Size I Beam can be reduce.

Each point load can


be reduced to be 6 Ton

Based on the email


1 1 1 1 300
10530
300
received 2nd
9930 September, the beam
4300 4300 4300 4300 4300 4300 4300 4300 is designed for
3850 3850 3850 3850 3850 3850 3850 3850 DETAIL 'C'
The horizontal B3 Beam can be omitted 18Ton

250
S.W.L 18T
LEVEL L3
B1
B3 B3
Noted

B3 B3

* 7250
B3 B3
B3 B3

B2

B2

B2

B2
B1

B1

B1

B1

B1

B1
10530

10530

10530

10530
9930

9930

9930

9930
B2

B2

B2

B2
B3 B3

B3 B3
LEVEL L2
B3 B3

15680
B3 B3 B1

* 3350
B3 B3
B3 B3 B3 B3 B3 B3
LEVEL L1

B2

1 1 1 1 R C WALL B3 Beam can be omitted R C WALL

* 4500
Noted

E7 & S5 PLAN VIEW - LEVEL L3 E7 & S5 PLAN VIEW - LEVEL L2 E7 & S5 PLAN VIEW - LEVEL L1 E7 & S5 PLAN VIEW - LEVEL L0 DETAIL 'A' DETAIL 'B'
SCALE :100 SCALE :100 SCALE :100 SCALE :100
LEVEL L0 B3 B3 B3

325
NOTE : - NOTE : - NOTE : - NOTE : -
B2
1. LOCATION OF THE BEAM TO BE CONFIRMED BY M&E ENGINEER 1. LOCATION OF THE BEAM TO BE CONFIRMED BY M&E ENGINEER 1. LOCATION OF THE BEAM TO BE CONFIRMED BY M&E ENGINEER 1. LOCATION OF THE BEAM TO BE CONFIRMED BY M&E ENGINEER
PRIOR TO INSTALLATION PRIOR TO INSTALLATION PRIOR TO INSTALLATION PRIOR TO INSTALLATION
600 600
LEGENDS:-

300 B1 - U.B 610x305x179kg/m


B2 - U.B 610x229x113kg/m
B3 - U.B 356x171x45kg/m E7 & S5 SECTION 1-1
SCALE :100
- DENOTES THE LEVEL TO BE CONFIRMED BY M&E ENGINEER
A

*
300
C
100 20
6 NOS OF M16 GRADE 8.8 BOLTS
40
350
40
B 5 NOS OF M16 GRADE 8.8 BOLTS
270 350
FIN PLATE 430x100x12 120 20 40 40
FIN PLATE 440x100x12

250
270
3 NOS OF M12 GRADE 8.8 BOLTS
100

EA 100x100x10 100
10 10

100
220mm LONG 50
40 70 70 70 70 70 40

350x700x16mm BASE PLATE 6 NOS OF M20 HILTI HIT-V BOLTS


150

GROUTED WITH HILTI RE-500

55

90 40
8 NOS OF M16 HILTI HIT-V BOLTS

40

250
GROUTED WITH HILTI RE-500

70 70
220
B3
430

200
700

90
B1

440

700
B2

40
B1

90
350x700x16mm BASE PLATE
150

250
40 90
100

8mm CFW

100
8mm CFW
50
100 B 50
100
E7&S5 - DETAIL - B S6 - SECTION B-B
A SCALE1:10 SCALE1:10

E7&S5 - DETAIL - A E7&S5 - SECTION A-A C


SCALE1:10 SCALE1:10 E7&S5 - DETAIL - C E7&S5 - SECTION C-C
SCALE1:10 SCALE1:10

SHOP DRAWING
Butiran Rujukan TRX CITY SDN. BHD. CADANGAN PENYURAIAN TRAFIK DAN KERJA-KERJA
MENAIKTARAF JALAN TUN RAZAK DARI JALAN LANGGAK
GOLF KE BULATAN KAMPUNG PANDAN KUALA LUMPUR
DIREKA OLEH : (PACKAGE 2)
NABIL
UNTUK TETUAN TRX CITY SDN. BHD.
DILUKIS OLEH : DISEMAK OLEH :
NABIL CHEONG