You are on page 1of 1

Ref No.

Global SMMIEC Preamble Description Unit Main Work QTY Quantities Rate Amount
Cost Code Reference Reference General LPG4 Substation Supply Install
plant area
S$
2.2.3 Rejuvenation of Existing 400V Switchgear HV5-ESB-01 at SH60 as follows (Ref. Drawing Nos. 0591-8530-70-0012 : Set
- BUS B:- Feeder C2 K - 250/160, 63A SFU (new fuse rating).
-c/w Suitable rating SFU, Contactor, CT etc. as applicable
Scope includes supply of 3nos 63A SFU and replacement of Existing Fuses, power terminals and with associated
wiring as applicable as per Drawing as applicable.
Location: SH60 Indoor

2.2.4 Existing 110V AC VITAL BOARD CD3-IVB-1 in SH13B FAR -tapping power from spare Power Feeder: (Refer SLD) : Set - 1 0 0
0591-8530-70-0013

The Contractor scope includes Replacement of fuse (Maximum size 25A) for feeders wherever specified in drawing,
power tapping, testing, pre commissioning of existing feeder and energization of modules after cable connections etc.
Location: SH13B CD3 FAR Indoor

2.2.5 Existing 240V AC VITAL BOARD CD3-IVB-2 in SH13B/CD3 FAR -tapping power from spare Power Feeder: (Refer Set - 1 0 0
SLD) : 0591-8530-70-0015

The Contractor scope includes Replacement of fuse (Maximum size 25A) for feeders wherever specified in drawing,
power tapping, testing, pre commissioning of existing feeder and energization of modules after cable connections etc.

Location: SH13B CD3 FAR Indoor

2.2.6 Existing 415/240V AC Existing Analyzer Distribution Panel out side SH22 -tapping power from 2 spare Power Feeders Set - 1 0 0
for H2S Analyser: (Refer Drg) : 0591-8530-70-0014.
- Existing Equipment item (Feeder 2-R1) - 10A for Electrical Heating system of LPG4 Analyzer.
- Existing Equipment item (Feeder 5-B3) - 10A for H2S Analyzer for LPG4.

The Contractor scope includes supply of 2nos 20A SFU and power tapping, testing, pre commissioning of existing
module and energization of modules after cable connections etc.

Location: SH22 Outdoor.

2.2.7 Sea water filter Power & control panel (S-2754A) wall mounted Set - 1 by SEPL/Wood 0
Location: SH22 Indoor
(Overall dimensions : 800 mm (W) X 300 mm (D) X 1000 mm(H)
Weight : Approx. 80 kg
Refer Dwg No. K2019/25/5830-1000

2.2.8 Sea water filter control section panel for S-2754A Set 1 - by SEPL/Wood 0
Location: LPG-4 Plot (Outdoor)
Ex rated , stainless steel Panel
(Overall dimensions : 400 mm (W) X 150 mm (D) X 900 mm(H)
Weight : Approx. 25 kg
Refer Dwg No. K2019/25/5830-1000
Note : Filter Vendor (Taprogge) have supplied Stanchion support along with canopy/sunshed. Contractor need to install
this stanchion and Panel.
Refer Supplier drawing number K2029/25/5830-0536 for Stanchion support and K2019/25/5830-1000 for panel drawing

2.2.9 Replacement of old ELCBs with New ELCBs of 6 nos circuits at Lighting distribution board (SH22) Set 1 0 0
New ELCBs shall be 2 Pole , 25A with sensitivity 30 mA (Make : Schneider) .
Refer Lighting DB Outside SH-22 drawing number 0591-8530-75-0006 for details
Note : All new ELCBs shall be tested before installation

2.3 2735 / 3735 J.7 9.6, J70 Control Stations and Socket Outlets
2.3.1 3735 Local Control stations (RCU) Installation
2.3.1.1 Remote control unit "OFF-AUTO-ON" / "OFF-0-ON" c/w padlocking at "off" position, with CT connection & ammeter nr 17 - by SEPL/Wood 0
suitable for - Zone 1,Gas group IIC,T3 application. Scope includes installation of new RCU c/w support structure .
(Contractor installation scope includes supply, design, fabrication and installation of structural steel support brackets,
Canopy for the RCU)

2.3.1.2 Welding Socket Outlets


125A, 4 Pole, 400V- Welding SOCKET OUTLET(Wall / Structure mounting Type) suitable for Zone 1,Gas group IIC,T3 nr 2 - by SEPL/Wood 0
complete with cable glands.
(Contractor installation scope includes supply, design, fabrication and installation of structural steel support brackets,
Canopy for the Welding Socket Outlet)
2.3.1.3 Socket Outlet
16A, 2P, 230V Convenience SOCKET OUTLET ( Wall / Structure mounting Type) suitable for Zone 1,Gas group nr 11 - by SEPL/Wood 0
IIC,T3 with Canopy Shall be fitted with cable glands.
(Contractor installation scope includes supply, design, fabrication and installation of structural steel support brackets,
Canopy for the Socket Outlet)

2.4 2734 Above Ground Earthing-Supply and Installation


2.4.1 J.9 9.8, J90 Earth Bus, Tinned Copper (with insulated Base frame,bolt & nuts)
J.8 9.7, J80
2.4.1.1 400mm x100mm x 10mm nr 18 0 0 0
2.4.1.2 Earth Boss (As per S68.004) for existing pipe rack , New Platform , Stair case and Pipe supports nr 50 0 0 0
2.4.2 Earthing and Lightning Cable Termination including lugs, saddles, clips etc.
2.4.2.1 1C 6 sqmm Cu PVC nr 0 0 0 0
2.4.2.2 1C 25 sqmm Cu PVC nr 85 4 0 0
2.4.2.3 1C 70 sqmm Cu PVC nr 250 4 0 0

2.5 2782 J.9 9.8, J90 Air Termination for Lightning Protection as per drawings 0591-8530-72-0013, 0591-8530-72-0014, 0591-8530-72-0015

2.5.1 Copper lightning air Rod : 15mm dia or 16 mm dia ,1m long (Make: Furse or equivalent) complete with bi-metallic nr 4 0 0
Adapter for fixing Air rod, 2m long mast, mast supports and other fixing material required to mount on platform handrail.
Note : Contractor to consider bimetallic adapter between Copper Air rod and mast for avoiding corrosion due to
connection of dissimilar material.
2.5.2 Test box for Lightning conductor nr 0 0 0

3.0 3732 J.6.1, J.6.2, 9.4, J50 Cable Above Ground (in sq mm)-Installation of cables free issued
J.6.4
3.0.1 Cable laid above ground as per Shell Typical
Cable types are listed by voltage grade, number of cores, cross sectional area and make up.
3.0.1.1 0.6/1 kV 1C 630 sqmm Cu/EPR/LS/AWA/PVC m
3.0.1.2 0.6/1 kV 2C 2.5 sqmm Cu/XLPE/LS/SWB/PVC m
3.0.1.3 0.6/1 kV 2C 4 sqmm Cu/XLPE/SWB/PVC m
3.0.1.4 0.6/1 kV 2C 6 sqmm Cu/XLPE/SWB/PVC m
3.0.1.5 0.6/1 kV 2C 10 sqmm Cu/XLPE/SWB/PVC m
3.0.1.6 0.6/1 kV 2C 16 sqmm Cu/XLPE/SWA/PVC m
3.0.1.7 0.6/1 kV 2C 25 sqmm Cu/XLPE/SWA/PVC m
3.0.1.8 0.6/1 kV 2C 35 sqmm Cu/XLPE/SWA/PVC m
3.0.1.9 0.6/1 kV 2C 50 sqmm Cu/XLPE/SWA/PVC m
3.0.1.10 0.6/1 kV 3C 2.5 sqmm Cu/XLPE/SWA/PVC m
3.0.1.11 0.6/1 kV 3C 4 sqmm Cu/XLPE/SWA/PVC m
3.0.1.12 0.6/1 kV 3C 6 sqmm Cu/XLPE/SWA/PVC m
3.0.1.13 0.6/1 kV 3C 10 sqmm Cu/XLPE/SWA/PVC m
3.0.1.14 0.6/1 kV 3C 16 sqmm Cu/XLPE/SWA/PVC m
3.0.1.15 0.6/1 kV 3C 25 sqmm Cu/XLPE/SWA/PVC m
3.0.1.16 0.6/1 kV 3C 35 sqmm Cu/XLPE/SWA/PVC m
3.0.1.17 0.6/1 kV 3C 50 sqmm Cu/XLPE/SWA/PVC m
3.0.1.18 0.6/1 kV 3C 150 sqmm Cu/XLPE/SWA/PVC m
3.0.1.19 0.6/1 kV 4C 2.5 sqmm Cu/XLPE/SWA/PVC m
3.0.1.20 0.6/1 kV 4C 4 sqmm Cu/XLPE/SWB/PVC m
3.0.1.21 0.6/1 kV 4C 6 sqmm Cu/XLPE/SWB/PVC m
3.0.1.22 0.6/1 kV 4C 10 sqmm Cu/XLPE/SWB/PVC m
3.0.1.23 0.6/1 kV 4C 16 sqmm Cu/XLPE/SWA/PVC m
3.0.1.24 0.6/1 kV 4C 25 sqmm Cu/XLPE/SWA/PVC m
3.0.1.25 0.6/1 kV 4C 35 sqmm Cu/XLPE/SWA/PVC m
3.0.1.26 0.6/1 kV 4C 50 sqmm Cu/XLPE/SWA/PVC m
3.0.1.27 0.6/1 kV 4C 70 sqmm Cu/XLPE/SWA/PVC m
3.0.1.28 0.6/1 kV 4C 95 sqmm Cu/XLPE/SWA/PVC m
3.0.1.29 0.6/1 kV 4C 120 sqmm Cu/XLPE/SWA/PVC m
3.0.1.30 0.6/1 kV 4C 150 sqmm Cu/XLPE/SWA/PVC m
3.0.1.31 0.6/1 kV 4C 185 sqmm Cu/XLPE/SWA/PVC m
3.0.1.32 0.6/1 kV 2C 2.5 sqmm Cu/XLPE/OS/SWB/PVC FRLS m
3.0.1.33 0.6/1 kV 4C 2.5 sqmm Cu/XLPE/OS/SWB/PVC FRLS m
3.0.1.34 0.6/1 kV 6C 2.5 sqmm Cu/XLPE/OS/SWB/PVC FRLS m
3.0.1.35 0.6/1 kV 7C 2.5 sqmm Cu/XLPE/OS/SWB/PVC FRLS m
3.0.1.36 500V 3X4X0.8 sqmm Cu/XLPE/OS/SWB/PVC FRLS m
3.0.1.37 500V 4X2X1.5 sqmm Cu/XLPE/OS/SWB/PVC FRLS m
0591-8530-BQ-0001_Rev F1 10 of 13 Electrical Works BOQ

You might also like