The following works are to be carried out only in powerless condition of the system. Picture 1 represents a central unit of the PLC (Central unit in ECR, open the cabinet with display).
The procedure HW-Reset:
- Switch off the remote control system of cpp
- open the cover E - check the small black switch G, should be on position 3 (pointer shows downward) - remove the battery F behind the cover - wait 30 sec. under powerless conditions - press the H button and hold it 1 second - put the battery F in - switch on the system (power supply) - yellow LED “RUN” should be on, after a delay time (over the memory card D)
C – Status Led`s A - terminals
D – Memory Card
E – Flap (cover) with battery behind
B- BUS connector A- terminals
Show below Picture