a 500 ms send signal is issued
through a binary signal input or by means of a setting parameter. The remote station
receives this signal if the transmission link is in order.
GFSIG: General
enable USER
[ 016 078 ]
0
1
0: No
1: Yes
GFSIG: Enable
PSx
[ * ] GFSIG: Enabled
[ 040 091 ]
0 GFSIG: DC loop
op. mode PSx
1 [ * ]
GFSIG: Send
0: No (transm.relay)
1: Yes 1 [ 037 089 ]
MAIN: Protection
active 2
306 001
GFSIG: Test 1: Transm.relay
telecom. USER break c
[ 016 079 ] 2: Transm.relay
make co
0
GFSIG: Rel. time
1 send PSx
[ * ]
0: don't execute
1: execute GFSIG: Send
(signal)
GFSIG: Test [ 037 088 ]
telecom. EXT
[ 037 045 ]
GFSIG: Test
telecom.
[ 034 025 ]
GFSIG: Operate
delay PSx
[ * ]
GFDSS: Release
delay BS PSx
[ * ]
GFSIG: Telecom.
GFDSS: Grd. fault faulty
pow./adm. [ 038 017 ]
[ 009 037 ]
SFMON: Telecom.
faulty/GFSIG
[ 098 012 ]
Parameter GFSIG: Enable GFSIG: Operate GFSIG: DC loop GFSIG: Rel. time GFDSS: Release
PSx delay PSx op. mode PSx send PSx delay BS PSx
set 1 001 134 016 076 016 077 016 074 016 073
set 2 001 136 001 142 001 145 001 139 001 008
set 3 001 137 001 143 001 146 001 140 001 009
set 4 001 138 001 144 001 147 001 141 001 010
45Z63BWA_EN
Enabling/disabling the
transient ground fault
detection function
The transient ground fault detection function (TGFD) can be disabled or enabled using
setting parameters. It is enabled as a function of a parameter subset via
PSIG: Enable PSx.
Protection is enabled.
The transient ground fault detection function is enabled.
The nominal frequency is set to 50 Hz.
There is no external blocking.
Transient ground fault detection has issued no directional decisions.
Self-monitoring has detected no faults with transient ground fault detection.
MAIN: Protection
active
306 001
TGFD: Enable
PSx
[ * ]
1
0: No
1: Yes
TGFD: General
enable USER
[ 016 040 ]
0 TGFD: Enabled
[ 037 100 ]
1
0: No
1: Yes
MAIN: Nominal
frequ. fnom
[ 010 030 ]
50: 50 Hz SFMON: Fcts.not
perm.f.60Hz
60: 60 Hz [ 093 098 ]
TGFD: Ready
[ 037 080 ]
TGFD: Blocking
EXT
[ 004 034 ]
TGFD: Direct.
determined
[ 004 030 ]
SFMON: TGFD mon.
triggered
[ 093 094 ]
TGFD: Not ready
[ 037 081 ]
SFMON: Module N
RAM faulty
[ 093 091 ]
SFMON: Time-out
module N
[ 093 092 ]
SFMON: Invalid SW
vers. N
[ 093 093 ]
SFMON: Module N
DAC faulty Parameter TGFD: Enable
[ 093 095 ] PSx
SFMON: Module N set 1 001 054
+15V faulty
[ 093 096 ] set 2 001 055
SFMON: Module N set 3 001 056
-15V faulty set 4 001 057
[ 093 097 ]
49Z6480 A_EN
3-316 Enabling, disabling and readiness of the transient ground fault detection function
TGFD: Evaluation
VNG PSx
[ * ]
VN-G 2
1
VA-G
VB-G 1 2 TGFD: VNG
VC-G 304 200
1: Sum (VA-B-C-G)
2: Measured
Parameter TGFD: Evaluation
VNG PSx
set 1 016 048
set 2 001 058
set 3 001 059
set 4 001 060
45Z6361A_EN
Determination of ground
fault direction
A ground fault's direction can only be determined if the TGFD function is ready.
Higher frequency components are filtered out of the measured values for residual current
and neutral-point displacement voltage. Settable triggers monitor the magnitudes of the
residual current and neutral-point displacement voltage harmonics as well as the neutral-
point displacement voltage fundamental. To determine the ground fault direction the
P43x will evaluate trigger decisions by the harmonics monitoring function, separately for
the positive and negative half-waves.
Furthermore the operation of a current trigger will start a timer stage that, after it has
elapsed, will enable the TGFD function to detect further transient ground faults.
The time period after which a new transient ground fault may be detected is given by the
setting of the operate delay +40 ms.
TGFD: Hardware
fault
304 207
IN TGFD: IN,p
triggered
304 201
TGFD: VNG>
PSx TGFD: Operate
[ * ] delay PSx
[ * ]
TGFD: Ground
t 0 fault
TGFD: VNG [ 004 033 ]
304 200
t+40 ms 0
20 ms 0
TGFD: VNG>
triggered
304 203
TGFD: Measurem.
direc. PSx
[ * ]
1 TGFD:
Direction LS
Parameter TGFD: IN,p> TGFD: VNG> TGFD: Operate TGFD: Measurem. 304 204
PSx PSx delay PSx direc. PSx 1
TGFD:
set 1 016 042 016 041 016 044 016 045 Direction BS
set 2 001 064 001 061 001 067 001 073 2 304 205
45Z63EUA_EN
Directional decisions are output for the duration of the set buffer time. If the buffer time
is set to 0 s directional decisions are issued for as long as the fundamental component of
the neutral-point displacement voltage exceeds the trigger threshold set at
TGFD: VNG>.
TGFD: Hardware
fault
304 207
TGFD: Forward /
TGFD: LS
Direction LS [ 004 031 ]
304 204
TGFD: Backward /
BS
TGFD: [ 004 032 ]
Direction BS
304 205
TGFD: Direct.
TGFD: Reset t = 0 s determined
signal 100ms 0 [ 004 030 ]
304 206
TGFD: Reset
signals USER
[ 003 009 ]
0
1 ≥1 100 ms TGFD: Signals
reset
0: don't execute [ 004 141 ]
1: execute
TGFD: Reset
signals EXT
[ 004 140 ]
MT_RC: Reset
record. USER
[ 003 008 ]
1: execute
MT_RC: Reset
record. EXT
[ 005 240 ]
45Z63EXA_EN
TGFD: Ground
fault + TGFD: No. GF
[ 004 033 ] [ 004 015 ]
R
0
1 ≥1
MAIN: General 0: don't execute
reset USER 1: execute
[ 003 002 ]
1: execute
MAIN: General
reset EXT
[ 005 255 ]
TGFD: Reset
counters EXT
[ 005 246 ]
12Z61EYA_EN
Disabling or enabling
thermal overload protection
Thermal overload protection may be disabled or enabled using setting parameters.
Moreover, enabling can be carried out separately for each parameter subset.
Tripping characteristics
The maximum phase current is used to track a first-order thermal replica as specified in
IEC 255-8. The following parameters will govern the tripping parameters:
2
⎛ I ⎞
⎜⎜ ⎟⎟ − ΘP
t = τ ⋅ ln ⎝ Iref ⎠
2
⎛ I ⎞ ⎛ Θ a − Θ a,max ⎞
⎜⎜ ⎟⎟ − Θ trip ⋅ ⎜⎜1 − ⎟
⎟
⎝ Iref ⎠ ⎝ Θ max − Θ a,max ⎠
Figure 3-324 shows the tripping characteristic for Θ P = 0 % and the setting for the
maximum permissible coolant temperature and the maximum permissible protected
object temperature to identical values.
By setting the operating mode, the user selects an ‘absolute’ or ‘relative’ replica. If the
setting is for Absolute replica, the P43x will operate with a fixed trip threshold (Θtrip) of
100 %.
θtrip / %
10000
200
1000
110
τ /min
50
100 200
110
10 1000
50
t/min 200
110
1
50
30
0.1
0 1 2 3 4 5 6 7 8 9 10 11
I/Iref
D5Z50BEA_EN
3-324 Tripping characteristic for Thermal Overload Protection (tripping characteristics apply to Θ P = 0 % and the setting for the maximum
permissible coolant temperature and the maximum permissible protected object temperature to identical values)
To permit coolant temperature acquisition the analog module Y must be fitted. If this
module is not available in the P43x then the setting for T H E R M : C o o l a n t t e m p .
P S x is included in the calculation of the tripping time.
Warning
A warning signal can be set in accordance with the T H E R M : Θ w a r n i n g P S x set
operate value. Additionally, a time-to-tripping threshold (pre-trip time) can be set. When
the time left until tripping falls below this setting, a warning signal will be issued.
If the current falls below the default threshold of 0.1 Iref, the buffer is discharged with the
T H E R M : T i m . c o n s t . 2 , < I b l P S x set time constant. The thermal replica may be
reset either via a setting parameter or via an appropriately configured binary signal input.
Resetting is possible even when thermal overload protection is disabled. Thermal
overload protection can be blocked via an appropriately configured binary signal input.
The time-voltage protection function evaluates the fundamental wave of the phase
voltages and of the neutral-point displacement voltage as well as the positive-sequence
voltage and negative-sequence voltage obtained from the fundamental waves of the
three phase-to-ground voltages.
Disabling or enabling
V<> protection
V<> protection can be disabled or enabled using setting parameters. Moreover,
enabling can be carried out separately for each parameter subset.
V<>: Evaluation
VNG PSx
[ * ]
VN-G 2
1
VA-G
VB-G 1 ... 2 V<>: VNG
VC-G 305 252
1: Calculated
2: Measured
V<>: VNG
not ready
MCMON: Meas. 310 048
circ. V faulty
[ 038 023 ]
MCMON: M.circ.
VNG flty.
[ 007 214 ]
Parameter V<>: Evaluation
VNG PSx
set 1 076 002
set 2 077 002
set 3 078 002
set 4 079 002
45Z6370A_EN
V<>: Blocking
tVNG> EXT
[ 041 072 ]
V<>: tVNG>
V<>: Hyst. V<> PSx
deduc. PSx [ * ]
[ * ]
V<>: VNG>
MAIN: Protection PSx
active [ * ]
306 001
V<>: VNG
not ready
310 048 V<>: tVNG>
elapsed
[ 041 045 ]
V<>: tVNG>>
V<>: VNG elapsed
305 252
[ 041 046 ]
V<>: Starting
VNG>>
[ 042 008 ]
Parameter V<>: VNG> V<>: tVNG> V<>: VNG>> V<>: tVNG>> V<>: Hyst. V<>
PSx PSx PSx PSx deduc. PSx
set 1 076 011 076 013 076 012 076 014 076 049
set 2 077 011 077 013 077 012 077 014 077 049
set 3 078 011 078 013 078 012 078 014 078 049
set 4 079 011 079 013 079 012 079 014 079 049 45Z6371A_EN
V<>: Blocking
tVref> EXT
[ 007 036 ]
V<>: Hyst. V<> V<>: tVref>
deduc. PSx PSx
[ * ] [ * ]
V<>: Vref>
C PSx C
[ * ]
V<>: tVref>
Vref elapsed
[ 007 047 ]
V<>: Starting
V<>: Blocking Vref>
tVref>> EXT [ 007 051 ]
[ 007 037 ]
V<>: tVref>>
PSx
[ * ]
V<>: Vref>>
C PSx C
[ * ]
V<>: tVref>>
elaps.
[ 007 048 ]
V<>: Blocking V<>: Starting
tVref< EXT Vref>>
[ 007 039 ] [ 007 052 ]
V<>: tVref<
PSx
[ * ]
V<>: Blocking
tVref<< EXT Setting(s) blocked
[ 007 046 ] V<>: Starting
Vref<
[ 007 055 ]
V<>: tVref<<
PSx V<>: tVref<<
[ * ] elaps.
[ 007 054 ]
MAIN: Protection V<>: Vref<<
active C PSx C
306 001 [ * ]
MCMON: M.circ.
Vref flty.
[ 007 213 ]
V<>: Fault Vref<<
[ 007 062 ]
Setting(s) blocked
V<>: Starting
Vref<<
[ 007 056 ]
V<>: tTransient
PSx
[ * ] V<>: tVref<
elaps. trans.
[ 007 057 ]
V<>: tVref<<
elaps.trans.
[ 007 060 ]
V<>: tVref</<<
elap.trans
[ 007 063 ]
Parameter V<>: Vref> V<>: tVref> V<>: Vref>> V<>: tVref>>
PSx PSx PSx PSx
set 1 007 064 007 066 007 065 007 067
set 2 007 071 007 069 007 068 007 070
set 3 007 075 007 073 007 072 007 074
set 4 007 079 007 077 007 076 007 078
Parameter- V<>: Vref< V<>: tVref< V<>: Vref<< V<>: tVref<< V<>: tTransient V<>: Hyst. V<>
PSx PSx PSx PSx PSx deduc. PSx
set 1 007 086 007 088 007 087 007 096 076 029 076 049
set 2 007 097 007 099 007 098 007 100 077 029 077 049
set 3 007 101 007 103 007 102 007 104 078 029 078 049
set 4 007 105 007 107 007 106 007 108 079 029 079 049 45Z6372A_EN
The P43x monitors the voltage to determine whether its frequency exceeds or falls below
set thresholds. The frequency is determined from the difference in time between the
zero crossings of the voltage (voltage zeroes). The over-/underfrequency protection
function has four stages. The operation of over-/underfrequency protection will be
explained below using the first stage as an example.
Disabling or enabling
over-/underfrequency
protection
The frequency protection function can be disabled or enabled using setting parameters.
Moreover, enabling can be carried out separately for each parameter subset.
Frequency monitoring
Frequency monitoring combined with differential frequency gradient monitoring (df/dt)
Frequency monitoring combined with mean frequency gradient monitoring (∆f/∆t)
Frequency monitoring
Depending on the setting, the P43x monitors the frequency to determine whether it
exceeds or falls below set thresholds. If an operate threshold in excess of the set
nominal frequency is set, the P43x checks to determine whether the frequency exceeds
the operate threshold. If an operate threshold below the set nominal frequency is set,
the P43x checks to determine whether the frequency falls below the operate threshold.
If it exceeds or falls below the set threshold, a set timer stage is started. The timer stage
can be blocked by way of an appropriately configured binary signal input.
Frequency monitoring
combined with differential
frequency gradient
monitoring (df/dt)
In this operating mode of the over-/ underfrequency protection function, the frequency is
also checked to determine whether the set frequency gradient is reached (in addition to
being monitored for exceeding or falling below the set threshold). Monitoring for
overfrequency is combined with monitoring for a frequency increase; monitoring for
underfrequency is combined with monitoring for a frequency decrease. If both operate
conditions are satisfied, a set timer stage is started. The timer stage can be blocked by
way of an appropriately configured binary signal input.
Frequency monitoring
combined with mean
frequency gradient
monitoring (∆f/∆t)
The frequency gradient can differ for system disturbances in individual substations and
may vary over time due to power swings. Therefore it makes sense to take the mean
value of the frequency gradient into account for load-shedding systems.
Monitoring the mean value of the frequency gradient is started with the starting of
frequency monitoring. If the frequency decreases by the set value ∆f within the set
time ∆t, then the ∆t/∆f monitoring function operates instantaneously and generates a trip
signal. If a frequency change does not lead to an operate decision of the monitoring
function, then the ∆t/∆f monitoring function will be blocked until the underfrequency
monitoring function drops out. The trip signal can be blocked by way of an appropriately
configured binary signal input.
fmin/fmax measurement
For the acquisition of the minimum frequency during an underfrequency condition and for
the acquisition of the maximum frequency during an overfrequency condition, the two
following measured event values are available:
Both measured event values are reset automatically at the onset of a new overfrequency
or underfrequency situation. A manual reset and a reset with a binary signal are also
possible:
The power directional protection function determines the active and reactive power from
the fundamental currents and voltages. The sign of the active or the reactive power,
respectively, is evaluated for direction determination
Disabling or enabling
P<> protection
The power directional protection can be disabled or enabled via setting parameters.
Moreover, enabling can be carried out separately for each parameter subset.
Power determination
The device determines the active and reactive power from the fundamental waves of the
three phase currents and the phase-to-ground voltages. If the measuring-circuit
monitoring function detects malfunctioning in the voltage measuring circuit, power
determination will be blocked.
Power monitoring
The device checks the determined power values to detect whether they exceed or fall
below set thresholds. The triggers are followed by timer stages that can be blocked via
appropriately configured binary signal inputs.
Dynamic range-dependent
setting parameters
The logic diagrams following below display signal processing with the dynamic range for
the phase current measurement set to
M A I N : D y n a m i c r a n g e I = 'maximum range'. When the sensitive range is
selected, alternative parameters with a setting range that will permit lower operate values
will become effective, e.g.
P < > : P > s e n s . r a n g e P S 1 instead of
P<>: P> high range PS1.
Transient signals
If the decisions of power monitoring are to be included in the trip commands when values
have fallen below set thresholds, then it is recommended that transient signals be used.
Otherwise the trip command would always be present when the system voltage was
disconnected, and it would therefore not be possible to close the circuit breaker again.
When the active power exceeds the set thresholds, a starting results. The starting signal
is followed by the set operate and resetting delays.
P<>: Operate
delay P> PSx
[ * ]
P<>: Release
P<>: Blocking delay P> PSx
tP> EXT [ * ]
[ 035 082 ]
P<>: Signal
P<>: P> P> delayed
high range PSx [ 035 087 ]
[ * ]
P<>: Diseng.
ratio P> PSx
[ * ]
P<>: Starting
P<>: P P>
402 631 [ 035 086 ]
P<>: Operate
delay P>>PSx
[ * ]
P<>: Release
P<>: Blocking delay P>>PSx
tP>> EXT [ * ]
[ 035 083 ]
P<>: Signal
P<>: P>> P>> delayed
high range PSx [ 035 090 ]
[ * ]
P<>: Diseng.
ratio P>>PSx
[ * ]
P<>: Starting
P>>
[ 035 089 ]
3-346 The direction-dependent trip signal of the active power protection function when values exceed set thresholds
When the reactive power exceeds the set thresholds, a starting results. The starting
signal is followed by the set operate and resetting delays.
P<>: Starting
Q>
035 092
P<>: Starting
Q>>
035 095
P<>: Q> high range Diseng. ratio Operate delay Release delay
PSx
set 017 218
set 017 219
set 017 220
set 017 221
P<>: Q>> high range Diseng. ratio Operate delay Release delay
PSx
set 017 222
set 017 223
set 017 224
set 40Z5270A_EN
017 225
3-348 The direction-dependent trip signal of the reactive power protection function when values exceed set thresholds
Setting blocked
P<>: Starting P<
[ 035 054 ]
Setting blocked
P<>: Starting P<<
[ 035 060 ]
&
P<>: tP<<
elapsed trans.
[ 035 062 ]
P<>: tP</tP<<
elaps.trans
[ 035 178 ]
Parameter P<>: P< high P<>: Diseng. P<>: Operate P<>: Release
range PSx ratio P< PSx delay P< PSx delay P< PSx
set 1 017 013 017 034 017 060 017 226
set 2 017 014 017 035 017 061 017 227
set 3 017 016 017 036 017 062 017 228
set 4 017 020 017 037 017 063 017 229
P<>: P<< high P<>: Diseng.ratio P<>: Operate P<>: Release P<>: tTransient
Parameter range PSx P<< PSx delay P<<PSx delay P<<PSx pulse PSx
set 1 017 068 017 238 017 242 017 246 018 246
set 2 017 021 017 239 017 243 017 247 018 247
set 3 017 025 017 240 017 244 017 248 018 248
set 4 017 026 017 241 017 245 017 249 018 249
40Z5272B_EN
3-349 Active power monitoring when values fall below set thresholds
P<>: Starting
P<
[ 035 054 ]
Apparent > 0.010 Snom
power S
P<>: Direction
P< PSx
[ * ]
1
2
1: Forward directional
2: Backward directional
&
P<>: P+ &
402 633
P<>: P-
402 634
&
P<>: Starting
P<<
[ 035 060 ]
P<>: Direction
P<< PSx
[ * ]
1
2
1: Forward directional
2: Backward directional
P<>: Trip
3: Non-directional signal P<<
& & [ 035 064 ]
P<>: Signal P<<
delayed
[ 035 061 ]
&
&
3-350 The direction-dependent trip signal of the active power protection function when values fall below set thresholds
1
P<>: Starting P<
[ 035 054 ]
P<>: Operate
delay P< PSx
[ * ]
P<>: Release
delay P< PSx
[ * ] 2
P<>: Signal
P< delayed
[ 035 055 ]
P<>: tP<
elapsed trans.
[ 035 056 ] 3
1 P<>: Operate
delay P< PSx
*
2 P<>: Release
delay P< PSx
*
3 P<>: tTransient
pulse PSx
*
19Z5278A_EN
3-351 Performance of the transient signal and the fault signal issued by the active power monitoring
Setting blocked
P<>: Starting
Q<
[ 035 066 ]
P<>: Fault
& Q<
P<>: Blocking [ 035 069 ]
tQ<< EXT &
[ 035 053 ]
Setting blocked
P<>: Starting
Q<<
[ 035 010 ]
P<>: Fault
& Q<<
[ 035 049 ]
&
P<>: tQ<<
elapsed trans.
[ 035 016 ]
P<>: tQ</tQ<<
elaps.trans
[ 035 179 ]
Parameter P<>:
P<>:Q<Q< high P<>: Diseng. P<>: Operate P<>: Release
PSx
range PSx ratio Q< PSx delay Q< PSx delay Q< PSx
set 1 017
018 069
035 018 044 018 052 018 056
set 2 017
018 038
036 018 045 018 053 018 057
set 3 017
018 039
037 018 046 018 054 018 058
set 4 018 045
017 038 018 047 018 055 018 059
Parameter P<>:
P<>:Q<<
Q<< high P<>: Diseng.ratio P<>: Operate P<>: Release P<>: tTransient
PSx
range PSx Q<< PSx delay Q<<PSx delay Q<<PSx pulse PSx
set 1 017 079
018 085 018 095 018 213 018 236 018 246
set 2 017 086
018 046 018 096 018 214 018 237 018 247
set 3 018
017 087
049 018 097 018 215 018 238 018 248
set 4 018
017 088
051 018 098 018 216 018 239 018 249
40Z5276B_EN
3-352 Reactive power monitoring when values fall below set thresholds
P<>: Starting
Q<
[ 035 066 ]
Apparent > 0.010 Snom
power S
P<>: Direction
Q< PSx
[ * ]
1
2
1: Forward directional
2: Backward directional
&
P<>: Q+ &
402 635
P<>: Q-
402 636
&
P<>: Starting
Q<<
[ 035 010 ]
P<>: Direction
Q<< PSx
[ * ]
1
2
1: Forward directional
2: Backward directional
P<>: Trip
3: Non-directional & signal Q<<
P<>: Signal Q<< & [ 035 176 ]
delayed
[ 035 011 ]
&
&
&
3-353 The direction-dependent trip signal of the reactive power protection function when values fall below set thresholds
1
P<>: Starting
Q<
[ 035 066 ]
P<>: Operate
delay Q< PSx
[ * ]
P<>: Release
delay Q< PSx
[ * ] 2
P<>: Signal
Q< delayed
[ 035 067 ]
P<>: tQ<
elapsed trans.
[ 035 068 ] 3
1 P<>: Operate
delay Q< PSx
*
2 P<>: Release
delay Q< PSx
*
3 P<>: tTransient
pulse PSx
*
19Z5279A_EN
3-354 Performance of the transient signal and the fault signal issued by the reactive power monitoring
P<>: Direction P
& forw.
[ 035 181 ]
P<>: Starting P>
[ 035 086 ]
P<>: P-
402 634
19Z5274B_EN
P<>: Q+
402 635
P<>: Direction Q
forw.
P<>: Q-
402 636
& [ 035 193 ]
19Z 5275B_EN
The P43x features the CB failure protection function. After a trip command has been
issued the CBF function checks that the circuit breaker has actually been opened.
Enabling/disabling circuit
breaker failure protection
The function is enabled at C B F : G e n e r a l e n a b l e U S E R . If this parameter has
been activated the CBF function may be enabled or disabled using setting parameters or
through appropriately configured binary signal inputs. Parameters and configured binary
signal inputs have equal status. If C B F : E n a b l e E X T is the only function assigned
to a binary signal input, then circuit breaker protection will be enabled by a positive edge
of the input signal and disabled by a negative edge. If C B F : D i s a b l e E X T is the
only function assigned to a binary signal input, then a signal at this input will have no
effect.
CBF: General
enable USER
[ 022 080 ]
0
CBF: Enabled
1 & [ 040 055 ]
0: No
1: Yes
INP: Fct.
assignm. U xxx
[ xxx xxx ]
U x1
U x2
U x3
U xx
0
1
0: don't execute
1: execute
0
1
0: don't execute
1: execute
47Z1138 B_EN
Readiness of circuit
breaker protection
Circuit breaker failure protection will be unavailable under the following conditions:
&
CBF: Blocking EXT
[ 038 058 ]
CBF: t1 1p
[ 022 164 ] 1)
Blocked &
CBF: t1 3p
[ 022 165 ]
Blocked
CBF: t2
[ 022 166 ]
Blocked
CBF: Delay
/starting trig.
[ 022 155 ]
Blocked
CBF: Delay
/fault beh. CB
[ 022 171 ]
Blocked
CBF: Delay
/CB sync.superv
[ 022 172 ]
Blocked 1) only P435
45Z6364A_EN
Detecting a CB tripping
A break in current flow is the preferred criterion to detect a successful CB tripping.
Protection functions that have tripping criteria not directly dependent on current flow may
additionally be provided with status signals from CB auxiliary contacts for evaluation.
As long as the current flow remains higher than the set threshold value of C B F : I < ,
then the appropriate phase-selective messages, C B F : C u r r e n t f l o w A ,
C B F : C u r r e n t f l o w B , C B F : C u r r e n t f l o w C , and the C B F : C u r r e n t
f l o w P h x multiple signal will be issued continuously.
CBF: I<
[ 022 160 ]
47Z1139 D_EN
Evaluation of CB status
signals
Trip signals included in the G e n . T r i p c o m m a n d 1 , which use CB status signals
in addition to current flow monitoring, can be selected by setting
CBF: Fct.assignm. CBAux.
Applying CB status signals depends on the type of auxiliary contacts available. The
P43x can check the following CB status signals for plausibility and evaluate them:
If only one of the two possible CB status signals has been configured, then this
configured signal will always be considered plausible by the P43x.
As an alternative the status signals from the external device may be used by the P43x.
The required assignments are made by setting M A I N : S i g . a s g . C B o p e n or
M A I N : S i g . a s g . C B c l o s e d . Status signals from external devices are processed
similarly to the M A I N : C B o p e n 3 p E X T and M A I N : C B c l o s e d s i g . E X T
CB status signals.
INP: Fct.
assignm. U xxx
[ xxx yyy ]
U x01
U x02
U x03
U xxx
19Z6131 C_EN
Startup criteria
Startup of the circuit breaker failure protection function will occur when the CB is
recognized as closed during a startup criterion. The following criteria are evaluated as a
startup criterion:
CBF: Fct.
assignm. CBAux.
[ 022 159 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signal
CBF: CB pos.
implausible
[ 038 210 ]
MAIN: CB closed
>= 1p
[ 031 038 ]
U x01
U x02
U x03 &
U xnn
CBF: Start A
310 007
CBF: Start C
310 009
45Z6363A_EN
CBF: Fct.
assignm. CBAux.
[ 022 159 ]
Signal 1
Signal 2 m out of n
Signal n
Selected signals
CBF: CB pos.
implausible
[ 038 210 ]
CBF: I> >1 &
[ 022 160 ] &
IA >1 & S 1 1
IB R 1
IC
MAIN: CB closed
>= 1p
[ 031 038 ]
U x01
U x02
U x03 & >1
U xnn
CBF: Trip
t 0 signal t2
[ 038 219 ]
&
CBF: CB faulty
EXT
[ 038 234 ]
19Z6433A_EN
CBF: Trip 1p
c
[ 022 163 ]
0
1
0: No
1: Yes
CBF: Startup A t 0
[ 038 212 ] >1
CBF: Startup B
[ 038 213 ]
CBF: Trip
CBF: Startup C & signal t1, A
[ 038 214 ] [ 038 216 ]
CBF: Trip
& signal t1, B
[ 038 217 ]
& CBF: Trip
signal t1, C
[ 038 218 ]
CBF: Trip
>1 >1 signal t1
[ 038 215 ]
CBF: t1 3p
c
[ 022 165 ]
CBF: t2
c
[ 022 166 ]
t 0 CBF: Trip
>1 signal t2
t 0 [ 038 219 ]
>1
CBF: CB faulty &
EXT
[ 038 234 ]
47Z1133B_EN
Trip commands
While trip signals issued by the CB failure protection function have no timer stages
available the user can set minimum time delays for trip commands.
By appropriate setting it can be selected that trip commands, issued by the CB failure
protection function, will operate in latching mode. The corresponding trip command, set
to latching mode, will remain active until reset by operating parameters or through an
appropriately configured binary signal input.
CBF: Min.dur.
trip cmd.t1
[ 022 167 ]
MAIN: Trip cmd. CBF: Trip
blocked t 0 command t1
[ 021 013 ] & [ 038 220 ]
CBF: Trip
signal t1
[ 038 215 ]
CBF: Latching
trip cmd.t1
[ 022 169 ]
0 & S 1 1
1 R 1
CBF: Min.dur.
0: No trip cmd.t2
1: Yes [ 022 168 ]
CBF: Trip
command t2
& t 0 [ 038 224 ]
CBF: Trip
signal t2
[ 038 219 ]
CBF: Latching
trip cmd.t2
[ 022 170 ]
0 & S 1 1
1 R 1
0: No
1: Yes
MAIN: Rset.
latch.trip USER
[ 021 005 ]
0
MAIN: Latch.
trip c. reset
1 1 [ 040 139 ]
0: don't execute
1: execute
MAIN: Reset
latch.trip EXT
[ 040 138 ] 43Z6362A_EN
CBF: Min.dur.
trip cmd. t1
[ 022 167 ]
CBF: Latching
trip cmd. t1 t 0
[ 022 169 ]
t 0
0 t 0
1 t 0
0: No CBF: Trip
1: Yes >1 command t1, A
MAIN: Trip cmd. [ 038 221 ]
blocked
[ 021 013 ] &
0 t 0
1 CBF: Trip
>1 command t2
0: No [ 038 224 ]
&
1: Yes
CBF: Trip
signal t2 >1
[ 038 219 ]
& S 1 1
R 1
MAIN: Rset.latch.
trip USER
[ 021 005 ]
0
MAIN: Latch.
1 >1 1 trip c. reset
[ 040 139 ]
0: don't execute
1: execute
MAIN: Reset
latch.trip EXT
[ 040 138 ]
47Z1134B_EN
Starting trigger
The C B F : S t a r t i n g signal will be issued when the C B F : S t a r t i n g t r i g . E X T
signal is presented to an appropriately configured binary signal input and a general
starting condition is present. C B F : T r i p s i g n a l will be issued after timer stage
C B F : D e l a y / s t a r t i n g t r i g . has elapsed.
CBF: Delay/
starting trig.
[ 022 155 ]
45Z6368A_EN
Fault behind CB protection recognizes such faults through the current criterion if the
circuit breaker does not indicate that it is closed after the time delay set at
C B F : D e l a y / f a u l t b e h . C B has elapsed.
CBF: Delay
CBF: I< /fault beh. CB
[ 022 160 ] [ 022 171 ]
CBF: Fault
IA & & t 0 behind CB
[ 038 225 ]
IB
IC
MAIN: CB open 3p
EXT
[ 031 028 ]
MAIN: CB closed
sig. EXT
[ 036 051 ]
MAIN: CB closed 1)
A EXT
[ 031 029 ]
MAIN: CB closed 1)
B EXT
[ 031 030 ]
MAIN: CB closed 1)
C EXT
[ 031 031 ]
CBF: CB pos.
implausible
[ 038 210 ]
1) only P435 45Z6365A_EN
CB synchronization
supervision
CB synchronization supervision recognizes states where not all circuit breaker contacts
are open or closed. This function uses both current flow monitoring and evaluation of
CB status signals to detect CB synchronization. In order to bridge CB operate times the
C B F : D e l a y / C B s y n c h . s u p e r v time delay can be used. When this time period
has elapsed the C B F : T r i p S i g C B s y n c h . s u p e r signal is issued. Poles that are
recognized as being open will still be signaled.
CBF: Delay
/CB sync.superv
[ 022 172 ]
CBF: CB pos.
implausible t 0 CBF: TripSig
[ 038 210 ] & CBsync.super
[ 038 226 ]
MAIN: CB closed 1)
A EXT
[ 031 029 ]
MAIN: CB closed 1)
B EXT
[ 031 030 ]
MAIN: CB closed 1)
C EXT
[ 031 031 ]
&
MAIN: CB open 3p
EXT
[ 031 028 ]
MAIN: CB closed
sig. EXT
[ 036 051 ]
CBF: CBsync.
<3 superv A open
& [ 038 227 ]
CBF: CBsync.
& superv B open
[ 038 228 ]
CBF: CBsync.
CBF: I< & superv C open
[ 022 160 ] [ 038 229 ]
IA &
IB
IC
1) only P435
45Z6366A_EN
If any of the measured values exceeds or falls below one of these thresholds, then a
signal is issued after the associated time delay has elapsed.
VC-G
t 0
VPP,max LIMIT: tVPP>>
elapsed
VPP,min [ 040 229 ]
t 0
LIMIT: tVPP<
elapsed
[ 040 230 ]
t 0
LIMIT: tVPP<<
elapsed
[ 040 231 ]
t 0
LIMIT: tVPG>
elapsed
[ 040 224 ]
t 0
VPG,max LIMIT: tVPG>>
elapsed
VPG,min [ 040 225 ]
t 0
LIMIT: tVPG<
elapsed
[ 040 226 ]
t 0
LIMIT: tVPG<<
elapsed
[ 040 227 ]
47Z0154 B_EN
3-371 Limit value monitoring of maximum and minimum phase-to-phase voltages and maximum and minimum phase-to-ground voltages
LIMIT: General
enable USER
014 010
LIMIT:
Enabled
040 074
0: no
MAIN: Device 1: yes
on-line LIMIT: Vref> LIMIT: tVref>
003 030
042 144 042 148
1: yes (= on)
LIMIT: tVref>
elapsed
042 152
LIMIT: tVref>>
Vref elapsed
042 153
LIMIT: tVref<
elapsed
042 154
LIMIT: tVref<<
abgelaufen
042 155
19Z5215A_EN
Programmable (or user-configurable) logic enables the user to link binary signals within
a framework of Boolean equations.
Binary signals in the P43x may be linked by logical 'OR' or 'AND' operations with the
option of additional NOT operations by setting L O G I C : F c t . a s s i g n m . o u t p . n ,
where n = 1 to 32. The Boolean equations need to be defined without the use of
brackets. The following rule applies to the operators: ‘NOT’ before ‘AND’ before ‘OR’.
Logical operations can be controlled through the binary signal inputs in different ways.
Binary input signals L O G I C : I n p u t n E X T (n = 1 to 16) have an updating function,
whereas input signals L O G I C : S e t n E X T (n = 1 to 8) are latched. The logic can
only be controlled from the binary signal inputs configured for L O G I C : S e t n E X T
if the corresponding reset input, L O G I C : R e s e t n E X T , has been configured to a
binary signal input. If only one or neither of the two functions is configured, then this is
interpreted as ‘Logic externally set’. If the input signals of the two binary signal inputs
are implausible (such as when they both have a logic value of ‘ 1 ’), then the last
plausible state remains stored in memory.
When using the programmable logic, the user must carry out a functional type test to
conform with the requirements of the relevant protection/control application. In particular,
it is necessary to verify that the requirements for the implementation of logic linking (by
setting) as well as the time performance during device startup, during operation and
when there is a fault (device blocking) are fulfilled.
3-376 Control of logic operations via setting parameters or stored input signals
3-377 Setting options for programmable logic (shown here for output 1)
The output signal of an equation can be fed into a further, higher order, equation as an
input signal thus creating a sequence of interlinked Boolean equations. The equations
are processed in the sequence defined by the order of each equation. It should be noted
that in the case of overlapping equations, the result is provided by the equation with the
highest order.
The output signal of each equation is fed to a separate timer stage with two timer
elements and a choice of operating modes. This offers the possibility of assigning a
freely configurable time characteristic to the output signal of each Boolean equation. In
the 'Minimum time' operating mode, the setting of timer stage t2 has no effect. Figures
3-378 to 3-382 show the time characteristics for the various timer stage operating
modes.
Note: If the device is switched to 'off-line' the equations are not processed and all
outputs are set to a logic value of ' 0 '.
The P43x is designed to control up to 3 switchgear units. The bay type defines the
topology of a bay with its switchgear units.
Setting options for the P43x and the different possibilities to integrate a switchgear unit
into the functional sequence of the P43x (processing of status signals only or controlling
and signaling) will be explained below, using one switchgear unit as an example.
Function group DEV01 will be used throughout in this example. If a signal is identified in
the function diagrams by function group "C O M M 1 :" with a blank address [--- ---], it will
indicate that it is a signal to or from the communication interface and that it has not been
assigned an address.
The status signals ‘Open’ and ‘Closed’ are assigned to binary signal inputs. The signals
conditioned by debouncing and chatter suppression (see: ‘Main Functions of the P43x’)
are used for further processing. If no logic value of '1' is present at any of the two binary
signal inputs, the running time monitoring function is started. For the duration of the set
time period for running time monitoring or until the contacts on the switchgear unit are
back to a defined position - either ‘Open’ or ‘Closed’ - the signal ‘Intermediate position’ is
issued.
The ‘Faulty position’ signal is issued if the contacts on the switchgear unit have not
reached either their ’Open’ or ‘Closed’ position after the set time period for running time
monitoring and the time delay set in M A I N : D e l a y M a n . O p . S u p e r v . have
elapsed. If D E V 0 1 : S t a t . i n d . i n t e r m . p o s . is set to 'Yes', a time delay of 5 s is
started. Once this time delay has elapsed and if there is no status signal for the position,
the state actually present at the binary inputs will be signaled.
Switch truck
For switchgear units mounted on switch trucks with switch truck plugs, it is possible to
configure a single-pole position signal from the switch truck plug. If such a configuration
has been assigned, the status signal for the position of the associated switchgear unit is
set to ‘Open’ while the input has a logic value of ' 1 '.
DEV01: Interm.
pos. suppr.
[ 210 012 ]
0
1
0: No
1: Yes
DEV01: Inp.asg.
sw.tr. plug
[ 210 014 ]
Signal 1
Signal 2
Signal 3
Signal n
Without function
Selected Signal
DEV01: Switch.
device open
DEV01: Gr. [ 210 036 ]
assign. debounc.
[ 210 011 ] DEV01: Switch.
device closed
[ 210 037 ]
DEV01: Dev.
interm./flt.pos
[ 210 038 ]
Selected group
0
DEV01: Stat.ind. 1
interm.pos.
[ 210 027 ] 2
3
0
5s 0 DEV01: Control
1 0 ... 3 state
[ 210 018 ]
0: No 0: Interm. pos.
1: Yes 1: Open
2: Closed
3: Faulty pos.
45Z63AJA_EN
Depending on the respective position of control the P43x will issue the following logic
state signals:
For control via binary inputs, the appropriate control inputs need to be configured for the
switchgear units to be controlled. For control via the communication interface, the
control commands ‘Open’ or ‘Close’ will also address the switchgear unit to be
controlled.
LOC: Loc.acc.
block.active
[ 221 005 ]
LOC: Return t.
illum. trg
305 550
MAIN: Interlock
equ. viol.
[ 221 018 ]
DEV01
DEV01: Open
request
307 000
DEV01: Close
request
307 001
MAIN: Electrical
control
[ 221 061 ]
2: Local
1: Remote
LOC:Rem.acc.block.
active
[ 221 004 ]
DEV01: Inp.asg.el.
ctrl.open
[ 210 019 ]
Signal 1
Signal 2
Signal 3
Signal n
Selected signal
DEV01: Inp.asg.el.
ctr.close
[ 210 020 ]
Selected signal
DEV01: Latching
time runn.
307 011
12Z62AAA_EN
3-385 Generating a switching request with remote control via the communication interface
Enabling switching
commands
Before a switching command is executed, the P43x checks the interlocking conditions
defined in the interlocking logic to determine whether a switching command is
permissible. Bay interlock equations for operation with or without station interlock can be
defined. The assignment of an output relay from the interlocking logic to a switching
command determines the interlocking equations that define, for example, the conditions
for the 'Open' command for operation without station interlock.
3-386 Assignment of equations of the interlocking logic to the switching commands and enabling of switching commands by the bay interlock
function
If bay and station interlocking is to be checked, the bay interlock will be checked first.
If bay interlocking issues a switching enable signal, a switching request will be sent to
the substation control level. At substation control level, there will then be a check –
taking into account the station interlock functions – as to whether switching is permitted
or not. If the substation control level also issues an enabling command, the switching
operation is carried out provided that the enable signal from the bay interlock is still
present. Optionally, the ‘Open’ or ‘Close’ switching operation can be carried out without
checking the station interlock function conditions. In this case, the bay interlock
equations defined for operation without station interlock will be used.
Linking protection
commands to switching
commands
For circuit breakers, the ‘Open’ command can be linked to the protection trip signals.
The 'Close' command can also be linked to the close command of the protection
functions. The bay definitions specify which of the switchgear units are circuit breakers.
The trip (open) or close commands of the protection device are executed directly without
a prior check of the interlocking equations.
Issue of switching
commands
Depending on the operating mode (set at D E V x x : O p e r . M o d e c m d . ) set for
commands, switching commands are issued for the set timer durations or according to
time control.
When the automatic synchronism check (ASC) is active and the parameter
A S C : S y s t e m i n t e g r a t . P S x is set to 'Autom. synchr. control' a 'Close' request
will automatically issue a 'Close' command for the circuit breaker after a ‘close enable'
was issued by the ASC.
DEV01:
Protection
trip cmd.
307 013
DEV01:
Protect.
close cmd.
307 014
MAIN: Cmd.
dur.long cmd.
[ 221 230 ]
MAIN: Cmd. dur.
short cmd.
[ 221 231 ]
DEV01: Oper.
mode cmd.
[ 210 024 ]
1 1
t
2
3 1
t
1: Long command
2: Short
command
3: Time control
1
t
1
t DEV01: Open
command
[ 210 028 ]
DEV01: Enable
BI Open
307 019
DEV01: Open
request
307 000
DEV01: Enable
SI Close
307 005
DEV01: Enable
BI Close
307 020
DEV01: Close
request
307 001
ASC: AC active
for DEV01
305 040
ASC: Close
enable DEV01 AC
305 041
12Z62AGA_EN
If the contacts on the switchgear unit have not reached either their ‘Open’ or ‘Closed’
position after the set time period for running time monitoring has elapsed the signal
'Faulty position' is issued. If D E V 0 1 : S t a t . i n d . i n t e r m . p o s . is set to 'Yes', a
delay time of 5 s is started. Once this time period has elapsed and there is no status
signal for the position, the state actually present at the binary inputs will be signaled.
Switch truck
For switchgear units mounted on switch trucks with switch truck plugs, it is possible to
configure a single-pole position signal from the switch truck plug. If such a configuration
has been assigned, the status signal for the position of the associated switchgear unit is
set to ‘Open’ while the input has a logic value of '1'.
DEV01: Interm.
pos. suppr.
[ 210 012 ]
0
1
0: No
1: Yes
DEV01: Inp.asg.
sw.tr. plug
[ 210 014 ]
Signal 1
Signal 2
Signal 3
Signal n
Without function
Selected signal
DEV01: Switch.
device open
DEV01: Gr. [ 210 036 ]
assign. debounc.
[ 210 011 ] DEV01: Switch.
device closed
[ 210 037 ]
DEV01: Dev.
interm./flt.pos
[ 210 038 ]
Selected group
DEV01: Open
signal EXT Debouncing DEV01: End
[ 210 030 ] open command
307 002
& DEV01: End
close command
DEV01: Closed 307 003
chatter suppression DEV01: Op.time
signal EXT switch. dev.
[ 210 031 ] [ 210 004 ]
DEV01: Switch.
device runn.
307 010
DEV01: Open
command
[ 210 028 ] 0
DEV01: Close DEV01: Stat.ind. 1
command interm.pos.
[ 210 029 ] [ 210 027 ] 2
DEV01: Start 3
runn.time mon.
307 008 0
5s 0 DEV01: Control
0 ... 3 state
1 [ 210 018 ]
0: No 0: Interm. pos.
1: Yes 1: Open
2: Closed
3: Faulty pos.
45Z63AKA_DE
DEV01: Close
command
210 029 1
3
DEV01: Switch.
device open
210 036
DEV01: Switch.
device closed
210 037
4
1 10 ms
19Z5201A_EN
3-391 Sequence for time control of switching commands without external termination control
DEV01: Close
command
210 029
1
3
DEV01: Switch.
device open
210 036
DEV01: Switch.
device closed
210 037
DEV01:Inp.asg.
end Close
210 016
1 10 ms
3 DEV01: Latching time 210 005
19Z5202A_EN
3-392 Sequence for time control of switching commands with external termination control
The switching commands to the controllable switchgear units in the bay are enabled only
after interlock conditions have been checked. The interlock conditions are defined in the
form of Boolean equations in the interlocking logic function.
The choice of the bay type automatically defines the bay interlock conditions (or
equations) for the ‘Open’ and ‘Close’ operations of the individual switchgear units in the
bay. The bay interlock equations for operation with station interlock differ from the bay
interlock equations for operation without station interlock (see Appendix, ‘List of Bay
Types’). These automatically defined interlock conditions – determined by the choice of
bay type – can be modified by the user at any time to fit particular station requirements.
The following signals acquired by the P43x are linked by logic operations for the bay
interlock:
ILOCK: Fct.
assignm. outp. 1
[ 250 000 ]
MAIN: Fct.
block. 1 active
[ 221 015 ]
MAIN: Fct.
block. 2 active
[ 221 023 ]
LOGIC: Output 1
[ 042 032 ]
LOGIC: Output 1
(t)
[ 042 033 ]
LOGIC: Output 32
[ 042 094 ]
LOGIC: Output 32
(t)
[ 042 095 ]
DEV01: Switch.
device open
[ 210 036 ]
DEV01: Switch.
device closed
[ 210 037 ]
DEV01: Dev.
interm./flt.pos
[ 210 038 ]
DEV03: Switch.
device closed
[ 210 136 ]
DEV03: Switch.
device open
[ 210 137 ]
DEV03: Dev.
interm./flt.pos
[ 210 138 ]
SIG_1: Logic
signal S001
[ 226 005 ]
ILOCK: Output 1
[ 250 032 ]
45Z6367A_EN
The operating mode may be selected individually for each single-pole command.
The following settings are possible:
Long command
Short command
Persistent command
If the operating mode long or short command has been selected the output relay will be
triggered for the time period set at M A I N : C m d . d u r . l o n g c m d . or
MAIN: Cmd. dur. short cmd.
The setting options and the functional sequence are shown in the example for
Command C001. Equivalent considerations apply to all other single-pole commands.
3-394 Functional sequence for single-pole commands, as illustrated for Command C001
Binary, single-pole signals issued by the system can be transmitted by the P43x to the
control station via appropriately configured binary signal inputs.
Such single-pole input signals are conditioned by debouncing and chatter suppression
(see ‘Main Functions of the P43x’). This conditioned signal is then available as
SIG_1: Logic signal Sxxx.
Without function
Start/end signal
Transient signal
If the setting is 'Without function' then no message is transmitted when the signal state at
the binary signal input changes. If the setting is 'Start/end signal' then a message is
transmitted every time the signal state at the binary signal input changes.
The requirement for sending the 'start' signal is that the logic ' 1 ' signal be available for
the set minimum time. If the setting is 'Transient signal' then a message is transmitted
when the signal state at the binary signal input changes form logic ' 0 ' to logic ' 1 '.
The following figure displays setting modes and the functional sequence with the
example for logic signal S001. Equivalent considerations apply to all other single-pole
signals.
3-395 Functional sequence for single-pole signals, as illustrated for logic signal S001
4 Design
The P43x is available in different types of cases and with different combinations of
modules.
The P43x – like all other device types in the MiCOM Px30 range – is equipped with the
standard local control panel (HMI). The local control panel is covered with a tough film
so that the specified degree of IP protection will be maintained. In addition to the
essential control and display elements, a parallel display consisting of a total of 23 LED
indicators is also incorporated. The meaning of the various LED indications is shown in
plain text on a label strip.
The PC interface (9-pin D-Sub female connector) is located under the hinged cover at
the bottom of the local control panel.
4.1 Designs
The P43x is available in a surface-mounted and a flush-mounted case all with different
designs.
Electrical connections are made via plug-in threaded terminal blocks. The threaded
terminal blocks in the surface-mounted case are accessible from the front of the device
after unscrewing the crosshead screws on the sides (see Figure 4-1, c) and removing
the local control panel. The local control panel can then be secured by inserting the tabs
in the slots in the left side wall (see Figure 4-1, d). The flush-mounted case is
connected at the back of the case.
The secondary circuit of live system current transformers must not be opened! If the
secondary circuit of a live CT is opened, there is the danger that the resulting voltages
will endanger personnel and damage the insulation.
The threaded terminal block for system current transformer connection is not a shorting
block! Therefore always short-circuit the system current transformers before loosening
the threaded terminals.
4-1 Surface-mounted case, removal of local control panel (example for a 40TE device)
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod .
147,5
177,5
184,5
213,4 257,1
242,6
260,2
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod.
147,5
177,5
184,5
434,8 257,1
464,0
481,6
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod .
177,5
213,4 227,9
253,6
203,0
155,4
159,0
168,0
5,0
5,0
181,3
4-4 Dimensional drawing for flush-mounted 40TE case with instrument panel cut-out, flush-mount method 1 (without the angle brackets and
frame) (dimensions in mm)
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod .
177,5
101,6
213,4 227,9
253,6
242,6
260,2
6,4
101,6
186,5
224,5
242,6
4-5 Flush-mounted 40TE case with instrument panel cut-out, flush-mount method 2 (with angle brackets and frame)
Note: The device has increased mechanical robustness if flush-mount method 2 (with angle brackets and frame (shown in this
drawing) is used for the flush-mounted case.
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod .
177,5
434,8 227,9
253,6
284,9
259,0
25,9
159,0
168,0
5,0
5,0
410,0
4-6 Dimensional drawing for flush-mounted 84TE case with panel opening flush-mount method 1 (without the angle brackets and frame)
(dimensions in mm)
Aus-Kommando
Warnung
Block./Störung
Betrieb
Änderungsmod .
177,5
101,6
434,8 227,9
253,6
464,0
481,6
6,4
101,6
186,5
445,9
464,0
4-7 Flush-mounted 84TE case with panel opening, flush-mount method 2 (with angle brackets and frame)
Note: The device has increased mechanical robustness if flush-mount method 2 (with angle brackets and frame (shown in this
drawing) is used for the flush-mounted case.
Aus-Kommando
Warnung
Block./ Stör ung
Betr ieb
ACHTUNG:
Aus- Kommando
War nung
Block./ Störung
Betr ieb
ACHTUNG:
Aus- Kommando
War nung
107,3
Block./ Störung
Betr ieb
Änder ungsmod
.
177,5
206,0 20,7
46,3
197,5
192,5
148,0
168,0
3,0
181,3
4-8 Device and panel opening views for connection of detachable HMI
Note: Connection of protective grounding conductor: see Chapter 5.
4.3 Modules
The P43x is constructed from standard hardware modules. The following table gives an
overview of the modules relevant for the P43x.
(*: modules that are not shown in the location diagrams, {: optional, z: standard
equipment,
: depending on order).
A 9650 356 A ff { { { {
Communication module 2 (for wire connection) 4T
A 9650 354 A ff Communication module 2 4T { { { {
(For glass fiber, ST connector)
A 9650 355 A ff Communication module 2 (For plastic fiber) 4T { { { {
A 9651 427 E ff Ethernet module (for 100 Mbit/s Ethernet, glass fiber, 4T { { { {
SC connector and RJ45 wire)
A 9651 471 E ff Ethernet module (for 100 Mbit/s Ethernet, glass fiber, 4T { { { {
ST connector and RJ45 wire)
A 9650 827 B ff InterMiCOM Module COMM3 (RS 485) 4T { { { {
L 9651 473 C Local control module (Europ. for device version with
DHMI)
L 9651 474 B Local control module (Cyrillic for device version with
DHMI)
L 9650 563 F Front plate (for device version 40TE with DHMI)
L 9651 920 F Front plate (for device version 84TE with DHMI)
X 0336 971 D ff Binary I/O module (6 binary inputs & 8 output relays), 4T { { { {
Standard variant (switching threshold 18 V)
X 9651 334 A ff Binary I/O module (8 binary inputs & 6 output relays), 4T { { { {
switching threshold 90 V
X 9651 362 A ff Binary I/O module (8 binary inputs & 6 output relays), 4T { { { {
switching threshold 155 V
X 9651 306 A ff Binary I/O module (8 binary inputs & 6 output relays), 4T { { { {
switching threshold 73 V
X 9651 445 A ff Binary I/O module (8 binary inputs & 6 output relays), 4T { { { {
switching threshold 146 V
X 9651 493 ff Binary module (4 high-power contacts) 4T { { { {
X 9651 512 ff Binary I/O module (3 binary inputs & 6 output relays), 4T { { { {
Standard variant (switching threshold 18 V)
X 9651 514 ff Binary I/O module (3 binary inputs & 6 output relays), 4T { { { {
switching threshold 90 V
X 9651 515 ff Binary I/O module (3 binary inputs & 6 output relays), 4T { { { {
switching threshold 155 V
X 9651 513 ff Binary I/O module (3 binary inputs & 6 output relays), 4T { { { {
switching threshold 73 V
X 9651 516 ff Binary I/O module (3 binary inputs & 6 output relays), 4T { { { {
switching threshold 146 V
X 0337 377 ff Binary I/O module (6 binary inputs & 6 output relays), 4T { { { {
Standard variant (switching threshold 18 V)
X 9651 333 ff Binary I/O module (6 binary inputs & 6 output relays), 4T { { { {
switching threshold 90 V
X 9651 361 ff Binary I/O module (6 binary inputs & 6 output relays), 4T { { { {
switching threshold 155 V
X 9651 305 ff Binary I/O module (6 binary inputs & 6 output relays), 4T { { { {
switching threshold 73 V
X 9651 444 ff Binary I/O module (6 binary inputs & 6 output relays), 4T { { { {
switching threshold 146 V
Y 0337 406 D ff Analog I/O module, 4T { { { {
Standard variant (switching threshold 18 V)
The space available for the modules measures 4 H in height by 40TE or 84TE in width
(H = 44.45 mm, T = 5.08 mm). The location of the individual modules and the position of
the threaded terminal blocks in the P43x are shown in the location diagrams at the end
of Chapter 5.
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
The instructions given in the "Protective and Operational Grounding" section should be
noted. In particular, check that the protective ground connection is secured with a tooth
lock washer, as per the diagram "Installing the protective grounding conductor terminal".
If a cable screen is added to this connection or removed from it, then the protective
grounding should be checked again.
The SC connector and RJ45 wire of the Ethernet module cannot be connected at the
same time. (The selection for IEC : Eth e r n e t M e d i a should be noted.)
All P43x units are packaged separately in their own cartons and shipped inside outer
packaging. Use special care when opening cartons and unpacking devices, and do not
use force. In addition, make sure to remove supporting documents and the type
identification label supplied with each individual device from the inside carton.
The design revision level of each module included in the device when shipped can be
determined from the list of components (assembly list). This list of components should
be filed carefully.
If the P43x needs to be shipped, both inner and outer packaging must be used.
If the original packaging is no longer available, make sure that packaging conforms to
DIN ISO 2248 specifications for a drop height ≤ 0.8 m.
The nominal data and design type of the P43x can be determined by checking the type
identification label (see Figure 5-1). One type identification label is located under the
upper hinged cover on the front panel and a second label can be found on the inside of
the device. Another copy of the type identification label is fixed to the outside of the
P43x packaging.
The P43x design version can be determined from the order number. A breakdown of the
order number is given in Chapter 14 of this manual.
The P43x has been designed to conform to DIN 57 435 part 303. Therefore it is
important when choosing the installation location to make certain that it provides the
operating conditions as specified in above DIN norm sections 3.2 to 3.4. Several of
these important operating conditions are listed below.
Environmental Conditions
Ambient temperature: -5 °C to +55 °C [+23 °F to +131 °F]
Relative humidity: The relative humidity must not result in the formation of
either condensed water or ice in the P43x.
Ambient air: The ambient air must not be significantly polluted by dust,
smoke, gases or vapors, or salt content.
Mechanical conditions
Vibration stress: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Electromagnetic conditions
Substation secondary system design must follow the best of modern practices,
especially with respect to grounding and EMC.
5.4 Installation
The dimensions and mounting dimensions for surface-mounted cases are given in
Chapter 4. When the P43x is surface-mounted on a panel, the wiring to the P43x is
normally run along the front side of the mounting plane. If the wiring is to be at the back,
an opening can be provided above or below the surface-mounted case as shown in
Figure 5-2. Figure 5-2 shows such an opening which is below the surface-mounted
case. This will apply accordingly to opening above the surface-mounted case.
Flush-mounted cases are designed for control panels. The dimensions and mounting
dimensions are given in Chapter 4. Where the P43x is mounted on a cubicle door,
special sealing measures must be applied in order to provide the degree of protection
required for the cubicle (IP 51).
For flush-mount method 1 (without angle brackets and frame), the procedure is as
follows:
Before the P43x can be installed into a control panel, the local control panel must be
removed. The local control panel is removed as described below:
Remove both top and bottom hinged flaps from the device. (Lift/lower both hinged
flaps 180°up/down. Hold them in the middle and bend them slightly. The side
mountings of both hinged flaps can then be disengaged.)
Remove the M3 screws (see figures 5-3 and 5-4).
Then remove the local control panel.
Then remove the lower M4 screws and loosen the upper M4 screws (see figure 5-3 and
5-4). Now insert the P43x into the panel opening from the rear so that the upper M4
screws fit into the corresponding holes. Then tighten all the M4 screws. After this,
replace the local control panel.
Note: If the control panel thickness ≥ 2 mm, the longer M3 and M4 bolts must be
used. Longer screws are enclosed within the device packing.
Completely remove
the lower screws
before
installation.
12Y6181 B_EN
5-3 Installation of the 40TE case into a control panel, flush-mount method 1 (without angle brackets and frame).
The P43x has increased mechanical robustness if either the surface-mounted case or for the flush-mounted case flush-mount method 2
(with angle brackets and frame, see figure 5-6)) is used.
3 mm
M4
M3
Completely remove
the lower screws
before
installation.
12Y6182 B_EN
5-4 Installation of the 84TE case into a control panel, flush-mount method 1 (without angle brackets and frame).
The has increased mechanical robustness if either the surface-mounted case or for the flush-mounted case flush-mount method 2
(with angle brackets and frame, see figure ) is used.
For flush-mount method 2 (using the angle brackets and frame), the procedure is as
follows:
Remove the screws as shown in Figure 5-5, c and mount the enclosed angle
brackets using these same screws.
Then push the device into the control panel cutout from the front.
Secure the device to the control panel by using the enclosed M6 screws
(see Figure 5-6).
Assemble the cover frame and snap-fasten onto the fixing screws.
Angle brackets
M6
B6
6.4
M6 x 15
Height: 204 mm
Frame for the
80 mm
W idt h: 2 n ted cas e
sh -m o u
40T E flu
12Y6183 B_EN
5-6 Installation of a case into a control panel, flush-mount method 2 (with angle brackets and frame).
Example for a device in a 40TE case.
The cover frame width of the surface-mounted 40TE case is: 486 mm
The device has an increased mechanical robustness, if flush-mount method 2 (with angle brackets and frame, shown on this page) is
used for the flush-mounted cases.
The flush-mounted 84TE cases - after being fitted with angle brackets - are also suitable
for installation in enclosures or cubicles equipped with a 19" mounting rack.
A rack mounting kit can be used to combine a flush-mounted 40TE case with a second
sub-rack to form a 19" mounting rack (see Figure 5-8). The second sub-rack can be
another device, for example, or an empty sub-rack with a blank front panel.
In addition, a protective ground connection at the terminal contact on the power supply
module (identified by the letters "PE" on the terminal connection diagram) is also
required for proper operation of the device. The cross-section of this ground conductor
must also conform to applicable national standards. A minimum cross section of
1.5 mm2 is required.
The grounding connection at both locations must be low-inductance, i.e. it must be kept
as short as possible.
1 M4 nut 1 M4 nut
4 M4 bolt 4 M4 bolt
19Y5220 C_EN
The protective conductor (earth) must always be connected to the protective grounding conductor terminal in order to guarantee the
safety given by this set-up.
5.6 Connection
The P43x must be connected in accordance with the terminal connection diagram
indicated on the type identification label. The terminal connection diagram is included in
the supporting documents supplied with the device. The terminal connection diagrams
that apply to the P43x are also to be found at the end of this chapter.
In general copper conductors with a cross section of 2.5 mm² are sufficient to connect a
system current transformer to a current input on the P43x. To reduce CT knee-point
voltage requirements, it may be necessary to install shorter copper conductors with a
greater cross section between the system current transformers and the current inputs on
the P43x. Copper conductors with a cross section of 1.5 mm2 are adequate to connect
the binary signal inputs, the signaling and tripping circuits and the power supply input.
All connections run into the system must always have a defined potential. Connections
that are pre-wired but not used should preferably be grounded when binary inputs and
output relays are isolated. When binary inputs and output relays are connected to
common potential, the pre-wired but unused connections should be connected to the
common potential of the grouped connections.
Power supply
Before connecting the auxiliary voltage VA for the P43x power supply, it must be ensured
that the nominal value of the auxiliary device voltage corresponds with the nominal value
of the auxiliary system voltage.
Current-measuring inputs
When connecting the system transformers, it must be ensured that the secondary
nominal currents of the system and the device correspond.
The secondary circuit of live system current transformers must not be opened! If the
secondary circuit of a live CT is opened, there is the danger that the resulting voltages
will endanger personnel and damage the insulation.
The threaded terminal block for system current transformer connection is not a shorting
block! Therefore always short-circuit the system current transformers before loosening
the threaded terminals.
It is essential that the grounding configuration of the current transformers shown in the
diagram be followed. If the CT or VT connection is reversed, this can be taken into
account when making settings (see Chapter 7).
The steady-state ground fault direction determination requires either the three
phase-to-ground voltages or, alternatively, the neutral-point displacement voltage from
the open delta winding of a voltage transformer assembly as the measured voltage.
Phase voltage values are obtained from the same VTs as the measured values for
distance protection. An additional voltage transformer (T 90) is available in the P43x to
connect an open delta winding. When setting the protection function, the selected
voltage needs to be taken into account.
Figure 5-11 shows the standard connection for ground fault direction determination by
steady-state values where the voltage measuring circuit is connected to an open delta
winding. With this connection configuration, ‘forward/LS’ is displayed if a ground fault
occurs on the line side. A reversed connection is possible for the system current or
voltage transformer if the appropriate setting is configured (see Chapter 7).
Connection to a
Connection to a core balance
Holmgreen group (window) CT
BS
P43x
LS
45Z5060B_EN
5-11 Connecting the steady-state ground fault direction determination function to Holmgreen-configuration and core balance transformers
Connecting a resistance
thermometer
A resistance thermometer can be connected if the device is fitted with analog module Y.
This analog I/O module input is designed to connect a PT 100 resistance thermometer.
The PT 100 should be connected using the 3-wire method (see Figure 5-12). No supply
conductor compensation is required in this case.
P43x
P63x
The polarity for connected binary signal inputs is to be found in the terminal connection
diagrams. This is to be understood as a recommendation only. Connection to binary
inputs can be made as desired.
The protective signaling transmitting relay can be set to either Transm. rel. break con. or
Transm. rel. make con. In the first case the break contact of the transmitting relay must
be wired, and in the second case the make contact must be wired. The figures show the
connection for the setting Transm. rel. break con.
Furthermore the P43x is capable to operate with the protective signaling device type
SV 35A and the comparator relay type V 34 if it is guaranteed that there is at least one
10 mA pilot wire current flowing.
PC interface
The PC interface is provided so that personnel can operate the device from a personal
computer (PC).
Communication interfaces
The communication interface is provided as a permanent connection of the device to a
control system for substations or to a central substation unit. Depending on the type,
communication interface 1 on the device is connected either by a special fiber-optic
connector or a RS 485 interface with twisted pair copper wires. Communication
interface 2 is only available as a RS 485 interface.
The selection and assembly of a properly cut fiber-optic connecting cable requires
special knowledge and expertise and is therefore not covered in this operating manual.
The fiber-optic interface may only be connected or disconnected when the supply voltage
for the device is shut off.
01 02 03 04 05 06 07 08 09 10
P A N T X X Y V X
CH1 4I 6I 6I 4I 4I 6O
CH2 4U 8O 8O 8O
alt.
alt. alt. alt. alt. alt. alt. X
6I
A A T X X X 3O
alt.
ETH CH3
CH2
4I
5U
6I 6I 24I
6O 6O
X
4H
01 02 03 04 05 06 07 08 09 10
5-15 P433 in the 40TE case with pin- terminal connection (P433-410)
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
A N T Y X X X V
CH1 4I 4I 6I 6I 6O 4I
CH2 4U 8O 8O 8O
alt .
alt. alt. alt. alt . alt. X
6I
A A T X X X 3O
alt .
ETH CH3
CH2
4I
5U
24I 6I 6I X
6O 6O 4H
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
01 02 03 04 05 06 07 08 09 10 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A N T X X Y V X P A N T Y X X X X X V
CH1 4I 6I 6I 4I 4I 6O CH1 4I 4I 6I 6I 6I 6I 6O 4I
CH2 4U 8O 8O 8O CH2 4U 8O 8O 8O 8O 8O
alt. alt .
alt. alt. alt. X alt. alt. alt. alt. alt. alt. X
alt. alt. alt. 6I 6I
A A T X X X 3O A A T X X X 3O
alt. alt .
ETH CH3 4I 6I 6I 24I X ETH CH3 4I 24I 6I
60
6I
60
X
CH2 5U 6O 6O 4H CH2 5U 4H
01 02 03 04 05 06 07 08 09 10 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
5-17 The MiCOM P435 fitted into the 40TE case (P435-413 on the left side) and 84TE case (P435-414 on the right side) for pin terminal
connection
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
P A N T Y X X X X X V
CH1 4I 4I 6I 6I 6I 6I 6O 4I
CH2 4U 8O 8O 8O 8O 8O
alt .
alt. alt. alt. alt . alt. alt. X
6I
A A T X X X 3O
alt .
ETH CH3
CH2
4I
5U
24I 6I 6I X
6O 6O 4H
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21
Versorgung
25 7 + UH
26 8 - U100
27 9 PE
Binär- Typ X Binär- Typ X Binär- Typ X Binär- Typ X Binär- Typ X
baustein 6I / 8O baustein 6I / 6O baustein 6I / 3O baustein 6O baustein 4H
Ring Stift Ring Stift Ring Stift Ring Stift Ring Stift
X_1 X_ 1 Ausgangsrelais X_1 X_1 Ausgangsrelais X_1 X_ 1 Ausgangsrelais X_ 1 X_ 1 Ausgangsrelais X_ 1 X_ 1 Leistungskontakte
1 1 1 1 1 1 1 1 1 1
2 2 K_01 2 2 2 2 2 2 K_01 2 2
K_01
3 3 3 3 K_01 3 3 3 3 3 3
4 4 4 4 4 4 4 4 4 4
K_01
5 5 5 5 K_02 5 5 5 5 5 5 +
6 6 K_02 6 6 6 6 6 6 6 6
7 7 7 7 7 7 7 7 7 7
8 8 8 8 8 8 8 8 K_02 8 8
K_02
9 9 K_03 9 9 K_03 9 9 9 9 9 9
X_ 2 X_2
10 1 10 1 K_04 X_ 2 X_ 2 X_ 2
11 2 K_04 11 2 10 1 10 1 1) 10 1
12 3 K_05 12 3 11 2 11 2 11 2 K_02
13 4 K_06 13 4 12 3 12 3 12 3 +
14 5 K_07 14 5 13 4 13 4 1) 13 4
15 6 15 6 K_05 14 5 14 5 K_03 14 5
K_03
16 7 K_08 16 7 15 6 15 6 15 6
17 8 17 8 K_06 16 7 16 7 16 7
18 9 17 8 Signal- 17 8 17 8
Signaleingänge 18 9
eingänge 18 9 18 9
18 9
UE UE
U_01 X_3 Signaleingänge
U_01
X_ 3 19 1 X_ 3 X_ 3 X_ 3
UE UE
19 1 U_01 19 1 19 1 1) 19 1
U_02 K_03
20 2
UE
20 2
UE 20 2 UE
20 2 K_04 20 2 +
21 3 U_02 21 3 U_02 21 3 21 3 21 3
U_03
22 4 22 4 22 4 22 4 1) 22 4
UE UE UE
U_03 U_03 23 5 23 5 K_05 23 5
U_04
23 5 23 5 24 6 24 6 24 6
UE UE UE
24 6 U_04 24 6 U_04 25 7 25 7 25 7
U_05
25 7 25 7 26 8 26 8 K_06 26 8 K_04
UE UE UE
U_05 U_05 27 9 U_06 27 9 27 9 +
26 8 26 8
UE UE U_06
27 9 U_06 27 9
Kommunikations - Typ A Kommunikations - Typ A Kommunikations - Typ A Analog- Typ Y Binär- Typ X
baustein CH1 / CH2 baustein ETH / CH2 baustein (InterMiCOM) CH 3 baustein 4I baustein 24 I
1 13 4
M5[DCD] UE U_01
X10 RJ45 14 5
X//Y 2
D2[R]
1 15 6 X_ 3
3 D1[T] UE U_02 UE
2 D2 [R] 4 16 7 19 1
KOMM2 20 U_17
3 E 17 8 2
U20 Drahtanschluss 5 U27 UE U_03
4 E2[ G] 21 3
U_18
5 D1 [T] 18 9 22 4
U_19
X10 7 +UB UE U_04 U_20
X//Y 23 5
1 U_21
RS 485 X_ 3 24 6
2 D2[ R] U_22
RS 232 19 1 25 7
3 U_23
IRIG -B U20 20 2
U 26 8
4 U_05 U_24
Zeitsynchronisierung D1[ T] 21 3 0..20 mA
# 27 9
5
X11 22 4 U
1 # 23 5 PT100
U_06
#
U21 RS 485 24 6 #
Control through the PC interface is also possible. This requires a suitable PC and
support software (MiCOM S1).
Then there are seven keys with permanently assigned functions situated below the LCD
and there are six additional, freely configurable, function keys on the right hand side of
the LCD.
Furthermore the front panel user interface (HMI) is fitted with 17 LED indicators,
mounted vertically to the left of the LCD and there are six additional LED indicators
situated to the right of the six freely configurable function keys.
Further information on the function keys and their application can be found in Chapter 3,
sections 'Configurable Function Keys (Function Group F_KEY)' and 'Resetting Actions'
as well as in sections 'Configurable Function Keys F1 to Fx (general)' and 'Configurable
Function Keys F1 to Fx particularly as control keys' of this chapter.
H4
H3
TRIP
ALARM
F1 H18
H2 OUT OF SERVICE
H1
H17
HEALTHY
EDIT MODE
F2 H19
H5
H6
F3 H20
H7
H8 CG
H9
H10
G F4 H21
H11
H12
G G F5
G
H13 H22
H14
H15
H16
G F6 H23
12 Z6100B_EN
6-1 View of the local control panel and layout of the LED indicators
Display levels
All data relevant for operation and all device settings are displayed on two levels. At the
Panel level, data such as measurements are displayed in Panels that provide a quick
overview of the current state of the bay. The menu tree level below the panel level
allows the user to select all data points (settings, signals, measured values, etc.) and to
change them, if appropriate. To access a selected event recording from either the panel
level or from any other point in the menu tree, press the "READ" key .
1. On the hardware side the protection unit has to have been upgraded with a control
functionality. This requires that the optional binary I/O module to control switchgear
units has been ordered and is fitted to a slot.
2. A further condition is that the protection units are fitted with a communication module
with selectable communication protocol or the Ethernet module as well as with the
new front panel user interface (HMI) that includes function keys.
3. A bay type has been selected with parameter M A I N : T y p e o f b a y .
To access a selected event recording from either the panel level or from any other point
in the menu tree, press the "READ" key .
From the control and display panels (e.g. measured value panels or the bay panel) the
user can access the menu tree level by pressing the "ENTER” key.
To return to the previously selected control and display panel from the menu tree level
the user must simultaneously press the keys "Cursor up" and "RESET". (If previously no
panel was selected, i.e. after a system restart, then the bay panel, if available, is
accessed.)
After the set L O C : A u t o m . r e t u r n t i m e has elapsed the protection unit will also
return automatically from the menu tree level to the control and display panel last
selected.
The user can move from a bay panel to a measured value panel by pressing the key
"Cursor left" and back again by pressing the key “Cursor right".
Measured Value
Bay Panel Panel(s)
(state-dependent)
Record View
X0 :running Voltage VAB prim. Oper/Rec/OP_RC
>Q0 :running 20.7 kV Operat. data record.
G
Q8 :running Voltage VBC prim.
Local Remote 20.6 kV
+ CG G
Device Type
Bay panels
If available the bay panel will display switching state signals from external devices
(closed, open, intermediate position) and the active control site (local or remote).
The text display will show up to 3 external devices, one per line, where the external
device selected is marked with the flashing symbol ">" in front of the external devices’
designation text.
X0 :Interm. pos.
>Q0 :Interm. pos.
Q8 :Interm. pos.
Local Locked
The active control unit ("Remote" or "Local") is displayed in the fourth line and whether it
is "Locked" or "Unlocked".
Display panels
The P43x can display 'Measured Value Panels' which are selected automatically by the
device according to system conditions.
Selected measured values are displayed on the Measured Value Panels. The system
condition determines which Panel is called up (examples are the Operation Panel and
the Fault Panel). Only the Measured Value Panels relevant for the particular design
version of the given device and its associated range of functions are actually available.
The Operation Panel is always provided.
ENTER Key
Panel Level:
Press the ENTER key at the Panel level to go to the menu tree.
Menu Tree Level:
Press the ENTER key to enter the input mode. Press the ENTER key a second time
to accept the changes as entered and exit the input mode. The LED indicator labeled
EDIT MODE signals that the input mode is active.
CLEAR Key C
Press the CLEAR key to reset the LED indicators and clear all measured event data.
The records in the recording memories are not affected by this action.
Input mode:
When the CLEAR key is pressed all changes entered are rejected and the input
mode is exited.
READ Key
Press the READ key to access a selected event recording from either the Panel level
or from any other point in the menu tree.
Function keys F1 to F6
By pressing a function key the assigned function is triggered. More details on
assigning functions to function keys can be found in section "Configurable Function
Keys (Function Group F_KEY)" in Chapter 3. More details on handling function keys
can be found in this chapter, in section 'Configurable Function Keys F1 to Fx
(general)' and in section 'Configurable Function Keys F1 to Fx (particularly as control
keys)'.
The following presentation of the individual control steps shows which displays can be
changed in each case by pressing keys. A small black square to the right of the enter
key indicates that the LED indicator labeled EDIT MODE is illuminated. The examples
used here are not necessarily valid for the device type described in this manual; they
merely serve to illustrate the control principles involved.
XYYY
After the set return time has elapsed (setting in menu tree: 'Par/Conf/LOC'), the display
will automatically switch to the Panel level if a Measured Value Panel has been
configured.
If none of the control keys is pressed, the display illumination will switch off once the set
"hold" time has elapsed (‘Backlight time’ setting in the menu tree at ‘Par/Conf/LOC’).
Pressing any of the control keys will turn the display illumination on again. In this case
the control action that is normally triggered by that key will not be executed. Disabling of
the display illumination is also possible by using a binary input.
If continuous display illumination is required, the ‘return time illumination’ function is set
to ‘blocked’.
If they have not been configured as control keys, function keys F1 to Fx are enabled only
after the password for function keys has been entered.
Let us assume for the remainder of this section that the function key F1 is enabled only
after the password - as assigned at F _ K E Y : P a s s w o r d f u n c t . k e y 1 - has been
entered. After the password has been entered the function key will remain active for the
time period set at F _ K E Y : R e t u r n t i m e f c t . k e y s . Thereafter, the function key is
disabled until the password is entered again.
For this example it is further assumed that the password for the function keys is the
factory-set password. If the password has been changed by the user (see section
'Changing the Password'), the following description will apply accordingly.
'Left'
G
*
'Down' G
G
*
'Right' G
G
'Up’ G
4 When function keys are pressed while the Fx Voltage VAB prim.
20.7 kV
return time period of the function key is Voltage VBC prim.
elapsing, then the configured function is carried 20.6 kV
out directly, e.g. without again checking for the
password.
In this case different rules apply to checking the password (see the previous section) and
the configuration to 'Key/Switch' is ignored.
In case the control functionality is desired then each of the following four control
commands, should be assigned to a function key. The particular selection of the four
function keys out of the available six, however, does not matter.
The measured values that will be displayed on the Measured Value Panels can first be
selected in the menu tree under Par/Conf/LOC. The user can select different sets of
measured values for the Operation Panel, the Overload Panel, the Ground Fault Panel,
and the Fault Panel. Only the Measured Value Panels relevant for the particular design
version of the given device and its associated range of functions are actually available.
The selected set of values for the Operation Panel is always available. Please see the
section entitled ‘Setting a List Parameter’ for instructions regarding selection. If the
M A I N : W i t h o u t f u n c t i o n setting has been selected for a given panel, then that
panel is disabled.
The Measured Value Panels are called up according to system conditions. If, for
example, the device detects an overload or a ground fault, then the corresponding
Measured Value Panel will be displayed as long as the overload or ground fault situation
exists. Should the device detect a fault, then the Fault Panel is displayed and remains
active until the measured fault values are reset, by pressing the CLEAR key, for
example.
G
1 If more than two measured values have or
Voltage VCA prim.
20.8 kV
been selected, they can be viewed one page at Current IA prim.
a time by pressing the ‘up’ or ’down’ keys. The 415 A
device will also show the next page of the
Measured Value Panel after the set Hold-time
for Panels (setting in menu tree:
"Par/Conf/LOC") has elapsed.
At the root of the menu tree is the unit type; the tree branches into the three main folders
‘Parameters’, ‘Operation’ and ‘Events’, which form the first folder level. Up to two further
folder levels follow so that the entire folder structure consists of three main branches and
a maximum of three folder levels.
At the end of each branch of folders are the various function groups in which the
individual data points (settings) are combined.
PX yyy
Unit
type
Oper/
Folder Cyclic measurements
level 2
Oper/Cycl/
Folder Meas. operating data
level 3
Oper/Cycl/Data/
Function MAIN
groups
Oper/Cycl/Data/MAIN
Data Date
points 01.01.99 dd.mm.yy
The display on the local control panel can be switched between address mode and plain
text mode. In the address mode the display shows settings, signals, and measured
values in numerically coded form, that is, as addresses. In plain text mode the settings,
signals, and measured values are displayed in the form of plain text descriptions. In
either case, control is guided by the menu tree. The active branch of the menu tree is
displayed in plain text in both modes. In the following examples, the display is shown in
plain text mode only.
Although it is possible to select any data point in the menu tree and read the associated
value by pressing the keys, it is not possible to switch directly to the input mode. This
safeguard prevents unintended changes in the settings.
This setup is designed to prevent accidental output and applies even when the global
change-enabling function has been activated. The following example is based on the
factory-set password. If the password has been changed by the user (see section
"Changing the Password”), the following description will apply accordingly.
Par/Conf/LOC
Autom. return time
appear in the fourth line of the display. 50000 s
50000 s
'Right' G
Par/Conf/LOC
Autom. return time
G
50000 s
'Up’ G
Par/Conf/LOC
Autom. return time
G
50010 s
'Down' G
Par/Conf/LOC
The display will change as shown in the Autom. return time
G
G
4 Press the ENTER key again. The LED
G
indicator will go out. The unit is enabled for
further setting changes.
The same procedure applies to any setting change unless the global change-enabling
function has been activated. This method is recommended for a single setting change
only. If several settings are to be changed, then the global change-enabling function is
preferable. In the following examples, the global change-enabling function has been
activated.
Automatic return
The automatic return function prevents the change-enabling function from remaining
activated after a change of settings has been completed. Once the set return time (menu
tree ‘Par/Conf/LOC’) has elapsed, the change-enabling function is automatically
disabled, and the display switches to a Measured Value Panel corresponding to the
current system condition. The return time is restarted when any of the control keys is
pressed.
Forced return
The return described above can be forced from the local control panel by first pressing
the ‘up’ key and then holding it down while pressing the CLEAR key.
Note: It is important to press the ‘up’ key first and release it last in order to avoid
unintentional deletion of stored data.
Even when the change-enabling function is activated, not all settings can be changed.
For some settings it is also necessary to disable the protective function (menu tree:
Par/Func/Glob/MAIN, 'Protection enabled'). Such settings include the configuration
settings, by means of which the device interfaces can be adapted to the system.
If all the conditions for a value change are satisfied (see above), the desired setting can
be entered.
G
50000 s
50000 s
50010 s
meantime the device will continue to operate
with the old value.
Par/Conf/LOC
Autom. return time
labeled EDIT MODE will go out and the device 50010 s
will now operate with the new value. Press the
keys to select another setting for a value
change.
Using list settings, the user is able to select several elements from a list in order to
perform tasks such as defining a trip command or defining the measurements that will be
displayed on Measured Value Panels. As a rule, the selected elements are linked by an
‘OR’ operator. Other operators (NOT, OR, AND, NOT OR and NOT AND) are available
in the LOGIC function group for linking the selected list items. In this way binary signals
and binary input signals can be processed in a Boolean equation tailored to meet user
requirements. For the DNP 3.0 communication protocol, the user defines the class of a
setting instead of assigning operators. The definition of a trip command shall be used
here as an illustration.
OR #02 DIST
Trip zone 2
#02 DIST
mode. Trip zone 4
OR #02 DIST
only the ‘OR’ operator can be selected. There Trip zone 4
is no limitation on the selection of classes.
G
Par/Func/Glob/MAIN
Fct.assign.trip cmd.
will go out. The assignment has been made. OR #02 DIST
The unit will now operate with the new settings. Trip zone 4
G
8 If you wish to reject the new setting while C Par/Func/Glob/MAIN
Fct.assign.trip cmd.
you are still entering it (LED indicator labeled OR #02 DIST
EDIT MODE is on), press the CLEAR key. The Trip zone 2
LED indicator labeled EDIT MODE will be
extinguished.
Memories can be read out after going to the corresponding entry point. This does not
necessitate activating the change-enabling function or even disabling the protective
functions. Inadvertent clearing of a memory at the entry point is not possible.
G
Enabled USER
No
Enabled USER
No
point.
G
Checksum error param
(Yes) or is no Reset: No
longer detected (No) by the self- Number: 5
monitoring function.
Reset: The fault was no longer detected by
the self-monitoring function and
has been reset (Yes).
Number: The signal occurred x times.
point.
G
Event
In this example it is the 22nd fault since the last 22
reset.
Running time
signals in chronological order. The time shown 0.17 s
in the second line is the time, measured from
the onset of the fault, at which the value was
measured or the binary signal started or G
Fault recording 1
ended. 0 ms FT_RC
G
Record. in progress
Once the end of the fault has been reached Start
(after the ‘right’ key has been pressed
repeatedly), pressing the ‘right’ key again will
have no effect.
G
Fault recording 1
241 ms FT_RC
G
Record. in progress
End
Record. in progress
Start
01.01.99 10:00:33
6.7.7 Resetting
All information memories – including the event memories and the monitoring signal
memory – as well as the LED indicators can be reset manually. In addition, the LED
indicators are automatically cleared and initialized at the onset of a new fault – provided
that the appropriate operating mode has been selected – so that they always indicate the
latest fault.
The LED indicators can also be reset manually by pressing the CLEAR key, which is
always possible in the standard control mode. This action also triggers an LED indicator
test and an LCD display test. The event memories are not affected by this action, so that
inadvertent deletion of the records associated with the reset signal pattern is reliably
prevented.
Because of the ring structure of the event memories, the data for eight consecutive
events are updated automatically so that manual resetting should not be necessary, in
principle.
Deleting the event memories completely (e.g. after a function test), can be accomplished
by various resetting actions including the configuration of a group resetting for several
memories. An overview of all resetting actions can be found in section "Resetting
Actions" in Chapter 3.
Resetting a single memory from the local control panel is described in the following with
the example of a fault memory. In this example the global change-enabling function has
already been activated.
10
Execute
Certain actions from the local control panel such as a manual trip command for testing
purposes can only be carried out by entering a password so as to prevent unwanted
output even though the global change-enabling function has been activated (see section
"Change-Enabling Function").
This setup is designed to prevent accidental output and applies even when the global
change-enabling function has been activated. The password consists of a pre-defined
sequential key combination entered within a specific time interval. If the password has
been changed by the user (see section "Changing the Password”), the following
description will apply accordingly.
G
Oper/CtrlTest/MAIN
Man. trip cmd. USER
appear in the fourth line of the display. Don't execute
********
Don't execute
*
'Right' G
Oper/CtrlTest/MAIN
Man. trip cmd. USER
G
Don't execute
*
'Up’ G
Oper/CtrlTest/MAIN
Man. trip cmd. USER
G
Don't execute
*
'Down' G
Oper/CtrlTest/MAIN
The display will change as shown in the Man. trip cmd USER
G
Execute
G
Oper/CtrlTest/MAIN
Man. trip cmd. USER
indicator labeled EDIT MODE will go out. Don't execute
The unit will execute the command.
The password consists of a combination of keys that must be entered sequentially within
a specific time interval. The ‘left’, ’right’, ‘up’ and ‘down’ keys may be used to define the
password and represent the numbers 1, 2, 3 and 4, respectively:
3
G
1 2
G
The password can be changed by the user at any time. The procedure for this change is
described below. The starting point is the factory-set password.
G
Par/Conf/LOC
Password
appear in the fourth line of the display. ********
********
G
********
change as shown in the column on the right. *
G
Par/Conf/LOC
Password
G
********
*
G
Par/Conf/LOC
Password
G
********
*
G
Par/Conf/LOC
Password
G
********
*
G
*
followed by the DOWN key.
G
Par/Conf/LOC
Password
G
**
G
**
*
G
Par/Conf/LOC
Password
G
**
**
Par/Conf/LOC
Password
password has been re-entered correctly, the ********
LED indicator labeled EDIT MODE goes out
and the display appears as shown on the right.
The new Password L/R is now valid.
Operation from the local control panel without password protection is also possible. To
select this option, immediately press the ENTER key a second time in steps 4 and 6
without entering anything else. This will configure the local control panel without
password protection, and no control actions involving changes will be possible until the
global change-enabling function has been activated (see section "Change-Enabling
Function").
If the configured password has been forgotten, it can be called up on the LCD display as
described below. The procedure involves turning the device off and then on again.
G
TEST
directional keys (‘left’, ‘right’, ‘up’ and ‘down’) at
the same time and hold them down.
Password
startup, the password is displayed.
G
1234
7 Settings
7.1 Parameters
The P43x must be adjusted to the system and to the protected equipment by appropriate
settings. This chapter gives instructions for determining the settings, which are located in
the folder titled ‘Parameters’ in the menu tree. The sequence in which the settings are
listed and described in this chapter corresponds to their sequence in the menu tree.
All settings are reset to their default values after a cold restart. The P43x is blocked in
that case. All settings must be re-entered after a cold restart.
The device identification settings are used to record the ordering information and the
design version of the P43x. They have no effect on the device functions. These settings
should only be changed if the design version of the P43x is modified.
Identification of the change level of the texts of the data model. This display
cannot be altered.
DVICE: Text vers.data model 002 121
Using the ‘text replacement tool’ provided by the operating program, the
user can change the parameter descriptors (plain text designations) and
load them into the device. These customized data models contain an
identifier defined by the user while preparing the data model. This identifier
is displayed at this point in the menu tree. Standard data models have the
identifier ‘0’ (factory-set default).
DVICE: F number 002 124
The F number is the serial number of the device. This display cannot be
altered.
DVICE: AFS Order No. 001 000
Item number of the module inserted in the respective slot 1 to 20. The
display always shows the actual component configuration at any given time.
Index letter specifying the version of the module inserted in the respective
slot (1 to 20).
DVICE: Variant of module A 086 047
MAC address for the network hardware of the Ethernet module. This
address is introduced during manufacture and can only be read.
DVICE: Variant of module L 086 048
Set your numerically coded user data here for your records.
When set to 'Yes' it is apparent that the device is fitted with the local control
panel (HMI).
The password to be used for changing settings from the local control panel
can be defined here. Further information on changing the password is
given in Chapter 6.
LOC: Password L/R 221 040
The password to be used for changing settings from the local control panel
can be defined here. Further information on changing the password is
given in Chapter 6.
(This address is available LOC: Displ. ext.dev.desig 221 032
only with the P433.) This setting defines whether the external device designations shall be
displayed on the Bay Panel.
LOC: Display L/R 221 070
This setting defines whether the control site – local or remote – shall be
displayed on the Bay Panel.
LOC: Displ. interl. stat. 221 071
This setting determines whether the switching (using either the L/R key or
the key switch) is between local and remote control (L↔R) or between
local+remote and local control (R&L↔L).
LOC: Fct. reset key 005 251 Fig. 3-87
Selection of specified counters or event logs that are reset by pressing the
RESET key on the local control panel.
LOC: Fct. read key 080 110
Selection of the event log that will be displayed when the READ key is
pressed.
LOC: Fct. menu jmp list 1 030 238
Setting for the time period during which a panel is displayed, before
switching to the next panel. This setting is only relevant if more values are
selected than can be shown on the LC-Display.
LOC: Autom. return time 003 014 Fig. 3-2
If the user does not press a key on the local control panel during this set
time period, the change-enabling function is disabled.
LOC: Return time select. 221 030
If the user does not press a key on the local control panel during this set
time period, then the selection of a switchgear unit is cancelled.
LOC: Return time illumin. 003 023
If the user does not press a key on the local control panel during this set
time period, then the backlighting of the LCD display is switched off.
Set the same parity that is set at the interface of the PC connected to the
P43x.
PC: Spontan. sig. enable 003 187 Fig. 3-7
Enable for the cyclic transmission of measured values via the PC interface.
PC: Cycl. data ILS tel. 003 185 Fig. 3-7
The active power value is transmitted via the PC interface if it differs by the
set delta quantity from the last measured value transmitted.
PC: Delta f 003 057 Fig. 3-7
All measured values are transmitted again via the PC interface after this
time period has elapsed – provided that transmission has not been triggered
by the other delta conditions.
PC: Time-out 003 188
Setting for the time to elapse after the last telegram exchange via the PC
interface before activating the second communication channel of
communication module B.
Enabling additional settings that are relevant for the protocol based on
IEC 870-5-101.
COMM1: Addit. ILS enable 003 217 Fig. 3-8
Enabling additional settings that are relevant for the ILS protocol.
COMM1: MODBUS enable 003 220 Fig. 3-8
Select the communication protocol that shall be used for the communication
interface.
Setting for the length of the common address for identification of telegram
structures.
Note:
This setting is hidden unless the IEC 870-5-101 protocol is enabled.
"ASDU": Application Service Data Unit
COMM1: Octet 2 addr. ASDU 003 194 Fig. 3-10
Setting for the length of the common higher-order address for identification
of telegram structures.
Note:
This setting is hidden unless the IEC 870-5-101 protocol is enabled.
"ASDU": Application Service Data Unit
COMM1: Addr.length inf.obj. 003 196 Fig. 3-10
Setting for the length of the higher-order address for information objects.
Note: This setting is hidden unless the IEC 870-5-101 protocol is
enabled.
COMM1: Inf.No.<->funct.type 003 195 Fig. 3-10
Setting for the transmission direction. Normally this value will be set to '1' at
the control center and to '0' at the substation.
Note: This setting is hidden unless the IEC 870-5-101 protocol is
enabled.
COMM1: Time-out interval 003 228 Fig. 3-10
Setting for the maximum time that will elapse until the status signal for the
acknowledgment command is issued.
Note: This setting is hidden unless the IEC 870-5-101 protocol is
enabled.
COMM1: Reg.asg. selec. cmds 003 210 Fig. 3-12
Number of bits that must pass between the receipt of the 'request' and the
start of sending the 'response'.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Phys. Char. Timeout 003 242 Fig. 3-13
Number of bits that may be missing from the telegram before receipt is
terminated.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Link Confirm. Mode 003 243 Fig. 3-13
Setting the time period within which the master must acknowledge at the
link layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Link Max. Retries 003 245 Fig. 3-13
Number of repetitions that are carried out on the link layer if errors have
occurred during transmission (such as failure to acknowledge).
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Appl.Confirm.Timeout 003 246 Fig. 3-13
Setting the time period within which the master must acknowledge at the
application layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Time interval within which the slave cyclically requests time synchronization
from the master.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. bin. inputs 003 232 Fig. 3-13
Selection of data points and data classes for object 1 – binary inputs.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. bin.outputs 003 233 Fig. 3-13
Selection of data points and data classes for object 10 – binary outputs.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. bin. count. 003 234 Fig. 3-13
Selection of data points and data classes for object 20 – binary counters.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. analog inp. 003 235 Fig. 3-13
Selection of data points and data classes for object 30 – analog inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. analog outp 003 236 Fig. 3-13
Selection of data points and data classes for object 40 – analog outputs.
Assignment of indexes is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Delta meas.v. (DNP3) 003 250 Fig. 3-13
Cycle time at the conclusion of which the selected measured values are
again transmitted.
Note: This setting is hidden unless the Courier protocol is enabled.
Set the same parity that is set at the interface of the control system
connected to the P43x.
COMM2: Dead time monitoring 103 176 Fig. 3-16
The time between two polling calls from the communication master must be
less than the time set here.
COMM2: Positive ackn. fault 103 203
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
COMM2: Name of manufacturer 103 161 Fig. 3-16
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
COMM2: Spontan. sig. enable 103 177 Fig. 3-16
All measured values are transmitted again via the communication interface
after this time period has elapsed – provided that transmission has not been
triggered by the other delta conditions.
Adjustment of the baud rate for telegram transmission via the teleprotection
interface (InterMiCOM interface) so as to meet the requirements of the
transmission carrier.
COMM3:Source address 120 031
This timer triggers the alarm signals CO MM 3 : Com mu nic a ti ons fau l t
and SFM ON : Co mm un ic .fa ul t CO MM 3 and sets the received signals
to their user-defined default values. Time-out occurs when the set time has
elapsed since the most recent 100% valid telegram was received.
COMM3:Sig.asg. comm.fault 120 034
Using this setting, the alarm signal can be configured (assigned) to the
corresponding PSIG input signal.
COMM3:Time-out link fail. 120 035 Fig. 3-19
IEC 61850 Communication IEC: Function group IEC 056 059 Page: 3-31
Name of the device (IED has server function). This device name serves as
device identification in the IEC 61850 system; it is included in the Logical
Device Name in the IEC data model and must therefore be unambiguous.
All devices logged-on to the network should have non-recurring IED names.
IEC: TCP keep-alive timer 104 062
The subnet mask defines which part of the IP address is addressed by the
sub-network and which part by the device that is logged-on to the network.
Note:
In the S&R 103 operating program, the complete IP address is displayed at
IEC : Sub net m ask . The device’s front panel display only displays the IP
address distributed to these four data model addresses.
IEC: Gateway address 104 011
Device (IED) poll cycle time for time synchronization when operating mode
is set to Request from Server.
Time difference between UTC and local time at the devices' substation
(IED).
IEC: Diff. dayl.sav. time 104 207
These three parameters define the date (e.g. at what day of the year) for
switching from standard time over to daylight saving time. Available for
I E C : D a y l . s a v . t i m e s t a r t are the values 'first', 'second', 'third',
'fourth', and 'last'. For I E C : D a y l . s a v . t i m e s t . d the seven weekdays
are available so that for example a setting like "on the last Sunday in March"
may be used.
IEC: Dayl.sav.t.st.0:00 + 104 223
This defines the time difference and the time of day (on the specific
changeover day) when the clock is to be switched to daylight saving time.
The time is given in the number of minutes after midnight, e.g. when the
clock changeover to 3:00 AM always occurs at 2:00 AM, then the value to
be entered at I E C : D a y l . s a v . t . s t . 0 : 0 0 + is 120 [minutes] and at
I E C : D i f f . d a y l . s a v . t i m e it is 60 [minutes].
IEC: Dayl.sav.time end 104 225
This parameter defines the date and time of day for the clock changeover
from daylight saving time to standard time. The setting is similar to that for
the clock changeover to daylight saving time.
Setting to calculate the filter value for all measured value Report Control
Blocks (RCB) except the measured value for energy. Should a change
occur in one of the measured values, which is greater than the filter value,
the RCB is again sent to all clients. For each measured value the filter
value is calculated according to this formula:
Step size measured value • setting IEC : De adb an d va lue
IEC: Update Measurements 104 229
Setting to calculate the filter value for all IP Report Control Blocks (RCB).
Should a change occur in one of the IP measured values, which is greater
than the filter value, the RCB is again sent to all clients. For each measured
value the filter value is calculated according to this formula:
step size measured value • setting IEC: Dead band IP
IEC: Dead band IN 104 231
Setting to calculate the filter value for all IN Report Control Blocks (RCB).
Should a change occur in one of the IN measured values, which is greater
than the filter value, the RCB is again sent to all clients. For each measured
value the filter value is calculated according to this formula:
step size measured value • setting IEC : Dead ban d IN
IEC: Dead band VPP 104 232
Setting to calculate the filter value for all VPP Report Control Blocks (RCB).
Should a change occur in one of the VPP measured values, which is
greater than the filter value, the RCB is again sent to all clients. For each
measured value the filter value is calculated according to this formula:
step size measured value • setting IEC : Dead ban d VPP
IEC: Dead band VPG 104 233
Setting to calculate the filter value for all VPG Report Control Blocks (RCB).
Should a change occur in one of the VPG measured values, which is
greater than the filter value, the RCB is again sent to all clients. For each
measured value the filter value is calculated according to this formula:
step size measured value • setting IEC : D e a d b a n d V P G
IEC: Dead band f 104 234
Setting to calculate the filter value for all f Report Control Blocks (RCB).
Should a change occur in one of the f measured values, which is greater
than the filter value, the RCB is again sent to all clients. For each measured
value the filter value is calculated according to this formula:
step size measured value • setting IEC: Dead band f
IEC: Dead band P 104 235
Setting to calculate the filter value for all P Report Control Blocks (RCB).
Should a change occur in one of the P measured values, which is greater
than the filter value, the RCB is again sent to all clients. For each measured
value the filter value is calculated according to this formula:
step size measured value • setting IEC : Dead ban d P
Setting to calculate the filter value for all ö Report Control Blocks (RCB).
Should a change occur in one of the φ measured values, which is greater
than the filter value, the RCB is again sent to all clients. For each measured
value the filter value is calculated according to this formula:
step size measured value • setting IEC : Dead ban d ph i
IEC: Dead band Z 104 237
Setting to calculate the filter value for all Z Report Control Blocks (RCB).
Should a change occur in one of the Z measured values, which is greater
than the filter value, the RCB is again sent to all clients. For each measured
value the filter value is calculated according to this formula:
step size measured value • setting IEC : Dead ban d Z
IEC: Dead band min/max 104 238
Setting to calculate the filter value for all min/max Report Control Blocks
(RCB). Should a change occur in one of the min/max measured values,
which is greater than the filter value, the RCB is again sent to all clients.
For each measured value the filter value is calculated according to this
formula:
step size measured value • setting IEC : Dead ban d min/ma x
IEC: Dead band ASC 104 239
Setting to calculate the filter value for all ASC Report Control Blocks (RCB).
Should a change occur in one of the ASC measured values, which is
greater than the filter value, the RCB is again sent to all clients. For each
measured value the filter value is calculated according to this formula:
step size measured value • setting IEC : Dead ban d ASC
IEC: Dead band temp. 104 240
Setting to calculate the filter value for all temperature Report Control Blocks
(RCB). Should a change occur in one of the temperature measured values,
which is greater than the filter value, the RCB is again sent to all clients.
For each measured value the filter value is calculated according to this
formula:
step size measured value • setting IEC: Dead band te mp.
IEC: Dead band 20mA 104 241
Setting to calculate the filter value for all 20mA Report Control Blocks
(RCB). Should a change occur in one of the 20mA measured values, which
is greater than the filter value, the RCB is again sent to all clients. For each
measured value the filter value is calculated according to this formula:
step size measured value • setting IEC : Dead ban d 20mA
IEC: Update cycle energy 104 060
IEC Generic Substation GSSE: Function group GSSE 056 060 Page: 3-37
Status Events
Cancelling function group GSSC or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden. The parameters of this function group are
active only if function group IEC has been configured and is activated, and if
the parameters of this function group have been activated through the
parameter I E C : E n a b l e c o n f i g u r a t i o n or by switching the device
off-line/on-line.
GSSE: General enable USER 104 049 Page: 3-37
Minimum value for the GSSE repetition cycle time in ms. The repetition
cycle time for a GSSE message is calculated, according to a standard, with
this formula:
Repetition cycle time = Min. cycle + (1 + (increment/1000))N-1 [ms]
The repetitions counter N will be restarted at count 1 after each state
change of a GSSE bit pair.
GSSE: Max. cycle 104 053 Page: 3-37
Maximum value for the GSSE repetition cycle time in s. For the formula to
calculate the repetition cycle time see Min. cycle. Should the calculated
value for the repetition cycle time be equal to or greater than the set max.
value then the GSSE message will be sent repeatedly at the set max. value
time.
GSSE: Increment 104 054
Increment for the GSSE repetition cycle. For the formula to calculate the
repetition cycle time see Min. cycle.
GSSE: Operating mode 104 055
Setting with which GSSE bit pair the configured binary signal of the virtual
GSSE outputs is to be transmitted. A GSSE is always transmitted
consisting of a fixed number of 96 bit pairs, of which a maximum of 32 are
used by this device (IED) during a send operation.
GSSE: Output 1 fct.assig. 104 102 Page: 3-37
GSSE: Output 2 fct.assig. 104 105
Setting which GSSE bit pair is assigned to which virtual GSSE input.
A GSSE is always received consisting of a fixed number of 96 bit pairs, of
which a maximum of 32 are processed by this device (IED).
GSSE: Input 1 IED name 105 002 Page: 3-37
GSSE: Input 2 IED name 105 007
IED name for the virtual GSSE input used to identify a GSSE received.
GSSE: Input 1 default 105 003 Page: 3-37
GSSE: Input 2 default 105 008
Default for the virtual binary GSSE input. The state of a virtual two-pole
GSSE input will revert to default as soon as the continuously monitored
communication link to a GSSE sending device (IED situated on the opposite
side) is in fault or has disappeared altogether.
GSSE: Input 1 fct.assig. 105 004 Page: 3-37
Generic Object Oriented GOOSE:Function group GOOSE 056 068 Page: 3-34
Substation Event
Cancelling function group GOOSE or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden. The parameters of this function group are
active only if function group IEC has been configured and is activated, and if
the parameters of this function group have been activated through the
I E C : E n a b l e c o n f i g u r a t i o n parameter or by switching the device off-
line/on-line.
GOOSE:General enable USER 106 001 Page: 3-34
Goose ID being sent by this device (IED). GOOSE includes a Dataset with
32 binary and configurable virtual outputs and 10 two-pole states to the
maximum of 10 monitored external devices
GOOSE:VLAN Identifier 106 006 Fig. 3-20
VLAN identifier of GOOSE being sent by this device (IED). The VLAN
identifier makes it possible to have switches in the network filter messages,
if the switches support such a function. Because so-called multicast MAC
addresses are applied, switches are unable to filter messages in the
network if they do not include a VLAN identifier.
GOOSE:VLAN Priority 106 007 Fig. 3-20
Goose ID for GOOSE, which is to be received by this device (IED) for the
virtual binary GOOSE input.
GOOSE:Input 1 DataSet Ref 107 002
Default for the virtual binary GOOSE input. The state of a virtual two-pole
GOOSE input will revert to default as soon as the continuously monitored
communication link to a GOOSE sending device (IED situated on the
opposite side) is in fault or has disappeared altogether.
GOOSE:Input 1 fct.assig. 107 006 Page: 3-36
GOOSE:Input 2 fct.assig. 107 016
Goose ID for GOOSE, which is to be received by this device (IED) for the
virtual two-pole GOOSE input, representing the state of an external device.
Virtual GOOSE inputs can be linked with interlocking equations of assigned
external devices.
GOOSE:Ext.Dev01 DataSetRef 108 002
Default for the virtual two-pole GOOSE input, representing the state of an
external device. The state of a virtual two-pole GOOSE input will revert to
default as soon as the continuously monitored communication link to a
GOOSE sending device (IED situated on the opposite side) is in fault or has
disappeared altogether.
Once the password has been entered, the function keys remain active for
no longer than this time period. When this time period has elapsed the
password must again be entered.
Binary input
The P43x has opto coupler inputs for processing binary signals from the substation.
The number and connection schemes for the available binary signal inputs are shown in
the terminal connection diagrams.
The P43x identifies the installed modules during startup. If a given binary I/O module is
not installed or has fewer binary signal inputs than the maximum number possible at this
slot, then the configuration addresses for the missing binary signal inputs are
automatically hidden in the menu tree.
When configuring binary inputs, one should keep in mind that the same function can be
assigned to several signal inputs. Thus one function can be activated from several
control points having different signal voltages.
In order to ensure that the device will recognize the input signals, the triggering signals
must persist for at least 30 ms.
The operating mode for each binary signal input can be defined. The user can specify
whether the presence (active ‘high’ mode) or absence (active ‘low’ mode) of a voltage
shall be interpreted as the logic ‘1’ signal.
Input filter which is activated when either the mode "active ‘high’, filtered" or
active ‘low’, filtered" has been selected. In order to suppress transient
interference peaks at the logic signal inputs it is suggested to set this
parameter to 6 [steps]. For further information see Chapter 3.
INP: Fct. assignm. U 601 152 091 Fig. 3-23,
3-33
INP: Fct. assignm. U 602 152 094
Setting for the minimum current that must flow in order for the P43x to
display a measured value > 0 (zero suppression).
MEASI: IDC< open circuit 037 191 Fig. 3-27
If the input current falls below the set threshold, the P43x will issue an ‘open
circuit’ signal.
MEASI: IDC 1 037 150 Fig. 3-27
Setting for the input current that will correspond to a linearized value that
has been set accordingly.
Setting for the linearized current that will correspond to an input current that
has been set accordingly.
MEASI: Scaled val. IDC,lin1 037 192 Fig. 3-28
Binary outputs
The P43x has output relays for the output of binary signals. The number and connection
schemes for the available output relays are shown in the terminal connection diagrams.
The P43x identifies the installed modules during startup. If a given binary I/O module is
not installed or has fewer output relays than the maximum number possible at that slot,
then the configuration addresses for the missing output relays are automatically hidden
in the menu tree.
The contact data for the all-or-nothing relays permits them to be used either as
command relays or as signal relays. One signal can also be assigned simultaneously to
several output relays for the purpose of contact multiplication.
An operating mode can be defined for each output relay. Depending on the selected
operating mode, the output relay will operate in either an energize-on-signal (ES) mode
or a normally-energized (NE) mode and in either a latching or non-latching mode.
For output relays operating in latching mode, the operating mode setting also determines
when latching will be cancelled.
Setting for the transmission time of the selected measured value in BCD
form.
MEASO: Scaled min. val. BCD 037 140 Fig. 3-36
MEASO: Scaled max. val. BCD 037 141 Fig. 3-36
MEASO: BCD-Out min. value 037 142 Fig. 3-36
MEASO: BCD-Out max. value 037 143 Fig. 3-36
Setting for the time delay for output of the selected measured value.
MEASO: Scaled min. val. A-1 037 104 Fig. 3-38
Setting for the minimum scaled measured value to be output. The value to
be set is calculated according to the following equation:
M x,min
M x,scal,min =
M x,RL
where:
Mx,min : maximum transmitted value for the selected measured
value
M x,RL : range limit value of selected measured value
MEASO: Scaled knee val. A-1 037 105 Fig. 3-38
Setting for the scaled measured value for output that defines the knee point
of the characteristic. The value to be set is calculated according to the
following equation:
M x,knee
M x,scal,knee =
M x,RL
where:
M x,knee : knee point value to be transmitted for selected measured
value
M x,RL : range limit value of selected measured value
Setting for the output current that is output for measured values smaller
than or equal to the minimum measured value to be transmitted.
MEASO: AnOut knee point A-1 037 108 Fig. 3-38
Setting for the output current that is output if the measured value is in the
knee point of the characteristic.
with:
Mx,min ... Mx,max : measured values to be issued
MEASO: Output value 1 037 120 Fig. 3-38
LED indicators
The P43x has a total of 23 LED indicators for parallel display of binary signals. LED
indicator H 1 is not configurable. It is labeled "HEALTHY" and signals the operational
readiness of the protection unit (supply voltage present). LED indicators H 2 and H 3 are
not configurable either. H 2 is labeled "OUT OF SERVICE" and signals a blocking or
malfunction; H 3 is labeled "ALARM" and signals a warning alarm. LED indicator H 17
indicates that the user is in the "EDIT MODE".
Section 6.1 describes the layout of the LED indicators and the factory setting for LED
indicator H 4. At this point it is specifically emphasized that there is no permanent
connection given between the freely configurable function keys and the LED indicators
H 18 to H 23 situated directly next to these function keys.
An operating mode can be defined for each LED indicator. Depending on the set
operating mode, the LED indicator will operate in either energize-on-signal (ES) mode
('open-circuit principle') or normally-energized (NE) mode ('closed-circuit principle') and
in either latching or non-latching mode. For LED indicators operating in latching mode,
the operating mode setting also determines when latching will be cancelled.
With the multi-color LED indicators (H 4 – H 16, H 18 – H 23) the red and green colors
can be independently assigned to functions. The third color, amber, is a combination of
red and green, i.e. when both functions assigned to the LED indicator are simultaneously
present.
If a user-specific (customized) bay type has been loaded, its bay type No.
will be displayed. If no customized bay type has been loaded, the number '0'
will be displayed.
MAIN: Prim.Source TimeSync 103 210
Selection of the primary source for date and time synchronization. Available
are COMM1, COMM2/PC, IRIG-B or a binary input for minute signal pulses.
MAIN: BackupSourceTimeSync 103 211
Selection of the backup source for date and time synchronization. Available
are COMM1, COMM2/PC, IRIG-B or a binary input for minute signal pulses.
The backup source is used when there is no synchronization generated by
the primary source after M AIN : Ti me s ync . ti me -ou t has elapsed.
MAIN: Time sync. time-out 103 212
The user specifies the channel on which each physical variable is recorded.
Cancelling a protection
or control function
The user can adapt the device to the requirements of a particular high-voltage system by
including the relevant protection or control functions in the device configuration and
cancelling all others (removing them from the device configuration).
The following conditions must be met before cancelling a protection or control function:
None of the signals of the protection or control function may be linked to other signals
by way of an ‘m out of n’ parameter.
protection (BUOC)
Cancelling function group BUOC or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Check
Cancelling function group ASC or including it in the configuration.
If any function group is cancelled from the configuration, then all associated
settings and signals are hidden.
protection
(This address / function group
is available only with the
P435.)
Cancelling function group GFSC or including it in the configuration.
If any function group is cancelled from the configuration, then all associated
settings and signals are hidden.
protection signaling
(This address / function group
is available only with the
P435.)
Cancelling function group GSCSG or including it in the configuration.
If any function group is cancelled from the configuration, then all associated
settings and signals are hidden.
protection
Cancelling function group DTOC or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Protection
Cancelling function group IDMTx or including it in the configuration.
If the function group is cancelled from the configuration, then all associated
settings and signals are hidden, with the exception of this setting.
signaling
Cancelling function group GFSIG or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Direction Determination
Cancelling function group TGFD or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Protection
Cancelling function group f<> or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Protection
Cancelling function group CBF or including it in the configuration. If the
function group is cancelled from the configuration, then all associated
settings and signals are hidden.
Note:
If the IEC 870-5-101 communication protocol has been set, then the 'low
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN2.
DEV01: Inform. No., signal 210 035
Note:
If the IEC 870-5-101 communication protocol has been set, then the 'high
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN3.
DEV01: Funct. type, command 210 032
Note:
If the IEC 870-5-101 communication protocol has been set, then the 'low
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN2.
DEV01: Inform. No., command 210 033
Note:
If the IEC 870-5-101 communication protocol has been set, then the 'high
address' of the information object will be defined by this setting. If the ILS-C
protocol has been set, then this setting will correspond to DN3.
7.1.3.1 Global
Communication interface 1 COMM1: Command block. USER 003 172 Fig. 3-8
Communication interface 2 COMM2: Command block. USER 103 172 Fig. 3-16
When the test mode user is activated, signals or measured data for PC and
communication interfaces are labeled 'test mode'.
MAIN: Nominal frequ. fnom 010 030 Fig. 3-316,
3-342
Setting for the nominal frequency of the protected system.
MAIN: Rotary field 010 049 Fig. 3-49
For bay control function signals detected via binary signal inputs and
conditioned with debouncing it is now possible to select whether the time
tag for the signal is to be issued after debouncing or when the first pulse
edge is detected. Furthermore it is defined whether entries in the operating
data memory are made in chronological order or not.
Setting for the primary nominal current of the main current transformer for
measurement of residual current.
MAIN: Vnom V.T. prim. 010 002 Fig. 3-50
Setting for the primary nominal voltage of the system transformer for
measurement of phase-to-ground and phase-to-phase voltages.
MAIN: VNG,nom V.T. prim. 010 027 Fig. 3-51
Setting for the primary nominal voltage of the system transformer for
measurement of neutral-point displacement voltage.
MAIN: Vref,nom V.T. prim. 010 100 Fig. 3-52
Setting for the primary nominal voltage of the system transformer for
measurement of reference voltage for automatic synchronism check.
MAIN: Inom device 010 003 Fig. 3-44
Setting for the secondary nominal current of the system transformer for
measurement of phase currents. This also corresponds to the nominal
device current.
MAIN: IN,nom device 010 026 Fig. 3-44
Setting for the secondary nominal current of the system transformer for
measurement of residual current. This also corresponds to the nominal
device current.
MAIN: Dynamic range I 031 082 Fig. 3-53,
3-115
Setting for the dynamic range of the phase current transformers as used by
the P43x.
'Highest range' dynamic range: IP = 100 Inom
'Sensitive range' dynamic range: IP = 25 Inom
Note: The lower the setting for dynamic range, the more accurately the
device will operate. However, make sure that the dynamic range
is set no lower than the maximum possible short-circuit current.
MAIN: Vnom V.T. sec. 010 009 Fig. 3-44
Setting for the secondary nominal voltage of the system transformer for
measurement of phase-to-ground and phase-to-phase voltages.
MAIN: VNG,nom V.T. sec. 010 028 Fig. 3-44
Setting for the secondary nominal voltage of the system transformer for
measurement of neutral-point displacement voltage.
MAIN: Vref,nom V.T. sec. 031 052 Fig. 3-44
Setting for the secondary nominal voltage of the system transformer for
measurement of reference voltage for automatic synchronism check.
MAIN: Conn. meas. circ. IP 010 004 Fig. 3-44
This parameter allows inverting the sign for the following measured
operating values:
MAIN: Active power P prim. (004 050)
MAIN: Reac. power Q prim. (004 052)
MAIN: Active power P p.u. (004 051)
MAIN: Reac. power Q p.u. (004 053)
MAIN: Meas. value rel. IP 011 030 Fig. 3-45
Setting for the minimum current that must be exceeded so that measured
operating values of the phase currents and, if applicable, derived currents
are displayed.
MAIN: Meas. value rel. IN 011 031 Fig. 3-47
Setting for the minimum current that must be exceeded so that the
measured operating value of the residual current is displayed.
MAIN: Meas. value rel. V 011 032 Fig. 3-50
Setting for the minimum voltage that must be exceeded so that measured
operating values of the phase-to-ground voltages, phase-to-phase voltages,
and, if applicable, derived voltages are displayed.
MAIN: Meas. val. rel. VNG 011 033 Fig. 3-51
Setting for the minimum voltage that must be exceeded so that the
measured operating value of the neutral-point displacement voltage is
displayed.
MAIN: Meas. val. rel. Vref 011 034 Fig. 3-52
Setting for the minimum voltage that must be exceeded so that the
measured operating value of the reference voltage for the automatic
synchronism check is displayed.
MAIN: Op. mode energy cnt. 010 138 Fig. 3-56
Setting for the time after which the delayed maximum current display shall
reach 95% of the maximum current IP,max.
MAIN: Fct.assign. reset 1 005 248 Fig. 3-87
Setting the number of signal changes allowed during the chatter monitoring
time before chatter suppression operates.
MAIN: Cmd. dur.long cmd. 221 230
Definition of the binary signal used to switch from remote control to local
control.
MAIN: Auto-assignment I/O 221 065 Fig. 3-43
When a bay type is selected the binary inputs and outputs, required to
control switchgear, are automatically configured with function assignments.
MAIN: Electrical control 221 061
This setting determines whether the binary inputs, that are configured to
control switchgear, will be active with remote control or local control
MAIN: Delay Man.Op.Superv. 221 079
After the delay time period, to be set in this window, has elapsed (with the
signal "Sw. dev. interm. pos." already present and the status signal
continuously absent), the actual switchgear status signal, as obtained from
the respective binary inputs, will be issued. (See also "Processing status
signals from manually operated switchgear")
MAIN: W. ext. cmd. termin. 221 063
This setting determines if bay types, defined for direct motor control, can be
used together with external termination contacts to directly influence the
control process of motor driven switchgear.
MAIN: Inp.assign. tripping 221 010 Fig. 3-81
Selection of the protection function trip command that will be used to form
the CB trip signal.
MAIN: Inp. asg. CB trip 221 013 Fig. 3-81
Definition of the binary signal used by the P43x to signal the 'CB open'
position signal.
MAIN: Inp.asg.CB tr.en.ext 221 050 Fig. 3-81
Definition of the binary signal used to carry the CB trip signal of an external
device.
MAIN: Inp.asg. mult.sig. 1 221 051 Fig. 3-66
Parameter subset selection PSS: Control via USER 003 100 Fig. 3-90
The setting of this timer stage is relevant only if parameter subset selection
is carried out via binary signal inputs. Any voltage-free pause that may
occur during selection is bridged. If, after this time period has elapsed, no
binary signal input has yet been set, then the parameter subset selected
from the local control panel shall apply.
Fault Recording FT_RC: Fct. assig. trigger 003 085 Fig. 3-110
This setting defines the signals that will trigger fault recording and fault data
acquisition.
FT_RC: Pre-fault time 003 078 Fig. 3-112
Setting for the time during which data will be recorded before a fault occurs
(pre-fault recording time).
FT_RC: Post-fault time 003 079 Fig. 3-112
Setting for the time during which data will be recorded after the end of a
fault (post-fault recording time).
Fault Recording FT_RC: Max. recording time 003 075 Fig. 3-112
Setting for the maximum recording time per fault. This includes pre-fault
and post-fault recording times.
Distance Protection DIST: General enable USER 031 073 Fig. 3-113
This setting defines whether distance protection will operate with or without
stabilization against transient transformation errors of capacitive voltage
transformers.
Power swing blocking PSB: General enable USER 014 050 Fig. 3-158
The threshold operate value setting for the power swing blocking is a
percentage. It reflects the change in apparent power over a sampling
interval as referred to the apparent power at the end of the sampling
interval.
PSB: Operate delay, trip 014 063 Fig. 3-162
If the phase current exceeds this threshold, the blocking is cancelled without
time delay.
PSB: Ineg> 014 057 Fig. 3-161
Measuring-Circuit Monitoring MCMON: General enable USER 014 001 Fig. 3-164
Setting for the operate delay after which the 'Meas. circ. (V/I) faulty' signals
will be issued.
MCMON: FF, V enabled USER 014 009 Fig. 3-166
Setting for the time delay for "Fuse Failure" monitoring of the reference
voltage Vref.
Backup overcurrent-time BUOC: General enable USER 014 011 Fig. 3-169,
protection (BUOC) 3-170
Enabling or disabling BUOC protection
BUOC: Operating mode 014 000 Fig. 3-169,
3-170
Setting for the BUOC protection operating mode.
Switch on to Fault Protection SOTF: General enable USER 011 068 Fig. 3-171
The setting of the operating mode defines whether, while the timer is
running, a general starting will lead to a trip command ("trip with starting") or
if the measuring range of the impedance zone 1 is extended by the set zone
extension factor: D I S T : k z e H S R P S x ("trip with extension").
SOTF: Manual close timer 011 060 Fig. 3-171
Setting for the timer stage that will be started by a manual close.
Protective Signaling PSIG: General enable USER 015 004 Fig. 3-172
Auto-Reclosing Control ARC: General enable USER 015 060 Fig. 3-207,
3-221
Enabling or disabling the auto-reclosing control.
Automatic Synchronism ASC: General enable USER 018 000 Fig. 3-239
Check Enabling or disabling the automatic synchronism check.
ASC: Transm.cycle,meas.v. 101 212 Fig. 3-250
Ground fault (short-circuit) GFSC: General enable USER 018 060 Fig. 3-252
protection Disabling or enabling ground fault (short-circuit) protection.
(This address / function group GFSC: IN> 018 063 Fig. 3-253
is available only with the Setting for the operate value of the residual current.
P435.)
GFSC: VNG> 018 062 Fig. 3-253
Setting for the position of the straight line separating forward and backward
(reverse) directions.
GFSC: Start. oper. delay 018 064 Fig. 3-253
Setting for the operate delay of the trip signal in the event of a 'forward'
decision.
GFSC: t2 (backward) 018 067 Fig. 3-262
Setting for the operate delay of the trip signal in the event of a 'backward'
(reverse) decision.
GFSC: t3 (non-directional) 018 068 Fig. 3-262
Ground fault (short-circuit) GSCSG: General enable USER 023 069 Fig. 3-265
protective signaling Disabling or enabling ground fault (short-circuit) protection signaling.
(This address / function group
is available only with the GSCSG: Operating mode 023 079 Fig. 3-270
P435.) Setting for the operating mode of ground fault (short-circuit) protection
signaling.
GSCSG: Channel mode 023 078 Fig. 3-266,
3-268, 3-270,
This setting specifies whether GSCSG and PSIG operate with independent 3-272, 3-274
communication channels or with a common communication channel.
Note: Operation with a common communication channel is only
possible, if the same operating mode is set for both PSIG and GSCSG. The
correct assignment of signals to the functions must be done by setting the
time delays appropriately.
Setting for the delay of the send signal (of the signal comparison release
scheme) and the trip signal. This delay shall be used for coordinating
GSCSG with the other protection functions.
GSCSG: Release time send 023 076 Fig: 3-270,
3-271, 3-275
This setting specifies extension of the send signal after starting of ground
fault (short-circuit) protection has dropped out.
GSCSG: tBlock 023 077 Fig. 3-269
This setting specifies whether the blocking signal will be transmitted only in
the event of a backward (reverse) decision by ground fault (short-circuit)
protection or whether it will be transmitted as long as there is no forward
decision.
GSCSG: Echo on receive 023 080 Fig. 3-274
Setting for the transient blocking time of the echo signal in the event of a
change in fault direction.
GSCSG: Weak infeed trip 023 084 Fig. 3-272
This setting determines whether a trip signal will be issued when the weak-
infeed logic is triggered.
Note: Use of the weak-infeed logic only makes sense if the signal
comparison release scheme has been selected as the operating
mode.
GSCSG: Op.delay weak infeed 023 087 Fig. 3-272
Definite-time overcurrent DTOC: General enable USER 031 068 Fig. 3-276
protection Enabling or disabling the definite-time overcurrent protection function.
Inverse-Time Overcurrent IDMT: General enable USER 017 096 Fig. 3-287
Protection Enabling or disabling the inverse-time overcurrent protection function.
Ground Fault Direction GFDSS: General enable USER 016 060 Fig. 3-299
Determination Using Steady- Enabling or disabling ground fault direction determination by steady-state
State Values values.
GFDSS: Operating mode 016 090 Fig. 3-299
Ground Fault Tripping GFTRP: General enable USER 014 005 Fig. 3-313,
3-314
Disabling and enabling ground fault protection signaling.
Ground fault protective GFSIG: General enable USER 016 078 Fig. 3-315
signaling
Disabling or enabling ground fault protection signaling.
Transient Ground Fault TGFD: General enable USER 016 040 Fig. 3-316
Direction Determination
Enabling or disabling the transient ground fault direction determination.
Thermal Overload Protection THERM: General enable USER 022 050 Fig. 3-323
Time-Voltage Protection V<>: General enable USER 023 030 Fig. 3-328
Setting the evaluation time. The operate conditions must be met for the
duration of the set evaluation time so that a signal is issued.
f<>: Undervolt. block. V< 018 200 Fig. 3-340
Setting for the threshold of undervoltage blocking. If the voltage falls below
this threshold, the over-/underfrequency protection function will be blocked.
Power Directional Protection P<>: General enable USER 014 220 Fig. 3-343
Circuit Breaker Failure CBF: General enable USER 022 080 Fig. 3-357
Protection Enable/disable the circuit breaker failure protection function.
CBF: Start with man. trip 022 154 Fig. 3-361,
3-362
Setting that permit a manual trip signal to also be used as a start criterion.
CBF: Fct.assignm. CBAux. 022 159 Fig. 3-361,
3-362
Selection of trip signals - assigned to Gen. trip command 1 - for which, in
addition to current flow monitoring, status signals from CB auxiliary contacts
are evaluated.
CBF: tCBF 011 067
Setting for the operate delay at the end of which the ‘Circuit breaker failure’
signal is issued.
CBF: I< 022 160 Fig. 3-359,
3-361, 3-362,
3-368, 3-369
Setting for the threshold to detect a break in current flow.
(This address is available CBF: Trip 1p 022 163 Fig. 3-364
only with the P435.) Setting to 'Yes' allows 1-pole monitoring and re-tripping of the CB. Then a
1-pole general trip triggers the 1-pole startup of CBF (see section "CBF 1-
pole operating mode").
(This address is available CBF: t1 1p 022 164 Fig. 3-364
only with the P435.) Setting the 1st CBF timer stage to 1-pole operating mode.
CBF: t1 3p 022 165 Fig. 3-363,
3-364
Setting the 1st CBF timer stage to 3-pole operating mode.
CBF: t2 022 166 Fig. 3-363,
3-364
Setting for the 2nd CBF timer stage.
CBF: Min.dur. trip cmd.t1 022 167 Fig. 3-365,
3-366
Setting the 1st timer stage for minimum duration of trip command.
CBF: Min.dur. trip cmd.t2 022 168 Fig. 3-365,
3-366
Setting the 2nd timer stage for minimum duration of trip command.
CBF: Latching trip cmd.t1 022 169 Fig. 3-365,
3-366
The 1st timer stage trip command, set to latch mode, will remain active until
reset by operating parameters or through an appropriately configured binary
signal input.
CBF: Latching trip cmd.t2 022 170 Fig. 3-365,
3-366
The 2nd timer stage trip command, set to latch mode, will remain active until
reset by operating parameters or through an appropriately configured binary
signal input.
If during this delay time period the circuit breaker does not provide a signal
from its auxiliary contacts that it is closed, then faults behind the CB are
recognized through the current criterion (see section "Fault behind CB
protection").
CBF: Delay/CB sync.superv 022 172 Fig. 3-369
Setting for the time delay to bridge circuit breaker operate times during CB
synchronization supervision.
Limit Value Monitoring LIMIT: General enable USER 014 010 Fig. 3-370
Setting for the operate value of the first overcurrent stage for limit value
monitoring.
LIMIT: I>> 014 020 Fig. 3-370
Setting for the operate value of the second overcurrent stage for limit value
monitoring.
LIMIT: tI> 014 031 Fig. 3-370
Setting for the operate delay of the first overcurrent stage for limit value
monitoring.
LIMIT: tI>> 014 032 Fig. 3-370
Setting for the operate delay of the second overcurrent stage for limit value
monitoring.
LIMIT: I< 014 021 Fig. 3-370
Setting for the operate value of the first undercurrent stage for limit value
monitoring.
LIMIT: I<< 014 022 Fig. 3-370
Setting for the operate value of the second undercurrent stage for limit value
monitoring.
LIMIT: tI< 014 033 Fig. 3-370
Setting for the operate delay of the first undercurrent stage for limit value
monitoring.
LIMIT: tI<< 014 034 Fig. 3-370
Setting for the operate delay of the second undercurrent stage for limit value
monitoring.
LIMIT: VPG> 014 023 Fig. 3-371
Setting for the operate value of overvoltage stage VPG> for limit value
monitoring.
LIMIT: VPG>> 014 024 Fig. 3-371
Setting for the operate value of overvoltage stage VPG>> for limit value
monitoring.
LIMIT: tVPG> 014 035 Fig. 3-371
Setting for the operate delay of overvoltage stage VPG> for limit value
monitoring.
Setting for the operate delay of overvoltage stage VPG>> for limit value
monitoring.
LIMIT: VPG< 014 025 Fig. 3-371
Setting for the operate value of undervoltage stage VPG< for limit value
monitoring.
LIMIT: VPG<< 014 026 Fig. 3-371
Setting for the operate value of undervoltage stage VPG<< for limit value
monitoring.
LIMIT: tVPG< 014 037 Fig. 3-371
Setting for the operate delay of undervoltage stage VPG< for limit value
monitoring.
LIMIT: tVPG<< 014 038 Fig. 3-371
Setting for the operate delay of undervoltage stage VPG<< for limit value
monitoring.
LIMIT: VPP> 014 027 Fig. 3-371
Setting for the operate value of overvoltage stage VPP> for limit value
monitoring.
LIMIT: VPP>> 014 028 Fig. 3-371
Setting for the operate value of overvoltage stage VPP>> for limit value
monitoring.
LIMIT: tVPP> 014 039 Fig. 3-371
Setting for the operate delay of overvoltage stage VPP> for limit value
monitoring.
LIMIT: tVPP>> 014 040 Fig. 3-371
Setting for the operate delay of overvoltage stage VPP>> for limit value
monitoring.
LIMIT: VPP< 014 029 Fig. 3-371
Setting for the operate value of undervoltage stage VPP< for limit value
monitoring.
LIMIT: VPP<< 014 030 Fig. 3-371
Setting for the operate value of undervoltage stage VPP<< for limit value
monitoring.
LIMIT: tVPP< 014 041 Fig. 3-371
Setting for the operate delay of undervoltage stage VPP< for limit value
monitoring.
LIMIT: tVPP<< 014 042 Fig. 3-371
Setting for the operate delay of undervoltage stage VPP<< for limit value
monitoring.
LIMIT: VNG> 014 043 Fig. 3-372
Setting for the operate value of overvoltage stage VNG> for limit value
monitoring.
LIMIT: VNG>> 014 044 Fig. 3-372
Setting for the operate value of overvoltage stage VNG>> for limit value
monitoring.
Setting for the operate delay of overvoltage stage VNG> for limit value
monitoring.
LIMIT: tVNG>> 014 046 Fig. 3-372
Setting for the operate delay of overvoltage stage VNG>> for limit value
monitoring.
LIMIT: Vref> 042 144 Fig. 3-374
Setting for the operate value of overvoltage stage Vref> for limit value
monitoring. (Relevant only with circuit board 5V, i.e. ordering option Vnom
= 50 to 130 V {5 poles} for ASC).
LIMIT: Vref>> 042 145 Fig. 3-374
Setting for the operate value of overvoltage stage Vref>> for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref> 042 148 Fig. 3-374
Setting for the operate delay of overvoltage stage Vref> for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref>> 042 149 Fig. 3-374
Setting for the operate delay of overvoltage stage Vref>> for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: Vref< 042 146 Fig. 3-374
Setting for the operate value of undervoltage stage Vref< for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: Vref<< 042 147 Fig. 3-374
Setting for the operate value of undervoltage stage Vref<< for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref< 042 150 Fig. 3-374
Setting for the operate delay of undervoltage stage Vref< for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: tVref<< 042 151 Fig. 3-374
Setting for the operate delay of undervoltage stage Vref<< for limit value
monitoring. (Relevant only with circuit board 5V).
LIMIT: IDC,lin> 014 110 Fig. 3-373
Setting for the operate value IDC,lin> for monitoring the linearized direct
current.
LIMIT: IDC,lin>> 014 111 Fig. 3-373
Setting for the operate value IDC,lin>> for monitoring the linearized direct
current.
LIMIT: tIDC,lin> 014 112 Fig. 3-373
Setting for the operate value IDC,lin< for monitoring the linearized direct
current.
Setting for the operate value IDC,lin<< for monitoring the linearized direct
current.
LIMIT: tIDC,lin< 014 116 Fig. 3-373
These settings define the static input conditions for the logic function.
These settings define the operating modes for the output timer stages.
LOGIC: Time t1 output 1 030 002 Fig. 3-377
LOGIC: Time t1 output 2 030 006
These settings assign the function of a binary input signal to the output of
the logic equation.
LOGIC: Sig.assig.outp. 1(t) 044 001 Fig. 3-383
These settings assign the function of a binary input signal to the output of
the logic equation.
Group assignment for the debouncing time and the chatter suppression.
SIG_1: Min. sig. dur. S001 226 002 Fig. 3-395
The logic '1' signal must be available for this minimum time setting so that a
telegram can be sent in the "Start/end signal" mode.
Main function MAIN: Neutr.pt. treat. PSx 010 048 001 076 001 077 001 078 Fig: 3-114,
3-115, 3-116,
3-117, 3-169,
3-170, 3-214,
3-232, 3-247
The neutral-point treatment of the system must be set here.
(This address is available MAIN: 3p tr.if HSR off PSx 015 065 024 034 024 094 025 054 Fig. 3-74
only with the P435.) This setting defines whether single-pole trip commands shall be converted
to a three-pole trip command when ARC is disabled.
MAIN: Ground starting PSx 001 249 001 250 001 251 002 001
Fault data acquisition FT_DA: Line length PSx 010 005 010 006 010 007 010 008 Fig. 3-108
This setting defines the distance in km that the fault locator interprets as
100 % when calculating the line distance to a fault.
FT_DA: Line reactance PSx 010 012 010 013 010 014 010 015 Fig. 3-108
This setting defines the reactance X that the fault locator interprets as
100 % when calculating the line distance to a fault.
FT_DA: Start data acqu. PSx 010 011 010 042 010 043 010 044 Fig. 3-106
This setting determines at what point during a fault the acquisition of fault
data should take place.
FT_DA: Outp. flt.locat. PSx 010 032 010 033 010 034 010 035 Fig. 3-106
Setting for the conditions under which a fault location output occurs.
Distance Protection DIST: I>> PSx 010 054 010 074 010 094 011 014 Fig. 3-114
DIST: Z evaluation PSx 025 093 024 013 024 073 025 033 Fig. 3-122
This setting determines whether the P43x will carry out the starting
impedance calculation of the phase-to-ground loops using the phase current
corrected by the set ground factor or using twice the phase current.
Note: Calculation with twice the phase current may be necessary in
low-impedance-grounded networks in order to avoid inadvertent starting in
healthy lines as the result of the high ground fault current. Impedance is
calculated by the distance measuring system using solely the phase current
corrected by the set ground factor.
DIST: IN> high range PSx 010 055 010 075 010 095 011 015 Fig. 3-115
Operate value setting for the residual current stage of ground starting.
Note: This setting is effective only when Highest range is set for
‘Dynamic range I’.
DIST: IN> sens. range PSx 010 123 010 124 010 125 010 126 Fig. 3-115
Operate value setting for the residual current stage of ground starting.
Note: This setting is effective only when "Dynamic range I" is set to
'Sensitive range'.
DIST: tIN> PSx 010 057 010 077 010 097 011 017 Fig. 3-115
Operate value setting for the voltage trigger VNG> of ground starting.
DIST: VNG>> PSx 010 062 010 082 011 002 011 022 Fig. 3-115
Operate value setting for the voltage trigger VNG>> of ground starting.
DIST: tVNG>> PSx 010 061 010 081 011 001 011 021 Fig. 3-115
DIST: X1 (polygon) PSx 012 001 012 051 013 001 013 051 Fig. 3-138
DIST: X2 (polygon) PSx 012 002 012 052 013 002 013 052 Fig. 3-137
DIST: X3 (polygon) PSx 012 003 012 053 013 003 013 053 Fig. 3-137
DIST: X4 (polygon) PSx 012 004 012 054 013 004 013 054 Fig. 3-137
DIST: X5 (polygon) PSx 012 100 012 101 012 102 012 103 Fig. 3-137
DIST: X6 (polygon) PSx 012 104 012 105 012 106 012 107 Fig. 3-137
This setting defines the inclination of the limiting line of the tripping polygon
of impedance zones 1 to 6 in the R direction (resistance line).
DIST: σ1 (polygon) PSx 072 086 073 086 074 086 075 086 Fig. 3-138
DIST: σ2 (polygon) PSx 072 087 073 087 074 087 075 087 Fig. 3-137
DIST: σ3 (polygon) PSx 072 088 073 088 074 088 075 088 Fig. 3-137
DIST: σ4 (polygon) PSx 072 089 073 089 074 089 075 089 Fig. 3-137
DIST: σ5 (polygon) PSx 012 156 012 157 012 158 012 159 Fig. 3-137
DIST: σ6 (polygon) PSx 012 160 012 161 012 162 012 163 Fig. 3-137
This setting defines the inclination of the limiting line of the tripping polygon
of impedance zones 1 to 4 in the X direction (reactance line).
DIST: Z1 (circle) PSx 012 042 073 091 074 091 075 091 Fig. 3-134
DIST: Z2 (circle) PSx 012 043 073 092 074 092 075 092 Fig. 3-133
DIST: Z3 (circle) PSx 012 044 073 093 074 093 075 093 Fig. 3-133
DIST: Z4 (circle) PSx 012 045 073 094 074 094 075 094 Fig. 3-133
DIST: Z5 (circle) PSx 012 148 012 149 012 150 012 151 Fig. 3-133
DIST: Z6 (circle) PSx 012 152 012 153 012 154 012 155 Fig. 3-133
DIST: α1 (circle) PSx 072 090 073 090 074 090 075 090 Fig. 3-134
DIST: α2 (circle) PSx 072 095 073 095 074 095 075 095 Fig. 3-133
DIST: α3 (circle) PSx 072 096 073 096 074 096 075 096 Fig. 3-133
DIST: α4 (circle) PSx 072 099 073 099 074 099 075 099 Fig. 3-133
DIST: α5 (circle) PSx 012 164 012 165 012 166 012 167 Fig. 3-133
DIST: α6 (circle) PSx 012 168 012 169 012 170 012 171 Fig. 3-133
This setting is only important if the setting With arc compensation is active.
In this case, the setting at this address determines the angle where arc
compensation becomes active in zones 1 to 6.
DIST: Arc comp. circle PSx 012 038 012 090 012 091 012 092 Fig. 3-131
DIST: kze,PG HSR PSx 012 034 012 084 013 034 013 084 Fig. 3-134,
3-138
Setting for the HSR zone extension factor for phase-to-ground loops.
The setting for the zone extension factor modifies the zone 1 reactance and
resistance limits of the polygon characteristic. The following applies to the
measurement:
X1,zeHSR = (kzeHSR)·X1
R1,zeKU = (kzeHSR)·R1
DIST: kze,PP HSR PSx 012 035 012 085 013 035 013 085 Fig. 3-134,
3-138
Setting for the HSR zone extension factor for phase-to-ground or phase-to-
phase loops. The setting for the zone extension factor modifies the zone 1
reactance and resistance limits of the polygon characteristic. The following
applies to the measurement:
X1,zeHSR = (kzeHSR)·X1
R1,zeHSR = (kzeHSR)·R1
DIST: kze,PG TDR PSx 012 046 012 096 013 046 013 096 Fig. 3-134,
3-138
Setting for the TDR zone extension factor for phase-to-ground loops.
The setting for the zone extension factor modifies the zone 1 reactance and
resistance limits of the polygon characteristic. The following applies to the
measurement:
X1,zeTDR = (kzeTDR)·X1
R1,zeTDR = (kzeTDR)·R1
X1,zeTDR = (kzeTDR)·X1
R1,zeTDR = (kzeTDR)·R1
DIST: Abs. value kG PSx 012 037 012 087 013 037 013 087 Fig. 3-121
Setting for the absolute value of the complex ground factor kG.
Z 0 − Zpos
kG =
3 ⋅ Zpos
Z 0 : zero-sequence impedance
Z pos : positive-sequence impedance
kG =
( X 0 − X pos )2 + (R0 − Rpos )2
3 ⋅ Rpos 2 + X pos 2
If the calculated value cannot be set exactly, then a next smaller value
should be set.
DIST: Angle kG PSx 012 036 012 086 013 036 013 086 Fig. 3-121
Setting for the absolute value and the angle of the complex ground factor,
kG.
Z 0 − Zpos
kG =
3 ⋅ Zpos
Z 0 : zero-sequence impedance
Z pos : positive-sequence impedance
kG =
( X 0 − X pos )2 + (R0 − Rpos )2
3 ⋅ Rpos 2 + X pos 2
X 0 − X pos X pos
k G angle = arc tan − arc tan
R0 − Rpos Rpos
If the calculated value cannot be set exactly, then a next smaller value
should be set.
(This address is available DIST: Trip zone 1 PG PSx 011 050 011 051 011 052 011 053 Fig. 3-157
only with the P435.) For zone 1 the user can specify whether the distance trip in the event of
phase-to-ground faults shall be single-pole or three-pole.
Note: When the P43x is being operated with ARC, which will carry out
a reclosure in the event of a single-pole or three-pole trip, then the setting
here should be 1-pole.
(This address is available DIST: Trip zone 1 PP PSx 011 054 011 055 011 056 011 057 Fig. 3-157
only with the P435.) For zone 1 the user can specify whether the distance trip in the event of
phase-to-phase faults shall be single-pole or three-pole. Where a single-
pole trip has been selected, there is a choice as to whether the trip in the
event of a two-pole starting should be for the leading or the trailing phase.
Note: When the P43x is being operated with ARC, which will carry out
a reclosure in the event of a single-pole or three-pole trip, then the setting
here should be 1-pole.
Power swing blocking PSB: Enabled PSx 015 090 015 091 015 092 015 093
This setting defines the setting group in which the power swing blocking
function is enabled.
Backup overcurrent-time BUOC: I> PSx 010 058 010 078 010 098 011 018 Fig. 3-169,
protection (BUOC) 3-170
Operate value setting for the phase currents of the backup overcurrent-time
protection function.
BUOC: tI> PSx 010 059 010 079 010 099 011 019 Fig. 3-169,
3-170
Operate delay for the backup overcurrent-time protection.
BUOC: IN> PSx 010 064 010 084 011 004 011 024 Fig. 3-169,
3-170
Operate value setting for the residual current of the backup overcurrent-time
protection function.
Note: This setting is only active if the setting at
MAIN : N eutra l- po in t tre a tm. is low-impedance grounding.
BUOC: tIN> PSx 010 065 010 085 011 005 011 025 Fig. 3-169,
3-170
Operate delay for the backup overcurrent-time protection.
Protective Signaling PSIG: Enabled PSx 015 014 015 015 015 016 015 017 Fig. 3-172
PSIG: Oper. mode trip PSx 015 107 015 108 015 113 015 114 Fig: 3-185,
3-186, 3-188,
3-189, 3-191,
3-192
This setting defines whether a trip triggered by protective signaling will be a
function of direction or distance.
PSIG: Tripping time PSx 015 011 024 003 024 063 025 023 Fig. 3-173
The tripping time replaces timer stage t1,ze of distance protection when
protective signaling is ready.
PSIG: Release t. send PSx 015 002 024 001 024 061 025 021 Fig: 3-175,
3-180, 3-181,
3-182, 3-183,
3-185, 3-186,
3-188, 3-189,
3-191, 3-192,
3-194, 3-195,
3-199
This setting determines the duration of the send signal.
PSIG: DC loop op. mode PSx 015 012 024 051 025 011 025 071 Fig. 3-194,
3-195
This setting defines whether the transmitting relay will be operated in
energize-on-signal (ES) mode ('open-circuit principle') or normally-energized
(NE) mode ('closed-circuit principle'), i.e., 'Transm.relay make co' or
'Transm.relay break c', respectively.
Note: This setting is active only in the 'DC loop' operating mode.
PSIG: Echo on receive PSx 015 003 024 002 024 062 025 022 Fig. 3-203,
3-204
This setting determines whether protective signaling operates with or
without echo.
PSIG: Op. delay echo PSx 015 022 024 008 024 068 025 028 Fig. 3-203,
3-204
Setting for the operate delay of the echo pulse.
PSIG: Pulse dur. echo PSx 015 023 024 009 024 069 025 029 Fig. 3-203,
3-204
Setting for echo pulse duration.
PSIG: Trip signal V< PSx 015 021 024 007 024 067 025 027 Fig. 3-202
This setting determines whether a trip signal will be issued when the weak-
infeed logic is triggered.
PSIG: V< weak infeed PSx 015 020 024 006 024 066 025 026 Fig. 3-202
PSIG: 3ended line prot PSx 006 039 006 046 006 047 006 048 Fig. 3-174
Auto-Reclosing Control ARC: Enabled PSx 015 046 015 047 015 048 015 049 Fig. 3-207,
3-221
This setting defines the parameter subset in which ARC is enabled.
ARC: CB clos.pos.sig. PSx 015 050 024 024 024 084 025 044 Fig. 3-208,
3-222
This setting defines whether the CB closed position will be scanned or not.
If the setting is 'With', a binary signal input must be configured accordingly.
ARC: Operating mode PSx 015 100 015 101 015 102 015 103 Fig. 3-206,
3-220
This setting defines whether the ARC will carry out HSR and TDR, only
TDR, or only a test HSR.
ARC: Operative time 1 PSx 015 066 024 035 024 095 025 055 Fig. 3-218,
3-236
Setting for the operative time 1.
ARC: Operative time 2 PSx 015 083 024 042 025 002 025 062 Fig. 3-236
ARC: Mon. PSIG recv. PSx 015 082 024 050 025 010 025 070 Fig. 3-217,
3-235
This setting determines whether the number of PSIG receive signals is
monitored during the dead time.
ARC: Zone ext. f. HSR PSx 015 059 024 033 024 093 025 053 Fig. 3-216,
3-234
This setting determines whether the measuring range shall be extended by
the zone extension factor kze HSR during normal system operation and
while the operative times are elapsing.
Note: This setting is only active if protective signaling is not ready.
ARC: No. permit. TDR PSx 015 068 024 037 024 097 025 057 Fig. 3-218,
3-236
Setting for the number of time-delayed reclosures permitted. With the ‘0’
setting, only one HSR is carried out.
ARC: Trip time TDR PSx 015 073 024 041 025 001 025 061 Fig. 3-210,
3-224
The TDR tripping time replaces timer stage t1,ze of distance protection or
the operate delay of backup overcurrent-time protection – provided that the
BUOC operating mode is set accordingly – if a TDR is permitted and
protective signaling is not ready.
ARC: TDR dead time PSx 015 057 024 031 024 091 025 051 Fig. 3-218,
3-236
Setting for the TDR dead time.
ARC: Zone ext. f. TDR PSx 015 071 024 039 024 099 025 059 Fig. 3-216,
3-234
This setting determines whether the measuring range shall be extended
prior to a TDR.
ARC: Enable RRC PSx 015 085 024 044 025 004 025 064 Fig. 3-214,
3-232
Enabling the rapid reclosure (RRC) function.
ARC: tRRC PSx 015 086 024 045 025 005 025 065 Fig. 3-218,
3-236
Setting for the timer stage of rapid reclosure (RRC).
ARC: V> RRC PSx 015 087 024 046 025 006 025 066 Fig. 3-214,
3-232
Setting for the voltage threshold that must be exceeded in order for an RRC
to be carried out.
ARC: Reclaim time PSx 015 054 024 028 024 088 025 048 Fig. 3-218,
3-236
Setting for the reclaim time.
ARC: Block. time int. PSx 015 043 024 021 024 081 025 041 Fig. 3-209,
3-223
Setting for the time that will elapse before the ARC will be ready again after
cancellation of the blocks set by the P43x.
ARC: Block. time ext. PSx 015 058 024 032 024 092 025 052 Fig. 3-209,
3-223
Setting for the time that will elapse before the ARC will be ready again after
blocking by a binary signal input.
ARC: Zone ext.dur. RC PSx 015 088 024 047 025 007 025 067 Fig. 3-216,
3-234
This setting defines whether the following takes place:
A zone extension will be carried out during a close command by a HSR
that is not synchronism-checked.
Zone extension will occur with each reclose command.
ARC: Parallel trip PSx 015 053 024 027 024 087 025 047 Fig. 3-218,
3-236
This setting defines whether the trip commands of a protection device
operating together with the P43x will affect operation of the ARC function.
For further details see the section entitled ‘Parallel Blocking’ in Chapter 3.
Automatic Synchronism ASC: Enabled PSx 018 020 018 021 018 022 018 023 Fig. 3-239
Check This setting defines the parameter subset in which automatic synchronism
check (ASC) is enabled.
ASC: CB assignment PSx 037 131 037 132 037 133 037 134 Fig. 3-249
This setting defines the function group DEVxx that will control the circuit
breaker.
ASC: System integrat. PSx 037 135 037 136 037 137 037 138 Fig. 3-249
This setting defines whether ASC will operate in 'Autom. synchron. check' or
'Autom. synchr. control' mode.
ASC: Active for HSR PSx 018 001 077 030 078 030 079 030 Fig. 3-240
This setting defines whether reclosing after a three-pole HSR will occur only
after being enabled by ASC.
ASC: Active for TDR PSx 018 002 077 031 078 031 079 031 Fig. 3-240
This setting defines whether reclosing after a three-pole TDR will occur only
after being enabled by ASC.
ASC: Active for RRC PSx 018 006 077 033 078 033 079 033 Fig. 3-240
Auto-reclosing control:
Criteria for a close enable are defined by setting for the operating mode.
ASC: AR with tCB PSx 000 038 000 039 000 050 000 051
Auto-reclosing control:
In slightly asynchronous power systems, setting this parameter to yes
ensures that the circuit breaker closing time is taken into account by the
automatic synchronism check (ASC) to issue of a close command.
ASC: AR Op.mode v-chk.PSx 018 029 018 030 018 031 018 032 Fig. 3-244
Auto-reclosing control:
This setting defines the logic linking of trigger decisions for a voltage
controlled close enable.
ASC: AR V> volt.check PSx 026 017 077 043 078 043 079 043 Fig. 3-244
Auto-reclosing control:
Setting the voltage threshold that the phase-to-ground voltages and the
reference voltage must exceed so that they are recognized as "Voltage
showing".
Note: The logic linking of trigger decisions is defined by setting
ASC: AR Op.mode v-chk.PSx.
ASC: AR V< volt.check PSx 018 017 077 040 078 040 079 040 Fig. 3-244
Auto-reclosing control:
Setting the voltage threshold that the phase-to-ground voltages and the
reference voltage must fall below so that they are recognized as "Voltage
showing".
Note: The logic linking of trigger decisions is defined by setting
ASC: AR Op.mode v-chk.PSx.
ASC: AR tmin v-check PSx 018 018 077 041 078 041 079 041 Fig. 3-244
Auto-reclosing control:
Setting for the operate delay value to define the minimum time period during
which voltage conditions must be met so that the close enable of the ASC is
effected.
ASC: AR V> sync.check PSx 018 011 077 035 078 035 079 035 Fig. 3-246
Auto-reclosing control:
Setting for the threshold of the minimum voltage to obtain a synchronism
checked close enable.
ASC: AR delta Vmax PSx 018 012 077 036 078 036 079 036 Fig. 3-246
Auto-reclosing control:
Setting for the maximum differential voltage between measured and
reference voltages to obtain a synchronism checked close enable.
ASC: AR delta f max PSx 018 014 077 038 078 038 079 038 Fig. 3-246
Auto-reclosing control:
Setting for the maximum differential frequency between measured and
reference voltages to obtain a synchronism checked close enable.
ASC: AR delta phi max PSx 018 013 077 037 078 037 079 037 Fig. 3-246
Auto-reclosing control:
Setting for the maximum differential angle between measured and reference
voltages to obtain a synchronism checked close enable.
ASC: AR tmin sync.chk PSx 018 015 077 039 078 039 079 039 Fig. 3-246
Auto-reclosing control:
Setting for the operate delay value to define the minimum time period during
which synchronism conditions must be met so that the close enable of the
ASC is effected.
ASC: MC op. mode PSx 000 056 000 057 000 058 000 059 Fig. 3-247
ASC: MC delta f max PSx 000 084 000 086 000 087 000 088 Fig. 3-247
Ground fault (short-circuit) GFSC: Enabled PSx 018 072 018 073 018 074 018 075 Fig. 3-252
protection This setting defines the parameter subset in which ground fault (short-
(This address / function group circuit) protection is enabled.
is available only with the
P435.)
Ground fault (short-circuit) GSCSG: Enabled PSx 023 071 023 072 023 073 023 074 Fig. 3-265
protective signaling This setting defines the parameter subset in which ground fault (short-
(This address / function group circuit) protection signaling is enabled.
is available only with the
P435.)
Definite-time overcurrent DTOC: Enabled PSx 072 098 073 098 074 098 075 098 Fig. 3-276
protection This setting defines the parameter subset in which definite-time overcurrent
protection is enabled.
DTOC: I> PSx 072 007 073 007 074 007 075 007 Fig. 3-277
DTOC: Puls.prol.IN>,intPSx 017 055 073 042 074 042 075 042 Fig. 3-284
Setting for the pulse prolongation time of the hold-time logic for intermittent
ground faults.
DTOC: tIN,interm. PSx 017 056 073 038 074 038 075 038 Fig. 3-284
Setting for the tripping time of the hold-time logic for intermittent ground
faults.
DTOC: Hold-t. tIN>,intmPSx 017 057 073 039 074 039 075 039 Fig. 3-284
Setting for the operate delay of overcurrent stage Ineg> (Ineg = negative-
sequence current).
DTOC: tIneg>> PSx 072 024 073 024 074 024 075 024 Fig. 3-278
This setting defines which residual current will be monitored by the residual
current stages: the residual current calculated from the three phase currents
or the residual current measured at the T 4 transformer.
DTOC: IN> PSx 072 015 073 015 074 015 075 015 Fig. 3-280
DTOC: IN>>>> PSx 072 018 073 018 074 018 075 018 Fig. 3-280
Setting the operate value of the fourth overcurrent stage (residual current
stage).
Caution! The range of setting values includes operate values that are not
permitted as continuous current values (see Chapter 'Technical Data').
DTOC: tIN> PSx 072 027 073 027 074 027 075 027 Fig. 3-280
This setting defines the threshold value that the neutral-point displacement
voltage must exceed so that the direction determination is enabled.
DTOC: Angle phiG PSx 004 092 004 247 004 248 004 249 Fig. 3-282
Setting for the position of the straight line separating forward and backward
(reverse) directions.
DTOC: Direction tIN> PSx 072 032 072 042 072 082 072 091 Fig. 3-283
DTOC: Direction tIN>> PSx 072 033 072 043 072 083 072 092 Fig. 3-283
DTOC: Direction tIN>>> PSx 072 034 072 044 072 084 072 093 Fig. 3-283
DTOC: Direction tIN>>>>PSx 072 035 072 045 072 085 072 094 Fig. 3-283
Inverse-Time Overcurrent IDMT: Enabled PSx 072 000 073 000 074 000 075 000 Fig. 3-287
Protection
This setting defines the parameter subset in which inverse-time overcurrent
protection is enabled (phase current system).
IDMT: Iref,P PSx 072 050 073 050 074 050 075 050 Fig. 3-294
Setting for the factor kt,P of the starting characteristic (phase current
system).
IDMT: Release P PSx 072 059 073 059 074 059 075 059 Fig. 3-294
IDMT: Op. w/o volt. P PSx 072 068 073 068 074 068 075 068 Fig. 3-298
This setting determines the operating mode of IDMT protection in the event
of measuring voltage failure (phase current system).
IDMT: Iref,neg PSx 072 051 073 051 074 051 075 051 Fig. 3-294
This setting determines the operating mode of IDMT protection in the event
of measuring voltage failure (negative-sequence current system).
IDMT: Evaluation IN PSx 073 222 073 239 073 245 073 255 Fig. 3-288
This setting defines which residual current will be monitored by the residual
current stages: the residual current calculated from the three phase currents
or the residual current measured at the T 4 transformer.
IDMT: Iref,N (meas.) PSx 001 169 001 170 001 171 001 172
IDMT: Iref,N (calc.) PSx 072 052 073 052 074 052 075 052 Fig. 3-294
Setting for the minimum trip time of the residual current measuring system
This timer stage is started as soon as the minimum operate value is
exceeded. After the timer has elapsed, the trip signal is issued, regardless
of the value of the current.
IDMT: Factor kt,N PSx 072 055 073 055 074 055 075 055 Fig. 3-294
Setting for the factor kt,N of the starting characteristic (residual current
system).
IDMT: Release N PSx 072 061 073 061 074 061 075 061 Fig. 3-294
This setting determines the operating mode of IDMT protection in the event
of measuring voltage failure (residual current system).
IDMT: Comp.react. Xneg PSx 002 193 002 194 002 195 002 196
Setting for parameter Xneg to correct the measuring voltage (see sections
IDMT, GFSC, "Improved directional measurement for series compensated
line applications").
Ground fault direction GFDSS: Enabled PSx 001 050 001 051 001 052 001 053 Fig. 3-299
determination using This setting defines the parameter subset in which the GFDSS function is
steady-state values enabled.
GFDSS: Op.m.GF pow./adm PSx 016 063 000 236 000 237 000 238 Fig: 3-301,
3-307, 3-310
Setting for the operating mode of the ground fault direction determination by
steady-state values. The following settings are possible: The following
settings are possible:
"cos ϕ circuit" for resonant-grounded systems.
"sin ϕ circuit" for isolated neutral-point systems.
GFDSS: Evaluation VNG PSx 016 083 001 011 001 012 001 013 Fig. 3-300
GFDSS: f/fnom (I meas.) PSx 016 092 001 047 001 048 001 049 Fig. 3-305
Setting for the sector angle for measurement in the line side direction.
Note: This setting is effective only in the "cos ϕ circuit" operating mode.
GFDSS: Operate delay LS PSx 016 066 000 245 000 246 000 247 Fig. 3-304,
3-310
Setting for the operate delay of the direction decision in the forward
direction.
GFDSS: Release delay LS PSx 016 072 001 005 001 006 001 007 Fig. 3-304,
3-310
Setting for the release delay (reset time) of the direction decision in the
forward direction.
GFDSS: IN,act>/reac> BS PSx 016 067 000 251 000 252 000 253 Fig. 3-304
Setting for the sector angle for measurement in the direction of the busbar
side.
Note: This setting is effective only in the "cos ϕ circuit" operating mode.
GFDSS: Operate delay BS PSx 016 069 000 254 000 255 001 001 Fig. 3-304,
3-310
Setting for the operate delay of the direction decision in the backward
(reverse) direction.
GFDSS: Release delay BS PSx 016 073 001 008 001 009 001 010 Fig. 3-304,
3-310
Setting for the release delay (reset time) of the direction decision in the
backward direction.
GFDSS: IN> PSx 016 093 001 017 001 018 001 019 Fig. 3-305
Setting for the release delay (reset time) of steady-state current evaluation.
GFDSS: G(N)> / B(N)> LS PSx 016 111 001 029 001 030 001 031 Fig. 3-310
GFDSS: Y(N)> PSx 016 113 001 035 001 036 001 037 Fig. 3-311
Setting for the operate value of the admittance for non-directional ground
fault determination (in operating mode 'admittance evaluation').
GFDSS: Phi offset PSx 016 110 001 026 001 027 001 028 Fig. 3-307
Setting for the operate delay value of the admittance for non-directional
ground fault determination (in operating mode 'admittance evaluation').
GFDSS: Rel. delay Y(N)> PSx 016 115 001 041 001 042 001 043 Fig. 3-311
Setting for the release delay (reset time) of the admittance for non-
directional ground fault determination (in operating mode 'admittance
evaluation').
Ground Fault Tripping GFTRP: Enabled PSx 001 135 001 148 001 149 001 150
This setting defines the parameter subset in which the GFTRP function is
enabled.
Ground fault protective GFSIG: Enabled PSx 001 134 001 136 001 137 001 138
signaling This setting defines the parameter subset in which the GFSIG function is
enabled.
GFSIG: Operate delay PSx 016 076 001 142 001 143 001 144 Fig. 3-315
Transient Ground Fault TGFD: Enabled PSx 001 054 001 055 001 056 001 057 Fig. 3-316
Direction Determination This setting defines the parameter subset in which the TGFD function is
enabled.
TGFD: Evaluation VNG PSx 016 048 001 058 001 059 001 060 Fig. 3-317
TGFD: VNG> PSx 016 041 001 061 001 062 001 063 Fig. 3-318
Setting for the signal buffer time for transient ground fault direction
determination.
Thermal Overload Protection THERM: Enabled PSx 072 175 073 175 074 175 075 175 Fig. 3-323
Setting for the thermal time constants of the protected object with current
flow (Ibl: base line current).
THERM: Tim.const.2,<Ibl PSx 072 188 073 188 074 188 075 188 Fig. 3-326
Setting for the thermal time constants of the protected object without current
flow (Ibl: base line current).
Note: This setting option is only relevant when machines are running.
In all other cases, time constant 2 must be set equal to time
constant 1.
THERM: Max.object temp. PSx 072 182 073 182 074 182 075 182 Fig. 3-326
Selecting if and how the coolant temperature is measured: Via the PT100 or
the 20mA input.
THERM: Coolant temp. PSx 072 186 073 186 074 186 075 186 Fig. 3-326
Setting for the coolant temperature to be used for calculation of the trip time
if coolant temperature is not measured.
THERM: Bl. f. CTA fault PSx 072 178 073 178 074 178 075 178 Fig. 3-325
This setting specifies whether the thermal overload protection function will
be blocked in the event of faulty coolant temperature acquisition.
THERM: Θ warning PSx 072 184 073 184 074 184 075 184 Fig. 3-326
THERM: Θ trip PSx 072 181 073 181 074 181 075 181 Fig. 3-326
A warning will be given in advance of the trip. The time difference between
the warning time and the trip time is set here.
Time-Voltage Protection V<>: Enabled PSx 076 000 077 000 078 000 079 000 Fig. 3-328
V<>: tV> PSx 076 005 077 005 078 005 079 005 Fig. 3-330
Setting for the operate delay of overvoltage stage V> when all three trigger
stages are activated.
V<>: tV>> PSx 076 006 077 006 078 006 079 006 Fig. 3-330
Setting for the operate delay of undervoltage stage V< when all three trigger
stages are activated.
V<>: tV<< PSx 076 010 077 010 078 010 079 010 Fig. 3-331
V<>: VNG> PSx 076 011 077 011 078 011 079 011 Fig. 3-336
Setting for the time limit of the signals generated by the undervoltage
stages.
V<>: Hyst. V<> meas. PSx 076 048 077 048 078 048 079 048 Fig. 3-330
Setting for the hysteresis of the trigger stages for monitoring measured
voltages.
V<>: Hyst. V<> deduc. PSx 076 049 077 049 078 049 079 049 Fig. 3-333,
3-337
Setting for the hysteresis of the trigger stages for monitoring derived
voltages such as Vneg and VNG.
Over-/Underfrequency f<>: Enabled PSx 018 196 018 197 018 198 018 199 Fig. 3-338
Protection This setting defines the parameter subset in which over-/underfrequency
protection is enabled.
f<>: Oper. mode f1 PSx 018 120 018 121 018 122 018 123 Fig. 3-342
f<>: Oper. mode f2 PSx 018 144 018 145 018 146 018 147
f<>: Oper. mode f3 PSx 018 168 018 169 018 170 018 171
f<>: Oper. mode f4 PSx 018 192 018 193 018 194 018 195
f<>: f3 PSx 018 148 018 149 018 150 018 151
f<>: f4 PSx 018 172 018 173 018 174 018 175
f<>: tf3 PSx 018 152 018 153 018 154 018 155
f<>: tf4 PSx 018 176 018 177 018 178 018 179
f<>: df3/dt PSx 018 156 018 157 018 158 018 159
f<>: df4/dt PSx 018 180 018 181 018 182 018 183
f<>: Delta f3 PSx 018 160 018 161 018 162 018 163
f<>: Delta f4 PSx 018 184 018 185 018 186 018 187
f<>: Delta t3 PSx 018 164 018 165 018 166 018 167
f<>: Delta t4 PSx 018 188 018 189 018 190 018 191
Power Directional Protection P<>: Enabled PSx 014 252 014 253 014 254 014 255 Fig. 3-343
This setting for the measuring direction determines whether a P> trip signal
will be issued for forward, backward (reverse) or non-directional fault
decisions.
P<>: Diseng. ratio P> PSx 017 124 017 125 017 126 017 127 Fig. 3-345
Setting for the disengaging ratio of operate value P> of active power.
P<>: P>> high range PSx 017 214 017 215 017 216 017 217 Fig. 3-345
This setting for the measuring direction determines whether a P>> trip
signal will be issued for forward, backward (reverse) or non-directional fault
decisions.
P<>: Diseng. ratio P>>PSx 017 144 017 145 017 146 017 147 Fig. 3-345
Setting for the disengaging ratio of operate value P>> of active power.
P<>: Q> high range PSx 017 218 017 219 017 220 017 221 Fig. 3-347
P<>: Q> sens. range PSx 017 160 017 161 017 162 017 163
This setting for the measuring direction determines whether a Q> trip signal
will be issued for forward, backward (reverse) or non-directional fault
decisions.
P<>: Diseng. ratio Q> PSx 017 164 017 165 017 166 017 167 Fig. 3-347
Setting for the disengaging ratio of operate value Q> of reactive power.
P<>: Q>> high range PSx 017 222 017 223 017 224 017 225 Fig. 3-347
This setting for the measuring direction determines whether a Q>> trip
signal will be issued for forward, backward (reverse) or non-directional fault
decisions.
P<>: Diseng. ratio Q>>PSx 017 184 017 185 017 186 017 187 Fig. 3-347
Setting for the disengaging ratio of operate value Q>> of reactive power.
P<>: P< high range PSx 017 013 017 014 017 016 017 020 Fig. 3-349
P<>: Direction P< PSx 017 230 017 231 017 232 017 233 Fig. 3-350
This setting for the measuring direction determines whether a P< trip signal
will be issued for 'forward', 'backward' (reverse) or 'non-directional' fault
decisions.
P<>: Diseng. ratio P< PSx 017 034 017 035 017 036 017 037 Fig. 3-349
Setting for the disengaging ratio of operate value P< of active power.
P<>: P<< high range PSx 017 068 017 021 017 025 017 026 Fig. 3-349
This setting for the measuring direction determines whether a P< trip signal
will be issued for 'forward', 'backward' (reverse) or 'non-directional' fault
decisions.
P<>: Diseng.ratio P<< PSx 017 238 017 239 017 240 017 241 Fig. 3-349
Setting for the disengaging ratio of operate value P<< of active power.
P<>: Q< high range PSx 017 069 017 038 017 039 017 045 Fig. 3-352
This setting for the measuring direction determines whether a Q< trip signal
will be issued for 'forward', 'backward' (reverse) or 'non-directional' fault
decisions.
P<>: Diseng. ratio Q< PSx 018 044 018 045 018 046 018 047 Fig. 3-352
Setting for the disengaging ratio of operate value Q< of reactive power.
P<>: Q<< sens. range PSx 018 085 018 086 018 087 018 088
Setting for the disengaging ratio of operate value Q<< of reactive power.
P<>: tTransient pulse PSx 018 246 018 247 018 248 018 249 Fig: 3-349,
3-352, 3-354
Setting for the time limit of the signals generated by stages P<, P<<, Q<
and Q<< after the respective operate delays have elapsed.
7.1.3.4 Control
Enabling the bay interlocking function from the local control panel.
MAIN: SI active USER 221 002 Fig. 3-82
Enabling the station interlocking function from the local control panel.
Note: This parameter is visible only when
C O M M 1 : B a s i c I E C 8 7 0 - 5 e n a b l is set to 'Yes'.
MAIN: Inp.asg. fct.block.1 221 014 Fig. 3-60
MAIN: Inp.asg. fct.block.2 221 022 Fig. 3-60,
3-388
Definition of the binary signals assigned to function block 1 and 2.
MAIN: Op. delay fct. block 221 029 Fig. 3-60
Setting for the maximum number of CB operations for an ARC cycle (or for
a limited time period).
MAIN: CB1 ready fct.assign 221 085
Selecting the event which, when present, will initialize the counter at
M A I N : C B 1 a c t . o p e r . c a p . with the value at
MAIN: CB1 max. oper. cap.
Assigning the external device to one of eight groups for debouncing and
chatter suppression.
DEV01: Interm. pos. suppr. 210 012 Fig. 3-384,
3-390
DEV02: Interm. pos. suppr. 210 062
This setting determines whether the actual status will be signaled with a 5 s
delay after the 'Faulty position' signal is issued.
DEV01: Oper. mode cmd. 210 024 Fig. 3-389
DEV02: Oper. mode cmd. 210 074
Select the operating mode of the command from long command, short
command or time control.
DEV01: Inp.asg. sw.tr. plug 210 014 Fig. 3-384,
3-390
DEV02: Inp.asg. sw.tr. plug 210 064
This setting specifies whether the circuit breaker will be opened by “general
trip command 1” of the protection function.
Note: This setting is only visible (active) for external devices that are
defined as ‘circuit breakers’. This definition is included in the bay type
definitions.
DEV01: With gen. trip cmd.2 210 022
This setting specifies whether the circuit breaker will be opened by “general
trip command 2” of the protection function.
Note: This setting is only visible (active) for external devices that are
defined as ‘circuit breakers’. This definition is included in the bay type
definitions.
DEV01: With close cmd./prot 210 023
This setting specifies whether the circuit breaker will be closed by the "close
command" of the protection function.
Note: This setting is only visible (active) for external devices that are
defined as ‘circuit breakers’. This definition is included in the bay type
definitions.
DEV01: Inp.asg.el.ctrl.open 210 019 Fig. 3-385
This setting defines the binary signal that will be used as the control signal
to move the switchgear unit to the open position.
Note: Only signals that are defined in the DEVxx function groups can
be selected.
This setting defines the binary signal that will be used as the control signal
to move the switchgear unit to the 'Closed' position.
Note: Only signals that are defined in the DEVxx function groups can
be selected.
DEV01: Inp. asg. end Open 210 015
This setting defines the binary signal that will be used to terminate the
'Open' command.
DEV01: Inp. asg. end Close 210 016
This setting defines the binary signal that will be used to terminate the
'Close' command.
DEV01: Open w/o stat.interl 210 025
This setting defines which output will issue the 'Open' enable to the
interlocking logic when there is 'bay interlock with substation interlock'.
Note:
The interlock conditions for bay interlock with station interlock are included
in the bay type definitions (see List of Bay Types in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
This setting defines which output will issue the 'Close' enable to the
interlocking logic when there is 'bay interlock with substation interlock'.
Note:
The interlock conditions for bay interlock with station interlock are included
in the bay type definitions (see List of Bay Types in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
DEV01: Fct.asg.BI w/o SI op 210 041 Fig. 3-386
This setting defines which output will issue the 'Open' enable to the
interlocking logic when there is 'bay interlock without substation interlock'.
Note:
The interlock conditions for bay interlock without station interlock are
included in the bay type definitions (see List of Bay Types in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
DEV01: Fct.asg.BI w/o SI cl 210 042 Fig. 3-386
This setting defines which output will issue the 'Close' enable to the
interlocking logic when there is 'bay interlock without substation interlock'.
Note:
The interlock conditions for bay interlock without station interlock are
included in the bay type definitions (see List of Bay Types in the Appendix).
If the interlock condition is to be modified, this is possible by modifying the
corresponding Boolean equation in the interlocking logic or by defining a
new interlocking logic equation. Only in the latter case is it necessary to
change the function assignment.
The P43x generates a large number of signals, processes binary input signals, and
acquires measured data during fault-free operation of the protected object as well as
fault-related data. A number of counters are available for statistical purposes.
This information can be read out from the integrated local control panel.
All this information can be found in the ‘Operation’ and ‘Events’ folders in the menu tree.
Note:
8.1 Operation
While the hold time is running, the loop back test results can be checked by
reading out these values.
Measured Data Input MEASI: Current IDC 004 134 Fig. 3-27
Measured Data Output MEASO: Current A-1 005 100 Fig. 3-38
MEASO: Current A-2 005 099
Date display.
Note: The date can also be set here.
MAIN: Time of day 003 091 Fig. 3-85
Display of the updated value for the residual current as a primary quantity.
MAIN: Volt. VPG,max prim. 008 042 Fig. 3-50
Display of the updated value for phase-to-phase voltage A-B referred to Vnom.
MAIN: Voltage B-C p.u. 006 045 Fig. 3-50
Display of the updated value for phase-to-phase voltage B-C referred to Vnom.
MAIN: Voltage C-A p.u. 007 045 Fig. 3-50
Display of the updated value for phase-to-phase voltage C-A referred to Vnom.
MAIN: Active power P p.u. 004 051 Fig. 3-53
Ground Fault Direction GFDSS: Current IN,act p.u. 004 045 Fig. 3-304
Display of the updated value for the reactive component of residual current
referred to IN,nom.
GFDSS: Curr. IN filt. p.u. 004 047 Fig. 3-305
Display of the updated value for the harmonic content of residual current
referred to IN,nom. This display is only active when the steady-state current
evaluation mode of the ground fault direction determination function
(GFDSS) is enabled.
GFDSS: Admitt. Y(N) p.u. 004 191 Fig. 3-310
Thermal Overload Protection THERM: Status THERM replica 004 016 Fig. 3-326,
3-95
Display of the buffer content of the thermal overload protection function.
THERM: Object temperature 004 137 Fig. 3-326,
3-95
Display of the temperature of the protected object.
THERM: Coolant temperature 004 149 Fig. 3-326,
3-95
Display of the coolant temperature depending on the setting at
TH ER M : Se lec t C T A.
When set to 'Default temp. value' the set temperature value will be
displayed. When set to 'From PT 100' the temperature measured by the
resistance thermometer will be displayed. When set to 'From 20 mA input'
the temperature measured via an external transducer will be displayed.
THERM: Pre-trip time left 004 139 Fig. 3-326,
3-95
Display of the time remaining before the thermal overload protection
function will reach the tripping threshold.
If, on the other hand, the coolant temperature and the maximum permissible
coolant temperature have been set to the same value, then the coolant
temperature is not taken into account and the characteristic is a function of
the current only. The additional reserve amounts to 0 in this case.
Status Events
GSSE: Output 2 state 104 103
Substation Event
GOOSE: Output 2 state 106 012
Communication interface 1 COMM1: Command block. EXT 003 173 Fig. 3-8
COMM1: Sig./meas. block EXT 037 074 Fig. 3-9,
3-10, 3-11
COMM1: Command blocking 003 174 Fig. 3-8
COMM1: Buffer overrun 221 100
Display when an Ethernet module has not initiated properly, i.e. if the MAC
address is missing or there is a non-plausible parameter setting!
IEC: Control reservation 221 082
Substation Event
GOOSE: Ext.Dev02 position 109 005
Binary open state of the virtual two-pole GOOSE input, representing the
state of an external device.
GOOSE: Ext.Dev01 closed 109 002
Binary closed state of the virtual two-pole GOOSE input, representing the
state of an external device.
Measured Data Input MEASI: Reset Tmax EXT 006 076 Fig.*: 3-87
MEASI: Enabled 035 008 Fig. 3-24
MEASI: PT100 open circuit 040 190 Fig. 3-29
MEASI: Overload 20mA input 040 191 Fig. 3-27
MEASI: Open circ. 20mA inp. 040 192 Fig. 3-27
Binary outputs OUTP: Block outp.rel. EXT 040 014 Fig. 3-30
OUTP: Reset latch. EXT 040 015 Fig. 3-30
OUTP: Outp. relays blocked 021 015 Fig. 3-30
OUTP: Latching reset 040 088 Fig. 3-30
Signal that the protection unit is operational. By default this signal is linked
to L E D : F c t . a s s i g . H 1 g r e e n .
MAIN: Enable protect. EXT 003 027 Fig. 3-58
MAIN: Group reset 1 EXT 005 209 Fig. 3-87
MAIN: Reset c. cl/tr.c EXT 005 210 Fig.*: 3-87
MAIN: Reset IP,max,st. EXT 005 211 Fig.*: 3-87
MAIN: Reset meas.v.en. EXT 005 212 Fig.*: 3-87
MAIN: Group reset 2 EXT 005 252 Fig. 3-87
MAIN: General reset EXT 005 255 Fig.*: 3-87
MAIN: Disable protect. EXT 003 026 Fig. 3-58
MAIN: CB1 faulty EXT 221 086
Parameter subset selection PSS: Control via user EXT 036 101 Fig. 3-90
PSS: Activate PS 1 EXT 065 002 Fig. 3-90
PSS: Activate PS 2 EXT 065 003 Fig. 3-90
PSS: Activate PS 3 EXT 065 004 Fig. 3-90
PSS: Activate PS 4 EXT 065 005 Fig. 3-90
PSS: Control via user 036 102 Fig. 3-90
PSS: Ext.sel.param.subset 003 061 Fig. 3-90
PSS: PS 1 activated ext. 036 094 Fig. 3-90
PSS: PS 2 activated ext. 036 095 Fig. 3-90
PSS: PS 3 activated ext. 036 096 Fig. 3-90
PSS: PS 4 activated ext. 036 097 Fig. 3-90
PSS: Actual param. subset 003 062 Fig. 3-90
PSS: PS 1 active 036 090 Fig. 3-90
PSS: PS 2 active 036 091 Fig. 3-90
PSS: PS 3 active 036 092 Fig. 3-90
PSS: PS 4 active 036 093 Fig. 3-90
Operating data recording OP_RC: Reset record. EXT 005 213 Fig. 3-87
Monitoring Signal Recording MT_RC: Reset record. EXT 005 240 Fig. 3-93,
3-321
Overload Recording OL_RC: Reset record. EXT 005 241 Fig. 3-94,
3-95, 3-96,
3-97
OL_RC: Record. in progress 035 003 Fig. 3-96
OL_RC: Overl. mem. overflow 035 007 Fig. 3-97
Ground fault recording GF_RC: Reset record. EXT 005 242 3-98, 3-103,
3-104
GF_RC: Record. in progress 035 005 Fig. 3-103
GF_RC: GF memory overflow 035 006 Fig. 3-104
Fault data acquisition FT_DA: Trigger EXT 036 088 Fig. 3-106
Fault Recording FT_RC: Reset record. EXT 005 243 Fig. 3-110,
3-111, 3-112
FT_RC: Trigger EXT 036 089 Fig. 3-110
FT_RC: Trigger 037 076 Fig. 3-110
FT_RC: Record. in progress 035 000 Fig. 3-110
FT_RC: System disturb. runn 035 004 Fig. 3-110
FT_RC: Fault mem. overflow 035 001 Fig. 3-111
FT_RC: Faulty time tag 035 002
Distance Protection DIST: Zone extension EXT 036 046 Fig. 3-134,
3-138
DIST: Blocking Z1 EXT 036 034
Power swing blocking PSB: Blocking init. EXT 036 069 Fig. 3-161
PSB: Enabled 040 095 Fig. 3-158
PSB: Enable delay runn. 036 058 Fig. 3-158,
3-161
PSB: Blocking initiated 036 032 Fig. 3-158,
3-161
PSB: Z within polygon 036 024 Fig. 3-159
PSB: IP> triggered 036 012 Fig. 3-161
PSB: Ineg> triggered 036 011 Fig. 3-161
PSB: IN> triggered 036 010 Fig. 3-161
PSB: Perm. no. PS reach 006 030
Switch on to Fault Protection SOTF: Par. ARC running EXT 039 063 Fig. 3-171
SOTF: Enabled 040 069 Fig. 3-171
SOTF: Z1 extended 035 076 Fig. 3-171
SOTF: tManual-close runn. 036 063 Fig. 3-171
SOTF: Trip signal 036 064 Fig. 3-171
Auto-Reclosing Control ARC: Reset counters EXT 005 244 Fig.*: 3-87
Automatic Synchronism ASC: Reset counters EXT 006 074 Fig. 3-251
Check
ASC: Enable EXT 037 049 Fig. 3-239
ASC: Disable EXT 037 061 Fig. 3-239
ASC: AR close request EXT 000 106
Ground fault (short-circuit) GFSC: Enable EXT 039 095 Fig. 3-252
protection
(This address / function group
is available only with the
P435.)
GFSC: Disable EXT 039 096 Fig. 3-252
GFSC: Blocking EXT 043 068 Fig. 3-252
GFSC: Ext. enabled 039 097 Fig. 3-252
GFSC: Enabled 038 094 Fig. 3-252
GFSC: Ready 039 093 Fig. 3-252
GFSC: Not ready 039 094 Fig. 3-252
GFSC: Monitor. triggered 038 095 Fig. 3-264
GFSC: IN> triggered 039 088 Fig. 3-253
GFSC: VNG> triggered 039 089 Fig. 3-253
GFSC: Starting 038 096 Fig. 3-253
GFSC: Direct.determ.enabl. 043 061 Fig. 3-253
GFSC: Fault forward / LS 039 090 Fig. 3-262
GFSC: Fault backward / BS 039 091 Fig. 3-262
GFSC: t1 elapsed 038 097 Fig. 3-262
GFSC: t2 elapsed 038 098 Fig. 3-262
GFSC: t3 elapsed 038 099 Fig. 3-262
GFSC: Trip signal 039 092 Fig. 3-262
Ground fault (short-circuit) GSCSG: Enable EXT 043 050 Fig. 3-265
protection signaling GSCSG: Disable EXT 043 051 Fig. 3-265
(This address / function group GSCSG: Test telecom. EXT 043 056 Fig. 3-275
is available only with the GSCSG: Telecom. faulty EXT 043 053 Fig. 3-266
P435.) GSCSG: Blocking EXT 043 052 Fig. 3-266
GSCSG: Receive EXT 043 055 Fig. 3-268,
3-270, 3-271,
3-272, 3-274
GSCSG: Frequ.mon.trigd. EXT 043 054 Fig. 3-268
GSCSG: Ext. enabled 043 066 Fig. 3-265
GSCSG: Enabled 023 070 Fig. 3-265
GSCSG: Ready 043 057 Fig. 3-266
GSCSG: Not ready 043 058 Fig. 3-266
GSCSG: Test telecom. 034 029 Fig. 3-275
GSCSG: Send signal 043 059 Fig. 3-270,
3-271, 3-274,
3-275
GSCSG: Tripping time elaps. 043 063 Fig. 3-267
GSCSG: Telecom. faulty 046 060
Definite-time overcurrent DTOC: Blocking tI> EXT 041 060 Fig. 3-277
protection DTOC: Blocking tI>> EXT 041 061 Fig. 3-277
DTOC: Blocking tI>>> EXT 041 062 Fig. 3-277
DTOC: Blocking tI>>>> EXT 041 100 Fig. 3-277
DTOC: Blocking tIneg> EXT 041 102 Fig. 3-278
DTOC: Blocking tIneg>> EXT 041 103 Fig. 3-278
DTOC: Block. tIneg>>> EXT 041 104 Fig. 3-278
DTOC: Block. tIneg>>>> EXT 041 105 Fig. 3-278
DTOC: Blocking tIN> EXT 041 063 Fig. 3-280
DTOC: Blocking tIN>> EXT 041 064 Fig. 3-280
DTOC: Blocking tIN>>> EXT 041 065 Fig. 3-280
DTOC: Blocking tIN>>>> EXT 041 101 Fig. 3-280
DTOC: Enabled 040 120 Fig. 3-276
DTOC: Starting I> 035 020 Fig. 3-277
DTOC: Starting I>> 035 021 Fig. 3-277
DTOC: Starting I>>> 035 022 Fig. 3-277
DTOC: Starting I>>>> 035 023 Fig. 3-277
DTOC: tI> elapsed 040 010 Fig. 3-277
DTOC: tI>> elapsed 040 011 Fig. 3-277
DTOC: tI>>> elapsed 040 012 Fig. 3-277
DTOC: tI>>>> elapsed 035 032 Fig. 3-277
DTOC: Starting Ineg> 035 024 Fig. 3-278
DTOC: Starting Ineg>> 035 025 Fig. 3-278
DTOC: Starting Ineg>>> 035 026 Fig. 3-278
DTOC: Starting Ineg>>>> 035 027 Fig. 3-278
DTOC: tIneg> elapsed 035 033 Fig. 3-278
DTOC: tIneg>> elapsed 035 034 Fig. 3-278
DTOC: tIneg>>> elapsed 035 035 Fig. 3-278
DTOC: tIneg>>>> elapsed 035 036 Fig. 3-278
DTOC: Starting IN> 035 028 Fig. 3-280
DTOC: Starting IN>> 035 029 Fig. 3-280
DTOC: Starting IN>>> 035 030 Fig. 3-280
DTOC: Starting IN>>>> 035 031 Fig. 3-280
DTOC: Fault N forward 035 047 Fig. 3-282
DTOC: Fault N backward 035 048 Fig. 3-282
DTOC: H.-time tIN>,i. runn 040 086 Fig. 3-284
DTOC: tIN>,interm. elapsed 040 099 Fig. 3-284
DTOC: tIN> elapsed 035 037 Fig. 3-280
DTOC: tIN>> elapsed 035 038 Fig. 3-280
DTOC: tIN>>> elapsed 035 039 Fig. 3-280
DTOC: tIN>>>> elapsed 035 040 Fig. 3-280
DTOC: Trip sig. tIN>,intm. 039 073 Fig. 3-284
DTOC: Trip signal tIN> 035 043 Fig. 3-283
DTOC: Trip signal tIN>> 035 044 Fig. 3-283
DTOC: Trip signal tIN>>> 035 045 Fig. 3-283
DTOC: Trip sign. tIN>>>> 035 046 Fig. 3-283
Inverse-Time Overcurrent IDMT: Block. tIref,P> EXT 040 101 Fig. 3-294
Protection
IDMT: Block. tIref,neg>EXT 040 102 Fig. 3-294
IDMT: Block. tIref,N> EXT 040 103 Fig. 3-294
IDMT: Enabled 040 100 Fig. 3-287
IDMT: Starting Iref,P> 040 080 Fig. 3-294
IDMT: Trip signal tIref,P> 040 084 Fig. 3-294
IDMT: Starting Iref,neg> 040 107 Fig. 3-294
IDMT: Trip sig. tIref,neg> 040 108 Fig. 3-294
IDMT: Starting Iref,N> 040 081 Fig. 3-294
IDMT: Trip signal tIref,N> 040 085 Fig. 3-294
IDMT: Neg.seq.syst. forw. 035 041 Fig. 3-297
IDMT: Neg.seq.syst. backw. 035 042 Fig. 3-297
Ground fault direction GFDSS: Reset counters EXT 005 245 Fig. 3-306,
determination using 3-312
steady-state values GFDSS: GF (curr.) eval. EXT 038 020 Fig. 3-299
GFDSS: Enabled 042 096 Fig. 3-299
GFDSS: GF (pow.) ready 038 026 Fig. 3-299
GFDSS: GF (pow.) not ready 038 027 Fig. 3-299
GFDSS: GF (curr.) evaluat. 039 071 Fig. 3-299
GFDSS: GF (curr.) ready 038 028 Fig. 3-299
GFDSS: GF (curr.) not ready 038 029 Fig. 3-299
GFDSS: Admittance ready 038 167 Fig. 3-299
GFDSS: Admittance not ready 038 168 Fig. 3-299
GFDSS: Grd. fault pow./adm. 009 037 Fig. 3-301
GFDSS: Forward / LS 009 035 Fig. 3-304,
3-307, 3-310
GFDSS: Direct. backward/BS 009 036 Fig. 3-304,
3-310
GFDSS: Starting forward/LS 009 040 Fig. 3-304,
3-310
GFDSS: Starting backward/BS 009 041 Fig. 3-310
GFDSS: Trip signal forw./LS 009 031 Fig. 3-304,
3-310
GFDSS: Ground fault (curr.) 009 038 Fig. 3-305
GFDSS: Starting Y(N)> 009 074 Fig. 3-311
GFDSS: Trip Y(N)> 009 075 Fig. 3-311
GFDSS: Trip signal Y(N)> 009 072 Fig. 3-311
Ground Fault Tripping GFTRP: Blocking EXT 037 046 Fig. 3-313,
3-314
GFTRP: VNG> triggered EXT 037 047 Fig. 3-314
GFTRP: Enabled 040 092 Fig. 3-313,
3-314
GFTRP: Trip signal 037 091 Fig. 3-313,
3-314
Ground fault protective GFSIG: Test telecom. EXT 037 045 Fig. 3-315
signaling GFSIG: Receive EXT 037 044 Fig. 3-315
GFSIG: Enabled 040 091 Fig. 3-315
GFSIG: Test telecom. 034 025 Fig. 3-315
GFSIG: Telecom. faulty 038 017 Fig. 3-315
GFSIG: Send (signal) 037 088 Fig. 3-315
GFSIG: Send (transm.relay) 037 089 Fig. 3-315
GFSIG: Trip signal 037 087 Fig. 3-315
Transient Ground Fault TGFD: Blocking EXT 004 034 Fig. 3-316
Direction Determination TGFD: Reset counters EXT 005 246 Fig.*: 3-87
TGFD: Reset signal EXT 004 140 Fig. 3-320
TGFD: Enabled 037 100 Fig. 3-316
TGFD: Ready 037 080 Fig. 3-316
TGFD: Not ready 037 081 Fig. 3-316
TGFD: Ground fault 004 033 Fig. 3-318
TGFD: Direct. determined 004 030 Fig. 3-319
TGFD: Forward / LS 004 031 Fig. 3-319
TGFD: Direct. backward/BS 004 032 Fig. 3-319
TGFD: Signal reset 004 141 Fig. 3-320
Thermal Overload Protection THERM: Therm.repl.block EXT 041 074 Fig. 3-326
THERM: Reset replica EXT 038 061 Fig. 3-327
THERM: Enabled 040 068 Fig. 3-323
THERM: Reset replica 039 061 Fig. 3-327
THERM: Starting k*Iref> 041 108 Fig. 3-326
THERM: CTA error EXT 038 062 Fig. 3-325
THERM: Warning 039 025 Fig. 3-326
THERM: Trip signal 039 020 Fig. 3-326
THERM: Buffer empty 039 112 Fig. 3-326
THERM: CTA error 039 111 Fig. 3-325
THERM: Within pre-trip time 041 109 Fig. 3-326
THERM: Setting error,block. 039 110 Fig. 3-326
Time-Voltage Protection V<>: Blocking tV> EXT 041 068 Fig. 3-330
V<>: Blocking tV>> EXT 041 069 Fig. 3-330
V<>: Blocking tV< EXT 041 070 Fig. 3-331
V<>: Blocking tV<< EXT 041 071 Fig. 3-331
V<>: Blocking tVpos> EXT 041 090 Fig. 3-333
V<>: Blocking tVpos>> EXT 041 091 Fig. 3-333
V<>: Blocking tVpos< EXT 041 092 Fig. 3-333
V<>: Blocking tVpos<< EXT 041 093 Fig. 3-333
V<>: Blocking tVneg> EXT 041 094 Fig. 3-334
V<>: Blocking tVneg>> EXT 041 095 Fig. 3-334
V<>: Blocking tVNG> EXT 041 072 Fig. 3-336
V<>: Blocking tVNG>> EXT 041 073 Fig. 3-336
V<>: Blocking tVref> EXT 007 036 Fig. 3-337
V<>: Blocking tVref>> EXT 007 037 Fig. 3-337
V<>: Blocking tVref< EXT 007 039 Fig. 3-337
V<>: Blocking tVref<< EXT 007 046 Fig. 3-337
V<>: Enabled 040 066 Fig. 3-328
V<>: Ready 042 003 Fig. 3-328
V<>: Not ready 042 004 Fig. 3-328
V<>: Starting V>/>> A(-B) 041 031 Fig. 3-330
V<>: Starting V>/>> B(-C) 041 032 Fig. 3-330
V<>: Starting V>/>> C(-A) 041 033 Fig. 3-330
V<>: Starting V> 041 030 Fig. 3-330
V<>: Starting V> 3-pole 041 097 Fig. 3-330
V<>: Starting V>> 041 096 Fig. 3-330
V<>: tV> elapsed 041 034 Fig. 3-330
V<>: tV> 3-pole elapsed 041 098 Fig. 3-330
Power Directional Protection P<>: Blocking P> EXT 035 082 Fig. 3-345
P<>: Blocking P>> EXT 035 083 Fig. 3-345
P<>: Blocking Q> EXT 035 084 Fig. 3-347
P<>: Blocking Q>> EXT 035 085 Fig. 3-347
P<>: Blocking tP< EXT 035 050 Fig. 3-349
P<>: Blocking tP<< EXT 035 051 Fig. 3-349
P<>: Blocking tQ< EXT 035 052 Fig. 3-352
P<>: Blocking tQ<< EXT 035 053 Fig. 3-352
P<>: Enabled 036 250 Fig. 3-343
P<>: Starting P> 035 086 Fig. 3-345
P<>: Starting P>> 035 089 Fig. 3-345
P<>: Signal P> delayed 035 087 Fig. 3-345
P<>: Signal P>> delayed 035 090 Fig. 3-345
P<>: Trip signal P> 035 088 Fig. 3-346
P<>: Trip signal P>> 035 091 Fig. 3-346
P<>: Starting Q> 035 092 Fig. 3-347
P<>: Starting Q>> 035 095 Fig. 3-347
P<>: Signal Q> delayed 035 093 Fig. 3-347
P<>: Signal Q>> delayed 035 096 Fig. 3-347
P<>: Trip signal Q> 035 094 Fig. 3-348
P<>: Trip signal Q>> 035 097 Fig. 3-348
P<>: Starting P< 035 054 Fig. 3-349
External devices 01 to 03 DEV01: Open signal EXT 210 030 Fig. 3-40,
3-384, 3-390
DEV02: Open signal EXT 210 080
Single-Pole Signals SIG_1: Signal S001 EXT 226 004 Fig. 3-395
SIG_1: Logic signal S001 226 005 Fig. 3-395
SIG_1: Signal S002 EXT 226 012
Setting the enable for changing values from the local control panel.
Status Events
Command to reset monitoring counters as listed below.
GSSE: Enroll. IEDs flags L 105 160
Bar with state bits for all GSSE inputs, showing if the respective GSSE
sending device has logged-on and is transmitting free of fault (input 1 to 16).
GSSE: Enroll. IEDs flags H 105 161
Bar with state bits for all GSSE inputs, showing if the respective GSSE
sending device has logged-on and is transmitting free of fault (input 17 to
32).
GSSE: Tx message counter 105 162
State of the continuous counter sequence for the message counter sent
with each GSSE.
GSSE: Tx last message 105 166
State of the continuous counter sequence for state changes sent with each
GSSE.
GSSE: No. reject. messages 105 167
Setting for which GSSE sending device the following statistics information is
to be displayed.
GSSE: IED receiv. messages 105 172
State of the continuous counter sequence for the message counter received
with each GSSE.
GSSE: IED Rx last message 105 174
State of the continuous counter sequence for state changes received with
each GSSE.
GSSE: IED missed messages 105 175
Number of GSSE received after the validity time period has elapsed. This
counter is reset by G S S E : R e s e t c o u n t e r s .
Binary outputs OUTP: Reset latch. USER 021 009 Fig. 3-30
The output relay selected for testing is triggered for the duration of the set
time ( O U T P : H o l d - t i m e f o r t e s t ).
Setting the time period for which the selected output relay is triggered
during functional testing.
Measured Data Output MEASO: Reset output USER 037 116 Fig. 3-34
Main function MAIN: General reset USER 003 002 Fig. 3-86
The display of active and reactive energy output and input is reset.
MAIN: Reset c. cl/tr.cUSER 003 007 Fig. 3-65,
3-79, 3-80
The counters for counting close and trip commands are reset.
MAIN: Group reset 1 USER 005 253 Fig. 3-87
MAIN: Group reset 2 USER 005 254 Fig. 3-87
A 100 ms trip command is issued from the local control panel. This setting
is password-protected (see section entitled 'Password-Protected Control
Operations' in Chapter 6).
Note:
The command is only executed if the manual trip command has been
configured as trip command 1 or 2.
MAIN: En.man.clos.cmd.USER 003 105 Fig. 3-65
Setting for the release of a close command from the local control panel.
MAIN: Man. close cmd. USER 018 033 Fig. 3-65
A close command is issued from the local control panel for the set reclose
command time. This setting is password-protected (see section entitled
'Password-Protected Control Operations' in Chapter 6).
MAIN: Warm restart 003 039
A warm restart is carried out. The device functions as it does when the
power supply is turned on.
MAIN: Cold restart 000 085
Operating data recording OP_RC: Reset record. USER 100 001 Fig. 3-92
The operating data memory and the counter for operation signals are reset.
Monitoring Signal Recording MT_RC: Reset record. USER 003 008 Fig. 3-93
Overload Recording OL_RC: Reset record. USER 100 003 Fig. 3-97
Ground fault recording GF_RC: Reset record. USER 100 000 Fig. 3-104
Fault recording is enabled from the local control panel for 500 ms.
FT_RC: Reset record. USER 003 006 Fig. 3-111
A close request is issued from the integrated local control panel. This will
trigger the ASC functional operation. A close command is transmitted to the
CB if the check of the ASC is positive.
This control action is password-protected (see section entitled 'Password-
Protected Control Operations' in Chapter 6).
ASC: Reset counters USER 003 089 Fig. 3-251
A close request is issued from the integrated local control panel. This will
trigger the ASC functional operation. No close command is transmitted to
the CB if the check of the ASC is positive. Only a signal is issued.
Ground fault (short-circuit) GFSC: Enable USER 003 138 Fig. 3-252
protection Ground fault (short-circuit) protection is enabled from the local control panel.
(This address / function group
is available only with the GFSC: Disable USER 003 137 Fig. 3-252
P435.) Ground fault (short-circuit) protection is disabled from the local control
panel.
Ground fault (short-circuit) GSCSG: Enable USER 003 140 Fig. 3-265
protective signaling Ground fault (short-circuit) protection signaling is enabled from the local
(This address / function group control panel.
is available only with the
P435.) GSCSG: Disable USER 003 139 Fig. 3-265
Ground Fault Direction GFDSS: Reset counters USER 003 004 Fig. 3-306,
Determination Using Steady- 3-312
State Values
The counters for the ground fault direction determination function using
steady-state values are reset.
Ground fault protective GFSIG: Test telecom. USER 016 079 Fig. 3-315
signaling
A send signal is issued for 500 ms.
Transient ground fault TGFD: Reset signal USER 003 009 Fig. 3-320
direction determination
The direction decisions can be reset while the buffer time is elapsing.
TGFD: Reset counters USER 003 022 Fig. 3-322
The counters for the transient ground fault direction determination function
are reset.
Protection Resetting the measured event values f<> : m a x. fre qu . for f> and
f < > : m in . f r e qu . for f< .
Circuit Breaker Failure CBF: Enable USER 003 016 Fig. 3-357
Protection Circuit breaker failure protection is enabled from the local control panel.
CBF: Disable USER 003 015 Fig. 3-357
Circuit breaker failure protection is disabled from the local control panel.
Operating data recording OP_RC: Operat. data record. 003 024 Fig. 3-92
Monitoring Signal Recording MT_RC: Mon. signal record. 003 001 Fig. 3-93
8.2 Events
Main function MAIN: No. general start. 004 000 Fig. 3-70,
3-71
Number of general starting signals.
MAIN: CB1 act. oper. cap. 221 087
Setting for the maximum number of CB operations for an ARC cycle (or for
a limited time period).
MAIN: No. gen.trip cmds. 1 004 006 Fig. 3-79,
3-80
Number of general trip commands 1.
(This address is available MAIN: No. trip cmds. 1, A 005 006 Fig. 3-80
only with the P435.)
(This address is available MAIN: No. trip cmds. 1, B 005 007 Fig. 3-80
only with the P435.)
(This address is available MAIN: No. trip cmds. 1, C 005 008 Fig. 3-80
only with the P435.)
Number of general trip commands 1 per phase.
MAIN: No. gen.trip cmds. 2 009 050 Fig. 3-79,
3-80
Number of general trip commands 2.
MAIN: No. final trip cmds. 004 005 Fig. 3-79,
3-80
Number of final trip commands.
MAIN: No. close commands 009 055 Fig. 3-65
Counter for the number of times the measuring range of the active energy
output was exceeded.
MAIN: No.overfl.act.en.inp 009 091 Fig. 3-56
Counter for the number of times the measuring range of the active energy
input was exceeded.
MAIN: No.ov/fl.reac.en.out 009 092 Fig. 3-56
Counter for the number of times the measuring range of the reactive energy
output was exceeded.
MAIN: No.ov/fl.reac.en.inp 009 093 Fig. 3-56
Counter for the number of times the measuring range of the reactive energy
input was exceeded.
Operating data recording OP_RC: No. oper. data sig. 100 002 Fig. 3-92
Monitoring Signal Recording MT_RC: No. monit. signals 004 019 Fig. 3-93
Ground fault recording GF_RC: No. ground faults 004 100 Fig. 3-103
Number of faults.
FT_RC: No. system disturb. 004 010 Fig. 3-110
Automatic Synchronism ASC: No. RC aft. man.clos 004 009 Fig. 3-251
Check Number of reclosures after a manual close request.
ASC: No. close requests 009 033 Fig. 3-251
Ground fault (short-circuit) GFSC: No. of trip signals 009 054 Fig. 3-263
protection Number of trip signals.
(This address is available
only with the P435.)
Ground Fault Direction GFDSS: No. GF power/admitt. 009 002 Fig. 3-312
Determination Using Steady-
State Values
Number of ground faults detected by steady-state power evaluation.
GFDSS: No. GF (curr. meas) 009 003 Fig. 3-306
Overload data acquisition OL_DA: Overload duration 004 102 Fig. 3-94
Display of the load current used by the thermal overload protection function
to calculate the tripping time.
OL_DA: Object temp. THERM 004 035 Fig. 3-95
If, on the other hand, the coolant temperature and the maximum permissible
coolant temperature have been set to the same value, then the coolant
temperature is not taken into account and the characteristic is a function of
the current only. The additional reserve amounts to 0 in this case.
Ground fault data acquisition GF_DA: GF recording time 009 100 Fig. 3-98
Display of the ground fault duration of the most recent ground fault.
GF_DA: GF duration pow.meas 009 024 Fig. 3-99
Display of the ground fault duration of the most recent ground fault as
determined by the steady-state power evaluation feature of the ground fault
direction determination function.
GF_DA: Voltage VNG p.u. 009 020 Fig. 3-100
Display of the active component of the residual current of the most recent
ground fault referred to IN,nom.
Note: This display is active only when the steady-state power
evaluation mode of the GFDSS ground fault direction
determination function is enabled.
GF_DA: Curr.IN,reac p.u. 009 023 Fig. 3-100
Display of the reactive component of the residual current of the most recent
ground fault referred to IN,nom.
Note: This display is only active when the steady-state power
evaluation mode of the GFDSS ground fault direction
determination function is enabled.
GF_DA: GF durat. curr.meas. 009 026 Fig. 3-101
Display of the ground fault duration of the most recent ground fault as
determined by the steady-state current evaluation feature of the ground fault
direction determination function.
GF_DA: Curr. IN filt. p.u. 009 025 Fig. 3-102
Display of the residual current component having the set filter frequency for
the most recent ground fault (referred to IN,nom).
Fault data acquisition FT_DA: Fault duration 008 010 Fig. 3-105
Display of the fault location of the last fault (in %) referred to the setting at
FT_DA: Line reactance PSx.
FT_DA: Fault location 004 022 Fig. 3-108
Display of the load impedance (in Ω) after the general starting condition of
distance protection has ended. The display only appears if the fault has
been detected by the fault data acquisition function of the P43x.
FT_DA: Load angle post-flt. 004 038 Fig. 3-109
Display of the load angle (in degrees) after the general starting condition of
distance protection has ended.
The display only appears if the fault has been detected by the distance
protection function of the P43x.
FT_DA: Resid.curr. post-flt 004 039 Fig. 3-109
Display of the residual current referred to Inom after the general starting
condition of time-overcurrent protection has ended.
The display only appears if the fault has been detected by the distance
protection function of the P43x.
Ground fault (short-circuit) GFSC: Angle VNG/IN 009 098 Fig. 3-262
Ground fault recording GF_RC: Ground flt.record. 1 033 010 Fig. 3-104
GF_RC: Ground flt.record. 2 033 011 Fig. 3-104
GF_RC: Ground flt.record. 3 033 012 Fig. 3-104
GF_RC: Ground flt.record. 4 033 013 Fig. 3-104
GF_RC: Ground flt.record. 5 033 014 Fig. 3-104
GF_RC: Ground flt.record. 6 033 015 Fig. 3-104
GF_RC: Ground flt.record. 7 033 016 Fig. 3-104
GF_RC: Ground flt.record. 8 033 017 Fig. 3-104
9 Commissioning
Only qualified personnel, familiar with the "Warning" page at the beginning of this
manual, may work on or operate this device.
When installing and connecting the device the warning notices at the beginning of
Chapter 5 must be observed.
The device must be reliably grounded before auxiliary voltage is turned on.
The surface-mounted case is grounded using the bolt and nut, appropriately marked, as
the ground connection. The flush-mounted case must be grounded in the area of the
rear sidepieces at the location provided. The cross-section of the ground conductor must
conform to applicable national standards. A minimum cross section of 2.5 mm2 is
required.
In addition, a protective ground connection at the terminal contact on the power supply
module (identified by the letters "PE" on the terminal connection diagram) is also
required for proper operation of the device. The cross-section of this ground conductor
must also conform to applicable national standards. A minimum cross section of
1.5 mm2 is required.
Before working on the device itself or in the space where the device is connected, always
disconnect the device from the supply.
The secondary circuit of live system current transformers must not be opened! If the
secondary circuit of a live CT is opened, there is the danger that the resulting voltages
will endanger personnel and damage the insulation.
In units for pin terminal connection, the threaded terminal block for current transformer
connection is not a shorting block. Therefore always short-circuit current transformers
before loosening the threaded terminals.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock.
The fiber-optic interface may only be connected or disconnected when the supply voltage
for the device is shut off.
The PC interface is not designed for permanent connection. Consequently, the female
connector does not have the extra insulation from circuits connected to the system that is
required per VDE 0106 Part 101. Therefore, when connecting the prescribed connecting
cable be careful not to touch the socket contacts.
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see chapter entitled 'Technical
Data')
When using the programmable logic (function group LOGIC), the user must carry out a
functional type test to conform to the requirements of the relevant protection/control
application. In particular, it is necessary to verify that the requirements for the
implementation of logic linking (by setting) as well as the time performance during device
startup, during operation and when there is a fault (device blocking) are fulfilled.
Preparation
After the P43x has been installed and connected as described in Chapter 5, the
commissioning procedure can begin.
Before turning on the power supply voltage, the following items must be checked again:
After the wiring work is completed, check the system to make sure it is properly isolated.
The conditions given in VDE 0100 must be satisfied.
Once all checks have been made, the power supply voltage may be turned on. After
voltage has been applied, the device starts up. During startup, various startup tests are
carried out (see Chapter 3, ‘Self-Monitoring’). The LED indicators for ‘Operation’ (H1)
and ‘Blocked/Faulty’ (H2) will light up. After approximately 15 s, the P43x is ready for
operation. This is perceptible when the text "P43x" appears in the first line on the LCD.
Once the change enabling command has been issued (see Chapter 6, ‘Enabling
Parameter Changes’), all settings can be entered. The procedure for entering settings
from the integrated local control panel is described in Chapter 6.
If either the PC interface or the communication interfaces are to be used to set the P43x
and reading out event records, then the following setting parameters must first be
configured:
‘Par/DvID/’ folder:
DVICE: Device password 1
DVICE: Device password 2
‘Par/Conf/’ folder:
PC: Name of manufacturer
PC: Bay address
PC: Device address
PC: Baud rate
PC: Parity bit
COMM1: Function group COMM1
COMM1: General enable USER
COMM1: Name of manufacturer
COMM1: Line idle state
COMM1: Baud rate
COMM1: Parity bit
COMM1: Communicat. protocol
COMM1: Octet comm. address
COMM1: Octet address ASDU
COMM2: Function group COMM2
COMM2: General enable USER
COMM2: Name of manufacturer
COMM2: Line idle state
COMM2: Baud rate
COMM2: Parity bit
COMM2: Octet comm. address
COMM2: Octet address ASDU
COMM3: Function group COMM3
COMM3: General enable USER
COMM3: Baud rate
‘Par/Func/Glob/’ folder:
PC: Command blocking
PC: Sig./meas.val.block.
COMM1: Command blocking
COMM1: S i g . / m e a s . b l o c k . U S E R
COMM2: Command blocking
COMM2: Sig./meas.block.USER
Note: The settings given above apply to the IEC 60870-5-103 communication
protocol. If another protocol is being used for the communication interface,
additional settings may be necessary. See Chapter 7 for further details.
After the settings have been made, the following checks should be carried out again
before the blocking is cancelled:
Does the function assignment of the binary signal inputs agree with the terminal
connection diagram?
Has the correct operating mode been selected for the binary signal inputs?
Does the function assignment of the output relays agree with the terminal connection
diagram?
Has the correct operating mode been selected for the output relays?
Have all settings been made correctly?
M A I N : D e v i c e o n - l i n e 'Yes' (on)'
Tests
By using the signals and displays generated by the P43x, it is possible to determine
whether the P43x is correctly set and properly interconnected with the station. Signals
are signaled by output relays and LED indicators and entered into the event memory. In
addition, the signals can be checked by selecting the appropriate signal in the menu
tree.
If the user does not wish the circuit breaker to operate during testing, the trip commands
can be blocked through M A I N : T r i p c m d . b l o c k . U S E R (‘Par/Func/Glob’
folder) or an appropriately configured binary signal input. If circuit breaker testing is
desired, it is possible to issue a three-pole trip command for a set time duration at
M A I N : M a n . t r i p c m d . U S E R (‘Oper/CtrlTest’ folder) or an appropriately
configured binary signal input. Selection of the trip command from the integrated local
control panel is password-protected (see section entitled ‘Password-Protected Control
Operations’ in Chapter 6).
Note: The manual trip command is only executed if it has been configured for trip
command 1 or trip command 2.
If the P43x is connected at the control station level, the user is advised to activate the
test mode via M A I N : T e s t m o d e U S E R (folder ‘Par/Func/Glob’) or an
appropriately configured binary signal input. The telegrams are then identified
accordingly (reason for transmission: test mode).
This display appears regardless of the binary signal input mode selected.
Note: Testing is possible only if the device has been switched to "off-line"
beforehand at M A I N : D e v i c e o n - l i n e (‘Par/Func/Glob/’ folder).
Before starting the test, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
Checking the
communications interfaces
signals
When using the IEC 60870-5-103, IEC 870-5-101 or ILS-C interface protocols, each
signal generated in the P43x can be transmitted to the connected control station for test
purposes. First select the signal to be tested (C O M M x : S e l . s p o n t a n . s i g . t e s t ,
‘Oper/CtrlTest/’ folder). The respective signal is transmitted according to
C O M M x : T e s t s p o n t . s i g . s t a r t or C O M M x : T e s t s p o n t . s i g . e n d
(‘Oper/CtrlTest/’ folder). This control action is password-protected (see section entitled
'Password-Protected Control Operations' in Chapter 6).
Checking distance
protection
Before checking the distance protection function using a single-phase testing device,
disable the measuring circuit monitoring function (M C M O N : E n a b l e d U S E R ,
‘Par/Func/Main/’ folder) and the fuse failure monitoring function (M C M O N : F F , V
e n a b l e d U S E R , ‘Par/Func/Main/’ folder) since they would otherwise always operate
and block distance protection after the set operate delay had elapsed. Furthermore, the
signal at the binary signal input configured for M A I N : M . c . b . t r i p V E X T must
have a logic value of 0.
Checking starting
The starting settings can be illustrated in a V-I diagram (see Figure 9-1). The slope of
the impedance line plotted in the V-I diagram is a function of the settings for
underimpedance starting and the phase displacement between the measured values
(see Figure 9-2).
Checking Z<:
The phase displacement between the measured values V and I should be selected so as
to be greater than the angle set at D I S T : β P S x .
Note: The measured values should be selected in accordance with the selected
operate values such that only one starting measuring system operates.
Operation of the checked starting threshold is possible by checking the
phase-selective and starting-selective state signals ('Oper/Cycl/Log' folder).
When checking underimpedance starting using single-phase test current, we obtain the
following relation for the operate condition for phase-to-phase starting:
V test
= 2 ⋅ Z<
I test
V test ⋅ e jϕtest
= 2 ⋅ Z < ⋅ e jϕZ
I test ⋅ e j0 °
V test
= 2 ⋅ Z<
I test
ϕtest = ϕ Z
where:
ϕZ : Impedance Angle
In the range of the reactance limit, that is, for impedance angle ϕ Z in the range
φL < φz < 110°, the starting impedance is calculated as follows:
X fw
Z< =
sin ϕ Z
Xfw: D I S T : X f w P S x setting
The limit angle ϕL is defined by the point of intersection of reactance and resistance
limits and is calculated as follows:
X fw
ϕ L = arc tan
Rfw
Rfw : D I S T : R f w , P G P S x or D I S T : R f w , P P P S x setting
If underimpedance starting is to be checked under all angle conditions, then the starting
impedances for the individual angle ranges are calculated according to the following
equations:
β ≤ϕ Z ≤ϕ L Rfw
Z< =
cos ϕ Z
β: D I S T : β P S x setting
Zbw
: D I S T : Z b w / Z f w P S x setting
Zfw
V test
= (1 + k G ) ⋅ Z <
I test
V test ⋅ e jϕ test
I test ⋅ e j 0° ( )
= 1 + k G ⋅ e jϕ G ⋅ Z < ⋅ e jϕ Z
V test
= ⎛⎜1 + k G + 2 ⋅ k G ⋅ cos ϕ G ⎞⎟ ⋅ Z <
2
I test ⎝ ⎠
sinϕ Z + k G ⋅ sin(ϕ Z + ϕ G )
ϕ test = arc tan
cos ϕ Z + k G ⋅ cos (ϕ Z + ϕ G )
or
where:
ϕZ : Impedance Angle
kG : D I S T : A b s . v a l u e k G P S x setting
ϕG : D I S T : A n g l e k G P S x setting
From the input measured values, the P43x calculates the residual current IN and the
neutral-displacement voltage VNG, which are used for zero-sequence starting. They are
calculated according to the following equations:
I N = I A + I B + IC
1
V NG = ⋅ V A −G + V B −G + V C −G
3
For a single-phase test where |VB-G| = |VC-G| = 0, the result of the calculation formula for
VNG given above is that the D I S T : V N G > P S x or D I S T : V N G > > P S x triggers
operate if the test voltage exceeds the following value:
V
V test = 3 ⋅ VNG > ⋅ nom
3
Operation of ground starting is only signaled by the LED indicator if starting also
operates in a phase. The operation of ground starting can be observed, independently
of the operation of phase starting, at D I S T : Z e r o - s e q u . s t a r t i n g
(‘Oper/Cycl/Log/’ folder).
The values determined by the P43x for the residual current IN and the neutral-point
displacement voltage VNG are displayed by the operating data display (current:
M A I N : C u r r e n t I N p . u . and voltage: M A I N : V o l t a g e V N G p . u . in the
‘Oper/Cycl/Meas/’ folder).
V test
= 2 ⋅ Z<
I test
V test ⋅ e jϕ test
= 2 ⋅ Z < ⋅ e jϕ Z
j 0°
I test ⋅ e
V test
= 2 ⋅ Z<
I test
ϕ test = ϕ Z
where:
ϕZ : Impedance Angle
Characteristics
With the P43x, the user may choose between a polygonal and a circular tripping
characteristic. This selection of the tripping characteristic will then govern calculation of
the tripping impedances.
Circle characteristic
If the circle characteristic has been selected, the tripping impedance is set in the P43x.
If the setting Arc compensation: yes has also been selected, then the characteristic
shown in Figure 9-3 is obtained when measuring with sinusoidal quantities.
9-3 Impedance characteristic for distance and directional determination for the ‘Circle’ setting
The actual tripping impedance in the ranges −45 ° < ϕ Z < α and 135 ° < ϕ Z < ( α + 180 ° ) is
then calculated as follows:
Z trip = Z ⋅ (1 + sin δ )
The following relation applies in the range 135 ° < ϕ Z < ( α + 180 ° ) :
δ = α − ϕ Z + 180 °
where:
Z: settings D I S T : Z 1 ( c i r c l e ) P S x to D I S T : Z 4 ( c i r c l e ) P S x
ϕZ : Impedance Angle
α: settings D I S T : α 1 ( c i r c l e ) P S x to D I S T : α 4 ( c i r c l e ) P S x
When phase-to-ground loops are checked, the set complex ground factor kG must be
taken into account if the setting for D I S T : A b s . v a l u e k G P S x is not equal to
one and/or the setting for D I S T : A n g l e k G P S x is not equal to 0°. When the test
is carried out using single-phase test current, the following relation for the operate
condition is obtained:
V test
I test
(
= 1 + kG ⋅ Z< )
V test ⋅ e jϕ test
I test ⋅ e j 0°
( )
= 1 + k G ⋅ e jϕ G ⋅ Z < ⋅ e jϕ Z
V test ⎛ 2 ⎞
= ⎜1 + k G + 2 ⋅ k G ⋅ cosϕG ⎟ ⋅ Z <
I test ⎝ ⎠
sinϕ Z + k G ⋅ sin(ϕ Z + ϕ G )
ϕ test = arc tan
cos ϕ Z + k G ⋅ cos (ϕ Z + ϕ G )
or
where:
ϕZ : Impedance Angle
kG : D I S T : A b s . v a l u e k G P S x setting
ϕG: D I S T : A n g l e k G P S x setting
In impedance zone 1, the set zone extension factors kze enter into the tripping
impedance in all fault cases.
Ztrip = kze ⋅ Z1
where:
kze: D I S T : k z e , P G H S R P S x or D I S T : k z e , P P H S R P S x or
D I S T : k z e , P G T D R P S x or D I S T : k z e , P P T D R P S x setting
Z1: D I S T : Z 1 ( c i r c l e ) P S x setting
Whether the zone extension factors kze HSR are active or not is controlled by the
following protective functions:
If protective signaling is not ready, then control and switching to the zone extension
factor kze TDR, if applicable, is handled by the internal auto-reclosing function.
Regardless of the readiness of protective signaling, the zone extension factor kze HSR
may be activated during the reclose command – if set accordingly.
Polygon (quadrilateral)
characteristic
The tripping impedance is calculated in the range of the reactance limits (for impedance
angle φZ this means in the range φL < φZ < 90°) as follows:
X
Z< =
sin ϕ Z
The limit angle φL is defined by the point of intersection of reactance and resistance
limits and is calculated as follows:
X
ϕ L = arc tan
X
R+
tan α
R: DIST: R1,PG ( p o l y g o n ) P S x to
DIST: R6,PG ( p o l y g o n ) P S x or
DIST: R1,PP (polygon) PSx to
DIST: R6,PP ( p o l y g o n ) P S x settings
9-4 Impedance characteristic for distance and directional determination for the ‘Polygon’ setting
In the range of the resistance limits (for impedance angles this means in the range of
0° < φZ < φL), the tripping impedance is calculated according to the following equation:
R
Z< =
sin ϕ Z
cos ϕ Z −
tan α
When phase-to-ground loops are checked, the set complex ground factor kG must be
taken into account if the setting for D I S T : A b s . v a l u e k G P S x is not equal to
one and/or the setting for D I S T : A n g l e k G P S x is not equal to 0°. When the test
is carried out using single-phase test current, the following relation for the operate
condition is obtained:
V test
I test
(
= 1 + kG ⋅ Z< )
V test ⋅ e jϕ test
I test ⋅ e j 0° ( )
= 1 + k G ⋅ e jϕ G ⋅ Z < ⋅ e jϕ Z
V test ⎛ 2 ⎞
= ⎜1 + k G + 2 ⋅ k G ⋅ cosϕG ⎟ ⋅ Z <
I test ⎝ ⎠
sinϕ Z + k G ⋅ sin (ϕ Z + ϕ G )
ϕ test = arc tan
cos ϕ Z + k G ⋅ cos (ϕ Z + ϕ G )
or
where:
ϕZ : Impedance Angle
kG : D I S T : A b s . v a l u e k G P S x setting
ϕG: D I S T : A n g l e k G P S x setting
In impedance zone 1, the set kze zone extension factors enter into the tripping
impedance in all fault cases.
Rtrip = kze ⋅ R1
Xtrip = kze ⋅ X1
where:
kze: D I S T : k z e , P G H S R P S x or D I S T : k z e , P P H S R P S x or
D I S T : k z e , P G T D R P S x or D I S T : k z e , P P T D R P S x setting
X1: D I S T : X 1 ( p o l y g o n ) P S x setting
Whether the kze HSR zone extension factors are active or not is controlled by the
following protective functions:
If protective signaling is not ready, then control and switching to zone extension factor
kze TDR, if applicable, is handled by the internal auto-reclosing function. Regardless of
the readiness of protective signaling, zone extension factor kze HSR may be activated
during the reclose command – if set accordingly.
If the voltage memory is to be tested using a single-phase test device, checking should
only be done for an A-B fault.
With the starting signal, the voltage memory is decoupled from the synchronizing voltage
(VA-B), and the stored voltage can be used for directional measurement for 2 s maximum.
The P43x determines, on the basis of the magnitude of the fault voltage, whether the
direction will be determined using the fault voltage, the stored voltage, or the set angle á
(D I S T : α n ( p o l y g o n ) P S x , n: 1, 2, 3, 4, 5, 6). The following possibilities exist:
Enabled ϕX ϕX
Not enabled ϕF α
The user can check to make sure connection to the system’s current and voltage
transformers involves the correct phase by consulting the operating data displays for
load angle (M A I N : L o a d a n g l e p h i A , M A I N : L o a d a n g l e p h i B , and
M A I N : L o a d a n g l e p h i C in the ‘Oper/Cycl/Meas/’ folder). The load angles for all
three phases must be approximately equal. The load angles are only determined if at
least 5% of the nominal device current is flowing.
Checking measuring-circuit
monitoring
Both the current- and voltage-measuring circuits are monitored. Operation of the
monitoring functions can be observed by selecting logic state signals
M C M O N : M e a s . c i r c . V , I f a u l t y (‘Oper/Cycl/Log/’ folder ) or M C M O N : M .
c i r c . V , V r e f f l t y . (‘Oper/Cycl/Log/’ folder). The monitoring signals can also be
entered into the monitoring signal memory and identified by reading out the monitoring
signal memory.
Current-measuring circuits
Monitoring of current-measuring circuits functions only if 0.125 Inom flows in at least one
phase. The P43x determines the absolute value of the negative-sequence component,
from the three phase currents; the negative-sequence component is calculated
according to the following equation:
With
1
I neg = ⋅I
3 test
I P,max = I test
1
⋅I ≥ ( I neg > ) ⋅ I test
3 test
Therefore operation of the monitoring function for current-measuring circuits with single-
phase test current is only possible if the threshold operate value is set at less than 0.333.
1 1
I neg = ⋅I + a2 ⋅ ( − I test ) = ⋅ I test
3 test 3
IP,max = Itest
1
⋅ I test ≥ ( Ineg >) ⋅ I test
3
0.577 ≥ (Ineg> )
Therefore operation of the monitoring function for current-measuring circuits with a two-
phase test current in phase opposition is only possible if the threshold operate value is
set at less than 0.577.
If the threshold operate value satisfies the respective condition, then the monitoring
function for current-measuring circuits operates with a test current greater than
0.125 Inom after the set operate delay of + 300 s has elapsed.
Voltage-measuring circuits
Negative-sequence monitoring of the voltage-measuring circuits is enabled if at least one
phase-to-ground voltage exceeds the value 0.7 Vnom/√3. Other enabling criteria that can
be activated if desired are the following (selection of enabling criteria at
M C M O N : O p . m o d e v o l t . m o n . in the ‘Par/Func/Main/’ folder):
V neg =
1
3
(
⋅ 1V A − G + a 2 ⋅ 1V B − G + a ⋅ 1V C − G )
Anti-clockwise rotating field (or Phase sequence A-C-B):
1
(
V neg = ⋅ 1V A − G + a ⋅ 1V B − G + a 2 ⋅ 1V C − G
3
)
0
a = e j 120
0
a 2 = e j 240
The trigger threshold of Vneg is set permanently at 0.2 Vnom/√3. The result of a single-
phase test using |VB-G| = |VC-G| = 0 and also of the calculation formula for Vneg given
above is that the trigger operates when the test voltage exceeds the following value:
Vnom
V test ≥ 3 ⋅ 0.2 ⋅
3
A trip signal is issued once the set operate delay has elapsed.
Checking backup
overcurrent-time protection
The switch to backup overcurrent-time protection (BUOC) – provided it has been
appropriately set – is brought about by the measuring-circuit monitoring function or the
tripping of the voltage transformer miniature circuit breaker on the line side.
If the current exceeds the set operate value (B U O C : I > P S x ), then starting occurs in
the corresponding phase(s). After the set time delay (B U O C : t I > P S x ) has elapsed,
the P43x trips. If M A I N : N e u t r a l p o i n t t r e a t is set to Low-impedance-
grounding, then SN starting occurs if the residual current IN calculated by the P43x
exceeds the operate value set at B U O C : I N > P S x . After the set time delay has
elapsed (B U O C : t I N > P S x ) , the P43x trips.
When the inrush stabilization function is triggered, the BUOC function is blocked.
If the BUOC is set to activate the ARC, then timer stages B U O C : t I > P S x and
B U O C : t I N > P S x are blocked when the ARC is ready. The trip signal is then
issued instantaneously for phase starting or with an 80 s delay for zero-sequence
starting. Timer stage tIN> is also blocked by phase starting or while the ARC hold time is
elapsing.
The P43x calculates the resultant current IN according to the following equation:
I N = I A + I B + IC
In the case of a single-phase test (for example, IB = IC = 0), the following test current is
obtained:
Checking protective
signaling
The protective signaling function can only be tested if protective signaling is ready.
This can be determined by checking logic state signal P S I G : R e a d y
(‘Oper/Cycl/Log/’ folder).
If protective signaling is not ready, this may be due to the following reasons:
If the conditions for testing are satisfied, it is possible to generate a send signal for test
purposes using a setting parameter (P S I G : T e s t t e l e c o m . U S E R in the
‘Oper/CtrlTest/’ folder) or by triggering an appropriately configured binary signal input.
This pulse will be present for 500 ms and is extended for the set reset time. If the ‘with
echo’ setting has been selected in the protection device at the remote station, then the
received signal will be returned.
If the ARC function is not ready, this may be due to the following reasons:
A test HSR can be executed for testing purposes using a setting parameter or by
triggering binary signal inputs. The test HSR function first issues a trip command and
then issues a reclose command after the set dead time has elapsed.
The possible reasons for the ASC function not being ready are as follows:
The ASC function is not enabled. (This can be determined by checking logic state
signal A S C : E n a b l e d , ( ‘Oper/Cycl/Log/’ folder)). This can have the following
causes:
A S C : E n a b l e d U S E R (‘Par/Func/Main/’ folder) has been set to ‘No’.
A S C : E n a b l e P S x (‘Par/Oper/PSx/’ folder, depending on the parameter
subset) has been set to ‘No’.
ASC is disabled via an appropriately configured binary signal input or a setting
parameter.
(This can be determined by checking logic state signal A S C : E x t . e n a b l e d ,
‘Oper/Cycl/Log/’ folder.)
A logic ‘1’ signal is present at the binary signal inputs configured for M A I N : M . c . b .
t r i p V E X T or M A I N : M . c . b . t r i p V r e f E X T .
The ASC function will be blocked by triggering the binary signal input configured for
ASC: Blocking EXT.
The setting determines whether a close enable may be carried out in case of blocking.
For test purposes, a close request can be generated for 500 ms using A S C : T e s t
c l o s e r e q u U S E R the setting parameter (‘Oper/CtrlTest/’ folder) or by triggering an
appropriately configured binary signal input (A S C : T e s t c l o s e r e q u . E X T ). The
check can only be carried out if there is no ARC cycle running. The P43x checks
whether enabling is permitted or not according to the set conditions. If a positive
decision is reached, then there is an A S C : C l o s e e n a b l e signal. No (re-)close
command takes place! If the check determines that enabling is not permitted, the signal
A S C : C l o s e r e j e c t i o n is issued.
If ground fault short-circuit protection is not ready, this may be due to the following
reasons:
The ground fault short-circuit protection function calculates the neutral displacement
voltage VN-G via the three phase-to-ground voltages according to the following equation:
1
V NG = ⋅ V A −G + V B −G + V C −G
3
In the case of a single-phase test using |VB-G| = |VC-G| = 0, the result of the calculation
formula for VNG given above is that trigger G F S C : V N G > operates when the test
voltage exceeds the following value:
Vnom
V test = 3 ⋅ VNG > ⋅
3
VNG > : Setting G F S C : V N G >
The operation of the trigger can be determined by checking logic state signal G F S C :
V N G > t r i g g e r e d (‘Oper/Cycl/Log/’ folder)
Ground fault short-circuit protection signaling can be checked using a setting parameter
(G S C S G : T e s t t e l e c o m . U S E R ) or by triggering an appropriately configured
binary signal input (G S C S G : T e s t t e l e c o m . E X T ). The P435 then generates a
send signal for 500 ms.
Should the system permit such operation a ground fault on the busbar side (BS) or on
the line side (LS) may be simulated by wiring a short circuit. Then the P435 must issue
the corresponding signal. It is assumed that threshold values for residual current (set at
G F D S S : I N , a c t > / r e a c > B S P S x and G F D S S : I N , a c t > / r e a c > L S P S x
with steady-state power evaluation or G F D S S : I N > with steady-state current
evaluation) and the neutral-point displacement voltage (set at G F D S S : V N G > ) are
exceeded.
A ground fault functional test by wiring a short circuit is, in most cases, not possible as
there is the danger of a double ground fault occurring. As an alternative it is possible to
wire the system’s CTs and VTs such that a functional test is possible without causing a
ground fault.
The residual current and the neutral-point displacement voltage measured by the P435
are displayed as measured operating values in primary quantities referred to the nominal
quantities of the P435.
If current is measured at a Holmgreen group the secondary side of the phase A line
current transformer must be disconnected and shorted (see figure 9-5).
9-5 Ancillary circuit for systems with ground fault compensation and Holmgreen group, ground fault towards BS
A simulated ground fault on the busbar is displayed in the example. The current
connections or the voltage connections must be exchanged to test a ground fault on the
line side.
P43x
45Z5064B_EN
9-6 Ancillary circuit for systems with ground fault compensation and core balance current transformer, ground fault towards BS
If current is measured at a Holmgreen group the secondary side of the phase A and B
line current transformers must be disconnected and shorted (see figure 9-7).
P43x
9-7 Ancillary circuit for isolated neutral-point systems and Holmgreen group, ground fault towards LS
P43x
45Z5066B_EN
9-8 Ancillary circuit for isolated neutral-point systems and core balance current transformers, ground fault towards LS
Completion of
commissioning
Before the protection device is released for operation, the user should make sure that
the following steps have been taken:
After completion of commissioning, only the green LED indicator signaling ‘Operation’
(H1) should be on.
10 Troubleshooting
This chapter describes problems that might be encountered, their causes, and possible
methods for eliminating them. It is intended as a general orientation only, and in cases
of doubt it is better to return the P43x to the manufacturer. Please follow the packaging
instructions in the section entitled "Unpacking and Packing" in Chapter 5 when returning
equipment to the manufacturer.
Problem:
Before checking further, disconnect the P43x from the power supply.
Check to make sure that fuse F1 on power supply module V is not fused.
If the fuse is defective, it should not be replaced without determining the cause of
failure. If a fuse is replaced without eliminating the problem, there is the danger
that the damage will spread.
Required fuses:
Identify the specific problem by reading out the monitoring signal memory (see
section "Monitoring Signal Memory Readout" in Chapter 6). The table below lists
possible monitoring or warning indications (provided that a configuration setting has
been entered at S F M O N : F c t . a s s i g n . w a r n i n g ) , the faulty area, the P43x
response, and the mode of the output relay configured for 'Warning' and
'Blocked/faulty'.
Key:
-: No reaction and/or no output relay triggered.
Updating: The output relay configured for 'Warning' starts only if the monitoring
signal is still present.
1)
: The 'Blocked/faulty' output relay only operates if the signal has been
configured at M A I N : F c t . a s s i g n . f a u l t .
2)
: The 'Warning' output relay only operates if the signal has been
configured at S F M O N : F c t . a s s i g n m . w a r n i n g .
A cold restart has been carried out on account of a checksum error in the
memory (NOVRAM).
The +15 V internal supply voltage has dropped below a minimum value.
The +24 V internal supply voltage has dropped below a minimum value.
The -15 V internal supply voltage has dropped below a minimum value.
The +15 V internal supply voltage of the transient ground fault evaluation
module has dropped below a minimum value.
The -15 V internal supply voltage of the transient ground fault evaluation
module has dropped below a minimum value.
The checksum feature of the transient ground fault evaluation module has
detected a fault in the data transmission of the Dual-Port-RAM.
Fault in the program or data memory of the transient ground fault evaluation
module.
The checksum feature of analog I/O module Y has detected a fault in the
data transmission of the Dual-Port-RAM.
Undefined interrupt.
Faulty test pattern in the RAM. This can occur, for example, if the processor
module or the power supply module is removed from the bus module
(digital). This fault is only detected during device startup. After the fault is
detected, the software initializes the RAM. This means that all records are
deleted.
Software overloaded.
Incorrect or invalid software for transient ground fault evaluation module has
been downloaded.
1st device reaction / 2nd device reaction: Blocking of the ground fault
(short-circuit) protection
(function groups GFSC,
GSCSG) if they were set so that
they would operate with
measured values of the
neutral-point displacement
voltage.
2)
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes 1)
SFMON: M.c.b. trip V 098 000
The fuse failure monitoring function has detected a fault in the voltage-
measuring circuit.
The fuse failure monitoring function has detected a fault in the reference
voltage-measuring circuit.
The operating mode settings for protective signaling and ground fault (short-
circuit) protection signaling are not identical.
1st device reaction / 2nd device reaction: Blocking of ground fault (short-
circuit) protection signaling
'Warning' output relay: Yes / Yes 2)
'Blocked/faulty' output relay: -/-
A protective function has been activated that is not permitted for operation
at a system frequency of 60 Hz.
Multiple signal:
An invalid characteristic has been set for one of the analog output channels
of analog I/O module Y.
An invalid characteristic has been set for the analog input channel of analog
I/O module Y.
The plausibility logic was triggered during the acquisition of the circuit
breaker's (CB) status signals.
An invalid characteristic has been set for the BCD output channel of analog
I/O module Y.
Since the last complete valid message was transmitted the time set at
C O M M 3 : T i m e - o u t c o m m . f a u l t has elapsed and the receive
signals are set to their user-defined default values.
The P43x has detected an open circuit in the connection of the resistance
thermometer.
The P43x has detected an open circuit in the connection of the 20 mA input.
11 Maintenance
The P43x is a low-maintenance device. The components used in the units are selected
to meet exacting requirements. Recalibration is not necessary.
Maintenance procedures in
the power supply area
Electrolytic capacitors are installed in the power supply area because of dimensioning
requirements. The useful life of these capacitors is significant from a maintenance
standpoint. When the equipment is operated continuously at the upper limit of the
recommended temperature range (+55°C or 131°F), the useful life of these components
is 80,000 hours, or more than 9 years. Under these conditions, replacement of the
electrolytic capacitors is recommended after a period of 8 to 10 years. When the
operating temperatures are approx. +45°C inside the devices, the required maintenance
interval can be increased by about 1 year.
The P43x is equipped with a lithium battery for non-volatile storage of fault data and for
keeping the internal clock running in the event of failure of the auxiliary power supply.
Loss of capacity due to module-internal self-discharging amounts to less than 1% per
year over a period of availability of 10 years. Since the terminal voltage remains virtually
constant until capacity is exhausted, usefulness is maintained until a very low residual
capacity is reached. With a nominal capacity of 850 mAh and discharge currents of only
a few µA during device storage or in the range of the self-discharge current during
device operation, the result is a correspondingly long service life. It is therefore
recommended that the lithium battery only be replaced after the maintenance interval
cited above.
Always turn off the power (supply voltage) before removing a hardware module.
The power supply must be turned off for at least 5 s before power supply module V is
removed. Otherwise there is the danger of an electric shock!
Electrolytic capacitor:
on power supply module V.
Lithium battery:
on power supply module V.
There is a danger of explosion if the electrolytic capacitor and battery are not properly
replaced. Always check to make sure that the polarity of the electrolytic capacitor and the
battery is correct.
After the maintenance procedures described above have been completed, new
commissioning tests as described in Chapter 9 must be carried out.
The P43x incorporates in its system a very extensive self-monitoring function for
hardware and software. The internal structure guarantees, for example, that
communication within the processor system will be checked on a continuing basis.
Nonetheless, there are a number of sub-functions that cannot be checked by the self-
monitoring feature without injection testing from the device terminals. The respective
device-specific properties and settings must be observed in such cases.
In particular, none of the control and signaling circuits that are run to the device from the
outside are checked by the self-monitoring function.
The best way to carry out a static test of the analog input circuits is to check the primary
measured operating data using the operating data measurement function or to use a
suitable testing instrument. A "small" measured value (such as the nominal current in
the current path) and a "large" measured value (such as the nominal voltage in the
voltage path) should be used to check the measuring range of the A/D converter. This
makes it possible to check the entire dynamic range.
In addition, a dynamic test can be used to check transmission performance and the
phase relation of the current transformers and the anti-aliasing filter. This can best be
done by measuring the trigger point of the first zone when there is a two-phase
ungrounded fault. For this test, the short-circuit current should be dimensioned so that a
loop voltage of approximately 2 V is obtained at the device terminals with the set
impedance. Furthermore, a suitable testing instrument that correctly replicates the two-
phase ungrounded fault should be used for this purpose.
This dynamic test is not absolutely necessary, since it only checks the stability of a few
less passive components. Based on reliability analysis, the statistical expectation is that
only one component in 10 years in 1000 devices will be outside the tolerance range.
Additional analog testing of such factors as the impedance characteristic or the starting
characteristic is not necessary, in our opinion, since information processing is completely
digital and is based on the measured analog current and voltage values. Proper
operation was checked in conjunction with type testing.
Binary opto-inputs
The binary inputs are not checked by the self-monitoring function. However, a testing
function is integrated into the software so that the trigger state of each input can be read
out (‘Oper/Cycl/Phys’ folder). This check should be performed for each input being used
and can be done, if necessary, without disconnecting any device wiring.
Binary outputs
With respect to binary outputs, the integrated self-monitoring function includes even two-
phase triggering of the relay coils of all the relays. There is no monitoring function for
the external contact circuit. In this case, the all-or-nothing relays must be triggered by
way of device functions or integrated test functions. For these testing purposes,
triggering of the output circuits is integrated into the software through a special control
function (‘Oper/CtrlTest/’ folder).
Before starting the test, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
Serial Interfaces
The integrated self-monitoring function for the PC or communication interface also
includes the communication module. The complete communication system, including
connecting link and fiber-optic module (if applicable), is always totally monitored as long
as a link is established through the control program or the communication protocol.
12 Storage
If the units are stored without being connected to auxiliary voltage, then the electrolytic
capacitors in the power supply area need to be recharged every 4 years. Recharge the
capacitors by connecting auxiliary voltage to the P43x for approximately 10 minutes.
The P43x is supplied with standard labeling for the LED indicators. LED indicators that
are not already configured and labeled can be labeled using the label strips supplied.
Affix the label strips to the front of the unit at the appropriate location.
The label strips can be filled in using a Stabilo brand pen containing water-resistant ink
(Type OH Pen 196 PS).
14 Order Information
MiCOM P433
P433 Distance Protection Device P4 3 3- 9 0 -308 -4xx -612 -46x -9x x -9x x -8xx
Basic device:
Basic device 40TE, pin-terminal connection, 3 -410
Basic device 84TE, ring-terminal connection, 8 -411
basic complement with 4 binary inputs and 8 output relays
Current transformer:
Inom = 1 A / 5 A (T1...T4) 2) 9
Voltage transformer:
Vnom = 50 ... 130 V (4-pole) 4
Vnom = 50 ... 130 V (5-pole) 5
MiCOM P433
P433 Distance Protection Device P4 3 3- 9 0 -308 -4xx -612 -46x -9x x -9x x -8xx
With communication / information interface:
Only IRIG-B input For clock synchronization -90 0
Protocol IEC 60870-5-103 only -91
Protocol can be switched between: -92
IEC 60870-5-101/-103, Modbus, DNP3, Courier
and IRIG-B input for clock synchronization
and 2nd interface (RS485, IEC 60870-5-103)
For connection to wire, RS485, isolated 1
For connection to plastic fiber, FSMA connector 2
For connection to glass fiber, ST connector 4
Language:
English (German)
4)
Without order extension no.
Px40 English (English)
4)
On request -800
German (English)
4)
-801
French (English)
4)
On request -802
Spanish (English)
4)
On request -803
Polish (English)
4)
On request -804
Russian (English)
4) 7)
On request -805
7) Hardware option, supports Cyrillic letters instead of special West. Europe characters
8) Standard variant recommended, if higher pickup threshold not explicitly required by the application
MiCOM P435
P435 Distance Protection Device P4 3 5- 9 0 -308 -4xx -612 -46x -9x x -9x x -8xx
Basic device:
Basic device 40TE, pin-terminal connection, 3 -413
Basic device 84TE, pin-terminal connection, 7 -414
Basic device 84TE, ring-terminal connection, 8 -415
basic complement with 4 binary inputs and 8 output relays
Current transformer:
Inom = 1 A / 5 A (T1...T4)
2)
9
Voltage transformer:
Vnom = 50 ... 130 V (4-pole) 4
Vnom = 50 ... 130 V (5-pole) for Automatic Synchronism Check 5
MiCOM P435
P435 Distance Protection Device P4 3 5- 9 0 -308 -4xx -612 -46x -9x x -9x x -8xx
Switching threshold on binary inputs:
>18 V (standard variant) Without order extension no.
>90 V (60...70% of VA,nom = 125...150 V)
8)
-461
>155 V (60...70% of VA,nom = 220...250 V)
8)
-462
>73 V (67% of VA,nom = 110 V)
8)
-463
>146 V (67% of VA,nom = 220 V)
8)
-464
Language:
English (German) 4) Without order extension no.
Px40 English (English)
4)
On request -800
German (English)
4)
-801
French (English)
4)
On request -802
Spanish (English) 4) On request -803
Polish (English)
4)
On request -804
Russian (English)
4) 7)
On request -805
Language version
In order to display the Russian data model, the corresponding order extension number
(-805) must be added upon ordering so that the hardware option supporting Cyrillic
characters is integrated. With this ordering option, reference menu texts (English) will be
available for display. However, other Western European languages containing extra
characters will not be fully supported. Consequently, selecting the "Russian / English"
ordering option means that it will not be possible to download Western European data
models into the device.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P43x/EN M/Ac7 Version: -612 11/2010
Customer Care Centre
http://www.schneider-electric.com/CCC
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P43x/EN M/Am7 Version: -612 -614 -615 -630 -631, Vol. 1 06/2011