Professional Documents
Culture Documents
Abstract: The ability to properly assess existing reinforced concrete (RC) structures provides an opportunity to prevent costly rehabilitations
or replacements and aid in the optimization of future designs. Distributed fiber-optic sensing (DFOS) is a promising option in the assessment
Downloaded from ascelibrary.org by Heriot-Watt University on 10/09/21. Copyright ASCE. For personal use only; all rights reserved.
of these complex structures. Previous uses of this technology, however, have been limited to static measurements, prohibiting the assessment
of structures exposed to dynamic loads. This research intends to assess the dynamic sensing capabilities of a DFOS system and, in turn,
improve the current understanding of the dynamic behavior of an existing RC beam tested in situ through a case study. Based on the
data provided by the dynamic distributed fiber-optic sensors (DDFOS), dynamic measurements of distributed strains, distributed deflections,
and crack widths can all be provided. Further details regarding the use of the DDFOS system in assessment, including the determination
of support conditions and dynamic response factors, are presented and discussed. DOI: 10.1061/(ASCE)CF.1943-5509.0001488. © 2020
American Society of Civil Engineers.
Author keywords: Fiber-optic sensors; Distributed strain measurement; Dynamic loading; Reinforced concrete (RC); Crack widths;
Deflections; Monitoring; Serviceability.
Introduction Techniques have also been developed by Brault and Hoult (2019b)
to measure distributed concrete surface strains and use that data to
Current assessment methods for complex and heavily redundant simultaneously measure RC beam deflections, crack spacing, and
reinforced concrete (RC) structures often require conservative as- crack widths. These methods were also applied to the field assess-
sumptions, potentially leading to unnecessary costly rehabilitation ment of statically loaded RC beams during the construction of a
or reconstruction (Middleton 1997; Bentz and Hoult 2016). Addi- shopping center in Ottawa, Canada (Brault et al. 2018). Most pre-
tionally, the inability to fully understand the behavior of these vious uses of DFOS, including these studies, have been limited to
existing structures prohibits the opportunity for optimization in new static measurements. This prohibits the measurement of dynamic
designs (Orr et al. 2014). This can have negative economic and strains, and the corresponding deflections and crack widths, as the
environmental effects on new construction (Orr et al. 2014). Con-
result of cyclic or moving loads. By combining DFOS with dy-
sequently, the need exists for monitoring technologies that can pro-
namic sensing capabilities, it could then be possible to better under-
vide accurate and robust data sets to enable a better understanding
stand the behavior of these complex structural systems, as well as
of the behavior of these structures, specifically when exposed to
provide sufficient data for the proper assessment and future opti-
both dynamic and static loads.
mization of RC-structures.
Most current structural assessment and monitoring techniques are
Dynamic distributed fiber-optic sensing (DDFOS) is a new tech-
limited to discrete measurements of individual structural metrics,
such as electrical resistance-based strain gauges and displacement nology that can measure strain along the length of a fiber-optic
transducers (Gastineau et al. 2009). These discrete measurements cable at acquisition rates as high as 250 Hz (LUNA Technologies
often prohibit the ability to monitor the global behavior of a structure, 2017). Existing studies utilizing DDFOS technology are limited;
such as the deflected shape, as well as localized behavior in locations however, it has been shown that external RC strains can be recorded
where the sensors are not present, including the presence and size of during laboratory fatigue tests of RC beams (Barrias et al. 2018a).
cracks (Brault and Hoult 2019a). Other examples of DDFOS in use do exist in the transportation
Distributed fiber-optic sensing (DFOS) technologies improve (Wheeler et al. 2018) and aerospace (Davis et al. 2016) industries;
on traditional monitoring methods by providing the ability to re- however, to date, there are no studies that exhibit the use of DDFOS
cord accurate strain data (∼1 microstrain) at a dense spatial reso- for the full-scale assessment of existing RC-structures.
lution (<5 mm) (Kreger et al. 2007). Regier and Hoult (2014) In order to both utilize and evaluate the capabilities of DDFOS
provided evidence that DFOS can measure detailed external RC technology for structural assessment, a field study has been con-
strains throughout a fiber-optic cable when applied to an RC bridge. ducted. The study investigates the behavior of an existing RC beam,
which was instrumented and tested, in situ, under both static and
1 dynamic loads. The objectives of this research program were to
Researcher, Dept. of Civil Engineering, Queen’s Univ., 58 University
Ave., Kingston, ON, Canada K7L 3N6. Email: z.broth@queensu.ca (1) monitor existing RC beams using both discrete and dynamic dis-
2
Associate Professor, Dept. of Civil Engineering, Queen’s Univ., tributed sensors under varying load cases, (2) evaluate the results of
58 University Ave., Kingston, ON, Canada K7L 3N6 (corresponding DDFOS measurements by comparing them with those from discrete
author). Email: neil.hoult@queensu.ca
sensors, and (3) utilize DDFOS data to determine dynamic measure-
Note. This manuscript was submitted on June 13, 2019; approved on
March 13, 2020; published online on May 20, 2020. Discussion period ments of deflection, crack widths, and dynamic response factors as a
open until October 20, 2020; separate discussions must be submitted for result of the maximum expected dynamic loading on a structure.
individual papers. This paper is part of the Journal of Performance of The following section of this paper provides a brief background
Constructed Facilities, © ASCE, ISSN 0887-3828. on structural assessment methods and FOS technologies, followed
LP 3 40 mm LP 2 LP 1
Wall Face
9.24 m
9.10 m
6.93 m
4.62 m
(a)
Floor Slab
FOS Beam
550 mm 702 mm Location
356 mm
(b) (c)
Fig. 1. Beam schematics, including (a) beam profile and instrumentation; (b) beam cross-section; and (c) beam location within the 3rd floor floorplan
of Ellis Hall.
state of the beam could be measured. It should be noted that the data
acquisition rate of both the DDFOS and displacement data was
Testing Procedure
50 Hz, and the data was logged continuously throughout the tests.
The application of the dynamic loads applied during this investi- Therefore, any long-term effects caused by the UDL test prior to the
gation was provided by 38 student volunteers who were asked to PL test would be seen in the data. This is discussed further in the
jump in unison over the instrumented specimen. The use of human results section.
loading allowed for easier management of the load placement,
which resulted in the completion of two separate tests, including
a distributed and concentrated load test. The distributed load test Results and Discussion
was conducted by aligning the students across the full span of
the classroom (wall-to-wall) directly above the instrumented beam.
Deflection Behavior
For the concentrated load test, the students were gathered in a group
over the midspan of the beam. This concentrated load was intended Deflection data can be provided for the complete duration of the
to represent a point load. However, the group of students filled an two tests from the three LPs that were used during the investigation,
area that was approximately 3 by 3 m area centered over the mid- including the midspan, quarter-span, and column support. Fig. 2
span position within the tributary area of the beam. Based on an provides the deflection versus time data from two of the three
average recorded mass of the volunteers of 75 kg, the applied con- LPs (i.e., midspan and quarter-span). The data from the third LP
centrated load was determined to be approximately 28 kN, while were omitted due to the minimal deflection measured at the column
the distributed load was approximately 3 kN=m. This study refers support. The deflection measured by each LP began at zero, which
0 0
Displacement (mm)
Displacement (mm)
-0.2 -0.2
-0.4 -0.4
-0.6 -0.6
-0.8 -0.8
-1 -1
0 20 40 60 80 100 0 20 40 60 80 100
(a) Time (Seconds) (c) Time (Seconds)
0 0
Displacement (mm)
Displacement (mm)
-0.2 -0.2
-0.4 -0.4
-0.6 -0.6
-0.8 -0.8
-1 -1
0 20 40 60 80 100 0 20 40 60 80 100
(b) Time (Seconds) (d) Time (Seconds)
Fig. 2. Displacement results from the LPs, including (a) quarter-span UDL test; (b) midspan UDL test; (c) quarter-span PL test; and (d) midspan
PL test.
beam have grown to the height of the top fiber-optic cable. This is
within the deflection data. Within the jumping cycles, the unloaded supported by the alignment of the measured cracks within the top
phases of each jump do not always return to zero. This is attributed and bottom fibers, as it is expected that the flexural cracks would
to the timing of the volunteers’ jumps where it is unlikely that all grow vertically through the beam’s depth.
the volunteers were airborne at the exact same moment. Addition- The bottom fiber data also provide insight into the boundary
ally, the amount of time between the unloaded and impact phases conditions of the instrumented beam, including inflection points
may have not been long enough for the beam to respond to the near the supports of the beam (at approximately 2 and 8 m). Beyond
push-off force and return to the zero position before the impact the two inflection points, compressive strains are measured in the
occurred. Overall, the maximum dynamic deflections under the bottom fiber, suggesting that there is moment transfer at the sup-
two loading cases at midspan were 0.54 and 0.84 mm for the UDL ports. A single negative strain peak can be observed at approxi-
and PL tests, respectively. mately 1 m within the bottom fiber from each test. This peak likely
Following the jumping phase of the two tests, the beam returned represents the closing of a crack at this location due to the com-
to the statically loaded position while the volunteers were at rest. pressive stresses experienced in this area.
The beam was then unloaded as the volunteers walked off the beam
and away from the tributary area of the specimen. After the com- Dynamic Response Factor
pletion of the test, when the beam was unloaded, there are remain- By comparing the maximum distributed strains as a result of the
ing deflections of 0.03 and 0.04 mm at the midspan for the UDL dynamic jumping loads with the average static strain distribution,
and PL tests. Due to the intensity of the loading applied to the struc- it might be possible to quantify the dynamic response factor (DRF)
ture during the two tests (compared to the normal working loads on for the two loading arrangements. Fig. 4 provides both the static
the structure), the remaining deflections that can be measured are as and maximum dynamic strain distributions for both the UDL and
the result of crack development or growth. These residual deflec- PL tests. Based on this data, a distribution of DRF values was de-
tions, however, could also be the result of minor shifts in the LP termined throughout the fiber length. DRF values are important in
sensors due to the vibrations caused by the repeated impact loads or
because their supports moved. Temperature can also have an impact
on the fiber-optic measurements using Rayleigh backscatter for 400
Bottom Fibre
experiments occurring over a longer period of time (e.g., Davis Top Fibre
et al. 2017); however, it was not expected to impact the current tests 300
Strain (Microstrain)
Crack 1
that occurred over a duration of less than 5 min within a building.
200
This behavior is discussed in greater detail later in the results
section. Top Fiber
100
Ends
native measure of the beam’s DRF can be calculated based on the Fig. 5, as well as observe the dynamic behavior of cracks, an exami-
static and dynamic deflection measurements from the LP data pro- nation of the crack widths with time for the crack labeled in Fig. 3
vided in Fig. 2. The results of this calculation are 2.16 and 2.47 for was conducted. Brault and Hoult (2019b) proposed a method of
the UDL and PL test, respectively. It is clear that there is a signifi- estimating the area under the concrete surface strain plot in the
cant discrepancy between the DRF results and the DDFOS and LP vicinity of a crack to calculate the crack width. They proposed
data. Previous studies, such as Bakht and Pinjarkar (1989) and the two methods, and in this study, the method used was where the
Highway Research Board (1962), have discussed similar trends crack width is calculated using the area of a triangle with the maxi-
when comparing DRF results based on deflection measurements mum strain at the crack as the peak of the triangle and the slopes of
to those based on strain. In each case, the DRF values determined each side were defined by the minimum strains on either side of the
using deflection measurements were found to be greater than those crack. Based on this method provided by Brault and Hoult for static
for the strain-based results. However, in the current study, the crack width estimations, dynamic crack widths could be calculated
amount of variation in the DDFOS measurements means that it for each sampling of the DDFOS data and are provided in Fig. 6.
is not clear whether the difference in DRF values is a function The data display the opening and closing of cracks as a result of the
of the measurement technique or the sensor measurement accuracy. applied loads. Based on these results, both the static crack width
Thus, while using DDFOS data to calculate DRF values may be and maximum dynamic crack width can be determined. The two
possible if larger strains are present, it is not recommended for cracks grow throughout the duration of both tests, resulting in
the level of strain measured in this work (i.e., average values less an increased crack width due to static loading, as well as a residual
than 50 microstrain). crack width after the beam was unloaded. This is an important re-
sult since though locked-in strains can affect the minimum crack
Maximum Strain with Time width measurement, they would not affect the maximum crack
Fig. 5 provides the strain versus time data for the sensor located at width measurement and so it appears the cracks did grow during
the maximum strain location (4.22 m) throughout the UDL and PL the test. This behavior would result in both the residual strains seen
tests. Note that the maximum strains occurred at the location of in Fig. 5 and the remaining deflections shown in Fig. 2 after the
Crack 1, as labeled in Fig. 3, during both tests. It is important beam was unloaded. Following the UDL tests, the crack continues
to note that the strains at the beginning of the PL test are not zero. to grow throughout the static loading and jumping cycles of the PL
The UDL test was performed first followed by the PL test (1 min test, resulting in further crack growth after the beam was unloaded
and 30 s later), and the residual strains as a result of the UDL test the second time. The total crack growth measured after the com-
were carried over into the PL test. These residual strains observed at pletion of both tests is approximately 0.0025 mm. Although the
Crack 1 could be caused by the widening and growth of the crack, crack widths when the beam is unloaded could have been affected
resulting in an irrecoverable strain after the beam was unloaded by the residual strain phenomena explored by Brault et al. (2018),
during the UDL test. Creep could also contribute to the develop- these phenomena should not impact the maximum strains and thus
ment of these strains. Since it is assumed that the dynamic loads crack widths measured.
applied throughout the jumping cycles are likely the highest loads
experienced by the beam within its lifetime, they could have caused Deflected Shape
the cracks to extend and widen, contributing to the remaining de- Utilizing the strain data from both the bottom and top fiber-optic
flections measured at the LP locations along the RC beam after it cables and the distance between them, it is possible to calculate the
was unloaded. It is most likely that both mechanisms were occur- curvature along the fibers’ length. By applying Bernoulli–Euler
ring in the beam as short-term displacement increases have also elastic beam theory and the validated methods provided by Brault
been observed in the lab due to creep under constant load and a and Hoult (2019b), the curvature results can be double-integrated to
decrease in tension stiffening at the cracks under cyclic loading determine distributed bending displacement throughout the length
(Broth and Hoult 2020). However, isolating the effects of each of the instrumented section, as shown in Fig. 7. Though Brault and
mechanism on the behavior is not possible with the available data Hoult did this using static measurements, the method is applied for
as both mechanisms are highly variable, nonlinear, and time and the first time here using dynamic measurements. Fig. 7 shows the
load dependent. Both crack growth and concrete creep could also calculated deflected shape for the statically loaded case, maximum
explain the remaining displacements measured by the LP following dynamically loaded case, and unloaded case following the jumping
each test, as shown in Fig. 2. cycles for both load cases. Note that for each deflected shape to be
Another explanation for these residual strains, as investigated by calculated, two boundary conditions must be used. For all of the
Brault et al. (2018), could be due to locked-in strains within the results provided in Fig. 7, both the midspan and support LP data
fiber-optic cable or the epoxy used to bond the fiber-optic cable were used as boundary conditions, while the quarter-span LP was
to the concrete. Brault et al. indicated that irrecoverable strains used to verify the results. Also, note that deflection data could not
Strain (Microstrain)
Strain (Microstrain)
300 300
200 200
100 100
0 0
0 2 4 6 8 0 2 4 6 8
(a) Fibre Length (m) (c) Fibre Length (m)
Downloaded from ascelibrary.org by Heriot-Watt University on 10/09/21. Copyright ASCE. For personal use only; all rights reserved.
5 5
4 4
3 3
2 2
1 1
0 0
0 2 4 6 8 0 2 4 6 8
(b) Fibre Length (m) (d) Fibre Length (m)
Fig. 4. Dynamic response factor results, including (a) the dynamic/static strain profiles from the UDL test; (b) resulting DRF distribution for the UDL
test; (c) the dynamic/static strain profiles from the PL test; and (d) resulting DRF distribution for PL test.
400 400
Strain (Microstrain)
Strain (Microstrain)
300 300
200 200
100 100
0 0
0 20 40 60 80 0 20 40 60 80 100
(a) Time (Seconds) (b) Time (Seconds)
Fig. 5. Strain with time data for (a) UDL test at maximum strain location (x ¼ 4.22 m; Crack 1); and (b) PL test at maximum strain location
(x ¼ 4.22 m; Crack 1).
0.02 0.02
Crack Width (mm)
0.015 0.015
0.01 0.01
0.005 0.005
0 0
0 20 40 60 80 0 20 40 60 80 100
(a) Time (Seconds) (b) Time (Seconds)
Fig. 6. Crack width measurements with time for Crack 1 identified in Fig. 3, including (a) Crack 1—UDL; and (b) Crack 1—PL.
-0.2
Downloaded from ascelibrary.org by Heriot-Watt University on 10/09/21. Copyright ASCE. For personal use only; all rights reserved.
DDFOS was able to accurately capture the true behavior of assess reinforced concrete behaviour.” Eng. Struct. 204 (Feb): 110036.
the beam. https://doi.org/10.1016/j.engstruct.2019.110036.
• DDFOS data provided the ability to determine the dynamic re- Chang, P. C., A. Flatau, and S. C. Liu. 2003. “Review paper: Health
sponse factor of the instrumented structure, which was found to monitoring of civil infrastructure.” Struct. Health Monit. Int. J. 2 (3):
be lower than the deflection-based DRF results. Both are con- 257–267. https://doi.org/10.1177/1475921703036169.
Davis, C., M. Knowles, N. Rajic, and G. Swanton. 2016. “Evaluation of a
sidered valid DRF values, as similar comparisons are found in
distributed fibre optic strain sensing system for full-scale fatigue test-
previous studies.
ing.” Procedia Struct. Integrity 2: 3784–3791. https://doi.org/10.1016/j
• Distributed crack widths and deflected shapes, previously lim- .prostr.2016.06.471.
ited to static measurements, could be determined dynamically Davis, M. B., N. A. Hoult, S. Bajaj, and E. C. Bentz. 2017. “Distributed
utilizing the recorded strain data from the DDFOS system, sensing for shrinkage and tension stiffening measurement.” ACI
including the identification of the maximum results due to Struct. J. 114 (3): 753–764.
the applied dynamic load. Gastineau, A., T. Johnson, and A. Schultz. 2009. Bridge health monitoring
• In the future, the data from these experiments can be used in and inspections: A survey of methods. Rep. No. MN/RC 2009-29.
conjunction with a finite element model to undertake model up- St. Paul, MN: Minnesota Dept. of Transportation.
dating to develop more accurate approaches to design. However, Gebremichael, Y. M., et al. 2005. “A field deployable, multiplexed Bragg
it should be noted that data from multiple structures will be grating sensor system used in an extensive highway bridge monitoring
required to ensure the reliability and accuracy of these finite evaluation tests.” IEEE Sens. J. 5 (3): 510–519. https://doi.org/10.1109
element models for design. In addition, structures designed us- /JSEN.2005.846185.
ing these approaches should have sensors installed to confirm Highway Research Board. 1962. Special report 61D: The AASHO road
test. Rep. No. 4: Bridge Research. Publication 953. Washington,
the accuracy of these models.
DC: National Academy of Sciences, National Research Council.
Hoult, N., M. Dutton, A. Hoag, and W. A. Take. 2016. “Measuring crack
movement in reinforced concrete using digital image correlation: Over-
Data Availability Statement view and application to shear slip measurements.” Proc. IEEE 104 (8):
1561–1574. https://doi.org/10.1109/JPROC.2016.2535157.
Some or all data, models, or code generated or used during Kreger, S. T., D. K. Gifford, M. E. Froggatt, A. K. Sang, R. G. Duncan,
the study are available from the corresponding author by request M. S. Wolfe, and B. J. Soller. 2007. “High-resolution extended distance
(i.e., raw fiber-optic strain data and LP data). distributed fiber-optic sensing using rayleigh backscatter.” In Proc.,
Sensor Systems and Networks: Phenomena, Technology, and Applica-
tions for NDE and Health Monitoring. Bellingham, WA: SPIE.
Kreger, S. T., A. K. Sang, N. Garg, and J. Michel. 2013. “High resolution,
Acknowledgments
high sensitivity, dynamic distributed structural monitoring using optical
frequency domain reflectometry.” In Proc., Fiber Optic Sensors and
The authors would like to acknowledge the Natural Sciences
Applications X. Bellingham, WA: SPIE.
and Engineering Research Council of Canada for their financial
Kurashima, T., T. Horiguchi, and M. Tateda. 1990. “Distributed-
support. The authors would also like to thank Sara Nurmi, Eric temperature sensing using stimulated Brillouin scattering in optical
Pannese, Paul Thrasher, and Andre Brault from Queen’s University. silica fibers.” Opt. Lett. 15 (18): 1038–1040. https://doi.org/10.1364/OL
Finally, the authors would like to thank all of the volunteers who .15.001038.
were involved in the experiments. Lee, J. J., and M. Shinozuka. 2006. “A vision-based system for remote sens-
ing of bridge displacement.” NDT & E Int. 39 (5): 425–431. https://doi
.org/10.1016/j.ndteint.2005.12.003.
References LUNA Technologies. 2017. ODiSI-B optical distributed sensor interroga-
tor: User’s guide. Blacksburg, VA: Luna Innovations Incorporated.
ACI (American Concrete Institute). 2001. Control of cracking in concrete Majumder, M., T. K. Gangopadhyay, A. K. Chakraborty, K. Dasgupta, and
structures. ACI 224R. Farmington Hills, MI: ACI. D. K. Bhattacharya. 2008. “Fibre Bragg gratings in structural health
Bakht, B., and S. G. Pinjarkar. 1989. “Dynamic testing of highway monitoring—Present status and applications.” Sens. Actuators, A 147 (1):
bridges—A review.” Transp. Res. Rec. 1123: 93–100. 150–164. https://doi.org/10.1016/j.sna.2008.04.008.
Barrias, A., J. R. Casas, and S. Villalba. 2018a. “Fatigue testing of rein- Middleton, C. R. 1997. “Concrete bridge assessment: An alternative
forced concrete beam instrumented with distributed optical fiber sensors approach.” Struct. Eng. 75 (23/24): 403–409.
(DOFS).” In Proc., Civil Engineering Research in Ireland. Dublin, Mohamad, H., K. Soga, A. Pellew, and P. J. Bennett. 2011. “Performance
Ireland: Civil Engineering Research Association of Ireland. monitoring of a secant-piled wall using distributed fiber optic strain
Barrias, A., G. Rodriguez, J. R. Casas, and S. Villalba. 2018b. “Application sensing.” J. Geotech. Geoenviron. Eng. 137 (12): 1236–1243.
of distributed optical fiber sensors for the health monitoring of two real https://doi.org/10.1061/(ASCE)GT.1943-5606.0000543.
Tennyson, R. C., A. A. Mufti, S. Rizkalla, G. Tadros, and B. Benmokrane. jected to hydraulic transient excitation.” Struct. Health Monit. 17 (2):
2001. “Structural health monitoring of innovative bridges in Canada 298–312. https://doi.org/10.1177/1475921717691036.